Abstract
This paper proposes a method for robust tracking control synthesis of dual-active-bridge (DAB) DC–DC converters with parameter uncertainties and input saturation. In the proposed method, the nonlinear function of the phase shift ratio is expressed as a control input, and the phase shift ratio is determined by the one-to-one relationship with the control input. Especially, the proposed method is developed with consideration of the input saturation phenomenon that occurs physically in the phase shift ratio of DAB DC–DC converters. Furthermore, based on the proposed method, a set of exponential constrained stabilization conditions for DAB DC–DC converter systems with parameter uncertainties is provided to ensure a fast convergence rate. Finally, to verify the effectiveness of the proposed control method, various simulation results are provided and compared with the well-known improved model phase shift control (IMPSC) and load current feedforward (LCFF) control methods.
Keywords:
dual-active bridge (DAB); robust control; input saturation; isolative bidirectional DC–DC converter MSC:
93C05
1. Introduction
Isolated bidirectional DC–DC (IBDC) converters have been widely used in energy storage systems (ESSs) for DC microgrids or smart girds [1], automotive applications [2], and solid-state transformer (SST) applications [3]. Thus, many IBDC topologies have been discussed in both academia and industry, including dual-flyback converters [4], dual-Zeta converters [5], forward-flyback converters [6], dual-push–pull converters [7], dual-half-bridge converters [8], and dual-active bridge (DAB) converters [9]. Among all these types of IBDC converters, the DAB converter has been regarded as one of the most-promising topologies due to its distinct advantages such as inherent soft switching, bidirectional power transfer capability, symmetrical structure, and high power density. When developing the DAB DC–DC converter, the main challenges arise from the input voltage fluctuation, the output load change, and the output voltage or power reference variation. Furthermore, it is worth noticing that the transient response performance of the DAB DC–DC converter can be deteriorated by the parameter uncertainty of the converter. For this reason, various control strategies have been proposed such that the DAB DC–DC converter has more improved transient response performance. As one of the most intuitive techniques, References [10] and [11] proposed a method of using a proportional–integral (PI) controller to regulate the output voltage. However, the drawback of this method is that the output voltage performance deteriorates as the load current changes.
In order to prevent the output voltage performance degradation despite the change of the load current, the linearized control method [12,13], model phase shift control (MPSC) method [14], and load current feedforward (LCFF) control method [15,16] have been proposed by taking the output the load current as the measured disturbance. Thereafter, based on the MPSC method, the work in [17] proposed an improved model phase shift control (IMPSC) to achieve a fast dynamic response on the output voltage. However, the disadvantage of the proposals in [10,11,12,13,14,15,16,17] is that the phase shift ratio is still affected by the uncertainty of the internal inductance. To solve the problem arising from this parameter uncertainty, a virtual direct power control (VDPC) for DAB DC–DC converters was proposed in [18]. The main advantage of the VDPC is that the phase shift ratio can be determined without utilizing inductance information. However, the VDPC method (as well as MPSC, LCFF control, and IMPSC) has the disadvantage that one additional current sensor must be used to measure the output load current, and the uncertainty of the load resistance and capacitance on the output side cannot be taken into account. To avoid the addition of such a current sensor, Reference [19] proposed a method of designing a nonlinear disturbance observer (NDO) that can estimate the output load current. However, it should be noted that the NDO was also designed without consideration of parameter uncertainty. Recently, in [20,21], a moving discretized control set model-predictive control (MDCS-MPC) was proposed as a potential technique applicable to DAB DC–DC converters, where the trial and error method is used to find the best phase shift value. However, MDCS-MPC requires the use of a trial and error approach to obtain the optimal phase shift value and the implementation of an artificial neural network approach to find the weighting matrix of the cost function. Furthermore, MDCS-MPC provides no way to handle the problems of the disturbance and uncertainties present in power converter systems. As an alternative, the disturbance estimation method was introduced in [22,23], but it also has the weakness of having to set too many tuning parameters therein. Recently, an adaptive model predictive control for the DAB DC–DC converter was investigated based on the MDCS-MPC method [24]. This method enables the selection of the trapezoidal and triangular modulation to reduce switching losses.
To fill the gap discussed above, this paper proposes a method for robust tracking control of DAB DC–DC converters with parameter uncertainties and input saturation. Furthermore, the proposed control method is developed so that the DAB DC–DC converter can be robust against sudden changes in the input voltage source and load resistance. To be specific, the contributions of this paper are summarized as follows:
- Different from the the aforementioned methods, this paper provides a method to consider the phase shift nonlinearity term as a control input. Accordingly, this method opens the possibility that the phase shift ratio can be determined by designing a robust control input for DAB DC–DC converter systems with parameter uncertainties.
- In order to achieve a fast convergence rate, this paper proposes an effective method for exponential saturated control synthesis of DAB DC–DC converter systems with parameter uncertainties. Based on several convex optimization techniques, the overall stabilization conditions are formulated in terms of the linear matrix inequality (LMI), which offers a set of optimal control gains for DAB DC–DC converter systems.
- Indeed, the input saturation of DAB DC–DC converters has not been taken into account in the control design process until now. Thus, to overcome this lack of research, this paper proposes a method to analyze the saturation phenomenon that occurs physically in the phase shift ratio of DAB DC–DC converters and reflect its effect on the control design.
- In order to demonstrate the effectiveness of the proposed control method, our results are compared to the aforementioned IMPSC and LCFF control methods. Furthermore, to verify the robustness of the proposed method and to show the effect of saturated input, various scenarios are produced by considering changes in the source voltage and load resistance.
The rest of the paper is organized as follows. Section 2 presents the modeling of the DAB DC–DC converter system. Section 3 proposes the feedback control design, and Section 4 provides the simulation results. Finally, the paper is concluded in Section 5.
Notations: For any matrix , () means that is real symmetric and positive semidefinite (definite). In symmetric block matrices, is used as an ellipsis for terms induced by symmetry. For any square matrix , ; stands for a block-diagonal matrix; ; and denote the minimum and maximum eigenvalues of the corresponding matrix, respectively; and returns the sign of the corresponding argument. For any matrix , stands for an ellipsoid defined as ; for a scalar and a matrix , stands for a linear region defined as follows: .
2. System Description and Preliminaries
So far, various types of modeling for a DAB DC–DC converter system have been proposed such as the discrete-time model [25,26], generalized average model [27], reduced-order model [28,29], and improved reduced model [30]. Among these methods, the reduced-order model, presented in [28,29], exhibits the best choice in the aspects of complexity and accuracy [31], which will be utilized in this paper.
Figure 1 shows the topology of a two-stage single phase for a dual-active-bridge (DAB) DC–DC converter, where:
Figure 1.
The topology of a dual-active-bridge converter.
- and are the given constant input voltage and the measurable output voltages, respectively;
- is the output voltage on the primary bridge (Bridge 1);
- is the input voltage on the secondary bridge (Bridge 2);
- , , and are the output current, the capacitor current, and the load current, respectively;
- is the phase shift inductor current;
- L is the total inductance consisting of the external inductance and the transformer leakage inductor;
- R is the equivalent load resistance satisfying , where and are known;
- is the capacitance on the input side;
- is the capacitance on the output side such that , where and are known.
The considered DAB DC–DC converter consists of two bridges connected through an inductor L and an isolated transformer, and there are four gate drives on each bridge, where the switches to are used to control the gate drives. In general, the DAB DC–DC converter uses single-phase-shifted (SPS) square-wave modulation to control its power. Figure 2 shows the operating waveforms of this converter based on SPS square-wave modulation [9].
Figure 2.
Operating waveforms of the DAB converter using SPS modulation.
To be specific, a pair of switches , , , and operates complementarily, as shown in Figure 2.
Furthermore, the duty ratio of the primary and secondary bridges is fixed at , and the phase shift is adjustable to control the output voltage tracking the reference.
Especially, since the current is affected by and L, the transferred power from the primary bridge to the secondary bridge is generated by the phase shift .
Thus, as in [32], the power of the considered converter is obtained as follows:
where denotes the phase shift ratio, n denotes the transformer turns ratio, and denotes the switching frequency.
In addition, the transferred power is expressed as follows:
Furthermore, by the Kirchhoff current law, it is given that
Accordingly, using the first-order Euler approximation with the sampling time , the discrete-time model of (5) is represented as follows:
where
In addition, since and , the system coefficients are also bounded as and , which can be rearranged as follows:
where
Remark 1.
In (6), the replacement is reasonable because the phase shift ratio can be reconstructed by according to the following one-to-one relationship:
The purpose of this paper is to design a controller that allows the output voltage to track the reference voltage . To effectively address this reference tracking problem, this paper adds the following accumulator:
with . As a result, letting and combining (6) and (8), we can obtain
subject to the following input saturation:
where
In addition, based on (6) and (8), the steady-state values of , , and are given, respectively, as follows:
However, since R is bounded, it is hard to directly obtain from (11).
That is, based on , it is given that
Thus, can be represented as follows:
where is the central value in the steady state and is the uncertain constant value, i.e.,
Accordingly, it follows from (9) that
where and are the steady-state values of and , respectively,. By letting
the error system model is described as follows:
Subsequently, let us establish as follows:
where is a feedback control input and is a tuning control component used to eliminate .
Then, based on (16), the closed-loop system is described as follows:
As a result, since the tuning control component can be set as by making the steady-state error zero in real-time, this paper focuses on designing a feedback control that stabilizes the following system subject to (18):
where
The following lemmas will be used for our main derivation.
Lemma 1
([33]). Let X, , and Y be real matrices with appropriate dimensions. Then, if satisfies , then for a scalar , it holds that
Lemma 2
([34]). For a single control input , if holds, then
where denotes an element of the set and , and belongs to the standard simplex.
3. Feedback Control Design
To begin with, let us establish the feedback control input and the auxiliary control input, respectively, as follows:
where and are the variables to be designed later. In addition, let us consider the following Lyapunov function:
where . Then, it holds that
where and .
The following lemma provides the exponential stabilization conditions and the corresponding invariant ellipsoid set for (19).
Lemma 3.
Suppose that it holds that
Then, the saturated system (19) is robustly and exponentially stable, where the error state satisfies that .
Proof.
The following theorem provides the robust stabilization conditions for (19), formulated in terms of linear matrix inequalities (LMIs).
Theorem 1.
For a prescribed and a given initial error state , suppose that there exist , , , , and such that the following conditions hold:
Then, the saturated system (19) is robustly and exponentially stable, and the feedback control gain and the auxiliary control gain are obtained as and , respectively.
Proof.
By the Schur complement, Condition (34) is converted into , which ensures , i.e.,
In addition, Condition (34) is converted into , which is equivalent to (29) because . Thus, based on Lemma 3, Conditions (28), (34), and (35) lead to
Accordingly, by Lemma 2, it is given that
by substituting (38) into (19), it is obtained as follows:
where
Now, the remaining task is to obtain an LMI-based condition from (28). For this task, based on (39), let us first represent (28) as follows:
where and . Then, we can see that (28) is ensured by
for which the Schur complement becomes
Remark 2.
The smaller the value of ξ, the larger the value of α is, which accelerates the convergence speed of the error state to zero.
For a more detailed explanation, Figure 3 presents the block diagram of the proposed control scheme, where only the source voltage and the output voltage are required to be measurable.
Figure 3.
Block diagram of the robust control for the DAB DC–DC converter with steady-state error and input saturation.
In addition, the procedure of designing the phase shift ratio is summarized as follows:
- Step 1.
- Step 2.
- Step 3.
- Based on (7), obtain the phase shift ratio from , and apply to the single-phase-shift pulse modulator.
4. Simulation Results
For accurate verification, the performance of the controller designed for DAB DC–DC converters was analyzed using the PSIM software tool [35]. Furthermore, to demonstrate the effectiveness of the proposed method, our results were compared with the IMPSC method [17] and the LCFF control method [14]. For a specific simulation, the system parameters were set as shown in Table 1.
Table 1.
System parameters.
Based on such a setting, for , Theorem 1 provides
For comparison, the control gains of the IMPSC and LCFF control methods are designed based on the phase margin at 85 degree and the cutoff frequency at 4500 Hz such that its own optimized performance can be achieved.
Remark 3.
It is worth noticing that the IMPSC and LCFF methods require an additional current sensor, but the proposed method can be implemented only with input and output voltage sensors. That is, the number of measuring sensors can be reduced through the proposed control method.
In the first simulation, the reference tracking control was performed for nominal systems with and , where V. Figure 4 shows the simulation results of the DAB DC–DC converter during the start-up process. As shown in Figure 4a, the charging time of the capacitor output was ms for both the IMPSC and LCFF control methods. On the other hand, the proposed control method took only 8 ms to reach the capacitor output to the steady-state value, which illustrates that the proposed control method requires a shorter charging time and has an improved overshoot response compared to other methods. In addition, Figure 4b–d show the inductor current of the IMPSC, the LCFF control, and the proposed control method, respectively, during the start-up process.
Figure 4.
Simulation results of the IMPSC, the LCFF control, and proposed control schemes during the startup process.
Figure 5 shows the simulation results of the DAB DC–DC converter for the case where steps up from 40 V to 45 V at s. Specifically, from Figure 5b–d, it can be found that the IMPSC and the LCFF control methods required ms and ms, respectively, to approach the output voltage to its the steady-state value, and the proposed control method required only ms relatively. Furthermore, the proposed control method provided a smooth transient response without overshoot, but the IMPSC and LCFF control methods generated an overshoot response with a maximum value of V. Conversely, Figure 6 shows the simulation results for the case where steps down from 45 V to 40 V at s. As shown in Figure 6b–d, for the IMPSC, the LCFF control, and the proposed control methods, the settling times are given as ms, ms, and 7 ms, respectively. That is, from Figure 6, it can be seen that the proposed control method provides a better time response than the other methods.
Figure 5.
Simulation results of the output voltage when the reference steps up from 40 V to 45 V at s.
Figure 6.
Simulation results of the output voltage when the reference steps down from 45 V to 40 V at s.
In the second simulation, the load resistance was set to be changed to show the robustness of the proposed control method. Figure 7 shows the simulation results for the case where R steps up from 50 to 100 at s. As shown in Figure 7a, the change in the load resistance decreased the load current by A at s and caused a maximum overshoot of V on the output voltage. To be specific, for the IMPSC, the LCFF control, and the proposed control methods, the settling times are given as 22 ms, 14 ms, and 10 ms, respectively, which reveals that our method achieved a shorter settling time than the other methods. Conversely, Figure 8 shows the simulation results for the case where R steps down from 100 to 50 at s. As shown in Figure 8, the change in the load resistance increased the load current by A at s and caused a maximum overshoot of V on the output voltage. To be specific, for the IMPSC, the LCFF control, and the proposed control methods, the settling times are given as 81 ms, 42 ms, and 42 ms, respectively, which illustrates that the proposed method exhibited a smoother transient response and smaller oscillation than the other methods. Thus, from Figure 7 and Figure 8, it can be seen that the proposed control method provided better performance than the other methods.
Figure 7.
Simulation results of the output voltage when load steps up from 50 to 100 .
Figure 8.
Simulation results of the output voltage when load steps down from 100 to 50 .
In the third simulation, the source voltage was set to be changed to show the robustness of the proposed control method. Figure 9 shows the simulation results for the case where steps down from 100 V to 85 V at s, where = 40 V. As shown in Figure 9b–d, the IMPSC method caused a maximum overshoot of V, the LCFF control method caused a maximum overshoot of V, and the proposed control method caused a maximum overshoot of V. Overall, the transient response quickly disappeared as the output voltage converged to the reference voltage. Specifically, for the IMPSC, the LCFF control, and the proposed control methods, the settling times are given as ms, 16 ms, and 9 ms, respectively, which reveals that our method required a shorter settling time than the other methods. That is, from Figure 9, it can be seen that the proposed control method is the most excellent for improving the performance among the three control methods.
Figure 9.
Simulation results of the output voltage when the input voltage steps down from 100 V to 85 V.
Conversely, Figure 10 show the simulation results for the case where steps up from 85 V to 100 V at s. As shown in Figure 10b–d, the IMPSC and the LCFF control methods required ms and ms, respectively, to approach the output voltage to its steady-state value, and the proposed control method required 10 ms relatively. Thus, from Figure 10, it can be seen that our method had a shorter settling time than other methods. Finally, the fourth simulation is given to verify the effect of the proposed control method on the input saturation of DAB DC–DC converters. Figure 11 shows the transient response of the output voltage for the control system with/without input saturation. As shown in Figure 11b, the input saturation occurred during the time from ms to ms when the control signal became less than . In addition, Figure 11a shows that the controller designed without input saturation considerations required a settling time of ms, but our control method, which can cope with the saturation phenomenon, required a settling time of 8 ms. Thus, it can be seen that the proposed control method has more advantages when the input saturation occurs.
Figure 10.
Simulation results of the output voltage when the input voltage steps up from 85 V to 100 V.
Figure 11.
Simulation results of the output voltage when applying with/without input saturation.
To verify whether the proposed method can work well in the case of the no-load condition, Figure 12 shows the simulation results of the output voltage when the no-load condition was applied from s to s. It can be seen from Figure 12 that the output voltage of the DAB DC–DC converter was not affected by the no-load condition when the no-load situation occurred from s to s. In addition, the result shows that the proposed method worked well when the reference changes from 40 V to 45 V at s under the no-load condition.
Figure 12.
Simulation results of output voltage when the no-load condition is applied.
To validate the efficacy of the proposed method in the steady state, Figure 13 shows the simulation for the error between the reference and the output voltage.
Figure 13.
Simulation results for the error between the reference and the output voltage in the steady-state condition.
As shown in Figure 13, the steady-state error is given V, V, and V for the IMPSC, LCFF control, and the proposed methods, respectively, which indicates that the proposed method exhibited the best performance compared to other methods under the steady-state condition.
5. Concluding Remarks
This work focused on developing a robust tracking control design for DAB DC–DC converters with parameter uncertainties and input saturation. From the obtained results, the following two advantages of the proposed method were verified:
- (1)
- The fast transient response of DAB DC–DC systems was achieved by solving an exponential stabilization problem;
- (2)
- The output voltage performance for the change of voltage source and load resistance was further improved through the proposed method over the IMPSC and LCFF control methods.
In the future, the proposed method will be further generalized so that it can be combined with the sampled data control scheme.
Author Contributions
Conceptualization, N.N.N.; methodology, S.H.K. and N.N.N.; software, N.N.N.; validation, S.H.K. and N.N.N.; formal analysis, S.H.K. and N.N.N.; investigation, S.H.K. and N.N.N.; resources, S.H.K.; data curation, S.H.K. and N.N.N.; writing—original draft preparation, S.H.K. and N.N.N.; writing—review and editing, S.H.K. and N.N.N.; visualization, S.H.K. and N.N.N.; supervision, S.H.K.; project administration, S.H.K.; funding acquisition, S.H.K. All authors have read and agreed to the published version of the manuscript.
Funding
This work was supported by the National Research Foundation of Korea Grant funded by the Korean Government (NRF-2018R1D1A1B07041456).
Conflicts of Interest
The authors declare no conflict of interest.
References
- Ye, Q.; Mo, R.; Li, H. Low-frequency resonance suppression of a dual-active-bridge DC/DC converter enabled DC microgrid. IEEE J. Emerg. Sel. Top. Power Electron. 2017, 5, 982–994. [Google Scholar] [CrossRef] [Scilit]
- Hoek, V.; Neubert, H.; Doncker, M.D.; Rik, W. Enhanced modulation strategy for a three-phase dual-active-bridge—Boosting efficiency of an electric vehicle converter. IEEE Trans. Power Electron. 2013, 28, 5499–5507. [Google Scholar] [CrossRef] [Scilit]
- Shi, W.H.; Chen, H.; Hu, J.; Jiang, Y.; Chen, L.; Guipeng, M.J. Minimum-backflow-power scheme of DAB-based solid-state transformer with extended-phase-shift control. IEEE Trans. Ind. Appl. 2018, 54, 3483–3496. [Google Scholar] [CrossRef] [Scilit]
- Yang, J.W.; Do, H.-L. Soft-switching dual-flyback DC–DC converter with improved efficiency and reduced output ripple current. IEEE Trans. Ind. Electron. 2018, 64, 3587–3594. [Google Scholar] [CrossRef] [Scilit]
- Murthy-Bellur, D.K.; Marian, K. Isolated two-transistor zeta converter with reduced transistor voltage stress. IEEE Trans. Circuits Syst. II-Express Briefs 2010, 58, 41–45. [Google Scholar] [CrossRef] [Scilit]
- Zhang, F.; Yan, Y. Novel forward–flyback hybrid bidirectional DC–DC converter. IEEE Trans. Ind. Electron. 2008, 56, 1578–1584. [Google Scholar] [CrossRef] [Scilit]
- Zhang, Z.; Thomsen, O.C.; Andersen, M.A.E. Optimal design of a push-pull-forward half-bridge (PPFHB) bidirectional DC–DC converter with variable input voltage. IEEE Trans. Ind. Electron. 2011, 59, 2761–2771. [Google Scholar] [CrossRef] [Scilit]
- Han, B.; Bai, C.; Lee, J.S.; Kim, M. Repetitive controller of capacitor-less current-fed dual-half-bridge converter for grid-connected fuel cell system. IEEE Trans. Ind. Electron. 2018, 65, 7841–7855. [Google Scholar] [CrossRef] [Scilit]
- Doncker, R.W.D.; Divan, D.M.; Kheraluwala, M.H. A three-phase soft-switched high-power-density DC/DC converter for high-power applications. IEEE Trans. Ind. Appl. 1991, 27, 63–73. [Google Scholar] [CrossRef] [Scilit]
- Kheraluwala, M.N.; Gascoigne, R.W.; Divan, D.M.; Baumann, E.D. Performance characterization of a high-power dual-active-bridge DC-to-DC converter. IEEE Trans. Ind. Appl. 1992, 28, 1294–1301. [Google Scholar] [CrossRef] [Scilit]
- Qin, H.; Kimball, J.W. Closed-loop control of DC–DC dual-active-bridge converters driving single-phase inverters. IEEE Trans. Power Electron. 2013, 29, 1006–1017. [Google Scholar]
- Segaran, D.; Holmes, D.G.; McGrath, B.P. Enhanced load step response for a bidirectional DC–DC converter. IEEE Trans. Power Electron. 2012, 28, 371–379. [Google Scholar] [CrossRef] [Scilit]
- Tong, A.; Hang, L.; Chung, H.S.-H.; Li, G. Using sampled-data modeling method to derive equivalent circuit and linearized control method for dual-active-bridge converter. IEEE J. Emerg. Sel. Top. Power Electron. 2019, 9, 1361–1374. [Google Scholar] [CrossRef] [Scilit]
- Bai, H.; Nie, Z.; Mi, C.C. Experimental comparison of traditional phase-shift, dual-phase-shift, and model-based control of isolated bidirectional DC–DC converters. IEEE Trans. Power Electron. 2009, 25, 1444–1449. [Google Scholar] [CrossRef] [Scilit]
- Wang, X.; Lin, H. DC-link current estimation for load-side converter of brushless doubly-fed generator in the current feedforward control. IET Power Electron. 2016, 9, 1703–1710. [Google Scholar] [CrossRef] [Scilit]
- Ji, Z.; Wang, Q.; Li, D.; Sun, Y. Fast DC-Bias Current Control of Dual Active Bridge Converters With Feedforward Compensation. IEEE Trans. Circuits Syst. II-Express Briefs. 2020, 67, 2587–2591. [Google Scholar] [CrossRef] [Scilit]
- Zhao, W.; Zhang, X.; Gao, S.; Ma, M. Improved model-based phase-shift control for fast dynamic response of dual-active-bridge DC/DC converters. IEEE J. Emerg. Sel. Top. Power Electron. 2020, 9, 223–231. [Google Scholar] [CrossRef] [Scilit]
- Song, W.; Hou, N.; Wu, M. Virtual direct power control scheme of dual-active-bridge DC–DC converters for fast dynamic response. IEEE Trans. Power Electron. 2017, 33, 1750–1759. [Google Scholar] [CrossRef] [Scilit]
- Xiong, F.; Wu, J.; Liu, Z.; Hao, L. Current sensorless control for dual-active-bridge DC–DC converter with estimated load-current feedforward. IEEE Trans. Power Electron. 2017, 33, 3552–3566. [Google Scholar] [CrossRef] [Scilit]
- Chen, L.; Chen, S.; Shao, Q.; Xiao, L.; Tarisciotti, P.W. Wheeler and T. Dragičević. Model predictive control for dual-active-bridge converters supplying pulsed power loads in naval DC micro-grids. IEEE Trans. Power Electron. 2019, 35, 1957–1966. [Google Scholar] [CrossRef] [Scilit]
- Chen, L.; Tarisciotti, L.; Costabeber, A.; Wheeler, P.; Zanchetta, P. Model predictive control for isolated DC/DC power converters with transformer peak current shaving. In Proceedings of the 2018 IEEE Energy Conversion Congress and Exposition, Portland, OR, USA, 23–27 September 2018; pp. 5954–5960. [Google Scholar]
- Ali, M.; Yaqoob, M.; Cao, L.; Loo, K.H. Disturbance-observer-based DC-bus voltage control for ripple mitigation and improved dynamic response in two-stage single-phase inverter system. IEEE Trans. Ind. Electron. 2018, 66, 6836–6845. [Google Scholar] [CrossRef] [Scilit]
- Wu, Y.; Mahmud, M.H.; Zhao, Y.; Mantooth, H.A. Uncertainty and disturbance estimator-based robust tracking control for dual-active-bridge converters. IEEE Trans. Transp. Electrif. 2020, 6, 1791–1800. [Google Scholar] [CrossRef] [Scilit]
- Nardoto, A.; Amorim, A.; Santana, N.; Bueno, E.; Encarnação, L.; Santos, W. Adaptive Model Predictive Control for DAB Converter Switching Losses Reduction. Energies 2022, 15, 6628. [Google Scholar] [CrossRef] [Scilit]
- Shi, L.; Lei, W.; Li, Z.; Huang, J.; Cui, Y.; Wang, Y. Bilinear discrete-time modeling and stability analysis of the digitally controlled dual-active-bridge converter. IEEE Trans. Power Electron. 2016, 32, 8787–8799. [Google Scholar] [CrossRef] [Scilit]
- Zane, D.R.; Maksimović, D. Discrete-time small-signal modeling of a 1 MHz efficiency-optimized dual-active-bridge converter with varying load. In Proceedings of the 2012 IEEE 13th Workshop on COMPEL, Kyoto, Japan, 10–13 June 2012; pp. 1–7. [Google Scholar]
- Qin, H.; Kimball, J.W. Generalized average modeling of dual-active-bridge dc–dc converter. IEEE Trans. Power Electron. 2011, 27, 2078–2084. [Google Scholar]
- Bai, H.; Mi, C.; Wang, C.; Gargies, S. The dynamic model and hybrid phase-shift control of a dual-active-bridge converter. In Proceedings of the 34th Annual Conference of the IEEE Industrial Electronics Society, Orlando, FL, USA, 10–13 November 2008; pp. 2840–2845. [Google Scholar]
- Alonso, A.R.R.; Sebastian, J.; Lamar, D.G.; Hernando, M.M.; Vazquez, A. An overall study of a Dual Active Bridge for bidirectional DC/DC conversion. In Proceedings of the 2010 IEEE Energy Conversion Congress and Exposition, Atlanta, GA, USA, 12–16 September 2010; pp. 1129–1135. [Google Scholar]
- Zhang, K.; Shan, Z.; Jatskevich, J. Large-and small-signal average-value modeling of dual-active-bridge DC–DC converter considering power losses. IEEE Trans. Power Electron. 2016, 32, 1964–1974. [Google Scholar] [CrossRef] [Scilit]
- Shao, S.; Chen, L.; Shan, Z.; Gao, F.; Chen, H.; Sha, D.; Dragicevic, T. Modeling and advanced control of dual-active-bridge DC–DC converters: A review. IEEE Trans. Power Electron. 2021, 37, 1524–1547. [Google Scholar] [CrossRef] [Scilit]
- Mi, C.C.; Bai, H.; Wang, C.T.; Gargies, S. Operation, design and control of dual H-bridge-based isolated bidirectional DC–DC converter. IET Power Electron. 2008, 1, 507–517. [Google Scholar] [CrossRef] [Scilit]
- Xie, L.; de Souza Carlos, E. Robust H/sub infinity / control for linear systems with norm-bounded time-varying uncertainty. IEEE Trans. Autom. Control 1992, 37, 1188–1191. [Google Scholar] [CrossRef] [Scilit]
- Cao, Y.-Y.; Lin, Z.; Shamash, Y. Set invariance analysis and gain-scheduling control for LPV systems subject to actuator saturation. Syst. Control Lett. 2002, 46, 137–151. [Google Scholar] [CrossRef] [Scilit]
- PSIM User’s Manual. Powersim Inc. 2021. Available online: https://powersimtech.com/wp-content/uploads/2021/01/PSIM-User-Manual.pdf (accessed on 16 November 2022).
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations. |
© 2022 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).












