A Convolutional Neural Network(CNN)–Residual Network (ResNet)-Based Faulted Line Selection Method for Single-Phase Ground Faults in Distribution Network

,
and
1
State Grid Sichuan Electric Power Company Electric Power Science Research Institute, Chengdu 610041, China
2
Power System Security and Operation Key Laboratory of Sichuan, Chengdu 610000, China
3
Anhui Hekai Electric Technology Co., Ltd., Hefei 230051, China
*
Author to whom correspondence should be addressed.
This article belongs to the Section Artificial Intelligence

Abstract

Single-phase ground faults account for more than 80% of total faults in distribution networks. However, the introduction of distributed generation complicates power grid topology, leading to strong nonlinearity and non-stationarity in the zero-sequence current. This limits the accuracy of traditional faulted line selection methods. To address this problem, a CNN–ResNet-based method for faulted line selection for single-phase ground faults in distribution networks is proposed. Firstly, a 10 kV arc ground fault simulation test platform is built to analyze the nonlinear distortion characteristics of fault current. The WOA–VMD algorithm, optimized by permutation entropy, is used to denoise the zero-sequence current signal. The Gram Angular Difference Field (GADF) is then adopted to convert the one-dimensional signal into a two-dimensional image that retains its temporal characteristics. A hybrid deep learning model is constructed by fusing the one-dimensional time-domain features extracted by CNN and the two-dimensional time-frequency image features extracted by ResNet34. Matlab/Simulink simulations and physical experimental verification demonstrate that the proposed method achieves a training accuracy of over 97%, with zero misjudgments recorded in 15 arc grounding fault tests, representing a significant improvement in accuracy compared with existing diagnostic algorithms. It can adapt to complex scenarios such as high-resistance grounding and changes in neutral point grounding mode, effectively improving the accuracy and robustness of faulted line selection and providing technical support for the safe operation of distribution networks.

1. Introduction

In China, distribution networks below 35 kV generally adopt the neutral point ineffectively grounded mode, where single-phase ground faults account for more than 80% of the total faults [1,2,3]. When a single-phase ground fault occurs in a small current grounding system, failure to clear the fault in time will cause insulation breakdown, trigger more serious faults, and affect the safe and reliable operation of the distribution network [4,5,6]. With access to distributed generation, the topology of the distribution network becomes more complex, and the zero-sequence current signal shows strong randomness and nonlinearity, making it difficult for traditional faulted line selection methods to identify the fault line accurately. Therefore, there is an urgent need to propose a new faulted line selection method to improve the accuracy of faulted line selection.
Current faulted line selection methods for small-current grounding systems (SCGSs), also referred to as non-effectively or non-solidly earthed distribution networks, are generally classified into model-driven and data-driven approaches based on the feature quantities and models they employ [7]. Model-driven methods follow a consistent technical framework: establishing a general physical model of the SCGS, extracting typical fault-related features from the model (both pre- and post-fault occurrence), and identifying the faulted line through mathematical calculation and analysis of these extracted features. The foundational techniques in this category include the zero-sequence current amplitude method and zero-sequence current phase method, with derivative approaches such as the zero-sequence admittance method and negative-sequence current method subsequently developed to overcome the limitations of early methods. However, traditional power frequency-based model-driven strategies often suffer from poor adaptability to complex scenarios (e.g., high fault resistance, weak fault signals, or distributed generator integration), prompting extensive research to advance the field via advanced signal processing, innovative decision criteria, scenario-specific designs, and hybrid technical integration.
To enhance the extraction of effective fault features, numerous studies have integrated advanced signal processing techniques. Reference [8] proposed a faulted line selection method based on wavelet analysis of transient process signals, while Reference [9] adopted the Hilbert transform to extract instantaneous power information for line identification. Complementary efforts include the fault-tolerant faulty phase selection method (coupled with the active-intervention arc suppression device AASD–SSM) that incorporates modified wavelet packet transform (MWPT) [10]; a single-phase grounding fault location method leveraging traveling wave time-frequency characteristics, implemented with B-spline wavelet and improved matrix pencil algorithm [11]; and a power frequency pre-breakdown voltage processing-based method to avoid misjudgments caused by EMVT free oscillation [12]. Reference [13] further developed a protection scheme using transient zero-sequence current kurtosis for fault detection and skewness for feeder identification, ensuring high reliability under complex conditions.
Novel decision criteria and mathematical algorithms have been introduced to improve judgment accuracy and robustness. Reference [14] proposed an active signal injection-based line selection method, integrating all-phase FFT (APFFT) for signal processing, dynamic injection frequency selection, and injected signal active power as the core criterion. Reference [15] developed a fault location method based on synchronous transient energy analysis in a selected frequency band (SFB), implemented with distribution-level phasor measurement units (D-PMUs). Reference [16] presented a Hausdorff distance-based faulty phase selection method for high-resistance single-phase-to-ground faults (SPGs) in resonantly grounded systems, validated via PSCAD/EMTDC simulations. Multi-criteria and machine learning-aided strategies have also gained traction: Reference [17] proposed a CEEMDAN–Hilbert transform combined multi-criteria voting method, while Reference [18] developed an improved Hilbert–Huang transform–random forest approach for binary classification of transient current features, enhancing adaptability to weak fault conditions.
For specialized application scenarios, tailored model-driven methods have been developed to address unique challenges. References [19,20] proposed identical zero-sequence current difference-based line selection methods for arc-extinguishing coil-grounded active distribution networks, featuring grounding mode switching, current ratio criteria, and strong transition resistance tolerance (validated via PSCAD). For asymmetric distribution networks, Reference [21] introduced an active current injection-based faulty phase selection method that suppresses zero-sequence overvoltage and ground-fault current, with high sensitivity to high-impedance faults verified by simulations and prototype experiments. Other scenario-specific designs include a neutral point flexible grounding method (built via ATP–EMTP with arc length control model) to suppress inrush current/voltage during intermittent arc SPG faults [22]; an ELFC-based faulted line identification method for Petersen coil-grounded systems, supported by custom measurement devices [23]; and a low-frequency signal superposition-based SPG fault location method for resonantly grounded (RG) networks, using SOP as the signal source and adaptive current criterion [24].
Hybrid approaches combining model-driven frameworks with machine learning or pattern recognition have emerged as a promising direction. Reference [25] proposed an SLG fault location method for transmission lines based on normalized harmonic amplitude features (from one-terminal three-phase voltage DFT), using k-NN regression without requiring two-terminal communication or current signals, and resistant to CT saturation. Reference [26] developed a fault diagnosis method based on GAF, improved CNN (with multi-scale module/attention mechanism), and transfer learning which achieved ~97.5% accuracy with noise. For distributed generator-integrated networks, Reference [27] proposed a fault section identification method based on synchronous waveform feature extraction, random matrix theory-based eigenvalues, and improved K-means clustering, verified by IEEE 34-node and multi-feeder systems. Reference [28] presented a multi-level classification architecture based on steady/transient feature quantization of waveform data, validated by field and artificial test data. Recent advances include the CWT–YOLOv11-based method [29], which converts current signals to feature maps via continuous wavelet transform (CWT) for faulted line selection, and the SPTEF location scheme [30] that simplifies feeder models and adopts golden section search and genetic algorithm (GA), verified via PSCAD/EMTDC and MATLAB. Complementarily, for neutral resonant/ineffectively grounded systems, a CEEMDAN-based faulty feeder selection method [31] adaptively extracts fault characteristics from transient zero-sequence current to address mode mixing and low sensitivity, with strong noise immunity and adaptability to diverse fault conditions. A linear optimization approach [32] further enables accurate fault section location by identifying transient zero-sequence current direction via line voltage, featuring fast solution and high fault tolerance.
When a single-phase ground fault occurs in the distribution network, the zero-sequence current shows strong nonlinearity and non-stationarity, making faulted line selection difficult. In addition, most current research on faulted line selection methods focuses on single-fault diagnosis models, which cannot fully capture the fault characteristics of the distribution network. Therefore, this chapter first analyzes the nonlinear distortion characteristics of the arc ground fault waveform through experiments; then, from the perspective of data input mode and autonomous mining of fault characteristics, it proposes a faulted line selection method for single-phase ground faults in distribution networks based on signal imaging and a convolutional neural network-residual network. This method fully applies graph transformation and CNN–ResNet neural network, which can fuse the one-dimensional and two-dimensional features of the time-frequency feature map of the zero-sequence current signal; further, through theoretical analysis, simulation modeling and experimental verification, the effectiveness of the method is fully verified, providing a new idea for faulted line selection in distribution networks.

2. Arc Ground Fault Test and Data Analysis

2.1. Test Platform

A 10 kV arc high-resistance grounding fault simulation test platform was established, as illustrated in Figure 1. The voltage of the platform is supplied by a 380 V power cabinet (S) and then stepped up to the 10 kV voltage level via a step-up transformer (T1). This system consists of four distribution lines, namely the cable/overhead hybrid line L1, cable line L2, overhead line L3, and cable/overhead hybrid line L4. All lines are equivalent to π-type equivalent circuits, with their corresponding lumped parameters presented in Table 1. A ground fault point is tapped from the overhead line L4, and a sphere gap is employed to simulate the arc high-resistance grounding fault. The fault grounding current is measured using a Rogowski coil. The equipment parameters of the platform are listed as follows: Transformer T1 is model SCZB10-800/10 with a rated capacity of 800 kVA; the Rogowski coil has a current-to-voltage ratio of 1 A: 0.01 V. The collected signals are recorded with an oscilloscope, whose sampling rate is set at 25.6 kHz.
Figure 1. 10 kV arc ground fault simulation test platform.
Table 1. Line parameters.

2.2. Analysis of Arc Ground Fault Waveform

The test measures the fault zero-sequence current when the transition resistance is 2 kΩ and there are different capacitive currents in the line; the waveform is shown in Figure 2. It can be seen that the amplitude of the fault zero-sequence current waveform under different capacitive currents varies greatly. However, there is always a section of nonlinear distortion near the current zero-crossing point caused by the “zero rest” characteristic of the fault arc. This is because after the arc is extinguished near the current zero-crossing point, the electrical strength of the arc channel is lower than the dielectric recovery strength in a short time, and the arc will reignite only when the voltage rises to a certain level, which is the “zero rest” phenomenon. This type of zero rest distortion has a clear physical meaning and is significantly different from common time-frequency domain features. The identification of arc ground faults can be realized by using this type of distortion.
Figure 2. Waveforms of fault currents obtained by experiments.

3. WOA-VMD Algorithm Optimized by Permutation Entropy

3.1. Permutation Entropy

Permutation entropy is a method used to detect sudden changes in the dynamics and randomness of time series, which can accurately evaluate the random noise level contained in the signal sequence. For a discrete time series {x(i), I = 1,2, …, N} of length N, phase space reconstruction is performed to obtain a reconstruction matrix composed of U reconstruction vectors, as shown below:
Y = x ( 1 ) x ( 1 + τ ) … x ( 1 + ( m − 1 ) τ ) x ( 2 ) x ( 2 + τ ) … x ( 2 + ( m − 1 ) τ ) ⋮ ⋮ ⋱ ⋮ x ( U ) x ( U + τ ) … x ( U + ( m − 1 ) τ )
where m ≥ 2 is the embedding dimension, τ is the time delay, and U = N + (m − 1)τ. The m elements in any reconstruction vector x(i) are rearranged in ascending order, that is:
{ x ( i + ( j 1 − 1 ) τ ) ≤ x ( i + ( j 2 − 1 ) τ ) ≤ … ≤ x ( i + ( j m − 1 ) τ ) }
It should be noted that if there are equal values among the m elements, they are sorted according to the size of the index value j. That is, when jp ≤ jq, the permutation order is:
x ( i + ( j p − 1 ) τ ) ≤ x ( i + ( j q − 1 ) τ )
Therefore, the symbol sequence of the reconstruction vector x(i) is obtained as follows:
S ( l ) = { j 1 , j 2 , … , j m }
According to the permutation and combination theorem, there are at most m! types of symbol sequences representing different mappings. Assuming that the occurrence probabilities of each symbol sequence in the reconstruction matrix Y are P1, P2, …, PK, where K ≤ m!. According to the Shannon entropy theorem, the permutation entropy of the time series {x(i), I = 1, 2, …, N} is calculated as follows:
H P = − ∑ j = 1 K P j ln P j
Obviously, HP satisfies 0 ≤ HP ≤ ln(m!). To facilitate the subsequent analysis of signal complexity, HP is normalized as follows:
0 ≤ P E = H P ln ( m ! ) ≤ 1
The complexity of the time series can be evaluated by using the value of permutation entropy. The fitness function takes the permutation entropy (PE) of the reconstructed signal (after eliminating noisy IMFs) as the core indicator, aiming to minimize the overall complexity of the denoised signal. Its explicit mathematical form is defined as follows:
F i t n e s s = 1 M ∑ i = 1 M P E I M F i
where M is the number of reserved IMFs, and PE(IMFi) is the permutation entropy of the i-th IMF calculated by Equations (5)–(6).
A smaller value indicates that the time series is regular, meaning the signal complexity is low; conversely, a larger value means the time series is more disordered, and the signal complexity increases accordingly. Therefore, by observing the change of permutation entropy, the subtle fluctuations of complex signals can be captured and highlighted.

3.2. Variational Mode Decomposition (VMD) Algorithm

Variational Mode Decomposition (VMD) is a novel adaptive signal decomposition and estimation method that combines Wiener filter theory, the Hilbert transform, and the concept of frequency mixing. It decomposes the signal into multiple sub-components in a non-recursive manner and can automatically determine the center frequency of each component based on the signal characteristics. Compared with Empirical Mode Decomposition (EMD), VMD decomposes the original signal into multiple Intrinsic Mode Functions (IMF) in the form of amplitude-modulated and frequency-modulated functions by establishing a constrained optimization model. This decomposition process benefits from the optimal setting of algorithm parameters, aiming to achieve signal decomposition without frequency aliasing and restore the original frequency components as much as possible. The relevant principles of VMD are as follows:
u k ( t ) = A k ( t ) × cos ( φ k ( t ) )
where, uk(t) is each order intrinsic mode component; Ak(t) is the instantaneous amplitude; φk(t) is the phase function, showing a non-monotonically decreasing trend.
To obtain the required demodulated signal, the Hilbert transform is used to process each component uk(t), and on this basis, the one-sided spectrum of uk(t) is further obtained. To better adjust the center frequency of each component, an exponential term is added to the demodulated signal of each component. Considering that the bandwidth limitation of each component can be described by Gaussian smoothness, the bandwidth distribution of each component is determined by calculating the L2 norm of the gradient of the demodulated signal. Based on the above analysis, the mathematical expression of the corresponding constrained variational problem can be expressed as:
min { u k } , { ω k } { ∑ k ∂ t [ ( δ ( t ) + j π t ) ∗ u k ( t ) ] e − j ω k t 2 2 } s . t . ∑ k u k ( t ) = x
where uk is the intrinsic mode function; ωk is the center frequency of each component; t is the first-order partial derivative with respect to time t; δ(t) is the impulse function; * represents convolution operation; x is the original signal; and δ ( t ) + j π t is the Hilbert transform kernel used to obtain the analytical signal.
To solve the optimization problem mentioned above, the augmented Lagrangian function method is used to convert the original constrained variational problem into an unconstrained variational problem as shown in the formula (10). The quadratic penalty factor α and the Lagrange multiplier λ(t), which play important roles, are introduced. By adding the quadratic penalty factor, the accuracy of reconstructing complex signals containing noise is significantly improved, ensuring the quality of the reconstructed signal. At the same time, the Lagrange multiplier strictly enforces the constraint conditions in the optimization process, ensuring the reliability and accuracy of the solution results and thereby effectively optimizing the original problem.
L ( { u k } , { ω k } , λ ) = α ∑ k ∂ t [ ( δ ( t ) + j π t ) ∗ u k ( t ) ] e − j ω k t 2 2 + x − ∑ k u k ( t ) 2 2 + [ λ ( t ) , x − ∑ k u k ( t ) ]
To obtain the optimal solution of formula (9), the alternating direction method of multipliers is used to solve it, and uk and ωk are updated step by step. According to Parseval’s theorem and the principle of Fourier transform, since the updated ukn+1 and ωkn+1 are the frequency domain representations of each mode after the iteration ends, it is necessary to convert them back to the time domain signal through inverse Fourier transform to obtain the optimal solution. The steps to solve the variational equation are as follows:
(1)
Initialize {uk}, {ωk}, λ, and set the number of iterations to 0;
(2)
Increase the number of iterations by 1, and iteratively update uk, ωk and λ according to the following formulas respectively.
u ^ k n + 1 ( ω ) = q ^ ( ω ) − ∑ v ≠ k u ^ v ( ω ) + λ ^ ( ω ) 2 1 + 2 α ( ω − ω k ) 2
ω k n + 1 = ∫ 0 ∞ ω u ^ k ( ω ) 2 d ω ∫ 0 ∞ u ^ k ( ω ) 2 d ω
λ ^ n + 1 ( ω ) = λ ^ n ( ω ) + τ ( q ^ ( ω ) − ∑ k = 1 K u ^ n + 1 ( ω ) )
where v is a positive integer, ̂ represents the Fourier transform, and τ is the noise tolerance coefficient.
(3)
Repeat step (2) until the components satisfy the formula, then the cycle ends, and K modal components are obtained.
∑ k = 1 K u k n + 1 − u k n 2 2 u k n 2 2 < ε
where ε is the discriminant accuracy.

3.3. Whale Optimization Algorithm (WOA)

Whale Optimization Algorithm (WOA) is a meta-heuristic optimization algorithm that simulates the hunting behavior of humpback whales. The main difference between the current work and other group optimization algorithms is that it uses random or optimal search agents to simulate hunting behavior and uses spirals to simulate the bubble net attack mechanism of humpback whales. This algorithm has the advantages of a simple mechanism, few parameters, and strong optimization ability, and has been widely used in economic dispatch, optimal control, photovoltaic systems, image segmentation, and other applications. The specific flow is shown in Figure 3.
Figure 3. Flow chart of Whale Optimization Algorithm.
The steps of the Whale Optimization Algorithm are as follows:
(1)
Encircling prey
The population initialization method of WOA is the same as that of most intelligent optimization algorithms. The initial solution set is composed of N individuals generated randomly. In the d-dimensional space, the position of the i-th individual is expressed as: X i = ( x t 1 , x t 2 , … , x t d ) , I = 1,2, …, N.
Humpback whales hunt by encircling their prey as a group. In the algorithm, when searching for the target prey in the unknown search space, the group changes its position through the information transmission of formula (15) to approach the optimal solution in the current search space.
X t + 1 = X t b e s t − A ⋅ D
D = C ⋅ X t b e s t − X t
A = 2 a ⋅ r a − a
C = 2 r b
a = 2 − 2 t t max
where Xtbest is the position of the whale individual that obtains the global optimal solution in the population when searching for the t-th generation, Xt is the position of the individual at the t-th iteration, D is the encircling step size, which measures the distance between the individual and the current optimal individual, A and C are coefficient vectors that adjust the search behavior, where ra and rb are random numbers uniformly distributed on [0, 1], and tMax is the maximum number of iterations.
The encircling mode of the algorithm is: in the process of individual search in the population, the contraction factor A adjusted by formula (18), where a changes linearly in a ∈ [0, 2] and A ∈ [−2, 2], obtains information in each iteration, and moves randomly to any position between the current position and the optimal individual. When the adjustment factor |A| ≤ 1, the algorithm switches from the encircling mode to the bubble net attack mode for a more refined search.
(2)
Bubble net feeding by spiral update
After humpback whales find the prey information, they move and shrink the encirclement in a spiral swimming mode according to formula (19), and detect the specific position of the prey by emitting bubbles, thereby approaching the target point.
X t + 1 = X t b e s t + D ′ ⋅ e b l ⋅ cos ( 2 π l )
D ′ = X t b e s t − X t
where formula (20) represents the distance between the individual and the target prey, b is a constant used to control the shape of the logarithmic spiral, and l ∈ [ 0 , 1 ] is a random vector.
Humpback whales encircle their prey with a circle as the trajectory and swim in a spiral upward mode, comprising two stages: shrinking the encirclement and executing a bubble net attack. When |A| < 1, since the whales swim along a spiral trajectory around the prey in the shrinking encirclement, the whales have a 50% chance to choose to encircle the prey and a 50% chance to choose the bubble net attack. The attack process is summarized as the following formula:
X t + 1 = X t b e s t − A ⋅ D ′ D ′ ⋅ e b l cos ( 2 π l ) + X t b e s t i f   p < 0.5 i f   p ≥ 0.5
where p ∈ [ 0 , 1 ] .
(3)
Search for prey randomly
When the population searches for prey, to improve the predation probability of the group, a random search mode is often adopted instead of taking the current optimal position as the final target. By expanding the search range, random individuals in the whale group obtain information and adjust their positions, while searching for prey within the group, to maintain as much diversity as possible. The model of this stage is:
X t + 1 = X t r a n d − A ⋅ D ″
D ″ = C ⋅ X t r a n d − X t
where Xtrand is the position of the random individual, D’’ is the random search vector, and A·D’’ is the random search step size.
The key parameters are the coefficient vectors A and C. When |A| > 1, the algorithm performs global search, and the population expands the search range to find the optimal solution; when |A| ≤ 1, the algorithm performs local exploration, and the local search ability is enhanced at this time. The parameter A regulates the algorithm under the adjustment of the convergence factor a. With the increase of a, the global search ability is improved, and with the decrease of a, the algorithm’s refined search ability is stronger, and the local search ability is enhanced.
(4)
Algorithm flow
The flow chart of the WOA–VDM algorithm optimized by permutation entropy proposed in this section is as follows:
(1)
Use WOA to find the optimal parameter combination after optimizing the VMD parameters, perform VMD decomposition on the collected zero-sequence current signal, use permutation entropy as the fitness function, and output K intrinsic mode components and penalty coefficient a when the termination condition is met.
(2)
Calculate the permutation entropy of each IMF component and eliminate the IMF components with permutation entropy greater than or equal to 0.6. The PE threshold of 0.6 is determined through a combination of theoretical analysis and empirical verification, which is validated as the optimal value to ensure both denoising effectiveness and fault feature integrity.
(3)
Reconstruct the remaining IMF components to obtain the denoised zero-sequence current.

4. Two-Dimensional Image Conversion Method Based on Gram Angular Difference Field (GADF)

To solve the problem of insufficient feature extraction in traditional methods when directly processing one-dimensional signals, a Gram Angular Difference Field (GADF) is used to convert the original one-dimensional time-domain signal into a two-dimensional feature image. This conversion not only retains the temporal characteristics of the signal but also enhances the explicit expression ability of fault features, providing a more effective feature representation for the neural network model, thereby improving fault diagnosis performance. The calculation process of the Gram Angular Difference Field is as follows:
(1)
For the collected one-dimensional signal X = {x1, x2, x3, …, xn}, normalize it to the range [−1, 1] according to the time sequence, and the calculation formula is as follows:
x ^ l = ( x i − max ( X ) ) + ( x i − min ( X ) ) max ( X ) − min ( X )
(2)
Convert the normalized value into a polar coordinate system with angle φ and time radius encoding r:
ϕ i = a r c cos ( x ^ l ) − 1 ≤ x i ≤ 1 r = t i N t i ∈ N
where ti is time, and N is a constant factor in the conversion process.
(3)
Gram Angular Difference Field (GADF) is a video feature extraction method based on polar coordinate conversion. Its core principle is to utilize the trigonometric function difference algorithm to analyze the correlation characteristics within different time intervals from the angle dimension of the time series, and then construct a two-dimensional feature-encoded image with high recognition.
G A S F = [ cos ( ϕ i + ϕ j ) ] = cos ϕ i · cos ϕ j − sin ϕ i · sin ϕ j = X ˜ ′ · X ˜ − I − X ˜ 2 ′ · I − X ˜ 2
After the above transformation, the one-dimensional zero-sequence current signal can be converted into a two-dimensional image symmetric along the main diagonal. The transformation process is shown in Figure 4.
Figure 4. Transformation process of Gram Angular Difference Field.

5. CNN–ResNet-Based Faulted Line Selection Method for Single-Phase Ground Faults in Distribution Networks

When a single-phase ground fault occurs in the distribution network, the zero-sequence current signal is affected by factors such as transition resistance, neutral point grounding mode, and noise, making it difficult to establish a fault diagnosis mathematical model effectively. Therefore, this paper realizes fault diagnosis through deep learning methods, avoiding the mathematical modeling process. The one-dimensional convolutional network (CNN) is used to extract the features of the steady-state zero-sequence current signal, and the ResNet34 network is used to extract the features of the time-frequency feature map, as shown in Table 2 and Figure 5.
Table 2. Network architecture of proposed method.
Figure 5. CNN–ResNet-based faulted line selection module.
The deep network adopts a hybrid structure combining CNN and ResNet34, with detailed parameter configurations as follows.
For the CNN module, the one-dimensional processing module uses a one-dimensional convolutional neural network to mine the features of the time-domain signal. This module is composed of a one-dimensional convolutional layer, batch standard deviation, activation function layer, flattening layer, and fully connected layer. The convolution kernel size is 1 × 5, the step size is 1, and padding is configured as 1 to avoid feature loss during convolution; the pooling operation employs max pooling to retain key feature information and reduce model complexity.
For the ResNet34 module, the input image size is set to 256 × 256 to ensure sufficient feature resolution while balancing computational efficiency. Pre-trained weights are adopted to leverage transfer learning advantages and improve feature extraction capability; specifically, the front convolution layers are frozen to maintain their ability to extract basic universal features, while only the final fully connected layer is retained and fine-tuned to adapt to the faulted line selection task. This configuration not only simplifies the training process but also enhances the model’s generalization performance for the target task. The first convolution layer contains 32 convolution kernels, and the second convolution layer contains 64 convolution kernels. The Dropout layer is used to improve the generalization ability of the network. After the flattening layer, it is connected to the fully connected layer, and 128 feature vectors are output through the fully connected layer. Considering that an overly deep network is prone to overfitting, the ResNet34 network is used to extract features from the time-frequency feature map, which is ResNet34 is selected for the balance between feature extraction capability, model complexity, and deployment cost. And these extracted features are combined with the features extracted by the one-dimensional convolutional neural network to form the final features. The fusion of 1D-CNN and 2D-ResNet34 features adopts channel-wise concatenation (a straightforward yet effective operation) to enhance network expression.
The proposed CNN–ResNet-based faulted line selection method forms an end-to-end diagnosis pipeline for single-phase ground faults in distribution networks, which takes the zero-sequence current signal as the core input and realizes the accurate prediction of faulted lines through sequential signal preprocessing, intelligent denoising, time-frequency imaging, dual-branch feature extraction/fusion and classifier decision-making. All technical modules (WOA–VMD optimized by permutation entropy, GADF, CNN–ResNet34) are organically combined and applied in a targeted manner for the nonlinear and non-stationary characteristics of zero-sequence current with distributed generation access. The detailed execution steps of the entire pipeline are as follows:

5.1. Step 1: Collection and Initial Normalization of Raw Zero-Sequence Current Signals

When a single-phase ground fault occurs in the distribution network, synchronous sampling is performed on the transient and steady-state zero-sequence current signals at the head end of each feeder (L1–L4) by the measurement unit, with a fixed sampling rate of 25.6 kHz (2048 sampling points per sample, 1024-point sliding window for sample generation) to ensure the reliability of phase information comparison of zero-sequence current between different feeders. The collected one-dimensional raw zero-sequence current time series X = {x1, x2, x3, …, xn} is normalized to the range of [−1,1] according to the time sequence (Formula 24 in this paper) to eliminate the influence of signal dimension and lay a foundation for subsequent polar coordinate conversion and signal decomposition.

5.2. Step 2: Denoising and Reconstruction of Zero-Sequence Current via Permutation Entropy-Optimized WOA-VMD

Aiming at the noise interference in the fault zero-sequence current and the difficulty of parameter setting in traditional VMD, the WOA–VMD algorithm optimized by permutation entropy is used for targeted signal denoising, and the core fault feature (zero-rest nonlinear distortion) is retained while suppressing noise:
(1)
WOA-based VMD parameter optimization: Taking the permutation entropy (PE) of the reconstructed signal as the core fitness function (Equation (7)), the Whale Optimization Algorithm (WOA) is used to iteratively search the optimal parameter combination of VMD (the number of Intrinsic Mode Functions K, penalty coefficient α), and the iteration is terminated when the fitness function converges to the minimum value.
(2)
VMD signal decomposition: The optimized VMD algorithm is used to decompose the normalized zero-sequence current signal into K IMF components in a non-recursive manner, avoiding frequency aliasing in the decomposition process.
(3)
IMF component screening: The permutation entropy of each IMF component is calculated (Equations (5) and (6)); combined with theoretical analysis and empirical verification, the IMF components with PE ≥ 0.6 (noise-dominated components) are eliminated to remove invalid noise interference.
(4)
Valid signal reconstruction: The remaining IMF components (fault feature-dominated components) are reconstructed to obtain the denoised pure zero-sequence current signal, which effectively preserves the “zero-rest” nonlinear distortion characteristic of the arc ground fault near the current zero-crossing point.

5.3. Step 3: Conversion of 1D Denoised Signal to 2D Time-Frequency Feature Map via GADF

To solve the problem of insufficient feature extraction of traditional one-dimensional signal processing methods, the Gram Angular Difference Field (GADF) is used to convert the one-dimensional time-series signal into a two-dimensional feature map, and the hidden fault features are encoded into the spatial domain of the image while retaining the temporal characteristics of the original signal:
(1)
Polar coordinate mapping: The normalized denoised zero-sequence current value is converted into a polar coordinate system composed of angle φ and time radius encoding r (Equation (25)), and the time sequence information is mapped to the polar coordinate space.
(2)
2D feature map construction: Based on the trigonometric function difference algorithm, the Gram angular difference of the polar coordinate angle dimension is calculated (Equation (26)) to analyze the correlation characteristics of the time series in different time intervals, and a 256 × 256 two-dimensional feature map, symmetric along the main diagonal, is constructed. The map encodes the local time-varying gradient, phase progression and transient variation of the zero-sequence current into the texture, spatial distribution and color gradient features of the image, which is more suitable for the feature extraction of convolutional neural networks.

5.4. Step 4: Dual-Branch Feature Extraction and Fusion via CNN-ResNet34 Hybrid Model

A hybrid deep learning model with 1D-CNN branch (for time-domain feature extraction) and ResNet34 branch (for 2D time-frequency feature extraction) is constructed to fully mine the multi-dimensional fault features of the zero-sequence current signal and the channel-wise concatenation is used for feature fusion to realize complementary expression of fault features:
(1)
1D-CNN branch for time-domain feature extraction: The denoised one-dimensional steady-state zero-sequence current signal is input into the 1D-CNN module (2 layers of 1D convolution with 32/64 convolution kernels of size 5 × 1, step size 1 + Batch Normalization + ReLU activation). After convolution operation, two layers of fully connected layers are used to map the features to 512-dimensional and 128-dimensional feature vectors in turn, and the one-dimensional time-domain steady-state features of the fault signal are fully extracted.
(2)
ResNet34 branch for 2D time-frequency feature extraction: The GADF-based 2D time-frequency feature map is input into the ResNet34 module (pre-trained weights are adopted for transfer learning, the front convolution layer is frozen, and only the final fully connected layer is fine-tuned). The module completes feature extraction through 2D convolution (64 convolution kernels of size 5 × 5, step size 1) + max-pooling (2 × 2, step size 2) + residual block multi-layer convolution, and outputs 128-dimensional 2D time-frequency image feature vectors through the fully connected layer, which mines the spatial domain fault features encoded by GADF.
(3)
Feature fusion: The 128-dimensional time-domain feature vector (from 1D-CNN) and 128-dimensional time-frequency feature vector (from ResNet34) are fused by channel-wise concatenation to form a comprehensive feature set containing both one-dimensional time-domain and two-dimensional time-frequency fault information, which significantly improves the discriminability of fault features compared with a single branch.

5.5. Step 5: Faulted Line Prediction and Decision-Making via State Classifier

The fused comprehensive feature set is input into the fault state classifier (a fully connected layer architecture with output dimension of 128× number of faulted line categories), and the Batch Normalization and ReLU activation functions are used to optimize the feature mapping process of the classifier. The classifier outputs the fault probability distribution of each feeder (L1–L4) in the distribution network, and takes the feeder with the maximum fault probability as the final decision result to realize the accurate prediction and identification of the faulted line.

6. Result Analysis

6.1. Dataset and Parameter Settings

Taking the distribution network shown in Figure 1 as the research object, the neutral-point-ungrounded system model built in MATLAB/Simulink is shown in Figure 6. The fault points are set at different positions of the distribution network to collect sample data. The fault type is an intermittent arc fault, and the detailed distribution of sample data is shown in Table 3. The data sampling frequency is 25.6 kHz, each sample contains 2048 sampling points, and a sliding window of 1024 points is adopted for sample generation. The samples are split into training and validation setting at an 8:2 ratio.
Figure 6. MATLAB/Simulink neutral point ungrounded system model.
Table 3. Model parameters.
We conducted the training process using the PyCharm 2024.1 integrated development environment on a workstation configured with an 11th Gen Intel(R) Core(TM) i7-11800H @ 2.30 GHz processor, 40.0 GB RAM, and an NVIDIA GeForce RTX 3060 GPU (running on the Windows 10 64-bit operating system), while the simulation platform was Matlab 2022b/Simulink. To achieve a better training effect for the network, it is necessary to carefully adjust the learning rate, batch size, and other hyperparameters, as the selection of these parameters directly affects the training speed, convergence, and final performance of the model. The learning rate determines the step size of the model when updating weights each time and is a very critical hyperparameter in deep learning. We used the grid search method to optimize the optimal parameters of the network model and determined the final hyperparameter configuration. We set the learning rate to 0.0001, the Batch Size to 8, and the batch processing size to 20. Additionally, the optimizer type is SGD (Stochastic Gradient Descent), the momentum is 0.001, and the weight decay is 0.1.

6.2. Ablation Experiment

To verify the contribution of various improvement measures to the faulted line selection method, two sets of ablation experiments were designed to observe the enhancement of fault diagnosis brought by each improvement.

6.2.1. Comparison of Ablation Experiments on Front-End Preprocessing

In existing fault diagnosis algorithms, input representations often include time-domain vector features, frequency domain and demodulation, as well as graphical time series. To verify the impact of different input representations on fault diagnosis performance, the modulation transfer function (MTF) method [33] and the direct spectrogram (DS) method [34] were selected for comparative analysis. First, the images converted by different methods were compared; the results are shown in Figure 7.
Figure 7. Images converted by different methods.
To verify the effectiveness of the proposed GADF method in input representation schemes, multiple ablation experiments were conducted on the three input representation schemes using a dataset with transition resistance ranging from 0 to 2000 Ω, under the premise of ensuring consistent subsequent feature extraction. The results of the ablation experiments for input representation schemes are shown in Figure 8.
Figure 8. Results of ablation experiments on front-end preprocessing.
Figure 8 indicates that the GADF method achieves significantly higher accuracy in fault diagnosis than the MTF method and the DS method. The reasons are as follows: The GADF method performs differencing operations on polar coordinate phase angles, encoding the local time-varying gradients, phase progression, and transient variations of the time series into two-dimensional textures. This enables the convolutional neural network to effectively capture temporal dependencies in the spatial domain via its convolutional receptive fields and enhance inter-class separability. Conversely, the MTF method cannot accurately quantify the degree and characteristics of nonlinear distortion. The DS method employs a linear mapping for signal amplitude representation, but the amplitude of nonlinear distortion components in fault zero-sequence currents is typically much lower than that of the fundamental wave component. As a result, the distortion features are easily masked by the strong energy spectral peaks of the fundamental wave, making it difficult to effectively highlight the time-frequency distribution patterns of the distortion. Therefore, in unsteady scenarios of arc high-resistance grounding faults, the GADF-based input representation demonstrates higher diagnostic accuracy and superior robustness.

6.2.2. Comparative Analysis of Model Ablation Experiments

To verify the necessity of the “CNN–ResNet” architecture, this section constructs three sets of comparative models by replacing only the feature extraction modules, while keeping the data partitioning methods completely consistent: the first set is CNN–ResNet and refers to the fusion of the left and right branches in Figure 5. The second set is 2D-ResNet and refers to the left branch of Figure 5. The third set is 1D-CNN and refers to the right branch of Figure 5. The fault recognition accuracy under different methods is compared and the results are shown in Figure 9, Figure 10 and Figure 11.
Figure 9. Accuracy curves.
Figure 10. Loss curves.
Figure 11. Confusion matrix.
The training results are shown in Figure 9 and Figure 10, and the corresponding values of F1-score are shown in Table 4. The model shows good performance during the training process, with a rapid increase in accuracy and a rapid decrease in loss value at the beginning. After 18 training sessions, the accuracy rises to more than 97% and remains stable, while the loss value remains at a low level, indicating that the network has converged. From the training results of the training set and test set, it can be seen that the trends of the two are roughly the same, indicating that the network operates effectively and does not exhibit underfitting or overfitting phenomena. We conducted comparative experiments on the training processes of three networks: one-dimensional convolutional neural network (1D-CNN), two-dimensional convolutional neural network (2D-ResNet), and CNN–ResNet. Among these methods, 1D-CNN only takes zero-sequence current signals as input, 2D-ResNet only takes feature maps as input, and CNN–ResNet simultaneously takes zero-sequence current signals and feature maps as input. It can be observed that the training accuracy of 1D-CNN and 2D-ResNet is lower than that of CNN–ResNet, indicating that the proposed method has better training performance than single-input networks and can ensure higher fault diagnosis accuracy.
Table 4. Values of F1-score.
After the network is trained, 4666 test samples are tested. The obtained confusion matrix is shown in Figure 11. The elements on the main diagonal represent the number of correctly classified samples. As shown in Figure 11, the proposed method exhibits higher accuracy in faulted line selection than the other two methods.

7. Experimental Analysis

Due to differences between the simulation experiment data and the actual situation, the test platform shown in Figure 12 is used to verify the accuracy of the proposed method; experiments on this platform can be more closely aligned with real fault environments. It is worth noting that low-current grounded systems are allowed to operate with faults for 2~3 h when single-phase ground faults occur, and the proposed method fully meets the practical engineering requirements for real-time performance: converting zero-sequence current signals to images via permutation entropy-optimized VMD and color coding takes 0.4 s, and identifying fault lines through deep learning takes 0.2 s, resulting in an overall faulted line selection time of less than 0.6 s. Additionally, the computational complexity of the proposed method is systematically analyzed in Table 5, which covers both time and space complexity. The key evaluation indexes include per-iteration run time (1.2 s), FLOPs (1.18 G), trainable parameters (25 M), and storage occupancy (98 MB), with their specific values clearly presented to demonstrate the method’s feasibility in practical deployment.
Figure 12. Test platform.
Table 5. Method complexity analysis.
To further validate the method’s reliability in practical scenarios, 15 arc ground fault tests were conducted by randomly selecting lines and phases among 4 feeders to verify the accuracy of line and phase selection. And a sphere gap is adopted to simulate the arc high-resistance grounding fault, and the simulated arc is a dynamic, intermittent transient arc rather than a stable arc, which matches the actual arc behavior required for transient analysis. Test samples were directly collected from the test platform, and the faulted line selection model did not require retraining. The results are shown in Table 6, from which it can be seen that the proposed method still accurately selects the fault line on the test platform without misjudgment.
Table 6. Test records.

8. Conclusions

Aiming at the problem of faulted line selection for single-phase ground faults in distribution networks, this paper proposes and verifies a fusion faulted line selection method based on CNN–ResNet. The main conclusions are as follows:
First, through dedicated arc ground fault tests, this work clarifies the “zero-rest” nonlinear distortion characteristic of fault zero-sequence current near the zero-crossing point. This unique physical phenomenon, derived from arc discharge mechanisms, provides a critical theoretical and experimental basis for targeted fault identification.
Second, three methodological innovations are proposed to enhance fault feature extraction and recognition accuracy. An improved WOA–VMD (Whale Optimization Algorithm–Variational Mode Decomposition) algorithm optimized by permutation entropy is introduced for zero-sequence current denoising. Compared with traditional signal processing methods (e.g., VMD, EEMD), this algorithm exhibits superior adaptability and stability in handling non-stationary fault signals, effectively preserving key distortion features while suppressing interference. To overcome the limitations of single-dimensional time-frequency feature representation, GADF (Gram Angular Difference Field) is employed for fault signal visualization. By converting one-dimensional (1D) time-series signals into two-dimensional (2D) time-frequency images, the color gradients, spatial distributions, and topological structures of the images enrich hidden feature information that is inaccessible in 1D signals. A hybrid dual-branch deep learning model fusing CNN and ResNet34 is constructed. This model synergistically extracts discriminative features from both raw 1D time-series data and 2D GADF images, achieving more comprehensive feature mining compared to 1D-CNN and 2D-ResNet networks and significantly improving the robustness of faulted line selection.
Third, simulation and experimental validations confirm the proposed method’s performance under complex operating conditions. It maintains high selection accuracy for single-phase ground faults with transition resistances ranging from 0 to 2000 Ω and different fault phase angles. This provides a reliable technical solution for rapid fault location, operational safety, and maintenance decision-making in modern distribution networks.
Despite these contributions, this study has certain limitations: the proposed method is primarily driven by the “zero-rest” characteristic of arc faults, and its performance may be constrained for non-arcing, low-impedance, single-phase ground faults where such nonlinear distortions are absent. Future work will focus on expanding the dataset to include more non-arcing fault cases, optimizing the model’s feature extraction and classification modules, and enhancing its ability to identify multiple fault types. This will further broaden the method’s applicability and promote its engineering application in distribution network fault diagnosis.

Author Contributions

Conceptualization, Q.S. and Z.Y.; methodology, Q.S. and Z.Y.; software, Q.S.; validation, Q.S., Z.Y. and S.Y.; formal analysis, Q.S.; investigation, Q.S.; resources, Q.S.; data curation, Q.S.; writing—original draft preparation, Q.S.; writing—review and editing, Z.Y. and S.Y.; visualization, Q.S.; supervision, Q.S.; project administration, Q.S.; funding acquisition, Q.S. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by the Key Scientific and Technical Funds of Sichuan Electric Power Corporation, The Rapid Isolation and Transfer Technology for Single-Phase Ground Faults in Cable Lines, grant number 52199723002N.

Data Availability Statement

The original contributions presented in this study are included in the article. Further inquiries can be directed to the corresponding author.

Conflicts of Interest

Authors Qianqiu Shao was employed by the company State Grid Sichuan Electric Power Company Electric Power Science Research Institute. Authors Zhen Yu and Shenfa Yin were employed by the Anhui Hekai Electric Technology Co., Ltd. The authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.

References

  1. Zhou, T.; Yuan, T.; Wei, S.; He, H.; Yang, Q. Temperature and composition of AC arc plasma of medium voltage distribution networks in the air. J. Phys. D Appl. Phys. 2022, 55, 245201. [Google Scholar] [CrossRef] [Scilit]
  2. Zhou, T.; Yang, Q.; Yuan, T.; He, H.; Liu, H. A Novel Mathematical–Physical Arc Model and its Application to the Simulation of High-Impedance Arc Faults in Distribution Networks. IEEE Trans. Power Deliv. 2024, 39, 1794–1806. [Google Scholar] [CrossRef] [Scilit]
  3. Toader, D.; Vintan, M. Mathematical Models of the Phase Voltages of High-, Medium- and Low-Voltage Busbars in a Substation during a Phase-to-Ground Fault on High-Voltage Busbars. Mathematics 2023, 11, 3032. [Google Scholar] [CrossRef] [Scilit]
  4. Subramanian, N.; Stonier, A.A. A Comprehensive Review on Selective Harmonic Elimination Techniques and Its Permissible Standards in Electrical Systems. IEEE Access 2024, 12, 141966–141998. [Google Scholar] [CrossRef] [Scilit]
  5. Teng, Y.; Zhang, Z.; Li, X. Improved approach to high-frequency current injection-based protection for grounding electrode line in high-voltage direct current system. IEEE Trans. Ind. Appl. 2020, 56, 2409–2417. [Google Scholar] [CrossRef] [Scilit]
  6. Daniel, K.; Kütt, L.; Iqbal, M.N.; Shabbir, N.; Raja, H.A.; Sardar, M.U. A Review of Harmonic Detection, Suppression, Aggregation, and Estimation Techniques. Appl. Sci. 2024, 14, 10966. [Google Scholar] [CrossRef] [Scilit]
  7. Zhang, H.; Li, Q.; Sun, Z.; Liu, Y. Combining Data-Driven and Model-Driven Methods for Robust Facial Landmark Detection. IEEE Trans. Inf. Forensics Secur. 2018, 13, 2409–2422. [Google Scholar] [CrossRef] [Scilit]
  8. Dong, X.; Shi, S. Identifying Single-Phase-to-Ground Fault Feeder in Neutral Noneffectively Grounded Distribution System Using Wavelet Transform. IEEE Trans. Power Deliv. 2008, 23, 1829–1837. [Google Scholar] [CrossRef] [Scilit]
  9. Cui, T.; Dong, X.; Bo, Z.; Juszczyk, A. Hilbert-Transform-Based Transient/Intermittent Earth Fault Detection in Noneffectively Grounded Distribution Systems. IEEE Trans. Power Deliv. 2010, 26, 143–151. [Google Scholar] [CrossRef] [Scilit]
  10. Yuan, W.; Li, Y.; Xu, L.; Li, T.; Chen, X. A Fast Faulty Phase Selection Method Considering Fault Tolerance for Single Phase to Ground Fault in Distribution Networks. IEEE Trans. Instrum. Meas. 2023, 72, 1–12. [Google Scholar] [CrossRef] [Scilit]
  11. Jianwen, Z.; Hui, H.; Yu, G.; Yongping, H.; Shuping, G.; Jianan, L. Single-phase ground fault location method for distribution network based on traveling wave time-frequency characteristics. Electr. Power Syst. Res. 2020, 186, 106401. [Google Scholar] [CrossRef] [Scilit]
  12. Kachesov, V.; Lebedev, A.; Kitova, E. Monitoring in 6–35 kV power networks, location of single-phase ground fault and detection of fault feeder. Int. J. Electr. Power Energy Syst. 2023, 152, 109271. [Google Scholar] [CrossRef] [Scilit]
  13. Liu, P.; Huang, C. Detecting Single-Phase-to-Ground Fault Event and Identifying Faulty Feeder in Neutral Ineffectively Grounded Distribution System. IEEE Trans. Power Deliv. 2017, 33, 2265–2273. [Google Scholar] [CrossRef] [Scilit]
  14. Niu, L.; Wu, G.; Xu, Z. Single-Phase Fault Line Selection in Distribution Network Based on Signal Injection Method. IEEE Access 2021, 9, 21567–21578. [Google Scholar] [CrossRef] [Scilit]
  15. Wang, X.; Zhang, H.; Shi, F.; Wu, Q.; Terzija, V.; Xie, W.; Fang, C. Location of Single Phase to Ground Faults in Distribution Networks Based on Synchronous Transients Energy Analysis. IEEE Trans. Smart Grid 2019, 11, 774–785. [Google Scholar] [CrossRef] [Scilit]
  16. Tang, Y.; Chang, Y.; Tang, J.; Xu, B.; Ye, M.; Yang, H. A Novel Faulty Phase Selection Method for Single-Phase-to-Ground Fault in Distribution System Based on Transient Current Similarity Measurement. Energies 2021, 14, 4695. [Google Scholar] [CrossRef] [Scilit]
  17. Wang, X.; Gao, J.; Wei, X.; Zeng, Z.; Wei, Y.; Kheshti, M. Single Line to Ground Fault Detection in a Non-Effectively Grounded Distribution Network. IEEE Trans. Power Deliv. 2018, 33, 3173–3186. [Google Scholar] [CrossRef] [Scilit]
  18. LI, Z.; Li, W.; Peng, W.; Lei, L.; Liang, L. Single—Phase–to–ground fault line selection method of distribution network based on IHHT–RF. J. Electr. Power Sci. Technol. 2024, 39, 171–182. [Google Scholar]
  19. Su, S.; Xie, Q.; Ma, P.; Li, Y.; Chen, F.; Zhang, J.; Li, B.; Wang, C. A Single-Phase Ground Fault Line Selection Method in Active Distribution Networks Based on Transformer Grounding Mode Modification. Energies 2024, 17, 4743. [Google Scholar] [CrossRef] [Scilit]
  20. Achitaev, A.A.; Suslov, K.V.; Volkova, I.O.; Kozhemyakin, V.E.; Dvoryansky, Y.V. Development of an Algorithm for Identifying Single-Phase Ground Fault Conditions in Cable and Overhead Lines in the Networks with Isolated Neutral. Energy Rep. 2023, 9, 1079–1086. [Google Scholar] [CrossRef] [Scilit]
  21. Guo, M.F.; Cai, W.Q.; Zheng, Z.Y.; Wang, H. Fault phase selection method based on single-phase flexible arc suppression device for asymmetric distribution networks. IEEE Trans. Power Deliv. 2022, 37, 4548–4558. [Google Scholar] [CrossRef] [Scilit]
  22. Zeng, H.; Yang, P.; Cheng, H.; Xin, J.; Lin, W.; Hu, W.; Wan, M.; Li, Y.; Wu, H. Research on Single-Phase to Ground Fault Simulation Base on a New Type Neutral Point Flexible Grounding Mode. IEEE Access 2019, 7, 82563–82570. [Google Scholar] [CrossRef] [Scilit]
  23. Yang, S.; Jiao, Y.; Chen, Q.; Li, H.; Zhou, L.; Zhu, H. A single-phase to ground fault identification method based on extremely low frequency current detection in distribution grids. IEEE Trans. Power Deliv. 2022, 37, 5214–5223. [Google Scholar] [CrossRef]
  24. Li, Z.; Ye, Y.; Ma, X.; Lin, X.; Xu, F.; Wang, C.; Ni, X.; Ding, C. Single-phase-to-ground fault section location in flexible resonant grounding distribution networks using soft open points. Int. J. Electr. Power Energy Syst. 2020, 122, 106198. [Google Scholar] [CrossRef] [Scilit]
  25. Farshad, M.; Sadeh, J. Accurate Single-Phase Fault-Location Method for Transmission Lines Based on K-Nearest Neighbor Algorithm Using One-End Voltage. IEEE Trans. Power Deliv. 2012, 27, 2360–2367. [Google Scholar] [CrossRef] [Scilit]
  26. Zhang, Q.; Qi, Z.; Cui, P.; Xie, M.; Din, J. Detection of single-phase-to-ground faults in distribution networks based on Gramian Angular Field and Improved Convolutional Neural Networks. Electr. Power Syst. Res. 2023, 221, 109501. [Google Scholar] [CrossRef] [Scilit]
  27. Shi, F.; Zhang, L.; Zhang, H.; Xu, K.; Vladimir, T. Diagnosis of the single phase-to-ground fault in distribution network based on feature extraction and transformation from the waveforms. IET Gener. Transm. Distrib. 2020, 14, 6079–6086. [Google Scholar] [CrossRef] [Scilit]
  28. Liang, Y.; Jin, X.; Xue, Y.; Yang, F. Type recognition of single-phase-to-ground faults in nonsolidly earthed distribution networks-architecture and method. Int. Trans. Electr. Energy Syst. 2019, 29, e12071. [Google Scholar] [CrossRef] [Scilit]
  29. Wang, Y.; Zhang, L.; Ning, K.; Guo, W.; Xing, N. Single-phase grounding fault line selection method based on CWT-YOLOv11. Electr. Power Syst. Res. 2025, 248, 111879. [Google Scholar] [CrossRef] [Scilit]
  30. Rui, L.; Nan, P.; Zhi, Y.; Zare, F. A novel single-phase-to-earth fault location method for distribution network based on zero-sequence components distribution characteristics. Int. J. Electr. Power Energy Syst. 2018, 102, 11–22. [Google Scholar] [CrossRef] [Scilit]
  31. Jin, T.; Zhuo, F.; Mohamed, M.A. A Novel Approach Based on CEEMDAN to Select the Faulty Feeder in Neutral Resonant Grounded Distribution Systems. IEEE Trans. Instrum. Meas. 2019, 69, 4712–4721. [Google Scholar] [CrossRef] [Scilit]
  32. Wang, Q.; Jin, T.; Mohamed, M.A.; Deb, D. A Novel Linear Optimization Method for Section Location of Single-Phase Ground Faults in Neutral Noneffectively Grounded Systems. IEEE Trans. Instrum. Meas. 2021, 70, 1–10. [Google Scholar] [CrossRef] [Scilit]
  33. Qi, L.; Zhang, R.; Hu, Z.; Li, L.; Wang, Q.; Ni, X.; Chen, F. Fast Thermal Infrared Image Restoration Method Based on On-Orbit Invariant Modulation Transfer Function. IEEE Trans. Geosci. Remote Sens. 2024, 62, 1–15. [Google Scholar] [CrossRef] [Scilit]
  34. Balestriero, R.; LeCun, Y. Contrastive and non-contrastive self-supervised learning recover global and local spectral embedding methods. Adv. Neural Inf. Process. Syst. 2022, 35, 26671–26685. [Google Scholar]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.