Principal–Slave Control Strategy for SLCC DC Interconnection System Considering Principal Station Capacity Margin

,
and
College of Electrical and Power Engineering, Hohai University, Nanjing 210098, China
*
Author to whom correspondence should be addressed.

Abstract

In flexible DC transmission and AC-DC interconnection systems, the Self-Adaption Station and Line Commutation Converter (SLCC) integrates static var compensation with conventional thyristor conversion functionality. This enables dynamic reactive power support at the valve side while improving commutation conditions, thereby enhancing the voltage support capability and operational robustness of DC systems. Under high renewable energy penetration, power fluctuations and sudden ramping challenges principal–slave controlled SLCC DC interconnection systems with a trade-off between principal-side DC voltage regulation and capacity margin constraints: Disturbance-induced active power demands may exceed available margins, causing DC voltage deviations and increasing protection trip risks. Leveraging the active/reactive decoupling characteristics of the SLCC topology, this paper proposes a principal–slave coordinated control strategy that accounts for principal station capacity margins. Methodologically, capacity margins are explicitly embedded into the principal station control mode. By reconstructing key variables in the DC voltage outer loop and introducing a closed-loop suppression mechanism with “over-capacity power” as feedback, the principal station maintains continuous voltage regulation while avoiding entry into over-capacity operation zones. On the slave side, a power support mechanism is designed to coordinate regulation among generation, storage, and load under power balance and equipment capacity constraints. This coordination process is formulated as a multi-objective optimization problem balancing disturbance economic losses with generation/storage utilization, solved using NSGA-II. Simulation results demonstrate that this strategy suppresses the risk of principle station overcapacity, enhances power sharing coordination during disturbance conditions, and improves DC voltage dynamic performance.

1. Introduction

As the global energy mix transitions toward a higher proportion of renewable energy, the volatility of power systems has significantly increased, driving a continuous rise in demand for large-scale flexible transmission technologies [1]. High-voltage direct current (HVDC) transmission remains a crucial technological pillar for future power systems due to its rapid regulation capability and decoupled active and reactive power control characteristics [2]. Among various HVDC topologies, the Self-Adaptive Station and Line Commutation Converter (SLCC) has garnered attention in recent years [3]. It achieves dynamic reactive power compensation and harmonic suppression on the valve side by introducing a cascaded H-bridge Static Var and Filter (SVF) on top of the traditional line-commutated converters (LCC).
Despite the advantages of wide bandgap devices like SiC in voltage withstand capability and thermal performance, their high manufacturing costs mean large-scale application in ultra-high voltage transmission projects remains in the developmental stage. In contrast, silicon-based IGBTs and thyristor devices benefit from mature supply chains and stable costs, with extensive operational experience accumulated in HVDC and large-capacity transmission and transformation projects. Therefore, converter technologies based on mature devices continue to hold significant importance in current engineering practice. Meanwhile, thyristor technology has not stagnated. The development of high-temperature, ultra-high-voltage SiC thyristors has expanded the operational boundaries of traditional line conversion technologies [4,5], though further engineering validation is required regarding their cost and long-term reliability [6]. Against this backdrop, hybrid topologies integrating mature LCC technology with modern power electronic devices represent a development direction that balances engineering feasibility with technological transition significance.
More importantly, the core enabling component of the SLCC is not merely the thyristor, but rather the cascaded H-bridge multilevel converter implemented with IGBTs in the SVF branch [7]. Cascaded H-bridge converters are supported by a well-established theoretical foundation in multilevel modulation, harmonic suppression, and fault-tolerant operation, and have been widely studied in STATCOM and flexible AC transmission systems [8,9]. By embedding a cascaded H-bridge SVF into an LCC-HVDC system, SLCC fundamentally improves commutation conditions, reduces transformer current stress, and enhances fault ride-through capability while preserving the high-capacity and low-loss characteristics of LCC transmission [10]. This hybrid topology bridges classical HVDC technology with modern multilevel converter theory, providing a technically robust and economically feasible solution for large-scale renewable power integration, and has been successfully implemented in the first engineering demonstration project at the Lingkou receiving station of the Yangzhou–Zhenjiang DC Transmission Phase II project, confirming its practical relevance and industrial potential.
Currently, multi-terminal DC systems predominantly adopt a principal–slave control architecture. This architecture faces severe operational challenges during high-power disturbances or significant fluctuations in renewable energy output: the principal converter station typically shoulders the core responsibility of maintaining DC voltage stability [11,12,13]. When power regulation demands exceed the principal station’s capacity limits, it can easily trigger an expansion of DC voltage deviation, potentially leading to converter lockout and shutdown, posing a serious threat to overall system safety and stability [14]. Therefore, maintaining voltage regulation capability under constrained principal station capacity has become a critical scientific issue requiring urgent resolution in this field [15,16,17].
Relevant studies indicate that SLCC demonstrates superior regulation performance compared to traditional grid-connected commutators (LCC) in scenarios with high renewable energy penetration, and holds promise for alleviating voltage regulation boundary constraints in SLCC-based DC systems caused by insufficient principal station capacity [18,19]. However, current research on SLCC primarily focuses on topological mechanisms, commutation process analysis, and local control strategy design [20,21]. Systematic exploration of the coupling mechanisms between SLCC and the principal–slave control architecture of SLCC-based DC systems remains lacking. Particularly concerning the critical issue of “how to leverage SLCC to enhance overall system regulation capability under constrained principal station capacity margins”, no unified theoretical or technical consensus has yet been established [22].
Existing literature proposes various solutions to these challenges, with some perspectives exhibiting significant divergence. One school of thought advocates mitigating power imbalance through traditional principal–slave switching, droop characteristic optimization, or secondary dispatch control mechanisms [13,23]. Another approach suggests installing additional auxiliary equipment (e.g., energy dissipation devices, dynamic reactive power compensation units) to compensate for converter station capacity deficits [24,25,26]. However, these approaches either carry risks of control delays and switching oscillations or entail high equipment investment costs. Moreover, none have thoroughly explored the synergistic control potential between multi-source dynamic devices (like SLCC) and the control architecture of DC systems based on SLCC. Consequently, there remains a lack of a coordinated control strategy that is both economically viable and engineering feasible, capable of ensuring stable system operation under principal station capacity constraints.
Based on this, the core research objective of this paper is: under the constraint of limited principal station capacity in SLCC-based DC systems, how can the multi-source dynamic compensation potential of SLCC be fully exploited to establish a stable, reliable, cost-effective, and engineering-feasible principal–slave coordinated control strategy? To achieve this goal, this paper first analyzes the dynamic response characteristics of SLCC and its adaptability in converter stations of SLCC-based DC systems from an engineering application perspective; Second, an improved control structure accounting for principal station capacity margin is established, incorporating a slave station power support strategy. Building upon this, a multi-objective optimization model is developed to achieve synergistic optimization of system economics and equipment losses. Simulation results demonstrate that the proposed control strategy not only effectively mitigates the risk of principal station overcapacity operation but also significantly enhances DC voltage stability and overall system power coordination capability.

2. Materials and Methods

2.1. SLCC Topology and Working Principle

The SLCC topology is shown in Figure 1, featuring a parallel-cascaded H-bridge SVF (Manufactured by China EPRI Science & Technology Co., Ltd., Beijing, China) between the converter transformer and the converter valves on the inverter side of the LCC-HVDC. Each phase of the SVF consists of N full-bridge submodules connected in series. Active power transmission remains under LCC control, while the SVF provides reactive power generation required for converter station operation. It generates compensating currents equal in magnitude but opposite in phase to harmonic currents, ensuring the inverter-side grid current distortion rate meets specified requirements.
Figure 1. SLCC topology diagram. The outermost dashed box contains the equivalent circuit topology of the SLCC converter station, labeled “SLCC” for clarification. The middle dashed box shows the equivalent circuit topology of the SVF, annotated as a cascaded H-bridge topology. The innermost dashed box presents the internal circuit topology of the SVF sub-module, with textual annotations indicating that each sub-module is a full-bridge configuration. An arrow adjacent to the innermost dashed box connects the sub-module’s schematic diagram to its exploded view. Symbols: uS denotes the grid voltage source; iS denotes the current flowing through the grid branch; LS denotes the internal reactance of the power source; T1 denotes a “Y-Y” transformer, while T2 denotes a “Y-Δ” type transformer. if denotes the SVF output current; iLCC denotes the current from the LCC side; Lf denotes the equivalent inductance of a DC reactor; Idc indicates direct current; Udc indicates DC voltage; Lj (j = a, b, c) indicates the equivalent inductance of each SVF phase; SMji(i = 1, 2, 3…N) indicates each sub-module per phase.
Benefiting from the complete elimination of the large AC filter yard, the total footprint of the SLCC station is significantly reduced compared to the traditional LCC scheme, achieving a high level of compactness comparable to VSC technology. Figure 2 shows the site layout drawing of the Lingkou SLCC converter station.
Figure 2. Diagram of SLCC converter station.
The steady-state circuit of the SLCC can be equivalent to a structure where the SVF voltage source is connected in parallel with the AC system voltage source [27,28], as shown in Figure 3. L s represents the sum of the converter transformer reactance and the internal reactance of the power source; L S V F denotes the bridge arm filter inductance value of the SVF; u P C C is the voltage at the PCC; u s is the grid voltage value; and u S V F is the equivalent voltage value of the SVF.
Figure 3. SLCC steady-state circuit diagram. uS denotes the grid voltage source; uSVF denotes the equivalent voltage source of the SVF; uPCC denotes the voltage at the PCC; LS denotes the sum of the converter transformer reactance and the internal reactance of the power source; LSVF denotes the bridge arm filter inductance value of the SVF; iS denotes the current flowing through the grid branch; iSVF denotes the current flowing through the SVF branch.
The equivalent model of the SLCC can be obtained using the Davenport equivalent transformation, as shown in Figure 4. In the figure, L e q represents the equivalent inductance and u e q represents the equivalent power supply. The expressions are as follows.
u e q = u s L s v g + u s v g L s L s + L s v g L e q = L s v g L s L s + L s v g
Figure 4. SLCC equivalent circuit diagram. Ueq donates the equivalent voltage source of the SLCC; Leq donates the equivalent circuit impedance of the SLCC; Ieq donates the current flowing through the equivalent branch of SLCC; uPCC denotes the voltage at the PCC.
At this point, substituting u e q and L e q into the equivalent circuit for the commutation process of the LCC enables calculation of the electrical quantities for the SLCC. The calculated electrical quantities for the SLCC are shown in Equation (2).
I d c = 3 U e q 2 ω 0 L e q cos ( α ) − cos ( α + μ e q ) μ e q = arccos cos α − 2 ω 0 L e q I d c 3 U e q − α
In the equation, U e q represents the equivalent no-load line voltage rms value on the valve side of the inverter station, I d c denotes the DC current, μ e q is the SLCC commutation overlap angle, α represents the inverter station trigger lag angle (from the natural commutation point to the thyristor trigger pulse), and ω 0 denotes the fundamental angular frequency. The newly added SVF branch reduces the composite inductance value L e q < LS of the SLCC, thereby decreasing μ e q and accelerating the commutation process. This effect is further illustrated by the AC current and voltage waveforms during commutation shown in Figure 5.
Figure 5. Waveforms of AC current and voltage during commutation. Since the time axes of the two adjacent graphs are perfectly aligned, dashed lines are used to indicate the waveform states at the same moment in both graphs. The dots here indicate the zero-crossing points of phase A power supply ua. The solid lines of different colors represent voltage and current values for each phase: yellow lines show phase A voltage/current, red lines show phase B voltage/current, and blue lines show phase C voltage/current.

2.2. SLCC Operation Control and Operating Modes

The SLCC system’s converter circuit comprises a converter transformer branch and an SVF branch, both connected in parallel to the LCC converter valves. Unlike the LCC system where valve commutation voltage is solely supplied by the AC grid, the SLCC system obtains its valve commutation voltage from both the AC grid and the SVF. This enables faster commutation, with the equivalent converter circuit’s commutation mechanism aligning with conventional DC converter circuits.
SLCC employs active-reactive decoupled control, where the LCC converter valves handle active power transmission while the SVF valves provide reactive power and perform filtering functions. Reactive power control in SLCC utilizes a combined reactive power-voltage control approach. The objective of reactive voltage control is to maintain zero reactive exchange on the converter station’s AC bus or keep the AC voltage within permissible operating limits. The DC station control system issues the required reactive power commands to the SVF. As a controlled reactive power unit, the SVF executes reactive power output commands from the DC control and protection system, participating in voltage and reactive power regulation control between the converter station and the AC grid.
The SVF control strategy primarily consists of fundamental current control and harmonic current control. The DC station control system issues reactive power commands, which are regulated through the reactive current regulator to adjust the fundamental reactive current and track the reactive power command. The fundamental active current is provided by the submodule capacitor voltage controller to compensate for active losses, stabilizing the submodule capacitor voltage at its rated value. The sum of the active and reactive components of the fundamental current serves as the fundamental current command, which is closed-loop controlled by the fundamental current controller. The SVF measures the converter transformer valve-side current, extracts the harmonic current components requiring compensation, and implements harmonic compensation through closed-loop current control by the harmonic current controller. The valve voltage command for the SVF is obtained by superimposing the outputs from the fundamental current controller and the harmonic current controller with voltage feedforward.

2.3. Basic Operating Mode of SLCC Converter Station

The operating modes of converter stations in DC interconnection systems based on SLCC can be categorized into four types: P-Q, Udc-Q, P-V, and droop. This paper focuses solely on the P-Q and Udc-Q operating modes.
The P-Q mode is the most fundamental operating mode for SLCC converter stations. In this mode, the active power reference value P r e f and reactive power reference value Q r e f are provided by the converter station’s control system. Their relationship with the phase φ between the AC-side current lagging the grid voltage is as follows.
φ = tanh Q r e f P r e f
At this point, the reference values for alternating current and circulating current on the d-axis and q-axis are respectively.
i s d _ r e f = 2 P r e f 3 u s d cos tanh Q r e f P r e f i z d _ r e f = 0 i s q _ r e f = 2 Q r e f 3 u s q sin tanh Q r e f P r e f i z q _ r e f = 0
In this context, the AC component of the circulating current is typically constrained to zero, resulting in zero dq-axis components that are independent of the converter station’s active and reactive power. The paper defines P > 0 as power output from the system, where power flows from the DC bus through the converter station to the AC feeder; P < 0 denotes power input to the system, where power flows from the AC feeder through the converter station to the DC bus.
In Udc-Q mode, the converter station controls the DC-side voltage with a reference value Udc-ref. Dual-loop control is employed, with the inner loop being the current loop and the outer loop being the DC voltage loop. The two operating modes are illustrated in Figure 6. In P-Q mode, there is no voltage outer loop, and the active power reference is directly set. In Udc-Q mode, the active power reference is generated by the voltage outer loop.
Figure 6. (a) Operating mode of converter station based on P-Q; (b) Operating mode of converter station based on Udc-Q. The arrows in the figure indicate the direction of signal flow; + indicates positive sign for signals entering the node; − indicates negative sign for signals entering the node; The dashed line is used to enclose the control block diagram of the voltage outer loop, which serves as the key distinguishing feature between (a) and (b). Dotted lines and the annotations above are used to explain the differences in Pref values between (a) and (b).

3. Principal Station Operation Mode Considering Capacity Margin

SLCC-based DC interconnection systems have garnered significant attention in recent years as an effective solution for enhancing grid stability and renewable energy integration. Due to its simplicity and reliability, principal–slave control strategies are widely adopted. However, traditional control methods face challenges in responding to sudden load increases and short-term fluctuations in renewable energy output, potentially leading to principle station overload.
To address principle station overload issues, this paper proposes a novel principal–slave control strategy. This approach incorporates the principle station’s capacity margin into its operating mode, adjusts the voltage loop structure, and adds a closed-loop suppression mechanism based on overload power. This ensures the principle station can continuously regulate the DC bus voltage.

3.1. System Constraints and Principle Station Basic Control Strategy

In DC interconnection systems based on SLCC, communication between converter stations can leverage existing fiber-optic composite overhead ground wires and the communication latency typically does not exceed 5 ms, meeting the rapid response requirements of principal–slave control. Principal–slave control generally designates one principle station operating in Udc-Q mode, with the remaining converter stations functioning as slave stations in P-Q mode. The system architecture employing principal–slave control is illustrated in Figure 7.
Figure 7. Basic architecture of the SLCC DC interconnection system. In the diagram, thick solid lines on both sides represent busbars, while thin solid lines connect circuit components. The dashed circles function similarly to those in Figure 1, illustrating from outer to inner layers: the SLCC station equivalent circuit topology, SVF equivalent circuit topology, and SVF sub-module topology. The bold arrow on the far right indicates load connection at the right SLCC converter station, with other arrows showing current flow directions during power delivery from the LCC station. ZS denotes DC line impedance, LT_high represents equivalent inductance connected to the high-voltage converter valve group transformer, and LT_low indicates equivalent inductance linked to the low-voltage converter valve group transformer. All other symbols remain consistent with those in Figure 1.
To simplify the analysis, ignoring converter station and line losses, the active power constraints for the SLCC DC interconnection system are derived from the power balance relationship between the principle station’s input power P U d c Q and the slave station’s output power P P Q i .
P U d c Q + ∑ i = 1 N P P Q i = 0
Additionally, the principle converter station must meet capacity constraints.
P U d c Q 2 + Q U d c Q 2 ≤ S U d c Q
In the formula: N denotes the number of slave stations; Q U d c Q represents the reactive power injected into the system by the principle station; S U d c Q is the capacity of the principle station. Since reactive power values are relatively small compared to active power, and reactive power has a relatively minor impact on DC bus voltage, active power is prioritized in capacity constraints for simplified analysis. Typically, the principle station possesses the largest capacity and ensures balance between system input and output power. Equation (5) can be transformed as follows.
P U d c Q = − ∑ i = 1 N P P Q i
Clearly, when P U d c Q > 0, the principle station operates in inverter mode, outputting power to the external system, defined as output power P o u t . When P U d c Q < 0, the principle station operates in rectifier mode, inputting power to the system, defined as input power P i n . Equation (3) can be transformed into Equations (8) and (9) based on the two operating modes of principle station rectification and principle station inversion, respectively:
P o u t Z = ∑ i = 1 N + P P Q i + = P U d c Q − − ∑ i = 1 N − P P Q i −
P o u t N = ∑ i = 1 N + P P Q i + + P U d c Q + = − ∑ i = 1 N − P P Q i −
In the equation: P o u t Z and P o u t N represent the output power of the principle station during rectification and inversion modes, respectively; P P Q i − denotes the power input to the system from the i-th slave station; P P Q i + denotes the power output from the system by the i-th slave station; N − and N + denote the number of slave stations inputting power to the system and outputting power from the system, respectively; P U d c Q − and P U d c Q + denote the power of the principle station in rectification and inversion modes, respectively. At this point, disregarding capacity constraints, the power required for the principle station to inject into the system can be directly derived from the output of the voltage outer loop. This power reference for the principle station, P U d c Q _ r e f , can be expressed as:
P UdcQ _ ref = K pUdcQ + K iUdcQ s U dc − U dc _ ref
In the equation, K p U d c Q and K i U d c Q represent the proportional and integral coefficients of the PI controller, respectively; s denotes the Laplace operator; and U d c _ r e f is the DC voltage reference value. When P U d c Q _ r e f > 0, the principle station outputs power to the system in inverter mode; when P U d c Q _ r e f < 0, the principle station inputs power to the system in rectifier mode. However, in practical engineering applications, the principle station’s capacity ( S U d c Q ) is finite and cannot meet all power demands. Therefore, when the power output requirement exceeds the principle station’s capacity, a principal–slave control strategy that ignores the principle station’s capacity limitations will cause system power imbalance.

3.2. Principle Station Operation Mode Considering Capacity Margin

After considering S U d c Q , the output value of the voltage outer loop changes from the principle station’s actual power injection reference P U d c Q _ r e f to the reference value P o u t _ r e f for the system’s total output power to the external AC feeder. Therefore, the voltage outer loop expressions during rectification and inversion by the principle station are rewritten from Equations (8) and (9) as follows.
P o u t _ r e f Z ≈ ∑ i = 1 N + P P Q i +
P out _ ref N ≈ ∑ i = 1 N + P PQi + + P UdcQ +
In Equations (11) and (12), since P o u t _ r e f represents the reference value for system output power, when the principle station operates in rectification mode, the sum of the power outputs from the slave stations approximates the system output power reference. When the principle station operates in inversion mode, the total output power from the slave and principle stations approximates the system output power reference. Therefore, based on the voltage outer-loop control structure, the principle station power references P U d c Q + _ r e f and P U d c Q − _ r e f for rectifier and inverter modes, respectively, can be redefined according to Equations (8), (9), (11) and (12), as shown in Equations (13) and (14).
P UdcQ − _ ref ≈ − P out _ ref − ∑ i = 1 N − P PQi − = − K pUdcQ + K iUdcQ s U dc − U dc _ ref − ∑ i = 1 N − P PQi −
P U d c Q + _ r e f ≈ P o u t _ r e f − ∑ i = 1 N + P P Q i + = K p U d c Q + K i U d c Q s U d c − U d c _ r e f − ∑ i = 1 N + P P Q i +
Additionally, to ensure the principle station always retains the capability to regulate the DC bus voltage and to prevent voltage loop output saturation from causing the principle station to degrade into constant power mode, the principle station must maintain a portion of capacity margin. Therefore, the actual power output of the principle station, P U d c Q , must also satisfy the following constraint:
| P U d c Q + | ≤ λ U d c S U d c Q | P U d c Q − | ≤ λ U d c S U d c Q
In the equation: λ U d c represents the power reference coefficient of the principle station, set at 95% in this paper to reserve a 5% power margin for the principle station, ensuring its ability to regulate the DC bus voltage. Based on the capacity margin requirement for the principle station defined by the above equation, the portion of the principle station’s power reference exceeding its capacity margin is defined as the over-capacity power Δ P U d c Q , yielding:
Δ P U d c Q = s g n ( P U d c Q ) ε ( P U d c Q P U d c Q − λ U d c S U d c Q ) × ( P U d c Q − λ U d c S U d c Q )
In the equation, sgn denotes the sign function; ε represents the step function, which determines whether the principle station power exceeds its capacity margin. If Δ P U d c Q = 0, the principle station power has not exceeded its capacity margin; if Δ P U d c Q > 0, the principle station power exceeds its capacity margin and is in inverter mode; if Δ P U d c Q < 0, the principle station power exceeds its capacity margin and is in rectifier mode. Therefore, to ensure the principle station power does not exceed its capacity margin, the over-capacity power should approach zero. This paper proposes a principle station control strategy based on an over-capacity power closed-loop. This strategy incorporates a control loop based on the over-capacity power closed-loop into the principle station control system. This loop reduces the calculated over-capacity power Δ P U d c Q to zero via a PI controller, thereby ensuring the principle station power remains within its capacity margin at all times. The principle station operating mode considering capacity margin is illustrated in Figure 8.
Figure 8. Principal operating mode with capacity margin.
As shown in Figure 8, the voltage outer-loop generates the system output power reference P o u t _ r e f , and the principle station power reference is calculated accordingly. This reference is reduced through over-capacity power constraints to fit within the principle station’s capacity margin. The final principle station power reference is then fed into the current inner-loop to complete principal–slave control. Power reference limits must not be added during operation mode, as this would cause the principle station to degrade to fixed-power mode operation, losing its ability to control the DC bus voltage.

4. Slave Station Power Support Strategy Considering the Capacity Margin of the Principle Station

4.1. Operating Modes and Constraints of the Receiving Station

In Section 3, the principle station operating mode is adjusted based on the principle station’s capacity margin. The principle station’s power output is passively adjusted based on slave station power demands. When unexpected operating conditions cause individual slave stations to generate incremental power beyond their original dispatch levels, and the dispatch mechanism cannot adjust instantly, the principle station’s power output may exceed its capacity margin, resulting in over-capacity power Δ P U d c Q . In such cases, besides reducing the principle station’s power output baseline according to the capacity margin constraints as outlined in Section 3, power support must also be coordinated from the slave stations by balancing their generation, storage, and load capacities.
Slave Stations can be categorized into bidirectional and unidirectional types based on their operational mode: Bidirectional slave stations connect to large-capacity generation and storage resources, enabling them to inject power into the system to share the principle station’s power demand in addition to drawing power. Unidirectional slave stations lack sufficient generation and storage capacity, resulting in power drawn from the system far exceeding their power injection. Within a dispatch cycle, the power variation caused by fluctuations in the station’s source-storage load can be uniformly defined as the change in the station’s power demand:
Δ P P Q _ m = Δ P G e n _ m + Δ P S t o r e _ m + Δ P U s e r _ m
In the equation, Δ P P Q _ m represents the change in power demand for the m-th slave station; Δ P G e n _ m represents the change in output of the power source (typically renewable energy equipment) connected to the m-th slave station relative to the original dispatch instruction; Δ P S t o r e _ m represents the change in power of the energy storage equipment connected to the m-th slave station relative to the original dispatch instruction; Δ P U s e r _ m represents the change in power at the load end of the AC feeder connected to the m-th slave station relative to the original dispatch instruction. The power changes of the source and storage equipment at the slave station must satisfy the following constraints.
0 ≤ Δ P G e n _ m ≤ Δ P G e n _ M a x _ m | Δ P S t o r e _ m | ≤ Δ P S t o r e _ M a x _ m
In the formula, Δ P G e n _ M a x _ m and Δ P S t o r e _ M a x _ m represent the maximum power increments that the m-th slave station’s generating and storage devices can output beyond their original dispatch command power, respectively. After determining the slave station’s operating mode, its power support method should be categorized into two power support strategies based on the principle station’s operating mode: principle station rectifier operation and inverter operation.

4.2. Slave Stations Power Support Strategy During Principle Station Rectifier Operation

During rectifier operation, the principle station injects power into the DC bus. Sudden operational conditions at the slave station—such as load surges or abrupt reductions in renewable energy output—may cause a power deficit Δ P P Q _ m relative to the original dispatch plan. Since dispatch strategies operate on extended time scales, they struggle to promptly eliminate power deficits caused by sudden events. This may lead to the principle station’s power demand exceeding its capacity margin. Therefore, rapid adjustments to the power commands of the slave station’s generation and storage equipment, or partial load shedding, are necessary to coordinate with the principle station’s power support. This aims to swiftly eliminate the power deficit caused by the unexpected condition and ensure system operational stability. Based on the principle of power conservation, the excess capacity power of the principle station and the power change of the slave station’s generation, storage, and load equipment must satisfy the following constraint equation.
Δ P U d c Q = ∑ m = 1 N ( Δ P U s e r _ m + Δ P G e n _ m + Δ P S t o r e _ m )
To swiftly eliminate power deficits caused by sudden operational conditions and ensure system stability, the optimization objective is to minimize economic losses during such events. The average unit output power of the power generation units connected to the m-th slave station is set as C G e n _ m ( t ) ; the average unit output power of energy storage devices is C S t o r e _ m ( t ) ; the average revenue per unit power input at the load end is C U s e r _ m ( t ) ; The direct economic loss from load shedding is denoted as C L o s t _ m ( t ) . To maximize power supply security at the load end, the objective is to avoid load reduction whenever possible when sufficient power is available from generation and storage resources, thereby minimizing the impact of load shedding on local production and daily life. Therefore, this objective is incorporated into the objective function, and a safety indicator coefficient ω m is defined to derive the cost minimization objective function.
min f 1 ( t ) = min ∑ m = 1 N ε Δ P U d c Q − ∑ m = 1 N Δ P G e n _ M a x _ m − ∑ m = 1 N Δ P S t o r e _ M a x _ m                       × ω m Δ P U s e r _ m C U s e r _ m ( t ) + C L o s t _ m ( t ) + Δ P G e n _ m C G e n _ m ( t ) + Δ P S t o r e _ m C S t o r e _ m ( t )            
According to Equation (18), when the power capacity of generation and storage facilities is sufficient to support the power increment during sudden load conditions, load reduction is not required, and thus load-side costs are disregarded. Only when the power capacity of generation and storage facilities is insufficient to meet the power increment demand must load reduction be implemented to ensure system power balance, at which point load-side costs are factored in.
Second, after ensuring system power balance and cost minimization, efforts should also be made to minimize operational losses in source and storage equipment. The objective is to minimize the total power consumed by source and storage devices during operation while simultaneously minimizing the combined proportion of their capacities relative to their respective slave stations. This prevents source and storage devices from operating at full load. Consequently, the objective functions f 2 ( t ) and f 3 ( t ) are established as follows. f 2 ( t ) minimizes the proportion of source and storage device losses relative to slave station capacity under principle station rectification mode, while f 3 ( t ) minimizes the total losses of source and storage devices.
min f 2 ( t ) = min ∑ m = 1 N | Δ P G e n _ m | + | Δ P S t o r e _ m | S P Q _ m min f 3 ( t ) = min ∑ m = 1 N | Δ P G e n _ m | + | Δ P S t o r e _ m |
In the equation, S P Q _ m represents the capacity of the m-th slave station. Based on the preceding discussion, considering system power balance and ensuring converter station power does not exceed its capacity margin, combined with Equations (5), (6), (15), (18) and (19), the system optimization model during rectifier operation must also satisfy the following constraints:
| P U d c Q − | ≤ λ U d c S U d c Q 0 ≤ Δ P G e n _ m ≤ Δ P G e n _ M a x _ m     m = 1,2 , ⋯ , N | Δ P S t o r e _ m | ≤ Δ P S t o r e _ M a x _ m     m = 1,2 , ⋯ , N Δ P U d c Q = ∑ m = 1 N Δ P U s e r _ m + Δ P G e n _ m + Δ P S t o r e _ m
By combining Equations (20)–(22), we obtain a multi-objective mathematical model for the SLCC DC interconnection system. This model, based on power balance during principal-station rectifier operation, minimizes costs and losses in power generation and storage equipment.

4.3. Slave Station Power Support Strategy During Principle Station Inverter Operation

When the principle station operates in inverter mode, it outputs power to the system. When the slave station experiences sudden load drops or surges in renewable energy output due to unexpected operating conditions, the system generates redundant power Δ P P Q _ m beyond the original dispatch plan. However, dispatch strategies operate on a longer time scale, making it difficult to promptly absorb this excess power generated by sudden events. This can easily cause the power input to the principle station to exceed its capacity margin. Furthermore, since load-side power demand is determined by users and cannot be actively increased, this excess power cannot be absorbed by boosting load. Instead, it requires rapid adjustments to the power output of slave-side generation and storage facilities to support the principle station. This enables swift elimination of excess power generated by unexpected events on top of the original dispatch plan, thereby ensuring system stability. According to the principle of power conservation, the excess capacity power of the principle station and the power variation of slave station sources and storage devices must satisfy the following equation constraint.
Δ P U d c Q = ∑ m = 1 N Δ P G e n _ m + Δ P S t o r e _ m
In this mode, the load-end power does not require adjustment, so load benefits, losses, and the safety factor ω m need not be considered. The cost-minimization objective function for this operating mode is:
min f 1 ( t ) = min ∑ m = 1 N Δ P G e n _ m C G e n _ m ( t ) + Δ P S t o r e _ m C S t o r e _ m ( t )
To rapidly absorb the system’s excess power, it may be necessary to reduce the output power of the station’s source equipment. Therefore, disregarding the expectation of source power adjustment, the objective functions f 2 ( t ) (minimizing the proportion of energy storage device losses relative to station capacity in inverter mode) and f 3 ( t ) (minimizing energy storage device losses) are defined as follows.
min f 2 ( t ) = min ∑ m = 1 N | Δ P S t o r e _ m | S P Q _ m min f 3 ( t ) = min ∑ m = 1 N | Δ P S t o r e _ m |
Similarly, the constraints that the system optimization model must satisfy during inverter operation can be expressed as:
| P U d c Q + | ≤ λ u d c S u d c Q 0 ≤ Δ P G e n _ m ≤ Δ P G e n _ M a x _ m     m = 1,2 , ⋯ , N | Δ P S t o r e _ m | ≤ Δ P S t o r e _ M a x _ m     m = 1,2 , ⋯ , N Δ P U d c Q = ∑ m = 1 N Δ P G e n _ m + Δ P S t o r e _ m
By combining Equations (24)–(26), we obtain a multi-objective mathematical model for the SLCC DC interconnection system. This model, based on power balance during principle station inverter operation, minimizes both costs and energy storage device losses.

4.4. Slave Station Power Support Strategy Considering Principle Station Capacity Margin

For the aforementioned multi-objective model, the core of optimization lies in coordinating the relationships among various objective functions to identify the optimal solution set that minimizes each objective function. To this end, this paper employs the NSGA-II algorithm, which can rapidly solve multi-objective problems. For details, refer to [29]. NSGA-II is applied to compute the total objective functions under rectification and inversion states, yielding optimal power variation commands for each slave station’s source-storage-load equipment under sudden load conditions, based on the existing dispatch framework. This achieves optimal power support from slave stations while ensuring the principle station’s power does not exceed its capacity margin. The power benchmark P P Q _ m _ r e f for the m-th slave station is defined as:
P P Q _ m _ r e f ≈ P U s e r _ m + P G e n _ m + P S t o r e _ m + Δ P U s e r _ m + Δ P G e n _ m + Δ P S t o r e _ m
In the equation, P U s e r _ m , P G e n _ m , and P S t o r e _ m represent the power dispatch commands for the load terminal, power source, and energy storage device connected to the m-th slave station, respectively.
After defining the optimal power support strategy for the slave station during both rectification and inversion states of the principle station, the slave station power support strategy considering the principle station’s capacity margin is shown in Figure 9. Here, P P Q _ r e f _ i n t i a l denotes the initial power reference value.
Figure 9. Slave station power support strategy considering principal station capacity margin. The arrow indicates the direction of signal inflow. The dashed box contains, from top to bottom: the “Slave Power Support Strategy Control Block Diagram with Principal Station Capacity Margin Consideration”, the “AC Current Control Block Diagram”, and the “Flow Current Control Block Diagram”. + indicates positive sign for signals entering the node; − indicates negative sign for signals entering the node; PPQ_ref_intial denotes the initial power reference value; izd represents the d-axis component of circulating current; izq represents the q-axis component of circulating current; Ucom_d denotes the d-axis component of common-mode voltage; Ucom_q denotes the q-axis component of common-mode voltage; C3/2 indicates conversion from dq two-phase to abc three-phase input mode; Upj_ref (j = a, b, c) represents the setpoint values for bridge arm voltages of phases A, B, and C. The remaining variables are explained in Figure 8. The number indicates the formula used to calculate the flowing signal, with the inflow signal to the corresponding module omitted. For example: (22) denotes the calculation using Equation (22) mentioned earlier; ? indicates determining the principal station’s operating status based on ΔPUdcQ values < 0. If ΔPUdcQ < 0, the principal station operates in rectification mode; if ΔPUdcQ > 0, it operates in rectification mode.
In the figure, the power reference for the slave station is jointly determined by the grid power demand connected to the slave station and the slave power support that accounts for the principle station’s capacity margin. When the principle station’s excess capacity Δ P U d c Q = 0, the slave power reference includes only the grid power demand component; when Δ P U d c Q ≠ 0, the power reference is adjusted using the slave power support that considers the principle station’s capacity margin.

5. Simulation Verification

To validate the feasibility and effectiveness of the proposed method, a symmetrical single-pole SLCC DC interconnection system simulation circuit model was constructed in PLECS using the Yangzhou-Zhenjiang Phase II DC project as an example. Simulations were conducted to compare the proposed method with the traditional principal-station-based capacity-limiting method described in the literature.
To visually demonstrate the structural differences between the two control strategies, we have provided the schematics of the control strategies used in our simulations and compared the power waveforms of the two strategies in Example 2 and Example 3. The control strategy schematics for both approaches are illustrated in the figure below:
In Figure 10a, the converter stations adopt the conventional multi-terminal DC operation modes. Specifically, the principal station operates in constant DC voltage control (Udc-Q mode), while the slave stations operate in constant active power control (P-Q mode).
Figure 10. Schematic comparison. (a) Traditional control; (b) principal–slave control strategy. The arrow indicates the area where the control signal corresponding to the control strategy is applied. In the two diagrams, the dashed box on the left shows the equivalent current of the principal station, while the dashed box on the right displays the equivalent circuit of the slave station. The solid boxes contain the corresponding control modules. In (a), “Udc-Q mode” and “P-Q mode” refer to the traditional principal-slave control modes mentioned in Section 2.3.
In Figure 10b, we highlight the structural integration of the capacity margin constraints. The principal station adopts the proposed principal station operation mode considering capacity margin (detailed in Figure 8 of the manuscript). Concurrently, the slave stations integrate the proposed slave station operation mode considering the capacity margin of the principle station (detailed in Figure 9).
Parameters for each converter station were configured based on relevant data from the Yangzhou-Zhenjiang Phase II DC project, as detailed in Table 1 and Table 2.
Table 1. LCC Parameters.
Table 2. SVF Parameters.

5.1. Example 1: Standard Principal–Slave Control, Without Considering Principle Station Capacity Margin

The simulation results from Example 1 indicate that under the conventional principal–slave control strategy, the SLCC principle station assumes responsibility for regulating the DC bus voltage, with its active power passively adjusted according to changes in system power demand.
As shown in Figure 11a–c, from the active and reactive power waveforms of the three stations, it can be observed that the active power of the LCC slave station and the SLCC redundant slave station consistently remained around 300 MW, indicating limited power regulation capability. The system power balance primarily relied on the principle station, which operated at near its rated capacity for active power.
Figure 11. Example 1 Waveforms. (a) Active/Reactive power response of principle station; (b) AC-side voltage and current waveforms; (c) Active/Reactive power response of slave station; (d) DC-side voltage and current waveforms; (e) Active/Reactive power response of redundant slave station; (f) SVF capacitor voltage waveform. The colored lines in (d,f) indicate that the waveform in the figure is a signal divided into three phases: A, B, and C. The red line can be considered as the A-phase waveform, the green line as the B-phase waveform, and the blue line as the C-phase waveform.
In Figure 11d, the AC-side voltage and current waveforms from the three stations reveal stable AC voltage amplitudes and continuous current waveforms across all converter stations. This indicates that conventional principal–slave control ensures basic operational stability during steady-state conditions. However, the principle station exhibits significantly higher AC-side current amplitudes than the slave stations, reflecting greater power regulation pressure.
Observation of the DC-side voltage and current waveforms in Figure 11e, reveals that the DC bus voltage generally remains near the reference value. However, during load distribution changes, the principle station exhibits larger fluctuations in DC current amplitude, indicating frequent power adjustments required to maintain system power balance.
Further analysis of the SVF capacitor voltage waveform in Figure 11f reveals that under full-load operation at the principle station, the voltage fluctuations of its SVF capacitor exhibit a large amplitude. Prolonged operation under these conditions will increase the voltage stress on the internal components of the converter, posing certain engineering operational risks.

5.2. Example 2: Considering Capacity Margin, the Principle Station Degrades to Fixed Power

In Case Study 2, a principal–slave control strategy incorporating principle station capacity margin is introduced. When the LCC slave station power increases from 300 MW to 400 MW, the SLCC principle station power remains constrained at 600 MW due to capacity margin limitations, causing the operating mode to degrade to fixed-power control. The DC voltage control task is then assumed by the SLCC redundant slave station.
As shown in Figure 12, compared with the traditional control strategy, the proposed method effectively restrains the power rise of the principal station during the sudden surge of the LCC slave station. The principal station does not continue to increase its output, thereby avoiding overload operation. Instead, the redundant slave station promptly absorbs the excess power and participates in power balancing. This coordinated power redistribution significantly suppresses power fluctuations and demonstrates the effectiveness of the capacity margin constraint and support mechanism under overload conditions.
Figure 12. Example 2 Waveforms. (a) Active/Reactive power response of principle station; (b) AC-side voltage and current waveforms; (c) Active/Reactive power response of slave station; (d) DC-side voltage and current waveforms; (e) Active/Reactive power response of redundant slave station; (f) SVF capacitor voltage waveform. The line colors in (a–c) are as indicated in the legend within the box. The yellow waveforms represent power signals from each station using traditional control methods, while the green waveforms correspond to power signals from each station employing the control method described in this paper. The colored lines in (d,f) indicate that the waveform in the figure is a signal divided into three phases: A, B, and C. The red line can be considered as the A-phase waveform, the green line as the B-phase waveform, and the blue line as the C-phase waveform.
As shown in Figure 12a–c, the AC-side voltage and current waveforms from the three stations show that despite the system mode switch, the AC-side voltages at each converter station remained stable. Current changes occurred smoothly without significant impacts, indicating excellent dynamic characteristics during the principal–slave role transition.
The DC-side voltage and current waveforms in Figure 12d reveal that when the principle station ceases direct DC voltage regulation, the redundant slave station rapidly assumes control. The DC bus voltage deviation remains minimal, ensuring stable system operation.

5.3. Example 3: Considering Capacity Margin, Principle Station Restores Voltage Control

Case Study 3 primarily verifies the reversibility and smooth recovery capability of the system operating mode under reduced power demand conditions. After the LCC slave station power decreased from 400 MW to 300 MW, the SLCC principle station regained capacity margin and switched back to DC voltage control mode, while the redundant slave station resumed fixed-power operation.
As illustrated in Figure 13, in comparison with the traditional strategy, the proposed method enables a smoother restoration process after the LCC slave station power decreases. The redundant slave station provides timely power support during the transition, effectively mitigating power oscillations. Meanwhile, the principal station gradually resumes DC voltage regulation, and the power redistribution occurs continuously without abrupt variations. This result verifies the reversibility and dynamic stability of the proposed principal–slave control strategy.
Figure 13. Example 3 Waveforms. (a) Active/Reactive power response of principle station; (b) AC-side voltage and current waveforms; (c) Active/Reactive power response of slave station; (d) DC-side voltage and current waveforms; (e) Active/Reactive power response of redundant slave station; (f) SVF capacitor voltage waveform. The line colors in (a–c) are as indicated in the legend within the box. The yellow waveforms represent power signals from each station using traditional control methods, while the green waveforms correspond to power signals from each station employing the control method described in this paper. The colored lines in (d,f) indicate that the waveform in the figure is a signal divided into three phases: A, B, and C. The red line can be considered as the A-phase waveform, the green line as the B-phase waveform, and the blue line as the C-phase waveform.
As shown in Figure 13a–c, the AC-side voltage and current waveforms from the three stations show that during the principal–slave role restoration process, the AC voltage magnitudes remained stable at each station, and current transitions were smooth. This demonstrates the robust performance of the control strategy.
The DC-side voltage and current waveforms in Figure 13d reveal that after the principle station resumed control of the DC voltage, fluctuations in the DC bus voltage further decreased, enhancing the system’s operational stability.

5.4. Example 4: Unbalanced and Three-Phase Load Variation Verification

To further evaluate the robustness of the proposed SLCC control strategy under asymmetric and severe operating conditions, additional simulations were conducted considering representative voltage sag scenarios. In order to ensure conciseness and comparability, a voltage sag level of 0.6 p.u. was selected for single-phase, two-phase, and three-phase conditions. All disturbances were initiated at t = 10 s and lasted for 3 s.
In Figure 14, under the single-phase 0.6 p.u. voltage sag condition, the AC-side voltage asymmetry reduces the effective commutation voltage of the LCC, thereby decreasing the commutation margin. However, due to the integration of the SVF, dynamic reactive power support enhances the commutation voltage. The simulation results show that no commutation failure occurred during the disturbance. Although the DC voltage experienced a moderate drop and the SVF reactive power output increased significantly, the system maintained stable power transmission throughout the fault period.
Figure 14. System waveforms under single-phase 0.6 p.u. voltage sag.
In Figure 15, under the two-phase 0.6 p.u. voltage sag condition, the reduction in line-to-line commutation voltage becomes more pronounced compared with the single-phase case. Nevertheless, the SVF continues to provide reactive compensation, supporting the commutation process. The DC voltage drop is more evident than in the single-phase scenario, and the power transmission capability is partially reduced; however, the SLCC system maintains continuous operation without triggering commutation failure.
Figure 15. System waveforms under two-phase 0.6 p.u. voltage sag.
In Figure 16, under the three-phase 0.6 p.u. voltage sag condition, the commutation voltage amplitude decreases significantly in all phases, leading to a substantial reduction in commutation margin. Temporary commutation failure occurs during the fault period, accompanied by noticeable DC voltage fluctuations. However, once the AC voltage recovers, the system rapidly restores stable operation without prolonged instability.
Figure 16. System waveforms under three-phase 0.6 p.u. voltage sag. Partial commutation failure occurred within the dashed box. The schematic diagram visually illustrates the commutation failure condition through the waveform of valve-side current. The colored lines in the waveform diagram represent the valve-side currents of three phases (A, B, and C). Specifically, the red line indicates phase A current, the green line phase indicates B current, and the blue line indicates phase C current.
Overall, the simulation results demonstrate that the integrated SVF effectively enhances the commutation support capability under asymmetric disturbances. Single-phase and two-phase voltage sags at 0.6 p.u. do not induce commutation failure, while even under severe symmetrical three-phase sag conditions, the SLCC system exhibits rapid recovery capability. These results confirm that the proposed control strategy improves not only steady-state power coordination but also operational robustness under unbalanced and symmetrical voltage disturbances.

6. Conclusions

This paper addresses the stable operation of SLCC-based DC interconnection systems under constrained principle station capacity margins. It proposes a principal–slave coordinated control strategy that accounts for principle station capacity margins, and conducts systematic analysis and simulation verification by integrating slave station power support mechanisms with SLCC engineering characteristics. Based on this research, the following conclusions are drawn.
(1) Under conventional principal–slave control, disturbances such as sudden load surges or rapid renewable-power fluctuations shift the primary regulation burden to the principal station, often driving its power beyond capacity limits and weakening DC-bus voltage regulation. The Yangzhou–Zhenjiang HVDC Phase II cases further indicate that power limiting or dispatch adjustments alone cannot simultaneously ensure stability and operational continuity under abrupt conditions.
(2) The proposed capacity-margin-aware strategy redefines the DC-voltage outer-loop control variables and introduces an over-capacity-power closed-loop suppression mechanism, enabling the principal station to maintain effective DC-bus voltage regulation under capacity constraints. Compared with degrading the principal station to fixed-power operation, it constrains principal-station power more smoothly, reduces overload risk, and better preserves overall stability.
(3) Building on the capacity-margin constraint, a slave-station power-support strategy is developed, with multi-objective optimization models for both rectifier and inverter operating states of the principal station. Coordinating slave-station generation, storage, and load-side resources alleviates the regulation burden on the principal station while satisfying power-balance and converter-capacity constraints, achieving a practical trade-off between economic efficiency and equipment losses; the Yangzhou–Zhenjiang Phase II cases also show that SLCC provides additional reactive-power support and operational flexibility, expanding the stable operating boundary and validating engineering feasibility.
Overall, the proposed principal–slave coordinated control framework accounting for principle station capacity margin enhances the operational robustness and adaptability of DC interconnection systems under high renewable energy penetration. It provides a viable technical pathway for ensuring the safe, stable, and economical operation of DC interconnection systems within new power systems.

Author Contributions

Formal analysis, C.W.; Data curation, Z.Z.; Writing—original draft, W.X. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Data Availability Statement

The original contributions presented in the study are included in the article, further inquiries can be directed to the corresponding author.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Alassi, A.; Bañales, S.; Ellabban, O.; Adam, G.; MacIver, C. HVDC Transmission: Technology Review, Market Trends and Future Outlook. Renew. Sustain. Energy Rev. 2019, 112, 530–554. [Google Scholar] [CrossRef] [Scilit]
  2. Flourentzou, N.; Agelidis, V.G.; Demetriades, G.D. VSC-Based HVDC Power Transmission Systems: An Overview. IEEE Trans. Power Electron. 2009, 24, 592–602. [Google Scholar] [CrossRef] [Scilit]
  3. Ma, W.; Wang, L.; Li, M.; Shen, X.; Wu, F.; Xu, Y. SLCC Converter Technology of UHVDC Transmission in New Power System. High Volt. Eng. 2022, 48, 4941–4948. [Google Scholar]
  4. Millan, J.; Godignon, P.; Perpiñà, X.; Pérez-Tomás, A.; Rebollo, J. A Survey of Wide Bandgap Power Semiconductor Devices. IEEE Trans. Power Electron. 2013, 29, 2155–2163. [Google Scholar] [CrossRef] [Scilit]
  5. Singh, R.; Creamer, S.; Lieser, E.; Jeliazkov, S.; Sundaresan, S. High Temperature Ultra High Voltage SiC Thyristors. Mater. Sci. Forum 2018, 924, 1662–1665. [Google Scholar] [CrossRef] [Scilit]
  6. Alatise, O.; Jahdi, S.; Gammon, P.M.; Ortiz-Gonzalez, J.; Hosseinzadehlish, M.; Floros, K.; Ludtke, I. Prospects and Challenges for SiC Power Devices in MMC-VSC-HVDC Applications. Key Eng. Mater. 2025, 1024, 39–47. [Google Scholar] [CrossRef] [Scilit]
  7. Sivapriya, A.; Kalaiarasi, N. A Review on Cascaded H-Bridge and Modular Multilevel Converter: Topologies, Modulation Technique and Comparative Analysis. In Advanced Power Electronics Converters for Future Renewable Energy Systems; CRC Press: Boca Raton, FL, USA, 2023; pp. 195–222. [Google Scholar]
  8. Xiao, Q.; Chen, L.; Jin, Y.; Mu, Y.; Cupertino, A.F.; Jia, H.; Neyshabouri, Y.; Dragičević, T.; Teodorescu, R. An Improved Fault-Tolerant Control Scheme for Cascaded H-Bridge STATCOM with Higher Attainable Balanced Line-to-Line Voltages. IEEE Trans. Ind. Electron. 2020, 68, 2784–2797. [Google Scholar] [CrossRef] [Scilit]
  9. Xie, D.; Lin, C.; Zhang, Y.; Sangwongwanich, A.; Ge, X.; Feng, X.; Wang, H. Diagnosis and Resilient Control for Multiple Sensor Faults in Cascaded H-Bridge Multilevel Converters. IEEE Trans. Power Electron. 2023, 38, 11435–11450. [Google Scholar] [CrossRef] [Scilit]
  10. Katir, H.; Abouloifa, A.; Noussi, K.; Lachkar, I.; El Aroudi, A.; Aourir, M.; El Otmani, F.; Giri, F. Fault Tolerant Backstepping Control for Double-Stage Grid-Connected Photovoltaic Systems Using Cascaded H-Bridge Multilevel Inverters. IEEE Control Syst. Lett. 2021, 6, 1406–1411. [Google Scholar] [CrossRef] [Scilit]
  11. Dewangan, L.; Bahirat, H.J. Comparison of HVDC Grid Control Strategies. In Proceedings of the 2017 IEEE PES Asia-Pacific Power and Energy Engineering Conference (APPEEC); IEEE: New York, NY, USA, 2017; pp. 1–6. [Google Scholar]
  12. Koutsoukis, N.C.; Siagkas, D.O.; Georgilakis, P.S.; Hatziargyriou, N.D. Online Reconfiguration of Active Distribution Networks for Maximum Integration of Distributed Generation. IEEE Trans. Autom. Sci. Eng. 2016, 14, 437–448. [Google Scholar] [CrossRef] [Scilit]
  13. Mei, Y.; Xie, H.; Zhou, J.; Fu, C.; Liu, H. Power Distribution Method of UHV Three-Terminal Hybrid DC System. South. Power Syst. Technol. 2020, 14, 1–5. [Google Scholar]
  14. Rehman, B.; Rehman, A.u.; Khan, W.A.; Sami, I.; Ro, J.-S. Operation and Challenges of Multi-Infeed LCC-HVDC System: Commutation Failure, AC/DC Power Flow, and Voltage Stability. Appl. Sci. 2021, 11, 8637. [Google Scholar] [CrossRef] [Scilit]
  15. Li, X.; Ma, R.; Gan, W.; Yan, S. Optimal Dispatch for Battery Energy Storage Station in Distribution Network Considering Voltage Distribution Improvement and Peak Load Shifting. J. Mod. Power Syst. Clean Energy 2020, 10, 131–139. [Google Scholar] [CrossRef] [Scilit]
  16. Meisner, D.J.; Niemann, B.; Shevchenko, M.; Fombang, E.; Khosravi, I.; von Geymüller, H. STATCOM with Active Filter Using STATCOM as Active Filter, Improving Power Quality and Reducing Harmonics. In Proceedings of the 2020 IEEE/PES Transmission and Distribution Conference and Exposition (T&D); IEEE: New York, NY, USA, 2020; pp. 1–5. [Google Scholar]
  17. Strunz, K.; Schilling, S.; Kuschke, M.; Czerwinska, A. Fast Contingency Analysis and Control for Overload Mitigation in Integrated High Voltage AC and Multi-Terminal HVDC Grids. IEEE Trans. Power Syst. 2023, 39, 5575–5590. [Google Scholar] [CrossRef] [Scilit]
  18. Jia, G.; Liu, Z.; Zhang, Z.; Chen, M.; Xu, F.; Niu, F. Research on Operation Control Strategy of Self-Adaption STATCOM and Line Commutation Converter. Proc. Chin. Soc. Electr. Eng. 2025, 45, 4843–4858. [Google Scholar]
  19. Long, H.; Sun, Y.; Zou, Y.; Wang, C. Coordinated Control Strategy of SLCC Considering the Carrying Capacity of SVF. In Proceedings of the 2025 8th International Conference on Electrical Engineering and Green Energy (CEEGE), Yangzhou, China, 4–6 July 2025; pp. 1–6. [Google Scholar]
  20. Zheng, J.; Xia, L.; Lin, S. Model and Fault Characterization Analysis of SLCC High Voltage Direct Current Transmission System (Part I): SLCC-HVDC Electromagnetic Transient Simulation Model. Power Syst. Technol. 2026; in press.
  21. Xia, L.; Liu, J.; Lin, S. Modeling and Simulation of SLCC High Voltage Direct Current Transmission System (Part II): Analysis of System Fault Characteristics. Power Syst. Technol. 2026; in press.
  22. Tavakoli, S.D.; Sánchez-Sánchez, E.; Prieto-Araujo, E.; Gomis-Bellmunt, O. DC Voltage Droop Control Design for MMC-Based Multiterminal HVDC Grids. IEEE Trans. Power Deliv. 2020, 35, 2414–2424. [Google Scholar] [CrossRef] [Scilit]
  23. Sha, G.; Liu, B.; Wu, W.; Duan, Q.; Sheng, W.; Wang, D. Hierarchical Control Strategy for Multiterminal Flexible Interconnected AC/DC Power Distribution Systems. High Volt. Eng. 2020, 46, 3509–3520. [Google Scholar]
  24. Saxena, N.K.; Mekhilef, S.; Kumar, A.; Gao, D.W. Marginal Cost-Based Reactive Power Reinforcement Using Dynamic and Static Compensators. IEEE J. Emerg. Sel. Top. Power Electron. 2022, 10, 4001–4013. [Google Scholar] [CrossRef] [Scilit]
  25. Singh, M.; Patil, D. An Operational Practice for Voltage Control & Reactive Power Management in National Grid. In Proceedings of the 2022 22nd National Power Systems Conference (NPSC), New Delhi, India, 17–19 December 2022; pp. 112–117. [Google Scholar]
  26. Li, Z.; Han, H.; Wang, H.; Feng, Q. Grid-Connected Adaptive Analysis and Control of the DC Wind Turbine under the Grid-Side Transient Faults. IEEE Access 2023, 11, 129340–129352. [Google Scholar] [CrossRef] [Scilit]
  27. Ding, R.; Deng, X.; Zhao, C.; Jia, X.; Shen, X.; Liang, C.; Guo, C. SLCC Topology and Control Strategy for Improved Commutation Process. Power Syst. Prot. Control 2024, 52, 86–94. [Google Scholar]
  28. Ye, M.; Hu, Y.; Liu, T.; Huang, L.; Zhu, Y.; Tu, L.; Shang, H.; Luo, C.; Li, J.; Su, M. Study on the Optimization of Large Capacity STATCOM and Weak Receiving-End VDCOL Coordinated Control Strategy in HVDC. South. Power Syst. Technol. 2024, 18, 1–9. [Google Scholar]
  29. Verma, S.; Pant, M.; Snasel, V. A Comprehensive Review on NSGA-II for Multi-Objective Combinatorial Optimization Problems. IEEE Access 2021, 9, 57757–57791. [Google Scholar] [CrossRef] [Scilit]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.