Renovation Methods for Atrium-Style Educational Buildings Based on Thermal Environment Testing in Cold Regions of China

,
,
,
and
1
Department of Architecture, Henan University of Technology, Zhengzhou 450001, China
2
Henan Key Laboratory of Grain and Oil Storage Facility & Safety, HAUT, Zhengzhou 450001, China
3
State Key Laboratory of Subtropical Building and Urban Science, School of Architecture, South China University of Technology, Guangzhou 510640, China
4
Department of Architecture, College of Design and Engineering, National University of Singapore, Singapore 119077, Singapore

Abstract

While cold regions in China experience harsh winters, their summers also present significant overheating challenges in atrium-style buildings due to excessive solar gain. This study investigates the thermal environment of a non-ventilated atrium educational building located in a cold region of China, with tests conducted throughout the four seasons. The findings indicate that the atrium temperature is 1.7 °C, 1.1 °C, and 1.7 °C lower than that of the inner corridor during spring, autumn, and winter, respectively, but 0.6 °C higher in summer. From 7:00 a.m. to 10:00 p.m. on summer days, north-facing rooms with horizontal shading are 0.5 °C warmer than those facing south. A retrofit strategy that combines ventilated atrium shading with north-facing vertical shading is proposed, leading to a 0.7 °C reduction in atrium temperature and a 9.4% decrease in summer air conditioning energy consumption. Additionally, this study develops a retrofit framework for existing buildings, encompassing scope definition, diagnostics, strategy formulation, and evaluation to support high-quality renovations.

Article Metrics

Citations

Article Access Statistics

Multiple requests from the same IP address are counted as one view.