Skip to Content
EnergiesEnergies
  • Article
  • Open Access

11 August 2026

30 Pages

Intelligent Ensemble Learning-Based Fault Diagnosis, Location, and Protection of Series-Compensated Transmission Lines for Smart Power Grid Applications

,
,
,
and
1
Department of Electrical Engineering, Indian Institute of Technology (ISM), Dhanbad 826004, India
2
Department of Electrical Engineering, National Institute of Technology Jamshedpur (NIT Jamshedpur), Adityapur 831014, India
3
Faculty of Engineering and Science, University of Agder, 4604 Kristiansand, Norway
4
Faculty of Logistics, University of Maribor, Mariborska Cesta 7, 3000 Celje, Slovenia
This article belongs to the Section F: Electrical Engineering

Abstract

Accurate fault diagnosis and protection of series-compensated transmission lines remain challenging due to the nonlinear behavior of series capacitors and associated protective devices, which degrade the performance of conventional protection relays under varying operating conditions. To address these challenges, this paper proposes an intelligent ensemble learning-based protection framework for fault detection, fault classification, fault section identification, and fault location estimation in fixed series-compensated transmission networks. The proposed framework integrates an Artificial Neural Network (ANN) and a random subspace ensemble classifier (RSEC), where the ANN performs fault detection, classification, and location estimation, while the RSEC identifies the faulted section using a majority-weighted voting strategy. In addition, four fault indices are formulated to effectively characterize fault conditions and improve diagnostic performance. The proposed framework is evaluated on a 400 kV, 50 Hz series-compensated transmission system under diverse fault scenarios and varying operating conditions, including different fault types, fault resistances, fault locations, compensation levels, and noisy measurements. The results demonstrate an average fault detection time of 4.05 ms, 100% fault classification accuracy, 98.646% fault section identification efficiency, a mean signed fault location error of −0.02988%, and a mean absolute location error of 0.0791%, indicating negligible systematic bias and high localization accuracy. Furthermore, real-time validation using the OPAL-RT digital real-time simulator confirms the computational feasibility of the proposed framework, demonstrating its potential as a reliable, accurate, and computationally efficient solution for intelligent protection and monitoring of modern smart transmission networks.

1. Introduction

The continuous evolution of technology and its capacity to handle substantial amounts of data have propelled the integration of intelligent devices into protection systems. Aimed at achieving selective tripping and quick restoration [1], various methods have been explored in the literature for detecting, classifying, and locating abnormalities in series-compensated transmission systems [2]. Despite the advantages of increasing stability and power transfer capability, the nonlinearity induced by the MOV (Metal Oxide Varistor) and its protecting equipment imposes a challenge to the conventional relaying schemes [3,4].
Distance and differential relaying schemes have long been employed for the protection of transmission lines. However, their performance may be influenced by various parameters such as fault resistance and the behavior of series capacitors during faults. In [5], the fault impedance is computed using the relay current, based on a linearized equivalent capacitor model. In [6], the mutual impedance between the phases of a transmission line is calculated to design a new distance protection scheme. Ref. [7] utilizes an impedance index factor used to start the fault detection method in an adaptive Mho protection strategy that uses memory-polarized positive-sequence voltage. However, due to the approximate capacitor model, accurate estimation of the fault impedance remains challenging. In [8] differential protection schemes for series-compensated transmission lines are proposed, which consider current measurements from both ends of the line along with a communication channel. Synchronized phasor measurement-based protection schemes [9] and traveling-wave-based [10,11] protection schemes have been widely adopted for improved relaying performance and accurate fault location. However, these methods may fail to detect faults when the fault inception angle is zero.
In recent years, digital or numerical relays have gained widespread acceptance in power system protection, gradually replacing conventional electromechanical relays. Advances in data processing capabilities and the implementation of complex algorithms have enabled the effective deployment of numerical relays. However, these relays require the extraction and processing of large volumes of data. Consequently, signal processing techniques combined with the decision-making capabilities of artificial intelligence (AI) and machine learning (ML) tools are increasingly being utilized to develop efficient and reliable protection schemes [12,13].
First, voltage and current signals measured at the relaying bus are processed using signal processing techniques such as the Fourier Transform (FT) [14] and [15], S-Transform (ST) [16], and Wavelet Transform (WT) [17,18] to extract informative feature vectors through signal decomposition. Statistical features such as maximum, mean, and standard deviation are then obtained from the transformed signals. Finally, these features can be used for direct fault identification or provided as inputs to decision-making algorithms for reliable fault detection and classification. In the literature, AI tools such as Artificial Neural Network (ANN) [19,20] and [21], Chebyshev Neural Network (ChNN) [22], Graph Neural Network Model (GNN) [23], Adaptive Neuro-Fuzzy Inference System (ANFIS) [24,25], and Ref. [26] have been used as learning or decision-making tools. In addition, Fuzzy Logic (FL) [14], decision tree (DT) [27], and Support Vector Machine (SVM) [28] have also been employed to protect series-compensated transmission lines. However, the methods presented in the literature mainly use individual standalone classifiers to identify, categorize, and locate faults. These standalone classifiers often exhibit limitations when dealing with complex systems involving large volumes of data. This limitation motivates the use of a combination of classifiers (ensemble or hybrid) to improve decision-making performance.
To overcome the limitations of standalone classifiers, the ensemble concept has been adopted to improve classification accuracy and stability, as it reduces the probability of maloperation associated with a single classifier by combining the decisions of multiple classifiers [29]. Ensemble methods are particularly effective when combining weak classifiers such as decision trees, Naïve Bayes, and k-Nearest Neighbors. An ensemble system mainly consists of two components: methods for forming the ensemble and mechanisms for combining the outputs of individual classifiers. Techniques such as bagging, boosting, and AdaBoost are commonly used to create ensembles, while the final decision is usually obtained through voting or weighted averaging.
The literature extensively discusses the advantages of ensemble classifiers in improving the sustainability and reliability of grid protection compared with single classifiers. Ensemble models are commonly constructed using bagging [30] and boosting approaches [31,32]. A conservative OR-based ensemble fusion strategy, which combines machine learning (ML) and Deep Neural Network (DNN) classifiers, is discussed in [33]. Bagging involves generating multiple classifiers by training them on randomly sampled subsets of the original dataset. In contrast, boosting sequentially trains classifiers by updating the training data based on the errors of the previous classifier. Random subspace-based ensemble techniques, where feature subsets are selected randomly, have also been proposed to train weak learners [34]. In [35], a random subspace-based ensemble of decision trees with a majority voting strategy is proposed for decision-making. In [36], random subspace and random projection-based nearest neighbor classifiers are proposed for handling high-dimensional data. The study demonstrates that ensemble nearest neighbor classifiers using the random subspace method perform more effectively than ensembles created using bagging or boosting techniques. Furthermore, Ref. [37] discusses the construction of a hybrid KNN classifier using a random subspace ensemble approach, whereas Ref. [38] presents a method for generating feature classifier weights for each classifier based on the distance from each feature subset. Despite the implementation of several intelligent and ensemble-based protection schemes, limited attention has been given to the combined task of fault detection, fault classification, fault section identification, and exact fault location in series-compensated transmission lines.
The qualitative analysis of fault diagnosis steps available in the state of the art is briefed in Table 1, where Discrete Fourier Transform (DFT), Discrete Wavelet Transform (DWT), Least-Squares Estimation (LSE), Bagged Tree Ensemble Classifier (BTEC), and Fast Discrete Orthonormal S-Transform (FDOST) are the abbreviations used in the table. Entries related to the proposed method are listed in the last column of the table and will be discussed in the later parts of the article.
Table 1. Overview of proposed protection scheme with the existing state of the art.
In a previous study [39], an ANN-based adaptive relay system was proposed for fault diagnosis in conventional transmission lines, with particular emphasis on the adaptive diagnosis of high-impedance faults (HIFs). That work established the implementation framework for the ANN-based protection system and demonstrated its real-time feasibility using the OPAL-RT digital simulator. Although promising results were achieved, the proposed methodology was developed for conventional uncompensated transmission lines and did not consider the nonlinear transient behavior introduced by fixed series compensation. The present work builds upon this foundation by addressing the protection of fixed series-compensated transmission lines through a task-specific hybrid intelligent protection framework that integrates ANN and RSEC. The ensemble classifiers are suggested to identify the fault section due to their superiority over single-class classifiers, while trained ANNs handle the detection, classification, and location tasks. The ensemble classifier is created using a set of KNNs, as weak learners are implemented using a random subspace-based learning approach. The majority-weighted voting combination technique is applied to the individual predictions of KNN classifiers to predict the ensemble output. To determine the fault occurrence, fault type, fault section, and location, this article adapts four unique indices. The Fault Detection Index (FDI), Fault Classification Index (FCI), and Fault Location Index (FLI) are predicted by the trained ANN units, whereas RSEC estimates the Fault Section Index (FSI). The salient features of the article are summarized as follows:
  • A unified intelligent protection framework is developed for series-compensated transmission lines to perform fault detection, fault classification, fault section identification, and fault location estimation.
  • A task-specific hybrid machine learning strategy is proposed, where the ANN is employed for fault detection, fault classification, and fault location estimation, while the RSEC is utilized for fault section identification to maximize overall protection accuracy and reliability.
  • The RSEC, constructed using multiple KNN base classifiers and a majority-weighted voting strategy, enhances the robustness and accuracy of fault section identification under varying fault and operating conditions, thereby improving the reliability of subsequent fault location estimation.
  • Four fault indices (FDI, FCI, FSI, and FLI) are developed to effectively characterize fault conditions and provide reliable inputs for intelligent fault diagnosis and location estimation.
  • Comprehensive comparative studies with multiple standalone classification and regression models are performed under identical training and testing conditions to justify the selection of the ANN and RSEC for their respective protection tasks.
  • The proposed framework achieves high fault diagnosis accuracy, robust fault section identification, and precise fault location estimation while operating at a reduced sampling frequency, thereby minimizing computational burden.
  • The effectiveness and real-time feasibility of the proposed method are validated through extensive MATLAB/Simulink 2023b simulations and an OPAL-RT real-time digital simulator implementation.
The rest of the article is as follows: Section 2 presents the system model, data preparation and feature extraction steps. Section 3 describes the procedures for developing the proposed intelligent task-specific protection framework. Section 4 discusses the analytical results followed by validation results in Section 5. The findings of the study are concluded in Section 6.

2. Data Preparation and Feature Extraction

As discussed in the literature, reliable and efficient protection is essential for enhancing the security and reliability of series-compensated transmission systems. Data preparation and feature extraction play a vital role in constructing reliable training and testing datasets. The sampled phase voltage, line current, and zero-sequence current signals are pre-processed to extract discriminative feature vectors, which serve as inputs to the proposed task-specific intelligent protection framework for fault detection, fault classification, fault section identification, and fault location estimation. These features aid in distinguishing between no-fault and fault events. In addition, suitable input–target pair arguments are generated to classify and locate the fault. Figure 1 depicts a block diagram of the basic protection scheme discussed in this article. Each index block describes the state of the task in the block diagram.
Figure 1. Block diagram of the basic data-driven protection scheme.
FDI detects the fault and activates the subsequent fault diagnosis events. Fault classification, section and location are carried out by FCI, FSI, and FLI. As the series compensation sectionalizes the entire transmission line into two sections, FSI is incorporated in the block diagram to sectionalize and further locate faults effectively.

2.1. Test System Description

A 400 kV, 50 Hz transmission system shown in Figure 2 is implemented in a MATLAB/Simulink environment. The network consists of two synchronous generators connected by a 300 km transmission line. A fixed series capacitor [40] compensation is provided at the middle of the transmission line to increase the power transfer capability and stability. Since the series capacitor is susceptible to excessive overvoltages during fault conditions, a protection circuit comprising a Metal Oxide Varistor (MOV) and a spark gap is employed to ensure its safe operation. The MOV is connected in parallel with the series capacitor and begins to conduct when the capacitor voltage exceeds a predefined threshold, thereby bypassing a portion of the fault current and limiting the voltage across the capacitor. Owing to its nonlinear voltage–current characteristics, the MOV modifies the apparent impedance and transient response of the transmission line during faults, making fault detection, classification, and location more challenging for conventional protection algorithms. The series capacitor at the midpoint divides the line section into two sections, S1 and S2. The typical transmission system, generator, and load data parameters considered for simulation are illustrated in the Appendix A. Relay-A senses the voltage and current signals for each simulated fault event. These signals are sampled at a 1 kHz sampling frequency and stored for further analysis.
Figure 2. Test system under study.

2.2. Data Pre-Processing and Feature Extraction

The extracted signal samples are subsequently processed to generate the feature vectors by computing the standard deviation (S.D.) over a one-cycle moving window. During feature extraction, the moving window is updated sample by sample, allowing the extracted features to capture the dynamic transition from pre-fault to post-fault conditions. The standard deviation quantifies the dispersion of the signal samples about their mean value and effectively characterizes fault-induced disturbances. The resulting feature vectors are then supplied to the intelligent protection framework for fault diagnosis and location estimation. The standard deviation (S.D.) of a signal containing N samples within the one-cycle moving window is calculated as given by Equation (1).
S . D = ∑ i = 1 N ( x i − μ ) 2 N − 1
where xi is the value of the ith sample and μ = ∑ i = 1 N x i N is the average of the signal.

2.3. Fault Event Simulation and Dataset Preparation

Table 2 summarizes the possible combinations of the fault events simulated in sections S1 and S2. No-fault events are generated by varying the compensation level and loading by ±10%. Eleven fault categories are simulated by varying the fault location, fault resistance and fault inception angle. The terms L and G denote faults involving the corresponding line(s) and ground, respectively.
Table 2. Summary of fault events simulated on the test system.
Before training and testing, all extracted feature vectors are normalized using min–max normalization to scale each feature into the range of 0 to 1. This normalization improves numerical stability, accelerates network convergence, and prevents features with larger numerical ranges from dominating the learning process. Training data is prepared by assigning specific targets to each fault event based on the task to be performed. Testing data are used to estimate the effectiveness of the proposed scheme in analyzing the fault event. Although the parameter ranges used for training and testing are identical to ensure coverage of the operating space, no identical fault cases or duplicate samples were included in more than one dataset, and the testing dataset was used solely for the final performance evaluation. A total of seven features (F1 to F7) are computed for each case. The input features considered in this study for training the proposed ANN and ensemble units are:
  • F1, F2, F3: Standard deviation of the line-to-ground voltages of phases A, B and C respectively.
  • F4, F5, F6, F7: Standard deviation of the line currents of phases A, B, C and ground respectively.
To reduce computational complexity, the extracted features are selectively supplied to the intelligent units according to the respective protection tasks. The FDI and FCI-ANN models utilize only the four current-based features (F4 to F7), resulting in a 4 × 8 × 1 input–hidden–output architecture for FDI and a 4 × 10 × 4 architecture for FCI respectively. In contrast, the ensemble-based FSI classifier and FLI-ANN regression models utilize all seven features (F1–F7).

3. Proposed Intelligent Protection Framework

The first two stages, namely data preprocessing and feature selection, of the basic protection schemes were discussed in the earlier section. This section presents the proposed intelligent relaying scheme for performing the remaining protection tasks. The proposed framework extends our previous ANN-based protection methodology for conventional transmission lines to fixed series-compensated transmission systems by introducing a task-specific hybrid ANN–RSEC architecture together with dedicated fault indices and ensemble-based fault section identification to address the nonlinear fault dynamics introduced by series compensation. Four distinct indices are formulated in this work to indicate fault occurrence, fault type, fault section, and fault location. These indices are defined as follows:
  • FDI: Fault Detection Index [0 for no-fault event and 1 for fault event]
  • FCI: Fault Classification Index [a 4-digit binary code; e.g., 1100 represents AB fault]
  • FSI: Fault Section Index [0 for fault before the capacitor, 1 for fault after the capacitor]
  • FLI: Fault Location Index [indicates the fault location and ranges from 0 to 300 km]

3.1. Overall Protection Architecture

Figure 3 shows the flowchart of the proposed task-specific intelligent hybrid protection framework. The algorithm estimates the input features by computing the standard deviations of the sampled phase voltage, line current, and zero-sequence current signals obtained from the Potential Transformer (PT) and Current Transformer (CT) using a moving window of one cycle (20 samples at 1 kHz). During training, the moving window is shifted sample by sample to generate feature vectors containing both pre-fault and post-fault information. During online implementation, the moving window is updated continuously as new samples become available, enabling the trained models to detect faults without waiting for a complete post-fault cycle.
Figure 3. Flowchart of the proposed intelligent protection scheme.
The ANN monitors the input feature pattern in each cycle (sliding window data) to identify abnormalities and estimate the FDI. The FDI value of 1 indicates the uncertainty in the system, which subsequently activates the fault classification, section identification and fault location stages. The instant of fault detection is recorded as TD (in ms). Thereafter, the fault type is determined from the FCI response. The FCI output is considered after a delay of one cycle from the fault detection instant, and the instant is recorded as TC, where TC = TD + 20 ms.
Before estimating the fault location, the FSI obtained from a random subspace ensemble classifier is used to sectionalize the fault. Over a two-cycle observation window (40 samples) from the fault detection instant, if the ensemble output is greater than or equal to 1 for more than 20 instances (Kd ≥ 20), then the FSI indicates that the fault is in section S2; otherwise, the fault is identified in section S1. The FLI module comprises three ANN units, where only one unit is activated at any given instant based on the identified fault type, namely LG, LL/LLG, or LLL/LLLG. The corresponding trained ANN estimates the FLI, which represents the fault location. The detailed working principles of the ANN and the selection of random subspace KNN ensemble classifier are discussed in the following subsections.

3.2. ANN-Based Fault Detection, Classification and Location Estimation

The sampled attributes are used to train the ANNs through supervised learning. Gradient-based models offer the advantage of directed search in which the weights are continually updated to minimize the error. In this work, backpropagation algorithms are employed to train the ANN units. The feature vectors F1 to F7 are used as input to train the ANN units. The output layer of the ANN is assigned with FDI, FCI and FLI, for fault detection, classification and fault location, respectively. The FDI is assigned a value of 0 for a no-fault event and 1 for a fault event. The classification network consists of four neurons in the output layer representing the states of the three phases and the ground, respectively. The FCI is a 4-digit code assigned to the classifier training data; for example, 1001 denotes an AG fault. The fault locating network, a regression model, consists of a single output neuron that provides the fault location information and is represented by the FLI.
The selection of the ANN model is justified through a comparative performance evaluation with various standalone machine learning classifiers. A detailed comparison is presented in Table 3 for fault detection, classification and sectionalization and in Table 4 for fault location estimation. Since fault detection and fault classification are classification tasks, the performance of different classifiers was compared in terms of classification accuracy. The results indicate that both the ANN and the ensemble KNN classifiers achieve comparable and near-perfect classification performance. However, the ANN was selected because it provides nearly 100% classification accuracy while employing a single standalone classifier, resulting in a simpler architecture and lower computational complexity compared with the ensemble-based approach.
Table 3. Performance comparison of selected classification models for fault detection, classification and fault section estimation.
Table 4. Performance comparison of selected regression models for fault location estimation.
Fault location estimation is treated as a regression problem. Accordingly, various regression models were compared using the performance metrics Root Mean Square Error (RMSE), Mean Square Error (MSE), mean absolute error (MAE), and the coefficient of determination (R2) to identify the most suitable model for fault location estimation. An overall performance score was computed by jointly normalizing the average RMSE, MAE, and R2 values obtained for the LG, LL, and LLL fault categories and combining them into a single score ranging from 0 to 100, where a higher score indicates better overall regression performance. Lower RMSE and MAE values together with a higher R2 value indicate superior prediction accuracy. As shown in Table 4, the ANN exhibits the best overall performance, achieving the lowest average RMSE and MAE while maintaining an average R2 value close to unity.
All the results presented in Table 3 and Table 4 were obtained by training the respective models using the training dataset described in Section 2.3. During the training, each ANN model employs a sigmoidal activation function and is trained using the backpropagation learning algorithm. The weights and biases are initialized randomly before training. The maximum number of training epochs is set to 500, and training is terminated when either the Mean Square Error (MSE) reaches 1 × 10 − 5 or lower, the maximum number of training epochs is attained, or the validation checks are violated, whichever occurs first.

3.3. RSEC-Based Fault Section Identification

Conventional decision-making tools such as ANN, SVM, decision tree, and CNN use a single classifier unit for fault classification or location. With large training datasets, however, these units may become biased toward a particular decision. The human tendency to consider multiple opinions while making decisions motivates the use of a group of classifiers, known as an ensemble classifier, for solving complex problems. Ensemble classifiers have been applied in engineering systems to address numerous decision-making problems. An ensemble classifier system uses multiple classifiers, where each classifier predicts a specific class. The outputs of the individual classifiers are then aggregated and weighted to produce a final decision. In this article, a random subspace-based ensemble classifier algorithm [36] is adopted, as illustrated in Figure 4.
Figure 4. Random subspace KNN ensemble classification model.
The selection of the ensemble classifier for fault section identification is justified through a comparative performance evaluation with various standalone machine learning classifiers. The classification performance of different classifiers under diverse fault conditions is presented in Table 3, where the overall classification efficiency of each method is summarized in the final column. The results indicate that the proposed RSEC consistently achieves the highest classification accuracy, outperforming individual KNN, ANN, SVM, Linear Discriminant Analysis (LDA), and Fine Tree classifiers.
Although the ANN also demonstrates high classification accuracy, fault section identification is a critical intermediate step because any misclassification at this stage directly affects the subsequent fault location estimation. Therefore, maximizing the reliability of section identification is more important than minimizing model complexity. A random subspace ensemble classifier (RSEC) is selected to do the sectionalization task. The RSEC combines the decisions of multiple KNN base learners through a majority-weighted voting strategy, thereby reducing the influence of individual classifier errors and improving robustness under varying operating conditions. Consequently, the RSEC was selected for fault section identification because it provides the highest classification accuracy and the most reliable decision-making performance, which ultimately enhances the overall accuracy of the proposed protection framework.
Accordingly, the proposed framework adopts a task-specific model selection strategy, where the most suitable learning model is employed for each protection function to maximize overall protection accuracy and reliability.
The random subspace classifier enables the parallel processing of weak learners driven by randomly selected feature subsets. The widely used KNN classifier is selected as the weak learner. The individual feature subsets are subjected to feature weighting to improve the classification rate. This weighting helps distribute predictors more uniformly among learners compared with uniform weighting. The majority-weighted voting technique is then applied to the individual predictions of the KNN classifiers to obtain the ensemble output.
The proposed RSEC selects a subset (subspaces) of features denoted by Ns randomly from the entire feature space of dimensionality N (F1 to FN). The subset dimensionality Ns is always smaller than the complete feature space dimensionality N. After suitable weighting, each dataset is trained independently using M weak classifiers, each corresponding to an individual KNN. Each classifier predicts one among P classes based on the selected number of nearest neighbors, k. The outputs of the individual classifiers are combined through majority-weighted voting to estimate the ensemble output.
Let the decision of mth classifier (m = 1, 2…M) for detecting class C p (p = 1, 2…P) be denoted by dm,p ε {0,1}, where dm,p = 1 if the mth classifier predicts class Cp, and dm,p = 0 otherwise. According to the majority-weighted voting technique, all individual classifiers are assigned weights w m in proportion to their performance achieved during the training. The weighted average of the ensemble for predicting a class Cj (j is the class to be detected from the new data set) is given by Equation (6) [29], where the left-hand side represents the final ensemble decision, and the right-hand side returns the class C p , that receives the highest weighted vote among all classes. The final ensemble output is computed by following the steps below.
Assume an ensemble consisting of M classifiers:
H = h 1 , h 2 , .......... , h M
where each classifier predicts one class from the set of P target classes:
C = C 1 , C 2 , .......... , C P
For an input feature vector x , the prediction of the mth classifier is represented as:
h m ( x ) = C p
Binary decision function:
The binary decision function for classifier h m is defined as:
d m , p = 1       i f   h m ( x ) = c p 0       o t h e r w i s e
where d m , p indicates whether classifier m assigns the input sample to class C p .
Classifier Weight Computation:
Each classifier is assigned a normalized weight according to its validation accuracy:
w m = A c c m ∑ k = 1 M A c c k
subject to ∑ m = 1 M w m = 1
where A c c m denotes the validation accuracy of classifier h m .
Weighted Vote Aggregation:
The cumulative weighted score for class C p is computed as:
S p = ∑ m = 1 M w m d m , p
where S p represents the total weighted support received by class C p .
Final Ensemble Decision:
The final class label is determined using the Maximum Weighted Voting criterion:
C j = arg max p ∈ 1 , 2 , ...... P S p
Substituting S p , the complete majority-weighted voting of the model becomes:
C j = arg max p   ∈   1 , 2 , ...... P   ∑ m = 1 M w m d m , p
The random subspace technique depends on the feature subset size and the number of weak classifiers to improve classification performance. In this study, a random subspace KNN ensemble is used to identify the fault section by taking the voltage and current feature vectors (F1 to F7) as input. The parameters k , M , and N s were selected empirically through iterative performance evaluation. Multiple parameter combinations were investigated, and the final values were chosen based on their ability to provide the highest classification accuracy, improved robustness, and acceptable computational complexity across the considered operating conditions. Here, subspaces are formed by selecting 4 features randomly (Ns = 4) from the 7 available features (N = 7), as well as 10 weak classifiers (M = 10), with each classifier using k = 5 , are used to construct the ensemble. The majority-weighted voting technique is then employed to figure out whether the fault has occurred in section S1 or S2.

4. Results and Discussion

The response of the proposed ensemble KNN-based intelligent relay under different fault conditions is discussed in this section. The trained network structures are retained online to diagnose the simulated fault events. The index values generated by each trained network represent the characteristics of the simulated fault. These fault indices are discussed in detail, and their responses under different fault scenarios are analyzed and discussed.

4.1. Evaluation of Proposed Ensemble Assisted Intelligent Relay

The FDI and FCI are the indices obtained from the trained ANN, representing the fault that stands for the fault/no-fault event and the type of fault if detected. The FSI, the index generated from the ensemble KNN, identifies the fault section by considering the state of FCI and the feature vector. The FLI obtained from the trained ANN locates the fault for maintenance and service purposes.
To evaluate the performance of the proposed intelligent relay in both sections S1 & S2, two representative fault cases are analyzed independently. In section S1, an AG fault is simulated at 75 km from relay-A with Rf = 0 ohm, Tf = 0.4 s. Voltage and current waveforms obtained from relay-A and the measured current standard deviations are represented in Figure 5. The state of each index generated from the trained intelligent networks for the simulated case is represented in Figure 6. For effective understanding, the response ranging from nearly 0.4 to 0.45 s is shown on the right half of the figure. The time instances tf (fault inception time), td (fault detection time), tc (fault classification time) and ts (fault section instant) are calibrated for each case and represented inside the figure. The response is also recorded by simulating an AG fault in section S2 at 225 km, and the respective signals and indices are represented in Figure 7 and Figure 8 respectively. Comparing the respective indices, it is evident that the responses of FDI and FCI are insensitive to the fault section, whereas the response of FSI varies with the fault section.
Figure 5. V, I and standard deviation of current for faults initiated in section S1. (AG fault simulated at 75 km, Rf = 0 ohm, Tf = 0.4 s).
Figure 6. Performance indices of the proposed method for faults in section S1. (AG fault simulated at 75 km, Rf = 0 ohm, Tf = 0.4 s).
Figure 7. V and I and standard deviation of current for faults initiated in section S2. (AG fault simulated at 225 km, Rf = 0 ohm, Tf = 0.4 s).
Figure 8. Performance indices of the proposed method for faults in section S2. (AG fault simulated at 225 km, Rf = 0 ohm, Tf = 0.4 s).

4.1.1. Fault Detection Index

A multilayer feedforward neural network having a configuration of (4 × 8 × 1) is trained to detect the fault. The output layer of the ANN represents the FDI. For the test cases simulated, the FDI output is depicted as a subplot in Figure 6 and Figure 8. The FDI gives an active high output at 0.402 s and 0.403 s, respectively, for faults simulated in sections S1 & S2. The fault is initiated at 0.4 s, making the detection unit response times 2 ms and 3 ms. Figure 5 and Figure 7 clearly show that the standard deviation values are comparatively less for the faults in section S2. However, the proposed method detects the faults by tracking the existing pattern rather than concluding based on the magnitudes.

4.1.2. Fault Classification Index

A multilayer feedforward neural network having a configuration of (4 × 10 × 4) is trained to classify the fault. The four neurons at the output layer, each representing the state of phases A, B, C and ground, give information about the type of fault initiated. Better classification of fault evades the unnecessary tripping of healthy lines or helps to achieve selective tripping. For the test case considered, the response of FCI is shown as a subplot in Figure 6 and Figure 8, respectively, for faults in sections S1 & S2. The FCI predicts the fault accurately, as the output is 1001 at 0.422 s and 0.423 s for case-1 and for case-2 respectively, and it remains the same after that, representing an AG fault.

4.1.3. Fault Section Index

Knowing the information about the fault event and type, the next task is to identify the faulty section. Depending on the type of fault (LG, LL & LLG, LLL & LLLG) three different ensemble KNNs are trained separately to perform the task of fault section identification. For the test case simulated, the ensemble KNN representing the LG fault identifies the fault section. The response of the ensemble for a two-cycle duration from the instant of fault detection is computed and stored into the variable Kd. For each active high output, the Kd value gets aggregated.
A threshold value of 20 is fixed for Kd to differentiate the faults in section S1 from section S2. The response of FSI is shown as a subplot in Figure 6 and Figure 8 and from the figures, it is observed that the value of Kd is <20 for case-1 and Kd is ≥ 20 for case-2, where Kd is the number of active high instances within a two-cycle duration from the instant of fault detection.

4.1.4. Fault Location Index

A multilayer feedforward network(s) is trained to locate the fault in each section knowing the FDI, FCI and FSI indices. The output layer of the ANN directly depicts the fault location, represented as Fault Location Index (FLI). FCI directs the choice of the corresponding ANN unit (LG, LL/LLG, and LLL/LLLG) to locate the fault for a simulated fault event. An effective location of fault enhances reliability by minimizing the restoration time. For the test cases simulated, the values of FLI obtained are 74.5 km and 224.5 km, making the absolute location error value 0.33%. The length of the line section is considered as 150 km and 300 km during the training of ANN units for sections S1 & S2 faults respectively.
The response of the proposed FDI, FCI, FSI and FLI for selected test cases are represented in Table 5. The proposed FDI detects the fault within 10 ms as recorded in the table, and FCI can classify the fault effectively. The fault section is calibrated from the Kd value obtained from the ensemble KNN and is shown under the FSI column. The Kd value of less than 20 (fixed after observing numerous test and training data) represents the fault in section S1 and vice versa. ANN-based FLI estimates the fault location (Le) and is recorded in the table. The absolute error in locating the fault is computed using Equation (7). The absolute percentage error computed and represented under FLI comes below 1% error range.
%   E r r o r = L f − L e Length   of   the   Line   Sec tion   ∗ 100
Table 5. Response of proposed ensemble assisted intelligent relay for different fault cases.

4.2. Sensitivity Analysis of the Proposed Method for Parameter Variation

The performance of the proposed method is examined for various fault conditions by varying the fault type, location, inception and resistance. In addition, the effectiveness of the proposed algorithm is verified by changing the burden on the transmission line. The following subsections acquaint the proposed method response to the different fault conditions mentioned earlier.

4.2.1. Effect of Fault Type

The effect of fault type on the response of the proposed method is demonstrated by simulating various types of faults in sections S1 & S2 of the transmission line. Figure 9a,b show the average FDI response and the mean absolute location error obtained from FLI for each fault type, respectively. The figure shows that the proposed method achieves an average FDI response time of 4.05 ms, while the FLI estimates the fault location with a mean absolute error (MAE) of 0.0791%.
Figure 9. Effect of fault type on (a) FDI response time and (b) FLI location estimation.
Table 6 summarizes the response of the proposed algorithm to the selected fault type while keeping the remaining parameters constant. The table demonstrates that the proposed method can detect, classify, and locate faults effectively regardless of fault type. The FCI and FSI responses are computed and are observed to be sensitive to parameter variations.
Table 6. Effect of fault type on the performance of the proposed method.

4.2.2. Effect of Fault Location

To comprehensively evaluate the effect of fault location on the proposed algorithm, various fault events are simulated at each test location by varying the fault resistance and fault inception angle for each fault type. Figure 10a depicts the average FDI response for each fault type (BG, AB, BCG, and ABC) versus fault location. According to the figure, the maximum FDI response time is less than 10 ms. At 150 km, two instances indicate the fault just before and after the series capacitor. With increasing fault location, the average FDI response is observed to increase. Figure 10b depicts the MAE value obtained from the FLI response. It shows that the suggested method can locate the faults efficiently along the entire line length.
Figure 10. Fault location vs. (a) average FDI response and (b) mean absolute location error of FLI.
Table 7 lists the responses of the proposed method for faults (BG, AB, BCG, and ABC) simulated at 90, 180, and 270 km with the remaining parameters held constant. The FDI and FCI can detect and classify the fault accurately over the line length. The FSI is identified by estimating the Kd obtained from the ensemble KNN. If Kd is greater than 20, the fault is in section S2, and vice versa. The prediction made from the FSI directs the selection of the FLI unit to locate the fault. The FLI response is recorded for the said cases, and the calibrated MAE value is shown in the last column of the table.
Table 7. Effect of fault location on the performance of the proposed algorithm.

4.2.3. Effect of Fault Inception

This section explores the impact of fault inception on the performance of the proposed method in detecting and locating the fault. Case studies are conducted at each fault inception while keeping the remaining fault parameters constant. Figure 11a depicts the mean FDI response against fault inception. The FDI response for each fault type is the same for faults generated at peak voltage magnitude (72°, 108°) and at near zero voltage magnitude (0°, 180°). Figure 11b demonstrates that regardless of the inception of the fault, the FLI locates the faults with minimal variation in error.
Figure 11. Fault inception vs. (a) mean FDI response and (b) mean absolute location error of FLI.
To further understand the working of the proposed method with fault inception, a few scenarios have been listed in Table 8. It demonstrates that the proposed FDI, FCI, FSI, and FLI can diagnose the faults while being less sensitive to fault initiation. Regardless of the fault inception, the value of Kd is always less than 20 for faults initiated at 60 km. FLI locates the fault with less error for variations in fault inception. These discussions prove that the DC-offset has less impact on the proposed algorithm.
Table 8. Effect of fault inception on the performance of the proposed algorithm.

4.2.4. Effect of Fault Resistance

High resistance along the fault path adversely impacts the decision of the conventional relaying methods. The suggested strategy can counteract this effect by selecting adequate data to train the network effectively. Figure 12a,b demonstrate the responses of FDI and FLI, respectively, when the fault resistance value is adjusted between 0 and 200 ohms in increments of 40 ohms. For LL and LLL faults, the resistance varies in steps of 10 from 0 to 50 ohms. These figures show that the proposed methodology can identify and locate high-resistance faults. Table 9 shows the proposed method responses to variations in fault resistance. The FDI reacts in about 2 to 3 ms for the recorded cases. The FCI classifies the fault effectively during low- and high-resistant faults. For faults initiated at 60 km, the progressive Kd value during the two-cycle duration increases slightly (but <20) with the increase in fault resistance. The FSI accurately estimates the fault section as S1. The FLI efficiently locates high-resistance faults, hence improving the overall efficiency of the proposed method.
Figure 12. Fault resistance vs. (a) mean FDI response and (b) mean absolute location error of FLI.
Table 9. Effect of fault resistance on the performance of the proposed algorithm.

4.2.5. Effect of Arcing Faults

To evaluate the effect of arcing faults on the proposed method, a high-impedance fault (HIF) model is implemented, as shown in Figure 13. The model consists of two antiparallel DC sources ( V p and V n ) connected through diodes and resistances to stand for the nonlinear and arcing characteristics of HIFs near the zero-crossing region. Current flows when the phase voltage exceeds the threshold voltages, while no current flows within the range V n < V p h < V p . The values of V p and V n   are selected based on the transmission line phase voltage.
Figure 13. High-impedance fault (HIF) model.
The performance of the proposed algorithm under HIF conditions is evaluated by simulating an AG fault at 225 km initiated at 0.4 s, with R p and R n set to 100 Ω . The response shown in Figure 14 shows that the proposed method effectively oversees the nonlinear behavior associated with arcing faults. The FDU detects the fault within 11 ms, while the FCU finds the fault type as AG (1001). The estimated K d value is greater than 20, indicating that the fault is in section S2. In addition, the FLU estimates the fault location at 228.63 km, resulting in a mean absolute fault location error of 1.21%.
Figure 14. Response of the proposed method for arcing (HIF) faults.

4.2.6. Effect of Transducer Errors

In practical power system environments, transducer errors may arise due to sensor inaccuracies, electromagnetic interference, saturation effects, thermal drift, quantization errors in A/D converters, and communication disturbances. The presence of such inaccuracies could introduce some distortions into the acquired signals, thus compromising the process of feature extraction and fault detection. Furthermore, the presence of noise in the measurements could lead to relay mal-operation and delay in fault detection.
The robustness of the proposed algorithm against transducer and A/D conversion errors is evaluated by adding 20 dB SNR (signal-to-noise ratio) noise to the original signals, and the corresponding response is shown in Figure 15. The results correspond to an AG fault simulated at 75 km from relay-A, initiated at 0.4 s with R f = 0   Ω . The obtained responses demonstrate that the proposed method effectively withstands noise variations and measurement uncertainties while accurately diagnosing faults under noisy operating conditions.
Figure 15. Response of the proposed method with transducer errors.

4.2.7. Effect of Load Variation

The response of the proposed method has been assessed by changing the burden on the transmission line to 1.1, 1 and 0.9 times of a 200 MW load (F. L= 200 MW). Test cases are conducted at 240 km considering solid phase-A to ground fault. The response from FDI, FCI, and FSI for the cases mentioned above is shown in Figure 16. The figure shows that, regardless of the burden on the line, the proposed method can diagnose the fault effectively. At td = 0.403 s, the FDI detects the fault. At tc = 0.423 s, the FCI response for phase-A is high for all the cases. The response of the KNN ensemble-based FSI is obtained by computing the Kd value from the instant td to ts (ts = 0.443 s). The Kd value of 40 indicates that the faults are initiated in section S2, which favors the test condition. FLI locates the fault at 236.2 km, 238.4 km, and 242.1 km with respective percentage absolute errors of 1.26, 0.53, and 0.7. Table 10 summarizes all these test cases. This table shows that the proposed method can detect faults under varying load conditions.
Figure 16. Proposed protection scheme response Vs Loading.
Table 10. Effect of load variation on the performance of the proposed algorithm.

5. Validation

5.1. Validation Through Simulation Data

The proposed ensemble section classifier performance and the ANN-based FDI, FCI, and FLI are validated by conducting 4760 test cases simulated by varying the fault location, resistance, inception, and transmission line burden. This section evaluates and summarizes the quantitative responses to each test case. Figure 17a depicts the histogram of FDI response data. The figure includes a normal distribution curve that fits the FDI response. According to the figure, the mean response time of FDI is 4.051 ms, and there is a 95% chance that the new test case is detected within the interval [3.98 4.11] ms. Figure 17b presents the histogram of the signed fault location error, defined as the difference between the estimated and actual fault locations expressed as a percentage of the transmission line length. Positive values indicate overestimation of the fault location, whereas negative values indicate underestimation. The proposed FLI achieves an average signed error of −0.02988%, indicating that the estimator exhibits negligible systematic bias. The corresponding 95% confidence interval for the mean signed error is [−0.057% −0.002%].
Figure 17. Histogram with normal distribution for (a) FDI response error and (b) mean fault location (FLI response) error.
Figure 18 displays the FCI response to parameter change for chosen test cases. It has been noted that the FCI categorizes the fault with 100% accuracy. The portrait demonstrates that the proposed FCI is robust and can accurately and effectively classify the fault, regardless of parameter fluctuation.
Figure 18. FCI response with variation in (a) fault type, (b) fault location, (c) fault inception and (d) fault resistance.
The RSEC, trained using the training dataset, is employed to identify the faulted section, and its performance is evaluated using the independent test dataset. The response of FSI is calculated for each fault type by adjusting the remaining fault parameters. The fault section prediction is based on the cumulative K d value computed over two cycles following fault detection. Figure 19a,b show the heat maps of the ensemble Fault Section Identifier (FSI) for faults occurring in sections S1 & S2, respectively. The corresponding box plot representations are presented in Figure 20. Based on observations from Figure 20a,b, the selection of the threshold value for Kd as 20 is justified. The proposed ensemble-based FSI can identify the fault section correctly with an efficiency of 98.646%.
Figure 19. Confusion matrix of proposed RSEC for faults in (a) section S1 (b) section S2.
Figure 20. Box plot representation of RSEC (FSI) response for faults in (a) section S1 (b) section S2.
Table 11 presents a comparison between the outcomes of the proposed approach and the current state of the art. The table displays performance parameters such as mean fault detection time, fault type classification, fault section estimation, and mean fault location error achieved by the proposed method. The proposed method detects the fault with an average response time of 4.051 ms and can classify the faults with 100% accuracy. The proposed ensemble KNN classifier identifies the fault section with an efficiency of 98.646%, and the FLI estimates the location with a mean signed fault location error of −0.02988% and a mean absolute location error of 0.0791%, indicating negligible systematic bias and high localization accuracy.
Table 11. Performance comparison of the proposed protection scheme with the existing state of the art.
The negative sign of the mean signed error indicates a slight tendency of the estimator to underestimate the actual fault location; however, its magnitude is very small (0.02988%), demonstrating negligible systematic bias. The remaining parameters like fault resistance, compensation level, and total number of fault cases along with the sampling frequency considered are compared with the literature and represented in the table. Figure 21 presents a comprehensive visual comparison of the proposed protection scheme with the existing state-of-the-art methods using multiple performance parameters. Compared with existing techniques, the proposed framework provides faster fault detection, lower fault location error, and reliable operation at a reduced sampling frequency of 1 kHz. In addition, the use of only local voltage and current measurements eliminates the dependency on remote-end communication, thereby reducing communication latency and enhancing the suitability of the proposed method for real-time protection applications.
Figure 21. Visual comparison of the proposed protection scheme with the existing state of the art [5,18,22,24,25,30].

5.2. Validation Through OPAL-RT Real-Time Digital Simulator

The proposed protection framework was validated using the OPAL-RT OP4510 hardware-in-the-loop real-time digital simulator. The experimental setup comprising the OPAL-RT platform, host workstation, and Digital Storage Oscilloscope (DSO) is illustrated in Figure 22. The transmission line model developed in MATLAB/Simulink was deployed onto the OPAL-RT platform through the RT-LAB environment, which enables real-time execution of the power system model and communication with the host workstation. During real-time operation, the simulator generated the phase voltage, line current, and zero-sequence current signals at the relay location, which were acquired by the host computer for processing by the proposed intelligent protection algorithm implemented in MATLAB/Simulink. The algorithm performed fault detection, fault classification, fault section identification, and fault location estimation in real time. The computed protection decisions were then compared with the corresponding offline simulation results to verify the correctness, consistency, and computational feasibility of the proposed framework under real-time execution. The responses obtained from the analog output channels of the OPAL-RT OP4510 were monitored and captured using a DSO. The close agreement between the real-time and offline simulation results confirms the suitability of the proposed protection framework for real-time digital implementation.
Figure 22. Experimental setup of OPAL-RT real-time digital simulator.
The response of the proposed scheme on a real-time scale is captured by creating AG-faults in section S1 (75 km) and section S2 (225 km) respectively. The response of OPAL-RT for the simulated faults is shown in Figure 23. Figure 23a,b shows the state of the index (FDI, FCI, and FSI) obtained from the trained intelligent network, as well as the three-phase voltage and current waveforms. The time instances tf, td, tc and ts are calibrated for each case and represented inside the figure. For the fault initiated at 0.4 s, the DSO captures the waveforms from 0.3 s to 0.5 s. From Figure 23a, it is evident that the FDI reaches 1 at 0.402 s, FCI classifies the fault as AG-fault (A = 1, B = 0, C = 0, and G = 1 at tc s) and FSI identifies the fault section as S1 (before capacitor) as Kd < 20 holds good at ts s. From Figure 23b, it is observed that the FDI reaches to 1 at 0.403 s, FCI classifies the fault as AG-fault (A = 1, B = 0, C = 0, and G = 1 at tc s) and FSI identifies the fault section as S2 (after capacitor) as Kd  ≥ 20 holds good at ts s.
Figure 23. OPAL-RT real-time digital simulator results for AG—fault in (a) section S1 (Lf = 75 km, Rf = 0 ohm, Tf = 0.4 s) and (b) section S2 (Lf = 225 km, Rf = 0 ohm, Tf = 0.4 s).
Although the proposed protection framework has been extensively validated through MATLAB/Simulink simulations and OPAL-RT real-time digital simulation, the current validation is limited to a real-time simulation environment. The OPAL-RT implementation confirms the computational feasibility and real-time execution capability of the proposed algorithm. However, practical deployment may be influenced by factors such as CT/PT measurement errors, transmission line parameter uncertainties, synchronization and communication delays, and noise measurement, which have not been explicitly considered in the present study. Therefore, comprehensive hardware-in-the-loop validation under realistic operating conditions, followed by field implementation and testing, constitutes an important direction for future research.

6. Conclusions

The present work extends our earlier ANN-based protection framework for conventional transmission lines to the more challenging problem of protecting fixed series-compensated transmission systems. The proposed framework integrates an Artificial Neural Network (ANN) and a random subspace ensemble classifier (RSEC) to perform fault detection, fault classification, fault section identification, and fault location estimation. A task-specific learning strategy was adopted by employing the ANN for detection, classification, and location estimation tasks, while the RSEC, through a majority-weighted voting mechanism, enhanced the robustness and reliability of fault section identification, thereby improving the accuracy of subsequent fault location estimation.
The proposed protection framework was extensively evaluated on a 400 kV, 50 Hz fixed series-compensated transmission system under a wide range of fault and operating conditions. The results demonstrated an average fault detection time of 4.051 ms, 100% fault classification accuracy, 98.646% fault section identification efficiency, a mean signed fault location error of −0.02988%, and a mean absolute location error of 0.0791%, indicating negligible systematic bias and high localization accuracy. The framework also exhibited robust performance under varying fault resistance, fault location, compensation level, source impedance variations, and noisy measurement conditions while operating with a reduced sampling frequency, thereby reducing computational requirements without compromising protection performance.
The real-time implementation using the OPAL-RT digital simulator further verified the computational feasibility and real-time execution capability of the proposed framework for intelligent digital protection applications. Overall, the obtained results demonstrate that the proposed task-specific ensemble learning framework provides a reliable, accurate, robust, and computationally efficient solution for the protection and monitoring of modern series-compensated transmission networks within the scope of the present study. Nevertheless, although the proposed framework has been validated through MATLAB/Simulink and OPAL-RT real-time digital simulations, comprehensive hardware-in-the-loop and field validation under realistic operating conditions remain important directions for future research prior to practical deployment.

Author Contributions

J.R.M.: conceptualization, methodology, investigation, visualization, writing—original draft preparation. K.N.B.: supervision, validation, writing—reviewing and editing. R.N.K.: writing—review and editing. M.L.K.: visualization and supervision. J.B.: visualization and supervision. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Data Availability Statement

The original contributions presented in this study are included in the article.

Conflicts of Interest

The authors declare no conflicts of interest.

Abbreviations

The following abbreviations are used in this manuscript:
ANNArtificial Neural Network
RSECRandom subspace ensemble classifier
KNNk-Nearest Neighbor
MOVMetal Oxide Varistor
FDIFault Detection Index
FCIFault Classification Index
FSIFault Section Index
FLIFault Location Index
S. DStandard deviation
SNRSignal-to-noise ratio
MAEMean absolute error
RMSERoot Mean Square Error

Appendix A

The appendix provides the parameters used to implement the base model in the MATLAB/Simulink software.
Table A1. Test system data.

References

  1. Anderson, P.M.; Henville, C.; Rifaat, R.; Johnson, B.; Meliopoulos, S. Power System Protection, 2nd ed.; Wiley-IEEE Press: Hoboken, NJ, USA, 2021. [Google Scholar]
  2. Vyas, B.; Maheshwari, R.P.; Das, B. Protection of Series Compensated Transmission Line: Issues and State of Art. Electr. Power Syst. Res. 2014, 107, 93–108. [Google Scholar] [CrossRef] [Scilit]
  3. Al-Mohammed, A.H.; Abido, M.A.; Shafiullah, M. Chapter 9—Fault Diagnosis in Series Compensated Power Transmission Lines. In Power System Fault Diagnosis: A Wide Area Measurement Based Intelligent Approach; Elsevier: Amsterdam, The Netherlands, 2022; pp. 223–248. [Google Scholar] [CrossRef] [Scilit]
  4. Rocha, S.A.; Cardoso, R.T.N.; da Silveira, E.G.; Luiz, A.S.A. Application of Nonlinear Optimization for Fault Location in Transmission Lines with Series Compensation Protected by Varistors. Energies 2023, 16, 5595. [Google Scholar] [CrossRef] [Scilit]
  5. Abd el-Ghany, H.A.; Elsadd, M.A.; Ahmed, E.S. A Faulted Side Identification Scheme-Based Integrated Distance Protection for Series-Compensated Transmission Lines. Int. J. Electr. Power Energy Syst. 2019, 113, 664–673. [Google Scholar] [CrossRef] [Scilit]
  6. Hashemi, S.M.; Hagh, M.T.; Seyedi, H. A Novel Backup Distance Protection Scheme for Series-Compensated Transmission Lines. IEEE Trans. Power Deliv. 2014, 29, 699–707. [Google Scholar] [CrossRef] [Scilit]
  7. Abo-Hamad, G.M.; Ibrahim, D.K.; Aboul Zahab, E.; Zobaa, A.F. Adaptive Mho Distance Protection for Interconnected Transmission Lines Compensated with Thyristor Controlled Series Capacitor. Energies 2021, 14, 2477. [Google Scholar] [CrossRef] [Scilit]
  8. Gupta, R.; Ali, S.; Kapoor, G. A New Differential Protection Scheme for Fixed Series-Compensated Transmission Line. Multiscale Multidiscip. Model. Exp. Des. 2022, 5, 1–30. [Google Scholar] [CrossRef] [Scilit]
  9. Jena, M.K.; Samantaray, S.R.; Panigrahi, B.K. A New Wide-Area Backup Protection Scheme for Series-Compensated Transmission System. IEEE Syst. J. 2017, 11, 1877–1887. [Google Scholar] [CrossRef] [Scilit]
  10. Mishra, S.; Gupta, S.; Yadav, A.; Abdelaziz, A.Y. Traveling Wave-Based Fault Localization in FACTS-Compensated Transmission Line via Signal Decomposition Techniques. Energies 2023, 16, 1871. [Google Scholar] [CrossRef] [Scilit]
  11. Naidu, O.D.; Pradhan, A.K.; George, N. A Hybrid Time-Domain Protection Scheme for Series Compensated Transmission Lines. IEEE Trans. Power Deliv. 2022, 37, 1823–1833. [Google Scholar] [CrossRef] [Scilit]
  12. Kanwal, S.; Jiriwibhakorn, S. Artificial Intelligence Based Faults Identification, Classification, and Localization Techniques in Transmission Lines-A Review. IEEE Lat. Am. Trans. 2023, 21, 1291–1305. [Google Scholar] [CrossRef] [Scilit]
  13. Paolini, D.; Dini, P.; Elhanashi, A.; Saponara, S. Advanced Fault Detection and Diagnosis Exploiting Machine Learning and Artificial Intelligence for Engineering Applications. Electronics 2026, 15, 476. [Google Scholar] [CrossRef] [Scilit]
  14. Mishra, P.K.; Yadav, A. Combined DFT and Fuzzy Based Faulty Phase Selection and Classification in a Series Compensated Transmission Line. Model. Simul. Eng. 2019, 2019, 1–18. [Google Scholar] [CrossRef] [Scilit]
  15. Elmitwally, A.; Ghanem, A. Local Current-Based Method for Fault Identification and Location on Series Capacitor-Compensated Transmission Line with Different Configurations. Int. J. Electr. Power Energy Syst. 2021, 133, 107283. [Google Scholar] [CrossRef] [Scilit]
  16. Moravej, Z.; Khederzadeh, M.; Pazoki, M. New Combined Method for Fault Detection, Classification, and Location in Series-Compensated Transmission Line. Electr. Power Compon. Syst. 2012, 40, 1050–1071. [Google Scholar] [CrossRef] [Scilit]
  17. Megahed, A.I.; MonemMoussa, A.; Bayoumy, A.E. Usage of Wavelet Transform in the Protection of Series-Compensated Transmission Lines. IEEE Trans. Power Deliv. 2006, 21, 1213–1221. [Google Scholar] [CrossRef] [Scilit]
  18. Swetapadma, A.; Mishra, P.; Yadav, A.; Abdelaziz, A.Y. A Non-Unit Protection Scheme for Double Circuit Series Capacitor Compensated Transmission Lines. Electr. Power Syst. Res. 2017, 148, 311–325. [Google Scholar] [CrossRef] [Scilit]
  19. Abdullah, A. Ultrafast Transmission Line Fault Detection Using a DWT-Based ANN. IEEE Trans. Ind. Appl. 2018, 54, 1182–1193. [Google Scholar] [CrossRef] [Scilit]
  20. Abdelaziz, A.Y.; Ibrahim, A.M.; Mansour, M.M.; Talaat, H.E. Modern Approaches for Protection of Series Compensated Transmission Lines. Electr. Power Syst. Res. 2005, 75, 85–98. [Google Scholar] [CrossRef] [Scilit]
  21. Rocha, S.A.; de Mattos, T.G.; da Silveira, E.G. A Practical Approach for Fault Location in Transmission Lines with Series Compensation Using Artificial Neural Networks: Results with Field Data. Energies 2025, 18, 145. [Google Scholar] [CrossRef] [Scilit]
  22. Vyas, B.; Das, B.; Maheshwari, R.P. An Improved Scheme for Identifying Fault Zone in a Series Compensated Transmission Line Using Undecimated Wavelet Transform and Chebyshev Neural Network. Int. J. Electr. Power Energy Syst. 2014, 63, 760–768. [Google Scholar] [CrossRef] [Scilit]
  23. Wang, F.; Hu, Z. A Novel Fault Diagnosis and Accurate Localization Method for a Power System Based on GraphSAGE Algorithm. Energies 2025, 14, 1219. [Google Scholar] [CrossRef] [Scilit]
  24. Tabari, M.; Sadeh, J. Fault Location in Series-Compensated Transmission Lines Using Adaptive Network-Based Fuzzy Inference System. Electr. Power Syst. Res. 2022, 208, 107800. [Google Scholar] [CrossRef] [Scilit]
  25. Eristi, H. Fault Diagnosis System for Series Compensated Transmission Line Based on Wavelet Transform and Adaptive Neuro-Fuzzy Inference System. Measurement 2013, 46, 393–401. [Google Scholar] [CrossRef] [Scilit]
  26. Kanwal, S.; Jiriwibhakorn, S. Advanced Fault Detection, Classification, and Localization in Transmission Lines: A Comparative Study of ANFIS, Neural Networks, and Hybrid Methods. IEEE Access 2024, 12, 49017–49033. [Google Scholar] [CrossRef] [Scilit]
  27. Mohammad Taheri, M.; Seyedi, H.; Nojavan, M.; Khoshbouy, M.; Mohammadi Ivatloo, B. High-Speed Decision Tree Based Series-Compensated Transmission Lines Protection Using Differential Phase Angle of Superimposed Current. IEEE Trans. Power Deliv. 2018, 33, 3130–3138. [Google Scholar] [CrossRef] [Scilit]
  28. Dash, P.K.; Samantaray, S.R.; Panda, G. Fault Classification and Section Identification of an Advanced Series-Compensated Transmission Line Using Support Vector Machine. IEEE Trans. Power Deliv. 2007, 22, 67–73. [Google Scholar] [CrossRef] [Scilit]
  29. Polikar, R. Ensemble Based Systems in Decision Making. IEEE Circuits Syst. Mag. 2006, 6, 21–45. [Google Scholar] [CrossRef] [Scilit]
  30. Mishra, P.K.; Yadav, A.; Pazoki, M. A Novel Fault Classification Scheme for Series Capacitor Compensated Transmission Line Based on Bagged Tree Ensemble Classifier. IEEE Access 2018, 6, 27373–27382. [Google Scholar] [CrossRef] [Scilit]
  31. Nawaz, R.; Wadood, A.; Khalid Mehmood, K.; Basit Ali Bukhari, S.; Albalawi, H.; Mohammed Alatwi, A.; Sajid, M. Gradient Boosting Feature Selection for Integrated Fault Diagnosis in Series-Compensated Transmission Lines. IEEE Access 2025, 13, 63640–63670. [Google Scholar] [CrossRef] [Scilit]
  32. Alghazzawi, D.M.; Alquraishee, A.G.A.; Badri, S.K.; Hasan, S.H. ERF-XGB: Ensemble Random Forest-Based XG Boost for Accurate Prediction and Classification of E-Commerce Product Review. Sustainability 2023, 15, 7076. [Google Scholar] [CrossRef] [Scilit]
  33. Khan, B.M.; Wadood, A.; Albalawi, H.; Khan, S.; Alatwi, A.M.; Albalawi, O.H. A Hybrid Ensemble-Based Intelligent Decision Framework for Risk-Aware Photovoltaic Panel Soiling Detection and Cleaning. Electronics 2026, 15, 1192. [Google Scholar] [CrossRef] [Scilit]
  34. Ho, T.K. The Random Subspace Method for Constructing Decision Forests. IEEE Trans. Pattern Anal. Mach. Intell. 1998, 20, 832–844. [Google Scholar] [CrossRef] [Scilit]
  35. Samantaray, S.R. Ensemble Decision Trees for High Impedance Fault Detection in Power Distribution Network. Int. J. Electr. Power Energy Syst. 2012, 43, 1048–1055. [Google Scholar] [CrossRef] [Scilit]
  36. Deegalla, S.; Walgama, K.; Papapetrou, P.; Boström, H. Random Subspace and Random Projection Nearest Neighbor Ensembles for High Dimensional Data. Expert Syst. Appl. 2022, 191, 116078. [Google Scholar] [CrossRef] [Scilit]
  37. Yu, Z.; Chen, H.; Liuxs, J.; You, J.; Leung, H.; Han, G. Hybrid κ-Nearest Neighbor Classifier. IEEE Trans. Cybern. 2016, 46, 1263–1275. [Google Scholar] [CrossRef] [Scilit] [PubMed]
  38. Nanni, L.; Lumini, A. Evolved Feature Weighting for Random Subspace Classifier. IEEE Trans. Neural Netw. 2008, 19, 363–366. [Google Scholar] [CrossRef] [Scilit] [PubMed]
  39. Moparthi, J.R.; Bhukya, K.N.; Chinta, D.P.; Biswal, M. Enhancing Transmission Line Protection with Adaptive ANN-Based Relay for High Resistance Fault Diagnosis. Electr. Eng. 2024, 106, 7117–7132. [Google Scholar] [CrossRef] [Scilit]
  40. Goldsworthy, D.L. A Linearized Model for Mov-Protected Series Capacitors. IEEE Trans. Power Syst. 1987, 2, 953–957. [Google Scholar] [CrossRef] [Scilit]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Article Metrics

Citations

Article Access Statistics

Multiple requests from the same IP address are counted as one view.