Abstract
A flexible low-frequency AC transmission system (LFTS) can extend the AC export range of offshore wind farms, but interactions among converter control loops may restrict its stable operating region. This paper develops a unified small-signal model comprising a grid-following wind farm, low-frequency cable, modular multilevel matrix converter (M3C), and receiving grid. A matrix-valued generalized Nyquist return ratio, together with modal participation and parameter-sensitivity analyses, indicates that the approximately 30 Hz dominant mode is strongly associated with the coupled control and network dynamics involving the phase-locked loop, wind-farm outer loops, M3C low-frequency voltage control, and transmission network. Based on bandwidth separation, a coordination strategy is proposed to move the critical control dynamics away from the interaction region. Comparisons between the state-space model and MATLAB/Simulink R2023b time-domain simulations show local agreement at the tested operating points. Power-step, weak-grid, bandwidth-sweep, and parameter-variation tests show that the proposed strategy, implemented solely through controller-parameter coordination without requiring additional hardware, suppresses oscillations, improves small-signal stability, and indicates a higher representative tested power-transfer boundary than PLL retuning at SCR = 1.50; 16 and 25 MW per turbine are the respective instability test points.
1. Motivation and Introduction
1.1. Motivation
Long-distance offshore wind export through submarine cables operated at 50 Hz is constrained by capacitive charging current, which increases with cable length and occupies transmission-current capacity that would otherwise be available for active-power transfer.A flexible low-frequency AC transmission system (LFTS), whose frequency-conversion and active voltage- and power-regulation capabilities are enabled by power-electronic converters, reduces this current while retaining an AC interface, and optimal-frequency studies show that frequency selection directly affects transfer capability and network utilization [1]. Techno-economic comparisons place LFTS between high-voltage AC and high-voltage DC options, with the preferred scheme depending on distance, rating, and converter cost [2]. At the onshore terminal, the modular multilevel matrix converter (M3C) performs frequency conversion and voltage regulation; its energy-balancing controls introduce additional converter dynamics [3]. This coupling motivates coordinated rather than independent controller tuning.
1.2. Introduction
Recent reviews of offshore wind integration summarize the transmission, converter, power-quality, and stability challenges of converter-dominated export systems [4]. Current research on low-frequency AC transmission has also extended from normal power transfer to system-level operating requirements, including black-start control for alternative offshore converter interfaces [5]. Design and optimization studies jointly consider transmission frequency, voltage, reactive compensation, losses, and converter rating [6].
Converter research has increasingly focused on the M3C and its interactions with the surrounding AC networks. Recent topology and control studies demonstrate direct medium- and high-voltage AC–AC conversion and dynamic operation of the M3C [7]. Low-frequency-side impedance models provide a terminal stability criterion [8]. A small-signal state-space model of the grid-following (GFL) offshore wind farm integrated through an LFTS has been established, and the effects of operating conditions and controller parameters on stability have been examined through eigenvalue analysis [9]. High-frequency resonance studies expose additional converter-network interactions [10], and a four-port model separates industrial-frequency, fractional-frequency, and coupling contributions over a wider frequency range [11].
At the wind-farm terminal, reactive-power characteristics can materially change the low-frequency damping of offshore wind power plants [12]. Direct–quadrature impedance models further show how converter controls and grid impedance jointly determine the closed-loop stability boundary [13]. For GFL converters, phase-locked-loop (PLL) synchronization reshapes terminal admittance as grid strength decreases [14]; coordinated current-loop and PLL tuning can maintain operation at very low short-circuit ratios [15], while impedance reshaping can extend the stable power-transfer range [16]. Published studies of improved PLL structures and PLL–grid-impedance decoupling further show that synchronization dynamics can be reshaped to improve weak-grid stability [17,18]. Control-loop interaction adds another mechanism: PLL, DC-link voltage control (DVC), reactive-power control, and voltage regulation can accumulate gain and phase lag in the same frequency band. Loop-shaping principles therefore motivate coordinated separation of the dominant bandwidths [19].
The reliability of such a design also depends on how physical and control parameters are represented. In model-based predictive motor control, parameter mismatch directly produces current deviation and oscillation, while online identification restores tracking and stability [20]. Although the plant is different, the methodological implication carries over: an LFTS stability design should state how controller gains map to effective bandwidths and should test sensitivity to parameter variation.
To clarify the methodological differences from previous studies, Table 1 systematically compares representative LFTS/M3C and GFL stability methods.
Table 1.
Comparison of representative LFTS/M3C and GFL stability studies.
Existing LFTS studies provide detailed models and stability diagnoses [9,11], while general GFL studies explain synchronization dynamics and control-loop interactions [14,19]. Building on the modeling foundation in [9], this work adopts a terminal-interaction perspective to connect stability analysis with coordinated controller design. The remaining issue is how interactions between the wind-farm controls and M3C low-frequency voltage regulation can guide their joint parameter selection. To address this issue, the wind-farm admittance and LFTS-side impedance are used to construct a generalized Nyquist (GN) return-ratio matrix. This representation supports the analysis of terminal interactions and informs bandwidth coordination among the wind-farm PLL, DVC, reactive-power loop, and M3C low-frequency voltage loop. The resulting design is then assessed through interconnected-system stability analysis and time-domain simulation.
1.3. Contribution and Organization
The main contributions are as follows:
- (1)
- A terminal-interaction formulation expresses the interconnected LFTS model as wind-farm admittance and LFTS-side impedance matrices. Their GN return ratio provides an interface-based perspective on stability.
- (2)
- Operating-power and short-circuit-ratio (SCR) effects are examined through GN eigenvalue loci, relating changes in wind-farm and network dynamics to terminal stability characteristics.
- (3)
- A multi-loop bandwidth-coordination procedure connects terminal-interaction analysis with controller parameter selection for the wind-farm PLL and outer loops and M3C low-frequency voltage loop, followed by interconnected-system stability assessment.
The remainder of this paper is organized as follows. Section 2 establishes the LFTS component, state-space, and impedance models and presents the baseline GN stability analysis. Section 3 derives the operating-point influence and the proposed bandwidth-coordination method, followed by GN verification of the redesigned parameters. Section 4 presents the simulation verification. Section 5 summarizes the principal findings, limitations, and further work.
2. LFTS Modeling and Stability Analysis
2.1. System Configuration and GFL Wind-Farm-Side Converter Model
The studied LFTS is shown conceptually in Figure 1. A GFL offshore wind farm is collected through a low-voltage and medium-voltage AC network, stepped up to the low-frequency transmission voltage, transmitted by a submarine cable operating at the low-frequency fundamental , and then connected to the main 50 Hz grid through an M3C and an onshore transformer. In a 50 Hz power system, a commonly used LFTS operating frequency is Hz, which offers an integer frequency ratio with the main grid and significantly reduces cable charging current.
Figure 1.
Configuration of the GFL offshore wind farm integrated through an M3C-based LFTS.
The LFTS considered in this study consists of the wind-farm-side GFL converter with its synchronization and outer control loops, the low-frequency submarine cable and transformers, the M3C low-frequency-side voltage and current control loops, the M3C power-frequency-side DC-capacitor-voltage, reactive-power, and synchronization control loops, and the equivalent 50 Hz receiving-end grid. The following modeling process therefore keeps both the low-frequency electrical network and the converter control dynamics, so that the interaction among wind-farm control, cable impedance, M3C regulation, and grid strength can be analyzed in a unified small-signal framework. Unless otherwise stated, bold lowercase symbols denote vectors, a superposed dot denotes the time derivative, denotes transpose, and the superscripts W and M denote wind-farm-side and M3C-side quantities, respectively.
For the ith wind turbine, the grid-side converter is modeled using an averaged GFL-converter representation, and the control equations are reorganized into a compact state form to facilitate the subsequent linearization. Under identical turbine parameters, operating points, and connection conditions, one representative turbine is modeled explicitly, while the remaining turbines are represented by controlled current injection equal to times its instantaneous branch current at the collection bus, with . This representation retains the common dynamic response of the turbine controls. The method retains the common-mode control dynamics of all 19 turbines, whereas inter-turbine differential modes caused by parameter differences or asymmetric collection lines are outside the scope of the present model. The GFL control topology adopted for the wind-farm-side converter is shown in Figure 2, where the PLL, DC-link voltage loop, reactive-power loop, and current inner loop jointly generate the converter voltage command.
Figure 2.
GFL wind-turbine converter control structure.
Taking the q-axis voltage at the point of common coupling (PCC) as the synchronization error, the PLL is expressed by
where is the PLL integral state, is the controller phase angle, is the PCC q-axis voltage in the controller reference frame, is the low-frequency angular frequency, and and are the proportional and integral gains of the wind-farm-side PLL, respectively. The power-frequency-side PLL of the M3C uses the same state form, with , , , , and replaced by , , , , and , respectively.
The DC-link voltage loop and reactive-power loop are described through an outer-loop error vector. Let , where and Q are the measured DC-link voltage and reactive power, and and are their references. The outer-loop state and current-reference vectors are defined as and , respectively. The current references are then generated by
where forms a diagonal matrix. The matrices and collect the proportional and integral gains of the DC-link voltage and reactive-power loops, with diagonal elements and , respectively.
For the current inner loop, define , , , and as the converter current, current-loop integral state, PCC voltage, and converter voltage-command vectors, respectively. The cross-coupling matrix is defined in the text by , , and . The inner controller is written as
In (3), and are the proportional and integral gains of the wind-farm-side current controller, and is the filter inductance.
The inductor-capacitor-inductor (LCL) filter dynamics retained for the GFL converter are
where is the averaged converter terminal voltage, is the grid-side current vector, and is the filter capacitance. When the pulse-width-modulation delay is neglected, follows in the averaged model. Equations (1)–(4) explicitly retain the PLL, DC-link voltage loop, reactive-power loop, current inner loop, and filter states. Therefore, the active-current command is not treated as a constant, and the interaction among PLL angle, DC-link voltage, current control, and low-frequency network impedance can be captured in the subsequent small-signal model.
2.2. Low-Frequency Cable and M3C Dynamic Model
The low-frequency transmission path is modeled in the same synchronous frame as the wind-farm-side converter. The wind-turbine step-up transformer and collection line, the transformer leakage branches, and the series branch of the -equivalent cable are written in a unified form. For a branch ℓ with referred sending- and receiving-end voltages and , the current state satisfies
where is the branch current, and are the branch inductance and resistance, and and are the sending- and receiving-end voltages referred to the same voltage level. The branch w represents the equivalent impedance of transformer and the wind-farm collection line, with parameters and . The transformer ratios , , and are absorbed into the referred voltages. The two shunt capacitors of the cable are kept as bus-voltage states:
Here, and are the sending- and receiving-end cable voltages after voltage-ratio conversion, is the equivalent shunt capacitance at each cable terminal, and , , and are the currents through transformer , the cable series branch, and transformer , respectively. Equations (5) and (6) are equivalent to the separate d- and q-axis models of the transformers and cable, but collect them into a compact state-space form.
It is worth noting that, when the transmission distance changes, the cable resistance, inductance, and capacitance vary approximately in proportion to the cable length, thereby affecting the voltage drop, charging current, terminal impedance, and small-signal stability boundary. Nevertheless, the method subsequently proposed in this paper remains applicable to different transmission distances after the corresponding cable parameters are updated.
The M3C is represented by an averaged nine-arm AC–AC model. In the M3C equations, the subscripts F and I denote the low-frequency side and the power-frequency side, respectively. For the double- arm representation, the bridge-current vector and inserted-voltage vector are arranged as and , where stacks its arguments into one column vector. The vector contains the currents of the low-frequency-side sub-converters a, b, and c represented in the power-frequency frame, and contains the currents of the power-frequency-side sub-converters u, v, and w represented in the low-frequency frame. The inserted-voltage vectors follow the same ordering, namely and . The arm dynamics of the M3C can then be reorganized as
where and are the arm inductance and resistance, and and are the power-frequency- and low-frequency-side terminal-voltage vectors. The compact matrix definitions are , , , , and , with and . Here, is a three-dimensional all-one column vector, and are identity matrices, is a zero matrix, ⊗ denotes the Kronecker product, and forms a block-diagonal matrix. Thus, repeats the power-frequency-side voltage in the first three bridge-current equations, repeats the low-frequency-side voltage in the last three bridge-current equations, and collects the and cross-coupling terms.
- (1)
- M3C DC model. The average submodule-capacitor voltage is retained because it is the energy state coupled to both AC sides. With the total equivalent capacitance denoted by , the averaged energy balance is written aswhere is the average capacitor-voltage reference, and are the low-frequency-side input power and power-frequency-side output power of the M3C, respectively, and is the average capacitor voltage.
- (2)
- M3C low-frequency and power-frequency model. The low-frequency-side and power-frequency-side control structure of the M3C is illustrated in Figure 3. The low-frequency side establishes the offshore AC voltage through a voltage loop and three sub-converter current loops, whereas the power-frequency side follows the 50 Hz grid and regulates the average capacitor voltage and reactive power.Figure 3. M3C low- and power-frequency control structure.
With and , the low-frequency voltage loop, the power-frequency outer loops, and the common sub-converter current loops are written as
where the side index denotes the low-frequency side and denotes the power-frequency side. All bold quantities carrying the subscript F or I are vectors in the corresponding synchronous control frame; for example, , , , and . The sub-converter sets are and , and the angular speeds are for and for . Here, is the low-frequency-side voltage reference, is the low-frequency-side grid-current feedforward, is the low-frequency-side filter capacitance, and are the power-frequency-side reactive power and its reference, and the matrices , , , , , and are the corresponding diagonal PI gain matrices. Compared with the component-wise expressions, (9) keeps the same controlled variables and feedforward structure while making the -vector nature of the F- and I-side variables explicit.
It is worth noting that the low-frequency terminal voltage is regulated by the M3C voltage outer loop and current inner loop, while the wind-farm reactive-power controller also affects the terminal-voltage dynamics. For the submarine cable, the series reactance and charging current satisfy and , respectively. Therefore, at 50/3 Hz, both quantities are approximately one third of their values at 50 Hz, thereby reducing reactive-power transfer and the associated voltage drop and additional conduction loss, although the line resistance loss cannot be completely eliminated. Under weak-grid conditions, the increased equivalent grid impedance amplifies the voltage response caused by current perturbations and strengthens the coupling between the M3C voltage loop and the wind-farm PLL and outer loops. Therefore, under weak-grid conditions, the voltage-support capability of the M3C and the dynamic coupling among multiple control loops must be considered simultaneously, which provides the basis for the subsequent stability analysis and coordinated controller design.
For the terminal small-signal analysis, the complete averaged nine-arm M3C model is reduced to four terminal states by retaining the common low-frequency terminal current and the low-frequency voltage-loop integral states; the corresponding reduction is derived in Appendix A.
2.3. Small-Signal State-Space Model and Stability Analysis
The small-signal impedance model is established at the low-frequency AC terminal, where the GFL wind farm and the LFTS network exchange voltage and current perturbations. Consistent with the notation in Section 2.1 and Section 2.2, the low-frequency synchronous frame and terminal perturbations are defined as
Here, denotes a small-signal perturbation. The d-axis is aligned with the steady-state low-frequency terminal voltage; hence a perturbation frequency in this frame directly represents the oscillatory envelope around the Hz fundamental component.
The impedance model is obtained by cutting the system at the low-frequency terminal. The wind-farm side is represented by its terminal admittance, whereas the cable–M3C–grid side is represented by its terminal impedance.
- (1)
- Wind-farm terminal admittance. The PLL, outer-loop, and current-loop dynamics of the wind-farm-side GFL converter have been formulated in (1)–(3). For the impedance derivation, these control loops are condensed into the small-signal converter-voltage responsewhere is obtained by linearizing the GFL control equations at the operating point. With and , the nonzero entries of the Jacobian matrices before port-input reduction are: , , , , and for ; , , , , , , , and for ; , , , and for ; and , , , , , , , and for ; all unlisted entries are zero. Here, is the steady-state d-axis low-frequency terminal voltage. In (11), the port-input matrices are obtained as and , where maps the terminal-voltage perturbation to the control input vector at the operating point. The key physical relation is provided by the LCL filter in (4), whose inductor impedance and shunt-capacitor admittance areCombining (11) with the filter relation first gives the terminal admittance of one representative wind turbine, denoted by . For n identical turbines operating under the same conditions, their admittances are referred through transformer to the 66 kV collection bus and connected in parallel. The resulting aggregated wind-farm admittance iswhere is the voltage ratio of transformer . Thus, the factor refers the single-turbine admittance from the 1.14 kV side to the 66 kV collection bus, and the factor n represents the parallel aggregation of the 19 turbines. Because is frequency dependent and contains , the common PLL, outer-loop, current-loop, and filter dynamics of all turbines are retained in .
- (2)
- LFTS-side terminal impedance. For the low-frequency transmission path, the series-branch admittances and cable shunt admittance are obtained from (5) and (6) asThus, , , , and are obtained by substituting , , , and , respectively, into the series-branch expression in (14). The M3C and receiving-end 50 Hz grid are seen from the low-frequency terminal through the equivalent controlled admittanceHere, – are the linearized M3C state, input, output, and feedthrough matrices, respectively. The LFTS nodal admittance isEach block in (16) is a matrix. Defining , the LFTS-side terminal impedance is
- (3)
- GN return-ratio matrix. Combining the wind-farm admittance and LFTS-side impedance givesThe corresponding closed-loop characteristic equation isTherefore, the GN curves plotted below are not independent fitted curves; they are the eigenvalue loci of the explicitly constructed matrix in (18). Let . Denote by P and Z the numbers of right-half-plane poles and zeros of , respectively, with P representing the open-loop RHP pole count used in the GN test, and by N the signed net number of counterclockwise encirclements of the origin by the determinant locus along the complete right-half-plane Nyquist contour, with counterclockwise encirclements taken as positive. According to the argument principle, . Hence, closed-loop stability requires , or equivalently . In particular, when , the required net encirclement count is zero. The complete determinant criterion is used to determine the closed-loop stability of each operating case, whereas the eigenvalue loci are mainly used to identify the critical frequency band and illustrate the effects of control parameters on the interaction characteristics [13,16]. The two eigenvalue branches, their critical-point distance, and the local real-axis indicator are defined asHere, measures the local distance between the closest eigenvalue branch and the critical point , whereas characterizes the local position of this branch relative to the vertical line . These quantities are supplementary indicators of critical-point proximity and local crossing tendency and cannot replace the complete generalized Nyquist stability criterion. Therefore, for each operating case investigated below, the open-loop right-half-plane pole count P, the required net encirclement count , the observed net encirclement count N, and the resulting closed-loop right-half-plane pole count are reported and used to determine the final stability conclusion.
Before drawing the GN loci, the main physical and control parameters used to evaluate , , and are adopted from the LFTS system reported in [9] and summarized in Table 2.
Table 2.
Physical parameters used for GN-plot calculation.
Based on the 100 km submarine-cable parameters in Table 2, the two-port frequency responses of the lumped -equivalent and distributed-parameter models were compared. Within 28–32 Hz, their maximum relative deviation is below 1.70%, indicating that the lumped -equivalent retains the principal cable dynamics in the frequency range of interest.
The conventional control case is shown in Figure 4. The closest approach to occurs at 30.85 Hz, where . The determinant criterion gives , , , and ; hence, the nominal case is stable but has a small critical-point distance around 30 Hz.
Figure 4.
GN loci of the conventional GFL wind-farm LFTS impedance model.
To examine how this local interaction indicator varies with operating and control conditions, three GN parameter sweeps are performed for wind-farm power, SCR, and PLL bandwidth. In each figure, the left panel gives the eigenvalue loci of , while the right panel gives . The complete determinant-based counts for all cases in Figure 4, Figure 5, Figure 6, Figure 7, Figure 8 and Figure 9 are summarized after Figure 9. To avoid ambiguity, every numerical value of and reported below is identified by the corresponding turbine power, SCR, and controller configuration.
Figure 5.
Power-sweep GN loci for 13 MW and 19 MW operation.
Figure 6.
SCR-sweep GN loci for strong- and weak-grid LFTS operation.
Figure 7.
PLL-bandwidth GN loci for 10, 50, and 200 Hz cases.
Figure 8.
GN comparison at 19 MW with conventional and bandwidth-separated parameters.
Figure 9.
GN comparison at 19 MW/turbine and SCR = 1.78 with conventional and bandwidth-separated parameters.
Figure 5 shows the influence of wind-farm active-power transfer using the conventional controller parameters. At 13 MW/turbine, and the complete count gives , indicating stable operation. At 19 MW/turbine, the local indicator decreases to , while the determinant count becomes ; thus, the system is unstable and has two closed-loop right-half-plane poles.
Figure 6 compares two grid-strength conditions at 16 MW/turbine using the conventional controller parameters. For SCR values of 2.24 and 1.78, the 30 Hz local indicators are 0.0879 and 0.0583, respectively, and the minimum distances in the 28–32 Hz band decrease from 0.0288 to 0.0109. Both cases satisfy and are stable, although the weaker grid increases the interaction risk around 30 Hz.
Figure 7 compares PLL bandwidths of 10, 50, and 200 Hz at 16 MW/turbine and SCR = 1.78. Their 30 Hz local indicators are 0.0583, 0.0670, and 0.1003, respectively, and all three cases satisfy . Thus, the three cases remain stable, while PLL tuning reshapes the local interaction around the critical frequency and motivates the multi-loop bandwidth-separation method in Section 3.
3. Bandwidth-Separation-Based Stability Enhancement Method
3.1. Influence of PLL and Grid Strength on the Critical GN Indicators
The GN sweeps in Section 2.3 show that the high-power and weak-grid cases are the two most sensitive operating conditions. This behavior can be explained from the small-signal coupling introduced by the PLL and by the equivalent LFTS-side impedance. Around the operating point, the PLL angle response to the q-axis voltage perturbation can be approximated as
where is the steady-state d-axis voltage at the synchronized terminal. The angle perturbation rotates the steady-state current vector in the frame. For an operating point dominated by active-power transfer, the induced q-axis current perturbation is approximately
Equations (21) and (22) indicate that the PLL-related coupling term increases with active power. Hence, when the wind-farm power is raised from 13 MW to 19 MW, the controlled admittance contains a stronger angle–current interaction, and the corresponding GN eigenvalue locus is more likely to approach the critical point .
Grid strength further amplifies this mechanism through the LFTS-side impedance. In per-unit form, the receiving-end equivalent grid impedance is inversely related to the SCR,
Since the return-ratio matrix is , a lower SCR increases the magnitude and phase contribution of . A qualitative heuristic for interpreting the variation tendency of the critical interaction is therefore
where represents the PLL response in (21). Equation (24) is used only to explain qualitatively how power, SCR, and PLL dynamics influence the control–network interaction strength; it is not an exact system-level proportionality for the complete MIMO return-ratio matrix. The complete model also includes the DVC, reactive-power loop, M3C control dynamics, and cable and grid impedances. Therefore, this heuristic is not used for quantitative stability assessment, and all numerical results and final stability conclusions are obtained from the complete return-ratio matrix and the determinant-based GN criterion.
Thus, increasing active power strengthens the wind-farm-side PLL and current coupling, while decreasing SCR enlarges the LFTS-side impedance. The two effects jointly move the eigenvalue loci toward near the weak interaction band. The complete determinant criterion shows that the 19 MW case at SCR = 2.24 is unstable, whereas reducing SCR from 2.24 to 1.78 at 16 MW preserves stability but reduces the critical-point distance around 30 Hz. Their combined effect under high-power and weak-grid operation is examined subsequently.
3.2. Bandwidth-Separation Principle and Coordination Strategy
The GN results in Section 2.3 show that the critical interaction is concentrated around 30 Hz. The return ratio in (18) contains both the controlled wind-farm admittance and the LFTS network impedance; the GN loci alone cannot uniquely identify the mode’s source or exclude a contribution from the cable/network dynamics. The GFL PLL, DVC, reactive-power loop, and M3C low-frequency voltage loop jointly shape this return ratio; when their phase lags overlap near 30 Hz, the eigenvalue loci are pushed toward . Accordingly, both the controlled-converter dynamics and the cable/network impedance can influence this mode.
In this paper, bandwidth refers to the nominal local closed-loop design bandwidth obtained from a decoupled single-loop approximation for PI-gain synthesis.
Inspired by published loop-shaping studies of PLL-based converters with different reactive-power controls [19], this paper develops a bandwidth-separation design for the GFL wind-farm LFTS. The key difference is that the terminal-voltage control effect is not only inside the wind-farm converter, but is also provided by the M3C low-frequency voltage regulation through . Hence, the relevant bandwidth set is written as
where , , and denote the effective wind-farm PLL, DVC, and reactive-power-loop bandwidths, while and denote the M3C low-frequency voltage-loop and current-loop bandwidths. The purpose of bandwidth separation is to prevent several outer loops from contributing large phase lag and admittance gain in the same 30 Hz neighborhood.
The proposed strategy coordinates the wind-farm and M3C control loops according to their roles in (18). First, the current inner loops should remain the fastest loops, so that the terminal admittance is mainly shaped by the outer-loop dynamics rather than by current tracking delay. Second, the wind-farm PLL bandwidth should be kept away from the 30 Hz weak interaction band or sufficiently separated from the DVC bandwidth, because a PLL–DVC overlap strengthens the active-power and angle coupling in . Third, the M3C low-frequency voltage loop should be fast enough to support the offshore voltage, but it should not be tuned to create an additional phase-lag peak near the wind-farm PLL-dominated interaction frequency.
For two outer loops a and b, their separation ratio is defined as
The coordination target is not to maximize every bandwidth independently, but to obtain a separated hierarchy in which the outer-loop interaction is shifted away from the critical GN band. The design is carried out in four steps. First, the 28–32 Hz critical band is identified from the conventional GN loci. Second, the outer-loop bandwidths are divided into a slow active-power/DC-voltage group, a synchronization group, and a fast voltage-support group. Third, candidate PI gains are converted into their effective closed-loop bandwidths and screened by the following constraints:
The separation ratio is used as a lower bound for preliminary candidate screening rather than as a standalone stability condition. To examine its influence, a multi-loop sensitivity analysis is performed at 19 MW/turbine and SCR = 2.24 for , 4, 5, 6, and 10. The PLL bandwidth is fixed at 10 Hz, while the remaining candidate bandwidths are assigned as , , , and . Each candidate is evaluated using the minimum GN distance, the complete determinant-based GN count, the dominant-mode damping ratio, and the active-power step response (see Table 3).
Table 3.
Sensitivity of the multi-loop separation ratio at 19 MW/turbine and SCR = 2.24.
For –5, the complete GN criterion detects closed-loop right-half-plane poles, the dominant-mode damping ratios are negative, and the step responses diverge, indicating that insufficient separation causes dynamic-band overlap and instability. Both and 10 yield stable responses. Compared with , requires lower high-frequency-loop bandwidths and gives a smaller overshoot (24.79% versus 29.72%) and a shorter settling time (0.812 s versus 1.356 s). Therefore, is adopted as the engineering separation ratio for the present case study. The 28–32 Hz interval is selected from the critical band identified in Section 2.3. Finally, the screened parameters are substituted into and , and the set with the largest among the candidates satisfying the complete GN criterion is retained.
For the PI-gain selection, the effective bandwidths are related to the controller-gain magnitudes using standard local closed-loop approximations. The loop-wise bandwidth–gain mappings and the resulting bandwidth-separated controller parameters are summarized together in Table 4, where is used for readability. Here, is the desired second-order damping ratio, is the equivalent series resistance of the wind-farm-side filter branch used in the current-loop bandwidth estimate, and the signs of the PI gains are determined by the error definitions in (2) and (9). In this design, the DVC is deliberately slowed down to 1 Hz, the PLL is kept below the 30 Hz interaction band, and the reactive-power and M3C low-frequency voltage-support loops are moved to higher bandwidths. Therefore, the main phase lags no longer accumulate around 30 Hz.
Table 4.
Bandwidth-gain mappings and separated control parameters for the proposed LFTS design.
It should be noted that the bandwidths in Table 4 are nominal design values obtained from local single-loop approximations. The 1 Hz DVC separates the relatively slow DC-energy regulation process from the critical interaction band, whereas the 60 Hz M3C low-frequency voltage loop and the 80 Hz reactive-power loop maintain the dynamic responses of voltage and reactive power. In practical digital implementation, the controller sampling and PWM frequencies should be substantially higher than these design bandwidths. Because these bandwidths are local-loop approximate design targets, they can be directly adjusted through the corresponding PI gains and provide effective design values for subsequent coupled-system verification. In addition, the negative signs in the table arise from the adopted error definitions, current directions, and control-voltage polarities; they do not indicate negative bandwidths and can be used directly for controller-parameter tuning.
The nominal local bandwidths may differ from the actual dynamic bandwidths of the interconnected system. To quantify the bandwidth shift caused by the multi-loop and electrical-network coupling, the complete 19-state model is linearized at 19 MW/turbine and SCR = 2.24. For each loop k, the closed-loop frequency responses from the corresponding reference input to the controlled variable are calculated for both the local subsystem and the complete interconnected system. The first persistent dB frequencies are denoted by and , respectively. The coupled-system bandwidth is evaluated as , and its relative deviation is . Here, is the nominal design bandwidth obtained from the local single-loop approximation, and is the coupling-induced relative bandwidth deviation.
The results show that the complete-system coupling causes finite shifts from the local design values, with a maximum absolute deviation of 5.07%. The actual bandwidth hierarchy among the DVC, PLL, M3C low-frequency voltage loop, and reactive-power loop is nevertheless preserved. Therefore, the nominal local bandwidths provide suitable initial values for PI-parameter design (see Table 5).
Table 5.
Comparison between nominal local and coupled-system bandwidths at 19 MW/turbine and SCR = 2.24.
3.3. Stability Analysis
For a candidate bandwidth-coordinated parameter set , the wind-farm admittance and the LFTS-side impedance are recalculated as and , and then substituted into the return-ratio expression in (18). The minimum GN distance and local real-axis indicator are used to screen candidate parameters and quantify their local movement relative to the critical point, whereas the final stability classification is determined by the complete determinant criterion. These local design indicators are defined as
where denotes the eigenvalue branch closest to at each frequency. Compared with the conventional setting , the bandwidth-coordinated setting should satisfy
Equation (29) is a local parameter-screening objective rather than a standalone stability condition. Figure 8 compares the conventional and bandwidth-separated parameters at 19 MW/turbine and SCR = 2.24. The 30 Hz local indicator changes from to 0.3112. More importantly, the complete count changes from with the conventional parameters to with the proposed parameters, confirming that bandwidth coordination restores stability.
Figure 9 gives the corresponding comparison at 19 MW/turbine and SCR = 1.78. The 30 Hz local indicator changes from with the conventional parameters to 0.2881 with the proposed parameters. The determinant count correspondingly changes from to , demonstrating that the proposed multi-loop coordination restores stability under the combined high-power and weak-grid condition.
For every operating case in Table 6, the open-loop RHP pole count is , so the required net encirclement count is .
Table 6 shows that the local indicators describe proximity to the critical point but do not independently determine stability. The determinant-based count provides the final classification for every case.
To identify the state variables associated with the critical mode, the normalized participation factor of state in mode is defined using the corresponding right and left eigenvector elements, and , as . Because a state participation factor indicates where a mode is manifested but does not fully quantify how a controller parameter moves that mode, the normalized modal parameter sensitivity is further defined as . For this calculation, the PI gains of loop j are perturbed consistently with the corresponding bandwidth–gain mapping. The sensitivities are normalized over the PLL, DVC, reactive-power loop, and M3C low-frequency voltage loop. Table 7 compares the participation factors and modal sensitivities before and after bandwidth coordination at 19 MW/turbine and SCR = 2.24.
Table 7.
Participation factors and modal parameter sensitivities of the critical mode at 19 MW/turbine and SCR = 2.24.
The participation factors show that the critical oscillation is manifested mainly in the converter-current and cable/network states. The outer loops modify the current references, coordinate-transformation relationship, and terminal dynamics, and thereby affect the location and damping of the critical mode to different degrees. Consequently, a relatively small participation factor of an outer-loop state does not imply that its control parameters have a negligible influence on stability. The modal sensitivities further show that the reactive-power loop and M3C low-frequency voltage loop have stronger effects on the critical mode, whereas the PLL and DVC have smaller effects under this operating condition. Overall, the mode is strongly associated with the coupled control–network dynamics, although the influence of the individual control loops is not identical.
It should be noted that the approximately 30 Hz critical frequency is specific to the LFTS studied in this paper. For other systems or operating conditions, the terminal model should first be updated according to the actual parameters, and GN analysis should then be used to re-identify the critical frequency band and the main participating control loops. The nominal design bandwidths of the relevant loops are subsequently coordinated, followed by recalculation of the GN results and the eigenvalues of the complete state-space model. If the critical frequency band shifts or the stability requirements are not satisfied, the above procedure is repeated, and the final design is verified through time-domain simulation.
4. Simulation Verification
The simulation studies are organized to validate the small-signal model, reproduce the baseline instability, identify the multi-control-loop interaction, compare the conventional and coordinated parameters, and assess robustness and representative tested power-transfer boundaries. A per-turbine power of 16 MW is taken as the rated operating point, whereas 13 MW is selected as a stable partial-load baseline for initializing and recovering the power-step tests. The higher references of 19, 22, and 25 MW per turbine are applied to examine the evolution of stability beyond the rated condition, in which all power values are specified on a per-turbine basis.
The relevant simulation parameters are listed in Table 8. It should be noted that the current limit and modulation-command saturation listed in the table are imposed only as static constraints because the present study focuses on control coupling and small-signal stability around normal operating points.
Table 8.
Main simulation and controller implementation parameters.
4.1. Simulation Model and Small-Signal Model Validation
To validate the local accuracy of the small-signal model, a time-domain LFTS simulation was established and compared with the 19-state model provided in Appendix A. The simulation retains the dynamic behavior of the GFL wind-farm converter and its control system, the converter-side filter, the low-frequency cable and transformers, the M3C control system, and the receiving grid. The state-space branch uses the fixed Jacobian matrices evaluated at the same operating point. PWM-frequency ripple, dead-time effects, sensor noise, and quantization were included in the measurement channels but excluded from the state-space model, which represents the dominant small-signal dynamics.
The wind-farm active-power reference was increased from 16 MW to 16.16 MW at s, corresponding to a 1% perturbation. Figure 10 compares the resulting wind-farm active power , wind-farm reactive power , low-frequency PCC voltage , and M3C low-frequency-side active power over a 2 s observation interval.
Figure 10.
Simulation and state-space responses to a 1% wind-farm power-reference step.
As shown in Figure 10, the state-space responses closely follow the average envelopes of the simulation results. Both active-power variables exhibit the same damped overshoot and settling trend, while the transient reactive-power oscillation and PCC-voltage excursion are reproduced with consistent frequency and damping. The normalized root-mean-square errors calculated against the ripple-free simulation envelopes are 0.013%, 2.273%, 0.208%, and 0.030% for , , , and , respectively. The remaining high-frequency differences arise from switching and measurement effects rather than from the dominant electrical and control-loop dynamics. These results confirm that the state-space model retains the local dynamic characteristics required for the subsequent stability studies.
To further assess the model under a weak-grid condition, the validation was repeated at 16 MW and SCR . The operating point and state-space matrices were recalculated for this condition, and a 0.5% power-reference step from 16 to 16.08 MW was applied at s. As shown in Figure 11, the simulation and state-space responses exhibit consistent transient trends and settling characteristics. The maximum absolute differences between their ripple-free responses are MW, Mvar, pu, and MW for , , , and , respectively. The maximum real part of the state-space eigenvalues is s−1, confirming stable small-signal behavior at this weak-grid operating point.
Figure 11.
Simulation and state-space responses at 16 MW and SCR under a 0.5% wind-farm power-reference step.
To further examine the accuracy of the 19-state model over different operating conditions, six representative operating points were evaluated in addition to the two existing validation cases: 13 and 19 MW/turbine at SCR ; 13, 19, and 22 MW/turbine at SCR ; and 19 MW/turbine at SCR (see Table 9).
Table 9.
Maximum absolute errors between the simulation and the 19-state model at the six additional operating points.
The simulation and state-space active-power responses remain closely aligned in all six added cases. Across these cases, the maximum absolute errors of , , , and do not exceed MW, Mvar, pu, and MW, respectively (see Figure 12).
Figure 12.
Additional simulation and state-space validation at six representative operating points.
4.2. Time-Domain Reproduction of the Baseline Instability
The conventional-parameter case was next tested under a large operating-point variation. The wind-farm active-power reference was maintained at 13 MW during s, increased to 19 MW during s, and restored to 13 MW during s. The time-domain simulation described in Section 4.1 was retained without changing the electrical network or numerical configuration. The critical interaction affects the PLL angle, the GFL d-axis current, and the terminal electrical variables through the converter control loops. Linearization at the 19 MW operating point gives an intrinsic oscillatory mode at 30.69 Hz with a damping ratio of .
As shown in Figure 13, the 13 MW operating point remains steady before the power increase. After the reference is raised to 19 MW, a growing oscillation appears simultaneously in the wind-farm active and reactive powers, low-frequency PCC voltage, and PLL angle. Spectral analysis of the active-power response gives a dominant frequency of 32.22 Hz, close to the 30.69 Hz intrinsic eigenmode. The active-power oscillation amplitude increases from 4.20 MW in the early high-power interval to 24.32 MW in the late interval, corresponding to a growth ratio of 5.7900. When the reference returns to 13 MW at s, the oscillation becomes positively damped and progressively decays. The time-domain response therefore reproduces the operating-point-dependent instability indicated by the GN loci: increasing transferred power drives the conventional LFTS into the critical approximately 30 Hz interaction, whereas power reduction restores stable operation.
Figure 13.
Baseline instability under a 13–19–13 MW power-reference sequence.
4.3. Validation of Multi-Control-Loop Bandwidth Interaction
To distinguish individual-loop parameter adjustment from simultaneous multi-loop interaction, four controller configurations were evaluated using the same 13–19–13 MW sequence as in Section 4.2. In the first three configurations, only the PLL, DVC, or M3C low-frequency voltage-loop PI gains are adjusted, respectively, whereas the fourth configuration retains the conventional multi-loop-coupled parameters. The corresponding intrinsic oscillatory modes are 32.40, 32.37, 29.27, and 30.69 Hz.
Figure 14 shows that adjusting only one control loop does not produce a sustained approximately 30 Hz oscillation in this test. The late-to-early amplitude ratios are 0.0158, 0.0178, and 0.0024 for the PLL-only, DVC-only, and M3C-voltage-loop-only cases, respectively. In contrast, the conventional multi-loop-coupled case has a negative damping ratio of ; its active-power oscillation grows from 4.20 MW to 24.32 MW, with a growth ratio of 5.7900 and a dominant response frequency of 32.22 Hz.
This simulation result is consistent with the participation-factor and modal-sensitivity analysis in Section 3. The critical oscillation is manifested mainly in the current and network variables, while the outer loops modify its damping to different degrees through the current references, coordinate-transformation relationship, and terminal dynamics. These results indicate that the mode is strongly associated with the coupled control and network dynamics and is modulated by different outer-loop parameters. The substantial participation of the cable/network states is retained in this interpretation, so the mode is not attributed exclusively to either a single control loop or a cable/network resonance.
Figure 14.
Active-power responses for individual-loop parameter adjustment and the multi-loop-coupled case.
4.4. Comparison of Conventional and Proposed Parameters
The time-domain effectiveness of the bandwidth-separated parameter set was evaluated for the two stressed operating conditions analyzed by the GN plots in Section 3.3. For the high-power test, the active-power reference follows the 13–19–13 MW sequence at SCR = 2.24. For the weak-grid test, the wind-farm reference remains at 13 MW while SCR follows a 2.24–1.78–2.24 sequence over the same 3 s interval. The conventional and proposed simulations use identical plant states, disturbance timing, and numerical settings.
As shown in Figure 15a, the conventional parameters give a modal damping ratio of at 19 MW. The 32.22 Hz active-power component increases from 4.20 MW to 24.32 MW, with a growth ratio of 5.7900. With the proposed parameters, Figure 15b gives a positive damping ratio of 0.0519, and the amplitude ratio decreases to 0.0161. At SCR = 1.78, the conventional case has a damping ratio of and an amplitude growth ratio of 1.1706, whereas the proposed case retains a damping ratio of 0.0692 and reduces the amplitude ratio to 0.0013. The dominant response frequencies remain within 32.22–34.44 Hz. These time-domain results are consistent with the relative GN-locus movements in Figure 8 and Figure 9: bandwidth separation improves the damping of the critical mode under both increased power transfer and reduced grid strength.
Figure 15.
Time-domain comparison of conventional and bandwidth-separated parameters under stressed operating conditions.
Table 10 summarizes the frequency-domain, eigenvalue, and time-domain indicators for Figure 15. Here, and denote the minimum critical-point distance and local real-axis position indicator, respectively; and denote the eigenvalue pair and damping ratio of the critical oscillatory mode, respectively; is the dominant time-domain oscillation frequency; and is the ratio of the late-window to early-window oscillation amplitude, with indicating growth and indicating decay. In the high-power case, the negative local real-axis indicator is accompanied by a right-half-plane critical mode, negative damping, and a growing response. Under SCR = 1.78 with conventional parameters, remains slightly positive while the critical eigenvalue and time-domain envelope indicate weak instability, confirming that this local real-axis indicator is an auxiliary proximity indicator rather than a standalone stability criterion. In both proposed cases, the critical mode moves into the left-half plane, the damping ratio becomes positive, and decreases well below unity. The close agreement between the modal and time-domain frequencies further confirms that the responses are governed by the same approximately 30 Hz interaction mode.
Table 10.
Comparison of the local GN indicators, critical mode, and time-domain responses for the cases in Figure 15.
4.5. Robustness and Operating-Range Verification
The operating range of the proposed bandwidth-separated parameters was further evaluated using four progressively stressed cases. All tests start from 13 MW, apply the specified operating condition during s, and return to 13 MW during s. Cases (a)–(c) examine 16 MW at SCR = 2.24, 19 MW at SCR = 1.78, and 22 MW at SCR = 1.78, respectively. Case (d) combines 19 MW with SCR = 1.50 and simultaneous 20% parameter deviations: wind-farm filter inductance, first equivalent cable shunt capacitance, second equivalent cable shunt capacitance, and M3C response time. The same proposed controller parameters are used across the four cases.
Figure 16 shows stable tracking in all tested conditions, although the transient excursion increases as the operating stress becomes more severe. The modal damping ratios in cases (a)–(d) are 0.0631, 0.0485, 0.0279, and 0.0455, respectively. Using the ratio between the late- and early-window amplitudes of the dominant component as the decay index, the corresponding values are 0.0071, 0.0141, 0.0034, and 0.0056; all remain below unity. The dominant response frequencies are 33.33, 31.11, 30.00, and 27.78 Hz, respectively. Even in case (d), the oscillatory amplitude decreases from 0.06 MW to MW. The proposed coordination therefore preserves positive damping over the tested power, grid-strength, and parameter-variation range.
Figure 16.
Operating-range verification under power, SCR, and parameter variations.
To distinguish the independent effects of individual parameter uncertainties, a structured sensitivity analysis is performed at 19 MW/turbine, SCR = 1.50, and the proposed controller setting. Except for the receiving-grid impedance angle, which is perturbed by , each parameter is independently varied by while the other parameters remain at their nominal values. Stability is determined using the complete determinant-based GN criterion, while and the critical-mode damping ratio are used as supplementary comparison indicators. The stable nominal case is not repeated in Table 12.
Table 12.
Structured stability-sensitivity analysis at 19 MW/turbine and SCR = 1.50.
The results show that a 20% decrease in the wind-farm filter inductance, a 20% increase in all retained controller gains, a 20% decrease in the M3C voltage-loop gains, and a 20% increase in the M3C reduced response time all yield under the complete GN criterion and therefore lead to instability. Increasing the cable length by 20% preserves stability but reduces the critical-mode damping ratio to 0.0078. In contrast, the tested variations in cable resistance, referred transformer impedance, receiving-grid impedance angle, and PLL gains do not cause instability. These results therefore demonstrate selected-case robustness only within the tested parameter ranges, rather than general robustness over the entire uncertainty space.
Furthermore, a comparative scheme in which only the PLL gains were retuned was constructed. Both schemes were evaluated at SCR .
At SCR , Figure 17a shows that the PLL-retuning scheme develops a growing oscillation at 16 MW/turbine during the 13–16–13 MW/turbine test. Figure 17b shows that the proposed method develops an approximately 30 Hz growing oscillation at 25 MW/turbine during the 13–25–13 MW/turbine test, and the oscillation gradually decays after the power reference returns to 13 MW/turbine. The 16 and 25 MW/turbine levels are representative instability test points for the PLL-only and proposed controllers, respectively; these discrete tests indicate a higher tested power-transfer boundary for the proposed controller.
Figure 17.
Comparison of representative tested power-transfer boundaries at SCR (unstable test points): (a) PLL retuning; (b) proposed bandwidth coordination.
It is worth noting that, from an engineering implementation perspective, the proposed method can be used as an offline controller-design and commissioning tool without modifying the existing LFTS topology or introducing additional control loops. First, the terminal model can be established using the equipment parameters, operating power, and grid SCR. GN analysis is then employed to identify the critical interaction band and the participating control loops, after which the existing PI gains of the wind-farm PLL, DVC, reactive-power loop, and M3C low-frequency voltage loop are coordinated according to the bandwidth-separation criterion. Before field commissioning, the resulting parameters can be verified through digital simulation and controller testing. Therefore, the proposed procedure provides a practical route from stability diagnosis to controller tuning.
4.6. Power-Loss, Cost-Benefit, and Sensitivity Analysis
To further evaluate the operating losses and engineering benefits of the LFTS, the terminal voltage, active power, and reactive power obtained from the simulations are used together with the line and M3C parameters in Table 2. For a wind farm comprising n identical wind turbines, the current of one turbine and the total cable current are expressed as
Accordingly, the resistive loss of the collection lines is .
The cable charging current is , where and f are the cable charging current and operating frequency, respectively. Assuming that the active-current and charging-current components are approximately orthogonal, the cable resistive loss and the corresponding reduction obtained by changing from 50 Hz to 50/3 Hz are given by
At 19 MW/turbine, the simulated cable-side voltage is 1.045 pu. The cable charging currents at 50/3 Hz and 50 Hz are 100.12 A and 300.36 A, respectively, and the corresponding total cable losses of the 19-turbine wind farm are 34.91 MW and 38.28 MW. Thus, low-frequency operation reduces the cable loss by 3.37 MW, or 8.80%. The collection-line loss in the same case is 0.22 MW. For the nine-arm M3C, the equivalent conduction loss is
where is the RMS current of arm b, and and are the M3C low-frequency- and power-frequency-side terminal currents, respectively. The calculated M3C equivalent conduction loss is 1.85 MW. After deducting this loss, low-frequency transmission retains a net operating-loss benefit of approximately 1.52 MW compared with 50 Hz transmission.
The proposed bandwidth-coordination method does not require additional hardware; its potential economic benefit in this case study is evaluated using the model-estimated increase in locally stable power transfer. At SCR = 1.50, a separate sweep of the critical eigenvalues of the 19-state model yields estimated local transition powers of approximately 14.88 MW/turbine for PLL-only retuning and 21.03 MW/turbine for the proposed method. These model-based estimates are distinct from the 16 and 25 MW/turbine instability test points in Figure 17. Their estimated difference is 6.15 MW/turbine, corresponding to 116.81 MW for the 19-turbine wind farm. With equivalent utilization hours H and electricity price , the loss-reduction and power-transfer benefits are
where H and are the annual equivalent utilization hours and the electricity price, respectively, and and are the net loss reduction and model-estimated increase in locally stable transfer capability for the stated case, respectively. At h/year and CNY/kWh, the net loss-reduction benefit is approximately 0.61 million CNY/year, whereas the potential gross benefit associated with this model-estimated increase is approximately 46.72 million CNY/year.
To evaluate parameter sensitivity, the normalized sensitivity is defined as , where x and Y are the investigated parameter and the corresponding performance indicator, respectively. At 19 MW/turbine, varying the cable length by changes the cable-loss reduction from 1.72 MW to 5.82 MW. Varying the cable resistance by changes this value to 2.69–4.04 MW, varying the cable capacitance by changes it to 2.16–4.85 MW, and varying the terminal voltage by changes it to 2.73–4.08 MW. Cable length has the greatest influence because and , giving the approximate relation .
5. Conclusions
This paper established a unified small-signal and impedance framework for a GFL offshore wind farm connected through an M3C-based LFTS. The GN analysis, modal participation, parameter-sensitivity results, and time-domain loop-isolation tests jointly indicate that the approximately 30 Hz mode is strongly associated with coupled control–network dynamics, with controller tuning and network impedance both affecting its damping. Separating the PLL, DVC, reactive-power, and M3C voltage-loop bandwidths to 10, 1, 80, and 60 Hz increased the local real-axis indicator from (conventional) to 0.3112 (proposed) at 19 MW/turbine and SCR = 2.24, and from (conventional) to 0.2881 (proposed) at 19 MW/turbine and SCR = 1.78. MATLAB/Simulink verification gave state-space-model errors below 2.273%; the conventional approximately 30 Hz power oscillation increased from 4.20 to 24.32 MW, whereas the coordinated cases retained positive damping. Positive damping was maintained under the tested operating conditions, including 22 MW and SCR = 1.50 with 20% parameter deviations. At SCR = 1.50, an additional power-step test produced a growing approximately 30 Hz oscillation at 25 MW/turbine, identifying this value as an unstable test point at a representative tested power-transfer boundary. Taken together, the unified model, GN-based interaction diagnosis, bandwidth-coordination design, and time-domain verification provide a systematic framework for analyzing and enhancing the small-signal stability of GFL offshore wind farms connected through M3C-based LFTS. The proposed strategy requires no additional hardware and improves the small-signal stability and representative tested power-transfer boundary of the LFTS under high-power and weak-grid conditions solely through controller-parameter coordination. This can help reduce wind-power curtailment or converter tripping caused by control-interaction oscillations, thereby improving the utilization of the offshore wind farm and existing transmission corridor. Furthermore, future work will incorporate switching-level effects, dynamic current-limiting and current-priority control, anti-windup implementation, fault-ride-through control, and protection coordination, thereby enabling a more comprehensive assessment of LFTS stability and operational reliability under severe disturbances.
Author Contributions
Conceptualization, Y.L. and J.L.; methodology, Y.L., Z.L. and J.L.; software, Z.L. and J.Y.; validation, J.Y., Y.Y. and C.D.; formal analysis, Y.L. and Z.L.; investigation, Y.Y. and C.D.; resources, X.N.; data curation, J.Y. and Y.Y.; writing—original draft preparation, Y.L. and Z.L.; writing—review and editing, C.D., X.N. and J.L.; visualization, J.Y. and C.D.; supervision, X.N. and J.L.; project administration, X.N.; funding acquisition, X.N. All authors have read and agreed to the published version of the manuscript.
Funding
This research was funded by the Science and Technology Project of State Grid Zhejiang Electric Power Co., Ltd., grant number B311DS25Z021.
Data Availability Statement
Data is contained within the article.
Conflicts of Interest
Authors Yi Lu, Ziming Li, Jiachuan You, Yanxia Yao, Chao Ding and Xiaojun Ni were employed by State Grid Zhejiang Electric Power Co., Ltd. The remaining author declares that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.
Nomenclature
| Symbol | Definition |
| Direct and quadrature axes of the synchronous reference frame | |
| Small-signal perturbation around an equilibrium point | |
| s | Laplace variable |
| Low-frequency- and power-frequency-side angular frequencies | |
| Voltage and current vectors in the frame | |
| Active power, reactive power, and DC-link voltage | |
| Wind-turbine converter filter parameters | |
| Wind-farm collection-line resistance and inductance | |
| Submarine-cable resistance, inductance, and shunt capacitance | |
| Equivalent transformer winding resistances and leakage inductances | |
| Receiving-grid equivalent resistance and inductance | |
| M3C arm resistance, arm inductance, and filter capacitance | |
| PLL angle and its deviation from the low-frequency reference angle | |
| Proportional and integral gains of the wind-farm PLL | |
| Proportional and integral gains of the wind-farm DC-voltage controller | |
| Proportional and integral gains of the wind-farm reactive-power controller | |
| Proportional and integral gains of the wind-farm current controller | |
| Proportional and integral gain matrices of the M3C low-frequency voltage controller | |
| State, input, output, and feedthrough matrices | |
| Single-turbine and aggregated wind-farm terminal admittance matrices | |
| LFTS nodal-admittance and terminal-impedance matrices | |
| Generalized Nyquist return-ratio matrix | |
| Return-difference determinant | |
| (GN criterion) | Open-loop RHP pole count and signed net counterclockwise encirclement count |
| Required net encirclement count () and closed-loop RHP pole count () | |
| Eigenvalue branch of the generalized Nyquist return-ratio matrix | |
| Critical-point distance and local real-axis indicator | |
| Short-circuit ratio of the receiving grid | |
| Minimum nominal bandwidth-separation ratio | |
| Nominal local closed-loop design bandwidth of control loop k | |
| Number of wind turbines and voltage ratio of transformer | |
| Per-turbine active power, reactive power, terminal voltage, and cable-side voltage | |
| Per-turbine current, total cable current, and cable charging current | |
| Collection-line loss, cable loss, and cable-loss reduction | |
| RMS M3C arm current and low- and power-frequency-side terminal currents | |
| M3C conduction loss, net loss reduction, and model-estimated increase in locally stable transfer capability for the stated case | |
| Annual equivalent utilization hours, electricity price, loss-reduction benefit, and power-transfer benefit | |
| Normalized sensitivity, varied parameter and indicator with their nominal values, cable length, and operating frequency |
Appendix A
For the terminal-oriented reduction, balanced three-phase operation, identical arm parameters, and identical control parameters for the three sub-converters on each side are assumed. The low-frequency-side sub-converter current vector is decomposed as
Here, is the common low-frequency terminal current, whereas contains the internal differential and circulating-current components. Because the latter components sum to zero at the low-frequency terminal, they do not contribute directly to the terminal voltage–current relationship and are therefore not retained as independent states. The dominant terminal response of the complete current-control dynamics is represented by
where is the equivalent current-response time constant of the complete averaged model at the low-frequency terminal. Consequently, the reduced M3C model retains the two terminal-current states and and the two low-frequency voltage-loop integral states and , giving the four M3C-related states used in the 19-state model.
Based on Equations (1)–(9), the 19 state variables of the model are given by
Their differential equations can be expressed as
Here, is the PLL-angle deviation and is the coordinate-transformation matrix. The vectors and collect the M3C current and voltage-loop integral states, respectively, while and , , , , and denote the wind-farm current error, converter-voltage command, M3C terminal-voltage error, and M3C current reference, respectively. The quantities and are the terminal shunt capacitances, and are the corresponding damping conductances, and and are the equivalent DC-link and M3C current-response time constants, respectively. The state-space equations are then obtained as
Writing , , and , the nonzero entries obtained by linearizing (A2) at the equilibrium point are listed below; all unlisted entries are zero.
For the first row of , , , , , , , , , , and .
For the second row, , , , , , , , , , and .
For rows 3–5, , , , , , , , , and .
For the PLL states, , , , , , , and .
For the current-controller integral states, , , , , , , , , , , and .
For the network states, , , , , , , , , , , , , , , , and .
The remaining network and M3C entries are , , , , , , , , , , , , , , , and .
The only nonzero entry of is . The nonzero entries of are , , , , , , , , , , , , , and . Here, is the power base, and denote the nonlinear state and output mappings, respectively, and the subscript 0 indicates evaluation at the equilibrium point.
References
- Sehloff, D.; Roald, L.A. Low Frequency AC Transmission Upgrades with Optimal Frequency Selection. IEEE Trans. Power Syst. 2022, 37, 1437–1448. [Google Scholar] [CrossRef] [Scilit]
- Meng, Y.; Yan, S.; Wu, K.; Ning, L.; Li, X.; Wang, X.; Wang, X. Comparative Economic Analysis of Low Frequency AC Transmission System for the Integration of Large Offshore Wind Farms. Renew. Energy 2021, 179, 1955–1968. [Google Scholar] [CrossRef] [Scilit]
- Ma, J.; Dahidah, M.S.A.; Pickert, V.; Yu, J. Hierarchical Energy Balance Control Method for M3C Based on Injecting Output Frequency Circulating Currents. IEEE Trans. Power Electron. 2020, 35, 2424–2435. [Google Scholar] [CrossRef] [Scilit]
- Ali, S.W.; Sadiq, M.; Terriche, Y.; Naqvi, S.A.R.; Hoang, L.Q.N.; Mutarraf, M.U.; Hassan, M.A.; Yang, G.; Su, C.L.; Guerrero, J.M. Offshore Wind Farm-Grid Integration: A Review on Infrastructure, Challenges, and Grid Solutions. IEEE Access 2021, 9, 102811–102827. [Google Scholar] [CrossRef] [Scilit]
- Xiao, H.; Huang, X.; Huang, Y.; Liu, T.; Yang, P. Black Start Strategy of DRU-Based Low-Frequency AC Transmission System for Offshore Wind Power Integration. IEEE Trans. Ind. Appl. 2024, 60, 8319–8328. [Google Scholar] [CrossRef] [Scilit]
- Dakic, J.; Cheah-Mane, M.; Gomis-Bellmunt, O.; Prieto-Araujo, E. Low Frequency AC Transmission Systems for Offshore Wind Power Plants: Design, Optimization and Comparison to High Voltage AC and High Voltage DC. Int. J. Electr. Power Energy Syst. 2021, 133, 107273. [Google Scholar] [CrossRef] [Scilit]
- Bravo, P.; Pereda, J.; Merlin, M.M.C.; Neira, S.; Green, T.C.; Rojas, F. Modular Multilevel Matrix Converter as Solid State Transformer for Medium and High Voltage AC Substations. IEEE Trans. Power Deliv. 2022, 37, 5033–5043. [Google Scholar] [CrossRef] [Scilit]
- Ning, L.; Wu, Z.; Wang, X.; Wang, X.; Yi, L. Low-Frequency Side Impedance Modeling and Stability Discrimination of Fractional Frequency Transmission System Based on Modular Multilevel Matrix Converter. Power Syst. Technol. 2022, 46, 3720–3730. [Google Scholar]
- Lu, Z.; Cheng, C.; Liu, B.; Wang, T.; Meng, Y.; Zhao, B.; Jia, C. Small-Signal Stability Analysis of Grid-Following Offshore Wind Farms Integrated via Flexible Low-Frequency Transmission Systems. Power Syst. Technol. 2026. [Google Scholar] [CrossRef]
- Ni, X.; Ding, C.; Tang, Y.; Chen, A.; Lu, Y. Research on High-Frequency Resonance in Flexible Low-Frequency AC Transmission Systems. Zhejiang Electr. Power 2025, 44, 109–117. [Google Scholar] [CrossRef]
- Zhang, H.; Han, J.; Sha, Z.; Wei, F.; Wang, X.; Wang, X. System Wide-Band Oscillation Analysis of Fractional Frequency Offshore Wind Power Systems. IET Gener. Transm. Distrib. 2024, 18, 4386–4398. [Google Scholar] [CrossRef] [Scilit]
- Zhou, W.; Wang, Y.; Torres-Olguin, R.E.; Chen, Z. Effect of Reactive Power Characteristic of Offshore Wind Power Plant on Low-Frequency Stability. IEEE Trans. Energy Convers. 2020, 35, 837–853. [Google Scholar] [CrossRef] [Scilit]
- Li, C.; Liang, J.; Cipcigan, L.M.; Ming, W.; Colas, F.; Guillaud, X. DQ Impedance Stability Analysis for the Power-Controlled Grid-Connected Inverter. IEEE Trans. Energy Convers. 2020, 35, 1762–1771. [Google Scholar] [CrossRef] [Scilit]
- Wang, X.; Taul, M.G.; Wu, H.; Liao, Y.; Blaabjerg, F.; Harnefors, L. Grid-Synchronization Stability of Converter-Based Resources—An Overview. IEEE Open J. Ind. Appl. 2020, 1, 115–134. [Google Scholar] [CrossRef] [Scilit]
- Li, C.; Wang, S.; Liang, J. Tuning Method of a Grid-Following Converter for the Extremely-Weak-Grid Connection. IEEE Trans. Power Syst. 2022, 37, 3169–3172. [Google Scholar] [CrossRef] [Scilit]
- Huang, L.; Wu, C.; Zhou, D.; Blaabjerg, F. A Double-PLLs-Based Impedance Reshaping Method for Extending Stability Range of Grid-Following Inverter Under Weak Grid. IEEE Trans. Power Electron. 2022, 37, 4091–4104. [Google Scholar] [CrossRef] [Scilit]
- Guo, X.; Zhang, S.; Yan, Z.; Wei, Y.; Hu, X. A Novel Phase-Locked Loop Structure to Enhance Converter Stability in Weak Grids. IEEE Trans. Power Electron. 2023, 38, 13855–13865. [Google Scholar] [CrossRef] [Scilit]
- Lin, X.; Yu, J.; Yu, R.; Zhang, J.; Yan, Z.; Wen, H. Improving Small-Signal Stability of Grid-Connected Inverter Under Weak Grid by Decoupling Phase-Lock Loop and Grid Impedance. IEEE Trans. Ind. Electron. 2022, 69, 7040–7053. [Google Scholar] [CrossRef] [Scilit]
- Huang, L.; Xin, H.; Li, Z.; Ju, P.; Yuan, H.; Lan, Z.; Wang, Z. Grid-Synchronization Stability Analysis and Loop Shaping for PLL-Based Power Converters With Different Reactive Power Control. IEEE Trans. Smart Grid 2020, 11, 501–516. [Google Scholar] [CrossRef] [Scilit]
- Chen, J.; Wu, J.; Shi, B.; Chen, Q.; Fan, Y.; Fang, Y.; Wang, X. Parameter Identification for Magnetic-Geared Motors Combining Resonance Characteristics and BP-NN. Measurement 2026, 290, 122794. [Google Scholar] [CrossRef] [Scilit]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2026 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.