Dynamic Hygrothermal Analysis for Retrofitting Opaque Envelopes in Humid Climates: From Simulations to Guidelines

,
,
and
Mechanical, Energy and Management Engineering Department, University of Calabria, V. P. Bucci 46/C, 87036 Rende, Italy
*
Author to whom correspondence should be addressed.

Abstract

This paper introduces the dynamic hygrothermal performances of existing walls in humid climates using the EN ISO 15026 procedure. Water content, mould formation and freezing risk were investigated considering rock wool (RW) and expanded polystyrene (EPS) allocated at different points of two typologies of existing walls requiring renovation. Results show that RW is recommended for insulation on the external side, whereas EPS is more suitable for the internal side. A freezing risk occurs in massive walls insulated internally with RW in severe winter climates. Mould formation appears in the initial phases on the renovated side, driven by the built-in humidity of the new layers. Wall thermal transmittance shows large fluctuations, especially in lightweight structures renovated with EPS, reaching an increase of over 22% at the beginning of the heating period, driven by EPS water content peaks of 1.9 kg/m2 in cold climates when installed on the external side, achieved in a stabilized regime and independently from the wall’s technical solution. Outcomes confirm transient hygrothermal analysis as the recommended approach to evaluate the component behaviour over a long-term projection, facilitating sizing in the design phase and ensuring compliance with regulations for retrofitted elements.

1. Introduction

The current building stock represents the sector absorbing the greatest share of primary energy worldwide, with a continuously increasing trend of energy demands [1]. In Europe, the building stock contributes 35% of greenhouse emissions, due to a large share of aged edifices often equipped with low-efficiency plants [2]. For this purpose, the last modifications in the Energy Performance of Buildings Directive have set the European framework to reduce energy use in existing buildings without sacrificing thermal comfort conditions and occupant well-being [3]. Among the different Energy Efficiency Measures (EEM) for refurbishment [4], the insulation of opaque dispersing surfaces allows the enhancement of a building’s thermal performance by contrasting winter thermal losses and summer heat gains [5]. Nevertheless, opaque envelopes are usually made of porous materials; therefore, the application of an insulation layer also determines modifications in the vapour transport through the wall, affecting component healthiness, condensation phenomena and steady-state thermal transmittance [6].
In light of this, the effects of moisture transfer on the building energy performance were investigated in depth in the relevant literature. In Ref. [7], a detailed code was implemented to consider combined heat and moisture transfer through the walls, taking into account moisture sources inside the rooms, capillary action, diffusion and vapour absorption/desorption processes, finding the significant role of latent exchanges. In Ref. [8], the effects related to the simulation of hygroscopic materials allowed for determining heating and cooling savings ranging between 5% and 30% in the presence of well-controlled HVAC systems. The investigation carried out in ref. [9] in the Chinese context found a significant amount of water in the initial phases in walls insulated with EPS (expanded polystyrene), which requires a long time for evaporation. Regarding three different climatic zones, a simplified model to evaluate the effects of the moisture content on the wall performances was introduced in ref. [10], allowing for reducing computational effort without sacrificing the accuracy of the results. The case study described in Ref. [11] stated the strong influence of adsorption and desorption phenomena on the calculation of thermal loads and energy consumption, confirming that the disregard of moisture transfers may oversize the HVAC by 13% and underestimate the cooling energy consumption by 4%. A comparison between hygrothermal and sole thermal simulations was carried out in ref. [12], showing a non-negligible underestimation of heating and cooling energy demands when the moisture transfer is ignored. In ref. [13], the hygrothermal performances of typical Chinese external walls were numerically investigated through a validated in-house code, both in hot summer and cold winter humid climates, detecting thermal load overestimations of 2.1–10.1% when the moisture transfer is neglected. In Ref. [14], it is confirmed that moisture is the primary agent for building elements deterioration, allowing for a rapid identification of the wall’s vulnerable points in the design phase. An experimental investigation targeted at assessing the drying capacity of different configurations of wall panels was carried out in ref. [15], introducing the evaporation rates and the moisture content profiles in different samples. A similar work, but based on an entire wall, can be found in ref. [16]. A hygrothermal model to evaluate the development of mould growth on building structures was presented in ref. [17], identifying the critical conditions required for biological growth and simulating the progression over time under different surface conditions. An analogous work was conducted in ref. [18], but specifically for some wooden materials employed in the building sector.
Beyond in-house implemented codes, the transient moisture content inside opaque walls on a long-term projection can be determined in detail by commercial tools, taking into account other factors that do not appear in simplified procedures [19], such as the built-in humidity levels in building elements, pouring rain on the exposed surfaces and the rising of groundwater. In particular, the sophisticated process of vapour and liquid transient transportation in walls can be investigated by software packages such as Delphin, HygIRC, Latenite, Match, MOIST and WUFI [20], with the latter based on Kunzel’s model, which is the most validated in the field [21]. For instance, WUFI was employed to assess the transient hygrothermal behaviour of a novel SIP (Stay-In-Place) wall conceived for the Mediterranean climate, considering that these structures suffer from a higher thermal transmittance variation than traditional masonry solutions [22]. WUFI was also used to investigate typical heritage buildings in Korea, by combining an experimental campaign aimed at measuring the initial moisture content inside the walls after renovation with a numerical investigation to simulate the hygrothermal behaviour over 70 years [23]. The hygrothermal performance of rendered solid brick wall constructions to identify the optimum and most appropriate retrofit intervention carried out by WUFI is presented in ref. [24]. Furthermore, WUFI was employed to investigate the mould growth risk in timber building envelopes, considering the role of material properties, climatic data variation, initial conditions and diffusion characteristics, as introduced in ref. [25].
These documents highlight that results from a hygrothermal analysis are difficult to generalize, because the same technological solution offers different behaviour when internal and external boundary conditions are varied. Moreover, hygrothermal assessments allow for observing issues connected with vapour transfer, which can emerge with time, supporting decisions aimed at preserving material durability, occupant well-being and compliance with regulations in the building sector by identifying the best allocation of the insulation layer inside the structure.
For this purpose, the goal of this investigation is the evaluation of the transient hygrothermal performance by the software WUFI 6, which implements the EN ISO 15026 procedure [26], of two opaque wall solutions requiring renovation in a humid climatic context, when retrofitted with common insulation materials. The moisture accumulation, mould risk, freezing phenomena and thermal transmittance variability were determined by WUFI by varying external boundary conditions, wall typology, insulation material and positioning. The paper is structured as follows: Section 2 details the methodology, including the description of the considered wall configurations, boundary conditions and simulation criteria; Section 3 presents transient results on moisture content, thermal transmittance, mould formation and risk of freezing; Section 4 discusses material-specific performance and climatic influences; and Section 5 concludes with actionable recommendations and conclusions for providing suggestions for retrofitting opaque vertical walls in humid climates. Considering that, in the medium term, the EU regulations are expected to avoid the sale and the rent of energy-intensive building-plant systems [27], forcing their refurbishment, this work aims to provide climate-specific retrofitting guidelines to support the design phase [28].

2. Materials and Methods

The hygrothermal analyses involve two different vertical walls that are renovated by adding EPS and rock wool (RW) insulation layers, considering different points of allocation. These materials, commonly employed in the considered climatic zone, were already investigated by WUFI, with results validated in [29]. Furthermore, to observe the different behaviour with different weather data, opposite climatic conditions were considered as boundary conditions on the external side. In particular, a severe winter location (Milan, Northern Italy, Lat. 45.17° N, Long. 9.17° E) and a cooling-dominant zone (Sibari, Southern Italy, Lat. 39.75° N, long. 16.45° E), both affected by high external humidity ratios, were simulated by keeping internal boundary conditions unchanged. The main goal is the identification of the typology and the correct positioning of the insulation layer in two common solutions of external wall, which better preserve durability and thermal performance. The high external humidity ratio determines a high partial vapour pressure difference between the indoor and outdoor environment, driving the water vapour flux crossing the structure. Beyond water vapour migration, other humidity sources in buildings derive from the pouring rain, the (eventual) endogenous vapour production, the material’s built-in humidity in the assembling phase and the groundwater rise from the basement. These are taken into account in WUFI 6 [30], which implements the dynamic model described in the standard EN 15026:2023, the software employed to carry out this investigation. The tool incorporates a material library that allows for considering thermal conductivities and water vapour diffusion resistance as functions of temperature and relative humidity, as well as hygroscopic sorption and liquid transport coefficients. The main equations governing the hygrothermal assessments following the EN 15026 model are the heat conservation law and the humidity transport equation. In the first case, the stored and the generated thermal powers per volume unity are set as equal:
[ c m · ρ + c w · w ( φ ) ] ∂ θ ∂ t = − ∂ ∂ x [ − λ ( w ) · ∂ θ ∂ x + h e · g v ]
in which the first square bracket includes the thermal capacity of the dry material (cm·ρ) and the water thermal capacity (cw), depending on the mass humidity content (w) function of the relative humidity (φ); θ is the temperature and x is the material thickness. The last square bracket contains the sensible heat flux (first term), determined considering the thermal conductivity (λ) variable with the mass humidity content, and the latent heat flux share is calculated starting from the water vaporization heat (he) and the diffusion vapour flux (gv). The latter is determined with the following formula:
g v = 1 μ ( φ ) · δ 0 · ∂ p v ∂ x
in which μ is the vapour resistance factor, depending on the relative humidity, δ0 is the air–water vapour permeability evaluated at the partial pressure pv. Regarding the humidity transport equation, the humidity flux is determined as the sum of the diffusion vapour flux and the water flux driven by capillary transport, the latter strictly depending on the material porosity:
∂ w ( φ ) ∂ φ · ∂ φ ∂ t = ∂ ∂ x · [ g v + K ( p s u c ) · ∂ p s u c ∂ x ]
where psuc is the suction pressure determining the value of the transport coefficient K that takes into account the liquid conductivity determined as a function of the transport coefficient Dw (in turn, depending on the water content) and the material and boundary conditions:
K ( p s u c ) = − D w · ∂ w ∂ p s u c
Figure 1 shows the technical solutions of two external walls considered for the hygrothermal assessment, both assembled with external and internal plaster layers, 1.5 cm and 1 cm, respectively. The first solution (1), heavyweight, is made of a single brick layer of 30 cm, while the second one (2), lightweight, is made of two brick layers, 15 cm and 8 cm thick, respectively, incorporating an internal non-ventilated air gap of 8 cm. These solutions have been largely adopted in the previous century in the Mediterranean area to assemble vertical walls. The different thicknesses of hollow bricks produce diverse thermal resistances and densities, although they were all based on clay as the raw material. In WUFI, the hollow 8 cm-thick brick was set with a density lower than the other two clay elements, which were conversely simulated with the same hygrothermal properties.
Figure 1. Technological solutions of non-renovated external walls considered for the hygrothermal analyses, without (1) and with (2) an internal non-ventilated air gap.
For the energy renovation of the opaque walls, two different techniques of insulation have been contemplated for both structures to consider different application cases:
  • Insulation on the wall’s external side (ETICS, especially in isolated structures);
  • Insulation on the wall’s internal side (historical buildings, apartments).
The water content within the insulation layer significantly affects the achievable thermal performance; indeed, the humidity absorbed by diffusion leads to an increase in thermal conductivity, as depicted in Figure 2 for the considered materials, with points that a quadratic relation can reasonably interpolate. It can be appreciated that thermal conductivity is quite similar, with RW offering a lower value when the water content is lower than 450 kg/m3. For greater water contents, EPS is preferable. Furthermore, the thermal conductivity values double for water contents slightly higher than 200 kg/m3.
Figure 2. Trends of the thermal conductivity of EPS and rock wool layers as a function of the water content [31].
An insulation thickness of 10 cm was set to make the renovated wall compliant with current regulations concerning building refurbishment, to obtain a thermal transmittance (steady-state U-value) lower than 0.28 W/m2 K, which is a threshold value valid for Italy [28], but is calculated considering dry layers. Table 1 lists the thermal and hygroscopic properties of the involved materials, opportunely selected from the WUFI library and derived from experimental tests (ρ is the density in dry conditions, ε is the material porosity, c is the specific heat, λ is the thermal conductivity and μ is the vapour resistance factor).
The hygrothermal analyses were conducted by referring to the north exposure, considering a wall 90° tilted and adopting the rain load calculated according the ASHRAE 160 standard, with the parameters listed in Table 2. It is worth noting that, in the Mediterranean area, the role of solar irradiance is significant to dry the opaque element; therefore, this orientation represents the worst conditions, as it lacks the latent drying exchanges promoted by beam solar irradiance, even in summer. This promotes a greater share of water content within the structure, which remains more susceptible from the hygrothermal viewpoint, as depicted in other investigations [32,33].
Regarding the boundary conditions on the external surfaces, we used weather data taken from an HRY (Hygrothermal Reference Year) and data included in the WUFI library. Indeed, to predict long-term moisture-related risks in building components, the literature suggests using an HRY or MRY (Multilayer Weather Dataset), rather than MRYs (Moisture Reference Years) and TYs (Typical Years) [34], reducing computational effort [35]. Other model parameters concerning some properties of the wall’s outer surface are listed in Table 2.
Table 1. Density, porosity, specific heat, thermal conductivity in dry conditions and vapour resistance factors for the materials involved in the considered walls [31].
Table 2. Other key model parameters set in WUFI concerning the wall surface.
For the boundary conditions on the internal side, the EN 15026 approach, following the WTA 6.2 guideline and developed for heritage preservation, was set; the internal set-point is 20 °C when the outdoor air temperature is below 10 °C, it varies linearly for outdoor air temperatures ranging between 10 °C and 20 °C and is fixed at 25 °C when the outdoor air temperature exceeds 20 °C. Regarding the indoor relative humidity level, the medium humidity load +5% approach was set, which implies an increase of 5% of the average humidity level, set to 30% when the outdoor air temperature is below −10 °C, 60% when the outdoor air temperature exceeds 20 °C and a linear trend for intermediate outdoor temperatures is used. Simulations were carried out considering rainfall on external surfaces, but with limited water absorption effects, assuming that the walls’ external surfaces were painted with an acrylic tint, as indicated in Table 2. Given the significant climatic variability across Italy, two distinct zones have been considered: The first (A) is quite warm, with 973 HDD (Heating Degree Day) and a prevalent humid dry maritime climate, showing a yearly average outdoor temperature of 18.2 °C and significant solar irradiance on the exposed surfaces. The second one (B) has 2404 HDD; therefore, it is colder than the former, with a prevalent humid continental climate, for which the yearly average outdoor temperature is 14.7 °C, with lower solar irradiance magnitude on the exposed surfaces. The trends of the main weather data refer to the locations of Milano and Sibari, and they are shown in Figure 3; the west and north orientations are more affected by pouring rain.
Figure 3. Trends of outdoor air temperature (red) and relative humidity (green) for the climatic zones with 973 HDD (A) and 2404 HDD (B).
Regarding the initial conditions, the built-in moisture default levels suggested by WUFI were set for the layers added in the wall renovation (1.787 kg/m3, 0.820 kg/m3 and 400 kg/m3, respectively, for EPS, RW and plaster). In contrast, the existing layers were considered, with a humidity level determined after five years in preliminary simulations using the same boundary conditions on the wall surfaces, setting the default initial value at 80% for relative humidity. The simulation period is 5 years long to reach a “dynamic steady-state” trend, confirming the attainment of a stabilized behaviour of the opaque component and the goodness of the adopted solution.
The objectives of this investigation are as follows:
-
The evaluation of the dynamic water content inside the entire wall structure and in the insulation layers, to verify if the water content is controlled to avoid material strength loss, rotting and mould growth. Usually, the water content should decrease after the initial conditions due to the drying process of the built-in humidity, whereas the successive periodic seasonal fluctuations denote the achievement of the dynamic steady state.
-
The evaluation of mould formation risk, which could occur even though condensation phenomena are avoided. The physical condition that allows for mould growth implies high relative humidity in the proximity of the internal wall surface for long periods, representing ideal conditions for mould spore germination and proliferation. WUFI uses the Biohygrothermal Model, which compares the material’s critical water content with the simulated water content in mould spores to predict germination and growth, alongside the VTT/Viitanen model for determining a simpler mould index. The risk is evaluated by referring to CLASS II as a substrate category, indicating mineral/porous material (moderate risk). The quantitative measure is carried out by determining the mould index (MI), whereas graphically, WUFI produces a dynamic graph in terms of isopleth curves in which relative humidity is shown as a function of the air temperature. The time variable is accounted for by depicting the points with different colours: yellow for the first timestep and tonalities that become darker proceeding to the end of the simulation. In ideal conditions, these points must be below the threshold isopleth curves to ensure that it is physically impossible for mould formation; conversely, the risk of mould formation cannot be excluded, and non-compliance is achieved when MI ≥ 2, since mould growth is visible to human eyes. The threshold curves are drawn by connecting the points that allow for the proliferation of two typical mould species in residential indoor environments.
-
The evaluation of the freezing risk inside the wall, because a significant number of freezing–thawing cycles can weaken and/or damage the porous materials. Indeed, the allowed moisture content depends on the material’s typology and elements such as plaster, masonry and concrete can theoretically reach saturation without presenting problems because they are frost-resistant (although high humidity levels increase the risk of mould formation on the external surface). Conversely, porous elements (clay bricks) are frost-sensitive; therefore, it is mandatory to limit the critical combinations of water content and temperature. The WTA guidelines suggest a threshold of 95% in relative humidity in the porous elements to avoid frost damage in less resistant materials. A control point was located on the interface between hollow bricks and the insulation layer: if the relative humidity exceeds 95% when the surface temperature is lower than 0 °C, freezing occurs. A count of potential freeze–thaw episodes was carried out, considering dangerous the attainment of several cycles in the range 6–35, which makes structural damage likely and leads to non-compliance of the structure.
-
The calculation of the monthly average thermal transmittances by using a proper “Thermal Transmission Model” available in the software. Indeed, the water content in the layers affects the heat transfer, because the increase in moisture level within the wall significantly reduces the layer’s thermal resistance. An average value calculated yearly is then compared with the U-value calculated with dry layers and employed to determine threshold values, obtaining the wall’s compliance when the former exceeds the latter by a maximum of 0.01 W/m2 K, which is considered a tolerated interval to ensure U-value invariance at a yearly level.

3. Results

The main results of the hygrothermal analyses are introduced in graphical form for each analyzed case in terms of humidity content, isopleth curves, temperature against relative humidity graph in the critical wall sections and the monthly average thermal transmittances. To identify the investigated technical solution, every wall configuration in the correspondent climate is indicated by using a series of four characters: the first refers to the technical solution (1 or 2), the second refers to the climate (A or B), the third to the insulation material (X for EPS and W for rock wool) and the fourth specifies the insulation position (i for internal and e for external). So, combination 2BWe indicates the wall with the air gap located in the coldest climate renovated with the insulation layer made of rock wool installed on the external side. A continuous five-year long simulation was set, which started on 1 October 2025 and ended on 30 September 2030.

3.1. Hygrothermal Assessments for the Wall Without Air Gap: Technical Solution 1

In Figure 4a, the comparison in terms of total water content inside the wall is depicted for the configurations 1AXe and 1Awe: it can be appreciated that the lower water content offered by the first solution is only in the spring–summer of the first year, whereas in a long-term projection, 1AWe performs better. Anyway, after the second year, 1AWe reaches a dynamic steady-state trend, whereas 1AXe requires an additional year, showing a total water content fluctuating around a value of about 3 kg/m2. Figure 4b depicts the same quantities but specifically for the insulation layers; after the quick drying of the built-in humidity in the first spring/summer for both materials, EPS exhibits a higher water content than rock wool, which fluctuates while remaining below 1 kg/m2 due to its better breathability. Anyway, the water content remains limited to values below 1.5 kg/m2, already reaching a dynamic steady-state regime in the second year without highlighting peaks.
Figure 4. Comparison between technical solutions 1AXe and 1AWe in terms of the following: (a) Total water content in the wall. (b) Water content in the insulation layer.
Figure 5 refers to the mould formation risk on the interior wall surface for both solutions; as largely expected for ETICS solutions, the verification of mould formation prevention is satisfied for both 1AXe and 1AWe, as all points remain below the two threshold curves (the dashed black line and the grey line) throughout the simulations, showing identical trends.
Figure 5. Mould risk formation on the internal layer for solutions 1AXe and 1Awe: yellow points for the first timesteps and darker tonalities proceeding to the end of the simulation.
Figure 6 shows the risk of freezing, setting the critical section at the interface between the insulation layer and the hollow brick. The presence of the insulation layer on the external side maintains the wall’s warmer temperature; therefore, both of the technical solutions hinder ice formation, always observing a temperature greater than 12 °C and relative humidity lower than 80%.
Figure 6. Freezing risk for technical solutions 1AXe and 1Awe: yellow points for the first timesteps and darker tonalities proceeding to the end of the simulation.
Figure 7 depicts the monthly average thermal transmittances that consider the water content in each layer. It can be appreciated that both of the insulation materials respect the threshold value throughout the simulation, with mean values (red line) of 0.245 W/m2 K and 0.228 W/m2 K for 1AXe and 1AWe, respectively. The 1AWe configuration shows lower transmittance values, as the higher breathability results in a lower water content and, consequently, preserves its thermal performance. The black line refers to the thermal transmittance calculated by considering all the layers completely dry, obtaining the best values of 0.195 W/m2 K and 0.183 W/m2 K, respectively. The highest value in the considered climatic zones occurs at the beginning of the winter season and, when the dynamic steady state is achieved, amounts to 0.268 W/m2 K and 0.237 W/m2 K, respectively, for 1AXe and 1AWe. The annual variations are 0.041 W/m2 K for 1AXe and 0.030 W/m2 K for 1AWe. Finally, it is observed that the oscillation around the mean value of the total transmittance for configuration 1AXe is greater than that for configuration 1AWe. As is shown in Figure 4b, the temporal variation in the water content in the insulating layer is lower in the 1AWe case compared to the 1AXe case.
Figure 7. Monthly average thermal transmittance between technical solutions 1AXe and 1AWe.
Consequently, in the latter case, the thermophysical properties of the insulation exhibit greater variations over time, leading to a higher fluctuation in the overall wall transmittance.
Figure 8a depicts the total water content in the technical solutions 1AXi and 1AWi, highlighting the drawbacks emerging from the wall insulation installed on the inner side. It can be appreciated that the greater water content affecting the wall is about 1.5 times the values detected for cases 1AXe and 1AWe. Indeed, with the insulation placed on the interior, the temperature of the hollow brick decreases and, consequently, the evaporation of the water content within the layer is hindered. The dynamic steady state is reached in the fourth year, but in the case of inner-side insulation, EPS allows for achieving better results than rock wool, which, conversely, suffers from great fluctuation throughout the year, passing from 3.5 kg/m2 to over 4.5 kg/m2. The 1AWi configuration tends to dry at the beginning of the heating season and to accumulate further humidity at the beginning of spring, but this behaviour is due primarily to the water storage in the hollow brick. Indeed, by analyzing the water content in the insulation layers (Figure 8b), rock wool presents a lower water content than EPS, which, instead, suffers from greater fluctuation during the year. In both cases, the water content is lower than 1 kg/m2; therefore, 1AXi and 1AWi produce values lower than those detected for cases 1AXe and 1AWe, confirming that most of the water content inside the entire wall is in the hollow brick, whereas the insulation layers efficiently block water vapour migration during winter, detecting water content of about 0.7 kg/m2.
Figure 8. Comparison between technical solutions 1AXi and 1AWi in terms of the following: (a) Total water content in the wall. (b) Water content in the insulation layer.
The lower fluctuations shown by rock wool can be explained by better breathability, showing rapid attainment of a stabilized trend, whereas EPS requires about three years to reach the dynamic steady state.
Figure 9 confirms that both solutions 1AXi and 1AWi suffer from mould risk on the wall’s inner surface at the beginning of the simulation (yellow points), driven by the built-in humidity level in the assembling phases. Indeed, after the initial time, all the combinations of relative humidity and temperature points remain below the threshold curves.
Figure 9. Mould risk formation on the internal layer for solutions 1AXi and 1AWi: yellow points for the first timesteps and darker tonalities proceeding to the end of the simulation.
Considering the interface between the external plaster layer and the hollow brick as the critical section to evaluate the freezing risk, Figure 10 indicates that both solutions 1AXi and 1AWi assure a positive verification, with all the points with temperatures close to 0 °C, always with relative humidity lower than 95%. This result is due to the favourable climatic conditions characterizing location A.
Figure 10. Freezing risk for technical solutions 1AXi and 1AWi: yellow points for the first timesteps and darker tonalities proceeding to the end of the simulation.
Figure 11 highlights that the diverse allocation of the insulation layer within the wall’s stratigraphy influences the calculation of the thermal transmittance noticeably. It can be appreciated that 1AXi offers an average thermal transmittance value of 0.268 W/m2 K, 9.4% greater than the 1AXe solution, with peaks of 0.278 W/m2 K at the beginning of autumn. The 1AWi configuration performs better in light of an average value of about 0.239 W/m2 K and peaks of 0.245 W/m2 K. Anyway, in both technical solutions, the overall wall transmittance exhibits minimal variation around the mean value, as the water content within the insulating layer remains low. Consequently, the influence of moisture on the total wall transmittance is less pronounced.
Figure 11. Monthly average thermal transmittance between technical solutions 1AXi and 1AWi.
Figure 12, Figure 13, Figure 14 and Figure 15 show the results for technical solutions 1BXe and 1BWe attained by considering the same wall typology but changing the climatic zone. The total water content offers similar trends to those seen for location A, with comparable values but greater fluctuations. Regarding the water content in the insulation layers, EPS shows a visible and quick drying process during the first summer, after which it reaches the dynamic steady-state trend easily. Again, rock wool offers better performance with a trend similar to that observed for location A. No issues related to mould formation on the wall’s inner surface appear, as well as any manifestations of freezing risks, considering high levels of relative humidity with warm temperatures at the considered interface. Interesting results have been achieved in terms of wall thermal transmittance: despite the average values remaining appreciable and equal to 0.256 W/m2 K and 0.236 W/m2 for 1BXe and 1BWe, respectively, a large fluctuation during the year was observed. In particular, in the dynamic steady state, 1BXe ranges between 0.315 W/m2 K and 0.220 W/m2 K, whereas 1BWe offers thermal transmittances that vary from a maximum of 0.292 W/m2 K to a minimum of 0.202 W/m2 K. These results confirm that thermal losses are strongly variable during the year by influencing the energy balance of the building.
Figure 12. Comparison between technical solutions 1BXe and 1BWe in terms of the following: (a) Total water content in the wall. (b) Water content in the insulation layer.
Figure 13. Mould risk formation on the internal layer for solutions 1BXe and 1BWe: yellow points for the first timesteps and darker tonalities proceeding to the end of the simulation.
Figure 14. Freezing risk for technical solutions 1BXe and 1BWe: yellow points for the first timesteps and darker tonalities proceeding to the end of the simulation.
Figure 15. Monthly average thermal transmittance between technical solutions 1BXe and 1BWe.
Figure 16a,b show the total water content in the technical solutions 1BXi and 1BWi and the water content in the insulation layers. It can be appreciated that 1BXi offers better performance than 1BWi, with the latter often exceeding 5 kg/m2 at the end of winter. Again, the dynamic steady state is achieved after a longer time compared to solutions with insulation layers on the wall’s external side. This confirms that internal humidity in the winter period migrates easily through the wall employing rock wool. Regarding the water content in the insulation layers, it is worth noting that the values are not so dissimilar to those determined for cases 1AXi and 1AWi, meaning that the greater total water content in the entire wall exclusively involves the hollow brick, majorly solicited by the worse climatic conditions of location B.
Figure 16. Comparison between technical solutions 1BXi and 1BWi in terms of the following: (a) Total water content in the wall. (b) Water content in the insulation layer.
Issues related to mould formation on the wall’s inner surface emerge for both solutions, as depicted in Figure 17, with MI > 2 detected in the initial phases. Again, the risk was detected during the first steps of the simulations because the added materials still suffer from the built-in humidity level. Anyway, it is interesting to note that mould formation does not occur for 1BXi and 1BWi in the dynamic steady-state regime.
Figure 17. Mould risk formation on the internal layer for solutions 1BXi and 1BWi: yellow points for the first timesteps and darker tonalities proceeding to the end of the simulation.
Figure 18 highlights that the freezing risk occurs for case 1BWi, observing many scattered points in which the relative humidity exceeds 95% with interface temperature below 0 °C, both at the beginning and at the end of the simulation, counting 32 freeze–thaw cycles. Conversely, since it is an insulating material that is less porous and located on the inner side, 1BXi obstructs water vapour migration inside the wall, producing relative humidity lower than the threshold of 95% even in the presence of low interface temperatures. This result seems to be in contrast with the lower average value achieved by solution 1BWi (Figure 19), which leads to the achievement of a warmer wall. Nevertheless, the higher water content inside configuration 1BWi prevails over the slight increase in the layer’s temperature. Despite the technical solutions respecting the thermal transmittance constraint, case 1BXi is borderline, detecting an average thermal transmittance value of 0.275 W/m2 K (highlighted by the red traffic light in Figure 19), whereas 1BWi performs better with 0.252 W/m2 K. Also, in terms of transmittance value fluctuations, configuration 1BWi shows better performance. Indeed, the values vary between 0.293 W/m2 K and 0.203 W/m2 K, while for configuration 1BXi, the transmittance ranges from 0.322 W/m2 K to 0.224 W/m2 K.
Figure 18. Freezing risk for technical solutions 1BXi and 1BWi: yellow points for the first timesteps and darker tonalities proceeding to the end of the simulation.
Figure 19. Monthly average thermal transmittance between technical solutions 1BXi and 1BWi.

3.2. Hygrothermal Assessments for the Wall with the Internal Air Gap: Technical Solution 2

Figure 20a depicts the total water content in the technical solutions 2AXe and 2AWe; the trends are similar to those observed for solution 1, with 2AWe again showing slightly better performance. Anyway, it should be noted that the water contents are lower than those determined for 1AXe and 1AWe, and this result can be explained by the lower amount of clay in the wall, despite the two layers of hollow brick, which obstruct water storage. Figure 20b confirms the significant role of the porous material, with the water content determined in the insulation layer comparable to that of the solution 1AXe and 1AWe, with a slight difference detected only in the initial simulation phase, in which EPS reaches a higher peak; however, the drying process remains quite fast in the first spring/summer season. Again, after two years, the dynamic steady-state trend was fully achieved.
Figure 20. Comparison between technical solutions 2AXe and 2AWe in terms of the following: (a) Total water content in the wall. (b) Water content in the insulation layer.
Regarding the mould formation risk on the wall’s inner surface, as well as the freezing risk in the critical interface, the obtained results perfectly overlap those determined for cases 1AXe and 1AWe; therefore, readers can refer to Figure 5 and Figure 6.
A different situation for the dynamic thermal transmittance was detected, as shown in Figure 21. Indeed, case 2AXe offers a worse thermal transmittance, with an average value throughout the simulation of 0.262 W/m2 K, while for case 2AWe, the average thermal transmittance is 0.240 W/m2 K.
Figure 21. Monthly average thermal transmittance between technical solutions 2AXe and 2AWe.
Similarly, the variation in thermal transmittance in a dynamic steady-state regime is greater for case 2AXe, passing from 0.295 W/m2 K at the beginning of the heating period to 0.242 W/m2 K at the end of winter, with a fluctuation range of 0.053 W/m2 K. In contrast, transient results for 2AWe vary between 0.262 W/m2 K and 0.220 W/m2 K, with a difference of 0.042 W/m2 K over the year, again larger than the 0.030 W/m2 K detected for 1AWe.
When the insulation layer is located on the wall’s inner side, the obtained trends are similar to those obtained for cases 1AXi and 1AWi, as depicted in Figure 22a. Again, the minor clay material involved in solution 2 allows for determining a lower total water content when compared to solution 1. Indeed, if the latter produces peaks over 4.5 kg/m2 with rock wool, solution 2’s wall limits the value under 4 kg/m2 using the same insulation material. It is confirmed that the better breathable properties of rock wool led to a lower water content than EPS, which at the end of the heating season and with the achievement of a dynamic steady state reached almost 0.8 kg/m2 (Figure 22b), lower than the 0.92 kg/m2 obtained for cases 1AXi and 1AWi. The water content in the insulation layers does not show evident deviances from those depicted in Figure 8b, with a rapid attainment of the dynamic steady state.
Figure 22. Comparison between technical solutions 2AXi and 2AWi in terms of the following: (a) Total water content in the wall. (b) Water content in the insulation layer.
No evident deviancies have been obtained for the risk of mould formation on the wall’s inner surface, as well as for the freezing risk, which again benefits from the favourable climatic conditions despite the location of the insulation on the internal side.
Figure 23 depicts the dynamic U-values highlighting a more stable trends, in line with the results depicted in Figure 11. Anyway, case 2AXi is again borderline, with an average thermal transmittance of 0.272 W/m2 K and a yearly variation of 0.056 W/m2 K, both higher than the 0.268 W/m2 K average value and 0.016 W/m2 K variation determined for case 1AXi. Case 2AWi contains thermal losses in a better way, resulting in an average thermal transmittance of 0.247 W/m2 and maximum and minimum values of 0.272 W/m2 K and 0.230 W/m2 K, producing an annual variation larger than the 0.036 W/m2 K value calculated for case 1AWi.
Figure 23. Monthly average thermal transmittance between technical solutions 2AXi and 2AWi.
When technical solution 2 is simulated in the colder thermal zone (B), the wall’s behaviour is similar to that seen for solution 1, again with lower water contents than those measured for 1BXe and 1BWe. Rock wool continues to be the better solution, with maximum water content in the dynamic steady-state regime of 2.78 kg/m2, 7.5% lower than 1BWe (see Figure 24a). Moving on to 2BXe, the maximum water content is 3.03 kg/m2, 5.8% lower than case 1BXe. Both values are achieved at the end of the heating period, after that the built-in humidity level is dried in the first summer, with a stabilized trend reached in the second year.
Figure 24. Comparison between technical solutions 2BXe and 2BWe in terms of the following: (a) Total water content in the wall. (b) Water content in the insulation layer.
Regarding the water content in the insulation layers (Figure 24b), it can be appreciated that the greatest peak is offered by EPS, which exceeds 3 kg/m2 in the first winter, and this is due to the larger heating season characterizing location B, which allows for storing a greater quantity; conversely, rock wool seems to be insensitive to the change in the climatic context.
Again, no more evident deviations have been detected for cases 2BXe and 2BWe than in cases 1BXe and 1BWe in terms of mould formation and freezing risk; therefore, the readers can refer to the graphs of Figure 13 and Figure 14.
Regarding the dynamic thermal transmittance (Figure 25), case 2BXe offers four values greater than the thermal transmittance threshold. In particular, thermal losses are amplified at the beginning of the heating season (October) and at the end (April); nevertheless, the average thermal transmittance is 0.271 W/m2 K because of the benefits from the lower values in the coldest months. It can be noticed that the great yearly fluctuation of the calculated values, which range between a maximum of 0.322 W/m2 K and a minimum of 0.232 W/m2 K, with an annual deviation of 0.090 W/m2 K, is larger than the corresponding value determined for case 1BXe. Similar behaviour is offered by case 2BWe, which often produces thermal transmittance exceeding the limit value, but with an actual average value of 0.250 W/m2 K. The annual fluctuation remains significant, with the dynamic thermal transmittances varying between 0.308 W/m2 K and 0.213 W/m2 K.
Figure 25. Monthly average thermal transmittance between technical solutions 2BXe and 2BWe.
The final simulations concern the technical solutions 2BXi and 2BWi. Figure 26a depicts the water content attained in the walls: it can be seen that the dynamic steady-state trend is reached with more difficulty than cases 1BXi and 1BWi, with 2BWi requiring four years to stabilize the trend. Furthermore, the technical solution is majorly affected by weather data, not only for the larger peak values but also for the distance growth between the peaks, which passes from 0.776 kg/m2 for solution 1 to 1.467 kg/m2 for solution 2. This means that rock wool performs worse than EPS in severe climatic conditions when applied to the wall’s inner side.
Figure 26. Comparison between technical solutions 2BXi and 2BWi in terms of the following: (a) Total water content in the wall. (b) Water content in the insulation layer.
Regarding the water content in the insulation layers (Figure 26b), it can be appreciated that in summer, EPS reaches lower values than rock wool, which instead maintains a similar profile to that depicted in Figure 22. Again, mould formation risk occurs in the first simulation phases due to the built-in humidity levels that require an adequate time for drying, in line with the situation shown in Figure 17. Regarding the freezing risk (Figure 27), the lower water content inside the wall moves the critical zone away, resulting in scattered points with the humidity level always below 95%, even in the presence of interface temperatures lower than 0 °C, denoting a frame different to that shown in Figure 18. In particular, for the configuration with rock wool as insulation on the inner side, it is evident that, unlike technical solution 1, the risk of freezing is avoided.
Figure 27. Freezing risk for technical solutions 2BXi and 2BWi: yellow points for the first timesteps and darker tonalities proceeding to the end of the simulation.
Conversely to case 2BWi, the thermal transmittance of 2BXi is not compliant with the regulations, in light of an average value of 0.295 W/m2 K; therefore, it is over the threshold of 0.28 W/m2 K, with an annual variation that ranges between 0.345 W/m2 K (+60% of the “dry” thermal transmittance) and 0.236 W/m2 K in the dynamic steady state. Similar deviances have also been detected for case 2BWi, with dynamic values varying between 0.312 W/m2 K and 0.217 W/m2 K; anyway, this solution respects the threshold limit, providing an average thermal transmittance slightly over 0.260 W/m2 K (Figure 28).
Figure 28. Monthly average thermal transmittance between technical solutions 2BXi and 2BWi.

4. Discussion

The results clearly show that rock wool performs better than EPS when the insulation layer is located on the wall’s external side; for both of the considered technical solutions, it is insensitive to climatic conditions, providing similar water content profiles that are quite flat in the dynamic steady state, and the built-in humidity level dries after the first phase. Conversely, EPS in ETICS systems requires longer periods to dry and shows water content peaks at the end of the heating period, but reaches the dynamic steady state quickly, in both technical solutions and both climates. The allocation of the insulation layer on the wall’s inner side instead privileges the use of EPS, which benefits from a greater water vapour resistance factor. Indeed, in winter, vapour migration is from indoors to outdoors; therefore, the better breathable features of rock wool favour the water storage in the bricks, producing larger water contents. The comparison of the technical solutions suggests that the performance of EPS improves with the augmentation of the porous material mass; however, the attainment of the stabilized trend is reached only after four years. The insulation layers show a lower water content than the ETICS solutions; therefore, the insulation layer is better protected from the external forcings, increasing the material’s durability. The expected drawback due to the installation of the insulation layer on the wall’s inner side concerns mould formation. However, this issue was detected only in the initial phases, because the inner surface is still affected by the built-in humidity level, whereas mould formation was not detected in the dynamic steady state, for the two technical solutions in both climates, and the risk is independent of the typology of the insulation material.
Conversely, the freezing risk, which is avoided using ETICS solutions, occurs in severe climatic zones by renovating the wall without an air gap with an internal rock wool layer. This is due to the achievement of high relative humidity in the critical wall interface when temperatures are lower than 0 °C. Paradoxically, the wall with the internal air gap internally renovated by a rock wool layer and located in the same climatic zone does not show freezing risk: the lower water content, due to the minor porous material within the stratigraphy, allows for limiting the humidity level in the critical interface.
The results highlight that a lower water content does not imply reduced variation in the wall’s thermal transmittance; indeed, the wall with the internal air gap offers a larger modification of monthly values, especially in ETICS solutions. This means that the materials involved in the wall with an internal air gap are mainly influenced by the variation in the thermo-physical properties driven by the water content. Conversely, the insulation on the inner side produced fewer deviances, but these wall configurations do respect the thermal transmittance threshold following regulation constraints, as detected for the average thermal transmittance calculated for the wall equipped with the air gap, internally and externally insulated with EPS, and located in the severe climatic zone. The same issue was also detected for the warm climatic zone with EPS located internally, and for the wall not equipped with an air gap when located in the colder zone and renovated by an internal EPS layer. The fluctuations of the dynamic thermal transmittance are more evident in severe climates. Quantitatively, in the worst scenario, the U-value increases in climatic zone B by 0.05 W/m2 K in October, when the monthly average daily temperature is 14.1 °C: considering that for this location it takes a maximum number of 420 h to maintain the indoor temperature at the set-point of 20 °C, the U-value variation produces further transmission energy losses equal to 0.6195 kWh/m2 in the five-year simulated period.
To state the goodness of the analyzed technical solution in the considered climatic zones, Table 3 lists the maximum water content by mass reached in the hollow bricks, representing the more critical elements that could be subjected to degradation with time, which confirms the good durability in light of water contents with percentages always lower than 3%. It is worth noting that rock wool, when employed on the wall’s inner side and in the colder zone, is more solicited for durability purposes.
Table 3. The maximum water content by mass determined for all the considered cases.

5. Conclusions

A hygrothermal analysis was carried out in transient conditions by WUFI 6 on two widespread external walls adopted in the Mediterranean context to evaluate the performances of EPS and rock wool (RW) as insulation materials to renovate existing envelopes on the external and internal sides, considering opposite and humid climatic zones. The goodness of the technical solutions was evaluated by evaluating the achievement of a dynamic steady-state trend concerning the water content within the wall and in the insulation layers, the mould formation risk on the wall’s inner surface, the freezing risk and the variation in the wall’s thermal transmittance due to the change in the material’s thermo-physical features with the water content. The main findings are as follows:
  • By using EPS, the total water content is reduced when placed on the inside, as it prevents vapour infiltration into the wall. However, RW is preferred when placed on the outside, as its higher porosity allows vapour to flow outward.
  • The risks of mould formation and freezing increase by placing insulation on the inside, as, although it hinders vapour flow into the wall, the temperature of the layers decreases, thereby inhibiting the evaporation of water content and reaching dangerous humidity levels.
  • Using RW on the interior side reduces the risk of freezing in the case of a lightweight wall with an internal air gap. In contrast, when using EPS on the interior side, no significant differences are observed.
  • The water content in the RW layer is almost independent of whether the insulation is positioned inside or outside.
  • The water content inside the wall decreases when an air gap is present, as the amount of porous material in the wall is reduced, allowing for limiting the storage of water.
  • Placing the insulation on the exterior increases the thermal transmittance fluctuation around the average value over time compared to the case with insulation on the interior side.
  • For the same type and position of insulation, the thermal transmittance fluctuates less in the case of a warmer climate zone.
The results can be summarized in the following table (Table 4).
Table 4. Synoptic frame summarizing the verification results of the hygrothermal analyses (√ compliant, X non-compliant, * non-compliant only in the initial phases).
Results suggest that RW is recommended for ETICS solutions in both climates; conversely, EPS is more indicated when the wall is to be insulated on the inner side. For these cases, excluding the initial phase in which the built-in humidity level vaporizes, the analyzed technical solutions are not affected by issues related to mould formation, avoiding exploitation aimed at ventilation strategies, and the results are independent of the insulation material.
The freezing risk appears in colder climatic zones when rock wool is employed, but specifically for the technical solution in which a great quantity of porous material is involved, because this element tends to store an amount of water greater than lightweight solutions, leading to the achievement of high humidity levels in the critical interfaces. In particular, RW is always recommended in mild climatic zones and for both of the technical solutions, whereas in severe winter, RW makes the wall non-compliant with the freezing risk for the heavyweight solution. Anyway, EPS is not a valid alternative because it is true that the freezing risk is avoided, but the mould formation remains in the first phases, and exceeding of the U-value threshold limit occurs. Thereby, designers are recommended to avoid the use of rock wool for internal insulation techniques in the presence of massive walls in severe winter. Indeed, it has to be noticed that, with reference to the Italian regulations, the actual average transmittance values could not respect the limit values for building refurbishment. It emerged that, at parity of wall configuration, severe weather data lead to a wide variation in the thermal transmittance, especially when the external wall is insulated on the outer surface, producing an amplification of the thermal losses. Quantitatively, adopting EPS in an ETICS technique, the water content within the wall produces an increase of 0.6195 kWh/m2 in transmission thermal losses solely for the more favourable month of October in the coldest climatic zone. Conversely, the porous materials, which could be affected by durability issues in the presence of large water content, offer appreciable durability guarantees, in light of values always lower than 3% by mass, which allows for avoiding material strength loss, rotting and mould growth.

Author Contributions

Conceptualization, A.C. and F.N.; methodology, C.C.; software, C.C.; formal analysis, R.B.; investigation, A.C.; resources, R.B.; data curation, F.N.; writing—original draft preparation, A.C. and F.N.; writing—review and editing, C.C. and R.B.; supervision, R.B. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Data Availability Statement

The data presented in this study are available on request from the corresponding author (the data are not publicly available due to ethical restrictions).

Conflicts of Interest

The authors declare no conflicts of interest.

References

  1. Berardi, U. A cross-country comparison of the building energy consumptions and their trends. Resour. Conserv. Recycl. 2017, 123, 230–241. [Google Scholar] [CrossRef] [Scilit]
  2. D’Agostino, D.; Mazzarella, L. Data on energy consumption and Nearly zero energy buildings (NZEBs) in Europe. Data Brief 2018, 21, 2470–2474. [Google Scholar] [CrossRef] [Scilit] [PubMed]
  3. Brinkman, D. EU climate law. In Sustainable Finance and Climate Change; Edward Elgar Publishing: Northampton, MA, USA, 2024; Volume 2021, pp. 116–136. [Google Scholar] [CrossRef] [Scilit]
  4. Carpino, C.; Bruno, R.; Carpino, V.; Arcuri, N. Improve decision-making process and reduce risks in the energy retrofit of existing buildings through uncertainty and sensitivity analysis. Energy Sustain. Dev. 2022, 68, 289–307. [Google Scholar] [CrossRef] [Scilit]
  5. Carpino, C.; Bruno, R.; Arcuri, N. Social housing refurbishment for the improvement of city sustainability: Identification of targeted interventions based on a disaggregated cost-optimal approach. Sustain. Cities Soc. 2020, 60, 102223. [Google Scholar] [CrossRef] [Scilit]
  6. Bruno, R.; Bevilacqua, P. Heat and mass transfer for the U-value assessment of opaque walls in the Mediterranean climate: Energy implications. Energy 2022, 261, 124894. [Google Scholar] [CrossRef] [Scilit]
  7. Künzel, H.M.; Holm, A.; Zirkelbach, D.; Karagiozis, A.N. Simulation of indoor temperature and humidity conditions including hygrothermal interactions with the building envelope. Sol. Energy 2005, 78, 554–561. [Google Scholar] [CrossRef] [Scilit]
  8. Osanyintola, O.F.; Simonson, C.J. Moisture buffering capacity of hygroscopic building materials: Experimental facilities and energy impact. Energy Build. 2006, 38, 1270–1282. [Google Scholar] [CrossRef] [Scilit]
  9. Kong, F.; Zheng, M. Effects of combined heat and mass transfer on heating load in building drying period. Energy Build. 2008, 40, 1614–1622. [Google Scholar] [CrossRef] [Scilit]
  10. Mendes, N.; Winkelmann, F.C.; Lamberts, R.; Philippi, P.C. Moisture effects on conduction loads. Energy Build. 2003, 35, 631–644. [Google Scholar] [CrossRef] [Scilit]
  11. Barbosa, R.M.; Mendes, N. Combined simulation of central HVAC systems with a whole-building hygrothermal model. Energy Build. 2008, 40, 276–288. [Google Scholar] [CrossRef] [Scilit]
  12. Moon, H.J.; Ryu, S.H.; Kim, J.T. The effect of moisture transportation on energy efficiency and IAQ in residential buildings. Energy Build. 2014, 75, 439–446. [Google Scholar] [CrossRef] [Scilit]
  13. Liu, X.; Chen, Y.; Ge, H.; Fazio, P.; Chen, G. Numerical investigation for thermal performance of exterior walls of residential buildings with moisture transfer in hot summer and cold winter zone of China. Energy Build. 2015, 93, 259–268. [Google Scholar] [CrossRef] [Scilit]
  14. Lacasse, M.A. Durability and performance of building envelopes. In Proceedings of the BSI 2003 Conference; Springer: Berlin/Heidelberg, Germany, 2003; pp. 1–6. [Google Scholar]
  15. Fazio, P.; Mao, Q.; Ge, H.; Alturkistani, A.; Rao, J. Test Method to Measure the Relative Capacity of Wall Panels to Evacuate Moisture from Their Stud Cavity. J. Archit. Eng. 2007, 13, 194–204. [Google Scholar] [CrossRef] [Scilit]
  16. Alturkistani, A.; Fazio, P.; Rao, J.; Mao, Q. A new test method to determine the relative drying capacity of building envelope panels of various configurations. Build. Environ. 2008, 43, 2203–2215. [Google Scholar] [CrossRef] [Scilit]
  17. Ojanen, T.; Viitanen, H.; Peuhkuri, R.; Vinha, J.; Salminen, K. Mold Growth Modeling of Building Structures TO IMPROVE THE MODEL. In Proceedings of the 11th International Conference on Thermal Performance of the Exterior Envelopes of Whole Buildings, Buildings XI, Clearwater Beach, FL, USA, 5–9 December 2010. [Google Scholar]
  18. Nofal, M.; Kumaran, K. Behavior of Engineered Wood Materials Under the Effect of Wetting and Drying Cycles; National Research Council Canada: Ottawa, ON, Canada, 2014. [Google Scholar]
  19. ISO 13788:2012; Hygrothermal Performance of Building Components and Building Elements—Internal Surface Temperature to Avoid Critical Surface Humidity and Interstitial Condensation—Calculation Methods. ISO: Geneva, Switzerland, 2013.
  20. WUFI—User Manual. Available online: https://wufi.de/en/ (accessed on 8 January 2026).
  21. Sanders, C.; Baker, P.; Hermann, C. Hygrothermal assessment of wind-driven rain as a risk for internal insulation retrofit of traditional buildings. In Proceedings of the 10th Nordic Symposium on Building Physics, Lund, Sweden, 15–19 June 2014. [Google Scholar]
  22. Bruno, R.; Carpino, C.; Bevilacqua, P.; Settino, J.; Arcuri, N. A novel Stay–In–Place formwork for vertical walls in residential nZEB developed for the Mediterranean climate: Hygrothermal, energy, comfort and economic analyses. J. Build. Eng. 2022, 45, 103593. [Google Scholar] [CrossRef] [Scilit]
  23. Chae, Y.; Kim, S.H. Interstitial hygrothermal analysis for retrofitting exterior concrete wall of modern heritage building in Korea. Case Stud. Constr. Mater. 2022, 16, e00797. [Google Scholar] [CrossRef] [Scilit]
  24. O’Leary, T.P.; Menzies, G.; Duffy, A. The design of a modelling, monitoring and validation method for a solid wall structure. Energy Procedia 2015, 78, 243–248. [Google Scholar] [CrossRef] [Scilit]
  25. Fedorik, F.; Niemi, A.H. Hygrothermal assessment and design models for mass timber building envelopes in northern conditions. Eng. Struct. 2024, 305, 117714. [Google Scholar] [CrossRef] [Scilit]
  26. EN 15026; Hygrothermal Performance of Building Components and Building Elements—Assessment of Moisture Transfer by Numerical Simulation. Cen: Brussels, Belgium, 2007.
  27. EPBD. Directive (EU) 2024/1275 of the European Parliament and of the Council of 24 April 2024 on the energy performance of buildings. Off. J. Eur. Union 2024, 1275, 1–68. [Google Scholar]
  28. Italian Ministry of Economic Development. Ministerial Decree 26/06/2015, Calculation Methodologies of the Building Energy Performance and Minimum Requirements for Buildings; Ministero dello Sviluppo Economico: Rome, Italy, 2015; pp. 1–8. (In Italian) [Google Scholar]
  29. Boardman, C.R.; Glass, S.V. Improving the Accuracy of a Hygrothermal Model for Wood-Frame Walls: A Cold-Climate Study. Buildings 2020, 10, 236. [Google Scholar] [CrossRef] [Scilit]
  30. Schmidt, T. WUFI® Pro 6 Manual; Fraunhofer Institute for Building Physics IBP: Stuttgart, Germany, 2019. [Google Scholar]
  31. Fraunhofer Institute WUFI Validation. Available online: https://wufi.de/en/software/validation/ (accessed on 8 January 2026).
  32. Künzel, H.M.; Schmidt, T.; Holm, A. Exterior Surface Temperature of Different Wall Constructions Comparison of Numerical Simulation and Experiment. In Proceedings of the 11th Symposium for Building Physics, Dresden, Germany, 23–25 September 2015; Fraunhofer IRB Verlag: Stuttgart, Germany, 2015; pp. 441–449. [Google Scholar]
  33. Bilardo, M.; Giorgio, F.; Fabrizio, E.; Prizzon, F. Static vs. Dynamic Hygrothermal Simulation for Cellulose-Based Insulation in Existing Walls: A Case Study Comparison. In Proceedings of the BSA Conference 2019: Fourth Conference of IBPSA-Italy; Springer: Cham, Switzerland, 2019; pp. 181–189. [Google Scholar]
  34. Schöner, T.; Zirkelbach, D. Development of Hygrothermal Reference Years for Germany. In Proceedings of the Central European Symposium on Building Physics (CESBP), Dresden, Germany, 14–16 September 2016; pp. 133–140. [Google Scholar]
  35. Urso, A.; Evola, G.; Costanzo, V.; Nocera, F. A critical analysis on the use of different weather datasets to assess moisture-related risks in building components for a Mediterranean location. J. Build. Eng. 2023, 76, 107177. [Google Scholar] [CrossRef] [Scilit]
  36. DIN 4108-3:2024-03; Thermal Protection and Energy Economy in Buildings—Part 3: Protection Against Moisture Subject to Climate Conditions—Requirements, Calculation Methods and Directions for Planning and Construction. DIN Deutsches Institut für Normung e.V.: Berlin, Germany, 2024.
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Article Metrics

Citations

Article Access Statistics

Multiple requests from the same IP address are counted as one view.