Ampacity Calculation Method for Overhead Conductors in High-Altitude Areas Based on Numerical Simulation

,
,
and
1
Powerchina Northwest Engineering Corporation Limited, Xi’an 710100, China
2
State Key Laboratory of Electrical Insulation and Power Equipment, School of Electrical Engineering, Xi’an Jiaotong University, Xi’an 710049, China
*
Author to whom correspondence should be addressed.

Abstract

Overhead transmission lines are critical carriers for power delivery, directly influencing the security of the power system. In high-altitude areas, special environmental conditions such as low air pressure and intense solar radiation significantly change the heat absorption and dissipation characteristics of conductors. Therefore, it is necessary to correct the overhead conductors’ ampacity in such areas to ensure safe operation. However, the ampacity calculation method and high-altitude ampacity correction coefficients proposed in existing standards have significant limitations, and there are also large errors in the calculation results. Therefore, based on the system of partial differential equations proposed in the “Guidelines for Calculating the Current-Carrying Capacity of Transmission Conductors at High Altitudes” and the suggestions for high-altitude meteorological parameter modifications from existing standards, this paper establishes a three-dimensional finite element model to study the ampacity calculation method for overhead conductors in high-altitude areas. The results show that a significant thermal shielding effect exists among bundled conductors, and meteorological condition variations significantly influence the temperature distribution of the conductors and their surrounding space. At altitudes of 4000~5000 m, the altitude correction coefficient for both twin-bundle and quad-bundle conductors is −0.06 A∙m−1 under specific conservative conditions.

1. Introduction

Due to the nonuniform spatial distribution of power generation and consumption, it is necessary to carry out high-voltage and long-distance transmission of electric energy [1]. Overhead transmission lines are the main carriers for electric energy delivery, directly related to the safety and stability of power systems. When the current through the conductor increases, the temperature of the conductor will gradually rise. If the temperature exceeds the maximum allowable operating temperature, it will cause a reduction in mechanical strength of the conductor and an increase in sag, which in turn may lead to serious accidents such as wire breakage, phase-to-phase short circuits, and fires [2,3]. Therefore, the current carried by the conductor must remain below its long-term allowable ampacity to ensure that the conductor temperature stays within the temperature limit.
Notably, meteorological conditions such as air pressure and solar radiation in high-altitude areas are significantly different from those at lower altitudes, which directly affects the heat absorption and dissipation processes of conductors and consequently changes their ampacity [4,5]. Therefore, correcting the ampacity of overhead conductors in high-altitude areas has important engineering significance.
At present, the calculation of overhead conductors’ ampacity primarily follows standards such as GB 50545, DL/T 5222, IEC TR 61579, CIGRE WG 22.12, and IEEE Std 738 [6,7,8,9,10]. GB 50545 and DL/T 5222 recommend fixed meteorological conditions such as wind speed and solar radiation for ampacity calculation, and provide comprehensive correction coefficients for the bare conductor ampacity under different altitudes and ambient temperatures [6,7]. Based on the principle of heat balance, IEC TR 61579 proposes a method to calculate the conductor ampacity under steady-state conditions, and it is applicable to different meteorological conditions and conductor types [8]. The method proposed by CIGRE WG 22.12 is similar to IEC TR 61579, but it considers the influence of altitude on air density, thereby quantifying the impact of altitude on the conductor’s ampacity [9]. IEEE Std 738 makes more detailed modifications to meteorological conditions such as solar radiation and air physical parameters, further improving the calculation accuracy [10].
However, due to the real-time changes in meteorological conditions and the diversity of conductor types, the comprehensive correction coefficients for conductor ampacity in high-altitude areas proposed in existing standards cannot be applied directly and require further correction, which has significant limitations. Additionally, the existing ampacity correction suggestions in the standards are only applicable to areas below 4000 m altitude, with no studies addressing areas in the 1000~5000 m altitude range. Furthermore, the calculation methods proposed in existing standards treat Joule heat generation, solar heat absorption, convective heat dissipation, and radiative heat dissipation of the conductor as volumetric heat sources. So, it is impossible to accurately calculate the temperature distribution of different parts of conductors and their surrounding space. Therefore, this method cannot reflect the thermal shielding effect among bundled conductors, leading to large errors in bundled conductors’ ampacity calculation.
Moreover, existing research primarily focuses on areas such as the development of new conductor materials, dynamic ampacity optimization, and intelligent monitoring technologies [11,12,13]. And research regarding the calculation errors in ampacity caused by special meteorological conditions at high altitudes and the thermal shielding effect among bundled conductors still remains limited.
In view of this, the National Energy Administration initiated the project “NB/T 11878-2025 Guidelines for Calculating the Current-Carrying Capacity of Transmission Conductors at High Altitudes”. Targeting plateau areas in the 1000~5000 m altitude range, the Guide proposes suggestions for modifying meteorological parameters and fully considers the temperature distribution of conductors and their surrounding space. It also provides a system of partial differential equations to calculate overhead conductors’ ampacity. This system can more accurately reflect the processes of conductor heat generation, absorption, and dissipation, as well as the thermal shielding effect among conductors, thereby enabling more precise calculation of overhead conductors’ ampacity in high-altitude areas.
Based on the system of partial differential equations proposed in the Guide and the suggestions for high-altitude meteorological parameter modifications provided by existing standards, this study takes the LGJ-400/50-54/7 conductor as an example and establishes a three-dimensional simulation calculation model by COMSOL Multiphysics 6.3. The finite element method is employed to solve the partial differential equations. Based on this, this study analyzes the thermal shielding effect among bundled conductors, investigates the influence of meteorological condition variations on the temperature distribution of the conductors, and corrects the ampacity of overhead conductors at 4000~5000 m altitudes.

2. Construction of Conductor Ampacity Calculation Model

2.1. Parameter Modification in High-Altitude Areas

An increase in altitude leads to enhanced solar radiation, reduced air pressure, and decreased ambient temperature, which change the heat absorption and dissipation characteristics of conductors significantly, thereby affecting conductor ampacity. Therefore, it is necessary to modify the air physical parameters and solar radiation at different altitudes.
According to IEC 60721-2-3, the relationship between the air pressure and altitude is given by [14]:
P air = P 0 ⋅ 1 − L H T 0 g / ( R L )
where Pair is the air pressure, Pa; H is the altitude, m, with H < 11,000 m. The parameters in Equation (1) are shown in Table 1.
Table 1. Modification parameters of Pair.
Based on the modified air pressure, the air density at different altitudes is obtained by using the ideal gas law:
ρ air = P air R T
where ρair is the air density, kg∙m−3; T is the temperature, K.
The decrease in ambient temperature and the heating effect of conductors on the surrounding air will also change the air physical parameters. According to IEEE Std 738 and the recommendations of the Guide, the air dynamic viscosity, thermal conductivity, and specific heat capacity at a constant pressure are modified as follows:
μ air = 1.458 × 10 − 6 × T 1.5 T + 110.4
k air = 0.02424 + 7.477 × 10 − 5 × ( T − 273.15 ) − 4.407 × 10 − 9 × ( T − 273.15 ) 2
C p , air = C 0 + C 1 ( T − 273.15 ) + C 2 ( T − 273.15 ) 2 + C 3 ( T − 273.15 ) 3 + C 4 ( T − 273.15 ) 4
where μair is the air dynamic viscosity, Pa∙s; kair is the air thermal conductivity, W∙m−1∙K−1; Cp,air is the air specific heat capacity at constant pressure, J∙kg−1∙K−1. The parameters in Equation (5) are shown in Table 2.
Table 2. Modification parameters of Cp,air.

2.2. Thermal Field Governing Equations

When the conductor delivers electrical energy, the Joule heating loss generated by the current and the heating effect of solar radiation on the conductor are the main heat sources. Since the temperature distribution in different parts of the conductor is nonuniform, heat transfers from high-temperature regions to low-temperature regions through three mechanisms: heat conduction, heat convection, and heat radiation. When the heat generation and absorption processes of the conductor reach a dynamic balance with the heat dissipation process, the temperature distribution of the conductor and its surrounding space no longer changes, achieving a steady-state temperature distribution. The heat balance equation is expressed as follows:
Q I + Q sun = Q con + Q rad
where QI is the Joule loss generation power of the conductor; Qsun is the solar heat absorption power of the conductor; Qcon is the convective heat dissipation power of the conductor; Qrad is the radiative heat dissipation power of the conductor, all with the unit of W.
The Joule loss generation of the conductor needs to consider the skin effect and the influence of conductor temperature on resistance:
Q I = k j I l o a d 2 R 0 1 − α ( T − 293.15 )
where Iload is the load current of the conductor, A; R0 is the DC resistance of the conductor at 293.15 K, Ω; α is the temperature coefficient of the conductor resistance, 0.00403 K−1; kj is the skin effect factor, a dimensionless number.
According to IEEE Std 738, the solar heat absorption power of the conductor is as follows:
Q sun = α sun ⋅ J sun ⋅ A sun ⋅ sin ( θ )
where αsun is the surface absorptivity of the conductor, a dimensionless number; Asun is the area of the conductor that receives light, m2; θ is the angle between the solar rays and the conductor axis, which is set to 90° in this study; Jsun is the direct solar radiation intensity, W∙m−2. According to GB/T 20626.3-2022, the maximum direct solar radiation intensity at different altitudes is shown in Table 3 [15].
Table 3. Maximum direct solar radiation intensity at different altitudes.
According to the Guide, heat inside the conductor transfers from high-temperature regions to low-temperature regions, and steady-state heat conduction follows Fourier’s law:
∇ ⋅ ( k wire ∇ T ) + Φ = 0
where kwire is the thermal conductivity of the conductor, W∙m−1∙K−1; Φ is the heat source power density, W∙m−3.
The convective heat dissipation process between the conductor surface and the ambient air follows the following conservation equations of mass, momentum, and energy:
ρ air ∇ ⋅ v air = 0 ρ air ( v air ⋅ ∇ ) v air = ∇ ⋅ − p air ⋅ I + μ air ( ∇ v air + ( ∇ v air ) T ) ρ air c p ,   air v air ⋅ ∇ T = ∇ ⋅ ( k air ∇ T ) + Φ
where vair is the air velocity, m∙s−1; I is the unit vector.
The radiative heat dissipation from the conductor to the ambient air follows the Stefan–Boltzmann law:
Q rad = ε ⋅ σ ⋅ ( T wire 4 − T a 4 ) ⋅ A wire
where ε is the surface emissivity of the conductor, a dimensionless number; σ is the Stefan–Boltzmann constant, with a value of 5.67 × 10−8 W∙m−2∙K−4; Twire is the surface temperature of the conductor, K; Ta is the ambient temperature, K; Awire is the surface area of the conductor, m2.

2.3. Three-Dimensional Finite Element Model

For transmission lines at 4000~5000 m altitudes, 220 kV and 330 kV conductors generally adopt a twin-bundled form, while 500 kV conductors usually use a quad-bundled form. Taking the LGJ-400/50-54/7 as an example, three-dimensional models of twin-bundled and quad-bundled transmission conductors are established, as shown in Figure 1. In the model, the length of the conductor is 2000 mm, the split spacing is 450 mm, and a cuboid is used to simulate the air domain. The dimensions of the air domain are 1800 mm × 1800 mm in the xy cross-section and 2000 mm in length. And it has been verified that this domain size is sufficiently large and will not affect the flow and thermal field around the conductors. Meanwhile, to further improve the calculation accuracy, the model refines the stranded structure on the conductor surface [16,17]. The single-conductor structure is shown in Figure 2.
Figure 1. Three-dimensional models of bundled conductors.
Figure 2. Schematic diagram of single-conductor structure.
The boundary layer mesh is applied to the conductor surface, while the remainder is meshed by free tetrahedral elements. The final mesh consists of ~3.63 million elements, with an average mesh quality of 0.8526, meeting the required computational accuracy.
The conductor physical parameters can be directly obtained from the material library, while the air physical parameters are modified according to the aforementioned method. For the boundary conditions, the inflow surface is set as the velocity inlet, the opposite outflow surface as the pressure outlet, and the remaining four side surfaces as open boundaries. For the radiation heat transfer process, the air is treated as a non-participating medium and the view factor is calculated by the hemi-cube method. Additionally, the model takes 2.5 μm as the spectral demarcation point to distinguish the solar radiation and thermal infrared radiation of the conductors.
Finally, the ampacity calculation model is established by integrating modules such as solid and fluid heat transfer, laminar flow, and surface-to-surface radiation. And a steady-state, segregated solver is employed for the simulations.
To ensure the safe and stable operation of the conductors, conservative meteorological conditions and conductor parameters are still used to calculate the conductor ampacity, as detailed in Table 4 and Table 5.
Table 4. Meteorological conditions.
Table 5. Conductor parameters.

2.4. Model Validation

To validate the reliability of the three-dimensional finite element model, systematic validation is required. However, due to the severe lack of experimental data on conductor ampacity in high-altitude areas, the validation work is mainly conducted by comparing the model’s calculation results with two recognized industry standards.
Firstly, the finite element model results are compared with the calculation method provided by IEEE Std 738. A program is developed based on the method recommended by this standard, ensuring that the air physical parameters, conductor parameters, and conservative meteorological conditions remain consistent with the finite element model. The calculation result shows that the ampacity at 4000 m altitude is 806 A. Under the same conditions, the result of the finite element model for a single conductor at 4000 m altitude is 798 A, with a relative error of ~1%, which preliminarily verifies the reliability of the finite element model. And the difference is likely because the finite element model solves the Navier–Stokes equations more accurately and refines the stranded structure on the conductor surface.
Secondly, the finite element model results are compared with the recommended values in DL/T 5222. According to DL/T 5222, when the ambient temperature is 298.15 K, the conductor ampacity at 4000 m altitude should be reduced by 11% compared to that at 1000 m. Research shows that the ampacity of the LGJ-400/50-54/7 conductor at 1000 m is 898 A [18]. At 4000 m altitude, the model’s calculated ampacity of the LGJ-400/50-54/7 conductor with different bundle configurations and the corresponding reduction ratio compared to 898 A are shown in Table 6. It can be seen that for a single conductor, the finite element model result is very close to the DL/T 5222 recommendation, further verifying the model’s reliability. For bundled conductors, the ampacity calculated by the finite element model is lower than the DL/T 5222 recommendation, indicating that the model can effectively reflect the thermal shielding effect among bundled conductors.
Table 6. Ampacity and reduction ratio compared to 898 A at 4000 m altitude.
The above comparisons show that the finite element model’s calculation result for the single conductor is consistent with recognized standards. Furthermore, the model can effectively reflect the thermal shielding effect among bundle conductors, providing a basis for subsequent ampacity correction in high-altitude areas.

3. Results and Analysis

3.1. Temperature Distribution of Conductors and Surrounding Space

Taking the quad-bundled conductor calculation results as an example, the temperature distribution characteristics of the conductors and their surrounding space are analyzed at 4000 m altitude under a load current of 786 A. The temperature distribution of the conductors’ xy cross-section (z = 100 mm) is shown in Figure 3, and the average and hotspot temperature of each conductor are presented in Table 7. Here, Conductors 1 and 2 are located on the sunward side, whereas Conductors 3 and 4 are on the shaded side. Conductors 2 and 3 are located on the upwind side, while Conductors 1 and 4 are on the downwind side. It can be seen that the temperatures of the sunward-side conductors are generally higher than those on the shaded side, and the temperatures of the downwind-side conductors are generally higher than those on the upwind side.
Figure 3. Temperature distribution of conductors’ xy cross-section (z = 100 mm).
Table 7. Temperature of each conductor (K).
The primary reason for this is that the solar direction vector is the negative y-axis. The sunward-side conductors shade those on the shaded side, so the temperatures of the sunward-side conductors are generally higher than those on the shaded side.
Meanwhile, since the wind direction is the positive x-axis, the thermal wake generated by the upwind-side conductors will affect the downwind-side ones. The convective heat flux distribution of the conductors’ xy cross-section (z = 100 mm) and the zx cross-section (y = 225 mm) are shown in Figure 4. It can be seen that the convective heat flux in the external flow region and the wake region around the downwind conductors is significantly smaller than that around the upwind ones. This indicates that the thermal wake from the upwind conductors weakens the convective heat dissipation efficiency on the downwind conductors.
Figure 4. Convective heat flux distribution of conductors’ cross-section: (a) xy cross-section (z = 100 mm); (b) zx cross-section (y = 225 mm).
This analysis reveals that among bundled conductors, both solar radiation shielding and thermal wake influence effects exist, collectively called the thermal shielding effect. Conductor 3 occupies the position with the best heat dissipation, while Conductor 1 is located at the position with the worst heat dissipation, show a hotspot temperature difference as high as 18.57 K. Therefore, the thermal shielding effect among conductors must be considered when calculating the ampacity of bundled conductors.

3.2. Influence of Meteorological Conditions on Conductor Temperature Distribution

3.2.1. Ambient Temperature

In areas at 4000~5000 m altitudes, observation data indicate that the lowest ambient temperature (Ta) is 237.15 K, while the highest can reach 313.15 K. Taking the quad-bundle conductors as an example, the study is conducted under the conditions of 4000 m altitude and a load current of 700 A. The Ta is varied across 233.15 K, 253.15 K, 273.15 K, 293.15 K, and 313.15 K to cover the full range of observed variation, thereby investigating the influence of ambient temperature on the temperature distribution of the conductors and their surrounding space. The variations in the conductors’ hotspot temperature (Tmax) with ambient temperature are shown in Table 8 and Figure 5. It can be seen that as the ambient temperature increases, the hotspot temperature of conductors increases almost linearly. This indicates that higher ambient temperatures significantly reduce the conductors’ heat dissipation efficiency.
Table 8. Variations in conductors’ hotspot temperature with ambient temperature.
Figure 5. Fitting curve for variations in conductors’ hotspot temperature with ambient temperature.

3.2.2. Wind Speed

Similarly, taking the quad-bundle conductors as an example under the conditions of 4000 m altitude and 700 A current, the wind speed is varied as 0.5 m∙s−1, 1 m∙s−1, 2 m∙s−1, 4 m∙s−1, and 8 m∙s−1 to investigate its influence on the temperature distribution of conductors and their surrounding space. To justify the selection of flow model under these wind speeds, the Reynolds numbers (Re) are calculated based on the air properties at 4000 m altitude and 298.15 K ambient temperature, as shown in Table 9. Studies indicate that the critical Re for boundary layer transition from laminar to turbulent on a single cylinder is typically on the order of 1.5 × 105. It can be seen that the calculated Re values are far below this critical value, confirming that the flow remains laminar in the region before boundary layer separation on the conductor surface.
Table 9. Variations in Re and conductors’ hotspot temperature with wind speed.
For comparison, a turbulence model is introduced at wind speeds of 2 m∙s−1 and 8 m∙s−1. The results show that the hotspot temperatures of the conductors by the turbulence model are ~1.2 K and ~3.5 K lower than those by the laminar model, with relative errors of 0.4% and 1.2%, respectively. This indicates that the laminar model yields more conservative results in conductor ampacity calculations, and the errors remain within an acceptable range for engineering calculations. Therefore, it is reasonable to employ the laminar model when studying the impact of wind speed on conductor temperature distribution and calculating ampacity under conservative conditions.
At different wind speeds, the variations in the conductors’ hotspot temperature with wind speed are shown in Table 9 and Figure 6. It can be seen that as the wind speed increases, the conductor temperature decreases almost exponentially. This indicates that the higher wind speed effectively enhances the conductors’ heat dissipation efficiency, but exhibits a saturation trend.
Figure 6. Fitting curve for variations in conductors’ hotspot temperature with wind speed.

3.2.3. Solar Direction Vector

When the solar rays are perpendicular to the conductor axis, taking the quad-bundle conductors as an example, the influence of solar direction vector variations on the temperature distribution of conductors and their surrounding space is investigated under the conditions of 4000 m altitude and 700 A current. The temperature distribution variations in the conductors’ xy cross-section (z = 100 mm) under different solar direction vectors are shown in Figure 7. It can be seen that as the solar direction changes, the temperature distribution varies slightly. The hotspot position shifts toward the sun, and the hotspot temperature shows minor variations. Generally, solar direction vector changes have a minor effect on the temperature distribution of the conductors.
Figure 7. Temperature distribution variations in conductors’ xy cross-section (z = 100 mm) under different solar direction vectors.

3.3. Ampacity Correction of Bundled Conductors at 4000~5000 m Altitudes

From the temperature distribution of the conductors and their surrounding space, it can be seen that due to the thermal shielding effect among bundled conductors, there is a significant difference in the operating temperature of each conductor. Therefore, when correcting the ampacity of bundled conductors, the conductor with the maximum temperature increase among the bundled conductors should be taken as the standard.
The maximum allowable operating temperature of the conductor is limited to 343.15 K. Through iterative calculations, the maximum allowable current is determined when the maximum hotspot temperature in the bundled conductors does not exceed 343.15 K. This current represents the conductors’ ampacity at that altitude. Subsequently, the conductors’ ampacity for areas between 4000 m and 5000 m altitude is fitted to the altitude data, yielding the altitude correction formula for conductor ampacity.
Under the conditions shown in Table 4 and Table 5, the ampacity of twin-bundle and quad-bundle LGJ-400/50-54/7 conductors at different altitudes are shown in Table 10 and Figure 8. The red horizontal line indicates the ampacity of the LGJ-400/50-54/7 conductors at 1000 m, reported as 898 A in Reference [18]. It can be seen that as the altitude increases, the conductor ampacity shows a linear decrease trend. Moreover, the ampacity of twin-bundled and quad-bundled conductors are very close at the same altitude, because the split spacing is the same, and the influence of the thermal wake from the upwind conductors on the downwind conductors is similar.
Table 10. Correction results of ampacity for bundled conductors at 4000~5000 m altitudes.
Figure 8. Fitting curve for ampacity of bundled conductors at 4000~5000 m altitudes.
Compared with the experimental data in Reference [18], the ampacity of bundled conductors decreases significantly in areas between 4000 m and 5000 m altitude. It can be seen that at 4000 m, the ampacity decreases by approximately 12.5%; at 5000 m, the reduction further increases to about 19.2%.
Subsequently, within the altitude range of 4000 m to 5000 m, the conductor ampacity is fitted to the corresponding altitude, resulting in an altitude correction formula for conductor ampacity under specific conservative conditions, as shown in Equation (12).
I = I 0 + K H H
where KH is the correction coefficient, −0.06 A∙m−1; I0 is the fitting constant, A. For the twin-bundled and quad-bundled LGJ-400/50-54/7 conductors with a split spacing of 450 mm, the values of I0 are 1024 A and 1026 A, respectively. And the mean square errors (MSE) are 0.031 and 0.011, respectively. These results indicate that the correction formula has a high fitting accuracy.

4. Discussion

This study establishes a three-dimensional finite element model to solve the system of partial differential equations for heat transfer proposed in the Guide, analyzes the thermal shielding effect among bundled conductors, and investigates the influence of meteorological condition variations on the temperature distribution of the conductors. Finally, the model is applied to correct the ampacity of bundled conductors in the altitude range of 4000 m to 5000 m.
Compared with traditional ampacity calculation methods, this model more accurately simulates the processes of heat generation, absorption, and dissipation of conductors. So, it effectively reflects the thermal shielding effect among bundled conductors and is closer to engineering practice. Furthermore, the model fully considers the environmental characteristics of high-altitude areas by modifying the air physical parameters. Under relatively conservative meteorological conditions, the ampacity correction range is extended to altitudes between 4000 m and 5000 m, providing a basis for conductor selection in high-altitude areas. Meanwhile, the model employs a parametric design, which enables rapid application to different conductor types and bundle configurations, thereby improving the ampacity correction system in high-altitude areas.
However, due to the lack of experimental research on conductor ampacity in high-altitude areas, the calculation results of this model have not yet been compared with more experimental results, so the model needs further validation. In the future, an experimental platform will be established to carry out measurements of conductor ampacity in high-altitude areas to further verify and optimize the model.
It is noted that this study reveals that meteorological condition variations significantly affect the temperature distribution of the conductors and their surrounding space, thereby influencing the conductors’ ampacity. In the future, combining this model with real-time meteorological monitoring data and machine learning algorithms can establish a conductor ampacity prediction model for high-altitude areas, ultimately realizing the efficient utilization of conductor capacity.

5. Conclusions

Based on the “NB/T 11878-2025 Guidelines for Calculating the Current-Carrying Capacity of Transmission Conductors at High Altitudes”, this paper established a finite element calculation model for overhead conductor ampacity in high-altitude areas. Then, it analyzed the temperature distribution of the conductors and surrounding space, investigated the influence of meteorological condition variations on the temperature distribution of the conductors, and corrected the conductor ampacity at 4000 m ~ 5000 m altitudes. The main conclusions are as follows:
(1)
The thermal shielding effect among bundled conductors will lead to a large temperature difference between each conductor. Therefore, when calculating the ampacity of bundled conductors, the conductor with the highest temperature should be taken as the standard.
(2)
The decrease in ambient temperature and the increase in wind speed both significantly enhance the heat dissipation efficiency of conductors, thereby affecting the ampacity. In contrast, when the solar rays are perpendicular to the conductor axis, variations in the solar direction vector have a minor influence on the temperature distribution of the conductor and its surrounding space.
(3)
Based on the variations in conductor ampacity between 4000 m and 5000 m altitude, the altitude correction method and coefficient are established under the specific conservative conditions detailed in Table 4 and Table 5. For the twin- and quad-bundled LGJ-400/50-54/7 conductors with a split spacing of 450 mm, the ampacity decreases linearly with increasing altitude and the correction coefficient is −0.06 A∙m−1. It should be noted that if the actual engineering conditions differ from this paper, the coefficient should be recalculated by the parametric model presented in this study.

Author Contributions

Methodology, J.L., W.L., H.Z. and X.L.; Validation, X.L.; Formal analysis, W.L. and H.Z.; Investigation, J.L.; Resources, J.L. and W.L.; Writing—original draft, H.Z.; Writing—review & editing, X.L.; Supervision, W.L. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Data Availability Statement

Dataset available on request from the authors.

Conflicts of Interest

Author Jia Li and Wei Liu were employed by the Powerchina Northwest Engineering Corporation Limited. The remaining authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.

References

  1. Ding, Z.W.; Zhang, X.P.; Zou, N.M.; Xiong, F.; Song, J.-Y.; Fang, X.; Wang, F.; Zhang, Y.-X. Phi-OTDR Based On-Line Monitoring of Overhead Power Transmission Line. J. Light. Technol. 2021, 39, 5163–5169. [Google Scholar] [CrossRef] [Scilit]
  2. Cui, Z.; Zhang, B.; Wang, X.; Yao, Y.; Zhou, X. Monitoring Conductor Sags for Dynamic Line Rating Based on Induced Signals in Overhead Ground Wires. IEEE Trans. Power Deliv. 2025, 40, 1289–1297. [Google Scholar] [CrossRef] [Scilit]
  3. Vejo, L.; Castro, P.; Manana, M.; Laso, A.; Lecuna, R.; Bustamante, S.; Sainz, E. Experimental Study of Dynamic Line Rating Applied to High-Temperature Low-Sag Conductors. Energies 2025, 18, 929. [Google Scholar] [CrossRef] [Scilit]
  4. Dzobo, O.; Tazvinga, H. Impact of Weather Conditions on Line Ampacity of Overhead Transmission Lines. In Proceedings of the 9th International Conference on Power Energy Systems (ICPES), Pretoria, South Africa, 2–4 December 2019; pp. 1–5. [Google Scholar] [CrossRef] [Scilit]
  5. Li, Z.Y.; Li, Q.; Lei, M.D.; Gan, Q.; Sun, Y.; Zhang, S.H. Analysis of the Effect of Multiple Environmental Factors at High Altitude on the Aging Performance of Silicone Rubber Materials. In Proceedings of the 2024 IEEE 2nd International Conference on Power Science and Technology (ICPST), Dali, China, 9–11 May 2024; pp. 442–447. [Google Scholar] [CrossRef] [Scilit]
  6. GB 50545-2010; Code for Design of 110kV~750kV Overhead Transmission Line. Ministry of Housing and Urban-Rural Development of China: Beijing, China; China Planning Press: Beijing, China, 2010.
  7. DL/T 5222-2021; Specification for Design of the Conductor and Electrical Equipment Selection. National Energy Administration: Beijing, China; China Planning Press: Beijing, China, 2021.
  8. IEC TR 61597:2021; Overhead Electrical Conductors—Calculation Methods for Stranded Bare Conductors. International Electrotechnical Commission IEC: Geneva, Switzerland, 2021.
  9. CIGRE Working Group 22.12. Thermal Behaviour of Overhead Conductors; CIGRE Technical Brochure No. 207; CIGRE: Paris, France, 2002. [Google Scholar]
  10. IEEE Std 738-2023; IEEE Standard for Calculating the Current-Temperature Relationship of Bare Overhead Conductors. IEEE Power & Energy Society: Piscataway, NJ, USA, 2023.
  11. Dai, X.; Yuan, Y.; Liao, R.; Liu, G.; Zhang, C.; Huang, H. Experimental Studies of a Novel Anti-Icing Aluminum Conductor with Excellent Durability and Improved Electrical Performance. IEEE Trans. Power Deliv. 2023, 38, 4489–4500. [Google Scholar] [CrossRef] [Scilit]
  12. Alberdi, R.; Albizu, I.; Fernandez, E.; Fernandez, R.; Bedialauneta, M.T. Overhead Line Ampacity Forecasting with a Focus on Safety. IEEE Trans. Power Deliv. 2022, 37, 329–337. [Google Scholar] [CrossRef] [Scilit]
  13. Kong, P.-Y.; Song, Y. Artificial-Neural-Network-Assisted Sensor Clustering for Robust Communication Network in IoT-Based Electricity Transmission Line Monitoring. IEEE Internet Things J. 2022, 9, 16701–16713. [Google Scholar] [CrossRef] [Scilit]
  14. IEC 60721-2-3:2013; Classification of Environmental Conditions—Part 2–3: Environmental Conditions Appearing in Nature—Air Pressure. International Electrotechnical Commission IEC: Geneva, Switzerland, 2013.
  15. GB/T 20626.3-2022; Specific Environmental Condition—Electric and Electronic Products for Plateau—Part 3: Protection Requirements of Lightning, Pollution, Condensation. State Administration for Market Regulation; China Quality Inspection Press: Beijing, China, 2022.
  16. Rahman, S.A.; Rayyan, A.A.I.; Kopsidas, K. Examining the Importance of Conductor Surface Trait on Ampacity Determination. In Proceedings of the IEEE International Conference on Power Engineering and Applications (ICPEA), Penang, Malaysia, 16–18 March 2022; pp. 1–5. [Google Scholar] [CrossRef] [Scilit]
  17. Steckiewicz, A.; Zajkowski, M.; Jovanovic, A. Potential Properties and Applications of Wires with Helical Structure in High-Voltage Overhead Power Lines and PV Systems. Energies 2025, 18, 6008. [Google Scholar] [CrossRef] [Scilit]
  18. Ministry of Water Resources and Electric Power; Northwest Electric Power Design Institute. Handbook of Electric Power Engineering Design—Primary Electrical System; China Water & Power Press: Beijing, China, 1989. [Google Scholar]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.