Influence of Photovoltaic Module Degradation on Photovoltaic Power Plant Investment Payback Time †

,
,
and
Faculty of Electrical Engineering, Computer Science and Information Technology Osijek, Josip Juraj Strossmayer University of Osijek, 31000 Osijek, Croatia
*
Author to whom correspondence should be addressed.
†
Presented at the 34th International Scientific Conference on Organization and Technology of Maintenance (OTO 2025), Osijek, Croatia, 12 December 2025.

Abstract

This paper presents a methodology for assessing the impact of photovoltaic (PV) module degradation on the payback time of PV power plant investment in a prosumer power system. The methodology uses PV module performance measurements to determine the current degradation level and compares it to the manufacturer-defined degradation level during its lifetime. This represents input data for the PV power plant simulation model, which determines its performance during its lifetime and the investment payback time. The proposed methodology is evaluated using experimental measurements of the performance of two 10-year-old PV modules from the commercially most widely used technologies. The performance measurements on PV modules indicate that the current degradation level does not align with the manufacturer’s defined one. Equal-size models of PV power plants are created in PVSOL Premium software to analyze the impact of manufacturer-defined and real-life degradation on the payback time of PV power plant investments. The simulations confirmed that this influences the payback time of investments, emphasizing the importance of choosing a high-quality PV module during planning and installation.

1. Introduction

The degradation of PV modules is affected by numerous environmental factors. Although the performance of PV plants largely depends on the design and manufacturing quality of the cells, outdoor installations face diverse environmental conditions that may cause both lasting and temporary reductions in performance [1].
The main characteristics of solar irradiance impacting PV modules are its intensity, spectral composition, and angle of incidence. High-energy photons of ultraviolet (UV) light are particularly harmful to polymeric materials over time leading to polymer embrittlement and discoloration [2]. Temperature is an environmental stressor for PV modules. Cell temperatures often exceed ambient levels due to solar irradiance, with heat dissipation influenced by module design, material properties, wind speed, and installation setup [3,4]. Moisture is another stress factor for PV modules. Outdoors, moisture appears as humidity, condensation, rain, snow, or ice. Water vapor can permeate polymer layers and accumulate inside the module, accelerating component degradation, while liquid water from dew or rain can also be absorbed or released by the materials [5,6,7].
Atmospheric deposits such as dust, pollution, sea salt, pollen, and organic debris can accumulate on PV panel surfaces and block sunlight, reducing energy output [8]. Dust, for example, is one of the most common atmospheric deposits where frequent dust storms can cause energy losses of up to 50% [9].
Shading is a major environmental factor that can greatly reduce PV system performance. It occurs due to obstructions like vegetation, buildings, or clouds, and even small shaded areas can cause significant power losses because of how solar cells are connected [8]. Recent research shows that partial shading from objects, vegetation, or terrain can cause power losses of 45% to 85%, depending on shadow severity and distribution [10].
Besides environmental stress, internal factors such as module design, materials, and manufacturing processes also affect PV module degradation. The lamination process is particularly crucial for ensuring quality and long-term reliability. Studies show that better encapsulation quality improves module reliability [3]. Poor manufacturing processes are often the main cause of PV module failures in the field. For example, thermal stress during stringing and lamination can create microcracks in solar cells [11,12]. Excessive thermal expansion of EVA during lamination can shift solar cells, widen gaps, and add stress to PV ribbons and solder bonds [12,13].
Based on the literature review, various studies have focused on factors that influence the degradation of PV modules and their performance. However, there is a gap in the literature, where this paper’s contribution lies, that analyzes the difference between expected (manufacturer-defined) and real-life degradation of PV modules. Furthermore, this paper observes the long-term effects of degradation on the entire PV plant’s performance and its investment payback time.
The remainder of this paper is organized as follows: Section 2 presents the methodology for assessing the influence of real-life degradation on the payback time of PV plant investment. Section 3 describes and presents results of the field testing of PV modules. Section 4 describes modeling and analysis of the influence of PV module degradation on investment payback time. Finally, conclusive remarks are given in Section 5.

2. Methodology

The proposed methodology (Figure 1) comprises multiple steps in determining the final influence of real-life degradation on performance and the payback time of PV plant investment. The first step implies field testing of PV module performance according to the IEC/EN 62446 standard. Following this, the post-analysis of field measurements assessed the performance of PV modules and the current level of degradation. Based on these results, a PV plant model in a prosumer power system was modeled in a software tool for two cases: based on manufacturer-defined and measured degradation. Finally, a software tool was used to simulate prosumer performance, as well as its PV plant, throughout its lifetime to determine the influence of degradation on the investment payback time.
Figure 1. Flowchart diagram of the proposed methodology.

3. Field Testing of PV Modules

Field testing of PV module performance was performed on two locations using the Metrel MI 3108 PV tester. Metrel MI 3108 PV tester enables testing and evaluation of PV modules according to the IEC/EN 62446 standard. This means that the measured values of electrical parameters, based on the current environment parameters of solar irradiance and module temperature, are estimated at the Standard Test Conditions (STCs) and compared to the nominal values defined by the manufacturer for the new PV module.

3.1. Location 1

The first location represents a 10-year-old 6 kWp PV plant consisting of 30 monocrystalline silicon ET-M572200WW PV modules with a rated power of 200 Wp . The PV plant is located in the vicinity of the city of Slavonski Brod in Croatia. Performance measurements were made on an arbitrarily selected module in the PV array. Before testing, all modules were cleaned and washed. Table 1 shows numerical field test results, while Figure 2 shows measured, STC-estimated, and nominal current-voltage and power-voltage characteristics of the ET-M572200WW PV module. Results presented in Table 1 show that STC estimated results are very close to the nominal ones defined by the manufacturer for the new module. The STC estimated power is 4 W lower than the nominal.
Table 1. ET-M572200WW PV module numerical field test results.
Figure 2. Measured, STC-estimated and nominal current-voltage (a) and power-voltage (b) characteristics of ET-M572200WW PV module.
Manufacturer of the ET-M572200WW PV module offers 25-year linear performance warranty resulting with the 81.4% of nominal power at the end of its 25-year lifetime, starting with 97% in the first year [14]. According to the field measurements and age of 10 years, PV module output resulted with 98% of nominal power. After linear extrapolation of measured degradation to the 25th year, this gives the expected output power of the 94.5% at the end of its lifetime. Based on the linear degradation assumption, it can be concluded that the PV module performs better than expected. A graphical representation of measured and manufacturer-defined degradation of ET-M572200WW PV module is shown in Figure 3.
Figure 3. Comparison of manufacturer-defined and measured degradation of ET-M572200WW PV module.

3.2. Location 2

The second location represents a 10-year-old 10 kWp PV plant consisting of 40 polycrystalline silicon BISOL BMU-250 PV modules with a rated power of 250 Wp . The PV plant is installed on the roof of the Faculty of Electrical Engineering, Computer Science, and Information Technology in Osijek, Croatia, as part of the Laboratory for Renewable Energy Sources. Like in a previous case, performance measurements are made on an arbitrarily selected and cleaned module in the PV array. Table 2 shows numerical field test results, while Figure 4 shows measured, STC-estimated, and nominal current-voltage and power-voltage characteristics of the BISOL BMU-250 PV module. Results presented in Table 2 show that the STC-estimated results are worse than expected, i.e., those defined by the manufacturer for the new module. The STC-estimated power is 23 W lower than the nominal.
Table 2. BISOL BMU-250 PV module numerical field test results.
Figure 4. Measured, STC-estimated and nominal current-voltage (a) and power-voltage (b) characteristics of BISOL BMU-250 PV module.
The manufacturer of the BISOL BMU-250 PV module offers a 25-year linear performance warranty, resulting in 85 % of nominal power at the end of its 25-year lifetime, starting with a 3% decline in performance after the installation [15]. According to the field measurements and age of 10 years, PV module output resulted in 90.8% of nominal power. After linear extrapolation of measured degradation to the 25th year, this gives the expected output power of the 76% at the end of its lifetime. Based on the linear degradation assumption, it can be concluded that the PV module performs worse than expected. A graphical representation of measured and manufacturer-defined degradation of BISOL BMU-250 PV module is shown in Figure 5.
Figure 5. Comparison of manufacturer-defined and measured degradation of BISOL BMU-250 PV module.

4. Modeling and Analysis of the Influence of PV Module Degradation on Investment Payback Time

This section describes the PV plant models and settings used for performing simulations in the software tool. Based on the simulation results, the remainder of this section presents results on the influence of degradation on PV plant performance and its investment payback time.

4.1. Model and Simulation Settings

Results of field testing are used to analyze the influence of expected (manufacturer-defined) and measured degradation on the payback time of PV plant investments in a prosumer power system. Prosumer represents a passive consumer with a PV plant installed behind the meter. Analysis is performed using the PV*SOL Premium 2024 software tool. Two same-size models of a prosumer with a 5 kWp PV plant are made in the software tool to assess this influence. Input data for the prosumer model represents the solar irradiation profile (Figure 6a) and electricity consumption profile (Figure 6b). Both prosumer models are located at the same location, resulting in yearly solar irradiated energy of 1258.6 kWh / m 2 and use the same consumption profile with the yearly electricity consumption of 5000 kWh . The only difference between the two models is the type and number of PV modules, due to their differing electrical characteristics, primarily in nominal power. This means that the PV plant at location 1 consists of 25 ET-M572200WW PV modules, while the PV plant at the location 2 consists of 20 BISOL BMU-250 PV modules.
Figure 6. Input data for PV plant models: (a) solar irradiation and (b) electricity consumption.
The defined investment cost per kWp of installed power for the two models is set to 1000 €/kWp. Annual maintenance costs are set to 2% of the investment price with inflation rate of 2%. The defined annual return on capital is set to 5%, and the calculation period is set at 25 years.
Both models use net metering electricity billing scheme. Two tariffs are defined for purchasing electricity from the grid, namely, a higher and a lower tariff. Models incorporate both daylight saving and winter time periods changes. The higher tariff price of electricity is set to 0.159 €/kWh, while the lower tariff is set to 0.083 €/kWh. The price of electricity exported to the electricity grid is set to 0.069 €/kWh.

4.2. Location 1 Results

Using the PV*SOL Premium software, annual production data were obtained by considering both manufacturer-defined degradation and measured degradation. Figure 7a shows electricity production of the PV plant, while Figure 7b shows accrued cash flow (cash balance) over the investment’s lifetime.
Figure 7. Location 1 PV plant electricity generation (a) and accrued cash flow (cash balance) (b) over the investment’s lifetime.
Annual PV plant production after 25 years for manufacturer-defined degradation is 4924 kWh , while for the measured degradation it is 5758 kWh . This means that the actual annual production of electricity is around 17% higher than the manufacturer-defined degradation parameters of the PV modules. Accrued cash flow (cash balance) after 25 years for manufacturer-defined degradation it is €5224.70, while for measured degradation it is €6127.30.
From the results obtained by the simulations, the return on investment rate with manufacturer-defined degradation is 9.5 years, while the return on investment rate with measured degradation is 9 years. This means that in reality the return on investment rate has decreased by 0.5 years or 6 months.

4.3. Location 2 Results

Figure 8a shows electricity production of the PV plant, while Figure 8b shows accrued cash flow (cash balance) over the investment’s lifetime.
Figure 8. Location 2 PV plant electricity generation (a) and accrued cash flow (cash balance) (b) over the investment’s lifetime.
Annual PV plant production after 25 years for manufacturer-defined degradation is 5409 kWh , while for the measured degradation it is 4852 kWh . This means that the actual annual production of electricity is around 10% lower than the manufacturer-defined degradation parameters of the PV modules. Accrued cash flow (cash balance) after 25 year for manufacturer-defined degradation is €5734.64, while for measured degradation it is €5322.11.
According to the simulation results, the return on investment rate for both manufacturer-defined and measured degradation is 9.1 years. The primary reason for this is the relatively low financial compensation for surplus electricity fed back into the grid, which is set at €0.069/kWh. According to the simulation results, the majority of the electricity produced by the PV system is exported to the grid, while only a small portion is used to meet consumption. Due to the low financial compensation for surplus electricity, it does not produce a profit large enough to significantly influence the investment’s payback time, unlike the savings for self-supplied electricity behind the meter.

5. Conclusions

This paper has assessed the impact of PV module degradation on the payback time of PV power plant investment in a prosumer power system, using experimental measurements of the performance of two 10-year-old PV modules.
The actual degradation of the ET-M572200WW PV module after ten years was considerably less than expected, highlighting the module’s high quality and the value of regular maintenance and performance monitoring. This reduced degradation led to higher annual electricity production, even as the return on investment decreased. The test results for the BISOL BMU-250 module showed a slight drop in performance after ten years, with degradation slightly exceeding factory standards. This led to a small decrease in annual electricity production. However, the return on investment remained unchanged, indicating that the performance drop did not impact the overall performance of the PV plant.
Research shows that photovoltaic module degradation varies based on quality and installation conditions. While this degradation is natural, choosing high-quality modules, ensuring proper installation, and conducting regular performance monitoring can significantly minimize its impact on electricity production and investment returns.
Future work will continue to monitor degradation at the studied locations with more frequent measurements of PV module performance. Further, it will monitor degradation on more than one PV module in the string to determine if a pattern exists. Another direction of research will focus on gathering measurements at multiple locations for various orientations and tilt angles of PV module installations, to analyze the influence of these factors on degradation.

Author Contributions

Conceptualization, M.Ž., D.Š., M.P. and M.D.; methodology, M.Ž. and M.D.; software, M.Ž. and M.D.; validation, M.Ž., D.Š. and M.P.; formal analysis, M.Ž. and M.P.; investigation, M.D. and M.P.; data curation, M.Ž., M.P. and M.D.; writing—original draft preparation, M.Ž. and M.D.; writing—review and editing, M.Ž.; visualization, M.Ž. and M.D.; supervision, M.Ž. and D.Š.; funding acquisition, M.Ž. All authors have read and agreed to the published version of the manuscript.

Funding

The APC was funded by Croatian Science Foundation under the project “Prosumer-rich distribution power network” (project number: UIP-2020-02-5796).

Data Availability Statement

The raw data supporting the conclusions of this article will be made available by the authors upon request.

Acknowledgments

This work was supported by the Croatian Science Foundation under the project ”Prosumer-rich distribution power network” (project number: UIP-2020-02-5796).

Conflicts of Interest

The authors declare no conflicts of interest.

References

  1. Rahman, T.; Mansur, A.A.; Hossain Lipu, M.S.; Rahman, M.S.; Ashique, R.H.; Houran, M.A.; Elavarasan, R.M.; Hossain, E. Investigation of Degradation of Solar Photovoltaics: A Review of Aging Factors, Impacts, and Future Directions toward Sustainable Energy Management. Energies 2023, 16, 3706. [Google Scholar] [CrossRef] [Scilit]
  2. Oreski, G.; Ottersböck, B.; Omazic, A. 6-Degradation Processes and Mechanisms of Encapsulants. In Durability and Reliability of Polymers and Other Materials in Photovoltaic Modules; Yang, H.E., French, R.H., Bruckman, L.S., Eds.; Plastics Design Library, William Andrew Publishing: Norwich, NY, USA, 2019; pp. 135–152. [Google Scholar] [CrossRef] [Scilit]
  3. Aghaei, M.; Fairbrother, A.; Gok, A.; Ahmad, S.; Kazim, S.; Lobato, K.; Oreski, G.; Reinders, A.; Schmitz, J.; Theelen, M.; et al. Review of degradation and failure phenomena in photovoltaic modules. Renew. Sustain. Energy Rev. 2022, 159, 112160. [Google Scholar] [CrossRef] [Scilit]
  4. Eitner, U.; Köntges, M.; Brendel, R. Measuring thermomechanical displacements of solar cells in laminates using digital image correlation. In Proceedings of the 2009 34th IEEE Photovoltaic Specialists Conference (PVSC), Philadelphia, PA, USA, 7–12 June 2009; pp. 001280–001284. [Google Scholar] [CrossRef] [Scilit]
  5. Soares, G.A.; David, T.W.; Anizelli, H.; Miranda, B.; Rodrigues, J.; Lopes, P.; Martins, J.; Cunha, T.; Vilaça, R.; Kettle, J.; et al. Outdoor performance of organic photovoltaics at two different locations: A comparison of degradation and the effect of condensation. J. Renew. Sustain. Energy 2020, 12, 063502. [Google Scholar] [CrossRef] [Scilit]
  6. Zielnik, A.F.; Burns, D.M. 13-Service Life Prediction of PV Materials. In Durability and Reliability of Polymers and Other Materials in Photovoltaic Modules; Yang, H.E., French, R.H., Bruckman, L.S., Eds.; Plastics Design Library, William Andrew Publishing: Norwich, NY, USA, 2019; pp. 297–328. [Google Scholar] [CrossRef] [Scilit]
  7. Kempe, M.D. Modeling of rates of moisture ingress into photovoltaic modules. Sol. Energy Mater. Sol. Cells 2006, 90, 2720–2738. [Google Scholar] [CrossRef] [Scilit]
  8. Sepúlveda-Oviedo, E.H. Impact of environmental factors on photovoltaic system performance degradation. Energy Strategy Rev. 2025, 59, 101682. [Google Scholar] [CrossRef] [Scilit]
  9. Santhakumari, M.; Sagar, N. A review of the environmental factors degrading the performance of silicon wafer-based photovoltaic modules: Failure detection methods and essential mitigation techniques. Renew. Sustain. Energy Rev. 2019, 110, 83–100. [Google Scholar] [CrossRef] [Scilit]
  10. Sai Krishna, G.; Moger, T. Reconfiguration strategies for reducing partial shading effects in photovoltaic arrays: State of the art. Sol. Energy 2019, 182, 429–452. [Google Scholar] [CrossRef] [Scilit]
  11. Köntges, M.; Kurtz, S.; Packard, C.; Jahn, U.; Berger, K.; Kato, K.; Friesen, T.; Liu, H.; Van Iseghem, M.; Wohlgemuth, J.; et al. Review of Failures of Photovoltaic Modules; International Energy Agency: Paris, France, 2014; ISBN 9783906042169. [Google Scholar]
  12. Schneller, E.J.; Brooker, R.P.; Shiradkar, N.S.; Rodgers, M.P.; Dhere, N.G.; Davis, K.O.; Seigneur, H.P.; Mohajeri, N.; Wohlgemuth, J.; Scardera, G.; et al. Manufacturing metrology for c-Si module reliability and durability Part III: Module manufacturing. Renew. Sustain. Energy Rev. 2016, 59, 992–1016. [Google Scholar] [CrossRef] [Scilit]
  13. Knausz, M.; Oreski, G.; Schmidt, M.; Guttmann, P.; Berger, K.; Voronko, Y.; Eder, G.; Koch, T.; Pinter, G. Thermal expansion behavior of solar cell encapsulation materials. Polym. Test. 2015, 44, 160–167. [Google Scholar] [CrossRef] [Scilit]
  14. ET Solar. ET-M572200WW PV Module Datasheet; ET Solar: Nanjing, China, 2014. [Google Scholar]
  15. BISOL Group d.o.o. BISOL BMU-250 PV Module Datasheet; BISOL Group: Prebold, Slovenia, 2014. [Google Scholar]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.