Dynamic Wind Loads on Double-Span Conductors and Their Influencing Factors: An Investigation Using Aeroelastic Wind Tunnel Tests and Finite Element Analysis

,
,
,
and
1
School of Civil and Environmental Engineering, Harbin Institute of Technology, Shenzhen 518055, China
2
State Grid Zhejiang Electric Power Co., Ltd. Research Institute, Hangzhou 310014, China
*
Author to whom correspondence should be addressed.

Abstract

Wind-induced conductor reactions contribute to the loading of overhead transmission-line supports, yet their dependence on span length, wind speed, and support arrangement requires further assessment. This study investigates the along-wind reaction at the central support of two equal conductor spans using aeroelastic wind-tunnel tests, Davenport-based analysis, and finite element simulations. The measured reaction standard deviation was 0.028 N, compared with an analytical prediction of 0.0294 N. At prototype scale, the analytical standard deviation was 0.3944 kN, compared with 0.39 kN from simulation. Neglecting resonance underestimated the fluctuating peak increments by 18.4% and 8.7% at model and prototype scales, respectively, while reducing the conductor-side design contributions by 3.6% and 1.3% with a separation coefficient of 0.75. The conductor-only peak-to-mean reaction factor generally decreased with increasing span length and varied non-monotonically between 1.45 and 1.54 over wind speeds of 20–50 m/s. The three idealized central-support arrangements (hinged, I-type, and V-type) yielded similar conductor-only factors (1.44–1.45) and reduced design combination factors (1.33–1.34) for a 400-m span at 30 m/s. These findings quantify the contributions of resonance and the effects of key parameters on conductor-induced support reactions under the investigated conditions.

1. Introduction

Overhead transmission lines are critical components of power networks, and their structural safety under strong winds is an important design consideration. Previous analytical studies and field observations have examined the wind response of transmission towers [1,2], while research on collapse mechanisms and structural vulnerability has highlighted the importance of wind-load patterns in tower assessment [3,4]. Because wind loads acting on conductors are transmitted to their supports, the resulting conductor-induced reactions are also relevant to the wind-load assessment of transmission-line systems.
Analytical formulations, field measurements, and wind-tunnel experiments provide complementary approaches to investigating wind effects on transmission-line systems. Davenport [5] developed a statistical gust-response formulation for transmission-line loading. Full-scale monitoring, including measurements of a transmission tower during Typhoon Haima [2], provides evidence under actual atmospheric conditions. However, the interpretation of such records is constrained by the specific wind events captured and the associated measurement uncertainty. Wind-tunnel experiments provide controlled and repeatable conditions for examining aerodynamic characteristics and systematically varying test parameters. Such experiments have been applied to transmission towers, including self-supported lattice towers [6,7]. For conductors, rigid sectional models have been used to measure aerodynamic coefficients and investigate the effects of turbulence intensity, angle of attack, conductor-bundle geometry, ice accretion, and surface roughness [8,9,10,11,12]. The measured aerodynamic coefficients have also been incorporated into nonlinear models of bundled-conductor response [13]. The reliability of wind-tunnel results depends on the representativeness of the scaled models and the extent to which the relevant similarity requirements and atmospheric turbulence characteristics can be reproduced.
Rigid sectional tests provide aerodynamic coefficients for mean-load calculations, whereas aeroelastic models can additionally reproduce conductor motion and dynamic support reactions [14]. Loredo-Souza and Davenport [15] conducted aeroelastic wind-tunnel tests and compared the measured responses with statistical predictions based on influence lines. Their results indicated that the background response was often dominant, although resonance could remain important depending on the conductor and wind conditions. Within the background–resonant decomposition, aerodynamic damping primarily affects the resonant component. For a fixed wind-load covariance function and structural influence function, increasing aerodynamic damping suppresses the resonant variance and consequently increases the relative contribution of the background variance to the total response variance, without increasing the absolute background response. Loredo-Souza and Davenport [16] subsequently proposed a horizontally distorted aeroelastic modelling approach to accommodate conductor spans within the limited width of a wind tunnel. Their work also highlighted the need to correct the measured response variance of the distorted model before interpreting it at the prototype scale.
The load–response correlation (LRC) method estimates equivalent static wind-load distributions associated with a specified structural response by accounting for the spatial covariance of fluctuating wind loads and the corresponding structural influence function [17,18]. Transmission-line design standards also incorporate spatial correlation and dynamic response through prescribed wind-loading factors. EN 50341-1:2012, Clause 4.4.1.2, defines the conductor structural factor using background and resonance response factors and recommends a zero resonance factor for its standard conductor treatment [19]. IEC 60826:2017, Clause 6.2.10.1, includes a conductor combined wind factor and a span factor [20]. DL/T 5551-2018, Clause 6.1.1, uses a conductor gust factor and a span reduction factor, with a spanwise correlation integral entering the span-reduction calculation [21]. ASCE Manual of Practice No. 74, fourth edition, Section 2.1.5 and Appendix F, provides simplified and complete gust-response formulations, with the latter retaining separate background and resonant terms [22]. These provisions address related aspects of spatial correlation and dynamic response, although they do not all explicitly prescribe the LRC method.
Building on these aeroelastic investigations, subsequent studies have examined transmission-line systems with different insulator configurations. Zhang et al. [14] investigated the three-dimensional dynamic reactions of transmission lines equipped with I-type, V-type, and strain-type insulators through theoretical analysis and aeroelastic wind-tunnel tests. They decomposed the dynamic reactions into background and resonant components and identified the first symmetric out-of-plane mode as an important contributor to the resonant response. More recently, Wang et al. [23] investigated the buffeting response of a double-span transmission-line-insulator system equipped with I-type and strain-type insulators. They developed an analytical framework based on influence functions and modal analysis to evaluate background and resonant responses in both the along-wind and longitudinal directions, and validated the theoretical predictions through full aeroelastic wind-tunnel tests. Their results showed that the background component dominated the along-wind response, whereas the longitudinal resonant response associated with the first in-plane mode remained non-negligible for the I-type insulator. These findings demonstrate that the relative importance of background and resonant components depends on the reaction direction and support configuration; conclusions regarding the along-wind reaction should therefore not be directly extrapolated to the longitudinal reaction.
Unlike a single-span conductor, a double-span assembly comprises two spans extending on opposite sides of a common intermediate support. The resultant wind-direction reaction at this support is contributed by both spans. Accordingly, the background response depends on the spatial covariance of fluctuating wind loads both within each span and across the two spans, whereas the resonant response depends on the projection of distributed aerodynamic loads onto the structural vibration modes of the conductor system. In actual transmission-line systems, adjacent spans may also interact dynamically through the swinging motion of suspension-insulator strings and the flexibility of tower cross-arms, potentially producing coupled global vibration modes. Therefore, the wind-induced response of a double-span assembly is governed by both the spatial correlation of aerodynamic excitation and the structural characteristics of the intermediate support. These two aspects need to be distinguished when evaluating the resultant support reaction, since correlated aerodynamic excitation does not necessarily imply structural dynamic coupling between adjacent spans.
Against this background, the present study investigates the wind-direction (along-wind) component of the resultant reaction transmitted by an equal-span double-span conductor assembly to its central suspension support. A horizontally distorted aeroelastic conductor model is tested in a wind tunnel, and the measured fluctuating-reaction statistics are compared with predictions from a Davenport-based analytical formulation. In this formulation, the background and resonant components are estimated separately using the LRC method and modal analysis, respectively, with the spatial-coherence model retaining the covariance of aerodynamic excitation across the two spans. These individual components are theoretical estimates and are not independently identified from the measured total response. A prototype-scale FE model is then used to perform time-history analyses for selected conductor span lengths (100–800 m), mean wind speeds (20–50 m/s), and idealized central-support configurations. The baseline FE prediction is compared with the analytical result, whereas the additional parametric cases are numerical predictions without independent wind-tunnel validation. The experimental and numerical models employ prescribed and idealized support conditions and do not fully represent the support-mediated structural coupling associated with flexible insulator strings and tower cross-arms. Accordingly, the study provides a case-specific assessment of the along-wind reaction under the adopted equal-span geometry, turbulent inflow, and support conditions, rather than a comprehensive evaluation of the dynamically coupled tower–line–insulator system.

2. Aeroelastic Wind Tunnel Tests on Double-Span Conductors

The analytical formulation adopted in this study to estimate the dynamic wind-direction reactions of conductors is based on Davenport’s gust-response framework for transmission-line loading [5] and is summarized in Appendix A and Appendix B. Related applications to single-span conductor wind loading and aeroelastic wind-tunnel modelling have been reported in previous studies [15,16]. This section presents the aeroelastic wind-tunnel investigation of an equal-span double-span conductor assembly, including characterization of the turbulent inflow, design of the distorted aeroelastic models, and the experimental setup. The measured total response is compared with the analytical prediction, in which the background and resonant contributions are evaluated separately. Particular attention is given to the standard deviation of the fluctuating wind-direction reaction, the PSD-based peak factor, and the conductor-only gust response factor (GRF), as defined in Appendix A. The measured inflow characteristics are subsequently used to specify the prototype-scale turbulent wind input for the FE analyses in Section 3.

2.1. Wind Field Generation

The wind-tunnel tests were conducted at the Shenzhen Engineering Lab for Wind Environment and Technology, Harbin Institute of Technology, Shenzhen, China. The test section is 24 m long, 6 m wide, and 3.6 m high, with a maximum controllable wind speed of 35 m/s. Considering the dimensions and operating limits of the facility, the turbulent inflow and double-span conductor models were designed according to the adopted similarity criteria.
The tests were conducted under a turbulent inflow with a nominally uniform mean-velocity profile, without imposing a vertical mean-wind-speed gradient. The measured mean wind speed and longitudinal turbulence intensity were V = 10.58 m/s and Iu = 10.04%, respectively. The measured one-sided power spectral density (PSD) of the longitudinal velocity fluctuations and the spanwise square-root coherence are presented in Figure 1. In addition, a separate low-turbulence test Iu ≈ 0% was conducted to identify the mean aerodynamic drag parameter, whereas the turbulent inflow described above was used for the fluctuating-response measurements.
Figure 1. Turbulence characteristics of the wind-tunnel inflow: (a) one-sided power spectral density (PSD) of the longitudinal velocity fluctuations and its fitted von Kármán spectrum; (b) measured spanwise square-root coherence as a function of the reduced frequency fΔx/V, together with the fitted Davenport exponential coherence model. In (a), Su(f) is expressed in m2·s−1 and f in Hz; in (b), the square-root coherence and reduced frequency are dimensionless. In (b), the marker shapes and colors distinguish sensor-pair separations, and the arrow identifies the fitted exponential curve.
The measured one-sided PSD of the longitudinal velocity fluctuations was fitted with the von Kármán spectrum [24,25], as shown in Figure 1a, with its mathematical expression provided in Equation (1). The fitted longitudinal integral length scale in the mean-wind (y) direction, Luy, was 0.71 m. The measured spanwise square-root coherence was fitted using a Davenport-type exponential root-coherence model [26], as defined in Equation (A12), yielding a dimensionless coherence-decay coefficient of C = 25.74 for the present inflow.
S u f = 4 σ u 2 L u , y / V 1 + 70.8 f L u , y / V 2 5 / 6
in which Su(f) is the one-sided power spectral density of the longitudinal wind-speed fluctuations, σu is their standard deviation, Lu,y is the longitudinal turbulence integral scale in the mean-wind direction, and V is the corresponding mean wind speed.
Under the adopted 1:25 streamwise length scale, the measured integral length scale of 0.71 m corresponds to a prototype-equivalent value of 17.75 m. This value is used to specify the longitudinal turbulence spectrum for the subsequent prototype-scale FE analyses in Section 3.

2.2. Design of Aeroelastic Models for Double-Span Conductors

To accommodate the double-span assembly within the 6-m-wide wind-tunnel test section, a distorted aeroelastic model was designed following Loredo-Souza and Davenport [16]. At the normal geometric scale of 1:25, each span would be 6 m long. Therefore, the horizontal span was further reduced by a distortion factor of γ = 0.4 to 2.4 m (1:62.5), while the vertical sag was maintained at 0.2 m (1:25). Retaining the sag preserves the sag-dependent first-mode frequency predicted by the idealized cable model in Equation (A14). The mass per unit length and effective aerodynamic drag parameter were scaled upward by 1/γ relative to their normal-scale values, thereby approximately preserving the total mass and nominal aerodynamic drag force over each span. The distorted model thus retains the selected sag-related dynamic and loading characteristics while relaxing horizontal geometric similarity.
The design parameters of the LGJ-300/40 prototype, the normal-scale reference model, and the distorted aeroelastic model are summarized in Table 1.
Table 1. Geometric, mechanical, and aerodynamic design parameters of the prototype and the normal-scale and distorted aeroelastic models (per span).
Using the dimensions in Table 1, the geometric scale factors of the distorted model are:
λ L ∗ = L m / L p = 2.4 / 150 = 0.0160 = 1 / 62.5
λ S ∗ = S m / S p = 0.2 / 5 = 0.04 = 1 / 25
λ l ∗ = l m / l p = 2.44 / 150.44 ≈ 0.01622 ≈ 1 / 61.66
The corresponding scale factors for mass per unit length, nominal mean wind speed, and effective aerodynamic drag parameter are:
λ M ∗ = 0.0045 / 1.13 ≈ 0.0040
λ V ∗ = 10 / 50 = 0.2
λ F ∗ = 0.0024 / 0.024 = 0.1
The time-scale factor based on the FE-estimated first-mode frequencies is:
λ t ∗ = T 1 , m / T 1 , p = f 1 , p / f 1 , m = 0.25 / 1.22 ≈ 0.2049
The nominal aerodynamic drag force per unit cable length scales with the square of the mean wind speed and the effective aerodynamic drag parameter. Assuming the same air density, the corresponding scale factor is λ q ∗ = λ V ∗ 2 λ F ∗ = 0.2 2 × 0.1 = 0.004 . The scale factor for the aerodynamic force integrated over one span is then obtained using the cable arc-length scale:
λ Fs ∗ = λ q ∗ λ l ∗ = 0.004 × 0.01622 ≈ 6.49 × 10 − 5
Because the two spans have identical geometry and scale factors, the same scale factor applies to their combined contribution to the central-support reaction.
The distorted model satisfies the sag-based Froude similarity condition, since λ V ∗ / λ S ∗ = 1 . The first-mode reduced-frequency ratio based on sag is also approximately preserved, with λ f ∗ λ S ∗ / λ V ∗ = 0.976 , where λ f ∗ = 1 / λ t ∗ = 4.88 is obtained from the FE-estimated natural frequencies. In contrast, the corresponding span-based Strouhal and Froude ratios are 0.3904 and 1.581, respectively, indicating that strict span-based similarity is not achieved. Thus, the distorted model approximately preserves the selected sag-related dynamic characteristics, while the effects of horizontal-span distortion should be considered when extrapolating the experimental results to the prototype conductor.
The as-built model had a span-averaged mass per unit length of 7.71 g/m, which is 71.3% higher than the design target of 4.50 g/m; this value includes the wooden cylinders attached along the conductor. The effective aerodynamic drag parameter CDld, identified from the low-turbulence mean-load test, was 0.0020 m, 16.7% lower than the target value of 0.0024 m. These as-built properties are used in the subsequent assessment of the model’s dynamic response.
For small-amplitude out-of-plane vibration of each span, the linearized governing equation is expressed as
m ∂ 2 w ∂ t 2 − H ∂ 2 w ∂ x 2 = 0
in which w denotes the out-of-plane displacement, m is the mass per unit length, and H is the initial horizontal tension. Because this motion does not produce first-order axial extension, the axial rigidity EA does not enter the linearized equation. Accordingly, the natural frequencies are governed by the ratio H/m, as expressed in Equation (A14).
For a parabolic cable under uniformly distributed self-weight, the initial horizontal tension is estimated as H = mgL2/(8S). For the distorted model, the nominal horizontal span and sag are 2.4 m and 0.2 m, respectively. The corresponding horizontal tensions are estimated as 0.1589 N using the target mass of 4.50 g/m and 0.2723 N using the measured mass of 7.71 g/m. Since H/m = gL2/(8S) remains unchanged for a fixed span and sag, Equation (A14) gives the same analytical first-mode frequency of approximately 1.238 Hz for both mass conditions. This value is approximately 1.5% higher than the FE-predicted frequency of 1.22 Hz.
The frequency comparison is limited to first-order out-of-plane vibration under the prescribed self-weight equilibrium. Axial-rigidity similitude was not imposed, and the effects of axial deformation, in-plane vibration, and nonlinear axial–transverse coupling are not represented in the present model. The design targets and corresponding measured or estimated properties of the distorted aeroelastic model are summarized in Table 2.
Table 2. Comparison of design targets and measured or estimated properties of the distorted aeroelastic model.
Under the prescribed fixed-span and fixed-sag self-weight equilibrium, the 71.3% increase in mass is accompanied by a proportional increase in horizontal tension, leaving H/m and the analytical first-mode frequency unchanged. However, the combined increase in mass and 16.7% reduction in the effective aerodynamic drag parameter reduce the calculated first-mode aerodynamic damping ratio from 45.1% to 21.9% (Table 2). The lower aerodynamic damping increases the resonant susceptibility, whereas the reduced drag parameter also decreases the aerodynamic excitation. Their combined effects should therefore be considered when evaluating the resonant response of the as-built model.

2.3. Installation and Testing of the Models

The double-span conductor assembly is mounted at the upper suspension points of a rigid force-transfer rod, as illustrated in Figure 2. The upper suspension level is located 1.0 m above the force-balance center, and the vertical spacing between the upper and lower suspension levels is 0.12 m. The two upper suspension points are spaced 0.10 m apart (Δy = 0.10 m), whereas the two lower suspension points are spaced 0.20 m apart. With the upper points arranged symmetrically about the balance centerline, the offset from the balance center to either upper point is Δ ′ y = Δ y / 2 = 0.05   m , as used in Section 2.4. The rod is mounted on a force balance fixed to the wind-tunnel pedestal, which records the forces and moments transmitted through the support. A non-contact Plexiglas tube surrounds the rod to shield it from direct wind exposure without mechanically loading the rod.
Figure 2. Schematic of the rigid force-transfer rod and force-balance assembly, showing the upper and lower suspension points, their vertical spacing, horizontal offsets, Plexiglas cover, rigid rod, force balance, and pedestal. All indicated dimensions are in millimeters. The arrow Fy denotes the wind-direction reaction transmitted to the force balance through the upper suspension point.
The conductor spans extend along the x-direction, while the incoming wind flow is aligned with the y-direction, perpendicular to the spans. As shown in Figure 3a, two anemometers are positioned on either side of the central support to measure the incoming flow. The support reaction is expressed in three components: the span-wise component Fx, the along-wind component Fy, and the vertical component Fz. In the present setup, Fy is recovered from the measured base bending moment and vertical force, as described in Section 2.4, and is the only reaction component analyzed in this study.
Figure 3. Wind tunnel experimental setup and force components of the double-span conductor assembly: (a) installed conductor models, anemometers, central suspension point, and force-balance system; (b) close-up view of the force-transfer rod, force balance, and corresponding coordinate system. The reaction components are resolved into the span-wise direction Fx, wind direction Fy, and vertical direction Fz, of which only Fy is analyzed in this study.
The rigid rod serves as a force-transfer fixture for the central support and does not reproduce the pendular dynamics of an actual suspension-insulator string or the flexibility of a tower cross-arm. The fixture is intended to provide a fixed central support. However, the rod–balance assembly has a finite dynamic response, which is accounted for by the spectral correction procedure described in Section 2.4. The corrected spectrum of Fy therefore represents the combined along-wind reaction transmitted by the two conductor spans to the central fixture, without including the dynamic contributions of tower motion or insulator-string swing.
The baseline FE model retains the same two-span arrangement and evaluates the along-wind reaction at the central support, corresponding to the load-transfer location measured in the wind tunnel. The I- and V-type configurations examined in Section 3 are additional idealized FE cases used to assess the influence of alternative central-support arrangements; they do not reproduce the wind-tunnel fixture or provide experimental validation of insulator-string dynamics.
The fluctuating-response measurements were conducted under the single turbulent inflow condition described in Section 2.1 (V = 10.58 m/s and Iu = 10.04%). The effects of span length, mean wind speed, and support arrangement are examined in Section 3 through FE time-history analyses rather than additional wind-tunnel tests. The corresponding parametric results are therefore numerical predictions under the adopted FE assumptions.

2.4. Results and Discussions

Taking moments about the x-axis at the force-balance center, the resultant along-wind reaction transmitted by the two conductor spans is obtained from the measured moment and vertical force as
M x = F y H = M ′ x − F ′ z Δ ′ y
in which H = 1.0 m is the vertical distance from the balance center to the upper suspension point, and Δy′ = 0.05 m is its horizontal offset (Section 2.3). M ′ x and F ′ z denote the moment about the x-axis and the vertical force recorded by the force balance, respectively.
Although the rod itself is sufficiently rigid, the rod–balance assembly exhibits a finite dynamic response, with its fundamental frequency falling within the frequency range of the measured response. Therefore, the correction procedure proposed by Zou and Liang [27], based on random vibration theory, is applied to remove the resonance associated with the measurement system. This correction accounts for the dynamic response of the rod–balance assembly only; the conductor’s structural resonant response is retained in the subsequent analytical calculations. The corrected PSD of the fluctuating along-wind reaction, denoted by S F y ∗ f , is expressed as
S F y ∗ f = S M x f H 2 1 + H 1 if 2 2 πf 4 + 4 ζ 1 2 2 π f ′ 1 2 2 πf 2
in which S M x f is the PSD of the base moment Mx obtained from Equation (11), H1(if) is the frequency-response function of the rod–balance system, ζ1 is its first-mode damping ratio, and f ′ 1 is its fundamental frequency.
The corresponding corrected PSD of the base moment is then recovered using the relationship Mx = HFy:
S M x ∗ f = H 2 S F y ∗ f
Figure 4 compares the original and corrected PSDs of the base moment Mx. The correction substantially reduces the spectral peak associated with the rod–balance resonance.
Figure 4. Comparison of the original and revised one-sided power spectral densities of the base bending moment Mx. The original PSD contains the resonant contribution of the semi-rigid rod–balance system, whereas the revised PSD is obtained after correcting for this resonance and is subsequently used to recover the fluctuating wind-direction force acting on the conductors. The frequency is expressed in Hz, and the PSD is expressed in N2·m2/Hz.
Using Equations (12) and (13), the corrected one-sided PSD of the fluctuating along-wind reaction Fy is obtained. Its zeroth spectral moment gives the PSD-derived experimental standard deviation of σrE = 0.028 N. The peak factor calculated from the spectral moments using Equation (A3) is gLE = 3.67, yielding a fluctuating peak increment of ΔrE = gLEσrE = 0.103 N for the equivalent model-scale reference duration Tc,m = 122.94 s (Appendix A). The low-turbulence test (Iu ≈ 0%) gives a mean reaction of r ¯ M = 0.33   N and an effective aerodynamic drag parameter of CDd = 0.0020 m.
By substituting the measured aerodynamic drag parameter, inflow characteristics, and as-built structural properties into Equations (A6) and (A10), the theoretical standard deviations of the background and first-mode resonant components are obtained as σrB = 0.024 N and σrR1 = 0.017 N, respectively. Their combination gives a theoretical total standard deviation of σT = 0.0294 N, which is approximately 5.0% higher than the PSD-derived experimental value of 0.028 N. The theoretical peak factor calculated from the response PSD using Equation (A3) and the same equivalent model-scale reference duration is gLT = 3.64, yielding a theoretical fluctuating peak increment of 0.1071 N, compared with the experimental estimate of 0.103 N. The two peak-factor estimates differ by approximately 0.8%, while the corresponding peak increments differ by approximately 4.0%. This agreement indicates consistency between the theoretical and experimental spectral estimates, although the single available turbulent-flow record does not permit an assessment of record-to-record variability. The theoretical background and first-mode resonant components account for 66.6% and 33.4% of the total response variance, respectively.
For the as-built model, Equation (A13) gives a first-mode aerodynamic damping ratio of ζa1 = 21.9%, based on the measured mass per unit length of 7.71 g/m, effective aerodynamic drag parameter of 0.0020 m, mean wind speed of 10.58 m/s, and first-mode frequency of 1.22 Hz. To isolate the effect of the mass deviation, a counterfactual calculation is performed by restoring the mass per unit length to its design value of 4.50 g/m while keeping the measured drag parameter unchanged. Under the same fixed-sag equilibrium condition, the first-mode frequency remains unchanged, and the aerodynamic damping ratio increases to 37.5%. Thus, the 71.3% excess in the as-built mass reduces the calculated aerodynamic damping ratio by approximately 41.6% relative to the target-mass condition. The difference between the 45.1% and 21.9% values in Table 2 reflects the combined effects of mass and aerodynamic drag deviations.
Under the narrow-band approximation in Equation (A10), and with the modal properties and generalized modal-force spectra held fixed, the resonant variance is inversely proportional to the total modal damping ratio ζa1 + ζS. Accordingly, the ratio of the resonant standard deviations under the target-mass and as-built conditions is expressed as 0.219 + ζ S / 0.375 + ζ S . Because the structural damping ratio of the physical model is unknown, setting ζS = 0 provides an upper-bound estimate of the mass-related effect. Under this assumption, the resonant standard deviation decreases from 0.017 N for the as-built model to approximately 0.0130 N for the target-mass condition. With the fluctuating-load covariance and LRC influence function held fixed, the background standard deviation remains unchanged at 0.024 N. Consequently, the total theoretical standard deviation decreases from 0.0294 N to approximately 0.0273 N. Thus, the excess mass may increase the total theoretical response standard deviation by up to approximately 7.8% relative to the target-mass condition. The difference becomes smaller when a nonzero structural damping ratio is considered.
Using the same theoretical peak factor gLT = 3.64 for both cases, neglecting the first-mode resonant component reduces the calculated fluctuating peak increment from 0.1071 N to 0.0874 N, corresponding to an underestimation of approximately 18.4%. The corresponding conductor-only peak-to-mean reaction factors are Gc = 1.324 and 1.265 for the full and background-only responses, respectively. For comparison with conventional tower–conductor design formulations, the separation coefficient εL = 0.75 is applied separately, yielding reduced design combination factors of Gd,c = 1.243 and 1.199, respectively. The corresponding reduced conductor-side design-combination contributions are 0.4103 N and 0.3955 N, indicating an underestimation of approximately 3.6% when resonance is neglected. These values represent the conductor-side contribution under the conventional separation assumption and do not include the tower wind load or the total response of the coupled tower–conductor system.

3. Influencing Factors for Dynamic Wind Loads on Conductors

In this section, the prototype-scale double-span conductor corresponding to the aeroelastic model is investigated using FE analysis. The FE-predicted modal frequencies are first compared with the analytical solutions of an idealized cable model, followed by a comparison of the baseline wind-direction reaction with the analytical background–resonant prediction. The FE model is subsequently used to investigate the effects of conductor span length, mean wind speed, and central support configuration on the wind-direction reaction.

3.1. FE Model and Comparison with Analytical Predictions

The prototype structural parameters listed in Table 1 are used to establish the FE model. Each conductor span is discretized using three-dimensional LINK10 spar elements. The tension-only option is activated by setting KEYOPT(3) = 0, while KEYOPT(2) = 0 is retained to avoid assigning additional residual stiffness to slack elements. The element real constants specify the conductor cross-sectional area (AREA) and an initial tensile strain (ISTRN) of 1.0 × 10−6. LINK10 carries axial force only and has three translational degrees of freedom at each node, without bending stiffness or rotational degrees of freedom [28].
The initial equilibrium profile of each conductor span is approximated by a parabola, assuming uniformly distributed self-weight. For the prototype conductor, the sag-to-span ratio is S/L = 5/150 = 1/30, satisfying the commonly adopted criterion of S/L < 1/8 for the parabolic approximation [29,30]. The first five span-wise out-of-plane natural frequencies are then extracted from the FE model and compared with the analytical solutions obtained using Equation (A14), as summarized in Table 3.
Table 3. Comparison of theoretical and FE natural frequencies for the first five span-wise modal orders of the conductor system.
Table 3 shows close agreement between the FE and analytical natural frequencies for the first five span-wise out-of-plane modal orders. The maximum relative difference is approximately 0.8%, occurring in the fifth mode. The corresponding representative FE mode shapes are presented in Figure 5.
Figure 5. First five representative span-wise out-of-plane vibration mode shapes of the double-span conductor FE model: (a) first mode, f1 = 0.247 Hz; (b) second mode, f2 = 0.494 Hz; (c) third mode, f3 = 0.743 Hz; (d) fourth mode, f4 = 0.994 Hz; and (e) fifth mode, f5 = 1.248 Hz. The upper-left panel shows the input geometry and its gravity-equilibrium configuration. The representative FE modal displacement patterns are amplified for visualization. The corresponding natural frequencies are listed in Table 3. Open triangles denote the remote hinges, and the blue concentric-circle marker denotes the central restraint and reaction location.
The baseline FE model consists of two identical 150-m conductor spans meeting at a fixed central support, with both remote ends modeled as hinged supports. At the central support, the out-of-plane displacement is restrained and spanwise sliding is prevented. Consequently, the two spans have no shared unconstrained translational degree of freedom and are structurally uncoupled in the linear out-of-plane modal analysis.
Because the two spans have identical geometric and mechanical properties, each span-wise modal order corresponds to a pair of repeated global eigenvalues. The associated eigenspace can be represented by modes localized in either span or by symmetric and antisymmetric combinations of the two span-wise modes. Figure 5 presents one representative single-span mode shape for each modal order. For calculating the resultant reaction at the central support, the symmetric global modal combination is adopted, whereas the antisymmetric combination has zero modal participation in the resultant reaction (Appendix A).
Although the two spans are structurally uncoupled, the aerodynamic loads acting on them remain spatially correlated. The LRC covariance integral in Equation (A6) and the generalized modal-force spectra in Equation (A11) are evaluated over the full double-span domain using the adopted spatial-coherence function, thereby retaining both within-span and cross-span covariance. Consequently, the calculated central-support reaction includes correlated aerodynamic contributions from both spans.
The prototype-scale inflow is obtained by scaling the wind-tunnel measurements according to the adopted similarity ratios. The resulting wind field is characterized by a mean wind speed of Vz = 50 m/s, a turbulence intensity of Iu = 10%, a longitudinal turbulence integral scale of Luy = 17.75 m, and a spanwise coherence decay coefficient of C = 25.74. The fluctuating wind field is generated using the harmonic superposition method, and its one-sided power spectral density is compared with the fitted von Kármán spectrum in Figure 6.
Figure 6. One-sided power spectral density of the simulated longitudinal fluctuating wind speed at the prototype scale and its comparison with the fitted von Kármán spectrum. The frequency f is expressed in Hz, and the PSD Su(f) is expressed in m2·s−2·Hz−1. The simulated wind field has a mean wind speed of Vz = 50 m/s, a turbulence intensity of Iu = 10%, and a longitudinal turbulence integral scale of Luy = 17.75 m.
The longitudinal turbulence integral scale Luy governs the frequency distribution of the longitudinal wind-speed spectrum Su(f), whereas the spanwise coherence decay coefficient C is fitted to the measured spanwise coherence in Figure 1b and defines the Davenport coherence function in Equation (A12). These two parameters describe different characteristics of the turbulent inflow. Through the frequency-dependent cross-spectral terms in Equations (A6), (A7) and (A11), the selected longitudinal integral scale affects the background and resonant responses differently.
Furthermore, the horizontal span distortion adopted in this study (1:62.5) does not preserve span-based Strouhal similarity, as discussed in Section 2.2. Therefore, the transfer of the measured spanwise coherence characteristics to the prototype scale remains approximate.
For the prototype conductor, the diameter is d = 0.024 m and the drag coefficient is CDL = 1.0. Equation (A13) gives a first-mode aerodynamic damping ratio of approximately 43%. A structural damping ratio of ζS = 0.05 is assigned using the modal damping ratio setting in ANSYS Mechanical APDL, Release [2023 R2] (Ansys, Inc., Canonsburg, PA, USA). Based on the modal frequency relationship fj = jf1, the aerodynamic damping ratio of the j-th mode is taken as ζaj = ζa1/j, and the total modal damping ratio is ζj = ζaj + ζS. Accordingly, the total damping ratios of the first five modes are 0.480, 0.265, 0.193, 0.158, and 0.136, respectively. The FE-predicted wind-direction reaction at the central suspension point is presented in Figure 7a, with its one-sided power spectral density shown in Figure 7b.
Figure 7. FE-predicted wind-direction reaction at the central suspension point of the double-span conductor assembly and its power spectral density: (a) 600-s time history of the resultant reaction, showing the mean reaction r ¯ S and the PSD-based upper and lower peak levels r ¯ S ± g L , FE σ S ; (b) one-sided PSD of the fluctuating reaction. The reaction time history is expressed in kN, the time in seconds, the frequency in Hz, and the PSD in N2·s.
The FE time-history analysis gives a mean wind-direction reaction of r ¯ S = 5.69   kN and a standard deviation of σS = 0.39 kN. The one-sided PSD of the fluctuating reaction in Figure 7b is used to calculate the spectral peak factor according to Equation (A3), yielding gL,FE = 3.32 for the 600-s prototype reference duration.
The background standard deviation calculated using the LRC method is σrB = 0.36 kN. The resonant contribution is evaluated using the complete frequency-response formulation presented in Appendix B, which accounts for the frequency-dependent generalized modal-force spectra and modal transfer functions over the full frequency range. Considering the first five span-wise modal families, the resulting resonant standard deviation is σrR,FRF = 0.1610 kN, compared with 0.1683 kN obtained using the narrow-band approximation in Equation (A10). Combining the background and resonant variances gives a theoretical total standard deviation of σr = 0.3944 kN, approximately 1.1% higher than the FE time-history value of 0.39 kN.
The background and resonant components account for 83.3% and 16.7% of the total response variance, respectively. The off-diagonal terms in the multimodal frequency-response integration are also evaluated using Equation (A20), with the cross-modal covariance contribution accounting for only 0.0581% of the total resonant variance.
Based on the FE time-history statistics, the conductor-only peak-to-mean reaction factor is Gc = 1.228. Applying the conventional separation coefficient εL = 0.75 gives a reduced design combination factor of Gd,c = 1.171. For the analytical response, the total standard deviation of 0.3944 kN and the same FE-derived peak factor of 3.32 give a fluctuating peak increment of 1.3093 kN. When the resonant component is neglected, the peak increment decreases to 1.1952 kN, corresponding to an underestimation of approximately 8.7%. The corresponding conductor-only peak-to-mean reaction factors are 1.230 and 1.210 for the full and background-only responses, respectively. After applying the separation coefficient of 0.75, the reduced design combination factors are 1.173 and 1.158, respectively. The resulting conductor-side design contributions are 6.6720 kN and 6.5864 kN, indicating an underestimation of approximately 1.3% when resonance is neglected. These values represent only the conductor-side contribution under the adopted separation assumption; the tower wind load and tower–conductor dynamic coupling are not included in the present FE model.
The background component accounts for 66.6% of the total response variance in the aeroelastic-model analysis and 83.3% in the prototype analysis. These values represent relative variance contributions. For a fixed wind-load covariance and LRC influence function, aerodynamic damping suppresses the resonant variance without changing the absolute background variance. The difference between the two variance shares cannot be attributed solely to aerodynamic damping, as the model and prototype also differ in mass per unit length, aerodynamic drag parameter, geometric configuration, natural frequency, and wind-speed scaling.

3.2. Parametric Analysis of Conductor-Only Wind-Direction Reaction

A series of nonlinear FE time-history analyses is conducted to investigate the effects of conductor span length, mean wind speed, and central support configuration on the conductor-only wind-direction reaction. For each case, the conductor-only peak-to-mean reaction factor Gc is calculated using Equation (A1a), and the corresponding reduced design combination factor Gd,c is obtained from Equation (A1b) using the separation coefficient εL = 0.75.
All cases are analyzed using full transient analysis (ANTYPE, 4; TRNOPT, FULL), with geometric nonlinearity and stress stiffening activated (NLGEOM, ON; SSTIF, ON). The initial equilibrium configuration under gravity and mean wind loading is established with time integration disabled (TIMINT, OFF), after which time integration is enabled for the fluctuating-wind time-history analysis.
For the span-length and mean-wind-speed analyses, two identical conductor spans are modeled with hinged supports at both remote ends, while the baseline central-support constraints described in Section 3.1 are retained. The sag-to-span ratio is kept constant at 1/30. The span length of each conductor span Lp is varied from 100 to 800 m at a constant mean wind speed of Vz = 30 m/s, whereas the mean wind speed is varied from 20 to 50 m/s for a fixed span length of Lp = 400 m. Table 4 summarizes the first-mode natural frequencies and aerodynamic damping ratios of these FE models, calculated using Equations (A14) and (A13), respectively. The transient analyses additionally include a structural damping ratio of ζS = 0.05. Accordingly, the total damping ratio of the j-th mode is calculated as ζj = ζa1/j + 0.05.
Table 4. Modal frequencies and first-mode aerodynamic damping ratios of the parametric FE models.
Changes in conductor span length and mean wind speed affect not only aerodynamic damping but also the modal properties and wind-induced excitation. Therefore, the resulting variations in Gc reflect their combined effects rather than an isolated aerodynamic-damping sensitivity.
The conductor-only peak-to-mean reaction factor Gc and the corresponding reduced design combination factor Gd,c are calculated for each FE case using Equations (A1a) and (A1b), respectively. The results are presented in Figure 8, with the corresponding numerical values summarized in Table 5. The reduced design combination factor is calculated using the separation coefficient εL = 0.75.
Figure 8. Variations in the conductor-only peak-to-mean reaction factor (Gc) and the reduced design combination factor (Gd,c) obtained from the FE parametric analyses: (a) effects of conductor span length at a constant mean wind speed of 30 m/s; (b) effects of mean wind speed for a constant span length of 400 m. Solid lines with circular markers represent Gc, while dashed lines with square markers represent Gd,c, calculated using the separation coefficient εL = 0.75. The numerical values for all cases are provided in Table 5.
Table 5. Conductor-only peak-to-mean reaction factors and reduced design combination factors for the FE parametric analyses.
As shown in Figure 8a, Gc decreases overall with increasing conductor span length, although a local increase occurs at 500 m; for spans of 600–800 m, Gc remains nearly constant at 1.39–1.40. This trend is accompanied by a decrease in the first-mode natural frequency and an increase in the aerodynamic damping ratio (Table 4), together with changes in the spatial integration of the aerodynamic excitation. Figure 8b shows a non-monotonic variation of Gc with mean wind speed, ranging from approximately 1.45 to 1.54 over the investigated range of 20–50 m/s. The corresponding normalized peak increment Gc − 1 ranges from approximately 0.45 to 0.54, indicating a larger relative variation in the peak increment than in the overall peak-to-mean reaction factor.
The non-monotonic variation of Gc with mean wind speed results from the combined effects of aerodynamic excitation, aerodynamic damping, spatial coherence, and the statistical peak factor. With the turbulence intensity and aerodynamic coefficients kept constant, the mean aerodynamic reaction approximately scales with the square of the mean wind speed. The fluctuating drag excitation also increases with wind speed, since its linearized component is proportional to Vzσu, where σu = IuVz. Consequently, the normalized fluctuating response does not necessarily increase proportionally with the mean wind speed.
In addition, the Davenport coherence function in Equation (A12) depends on the mean wind speed, thereby affecting the spatially integrated aerodynamic excitation. Meanwhile, the first-mode aerodynamic damping ratio increases from 0.28 to 0.70 as Vz increases from 20 to 50 m/s (Table 4), which suppresses the resonant response and partially counteracts the increase in aerodynamic excitation. The statistical peak factor gL may also change with the response power spectral density and modal damping. Therefore, G c = 1 + g L σ r / r ¯ is governed by the combined variations in mean reaction, fluctuating-response standard deviation, and peak factor, rather than by mean wind speed alone. Since εL remains constant, Gd,c follows the same non-monotonic variation according to Equation (A1b). Because the wind-speed cases are not evaluated using ensembles of independent random-phase realizations, the observed variation in Gc represents the case-dependent numerical response under the prescribed simulation conditions. The realization-to-realization variability and associated confidence intervals therefore cannot be quantified from the present results.
Additional FE analyses are performed to investigate the influence of central support configuration on the dynamic wind-direction reaction. Three configurations are considered, each consisting of two equal 400-m conductor spans with a sag-to-span ratio of 1/30 and a mean wind speed of 30 m/s. Both remote ends remain hinged. The central support is modeled as (i) an idealized hinged connection, (ii) an I-type arrangement in which the common conductor node is connected to a fixed upper attachment through one LINK8 element, and (iii) a V-type arrangement in which the same conductor node is connected to two fixed upper attachments through two inclined LINK8 elements.
Each LINK8 element is assigned an equivalent Young’s modulus of 2.0 × 1015 Pa, a Poisson’s ratio of 0.3, and a mass density of 50 kg/m3. Its cross-sectional area is specified through the element real constant, and the corresponding element mass is calculated from the assigned density, cross-sectional area, and element length. No initial strain is prescribed. These elements therefore provide an idealized representation of the axial stiffness and equivalent mass of the insulator assemblies.
The upper attachment nodes are fully restrained in the three translational directions (UX, UY, and UZ), while the conductor-side nodes are shared with the corresponding conductor nodes. LINK8 elements carry axial forces only and have no bending stiffness or nodal rotational degrees of freedom [28]. Previous transmission-line models also used LINK8 to idealize insulator strings [31,32]. Under the geometrically nonlinear formulation (NLGEOM, ON), their spatial orientations can change with the translational motion of the conductor-side nodes, allowing geometric reorientation of the idealized insulator assemblies.
For the idealized hinged arrangement, the wind-direction reaction is extracted at the central support node. For the I-type arrangement, it is obtained from the single fixed upper attachment node. For the V-type arrangement, the global wind-direction reaction components at the two fixed upper attachment nodes are summed. The same conductor properties, wind loading, and remote-end support conditions are maintained among the three configurations. The corresponding FE models and reaction-extraction locations are illustrated in Figure 9, and the numerical results are summarized in Table 6.
Figure 9. Schematic representations of the double-span conductor configurations with different central support arrangements: (a) idealized hinged central support, (b) I-type insulator-string central support, and (c) V-type insulator-string central support. The two conductor spans share a common central conductor-side node. For the I-type and V-type configurations, the upper attachment nodes are fixed, and the insulator strings are represented by high-axial-stiffness LINK8 elements. The tower and cross-arm flexibility are not included in the FE models. Circled markers identify the support-side nodes used to extract the wind-direction reaction. For the V-type arrangement, the reaction components at the two attachment nodes are summed. The wind direction is normal to the plane of the spanwise elevations and is indicated by horizontal arrows in the central sections. The schematics follow the idealized FE model topology and are not drawn to scale.
Table 6. Conductor-only and reduced design combination factors for conductors with different support arrangements.
In the I-type and V-type configurations, the two conductor spans share a common conductor-side node, ensuring displacement compatibility and nodal force equilibrium at the central connection. Under the geometrically nonlinear formulation, the LINK8 elements can reorient as the conductor node moves. However, the upper attachment nodes remain fully restrained, and the flexibility and dynamic motion of the supporting tower and cross-arms are not included. The present models therefore provide idealized representations of different central support arrangements rather than reproducing the fully coupled dynamics of an actual tower–cross-arm–insulator–conductor system. The internal flexibility, joint articulation, and realistic mass distribution of actual insulator strings are also not resolved. Liu et al. [33] incorporated insulator-string swing and displacement and force continuity at suspension points into a dynamic-stiffness model of multi-span transmission lines.
As shown in Table 6, the three central-support configurations yield similar but not identical factors: Gc ranges from 1.44 to 1.45, while Gd,c ranges from 1.33 to 1.34, when rounded to two decimal places. For the investigated case with a 400-m span and a mean wind speed of 30 m/s, the differences among the three idealized support arrangements are small (0.01 in each factor at the reported precision).
These similar results should not be interpreted as demonstrating the general dynamic equivalence of different insulator configurations. The LINK8-based models represent idealized high-axial-stiffness connections and do not account for the flexibility and articulated motion of actual insulator strings or the dynamic response of the supporting tower and cross-arms. Accordingly, the comparison is limited to the investigated support arrangements and modeling assumptions. The reduced design combination factor is used only to estimate the conductor-side design contribution; the dynamic response and non-simultaneous peak occurrence of the supporting tower are not simulated.
Table 7 summarizes the principal response quantities and identifies their respective sources, including wind-tunnel measurements, analytical calculations, and prototype-scale FE predictions.
Table 7. Evidence sources and scope of the principal response results.

4. Limitations and Discussion

The applicability of the findings in this paper is subject to several limitations:
(1) The present experimental and numerical analyses are restricted to the wind-direction reaction Fy; the spanwise Fx and vertical Fz reaction components are not considered. Wang et al. [23] showed that, for an I-type insulator, the resonant contribution associated with the first in-plane mode remains non-negligible in the longitudinal response, although the background component dominates the along-wind response. Accordingly, the present findings on the relative contributions of background and resonant responses apply only to Fy and should not be extended to the other reaction components.
(2) The study is limited to equal-span conductors. The parametric FE analyses also use a fixed sag-to-span ratio of 1/30 and idealized central and remote support conditions. The effects of unequal span lengths, different sag-to-span ratios, and more realistic support arrangements on the resultant reaction remain to be investigated.
(3) The fluctuating-response measurements were conducted under a single turbulent inflow condition with a nominally uniform mean-velocity profile; vertical wind shear is therefore not represented. The measured longitudinal turbulence integral scale Luy = 0.71 m corresponds to a prototype-equivalent value of 17.75 m under the adopted 1:25 streamwise scaling. For comparison, the ASCE 49-12 values cited by Simiu et al. [25] range from 110 to 190 m at 10 m above ground for surface roughness lengths between 0.0002 and 0.03 m. The present value is lower than these reference values; however, this comparison is indicative rather than a direct equivalence, as the present tests do not reproduce a roughness-dependent atmospheric boundary-layer profile at the same reference height.
(4) In addition, the Davenport exponential coherence model is fitted to the measured spanwise coherence. However, the horizontal span scale (1:62.5) differs from the 1:25 streamwise scale, and thus the distorted model does not strictly preserve the prototype spanwise coherence characteristics over all separations and frequencies. These limitations may affect the spatial covariance used in the LRC-based background-response calculation and the generalized modal-force spectra, thereby influencing the calculated conductor-only peak-to-mean reaction factor Gc and the corresponding reduced design combination factor Gd,c. The reported factors should therefore be interpreted as conditional estimates under the adopted turbulence spectrum and coherence model, rather than universal predictions for atmospheric boundary-layer conditions. Further investigations should consider larger longitudinal integral scales representative of prototype conditions, alternative spatial coherence models, vertically sheared mean-wind profiles, and nonstationary turbulent inflows.
(5) The experimental and numerical models do not capture the full support-mediated dynamics of an actual transmission-line system. In the wind-tunnel test, the rigid rod is fixed to the force balance and acts as a force-transfer fixture; it does not reproduce tower cross-arm flexibility or the pendular motion of suspension-insulator strings. In the baseline FE modal model, the fixed central support leaves the two spans structurally uncoupled in the linear out-of-plane modal analysis, although the spatial covariance of aerodynamic excitation across both spans is retained. Thus, the baseline model accounts for correlated aerodynamic loading but not structural coupling through the central support.
(6) The additional I-type and V-type FE models connect the two spans at a shared conductor-side node and represent the insulator assemblies using geometrically nonlinear LINK8 elements. However, the upper attachment nodes are fully restrained, and tower and cross-arm flexibility and inertia are not included. The LINK8 representation also does not resolve the articulation, joint flexibility, or realistic mass distribution of actual insulator strings. Accordingly, the calculated reactions should be regarded as case-specific estimates under the prescribed support conditions, rather than predictions of the fully coupled tower–cross-arm–insulator–conductor system. Future studies should incorporate flexible tower cross-arms and articulated insulator-string models, and resolve their coupled dynamic interaction with both adjacent conductor spans to quantify the effects on global modal properties and wind-induced reactions.

5. Conclusions

This study investigated the along-wind reaction at the central support of an equal-span double-span conductor assembly using aeroelastic wind-tunnel tests, Davenport-based analysis, and finite element (FE) simulations. The corrected experimental spectrum yielded a reaction standard deviation of 0.028 N and a peak factor of 3.67. The analytical background and resonant standard deviations were 0.024 N and 0.017 N, respectively, giving a total of 0.0294 N, approximately 5.0% higher than the experimental result. The background and resonant components contributed 66.6% and 33.4% of the total response variance, respectively.
The as-built aeroelastic model exhibited a 71.3% increase in mass per unit length and a 16.7% decrease in the effective aerodynamic drag parameter relative to their design targets. These deviations reduced the calculated first-mode aerodynamic damping ratio from 45.1% to 21.9%. When the drag parameter was held constant, the excess mass alone reduced the aerodynamic damping ratio by 41.6% and increased the theoretical response standard deviation by up to 7.8% under the zero-structural-damping assumption. These results indicate that model mass and aerodynamic properties must be considered together when interpreting the resonant response of distorted aeroelastic models.
At prototype scale, the analytical background and resonant standard deviations were 0.36 kN and 0.1610 kN, respectively, yielding a total of 0.3944 kN, compared with 0.39 kN from FE simulation. The background component accounted for 83.3% of the total response variance. Neglecting resonance underestimated the calculated fluctuating peak increments by 18.4% and 8.7% at model and prototype scales, respectively. With a separation coefficient of 0.75, the corresponding underestimations in the reduced conductor-side design contributions were 3.6% and 1.3%. Thus, resonance affects the fluctuating peak reaction more strongly than the reduced design contribution under the adopted separation assumption.
The FE parametric analyses showed that the conductor-only peak-to-mean reaction factor Gc generally decreased with increasing span length, with a local increase at 500 m, and remained nearly constant at 1.39–1.40 for spans of 600–800 m. For a 400-m span, Gc varied non-monotonically between 1.45 and 1.54 over mean wind speeds of 20–50 m/s. The idealized hinged, I-type, and V-type central supports yielded similar conductor-only factors (1.44–1.45) and reduced design combination factors (1.33–1.34) at 400 m and 30 m/s. These variations reflect the combined influences of aerodynamic excitation, spatial coherence, modal damping, and statistical peak factors. The findings are limited to the investigated equal-span configurations and idealized support conditions and do not represent the fully coupled tower–cross-arm–insulator–conductor response.

Author Contributions

Conceptualization, Y.T. and J.Y.; methodology, Y.T.; software, Y.T.; validation, W.Z. and Z.W.; formal analysis, Y.T. and J.Y.; investigation, Y.T. and J.Y.; resources, W.Z. and Z.W.; data curation, J.F.; writing—original draft preparation, Y.T.; writing—review and editing, Y.T. and J.F.; visualization, Y.T.; supervision, J.Y.; project administration, W.Z. and Z.W.; funding acquisition, W.Z. and Z.W. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by the Science and Technology Project of State Grid Zhejiang Electric Power Co., Ltd., grant number B311DS25Z009, and the Shenzhen Basic Research Program (General Program), grant number JCYJ20240813110504007.

Data Availability Statement

The data and code supporting this study are available from the authors upon reasonable request.

Conflicts of Interest

Authors Wenzhe Zheng and Zhenguo Wang was employed by the company State Grid Zhejiang Electric Power Co., Ltd. Research Institute. The remaining authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest. The authors declare that this study received funding from State Grid Zhejiang Electric Power Co., Ltd. The funder was not involved in the study design, collection, analysis, interpretation of data, the writing of this article or the decision to submit it for publication.

Appendix A. Theoretical Formulation of Dynamic Wind Loads on Conductors

Appendix A.1. Gust Response Factor and Variance Decomposition

The coordinate system and loading configuration of the double-span conductor assembly are shown in Figure A1. The origin is located at the central support. The left and right horizontal span lengths are denoted by l1 and l2, respectively, and the response considered is the resultant wind-direction reaction transmitted to the central support.
Figure A1. Coordinate system and loading configuration of the double-span conductor assembly. The origin o is located at the central suspension support. The x-axis is aligned with the conductor spans, the y-axis represents the horizontal wind direction, and the z-axis is vertically downward. The left and right span lengths are denoted by l1 and l2, respectively. The distributed wind load and conductor self-weight are indicated.
The conductor-only gust response factor (GRF), defined as the ratio of the statistical peak reaction to the mean reaction, is expressed as
G c = 1 + g L σ r / r ¯
in which Gc is the conductor-only GRF, r ¯ is the mean wind-direction reaction at the central support, σr is the standard deviation of its fluctuating component, and gL is the statistical peak factor.
For comparison with conventional transmission-line design formulations, a reduced conductor-side design combination factor is defined as
G d , c = 1 + ε L g L σ r / r ¯ = 1 + ε L G c − 1
in which εL is the separation coefficient accounting for the non-coincident occurrence of peak wind-induced responses of transmission towers and conductors/ground wires. Following Davenport [5] and Appendix F.4 of the third edition of ASCE Manual of Practice No. 74 [34], εL = 0.75 is adopted as an approximate value for typical transmission-line systems.
The corresponding statistical peak reaction and reduced conductor-side design contribution are expressed as
R c , peak = r ¯ + g L σ r
R c , comb = r ¯ + ε L g L σ r
Rc,peak represents the statistical peak reaction of the conductor assembly itself, whereas Rc,comb represents its conductor-side contribution after applying the separation coefficient. It is not the total transmission-line design load. Since the tower response is not modeled in this study, εL is applied only as a post-processing design assumption, while Gc remains the primary indicator of the conductor-only dynamic response.
The peak factor gL is determined using random vibration theory [35,36].
g L = 2 ln λ y T c + 0.5772 2 ln λ y T c
In Equation (A3), Tc is the reference duration, and λ y + is the mean positive zero-upcrossing rate of the zero-mean fluctuating reaction [37]. For a stationary Gaussian process and a one-sided PSD expressed in Hz, λ y + = m 2 / m 0 , where m n = ∫ 0 f N f n S r ′ y f df is the n-th spectral moment of the fluctuating wind-direction reaction and fN = 1/(2Δt) is the Nyquist frequency. For an ideal continuous theoretical spectrum, the upper integration limit is extended to infinity.
For the prototype conductor, the reference duration is taken as Tc,p = 600 s. Using the time-scale factor λ t ∗ = T m / T p = 0.2049 defined in Equation (8), the equivalent model-scale reference duration is T c , m = λ t ∗ T c , p = 0.2049 × 600 = 122.94   s . For dynamically similar response processes, the zero-upcrossing rate scales inversely with time, such that λ y , m + = λ y , p + / λ t ∗ . Consequently, the product λ y + T c , and hence the peak factor gL, remains invariant under the adopted time scaling.
The peak factor is a PSD-based statistical estimate for the specified reference duration. Accordingly, the corrected experimental PSD and the analytical and FE response PSDs are used to calculate the corresponding spectral moments and peak-factor estimates.
With the covariance between the background and resonant components neglected, the total variance of the fluctuating reaction is expressed as
σ r 2 = σ rB 2 + σ rR 2
in which σ rB and σ rR are the standard deviations of the background and total resonant components, respectively. The corresponding variance contribution ratios are defined as
η B = σ rB 2 / σ r 2 , η R = σ rR 2 / σ r 2 , η B + η R = 1
For multimodal responses, the total resonant variance is evaluated using the complete frequency-response formulation in Appendix B, which accounts for cross-modal covariance. When the cross-modal covariance is negligible, the total resonant variance can be approximated by summing the individual modal variances.

Appendix A.2. Background Response Based on the LRC Method

The background response is treated as quasi-static and evaluated using the Load–Response Correlation (LRC) method [17,18]. Its variance is obtained by integrating the spatial covariance of the fluctuating wind-direction loads, weighted by the influence function for the central-support reaction:
σ rB 2 = ∫ − L 1 L 2 ∫ − L 1 L 2 K F x 1 , x 2 I x 1 I x 2 d x 1 d x 2
in which KF(x1,x2) is the zero-lag covariance of the fluctuating wind-direction loads at locations x1 and x2, and I(x) is the dimensionless influence function for the wind-direction reaction at the central support. The load covariance is obtained from the one-sided cross-spectral density as
K F x 1 , x 2 = ∫ 0 ∞ Re S F x 1 , x 2 , f df
Here, SF(x1,x2,f) is the one-sided cross-spectral density of the fluctuating distributed wind loads at the two locations, and Re[⋅] denotes the real part. For the double-span configuration, the influence function is expressed as
I x = L 1 + x / L 1 − L 1 ≤ x ≤ 0 L 2 − x / L 2 0 < x ≤ L 2
The two branches correspond to the left and right spans, respectively, and follow from the static equilibrium of the two spans under the adopted support conditions. The influence function is zero at both remote supports and reaches unity at the central support.
All power spectral densities and cross-spectral densities in this appendix follow the one-sided convention and are defined for non-negative frequencies.

Appendix A.3. Resonant Response Based on Modal Analysis

The generalized modal force for the j-th global mode is obtained by projecting the distributed fluctuating wind load onto its signed mode shape:
Q j t = ∫ − L 1 L 2 ϕ j x F ′ y x , t dx
in which F ′ y x , t is the fluctuating wind load per unit length and ϕj(x) is the signed mode shape over the full double-span domain.
Under the narrow-band approximation, the variance of the central-support reaction contributed by the j-th mode is estimated as:
σ rRj = π 4 f j S Qj f j ζ aj + ζ S ∫ − L 1 L 2 m ϕ j x I x dx ∫ − L 1 L 2 m ϕ j 2 x dx 2 = π 4 f j S Qj f j ζ aj + ζ S ∫ − L 1 L 2 m ϕ j x I x dx ∫ − L 1 L 2 m ϕ j 2 x dx
in which SQj(fj) is the one-sided power spectral density of the generalized modal force evaluated at the natural frequency fj. The total modal damping ratio is ζj = ζaj + ζS, comprising the aerodynamic and structural damping ratios.
The one-sided power spectral density of the generalized modal force is obtained by integrating the spatial cross-spectral density of the fluctuating wind loads over the full double-span domain:
f j S Qj f j = 2 q z C DL d I u 2 f j S u f j σ u 2 ∫ − L 1 L 2 ∫ − L 1 L 2 ϕ j x 1 ϕ j x 2 γ u x 1 , x 2 , f j d x 1 d x 2
in which q z = ρ V z 2 / 2 is the mean wind pressure, CDL is the drag coefficient, d is the conductor diameter, Iu = σu/Vz is the longitudinal turbulence intensity, σu is the standard deviation of the longitudinal fluctuating wind speed, Su(f) is its one-sided power spectral density, and γu(x1,x2;f) is the square-root coherence.
Applying a Davenport-type exponential root-coherence model [26] to the spanwise separation gives
γ u 1 / 2 x 1 , x 2 ; f = exp − Cf x 1 − x 2 V z
in which γ u 1 / 2 denotes the square-root coherence, defined as the magnitude of the normalized cross-spectral density between two spatial locations, i.e., S u 1 u 2 f / S u 1 f S u 2 f . Accordingly, the magnitude-squared coherence is γ u . Here, C is the dimensionless coherence decay coefficient, which is determined by fitting the measured spanwise coherence data and is equal to 25.74 for the investigated wind field. The phase component of the normalized cross-spectrum is neglected in the adopted exponential model.
The aerodynamic damping ratio of the j-th mode is calculated as
ζ aj = C DL 4 π ρ d 2 m V z f j d
in which ρ is the air density, m is the mass per unit length of the conductor, and Vz is the mean wind speed.
For the equal-span configuration, the natural frequencies are estimated using the idealized cable model [29].
f j = j 2 L H m ,                 H = mg L 2 8 S , ϕ j x = ϕ j , L x ,                 − L ≤ x ≤ 0 ϕ j , R x ,                 0 < x ≤ L , max x ∈ − L , L ϕ j x = 1 ,                 L 1 = L 2 = L
in which j is the modal order, H is the initial horizontal tension, g is the gravitational acceleration, and S is the sag. The horizontal tension is estimated using the parabolic-cable approximation under uniformly distributed self-weight. The functions ϕj,L(x) and ϕj,R(x) denote the mode-shape branches of the left and right spans, respectively.
Under the fixed-sag equilibrium with uniformly distributed self-weight, Equation (A14) gives H/m = gL2/(8S), which is independent of the mass per unit length. Consequently, the predicted natural frequencies remain unchanged when the mass and the corresponding self-weight-induced horizontal tension increase proportionally. For a uniform equivalent mass distribution, m also cancels from the modal participation ratio in Equation (A10), whereas Equation (A13) indicates that ζaj is inversely proportional to m when CDL, d, Vz, and fj are fixed. Thus, the mass deviation primarily affects the resonant response through aerodynamic damping, while the background variance remains unchanged for a fixed wind-load covariance and influence function. The discrete masses of the attached wooden cylinders are represented by an equivalent uniform mass per unit length in this analysis.
The rigid central support restrains transverse displacement and longitudinal sliding, so the two spans have independent transverse vibration modes in the adopted linear modal model. For identical spans, each span-wise modal order produces a pair of repeated eigenvalues. The associated eigenspace can be represented by modes localized to individual spans or by symmetric and antisymmetric combinations. Because the influence function in Equation (A8) is symmetric for equal spans, the antisymmetric combination has zero modal participation in the resultant central-support reaction, whereas the symmetric combination contributes to the reaction and is adopted in Equations (A9)–(A11).
The symmetric global mode shapes used in Equations (A9)–(A11) are normalized over the full double-span domain such that max|ϕj(x)| = 1. The signed mode-shape ordinates are retained in Equation (A11) to account for the spatial distribution and cross-span correlation of the modal excitation. The resonant variance in Equation (A10) is independent of the arbitrary mode-shape normalization: scaling ϕj by a constant scales SQj by the square of that constant, while the squared modal participation factor scales inversely by the same factor.

Appendix B. Frequency-Response Formulation and Validation of the Resonant Response

Appendix B.1. Modal Frequency-Response Function

Equation (A10) estimates the resonant variance using a narrow-band approximation around each natural frequency. The corresponding modal frequency-response function is derived below to evaluate the response over the full frequency range.
For the j-th response-relevant global mode, the modal equation of motion [38] is
M j q ¨ j + 2 ζ j ω j q ˙ j + ω j 2 q j = Q j t
in which qj is the modal coordinate, Qj(t) is the generalized modal force defined in Equation (A9), and M j = ∫ m ϕ j 2 x dx is the generalized modal mass over the full double-span domain. Here, ωj = 2πfj is the circular natural frequency, and ζj = ζaj + ζS is the total modal damping ratio.
The modal contribution to the resonant central-support reaction is obtained from the modal inertial force. The frequency-response function relating the generalized modal force to this reaction component is expressed as:
H j f = − β j f 2 f j 2 − f 2 + i 2 ζ j f j f
in which i = − 1 , and βj is the modal participation factor associated with the central-support reaction:
β j = ∫ − L 1 L 2 m ϕ j x I x dx ∫ − L 1 L 2 m ϕ j 2 x dx
The negative sign follows the adopted support-reaction sign convention. The f2 numerator accounts for the frequency-dependent modal inertial contribution and is retained in the complete frequency-response calculation.

Appendix B.2. Complete Multimodal Frequency-Response Formulation

The resonant central-support reaction is obtained by summing the contributions of the retained global modes in the frequency domain. Because the generalized modal forces may be correlated through the spatially correlated wind loading, both the diagonal and off-diagonal terms are retained in the variance calculation. The total resonant variance is therefore evaluated as:
σ rR , FRF 2 = ∫ 0 ∞ Re ∑ j = 1 N ∑ k = 1 N H j f H k ∗ f S Q j Q k f df
in which N is the number of retained response-relevant global modes, the superscript * denotes complex conjugation, and S Q j Q k f is the one-sided cross-spectral density of the generalized modal forces Qj and Qk.
Projecting the spatial cross-spectral density of the fluctuating wind-direction load onto the signed global mode shapes gives:
S Q j Q k f = 2 q z C DL d I u 2 S u f σ u 2 ∫ − L 1 L 2 ∫ − L 1 L 2 ϕ j x 1 ϕ k x 2 γ u x 1 , x 2 , f d x 1 d x 2
Here, γu is the square-root coherence defined in Equation (A12). For j = k, Equation (A19) gives the one-sided power spectral density of the j-th generalized modal force, whose value at f = fj is used in Equation (A11). For j ≠ k, it gives the cross-spectral density between the generalized modal forces of modes j and k, accounting for their correlation induced by the spatially correlated wind loading.
To quantify the contribution of the off-diagonal terms to the total resonant variance, the cross-modal covariance ratio is defined as:
χ cross = ∫ 0 ∞ Re ∑ j ≠ k H j f H k ∗ f S Q j Q k f df σ rR , FRF 2 × 100 %
The summation includes all ordered pairs with j ≠ k, so no additional factor of two is required. Structural modal uncoupling does not necessarily imply statistically uncorrelated modal forces; χcross therefore represents the signed percentage contribution of the off-diagonal terms to the total resonant variance.
Under the narrow-band approximation, each diagonal term j = k in Equation (A18) yields the modal variance in Equation (A10), provided that the response is concentrated near fj and S Q j Q j f varies slowly over the corresponding modal bandwidth. The total resonant variance can then be approximated by summing the individual modal variances when the off-diagonal terms are negligible; their contribution is quantified by Equation (A20).

Appendix B.3. Numerical Validation Under Different Aerodynamic Damping Levels

To assess the accuracy of the narrow-band approximation in Equation (A10), three representative configurations with low, intermediate, and high first-mode aerodynamic damping ratios are selected from Table 4, corresponding to ζa1 = 0.21, 0.42, and 0.70, respectively. The corresponding span lengths and mean wind speeds are listed in Table A1. For each configuration, the complete frequency-response integration is performed using either the first mode alone or the first five response-relevant global modes, with the structural damping ratio fixed at ζS = 0.05. The resulting standard deviations are compared with those obtained using Equation (A10), and the contribution of the off-diagonal modal terms is evaluated using Equation (A20). The results are summarized in Table A1.
Table A1. Comparison of the narrow-band approximation and complete frequency-response integration for representative configurations with different first-mode aerodynamic damping ratios.
For the first five modes, the FRF/A10 ratios are 0.9401, 0.9534, and 1.0141 for the low-, intermediate-, and high-damping configurations, respectively. Accordingly, the complete frequency-response standard deviations are approximately 6.0% and 4.7% lower than the corresponding A10 estimates in the first two configurations, but 1.4% higher in the high-damping configuration. When only the first mode is considered, the corresponding ratios are 0.9352, 0.9582, and 1.0548, indicating that the complete frequency-response results are approximately 6.5% and 4.2% lower in the first two cases and 5.5% higher in the high-damping case. Overall, the complete frequency-response results differ from the corresponding A10 estimates by approximately 1.4–6.0% for the five-mode calculations across the three configurations. The differences reflect the combined effects of damping, modal properties, and wind-induced excitation, as the span length and mean wind speed also vary among the selected configurations.
For the prototype conductor, the complete frequency-response integration using the first five response-relevant global modes gives a resonant standard deviation of 0.1610 kN, compared with 0.1683 kN obtained using Equation (A10). The corresponding FRF/A10 ratio is 0.9566, indicating that the complete frequency-response result is approximately 4.3% lower than the narrow-band estimate. The off-diagonal modal terms contribute 0.0581% of the total resonant variance.
For the three configurations in Table A1, the off-diagonal terms contribute 0.0240%, 0.0051%, and 0.0215% of the total resonant variance, respectively. The corresponding contribution for the prototype conductor is 0.0581%. These values are all below 0.06%, indicating that the off-diagonal terms have a negligible effect on the total resonant variance in the configurations examined. The spatial coherence of the fluctuating wind loading is retained in the generalized modal-force spectra through Equation (A19), including the diagonal terms.

References

  1. Tapia-Hernández, E.; Sordo, E. Structural behaviour of lattice transmission towers subjected to wind load. Struct. Infrastruct. Eng. 2017, 13, 1462–1475. [Google Scholar] [CrossRef] [Scilit]
  2. Zou, Y.; Lei, X.; Yan, L.; He, X.; Nie, M.; Xie, W.; Luo, X. Full-scale measurements of wind structure and dynamic behaviour of a transmission tower during a typhoon. Struct. Infrastruct. Eng. 2020, 16, 820–830. [Google Scholar] [CrossRef] [Scilit]
  3. Tapia-Hernández, E.; Ibarra-González, S.; De-León-Escobedo, D. Collapse mechanisms of power towers under wind loading. Struct. Infrastruct. Eng. 2017, 13, 766–782. [Google Scholar] [CrossRef] [Scilit]
  4. Tapia-Hernández, E.; De-León-Escobedo, D. Vulnerability of transmission towers under intense wind loads. Struct. Infrastruct. Eng. 2022, 18, 1235–1250. [Google Scholar] [CrossRef] [Scilit]
  5. Davenport, A.G. Gust response factors for transmission line loading. In Wind Engineering; Proceedings of the Fifth International Conference on Wind Engineering, Fort Collins, CO, USA, 8–14 July 1979; Cermak, J.E., Ed.; Pergamon Press: Oxford, UK, 1980; Volume 2, pp. 899–909. [Google Scholar] [CrossRef] [Scilit]
  6. Huang, M.F.; Lou, W.; Yang, L.; Sun, B.; Shen, G.; Tse, K.T. Experimental and computational simulation for wind effects on the Zhoushan transmission towers. Struct. Infrastruct. Eng. 2012, 8, 781–799. [Google Scholar] [CrossRef] [Scilit]
  7. Zhang, W.; Xiao, Y.; Li, C.; Zheng, Q.; Tang, Y. Wind load investigation of self-supported lattice transmission tower based on wind tunnel tests. Eng. Struct. 2022, 252, 113575. [Google Scholar] [CrossRef] [Scilit]
  8. Li, X.-M.; Nie, X.-C.; Zhu, Y.-K.; You, Y.; Yan, Z.-T. Wind tunnel tests on aerodynamic characteristics of ice-coated 4-bundled conductors. Math. Probl. Eng. 2017, 2017, 1628173. [Google Scholar] [CrossRef] [Scilit]
  9. Cai, M.; Xu, Q.; Zhou, L.; Liu, X.; Huang, H. Aerodynamic characteristics of iced 8-bundle conductors under different turbulence intensities. KSCE J. Civ. Eng. 2019, 23, 4812–4823. [Google Scholar] [CrossRef] [Scilit]
  10. Li, J.-X.; Fu, X.; Li, H.-N. Experimental study on aerodynamic characteristics of conductors covered with crescent-shaped ice. Wind Struct. 2019, 29, 225–234. [Google Scholar] [CrossRef]
  11. Lou, W.; Chen, S.; Wen, Z.; Wang, L.; Wu, D. Effects of ice surface and ice shape on aerodynamic characteristics of crescent-shaped iced conductors. J. Aerosp. Eng. 2021, 34, 04021008. [Google Scholar] [CrossRef] [Scilit]
  12. Wan, Z.; Zhang, D.; Li, Z.; Mo, S.; Zhang, Y. A Wind Tunnel Study on the Aerodynamic Characteristics of Ice-Accreted Twin Bundled Conductors. Int. J. Struct. Stab. Dyn. 2022, 22, 2250038. [Google Scholar] [CrossRef] [Scilit]
  13. Riera, J.D.; Oliveira, T.T. Wind–structure interaction in conductor bundles in transmission lines. Struct. Infrastruct. Eng. 2010, 6, 435–446. [Google Scholar] [CrossRef] [Scilit]
  14. Zhang, Z.; Wang, D.; Wang, T.; Yu, Z.; Huang, Z.; Zhang, D. Aeroelastic Wind Tunnel Testing on the Wind-Induced Dynamic Reaction Response of Transmission Line. J. Aerosp. Eng. 2021, 34, 04020105. [Google Scholar] [CrossRef] [Scilit]
  15. Loredo-Souza, A.M.; Davenport, A.G. The effects of high winds on transmission lines. J. Wind Eng. Ind. Aerodyn. 1998, 74–76, 987–994. [Google Scholar] [CrossRef] [Scilit]
  16. Loredo-Souza, A.M.; Davenport, A.G. A novel approach for wind tunnel modelling of transmission lines. J. Wind Eng. Ind. Aerodyn. 2001, 89, 1017–1029. [Google Scholar] [CrossRef] [Scilit]
  17. Kasperski, M.; Niemann, H.-J. The L.R.C. (load-response-correlation)-method a general method of estimating unfavourable wind load distributions for linear and non-linear structural behaviour. J. Wind Eng. Ind. Aerodyn. 1992, 43, 1753–1763. [Google Scholar] [CrossRef]
  18. Kasperski, M. Extreme wind load distributions for linear and nonlinear design. Eng. Struct. 1992, 14, 27–34. [Google Scholar] [CrossRef] [Scilit]
  19. EN 50341-1:2012; Overhead Electrical Lines Exceeding AC 1 kV—Part 1: General Requirements—Common Specifications. European Committee for Electrotechnical Standardization (CENELEC): Brussels, Belgium, 2012.
  20. IEC 60826:2017; Design Criteria of Overhead Transmission Lines, 4th ed. International Electrotechnical Commission: Geneva, Switzerland, 2017.
  21. DL/T 5551-2018; Code for Overhead Transmission Line Loading. China Planning Press: Beijing, China, 2018. (In Chinese)
  22. Task Committee on Electrical Transmission Line Structural Loading. Guidelines for Electrical Transmission Line Structural Loading, 4th ed.; Agnew, F.W., Ed.; ASCE Manuals and Reports on Engineering Practice No. 74; American Society of Civil Engineers: Reston, VA, USA, 2020. [Google Scholar] [CrossRef] [Scilit]
  23. Wang, D.; Ma, Z.; Hong, X.; Fu, Y.; Sun, Q. Analytical estimation and experimental investigation of wind-induced buffeting response of transmission-line-insulator system. Eng. Struct. 2025, 329, 119759. [Google Scholar] [CrossRef] [Scilit]
  24. von Kármán, T. Progress in the Statistical Theory of Turbulence. Proc. Natl. Acad. Sci. USA 1948, 34, 530–539. [Google Scholar] [CrossRef] [Scilit] [PubMed]
  25. Simiu, E.; Potra, F.A.; Nandi, T.N. Determining Longitudinal Integral Turbulence Scales in the Near-Neutral Atmospheric Surface Layer. Bound.-Layer Meteorol. 2019, 170, 349–355. [Google Scholar] [CrossRef] [Scilit]
  26. Davenport, A.G. The spectrum of horizontal gustiness near the ground in high winds. Q. J. R. Meteorol. Soc. 1961, 87, 194–211. [Google Scholar] [CrossRef] [Scilit]
  27. Zou, L.H.; Liang, S.G. A method to evaluate wind force spectra of semi-rigid model in wind tunnel tests. J. Exp. Fluid Mech. 2007, 21, 76–81. (In Chinese) [Google Scholar] [CrossRef]
  28. ANSYS, Inc. Element Reference, Release 12.0; ANSYS, Inc.: Canonsburg, PA, USA, 2009; Sections LINK8 and LINK10; Available online: https://www.mm.bme.hu/~gyebro/files/fea/ansys/ansys_12_element_reference.pdf (accessed on 15 November 2026).
  29. Irvine, H.M.; Caughey, T.K. The linear theory of free vibrations of a suspended cable. Proc. R. Soc. Lond. A Math. Phys. Sci. 1974, 341, 299–315. [Google Scholar] [CrossRef] [Scilit]
  30. Zhang, M.; Zhao, G.; Li, J. Nonlinear Dynamic Analysis of High-Voltage Overhead Transmission Lines. Shock Vib. 2018, 2018, 1247523. [Google Scholar] [CrossRef] [Scilit]
  31. Wang, F.; Lin, H.; Ma, Z. Transmission Line Icing Prediction Based on Dynamic Time Warping and Conductor Operating Parameters. Energies 2024, 17, 945. [Google Scholar] [CrossRef] [Scilit]
  32. Xu, W.; Wang, Z.; Chen, H. Study on the Dynamic Response Characteristics of Non-Uniform Ice-Shedding from Ice-Covered Transmission Lines. Front. Mech. Eng. 2026, 12, 1832735. [Google Scholar] [CrossRef] [Scilit]
  33. Liu, X.; Hu, Y.; Cai, M. Free vibration analysis of transmission lines based on the dynamic stiffness method. R. Soc. Open Sci. 2019, 6, 181354. [Google Scholar] [CrossRef] [Scilit] [PubMed]
  34. Task Committee on Structural Loadings. Guidelines for Electrical Transmission Line Structural Loading, 3rd ed.; Wong, C.J., Miller, M.D., Eds.; ASCE Manuals and Reports on Engineering Practice No. 74; American Society of Civil Engineers: Reston, VA, USA, 2010. [Google Scholar] [CrossRef] [Scilit]
  35. Solari, G. A generalized definition of gust factor. J. Wind Eng. Ind. Aerodyn. 1990, 36, 539–548. [Google Scholar] [CrossRef]
  36. Solari, G. Gust Buffeting. II: Dynamic Alongwind Response. J. Struct. Eng. 1993, 119, 383–398. [Google Scholar] [CrossRef] [Scilit]
  37. Rice, S.O. Mathematical Analysis of Random Noise. Bell Syst. Tech. J. 1945, 24, 46–156. [Google Scholar] [CrossRef] [Scilit]
  38. Tedesco, J.W.; McDougal, W.G.; Ross, C.A. Structural Dynamics: Theory and Applications; Addison-Wesley: Menlo Park, CA, USA, 1999. [Google Scholar]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Article Metrics

Citations

Article Access Statistics

Multiple requests from the same IP address are counted as one view.