Abstract
Medium voltage induction motors (MVIM) are a key component of numerous industries, such as water treatment plants, sewage discharge stations, and chilled water systems. The starting process for these MV motors is critical as it is associated with a major impact on both motor lifetime and power grid quality. In this article, a proposed modified and comprehensive starting scheme of MV three-phase induction motors driving pumps for water stations is introduced. Firstly, the starting performance and its impact on power grid quality will be discussed when all motors are normally started with direct on line connection (DOL), which is already the normal established status. A modified starting scheme based on an optimized coordination of motor starting methods in addition to variable voltage variable frequency drive (VVVFD) drive and control implementation will be discussed. A transition between the starting of variant MV induction motors as well as the starting event coordination principle will be discussed to improve the power quality relative to the obligatory time shift required for the operation. The coordination is based on an algorithm implementation which is achieved using different optimization concepts based on artificial intelligence techniques, properly conducting the transition time in addition to the power delivered by the inverter unit rather than determining the number of DOL and VVVF-implemented motors. A comparison between using the optimized VVVFD soft-starting and the proposed modified scheme is performed, focusing on the power quality improvement rather than optimizing the cost function. The modified scheme is simulated using ETAP power station for brief analysis and study of load flow rather than the complete inspection and power quality assessment.
1. Introduction
Three-phase induction motors are used in many industrial drives, including compressors, pumps, fans, or blowers. Manufacturers prioritize these motors’ continuous, uninterrupted operation because they play an important role in production. Motor protection devices must be considered, especially in classified locations. Motors are monitored when they are turned on, and this monitoring involves various parameters, such as starting time and current. The protection concept’s efficacy depends on the motor data used in the concept [1].
DOL starting is an economical and reliable method of starting large induction motors in cases where the supply system is stiff. This starting method has been identified as a significant issue in scenarios where the motor is required to be switched on and off multiple times daily by conventional switching elements. However, the DOL method offers two advantages over other switching methods. First, it minimizes starting current and torque pulsations. Second, it eliminates the need for additional components. An appreciable demerit of using DOL is the reduced starting and maximum torque developed by the motor. A modeling approach is used to identify the optimal switching angles of thyristors [2,3].
The soft start drive smoothly increases the motor’s terminal voltage, regulating the current drawn. A VFD is the solution for ensuring that voltage and frequency stay within predetermined limits, thereby maintaining the stator current and consequently the air gap flux within a certain limit. VFDs control voltage and frequency using an efficiently designed controller. VFDs and VVVFDs affect both the applied terminal voltage and motor current, thereby influencing the developed torque. Soft starters are cheaper than VFD drives as they reduce the applied voltage while keeping the main source frequency constant. Large motors are difficult to start simultaneously due to operational constraints like emissions and voltage flickers. VFD technology improves this by starting multiple motors with a single, more affordable drive. This design balances investment and performance by starting motors with the most available torque in both starting and running regions. The East Texas design combines a starting duty drive below the motor’s voltage and current rating with different-sized motors and protection settings and multiplexed breaker controls [4,5,6].
Soft-starting with an AC chopper, for instance, uses phase control of the motor according to voltage level requirements. Single-phase control uses DOL starting with torque controls. Two-phase control reduces torque both transients and currents. The three-phase AC chopper prevents severe currents in some phases, making it the preferable soft start option above others. VFDs always start motors by applying low frequency and voltage initially to avoid high inrush currents [7].
A soft starter requires less capital investment compared to VFD. The minimum level of starting current depends on motor and load types. Concerns for the SCR-driven soft starter include switching transients and current rise rate during “on” and “off” processes, and overvoltages during “off” processes. Field experience shows a safe rise in current for practical SCR applications is about 75 A/μs. MV soft starters are designed with this knowledge [8].
The soft starter, used with artificial neural networks (ANNs) and adaptive neuro-fuzzy inference systems, reduced inrush currents, controlled and reduced up to a maximum of 1.5 times the rated current and eliminated torque pulsations, lowering mechanical stresses. The soft starter was implemented using DSP and neural network tools, which provides a low-cost solution, adjusting the firing angle of switching devices. ANNs can be trained offline or online; the online solution determines the thyristors’ firing angle. Two approaches are used; the implementations were compared based on training time, hardware complexity, neuron numbers, online and offline capabilities [9].
Configuring starting and control methods for MV motors is more challenging than for low-voltage motors due to motor size, impact on the primary system, and lower starting torque. When selecting the starting equipment for an electric motor-driven load, consider motor characteristics, motor-source line and system voltage effects, motor speed–torque characteristics, load torque characteristics, and load torque range. Also consider shock, vibration, and hammer impact [10,11,12].
In Ref. [13], a simple microcontroller strategy optimized the performance of a voltage-controlled induction motor starter. It ensures near-perfect current and torque during start-up and allows for custom acceleration profiles. However, effectiveness depends on grid stiffness and load torque needs. For high starting torque loads and weak grids, methods like frequency control or conventional techniques using wound rotor motors are necessary to produce high torques at low currents.
The multiple motor soft start/adjustable speed drive (MSASD) concept is advantageous with high-output voltages. MSASD technology performs better than LCI-based solutions, particularly with long cables [14,15].
A statistical analysis of medium-large induction machines was used to study uncertainties associated with scaling starting currents. The discrepancies between finite element model simulations and measurements increased with increasing test voltage, mostly negative due to incorrect saturation modeling. Parametric dependencies showed the tooth/airgap, end-region, and end-core regions most contributed to saturation modeling uncertainty [16,17,18].
Voltage sags due to motor starting on weak transmission networks pose challenges to rate-based utilities, especially when the load is far from generation. Static synchronous compensator (STATCOM)-based solutions mitigate motor starting voltage sags, but size and device specifications must be optimized based on transient performance, system losses, and successive motor start capability. While all devices met minimum requirements, a device based on open-loop reactive current control was chosen for its better transient performance, lower system losses, and successive motor start capability [19,20,21,22].
In Ref. [23], an analytical and convex optimization model representing the starting transients of the induction motor is used to find the optimal energization sequence of different loads following an outage in a distribution network.
In Ref. [24], a new VS classification method uses the transient finite element method (FEM) nonlinear solver. This proposal uses the Jiles–Atherton vector hysteresis model to improve precision, considering transformer windings and short circuits. Its accuracy is shown by comparing the proposed method, FEM, and other approaches with IEC data. The best connections for transformer windings are identified by the IM speed and torque variations.
2. System Description, Simulation, and Analysis
The system under study includes eight similar MV three-phase induction motors rated 1795 kW, 11 kV, which are connected to the network via the same busbar with properly designed and chosen protection instruments. The motors are usually DOL started in sequence with predefined time intervals between each two successive motors to ensure complete starting status rather than avoiding any overlap. Even though the starting interval is considered, the grid power quality deteriorates. Firstly, the system performance in addition to the grid power quality and load flow study are studied for DOL operation. Secondly, different starting scenarios are applied to fulfill the motor operation in addition to maintaining the power quality in a specified margin. An economic cost study will be introduced considering the high cost of the required VVVFD unit required for each motor. The complete system details, including the nameplate data for motors, utility parameters and transformer parameters, are tabulated in Appendix A. In addition, the details referring to VFD are set out in tabular form in Appendix B.
2.1. System Proposed Analysis
A detailed comparison between the proposed starting scenarios and the traditional DOL starting is performed. In each case the motor performance including line current, motor developed torque, and speed will be investigated. In addition, the power grid quality will be studied including power flow, short circuit analysis, power factor, and voltage dips. The detailed analysis steps are listed below:
Simulate the starting process with DOL of eight MV induction motors using ETAP, study the motor performance during starting period with VVVFD, study the motor performance when only four motors are started with DOL to the grid, where the other four motors are fed from VVVFD; and an economic study will be introduced.
2.2. System Model with ETAP
The system model is simulated using ETAP power station to study and investigate its overall performance, especially during the starting intervals. The system under test is composed of eight MV induction motors. Firstly, the existing status is analyzed with a clear power quality inspection and deeper assessment. Power quality at the busbar for the incoming power from transformers is being studied as it reflects the main issue of the study. The system of eight MV induction motors was presented alongside its mechanical load representation, which is the pumping system with load characteristics, as shown in Figure 1.
Figure 1.
Motor soft start with current limiting.
The centrifugal pump used in the station has square torque–speed characteristics. Initially, a small portion of the load torque is required to overcome the mechanical rest losses, which is usually 20% of the full load value. The pump torque subsequently drops to 10% of the rated value when reaching a speed of approximately 15% of the rated pump speed as shown in Figure 1. An ideal characteristic only provides a square relation from the standstill up to the rated operation, which is not realized in practice, as shown in Figure 2.
Figure 2.
Pump torque–speed characteristics.
2.3. Pump Load Torque Characteristics Model
According to the previous analysis, the pump torque–speed characteristics are approximately represented by a polynomial function. The first approach provides the torque–speed relation by:
To have the real pump characteristics, the polynomial coefficients are given by:
Another approach to verify the zero-torque rate at the lowest speed value (15% of the rated) is given by the equation:
The polynomial coefficients are given by:
The ideal square proportional case, real case with second order, and the third order polynomial are represented by the curves shown in Figure 2.
The load torque is represented by the equation:
According to the existing load pump performance characteristics, the equation constants are:
It is more convenient to adopt the previous analysis of the load to be properly implemented when the ETAP load profile is introduced.
Figure 3 shows the procedure for each starting scenario, as explained in Section 2.1. The following procedure will be carried out for each starting scenario. Firstly, set up the connection and settings for the current starting scenario in ETAP. Secondly, identify the proper SLD. Power flow study is then performed for the system. Power quality performance characteristics are finally discussed. Voltage dip, power factor, efficiency, motor speed and torque are all important factors.
Figure 3.
Overall performance assessment of sequential DOL start of multi MV induction motors.
2.4. Basic Scenario (DOL Starting) of MV Motors
Figure 4 shows the SLD of the starting process in the ETAP environment for eight similar MV induction motors rated 1795 kW, 11 kV.
Figure 4.
ETAP model and load flow of sequential DOL start of multi MV induction motors.
As demonstrated in Figure 5 and Figure 6, the comprehensive performance metrics encompass current, torque, speed, and power quality parameters during starting of the test motors with a DOL connection to the power grid. As illustrated in Figure 5a, the initial current for the first motor in the group of eight motors reaches 550% of the rated current, increasing by almost 10% during each starting period for each motor in the group. As demonstrated in Figure 5b, it is evident that each motor attains an approximate 550% increase in starting current during its own starting process, and a 10% rise in current during the DOL starting process for other motors.
Figure 5.
Current performance of DOL of eight all MV induction motors.
Figure 6.
Performance of sequentially DOL-starting MV induction motors.
As demonstrated in Figure 6a, the starting torque reaches 220%, and then decreases by 15% with each subsequent starting motor. Also, Figure 6b shows the initial motor undergoes a 2% decrease in speed with each subsequent starting motor. It is important to note that with every DOL start, there is a 2.5% voltage dip, and the maximum voltage dip after the last successive start is 4.5% as demonstrated in Figure 6c. Also, a 0.25% voltage drop is observed after each starting period, with a maximum of 2.2% voltage drop after starting all motors. Figure 6d presents the power factor of the supply generator/network during successive DOL starting, indicating that an excessive dip during the initial starting period reaches 60%, which subsequently decreases to reach 35% dips in power factor during subsequent periods. As demonstrated in Figure 6e, there is a marked increase in the demand for active and reactive power from the generator/network during DOL starting periods. The initial starting period is characterized by a substantial increase in reactive power, reaching a maximum of 12.5 MVAR, while the subsequent periods exhibit a more modest rise, culminating in 25 MVAR during the final starting period. The initial starting periods exhibited an increase in active power of 18 MW, while the subsequent periods demonstrated a rise of 28 MW. As illustrated in Figure 6f, the reactive power drawn by the first motor is 11 MVAR, which then decreased to 800 KVAR after the starting period, while the active power drawn by the first motor during the starting period reaches 9 MW, then reduced to 2 MW after the starting period. Figure 6g shows the bus voltage waveform, and its spectrum analysis is depicted in Figure 6h.
2.5. Second Scenario (VFD Starting) of MV Motors
The motors are sequentially soft started via VFD soft start with proper setting of the relation between both starting voltages and frequencies. The properly used starting shift time is set at 5 s. As demonstrated in Figure 7 and Figure 8, the comprehensive performance metrics encompass current, torque, speed, and power quality parameters during starting of eight MV induction motors with the aid of a VFD.
Figure 7.
Current performance of VFD of all eight MV induction motors.
Figure 8.
Performance of sequentially VFD-starting MV induction motors.
As illustrated in Figure 7a, the initial current for the first motor in the group of eight motors is limited to 150% of the rated current, increasing by almost 1.5% during each starting period for each motor in the group. As demonstrated in Figure 7b, it is evident that each motor remains limited to 150% starting current during its own starting process, and a 1.5% rise in current during the VFD starting process for other motors.
As demonstrated in Figure 8a, the starting torque is limited to 150%. Also, Figure 8b shows that there is no initial decrease in the motor speed with each subsequent starting motor and the motor speed reaches its rated value without any overshoots as the motor builds up its speed linearly and smoothly. It is important to note that with every VFD start, the voltage dips recorded 1.3%, as demonstrated in Figure 8c; also, an overall voltage drop after starting all motors with VFD is 2.2%. Figure 8d presents the power factor of the supply generator/network during successive VFD starting, indicating that the dips in power factor during starting periods almost disappeared with VFD and the overall reduction in power factor is 4.5%.
As demonstrated in Figure 8e, the overshoot in apparent and reactive power of the generator/network during VFD starting periods almost disappeared. The starting period is characterized by a smooth power transition without any excessive overshoots in neither apparent nor reactive power. As illustrated in Figure 8f, the reactive power drawn by the first motor does not exceed the rated values during starting periods. Figure 8g shows the bus voltage waveform, and its spectrum analysis is depicted in Figure 8h.
2.6. Third Scenario (Mixed DOL and VFD Starting) of MV Motors
In this scenario, different alternatives are implemented. Four motors are DOL started, while the remaining are VFD started. As demonstrated in Figure 9 and Figure 10, the comprehensive performance metrics encompass current, torque, speed, and power quality parameters during the starting of four MV induction motors starting with DOL and the other four MV motors started with the aid of a VFD. As illustrated in Figure 9a, the initial current for the first motor in the group of four motors with DOL is increased to 550% of the rated current and increases by almost 150% during each starting period for each motor in this group. As demonstrated in Figure 9b, it is evident that each motor remains limited to 150% starting current during its own starting, and a 1.5% rise in current during the VFD starting process for other motors.
Figure 9.
Current performance of 4-DOL- and 4-VFD-started MV induction motors.
Figure 10.
Performance of alternatively sequential VFD- and DOL-starting MV induction motors.
As demonstrated in Figure 10a, the starting torque is overshot to 220% for motors starting with DOL and limited to 150% for motors starting with VFD. Also, Figure 10b shows that there is no initial decrease in the motor speed with each subsequent starting motor and the motor speed reaches its rated value without any overshoots as the motor builds up its speed linearly and smoothly. It is important to note that with every DOL start, the voltage dips by 2.2% and the overall voltage drop due to starting four motors with DOL and another four motors with VFD is 2.5%, as demonstrated in Figure 10c. Figure 10d presents the power factor of the supply generator/network during successive DOL and VFD starting, indicating that the dips in power factor during starting periods almost disappeared with VFD and reappeared with DOL with a 65% dip. As illustrated in Figure 10f, the reactive power drawn by the first motor does not exceed the rated values during starting periods. Figure 10g shows the bus voltage waveform, and its spectrum analysis is depicted in Figure 10h.
3. Contributions
The contribution in this section focuses on the optimization process for selecting the number of DOL- and VFD-started motors will be introduced. The motors are started with a VFD, introducing better performance, but extra cost may be added due to the implementation of the VFD drives with properly specified characteristics. An objective function is proposed for the optimization of both cost and performance. The objective is to have better grid performance, primarily in power quality metrics (power factor or THD). The theoretically possible scenarios of operating the motors either DOL or via VFD drive are usually 28, which are 265 possibilities. Although these values are actual, some repeated cases or cases having the same effect on both the motor and grid are excluded. Figure 11 illustrates the definition of voltage dips and voltage drops in such a starting process. Finally, ten possibilities are implemented as shown in Table 1. The system performance, including the effect of harmonics and fluctuations in both motor current and developed torque, is studied. The power grid metrics such as voltage dip, voltage drop, voltage THD, current THD, and related cost for each case are studied and conducted to obtain results in Table 1. When equal importance of parameters is achieved in an optimization process, the assignment of a 50 percent weight to an objective function is adopted, which is based on a standard practice used to achieve equal importance, or precisely, parameter neutrality between different goals. This prevents prioritization of certain goals over others. Accordingly, these values may vary due to the expertise or literally the goal request of objective function competencies based on operator requests and major concerns regarding competencies. The weighted sum method concerns this approach; consequently, users may adopt other values (40–60%), for instance, based on the importance of goals. The weighted sum method provides neutrality, relative balance, smooth interpretation, and normalization needs [25,26,27,28]. The assumed cost was 100% for used DOL, adding 25% extra when a VFD unit was implemented [29].
Figure 11.
Voltage drop and voltage dip during starting.
Table 1.
Possible operating scenarios.
Basically, different values of both voltage and current THDs are associated with the starting sequence rather than just implementing DOL or VFD during starting. To distinguish this issue, the four basic buses of concern; BUSN1: bus at utility, BUSTF: bus feeding transformer, BUS00: main feeding bus, BUS0X: motor (X) terminals feeding bus, and BUSLL: lumped load bus are studied and discussed for both voltage and current THDs. The simulated values are given in Table 2 and Table 3, respectively. Voltage and Current THDs are plotted in Figure 12 and Figure 13 respectively for visualization concerning all scenarios. It is to be noted that scenarios five and ten pose the same results as the number of DOL and VFD started motors is the same with a proper equal transition interval between all motors. This will be divergent if the transition interval between starting actions has any overlap.
Table 2.
Percentage voltage THD at different buses.
Table 3.
Percentage current THD at different buses.
Figure 12.
Voltage THD variation at different buses.
Figure 13.
Current THD variation at different buses.
3.1. Optimization Function
Next, we introduce the optimization for motor starting techniques, including VFD. The optimization process will inform the objective regarding which metrics are more significant. The inputs will include the cost as a primary interest and one or two of the system metrics, such as power factor or THD, for either voltage or current. Different possibilities used as inputs to the optimizer are shown in Figure 14. The main source for the training data is the results shown in Table 1. The constraints are defined for the range of power factors, voltage drop, and maximum starting current.
Figure 14.
Possible objective functions.
The optimizer will search for the optimal solution within the 256 possibilities to ensure the right decision. For simplicity, as mentioned before, some scenarios may be omitted due to resemblance and expected results. Figure 15 shows the performance metrics for selected possible scenarios.
Figure 15.
Performance metrics for properly selected possible scenarios.
3.2. White Shark Optimizer (WSO)
The suggested WSO has the advantage of handling various optimization difficulties. WSO can handle many problems while requiring fewer parameters, due to its simplicity, flexibility, and robustness. Furthermore, WSO can identify the global solution for challenging optimization problems quickly and accurately. The mathematical model of the WSO is discussed and explained in this section to represent the behavior of white sharks during foraging, including tracking and hunting prey [30]. The initial population is created in the search domain with a uniform random initialization as:
where represents the initial position vector corresponding to the ith white shark in the ith dimension, while uj and lj, respectively, represent the upper and lower boundaries of the search domain in that dimension. The term r refers to a stochastic variable uniformly distributed over the interval [0, 1]. Each candidate solution is evaluated through a predefined fitness function. The position of a white shark is updated only if the new location provides superior fitness; otherwise, the current position is preserved. White sharks spend most of their time hunting, using their sharp senses of hearing, sight, and smell to detect prey. They locate it through wave disturbances caused by its movement and approach it in an undulating path, as defined in Equation (9).
where i = 1, 2, …, n is the index of the ith shark in a population of size n. and denote the new and current velocity vectors of the shark at steps (k + 1) and kth, respectively. is the best global position found up to iteration kth, while is the current position of the shark. represents the best-known position in the neighborhood, with being the index of the shark that achieved it. c1 and c2 are random numbers in [0, 1], determined by Equation (10), and represent the forces of the white sharks that control the effect of and on respectively, which are computed as given in Equations (11) and (12), respectively, and μ denotes the constriction factor introduced in WSO to examine the convergence behavior of white sharks, as defined in Equation (13).
where k and K denote the current and maximum number of iterations, respectively. Pmin and Pmax represent the lower and upper velocity limits that regulate the sharks’ motion, with their values determined by analysis as 0.5 and 1.5, respectively.
where τ represents the acceleration coefficient, determined through rigorous analysis to be 4.125. The behavior of white sharks toward prey is described in Equation (14).
Vectors a and b are binary arrays defined as given by Equations (15) and (16) respectively, wo is a logical vector specified in Equation (17), and f is the frequency of the wavy motion defined as described in Equation (18) and is formally defined in Equation (19). The variable rand is a random number in [0, 1], while mv is the movement force that increases with iterations, reflecting the shark’s approach toward prey, and is formally defined in Equation (19).
where fmin and fmax denote the minimum and maximum frequencies of the undulating motion, respectively, and rand is a uniformly distributed random number in [0, 1]. In this study, fmin = 0.07 and fmax = 0.75, values are determined through analysis and adaptable to various problems.
where a0 = 6.25 and a1 = 100 regulate the shift between exploration and exploitation, while mv represents the shark’s prey-detection ability, which intensifies with iterations. Great white sharks can maintain their position towards the best one that is close to prey. This behavior is formulated as shown in Equation (20).
The term sgn(r2 − 0.5) returns either 1 or −1 to alter the search direction. The variables r1, r2, and r3 are random numbers uniformly distributed in [0, 1]. The vector Dw represents the distance between the prey (food source) and the shark, as defined in Equation (20). Finally, Ss is a parameter that characterizes the strength of smell and sight senses when sharks follow others in proximity to the optimal prey, as formulated in Equation (21).
Selecting governs the balance between exploration and exploitation.
The collective behavior of white sharks is mathematically modeled by retaining the two best solutions, while updating the positions of the remaining sharks relative to these optimal solutions, as expressed in Equation (23).
A flow chart for WSO optimization of starting the MV motor is shown in Figure 16.
Figure 16.
Flow chart for WSO optimization of starting MV motor selection scheme.
3.3. Case Studies
Applying the WSO algorithm for different cases checks the effectiveness and reliability of the cost function. In each case, the optimal number of used DOL and VFD started motors was implemented. Users, as mentioned before, are free to adopt their importance factors according to their effectiveness rather than the power quality metrics concerned. Figure 17, Figure 18 and Figure 19 show optimization results for three chosen different operating cases, showing the optimal number of MV induction motors to be started with VFD based on the operating conditions, and characteristics parameters based on the different possible operating scenarios tabulated in Table 1 and Figure 14.
Figure 17.
Results for using WSO for case 1.
Figure 18.
Results for using WSO for case 2.
Figure 19.
Optimization performance of WSO and PSO algorithms for VFD motor selection (case 3).
CASE 1:
In this case, the main objective is determining the optimal distribution of MV induction motors started by either VFD or DOL, using the WSO algorithm in order to operate the system efficiently with acceptable voltage drop, a good power factor, and minimum total cost depending on what the user considers most important.
where
. In this case , and .
The results show that the optimal number of MV induction motors started via VFD is one motor and seven motors started with DOL that achieve minimum voltage drop, cost, and improved pf. Both algorithms converge to nearly the same optimal objective value (approximately 0.299). However, the PSO algorithm reaches the optimal value faster, while the WSO algorithm requires a few additional iterations before stabilizing at the global optimum, as shown in Table 4 and Figure 17.
Table 4.
Statistical results of WSO and PSO algorithms for motor optimization problem.
CASE 2:
In this case, the main objective is the same as in case 1, as shown in Equation (24), but with different weighting factors, where , , and . The optimization results demonstrate that the optimal configuration consists of two motors started via VFD, while the remaining six motors are started via DOL. This combination achieves the minimum voltage drop, reduced cost, and improved power factor. Both WSO and PSO algorithms successfully converge to nearly identical optimal objective values (approximately 0.377966), as illustrated in Table 4 and Figure 18. However, a notable difference in convergence behavior is observed: PSO exhibits faster convergence to the global optimum, whereas WSO requires slightly more iterations before stabilization.
CASE 3:
The main objective in this case is to concentrate on minimizing the total cost and improving power factors.
where
. In this case, and .
The results demonstrate that both WSO and PSO achieved the same optimal solution (3 VFD and 5 DOL motors) with identical objective values and zero standard deviation, indicating high stability. However, PSO is slightly faster in execution time than WSO, as depicted in Table 4 and Figure 19.
A comprehensive comparison was performed between the proposed WSO and the well-established PSO algorithm, as tabulated in Table 4. Both algorithms were executed for 30 independent runs under identical conditions (population size = 10, maximum iterations = 30) for different cases. Adding other optimization techniques or algorithms will result in a slight variation in both objective functions and results. The advantage of one algorithm over others will be the accuracy of execution rather than the time to reach the objective function output, without any expected change in the output decision of the number of DOL and VFD drive-started motors.
Since the case here is the starting issue of eight identical motors, all suggested algorithms will result in convergent outputs. In contrast, if the plant includes a larger number of motors or motors with non-identical specifications, the result will differ. In future work, the authors will conduct an analogous study on different motor types included in one plant or study two or more plants including different power-rated motors at the same time.
4. Conclusions
In this article, a new modified and comprehensive starting scheme for MV three-phase induction motors driving pumps for a water station was implemented, analyzed, and discussed. Firstly, the starting performance and its impact on power grid quality were discussed for the case where all motors are normally started with DOL, which is the current status. The results show that excessive starting current with DOL reaches 550% of the rated current with a starting torque of 220%. A speed drop occurs at starting due to the load performance when starting the first motor; also, voltage dips of 2.5% were recorded for each DOL start, and the overall voltage dip during starting with DOL was 4.5%. Voltage drops during the starting period for the eight motors recorded 0.2% for each motor starting and an overall voltage drop of 2.2% for the same case. Starting all motors with a VFD was simulated in the ETAP environment, showing improved performance; the starting current was limited to 150% and the starting torque was limited to 130%. The VFD was able to overcome the speed drop during the starting period, and voltage dips almost disappeared. Also, the implementation of starting only four MV motors with DOL and the others with VFD was simulated; the results showed a good performance, as the overall voltage dip was 2.2% for each starting motor with DOL and the overall voltage drop reached 2.5% during the stating process. A modified starting scheme based on an optimized coordination of motor starting methods—in addition to VFD drive and control implementation—was also discussed. A transition between the starting of variant MV induction motors as well as the coordination principle were discussed in detail to improve the power quality. The coordination algorithm is achieved using different artificial intelligence techniques, considering the transition time in addition to the power delivered by the inverter unit. A comparison between the optimized VFD soft-starting, and the proposed modified scheme was performed, focusing on the power quality improvement rather than solely optimizing the cost function. The modified scheme was simulated using ETAP for a brief analysis and study of load flow rather than a complete inspection and study of the power quality.
Author Contributions
Conceptualization, A.R., E.M.A. and H.S.; methodology, H.S. and M.E.E.; software, H.S. and E.M.A.; validation, A.R., M.E.E. and H.S.; formal analysis, A.R. and E.M.A.; investigation, E.M.A. and M.E.E.; resources, A.R.; data curation, A.R. and H.S.; writing—original draft preparation, A.R. and M.E.E.; writing—review and editing, E.M.A. and H.S.; visualization, E.M.A. and H.S.; supervision, A.R. and H.S.; project administration, H.S. All authors have read and agreed to the published version of the manuscript.
Funding
This research received no external funding.
Data Availability Statement
Data procced in this article will be available upon request via corresponding author.
Conflicts of Interest
All persons who meet authorship criteria are listed as authors, and all authors certify that they have participated sufficiently in the work to take public responsibility for the content, including participation in the concept, design, analysis, writing, or revision of the manuscript. Furthermore, each author certifies that this material or similar material has not been and will not be submitted to or published in any other publication before its appearance in the Electricity.
Abbreviations
| ANN | Artificial Neural Networks |
| CVSRT | Critical Voltage-Sag Removal Time |
| DOL | Direct On Line |
| FEM | Finite Element Method |
| HIL | Hardware-In-the-Loop |
| LCI | Load Commutated Inverter |
| MVIM | Medium Voltage Induction Motors |
| PSO | Particle Swarm Optimizer |
| SCR | Silicon-Controlled Rectifier |
| SOCP | Second Order Cone Programming |
| SSASD | Soft Start/Adjustable Speed Drive |
| STATCOM | Static Synchronous Compensator |
| THD | Total Harmonic Distortion |
| VFD | Variable Frequency Drive |
| VSD | Variable Speed Drive |
| VVVFD | Variable Voltage Variable Frequency Drive |
| WSO | White Shark Optimizer |
Appendix A. Complete System Details
Table A1.
Parameters of the system under test.
Appendix B. VFD Details
Table A2.
Parameters of VFD.
Figure A1.
Operation modes of frequency control of AC motors.
Figure A2.
Schematic of VFD Converter.
References
- Matanov, N. Study of the impact of induction motors starting on the supply voltage. In Proceedings of the 2019 16th Conference on Electrical Machines, Drives and Power Systems (ELMA), Varna, Bulgaria, 6–8 June 2019; pp. 1–5. [Google Scholar] [CrossRef] [Scilit]
- Yang, C.; Lee, B.S.; Jang, G.; Kim, S.; Jung, G.; Lee, J.; Shim, S.; Lim, Y.K.; Kim, J.; Park, S. Starting Current Analysis in Medium Voltage Induction Motors: Detecting Rotor Faults and Reactor Starting Defects. IEEE Ind. Appl. Mag. 2019, 25, 69–79. [Google Scholar] [CrossRef] [Scilit]
- Ćalasan, M.P. An invertible dependence of the speed and time of the Induction machine during no-load direct start-up. Automatika 2020, 61, 141–149. [Google Scholar] [CrossRef] [Scilit]
- Guentri, H.; Bouchra, B.; Bouchra, B.; Kabira, E. The impact of motor starting on the quality of the industrial electricity network. ITEGAM-J. Eng. Technol. Ind. Appl. ITEGAM-JETIA 2020, 6, 41–51. [Google Scholar] [CrossRef] [Scilit]
- VanderMeulen, A.H.; Natali, T.J.; Dionise, T.J.; Paradiso, G.; Ameele, K. Exploring New and Conventional Starting Methods of Large Medium-Voltage Induction Motors on Limited kVA Sources. IEEE Trans. Ind. Appl. 2019, 55, 4474–4482. [Google Scholar] [CrossRef] [Scilit]
- LeDoux, K.; Visser, P.W.; Hulin, J.D.; Nguyen, H. Starting Large Synchronous Motors in Weak Power Systems. IEEE Trans. Ind. Appl. 2015, 51, 2676–2682. [Google Scholar] [CrossRef] [Scilit]
- Xia, Y.; Du, H.; Yongsen, H.; Ai, M. Study on Transient Torque, Current Characteristics and Temperature Rise of Medium High-voltage Induction Motor under Different Load Modes. In Proceedings of the 2019 22nd International Conference on Electrical Machines and Systems (ICEMS), Harbin, China, 11–14 August 2019; pp. 1–4. [Google Scholar] [CrossRef] [Scilit]
- Damjanovic, A. Protection of Medium Voltage SCR Driven Soft-Starter from High-Frequency Switching Transients. IEEE Trans. Ind. Appl. 2016, 52, 4652–4655. [Google Scholar] [CrossRef] [Scilit]
- Kashif, S.A.R.; Saqib, M.A. Soft starting of induction motors using neuro fuzzy and soft computing. In Proceedings of the 2008 Second International Conference on Electrical Engineering, Lahore, Pakistan, 25–26 March 2008; pp. 1–7. [Google Scholar] [CrossRef] [Scilit]
- Ellis, R.G.; Seggewiss, J.G.; Paes, R.H.; Kay, J.A. Methods for the control of large medium-voltage motors: Application considerations and guidelines. IEEE Trans. Ind. Appl. 2000, 36, 1688–1696. [Google Scholar] [CrossRef] [Scilit]
- El-Hayes, M.; Gouda, E.; Abdelkader, S. Practical Transient State Assessment for Induction Motors Starting in Medium Voltage Networks. Mansoura Eng. J. 2020, 44, 1–9. [Google Scholar] [CrossRef] [Scilit]
- Kucuk, S.; Ajder, A. Analytical voltage drop calculations during direct on line motor starting: Solutions for industrial plants. Ain Shams Eng. J. 2022, 13, 101671. [Google Scholar] [CrossRef] [Scilit]
- Zenginobuz, G.; Cadirci, I.; Ermis, M.; Barlak, C. Performance Optimization of Induction Motors During Voltage-Controlled Soft Starting. IEEE Trans. Energy Convers. 2004, 19, 278–288. [Google Scholar] [CrossRef]
- Endrejat, F.; Pillay, P. Soft Start/Adjustable Speed Systems for Multiple MW Rated Motors. In Proceedings of the 2006 Record of Conference Papers—IEEE Industry Applications Society 53rd Annual Petroleum and Chemical Industry Conference, Philadelphia, PA, USA, 11–15 September 2006; pp. 1–10. [Google Scholar] [CrossRef] [Scilit]
- Rüncos, F.; Bachmeyer, M.; Sarris, M.; Stafford, A. High Torque Low Inrush Current Motor Design or Voltage Recovery Dependance for Loaded Start Conditions. In Proceedings of the 2022 IEEE IAS Petroleum and Chemical Industry Technical Conference (PCIC), Denver, CO, USA, 26–29 September 2022; pp. 521–531. [Google Scholar] [CrossRef] [Scilit]
- Arshad, W.M.; Kanerva, S.; Bono, S.; Menescardi, M.; Persson, H. Medium-Large Induction Machines Starting Currents: Scaling Accuracy & Saturation Uncertainties. In Proceedings of the 2007 IEEE Industry Applications Annual Meeting, New Orleans, LA, USA, 23–27 September 2007; pp. 2269–2276. [Google Scholar] [CrossRef] [Scilit]
- Habyarimana, M.; Dorrell, D.G. Methods to reduce the starting current of an induction motor. In Proceedings of the 2017 IEEE International Conference on Power, Control, Signals and Instrumentation Engineering (ICPCSI), Chennai, India, 21–22 September 2017; pp. 34–38. [Google Scholar] [CrossRef] [Scilit]
- Aree, P. Precise analytical formula for starting time calculation of medium- and high-voltage induction motors under conventional starter methods. Electr. Eng. 2018, 100, 1195–1203. [Google Scholar] [CrossRef] [Scilit]
- Ramamurthy, J.R.; Kolluri, S.; Mader, D.J.; Camm, E. Mitigation of Motor Starting Voltage Sags Using Distribution-Class STATCOM. In Proceedings of the 2018 IEEE/PES Transmission and Distribution Conference and Exposition (T&D), Denver, CO, USA, 16–19 April 2018; pp. 1–9. [Google Scholar] [CrossRef] [Scilit]
- Padimiti, D.S.; Christian, M.B.; Jarvinen, J. Effective Transient-Free Capacitor Switching (TFCS) for Large Motor Starting on MV Systems. IEEE Trans. Ind. Appl. 2019, 55, 1012–1020. [Google Scholar] [CrossRef] [Scilit]
- Hermawan, I.B.; Ashari, M. Modelling of Distribution Compensator for Inrush Current of Medium Voltage Induction Motor in an Air Separation Plant Power Systems. In Proceedings of the 2019 International Seminar on Intelligent Technology and Its Applications (ISITIA), Surabaya, Idonesia, 28–29 August 2019; pp. 155–158. [Google Scholar] [CrossRef] [Scilit]
- Aree, P. An analytical approach for calculating critical voltage-sag removal time of induction motors using manufacturer technical data. Electr. Eng. 2020, 102, 359–370. [Google Scholar] [CrossRef] [Scilit]
- Sekhavatmanesh, H.; Rodrigues, J.; Moreira, C.L.; Lopes, J.A.P.; Cherkaoui, R. Optimal Load Restoration in Active Distribution Networks Complying with Starting Transients of Induction Motors. IEEE Trans. Smart Grid 2020, 11, 3957–3969. [Google Scholar] [CrossRef] [Scilit]
- Seyedshenava, S.; Ahmadpour, A. Finite element method for optimal transformer connection based on induction motor characteristics analysis. Ain Shams Eng. J. 2021, 12, 1943–1957. [Google Scholar] [CrossRef] [Scilit]
- Rao, R.V.; Taler, J. (Eds.) Advanced Engineering Optimization Through Intelligent Techniques; Springer Nature: Singapore, 2023. [Google Scholar] [CrossRef] [Scilit]
- Ghosh, A.; Mal, P.; Majumdar, A. Advanced Optimization and Decision Making Techniques in Textile Manufacturing; CRC Press: Boca Raton, FL, USA, 2019. [Google Scholar]
- Barwasser, A.; Lentes, J.; Riedel, O.; Zimmermann, N.; Dangelmaier, M.; Zhang, J. Method for the development of Software-Defined Manufacturing equipment. Int. J. Prod. Res. 2023, 61, 6467–6484. [Google Scholar] [CrossRef] [Scilit]
- Fidanova, S. (Ed.) Recent Advances in Computational Optimization; Springer International Publishing: Cham, Switzerland, 2022; Volume 1044. [Google Scholar] [CrossRef] [Scilit]
- Miller, P.; Olateju, B.; Kumar, A. A techno-economic analysis of cost savings for retrofitting industrial aerial coolers with variable frequency drives. Energy Convers. Manag. 2012, 54, 81–89. [Google Scholar] [CrossRef] [Scilit]
- Braik, M.; Hammouri, A.; Atwan, J.; Al-Betar, M.A.; Awadallah, M.A. White Shark Optimizer: A novel bio-inspired meta-heuristic algorithm for global optimization problems. Knowl. Based. Syst. 2022, 243, 108457. [Google Scholar] [CrossRef] [Scilit]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2026 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.