Abstract
For power systems with a high penetration of renewable energy, energy storage allocation is important for enhancing system flexibility and supporting renewable energy integration. Existing planning methods cannot simultaneously reflect source-load uncertainty and the stage-wise evolution of system development. To address this issue, this paper proposes a stage-wise energy storage planning framework based on bilevel optimization. The proposed method employs an LSTM model to construct representative wind power, photovoltaic power, and load time series for the subsequent optimization analysis, and applies K-means clustering to extract representative operating scenarios. The Qinghai power system is selected as a case study for validation. The results show that the proposed method can reasonably capture the stage-wise characteristics of storage demand, with deviation rates of 4.6% for storage power and 3.2% for storage capacity. Under low-, medium-, and high-growth scenarios, storage demand increases significantly with renewable development scale. In the high-growth scenario, the required storage capacity increases from 277,836 MWh in 2030 to 926,120 MWh in 2035. Meanwhile, the role of storage shifts from short-term power balancing to peak shaving and inter-temporal energy shifting, while the optimal storage duration remains stable at 3–4 h. The proposed framework provides a basis for long-term energy storage planning in power systems with high renewable penetration.
1. Introduction
With the continuous expansion of wind and photovoltaic generation, renewable energy accounts for an increasing share of installed capacity in power systems [1,2,3]. This trend improves the low-carbon level of the power sector, but also increases the variability and uncertainty of system operation. As renewable penetration rises, higher requirements are imposed on power system flexibility and balancing capability [4,5,6,7]. In this context, energy storage has become an important resource for improving renewable-energy utilization and maintaining system operation. Therefore, the determination of appropriate storage power and capacity has become an important issue in power system planning [8,9,10,11].
Existing studies on energy storage planning can be broadly classified into several categories. The first category focuses on static siting and sizing or target-state planning, in which storage capacity and location are determined under assumed generation and load conditions for a representative planning stage [12,13,14]. The second category introduces uncertainty through scenario analysis, stochastic programming, or related probabilistic approaches, thereby improving the representation of renewable variability and load fluctuation [15,16,17]. In addition, some recent studies have extended storage planning to multi-stage formulations in order to better capture the gradual evolution of system expansion under uncertainty [18,19,20,21]. These studies have provided valuable support for energy storage planning. However, in long-term system development, renewable capacity and load demand do not remain fixed and instead evolve continuously across different planning stages. If storage configuration is determined only for representative target states or limited planning stages, the gradual expansion process of storage and the influence of intermediate development stages may not be fully represented. In parallel, some studies have also emphasized the importance of explicit network constraints, such as transmission-capacity limits, nodal power-flow restrictions, congestion effects, and security-related operating requirements, especially in transmission, distribution, or coupled energy system expansion settings [22,23]. In this context, a sequential recursive stage-wise framework is more suitable for long-term storage planning, because it can explicitly represent inter-stage coupling through the recursive updating of system scale and the cumulative expansion of storage configuration across planning stages. In addition, the uncertainty of future renewable expansion and load growth can be described through low-, medium-, and high-growth pathways constructed around the recent baseline growth trend.
Based on these considerations, this paper extends the existing bilevel optimization model [24] and develops a stage-wise energy storage planning framework for a multi-energy complementary power system. The methodological contribution of this study is reflected in three aspects. First, the proposed framework adopts a stage-wise recursive structure, in which the results of each planning stage provide updated conditions for the next stage. Second, the bilevel model coordinates renewable-energy utilization and economic benefit through hierarchical objectives: the lower level evaluates renewable-energy utilization, while the upper level determines storage configuration from the perspective of net electricity-sales benefit. Third, LSTM is used to generate wind power, photovoltaic power, and load time-series inputs, and K-means is used for representative scenario reduction. These components enable storage expansion, renewable-energy utilization, and economic performance to be jointly evaluated across planning stages. Historical statistics from 2021 to 2024 are used to construct low-, medium-, and high-growth scenarios. An LSTM model and K-means clustering are adopted to provide typical time-series inputs for the optimization model. The Qinghai power system is selected as a case study for validation. The remainder of this paper is organized as follows. Section 2 presents the methodological framework. Section 3 provides the case study and simulation results. Section 4 discusses the main findings and limitations. Section 5 concludes the paper.
2. Methodology
2.1. Bilevel Optimization Model for Energy Storage Planning
This study adopts the bilevel optimization model proposed in [24] to determine the optimal energy storage power and capacity. In this model, the upper level determines storage installation decisions by maximizing net electricity-sales benefit, while the lower level optimizes system operation by maximizing renewable-energy utilization under a given storage configuration.
The model considers the coordinated operation of generation, transmission, load, and storage resources, with constraints on power balance, renewable generation, storage operation, hydropower operation, and transmission capacity.
2.1.1. Research Boundaries and Modeling Ideas
The bilevel optimization model considers a multi-energy complementary power generation system consisting of wind farms, photovoltaic plants, hydropower stations, thermal power units, energy storage systems, and an external transmission corridor. The schematic structure of the system is illustrated in Figure 1. Within the defined system boundary, electricity is the primary form of energy exchanged among system components, and system flexibility is achieved through the coordinated operation of multiple energy resources. In this study, the storage component specifically refers to an electrochemical battery energy storage system.
Figure 1.
Structure of the multi-energy complementary power system.
Figure 1 shows the aggregated structure of the multi-energy complementary power system considered in this study. The system includes wind farms, photovoltaic plants, hydropower stations, thermal power units, energy storage, system load, and an external transmission corridor. Wind and photovoltaic generation represent the main renewable supply resources, while hydropower and thermal generation provide dispatchable support. Energy storage serves as a flexible balancing resource through charging and discharging, and the external transmission corridor represents the boundary of power exchange with outside areas. When renewable generation is abundant, surplus electricity can be absorbed by storage or exported; when renewable generation is insufficient, the deficit is compensated by storage discharge and other dispatchable resources. Therefore, Figure 1 is intended to illustrate the functional relationships among the main resources within an aggregated provincial-level planning boundary, rather than a detailed nodal network structure. Under this representation, the effect of internal network constraints is approximated through the external transmission corridor, which is suitable for provincial-level strategic planning focused on the stage-wise evolution of system-scale storage demand rather than detailed internal network operation.
2.1.2. Objective Function
Based on the system boundary defined above, this study adopts a bilevel optimization structure for storage planning. The basic formulation is developed with reference to the multi-energy complementary storage planning model reported in [24], while the present work further extends it to a stage-wise planning framework under evolving development scenarios. In the proposed structure, the upper level represents the planning decision on storage configuration, whereas the lower level evaluates system operation under the given storage scheme.
To avoid ambiguity, three temporal levels are distinguished in this study. First, the lower-level operational model is simulated on an hourly basis, where denotes the operational time-step index, , and h. All power variables in the lower-level model are defined at the hourly time step and expressed in MW, while storage energy is expressed in MWh. Second, denotes the calendar year used for historical statistics and annual growth-rate calculation. Third, denotes the planning stage (or planning node), and denotes the duration between adjacent planning nodes in years. In this study, the planning nodes are 2030 and 2035, and the corresponding stage duration is 5 years.
- (1)
- Upper-Level Objective:
The upper-level optimization model aims to maximize the net revenue from electricity sales as the optimization objective:
where is the net electricity-sales benefit of the system, in CNY; is the gross electricity-sales revenue of the system, in CNY; and is the total cost of the system, in CNY.
The calculation method of the total revenue from electricity sales, R of the system, is as follows:
where represents the electricity price at time period ; denotes the total power supplied to the grid at time ; is the total number of time periods; and represents the duration of each time interval.
The cost calculation method is as follows:
where is the total capital cost of the system, in CNY. In this study, only the investment cost of the newly configured energy storage system is considered in the planning decision, while the other generation resources are treated as existing facilities, and only their operation and maintenance costs are taken into account. is the operation and maintenance cost, in CNY; is the depreciation cost, in CNY; is the discount rate; and is the service life of the system. is the operation and maintenance cost coefficient, taken as 2%, and is the residual value coefficient, taken as 10% [25,26].
The calculation of each capital-cost component is given as follows:
where , , , and are the unit installed costs of wind power, photovoltaic power, hydropower, and thermal power, respectively, in CNY/MW; is the unit installed cost of storage power capacity, in CNY/MW; is the battery energy capacity of the storage system, in MWh; and is the unit installed cost of storage energy capacity, in CNY/MWh, with as the optimization variable.
- (2)
- Lower-Level Objective:
The lower-level optimization model aims to maximize the utilization rate of new energy β:
where β represents the renewable-energy utilization rate; and denote the output of the wind farm and photovoltaic power station during time period t, respectively, in MW; and are their corresponding normalized outputs; and represent the installed capacities of the wind farm and photovoltaic power station, respectively, in MW.
The interaction between the two objectives is handled through the bilevel solution procedure shown in Figure 2.
Figure 2.
Bilevel optimization procedure for coordinating renewable-energy utilization and net benefit.
The upper-level model optimizes storage configuration for net electricity-sales benefit, while the lower-level model evaluates renewable-energy utilization under the given storage scheme, so the two objectives are coupled through storage decisions and operational dispatch.
Therefore, the bilevel framework is applied to stage-wise storage planning under given development scenarios and representative operational conditions. Under this setting, the upper level represents the planning-level economic evaluation of candidate storage configurations, while the lower level represents the operation-level assessment of renewable-energy utilization. The framework is intended for scenarios in which storage planning must simultaneously consider economic performance and renewable-energy utilization under evolving system conditions. A larger storage configuration may improve renewable utilization and reduce curtailment, but it may also increase the associated planning and operational costs. Therefore, the final storage configuration should be interpreted as the result of balancing these two aspects within the adopted planning framework.
2.1.3. Constraints
To ensure the feasibility of system operation, the considered constraints consist of the power balance constraint for the multi-energy complementary generation system, the operation constraints of renewable energy units, the constraints related to renewable energy curtailment, as well as the operation constraints corresponding to energy storage equipment [24]. These constraints are elaborated as follows:
- (1)
- Power balance constraint:
- (2)
- New energy output range constraints [27]:
- (3)
- Abandoned wind and abandoned photovoltaic power state constraints [28]:
- (4)
- Operation Constraints of Energy Storage Power Station—Charging and Discharging Power Range [29]:
- (5)
- Operation Constraints of Energy Storage Power Station—Charging and Discharging States [30]:
- (6)
- Operational Constraints of Energy Storage Power Station—State of Charge [31]:
- (7)
- Operational Constraints of Energy Storage Power Stations—Range of Energy Storage Battery Capacity and Energy Storage Duration [32]
- (8)
- Constraint on the power range of thermal power units:
- (9)
- Power range constraints of hydroelectric generating units:
The main variables in the model are mutually coupled rather than independently defined. Among them, the power-balance equation serves as the central coupling relationship, linking renewable generation, dispatchable generation, storage charging/discharging power, load demand, and external power exchange in each time period. The renewable-output, curtailment-state, thermal-generation, and hydropower constraints determine the feasible ranges of the corresponding power variables, while the storage-operation constraints further relate charging/discharging power to the state-of-charge evolution over time. Together, these relationships define the feasible operating region of the multi-energy complementary system under the adopted planning boundary.
2.2. Stage-Wise Optimization Configuration Model
Conventional single-stage planning assumes fixed system conditions within the planning horizon. However, in renewable-dominated power systems, renewable capacity and load demand continue to change over time. Under these conditions, determining storage capacity only for a terminal target year cannot reflect the stage-wise evolution of the system.
Based on the previously bilevel model, a stage-wise optimization framework is developed. The planning horizon is divided into consecutive stages, and the storage configuration is updated stage by stage according to the system conditions of each stage.
The planning horizon is divided into stages in chronological order. Each stage corresponds to a planning node year, and adjacent stages are separated by a fixed time interval. In this study, 2030 and 2035 are selected as two planning nodes to represent a five-year rolling planning process.
Under this framework, storage capacity in each stage is determined on the basis of the capacity installed in the previous stage.
2.2.1. Historical Growth Rate Calculation
Let denote the scale of a key indicator in year (such as installed photovoltaic capacity, installed wind power capacity, installed hydropower capacity, installed thermal power capacity, or load electricity; the unit varies with the indicator, for example, installed capacity is in MW, and load electricity is in 108 KWh). Then, the annual growth rate of this indicator in year is defined as:
where is a dimensionless quantity (which can be converted into a percentage), and is the indicator scale quantity of the previous year. Based on the historical sample interval (this paper takes 2021–2024 as an example), let the growth rate sequence in the sample be , where is the sample length (number of years). Then the historical average growth rate and standard deviation are, respectively:
where represents the central tendency of the historical growth level, and represents the magnitude of growth fluctuation. Both are dimensionless quantities.
2.2.2. Stage-Wise Growth Rate Formulation
In scenario-based planning, future renewable development is usually characterized by uncertainty around a baseline growth pathway rather than by a fixed absolute deviation. Since the fluctuation of renewable expansion is closely related to the scale of the baseline growth rate, a multiplicative adjustment is adopted to represent proportional changes around the mean growth rate. Specifically, the mean growth rate is used as the baseline growth pathway, and the historical standard deviation expressed in percentage form is converted into a dimensionless volatility-adjustment coefficient . In this formulation, and represent downward and upward proportional adjustments around the baseline growth pathway, respectively. Accordingly, the low-, medium-, and high-growth scenarios are formulated as follows:
Low-growth scenario:
Medium-growth scenario:
High-growth scenario:
where , , and are annual growth rates under the low-, medium-, and high-growth scenarios, respectively; is the mean historical growth rate; and is the dimensionless volatility-adjustment coefficient obtained by converting the percentage-form standard deviation into decimal form. For each indicator, such as photovoltaic installed capacity, wind power installed capacity, and load electricity, the corresponding and are calculated separately, and the obtained scenario growth rates are used for recursive updating in subsequent planning stages.
2.2.3. Capacity Recursion Model
Under the condition of a given scenario growth rate , the indicator is updated recursively between stage nodes. Let and respectively represent the indicator scale quantities in the node years of stage and stage , then their recursive relationship is expressed as:
where represents the duration of the stage (in years). When the interval between planning nodes is 5 years, . This recurrence relation is used to map the stage growth rate obtained from historical statistics to the scale of stage nodes, thereby forming updated input of new energy installed capacity and load scale at each stage, and based on this, re-solving the bilevel optimization model to obtain the energy storage configuration results for the corresponding stage.
2.2.4. Stage Coupling Constraint
Considering that energy storage construction is cumulative and irreversible (under the planning context, the decommissioning or capacity reduction of existing energy storage is generally not considered), let represent the energy storage capacity (MWh) corresponding to the planning node of the k-th stage. Then, the inter-stage coupling constraint can be expressed as:
where is a decision variable, reflecting the incremental construction path of energy storage capacity in each stage.
2.3. Solution Method
In the proposed framework, the bilevel optimization model requires representative full-year hourly wind power, photovoltaic power and load time series for its time-sequential production simulation. These time-series inputs are necessary for evaluating the operating feasibility of candidate storage configurations under system constraints and for determining the optimal storage configuration under the corresponding source-load conditions.
However, installed capacity, resource endowment, and annual load scale alone cannot directly provide the hourly source-load curves required for such a simulation. In renewable-intensive systems, actual wind power and photovoltaic power outputs exhibit strong intermittency, fluctuation, and temporal dependence, while the load profile also exhibits strong temporal dependence [25,33,34]. Therefore, an LSTM model is introduced in this study to construct representative full-year hourly wind power, photovoltaic power, and load time series for the bilevel model. In this study, the corresponding time series are represented on an hourly basis with 8760 time steps per year.
In the proposed framework, the stage-specific installed capacities and load level obtained from the recursive growth model are used as boundary conditions for the bilevel optimization model, while the LSTM-generated representative time series provide the operational input required for time-sequential simulation.
Based on the generated source-load time series, K-means clustering is further applied to extract representative operating scenarios, thereby reducing the computational burden of the subsequent optimization while preserving the main temporal characteristics of source-load variation.
3. Case Study
3.1. Basic Conditions of Qinghai Power Grid
Qinghai is a renewable-intensive power system with a generation structure dominated by hydropower, photovoltaic power, and wind power, while thermal units and external transmission channels provide additional support. By 31 December 2024, the clean-energy installed capacity in Qinghai had reached 67,888 MW, accounting for 94% of the total installed power capacity. This included 16,445 MW of hydropower, 36,317 MW of photovoltaic power, 12,683 MW of wind power, and 210 MW of concentrating photovoltaic power. In addition, the installed capacity of energy storage had reached 2000 MW/6610 MWh by the end of 2024. These figures indicate that Qinghai has already formed a power supply structure with a very high share of renewable energy, while the rapid expansion of renewable generation has also created increasing demand for system regulation and balancing.
In this study, the Qinghai power system is represented by wind farms, photovoltaic stations, hydropower plants, thermal generating units, energy storage systems, and external transmission channels. With its high renewable share, rapid growth of clean energy capacity, and increasing storage deployment, Qinghai provides a representative case for studying stage-wise energy storage planning in renewable-dominated power systems.
3.2. Operational Results of the Bilevel Optimization Model
To illustrate the operational characteristics of the bilevel optimization model, a simulation was carried out using historical operation data of the Qinghai power system in 2023. The input data include wind power, photovoltaic power, hydropower, thermal power, and system load time series, which represent typical operating conditions of the multi-energy complementary power system.
Figure 3 shows the dispatch results of wind power, photovoltaic power, hydropower, thermal units, energy storage, and system load.
Figure 3.
Dispatch results of the multi-energy complementary power system obtained from the bilevel optimization model.
As illustrated in the figure, wind power and photovoltaic generation are the main renewable energy sources in the system, while hydropower and thermal units provide supporting regulation. When renewable generation exceeds load demand, the energy storage system charges to absorb surplus electricity. When renewable generation decreases or load demand increases, the storage system discharges to compensate for the power deficit. The dispatch results show that the bilevel optimization model can generate a feasible operating schedule and maintain system power balance through the coordinated operation of renewable generation, conventional generation, and energy storage.
For comparison, a single-level benchmark model is also constructed under the same system inputs, time-series data, and operational constraints. In this benchmark case, the storage configuration is determined only by the economic objective of maximizing net electricity-sales benefit, while renewable-energy utilization is calculated ex post rather than optimized as an independent lower-level objective. Therefore, the comparison between the two cases is used to illustrate the added value of the bilevel structure in coordinating economic performance and renewable-energy utilization. Figure 4 presents the corresponding comparisons of net electricity-sales benefit and renewable-energy utilization rate.
Figure 4.
(a) Comparison of net electricity-sales benefit with and without the bilevel model. (b) Comparison of renewable-energy utilization rate with and without the bilevel model.
The results show that, compared with the case without the bilevel model, the net electricity-sales benefit increases from 7.4 (108 CNY), to 9.2 (108 CNY), corresponding to an increase of 24.3%, while the renewable-energy utilization rate increases from 87% to 90%, corresponding to an increase of 3 percentage points. This indicates that, under the adopted case conditions, the bilevel structure can improve the coordination between economic performance and renewable-energy utilization.
3.3. Validation of the Solution Method
In this study, the LSTM model is used to construct representative full-year hourly wind power, photovoltaic power, and load time series required for time-sequential production simulation in the bilevel optimization model. The main parameter settings of the LSTM model are summarized in Table 1.
Table 1.
Main parameter settings of the LSTM model.
To evaluate the performance of the LSTM model, the generated wind power, photovoltaic power, and load time series are compared with the corresponding historical series using , RMSE, and MAPE. The corresponding results are summarized in Table 2.
Table 2.
Forecasting performance of the LSTM model on training and testing datasets.
In Table 2, Type 1, Type 2, and Type 3 correspond to wind power, photovoltaic power, and load, respectively. The testing R2 remains above 0.90, while RMSE and MAPE stay within acceptable ranges. This indicates that the model can effectively capture the main temporal variation characteristics of wind power, photovoltaic power, and load series. Therefore, the constructed time series can be used as representative input for the subsequent time-sequential simulation of the bilevel optimization model.
In addition to forecasting, K-means clustering is applied to extract representative operating scenarios from historical generation combinations. By grouping similar operating states into a limited number of typical scenarios, the clustering process significantly reduces the computational burden of the staged optimization model while maintaining the overall characteristics of the generation structure. Therefore, the scenario reduction strategy improves computational efficiency without affecting the overall optimization trend.
Additional validation results are provided in the Supplementary Material (Tables S1 and S2). The comparison with MLR, GAM, MLP, SVR, and DT shows that LSTM achieves the best overall performance, with reaching 0.96, and RMSE and MAPE decrease to 0.140 and 0.046, respectively, supporting its use for source-load time-series generation. In addition, K-means-based scenario reduction reduces computation time by 45.8%, while the deviations in storage power, storage capacity, and renewable-energy utilization remain small, at +1.3%, −2.2%, and +0.2 percentage points, respectively.
3.4. Stage-Wise Energy Storage Planning Results
3.4.1. Scenario Construction Based on Historical Growth Rates
To construct representative future development scenarios, the recent growth-rate observations are adopted as the primary basis for scenario setting in this study, rather than directly using the entire historical period. The reason is that the earlier years correspond to a substantially different development stage of the Qinghai power system, with different policy targets, installed-capacity bases, and renewable-development conditions. In contrast, the recent period is more relevant to the planning horizon considered in this study because it better reflects the current policy environment, renewable-expansion regime, and load-growth conditions. Moreover, the period from 2021 to 2024 provides a relatively stable recent reference for scenario setting. Accordingly, the growth-rate observations for 2021–2022, 2022–2023, and 2023–2024 are adopted for the construction of the low-, medium-, and high-growth scenarios.
In this study, photovoltaic capacity, wind power capacity, and annual load electricity are treated as scenario-dependent variables, while the installed capacities of hydropower and thermal power are fixed at the base-year level. This treatment is adopted because, under the adopted planning assumptions, the main variation in future storage demand is mainly associated with the continued expansion of wind power and photovoltaic power, together with load growth. The scenario-dependent variables are recursively updated between planning stages and then used as stage-specific inputs to the bilevel optimization model. In particular, the updated wind and photovoltaic installed capacities enter the lower-level objective and renewable-output constraints as exogenous installed-capacity parameters, thereby defining the renewable-generation conditions of each planning stage. It should be noted that this assumption applies only to installed capacities. The actual outputs of hydropower and thermal power remain dispatchable variables in the lower-level optimization model. The adopted recent growth rates are summarized in Table 3.
Table 3.
Historical growth rates of generation capacity and load demand (2021–2024).
Based on the statistical characteristics of historical growth rates, three representative development scenarios are constructed: low-growth, medium-growth, and high-growth scenarios. The medium-growth scenario corresponds to the historical mean growth rate, while the low-growth and high-growth scenarios represent lower and upper deviations from the mean value, respectively. These scenarios describe different possible development paths of generation capacity and load demand in the Qinghai power system. Using the above proportional adjustment formulation, the low-, medium-, and high-growth rates are obtained and summarized in Table 4, which are then used in the subsequent stage-wise storage planning analysis.
Table 4.
Growth-rate scenarios derived from historical statistics.
Table 4 shows clear differences in the growth rates of key indicators under the three scenarios. Among all generation types, photovoltaic capacity has the highest growth rate, ranging from 25.85% to 35.55%, indicating that photovoltaic expansion is the main driver of future system development. Wind power and hydropower also maintain positive growth, but at significantly lower rates than photovoltaic power. In contrast, thermal power capacity shows a continuous decline in all scenarios, reflecting the gradual transition toward a renewable-dominated power system. Meanwhile, load demand grows steadily, with a relatively narrow range from 6.85% to 7.35%. These results indicate that future storage demand will mainly be driven by the rapid expansion of renewable generation, especially photovoltaic power, together with the steady growth of system load.
To further verify the accuracy of the proposed stage-wise growth model, a historical back-testing experiment is conducted. The data of 2022 are taken as the base year, and the medium-growth scenario derived from historical statistics is applied to estimate the system indicators for 2023. The calculated results are then compared with the corresponding actual values.
As shown in Table 5, the calculated and actual energy storage installed power for 2023 are 2092 MW and 2000 MW, with a deviation rate of 4.6%; the calculated and actual storage capacity are 6398 MWh and 6610 MWh, with a deviation rate of 3.2%. This back-testing result provides a statistical validation of the proposed stage-wise formulation. The relatively small deviation rates indicate that the model can reasonably reproduce the short-term evolution trend of storage power and storage capacity under the adopted historical growth-rate assumptions.
Table 5.
Comparison of Calculated and Actual Values of Energy Storage Indicators.
Based on the validated growth-rate formulation, future development scenarios are further constructed to describe the possible evolution of generation capacity and load demand in the Qinghai power system. Figure 5 illustrates the projected trajectories of wind power, photovoltaic power, and annual load electricity under the low-, medium-, and high-growth scenarios.
Figure 5.
Evolution of generation capacity and annual electricity load under different growth scenarios.
As shown in the figure, photovoltaic capacity exhibits the fastest growth and the largest scenario difference, while wind power grows more moderately, and annual electricity load maintains a relatively stable upward trend. The differences among the three scenarios indicate that storage demand is mainly driven by the expansion rate of renewable generation, especially photovoltaic capacity. Because photovoltaic output is concentrated in daytime, rapid photovoltaic growth increases the mismatch between generation and load demand, thereby increasing the need for energy shifting. This explains why the high-growth scenario leads to a much larger storage requirement in the later planning stage. Under the recent policy and development background of Qinghai, this suggests that future storage demand is mainly associated with the continued expansion of variable renewable generation, especially photovoltaic power, together with sustained load growth.
3.4.2. Optimal Storage Configuration Results
Based on the development scenarios, the stage-wise optimization model is applied to determine the optimal energy storage configuration for each planning stage. Table 6 presents the optimal storage power and capacity for 2030 and 2035 under different scenarios, showing that the required storage capacity increases significantly over time.
Table 6.
Optimal energy storage configuration results under different development scenarios.
In the early planning stage (2030), the required storage capacity differs significantly across scenarios. Under the low-, medium-, and high-growth scenarios, the optimal storage capacity is 28,212 MWh, 120,488 MWh, and 277,836 MWh, respectively.
In the later planning stage (2035), the required storage capacity increases further to 200,778 MWh, 571,656 MWh, and 926,120 MWh under the three scenarios, respectively. These results show that storage demand increases significantly with both renewable development speed and planning stage. The optimal storage duration remains relatively stable across scenarios, ranging from 3 to 4 h. The increase in storage demand from 2030 to 2035 is mainly driven by the continuous expansion of renewable generation and load demand under the adopted scenarios. In particular, the rapid growth of photovoltaic capacity increases the temporal mismatch between daytime renewable generation and load demand, leading to a higher requirement for energy shifting. However, the optimal storage duration remains within 3–4 h, indicating that the main change in storage planning is reflected in the expansion of storage scale rather than a substantial change in discharge duration.
Overall, the results in Table 6 show a clear stage-wise increase in storage planning results from 2030 to 2035. In the earlier stage, storage mainly provides support for balancing renewable variability and load fluctuations. In the later stage, as the scale of renewable generation and load continues to increase under the adopted scenarios, the required storage scale also becomes larger. Therefore, the proposed stage-wise framework can reflect the progressive increase in storage demand under different development scenarios and provide corresponding planning results for different stages. In addition, possible long-term changes in climatic and hydrological resource availability are not explicitly modeled in the present study, because the main focus of this work is the stage-wise evolution of installed capacity and system scale under the adopted planning assumptions.
Additional sensitivity analyses are provided in the Supplementary Material (Figure S1 and Table S3). The results indicate that storage demand increases nonlinearly as the renewable-energy utilization target rises, especially in the high-utilization range. Load variation also affects storage configuration: higher load growth can partly reduce storage requirements by improving local renewable-energy consumption.
4. Discussion
4.1. Strengths and Advantages
Compared with conventional single-stage storage planning approaches, the proposed stage-wise framework provides a more realistic representation of the cumulative expansion process of storage deployment. Instead of determining storage size only for a terminal target year, the method yields stage-specific planning results for 2030 and 2035, which are more consistent with the gradual investment characteristics of large-scale energy infrastructure development.
A further advantage of the proposed framework is that it can reflect the differences in storage demand under different development pathways. Under the adopted low-, medium-, and high-growth scenarios, the required storage power and energy capacity both increase from 2030 to 2035, while the optimal storage duration remains within a relatively narrow range of 3–4 h. This indicates that, for the Qinghai case considered in this study, future storage expansion is mainly manifested in the increase of storage scale rather than in substantial changes in storage duration.
In addition, the framework can combine stage-wise system evolution with operational calculation in a unified planning process. The lower-level model evaluates system operation through time-sequential simulation, while the upper-level model compares the economic performance of feasible storage schemes. In this way, the proposed method can provide stage-specific storage planning results under the adopted assumptions, rather than only a single target-year result.
The framework also has practical value for systems with uncertain future development conditions. By constructing multiple growth scenarios, the method can provide a scenario-based analytical reference for medium- and long-term storage planning. For the Qinghai case, this is broadly consistent with the recent development background in which wind power and photovoltaic power continue to expand and storage is expected to play an increasingly important role in system balancing and renewable-energy utilization.
4.2. Limitations and Future Improvements
Although the proposed stage-wise storage planning framework provides useful insights for renewable-dominated power systems, several limitations remain and should be addressed in future research.
First, the forecasting model adopted in this study mainly focuses on renewable generation and electricity demand. Other uncertainties that may influence storage planning decisions, such as electricity price fluctuations, transmission congestion, and policy adjustments, are not explicitly considered. In practical power system planning, these factors may significantly affect the economic performance and investment timing of energy storage systems. Future research could incorporate additional uncertainties using stochastic optimization or probabilistic scenario modeling to further improve the robustness of planning results. Although sensitivity analyses of renewable-energy utilization targets and load variation are conducted, comprehensive uncertainty quantification and formal statistical robustness tests are not included in the present study. Future research will further expand the scenario set and introduce repeated simulations under perturbed input parameters to improve the robustness of the planning results.
Second, the development scenarios considered in this study are constructed based on historical statistical characteristics of renewable installed capacity and load demand. Although this approach provides a simple and transparent method for representing system growth, it may not fully capture policy-driven development pathways or technological breakthroughs in renewable energy deployment. Future studies could integrate energy system planning models or policy-based scenarios to obtain more comprehensive projections of long-term system evolution.
Third, the historical data window used in this study is relatively short. Although the adopted forecasting-and-scenario approach provides a transparent way to generate representative planning inputs, it may not fully capture non-stationary long-term changes caused by accelerated technology learning, policy adjustments, or increasing extreme climate events. Therefore, the results of this study should be understood as scenario-based planning references rather than exact forecasts of the system state in 2030 or 2035.
The present framework focuses on bilevel coordination between renewable-energy utilization and economic storage configuration, and does not simultaneously optimize broader objectives such as network security, reliability, carbon emissions, or global system-wide trade-offs. Future research will further extend the model to multi-objective or robust optimization settings. In addition, some important factors affecting long-term storage-planning decisions have not been explicitly incorporated into the present framework, including battery degradation, long-term electricity price uncertainty, and other long-term operational influences. These factors may affect the effective capacity, economic performance, and long-term configuration of energy storage systems. Therefore, future research will focus on incorporating degradation-related characteristics, richer electricity-price descriptions, and other relevant long-term factors into the proposed framework.
Despite these limitations, the proposed stage-wise optimization framework provides a practical analytical tool for evaluating energy storage deployment under evolving renewable energy systems. The methodology helps reveal the relationship between renewable expansion and storage capacity requirements and offers valuable insights for medium- and long-term energy storage planning during the ongoing energy transition.
5. Conclusions
Against the background of high-penetration renewable energy grid integration, energy storage planning for power systems must comprehensively account for multiple uncertainties arising from power supply development and load growth. To tackle this problem, this paper proposes a stage-wise energy storage planning method based on a bilevel optimization model. The method employs an LSTM model to construct representative wind power, photovoltaic power, and load time series for the time-sequential simulation of the bilevel optimization model, and integrates K-means clustering to extract typical operation scenarios. Historical growth statistics are adopted to construct future development scenarios. Taking Qinghai Power Grid as the case study, three growth scenarios (low, medium, and high) are established to characterize the coordinated variation of future renewable energy, conventional power supplies, and loads, followed by empirical analysis. The main conclusions are drawn as follows:
- (1)
- Effectiveness of the stage-wise energy storage planning framework
The proposed stage-wise energy storage planning framework can reasonably determine the optimal energy storage allocation capacity at different planning stages. Historical back-testing results demonstrate that the deviation rates between the calculated and actual values of energy storage power and capacity are 4.6% and 3.2%, respectively, verifying the favorable fitting accuracy of the framework.
- (2)
- Growth characteristics of storage demand under different development scenarios
The results under the low-, medium-, and high-growth scenarios show that the required storage power and energy capacity both increase significantly with renewable development and the progression of planning stages. In the high-growth scenario, the required storage energy capacity increases from 277,836 MWh in 2030 to 926,120 MWh in 2035. Meanwhile, the role of storage evolves from short-term balancing toward peak shaving and inter-temporal energy shifting, whereas the optimal storage duration remains relatively stable at 3–4 h across scenarios and planning stages.
The methodological contribution of this study lies in applying a stage-wise bilevel storage planning framework to coordinate renewable-energy utilization and economic benefit. In this framework, LSTM-generated source-load time-series inputs support the lower-level operation model for evaluating renewable-energy utilization, while the upper level determines the storage configuration from the perspective of improving net electricity-sales benefit. By introducing recursive updating across planning stages, the framework can represent the cumulative expansion of storage capacity under evolving system conditions. The Qinghai case study and historical back-testing further verify the rationality and applicability of the proposed method. Compared with conventional single-stage or terminal-year planning studies, the proposed framework does not assume fixed system conditions over the entire planning horizon. Instead, it combines stage-wise updating of renewable capacity and load scale with stage-specific bilevel optimization, so that the cumulative expansion characteristics of storage can be represented across planning stages. Therefore, the proposed method can provide a more practical scenario-based reference for medium- and long-term storage planning in renewable-dominated power systems.
Supplementary Materials
The following supporting information can be downloaded at: https://www.mdpi.com/article/10.3390/en19112612/s1, Figure S1: Optimal storage configuration results under different renewable-energy utilization targets; Table S1: Performance comparison of different learning models; Table S2: Comparison between the proposed scenario-reduction method and the full-time-series baseline model; Table S3: Storage power and capacity under different load-growth levels and renewable-energy utilization targets.
Author Contributions
Conceptualization, F.X. and C.T.; methodology, Y.H. and X.Y.; software, J.M., C.L. and J.Z., validation, L.Q. and L.L. All authors were involved in revising the paper. All authors have read and agreed to the published version of the manuscript.
Funding
The present work was supported by the Research and Development Project of State Grid Qinghai Electric Power Company Electric Power Science Research Institute’s Comprehensive study on power supply resilience of Qinghai’s high-proportion clean energy power system considering multiple extreme weather scenarios’ (52280725000T).
Data Availability Statement
The original contributions presented in this study are included in the article. Further inquiries can be directed to the corresponding author.
Acknowledgments
The authors thank the reviewers whose comments improved the quality of this paper.
Conflicts of Interest
Author Changjun Tuo, Yunlong Han, Jing Zhang, Ling Qin and Lincang Li were employed by the company State Grid Qinghai Electric Power Company Electric Power Science Research Institute. The remaining authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.
References
- Wang, Y.; Wang, R.; Tanaka, K.; Ciais, P.; Penuelas, J.; Balkanski, Y.; Sardans, J.; Hauglustaine, D.; Liu, W.; Xing, X.; et al. Accelerating the Energy Transition towards Photovoltaic and Wind in China. Nature 2023, 619, 761–767. [Google Scholar] [CrossRef] [Scilit]
- Ilieva, A. Fuelling Conflict? The Impact of the Green Energy Transition on Peace and Security. Available online: https://www.international-alert.org/publications/fuelling-conflict-the-impact-of-the-green-energy-transition-on-peace-and-security/ (accessed on 10 March 2026).
- Li, J.; Ho, M.S.; Xie, C.; Stern, N. China’s Flexibility Challenge in Achieving Carbon Neutrality by 2060. Renew. Sustain. Energy Rev. 2022, 158, 112112. [Google Scholar] [CrossRef] [Scilit]
- Liu, J.; Hu, H.; Yu, S.S.; Trinh, H. Virtual Power Plant with Renewable Energy Sources and Energy Storage Systems for Sustainable Power Grid-Formation, Control Techniques and Demand Response. Energies 2023, 16, 3705. [Google Scholar] [CrossRef] [Scilit]
- Shahzad, S.; Jasińska, E. Renewable Revolution: A Review of Strategic Flexibility in Future Power Systems. Sustainability 2024, 16, 5454. [Google Scholar] [CrossRef] [Scilit]
- Xie, R.; Li, M. A Review on Renewable Energy Generation Forecasting and Optimal Scheduling Based on Big Data and Artificial Intelligence: Variability Challenges and Construction of a Simulation Experiment Framework. Adv. Resour. Res. 2025, 5, 1335–1356. [Google Scholar] [CrossRef]
- Yue, K.; Li, R.; Wang, Y.; Pan, D.; Shen, C.; Liu, H. Flexibility Assessment in AC/DC Hybrid Distribution Networks via Spatiotemporal Source-Load Scenario Generation. IET Gener. Transm. Distrib. 2026, 20, e70242. [Google Scholar] [CrossRef] [Scilit]
- Rathor, S.K.; Saxena, D. Energy Management System for Smart Grid: An Overview and Key Issues. Int. J. Energy Res. 2020, 44, 4067–4109. [Google Scholar] [CrossRef] [Scilit]
- Castillo, A.; Gayme, D.F. Grid-Scale Energy Storage Applications in Renewable Energy Integration: A Survey. Energy Convers. Manag. 2014, 87, 885–894. [Google Scholar] [CrossRef] [Scilit]
- Yang, J.; Dong, Z.Y.; Wen, F.; Chen, Q.; Liang, B. Spot Electricity Market Design for a Power System Characterized by High Penetration of Renewable Energy Generation. Energy Convers. Econ. 2021, 2, 67–78. [Google Scholar] [CrossRef] [Scilit]
- Alizadeh, M.I.; Parsa Moghaddam, M.; Amjady, N.; Siano, P.; Sheikh-El-Eslami, M.K. Flexibility in Future Power Systems with High Renewable Penetration: A Review. Renew. Sustain. Energy Rev. 2016, 57, 1186–1193. [Google Scholar] [CrossRef] [Scilit]
- Bose, S.; Gayme, D.F.; Topcu, U.; Chandy, K.M. Optimal Placement of Energy Storage in the Grid. In Proceedings of the 2012 IEEE 51st IEEE Conference on Decision and Control, Maui, HI, USA, 10–13 December 2012; pp. 5605–5612. [Google Scholar] [CrossRef] [Scilit]
- Pandžić, H.; Wang, Y.; Qiu, T.; Dvorkin, Y.; Kirschen, D.S. Near-Optimal Method for Siting and Sizing of Distributed Storage in a Transmission Network. IEEE Trans. Power Syst. 2015, 30, 2288–2300. [Google Scholar] [CrossRef] [Scilit]
- Fernández-Blanco, R.; Dvorkin, Y.; Xu, B.; Wang, Y.; Kirschen, D.S. Optimal Energy Storage Siting and Sizing: A WECC Case Study. IEEE Trans. Sustain. Energy 2017, 8, 733–743. [Google Scholar] [CrossRef] [Scilit]
- Alharbi, H.; Bhattacharya, K. Stochastic Optimal Planning of Battery Energy Storage Systems for Isolated Microgrids. IEEE Trans. Sustain. Energy 2018, 9, 211–227. [Google Scholar] [CrossRef] [Scilit]
- Park, H. A Stochastic Planning Model for Battery Energy Storage Systems Coupled with Utility-Scale Photovoltaic Photovoltaics. Energies 2021, 14, 1244. [Google Scholar] [CrossRef] [Scilit]
- Bhattacharya, A.; Kharoufeh, J.P.; Zeng, B. Managing Energy Storage in Microgrids: A Multistage Stochastic Programming Approach. IEEE Trans. Smart Grid 2018, 9, 483–496. [Google Scholar] [CrossRef] [Scilit]
- Qiu, T.; Xu, B.; Wang, Y.; Dvorkin, Y.; Kirschen, D.S. Stochastic Multistage Coplanning of Transmission Expansion and Energy Storage. IEEE Trans. Power Syst. 2017, 32, 643–651. [Google Scholar] [CrossRef] [Scilit]
- Flores-Quiroz, A.; Strunz, K. A Distributed Computing Framework for Multi-Stage Stochastic Planning of Renewable Power Systems with Energy Storage as Flexibility Option. Appl. Energy 2021, 291, 116736. [Google Scholar] [CrossRef] [Scilit]
- Zhang, H.; Wu, Q.; Chen, J.; Lu, L.; Zhang, J.; Zhang, S. Multiple Stage Stochastic Planning of Integrated Electricity and Gas System Based on Distributed Approximate Dynamic Programming. Energy 2023, 270, 126892. [Google Scholar] [CrossRef] [Scilit]
- Chernyakhovskiy, I.; Joshi, M.; Rose, A. Power System Planning: Advancements in Capacity Expansion Modeling; National Renewable Energy Laboratory: Golden, CO, USA, 2021. Available online: https://www.osti.gov/biblio/1812327 (accessed on 10 March 2026).
- Nick, M.; Cherkaoui, R.; Paolone, M. Optimal Planning of Distributed Energy Storage Systems in Active Distribution Networks Embedding Grid Reconfiguration. IEEE Trans. Power Syst. 2018, 33, 1577–1590. [Google Scholar] [CrossRef] [Scilit]
- Zhang, S.; Zhang, X.; Zhang, R.; Gu, W.; Cao, G. N-1 Evaluation of Integrated Electricity and Gas System Considering Cyber-Physical Interdependence. IEEE Trans. Smart Grid 2025, 16, 3728–3742. [Google Scholar] [CrossRef] [Scilit]
- He, P.; Ma, J.; Liu, C.; Liu, T.; Li, Z.; Peng, Y.; Xiao, F. Optimal configuration of multi-energy complementary energystorage in Qinghai accounting for hydropower characteristics. J. Hydroelectr. Eng. 2026, 45, 2262. (In Chinese) [Google Scholar] [CrossRef]
- Notton, G.; Nivet, M.-L.; Voyant, C.; Paoli, C.; Darras, C.; Motte, F.; Fouilloy, A. Intermittent and Stochastic Character of Renewable Energy Sources: Consequences, Cost of Intermittence and Benefit of Forecasting. Renew. Sustain. Energy Rev. 2018, 87, 96–105. [Google Scholar] [CrossRef] [Scilit]
- Dagoumas, A.S.; Koltsaklis, N.E. Review of Models for Integrating Renewable Energy in the Generation Expansion Planning. Appl. Energy 2019, 242, 1573–1587. [Google Scholar] [CrossRef] [Scilit]
- Root, C.; Presume, H.; Proudfoot, D.; Willis, L.; Masiello, R. Using Battery Energy Storage to Reduce Renewable Resource Curtailment. In Proceedings of the 2017 IEEE Power & Energy Society Innovative Smart Grid Technologies Conference (ISGT), Washington, DC, USA, 23–26 April 2017; pp. 1–5. [Google Scholar] [CrossRef] [Scilit]
- Su, H.-I.; Gamal, A.E. Modeling and Analysis of the Role of Energy Storage for Renewable Integration: Power Balancing. IEEE Trans. Power Syst. 2013, 28, 4109–4117. [Google Scholar] [CrossRef] [Scilit]
- Caralis, G.; Christakopoulos, T.; Karellas, S.; Gao, Z. Analysis of Energy Storage Systems to Exploit Wind Energy Curtailment in Crete. Renew. Sustain. Energy Rev. 2019, 103, 122–139. [Google Scholar] [CrossRef] [Scilit]
- Ma, W.; Wang, W.; Wu, X.; Hu, R.; Tang, F.; Zhang, W.; Han, X.; Ding, L. Optimal Allocation of Hybrid Energy Storage Systems for Smoothing Photovoltaic Power Fluctuations Considering the Active Power Curtailment of Photovoltaic. IEEE Access 2019, 7, 74787–74799. [Google Scholar] [CrossRef] [Scilit]
- Branco, H.; Castro, R.; Setas Lopes, A. Battery Energy Storage Systems as a Way to Integrate Renewable Energy in Small Isolated Power Systems. Energy Sustain. Dev. 2018, 43, 90–99. [Google Scholar] [CrossRef] [Scilit]
- Luthander, R.; Lingfors, D.; Widén, J. Large-Scale Integration of Photovoltaic Power in a Distribution Grid Using Power Curtailment and Energy Storage. Photovolt. Energy 2017, 155, 1319–1325. [Google Scholar] [CrossRef] [Scilit]
- Lamsal, D.; Sreeram, V.; Mishra, Y.; Kumar, D. Output Power Smoothing Control Approaches for Wind and Photovoltaic Generation Systems: A Review. Renew. Sustain. Energy Rev. 2020, 113, 109245. [Google Scholar] [CrossRef] [Scilit]
- Hu, Z.; Zhang, P.; Cai, J.; Liu, H.; Wang, G.; Chen, Z. A Review of Research on Spatial-Temporal Forecasting of Power Load Based on Spatial-Temporal Data Mining. Int. J. Electr. Power Energy Syst. 2025, 173, 111428. [Google Scholar] [CrossRef] [Scilit]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2026 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.