Abstract
Voltage transformers (VTs) are part of the power quality (PQ) measurement system in renewable energy installations where harmonic distortion (HD) exists. Although they are designed for fundamental-frequency operation, VTs exhibit frequency-dependent behaviour that causes ratio and phase errors at harmonic frequencies. These errors decrease measurement accuracy and impact compliance verification under South African grid code standards. International standards such as IEC TR 61869-103 and IEEE 519 do not specify harmonic-frequency accuracy classes or correction methods. This paper examines published research on VT frequency response and considers its effects on harmonic measurement in South African renewable networks. The review highlights technical and regulatory challenges that affect the reliability of harmonic measurements and emphasises the need for structured frequency-response testing under local operating conditions. A complementary methodological study addressing this need has been submitted for publication.
1. Introduction
The integration of renewable energy sources (RESs) in South Africa has increased the demand for reliable harmonic measurements in power quality (PQ) monitoring. As the Renewable Energy Independent Power Producer Procurement Programme (REIPPPP) expands, accurate harmonic assessment remains essential for grid code compliance [1].
Voltage transformers (VTs) are used in medium- and high-voltage (MV and HV) networks to scale electrical signals for PQ analysis. Under harmonic-rich conditions, VTs display frequency-dependent behaviour that causes deviations in ratio and phase [2,3]. These deviations reduce measurement accuracy and potentially lead to incorrect compliance assessments [1,3]. IEC TR 61869-103 [4] acknowledges the existence of VT-induced errors but does not specify procedures for harmonic-frequency accuracy [2,3].
Inductive voltage transformers (IVTs) can exhibit ratio errors greater than 5% at various harmonic orders [1,4,5]. These errors are affected by core material, winding configuration, burden impedance, and resonance effects [1,6,7].
South Africa’s grid code requires Independent Power Producers (IPPs) to adhere to harmonic emission limits set by Network Service Providers (NSPs). Standards like NRS 048-4 [8] and IEC 61000-3-6 [9] specify acceptable distortion levels at the Point of Connection (POC).
Limited published data exists on VT frequency response in South African networks. Most available results are based on European (EU) VT designs, which may not reflect local design and manufacturing characteristics [2]. This paper reviews published research on VT frequency response. It assesses its relevance to South African renewable energy networks, highlighting technical and regulatory limitations that influence the reliability of harmonic measurements under local operating conditions.
2. Overview of the Frequency Response of Voltage Transformers
An accurate harmonic voltage representation depends on the VT’s frequency response. Assessment of this behaviour requires consideration of applicable international and South African standards that define emission limits and measurement requirements.
2.1. Standards and Compliance Requirements
VTs are part of the PQ measurement chain and directly influence the accuracy of harmonic assessments in inverter-based renewable installations. IEC 61000-3-6 sets harmonic emission limits for high-power installations at the POC based on short-circuit capacity [9]. NRS 048-4 applies similar principles within South African networks and establishes short-term (24 h) and long-term (seven days) harmonic limits for renewable energy producers [8]. Compliance verification uses Class A instrumentation, as defined in IEC 61000-4-30 [10].
IEC TR 61869-103 recognises the impact of ITs on PQ measurements but does not define harmonic-frequency accuracy classes or correction procedures [4]. IEEE 519 specifies distortion limits at the POC and defines acceptable harmonic levels in terms of system fault-current ratios [11].
These standards define harmonic emission thresholds but rely on the accuracy definitions specified at the fundamental frequency. None explicitly accounts for frequency-dependent VT behaviour under harmonic excitation. Table 1 summarises key PQ standards relevant to harmonic compliance.
Table 1.
Comparison of selected PQ standards.
Without definitions of harmonic-frequency accuracy, compliance verification may reflect transformer transfer limitations rather than actual grid distortion. Structured evaluation of VT frequency response is therefore necessary to support reliable PQ assessment in South African renewable networks.
2.2. VT Technologies and Harmonic Behaviour
VTs used for PQ measurement differ in construction and operating principles. In South African grids, the primary technologies include IVTs, capacitive voltage transformers (CVTs), and Electronic Voltage Transformers (EVTs), each exhibiting distinct frequency response characteristics that affect harmonic accuracy [4,10].
IVTs are the most widely used devices in MV and HV networks. They depend on magnetic coupling between primary and secondary windings. IVTs show frequency-dependent deviations at higher harmonic orders [1,4,5]. Under typical loading conditions, ratio errors can exceed 5% between the 7th and 49th harmonics [1,4,6,7].
CVTs are commonly used in HV and Extra-High-Voltage (EHV) transmission networks and employ a capacitive divider and an intermediate transformer to scale voltages. CVTs provide improved high-frequency behaviour compared with inductive units but remain sensitive to tuning, temperature variation, and stray capacitance [10,14].
EVTs use sensors, signal conditioning, and digital processing to provide extended bandwidth and low distortion [15]. Deployment in South African MV networks remains limited due to infrastructure compatibility and cost considerations [3].
Comparative studies show that IVTs typically experience a sharp degradation in accuracy beyond 1 kHz, while EVTs and Resistive-Capacitive Divider (RC) dividers maintain a stable response across the harmonic range [4]. The frequency response profiles of VT technologies, which illustrate how construction affects harmonic fidelity, are available in IEC 61869-103 [4].
IVTs remain dominant in South African MV installations due to existing infrastructure and cost considerations. Their frequency-dependent behaviour therefore has direct implications for the reliability of harmonic measurements in renewable energy networks.
2.3. Design Factors Influencing Frequency
Transformer design and construction affect performance under harmonic conditions. Core material, winding geometry, burden impedance, and tank configuration interact to shape the frequency response and error characteristics [1,4,6].
Core material determines magnetic behaviour and hysteresis losses. Grain-oriented silicon steel offers low loss at 50 Hz but exhibits nonlinear magnetisation and hysteresis at higher frequencies. Eddy-current and hysteresis losses increase with frequency, leading to distortion and phase lag beyond the 13th harmonic [1,4].
The winding layout influences leakage inductance and parasitic capacitance. These parasitic elements interact with burden impedance and external cabling, forming resonant circuits that alter harmonic magnitude [1,7]. The burden directly influences the ratio and phase error. An increased burden modifies the secondary voltage drop and phase displacement. Table 2 outlines permissible voltage error and phase displacement limits for different VT accuracy classes under defined burden conditions.
Table 2.
Permissible voltage error and phase displacement limits for VT accuracy classes [16].
These limits apply only at the rated frequency and under specified burden conditions. They do not extend to harmonic frequencies. Consequently, a VT may comply with Class 0.5 or Class 1.0 at 50 Hz while exhibiting undefined ratio and phase errors at higher harmonic orders.
Phase displacement is the angular difference between the primary and secondary voltages and affects the accuracy of power and energy measurements. Resonance between internal inductance and capacitance typically occurs between 800 Hz and 1.2 kHz [2,3]. Maintaining rated burden conditions reduces additional frequency-dependent distortion.
The tank construction and magnetic shielding affect stray flux coupling and damping. Shielding and damping influence high-frequency impedance and harmonic stability [4]. The winding configuration further influences performance. Open-delta and three-phase banks assembled from single-phase units may introduce unequal phase response under harmonic excitation [4]. Collectively, design factors and burden conditions define resonant behaviour and harmonic accuracy of VTs [4,17]. These interactions influence transformer transfer characteristics under harmonic excitation and directly affect the interpretation of measurements [4].
2.4. Measurement Errors and Correction Techniques
When operating beyond the rated frequency range, VTs introduce ratio and phase errors that distort harmonic magnitude and phase-angle measurements. The size of these errors depends on transformer design, burden impedance, and operating conditions [1,4,7]. As harmonic order increases, error magnitude increases sharply, often exceeding standard accuracy limits [1,4,5]. Table 3 summarises typical error ranges for IVTs under varying burden conditions.
Table 3.
Typical IVT error ranges at selected harmonic orders.
Ratio error is the deviation between the measured and theoretical secondary voltage, while phase error is the angular displacement between primary and secondary voltages. At higher frequencies, leakage inductance and parasitic capacitance dominate the transfer characteristic, causing attenuation and delay.
Correction techniques aim to compensate for frequency-dependent deviations and improve measurement accuracy. Analytical methods use a frequency-dependent equivalent circuit to derive correction factors from impedance parameters [4].
Empirical approaches use measured frequency-response data to generate correction profiles for post-processing or real-time implementation [18]. Hybrid techniques combine analytical modelling with experimental data to balance precision and practicality.
Despite these developments, IEC TR 61869-103 acknowledges VT-induced PQ errors but does not prescribe standardised correction procedures. In South Africa, no defined protocol exists for harmonic-frequency calibration or compensation [2,3,4]. This regulatory gap introduces uncertainty in compliance assessments and limits confidence in PQ data from renewable installations.
Effective correction methods must account for variations in burden, temperature effects, and transformer ageing to remain valid under field conditions. Without a valid transfer characterisation, measured harmonics may reflect transformer behaviour rather than actual network distortion.
2.5. South African Grid Conditions and Research Gaps
South Africa’s renewable energy expansion has introduced operating conditions that differ significantly from those in traditional grids. Inverter-based generation introduces harmonic components that interact with network impedance and influence transformer behaviour [1].
Environmental factors further complicate measurement accuracy. High temperatures, humidity, and airborne dust accelerate insulation ageing, modify stray capacitances, and shift resonance frequencies [19]. Table 4 outlines how these influences degrade VT performance during PQ assessments.
Table 4.
PQ challenges from renewable energy integration and effects on VT measurements.
Despite the increasing deployment of renewables, research on VT frequency response under South African conditions remains limited. Most published studies focus on CVTs or current transformers (CTs), while conventional MV VTs remain under-characterised in local networks [4,5]. Table 5 compares the structural and operational differences between EU and South African VT applications.
Table 5.
Comparison of European and South African VT applications.
International investigations have examined VT-induced harmonic errors in EU systems [19]. Differences in equipment design and operating conditions limit direct transfer to South African networks.
Currently, no national standard defines procedures for evaluating VT accuracy at harmonic frequencies. IEC TR 61869-103 acknowledges the issue but does not define thresholds for harmonic-frequency performance [4]. This regulatory gap introduces uncertainty in PQ compliance assessment.
Addressing these gaps requires a structured characterisation of VT frequency response under representative South African operating conditions. Reliable transfer verification is necessary to support accurate harmonic assessment in renewable networks.
3. Discussion: Implications for PQ Measurement and Grid Compliance
The literature consistently shows that VTs, particularly inductive types, introduce frequency-dependent errors that distort harmonic voltage measurements. These deviations stem from core non-linearity, winding parasitics, and burden interaction, and are influenced by environmental exposure and installation conditions [4,17]. While several international studies propose analytical and empirical correction methods, their direct applicability to South African transformer designs remains uncertain. The absence of local frequency response data limits the reliability of PQ assessments in renewable networks.
South African renewable power plants operate under environmental and network conditions that differ significantly from those in Europe. Elevated ambient temperatures and outdoor exposure influence magnetic and capacitive behaviour [4]. These effects increase distortion at higher harmonics and can lead to noncompliance with measurement requirements [4]. Recorded distortion may therefore reflect transformer behaviour rather than actual network emission levels.
The South African grid code allows a 50% HD tolerance band, yet IVTs have demonstrated ratio errors exceeding this margin between the 7th and 49th harmonics. Such errors can exceed permissible tolerances, leading to an incorrect interpretation of compliance [4]. IEC TR 61869-103 acknowledges the influence of ITs but does not define procedures for harmonic-frequency verification, leaving NSPs and IPPs without consistent criteria for verification [4].
Reliable PQ assessment requires verification of the transformer’s transfer behaviour under representative operating conditions. Structured harmonic-frequency evaluation methods have been proposed to address this need [4,17].
VT-induced errors are systematic rather than incidental. Compliance verification must therefore consider transformer-specific frequency response behaviour rather than assuming ideal transfer characteristics. Recognising this limitation strengthens the interpretation of harmonic measurements in renewable energy networks.
4. Conclusions
VTs are essential components in PQ measurement chains, yet their frequency-dependent behaviour limits the accuracy of harmonic assessment in renewable energy networks. This paper reviewed the literature on VT frequency response and examined how design characteristics, burden conditions, and environmental factors influence ratio and phase errors. Inductive transformers, although widely used in South African grids, display significant deviation at higher harmonic orders that can compromise grid code compliance.
International standards such as IEC TR 61869-103 and IEEE 519 acknowledge the impact of ITs on PQ measurement but do not specify harmonic-frequency accuracy classes or correction procedures. In South Africa, the absence of validated VT frequency-response data and standardised correction methods creates uncertainty when verifying compliance for renewable installations. Most available research is based on EU equipment, which differs in design and operating context from local infrastructure.
Structured evaluation of VT frequency response under representative South African operating conditions is therefore necessary to support reliable harmonic measurement. A complementary methodological study addressing harmonic-frequency evaluation procedures has been submitted for publication [20]. Recognising transformer-specific transfer limitations strengthens the interpretation of PQ data and improves confidence in assessing grid code compliance.
Author Contributions
Conceptualisation, S.E. and J.A.d.K.; methodology, S.E.; validation, S.E. and J.A.d.K.; formal analysis, S.E.; investigation, S.E.; resources, S.E. and J.A.d.K.; writing—original draft preparation, S.E.; writing—review and editing, J.A.d.K.; visualisation, S.E.; supervision, J.A.d.K.; project administration, S.E. and J.A.d.K.; funding acquisition, S.E. and J.A.d.K. All authors have read and agreed to the published version of the manuscript.
Funding
This research was funded by the ISH2009-SAIEE Research Scholarship in High Voltage Engineering, administered by the South African Institute of Electrical Engineers (SAIEE). No specific funding number is associated with this scholarship.
Institutional Review Board Statement
Not applicable.
Informed Consent Statement
Not applicable.
Data Availability Statement
No new data were created or analyzed in this study.
Conflicts of Interest
The authors declare no conflicts of interest.
References
- Murray, R. Quantifying and Compensating for the Influence of Instrument Transformers on Harmonic Measurements for Grid Code Compliance. Ph.D. Dissertation, The Department of Electrical and Electronic Engineering, North-West University, Potchefstroom, South Africa, 2024. [Google Scholar]
- Stiegler, R.; Meyer, J.; Kilter, J.; Konzelmann, S. Assessment of voltage instrument transformers’ accuracy for harmonic measurements in transmission systems. In Proceedings of the 2016 17th International Conference on Harmonics and Quality of Power (ICHQP), Belo Horizonte, Brazil, 16–19 October 2016; IEEE: New York, NY, USA, 2016; pp. 152–157. [Google Scholar] [CrossRef] [Scilit]
- Meyer, J.; Stiegler, R.; Elst, M.; Sperling, E.; Klatt, M. Accuracy of Harmonic Voltage Measurements in the Frequency Range up to 5 kHz using Conventional Instrument Transformers. Presented at the 21st International Conference on Electricity Distribution, Frankfurt, Germany, 6–9 June 2011. [Google Scholar]
- IEC 61869-103; Instrument Transformers—The Use of Instrument Transformers for Power Quality Measurement. International Electrotechnical Commission: Geneva, Switzerland, 2013.
- Schulze, R.; Sperling, E.; Gopp, D. Investigating the impact of external fields on the accuracy of LPVT. In Proceedings of the 27th International Conference on Electricity Distribution (CIRED 2023), Rome, Italy, 12–15 June 2023; IET Digital Library: London, UK, 2023; pp. 3899–3903. [Google Scholar] [CrossRef] [Scilit]
- Crotti, G.; D’Avanzo, G.; Letizia, P.S.; Luiso, M. Measuring Harmonics with Inductive Voltage Transformers in Presence of Subharmonics. IEEE Trans. Instrum. Meas. 2021, 70, 9005013. [Google Scholar] [CrossRef] [Scilit]
- Sperling, E.; Freiburg, M.; Gopp, D. Assessment of high frequency performance of voltage instrument transformers using the relative application bandwidth. In VDE High Voltage Technology, 4. ETG-Symposium; VDE Publisher: Berlin, Germany, 2023; pp. 1–6. [Google Scholar]
- NRS 048-4; Electricity Supply—Quality of Supply: Part 4—Application Guidelines for Utilities: Edition 1.1. South African Bureau of Standards: Pretoria, South Africa, 2000.
- IEC TR 61000-3-6; Electromagnetic Compatibility (EMC)—Part 3-6: Limits—Assessment of Emission Limits for the Connection of Distorting Installations to MV, HV and EHV Power Systems. International Electrotechnical Commission: Geneva, Switzerland, 2008.
- SANS 61000-4-30; Electromagnetic Compatibility (EMC) Part 4-30: Testing and Measurement Techniques—Power Quality Measurement Methods. South African Bureau of Standards (SABS): Pretoria, South Africa, 2009.
- IEEE Std 519-2014; IEEE Recommended Practice and Requirements for Harmonic Control in Electric Power Systems. IEEE: New York, NY, USA, 2014. [CrossRef] [Scilit]
- EN 50160; Voltage Characteristics of Electricity Supplied by Public Distribution Systems. European Committee for Electrotechnical Standardization: Brussels, Belgium, 2023.
- NRS 048-2; Electricity Supply—Quality of Supply: Part 2—Voltage Characteristics, Compatibility Levels, Limits and Assessment Methods: Edition 3. South African Bureau of Standards: Pretoria, South Africa, 2000.
- Overett, J.; Vermeulen, H.J. Quality assessment of harmonic measurement data from a utility-scale PV plant. In Proceedings of the 2017 IEEE AFRICON, Cape Town, South Africa, 18–20 September 2017; IEEE: New York, NY, USA, 2017; pp. 1189–1194. [Google Scholar] [CrossRef] [Scilit]
- SANS 61000-2-12; Electromagnetic Compatibility (EMC) Part 2-12: Environment—Compatibility Levels for Low-Frequency Conducted Disturbances and Signalling in Public Medium-Voltage Power Supply Systems. International Electrotechnical Commission: Geneva, Switzerland, 2005.
- IEC 61869-3; Instrument Transformers—Part 3: Additional Requirements for Inductive Voltage Transformers. International Electrotechnical Commission: Geneva, Switzerland, 2011.
- IEEE Std 1159-2019; IEEE Recommended Practice for Monitoring Electric Power Quality. IEEE: New York, NY, USA, 2019. [CrossRef] [Scilit]
- SANS 61000-3-3; Electromagnetic Compatibility (EMC) Part 3-3: Limits—Limitation of Voltage Changes, Voltage Fluctuations and Flicker in Public Low-Voltage Supply Systems, for Equipment with Rated Current ≤16 A per Phase and Not Subject to Conditional Connection. South African Bureau of Standards: Pretoria, South Africa, 2009.
- Mariscotti, A.; Mingotti, A. The Effects of Supraharmonic Distortion in MV and LV AC Grids. Sensors 2024, 24, 2465. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- Engelbrecht, S.; de Kock, J.A. Developing a Standardised Method for Frequency Response Evaluation of Voltage Transformers for Power Quality Compliance. Eng. Proc. 2026; accepted.
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2026 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.