Next Article in Journal
Novel Hybrid Processing Techniques for Wideband HF Signals Impaired by Ionospheric Propagation
Previous Article in Journal
A 2.4 GHz CMOS Pulse-Mode Transmitter for RF Body-Contouring Device Applications
Previous Article in Special Issue
An Impedance Measurement Method for Renewable Energy Power Station
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Fault Process Modeling and Transient Stability Analysis of Grid-Following Photovoltaic Converter Grid-Connected System

by
Ze Wei
1,
Tao Xu
2,
Yan Wang
1,
Jianan Mu
2,
Lin Cheng
3,
Ning Chen
4,
Luming Ge
4 and
Xiong Du
1,*
1
School of Electrical Engineering, Chongqing University, Shapingba District, Chongqing 400044, China
2
National Electric Power Dispatching and Control Center, Xicheng District, Beijing 100052, China
3
Northwest Branch of State Grid Corporation of China, Xi’an 710048, China
4
State Key Laboratory of Renewable Energy Grid-Integration, China Electric Power Research Institute, Haidian District, Beijing 100192, China
*
Author to whom correspondence should be addressed.
Electronics 2025, 14(24), 4827; https://doi.org/10.3390/electronics14244827
Submission received: 27 October 2025 / Revised: 28 November 2025 / Accepted: 3 December 2025 / Published: 8 December 2025
(This article belongs to the Special Issue Wind and Renewable Energy Generation and Integration)

Abstract

With the growing integration of renewable energy into power systems, transient stability throughout the whole fault process has become a critical issue. This process comprises three distinct stages: pre-fault, fault-on, and post-fault recovery. However, existing studies have largely overlooked the influence of active power recovery on transient stability, which leads to conservative estimates of critical fault clearing time (CCT) and potential misjudgment of stability analysis. Accordingly, this paper addresses this gap by examining a grid-following (GFL) photovoltaic (PV) converter grid-connected system. Therefore, this paper investigates the transient stability of a GFL PV converter grid-connected system during the whole fault process. Firstly, a transient stability analysis model is developed using the piecewise linearization method to represent the system behavior across the whole fault process. Secondly, based on the proposed model, the impact mechanism of the control strategy in the fault recovery stage on the transient stability of the system is revealed by using the equal area criterion (EAC). Finally, the accuracy of the theoretical analysis proposed in this paper is verified by the PSCAD/EMTDC simulation platform. The results show that a slower active power recovery rate enhances the system’s transient stability, as it creates a larger equivalent deceleration area. The critical fault clearing time calculated by the proposed model is less conservative.

1. Introduction

Photovoltaic (PV), wind power, and other renewable energy sources are environmentally friendly and renewable, leading to their widespread adoption in power systems. While the installed capacity of PV generation is expanding rapidly worldwide, its inherent intermittency and uncertainty pose significant challenges to power grid stability [1,2]. Furthermore, reduced system inertia caused by the decreasing share of synchronous generators (SG) has brought the stability of grid-following (GFL) PV grid-connected systems to the research focus [3,4,5].
The stability problem of a GFL-PV converter grid-connected system is mainly divided into small-disturbance stability and transient stability. Among these, small-signal stability has been extensively studied using linearization methods [6,7]. In [7], the impedance model of a PV power generation system is established, and the influence of maximum power point tracking (MPPT) control on the small-disturbance stability is evaluated. Due to the nonlinear and high-order characteristics of grid-following PV systems, the small-disturbance stability analysis methods mentioned above cannot be directly applied to transient stability studies [8]. Therefore, a series of studies have been carried out on the transient stability of GFL grid-connected systems in [9,10,11]. Reference [9] compares the mathematical similarities between a synchronous generator and a grid-following converter and employs the damping torque method to explain the multi-swing instability phenomenon from a damping perspective. In [10], a control strategy based on improved phase-locked loop (PLL) and energy dissipation is presented, aiming to enhance the transient stability of GFL converter grid-connected systems. In [11], the phase portrait method was employed to examine transient stability in the GFL converter during asymmetric faults, uncovering the coupling effects between positive- and negative-sequence PLLs.
A prevailing view in the existing literature identifies the PLL as the main cause of transient instability. However, studies [12,13,14,15,16] indicate that an analysis focusing exclusively on the PLL can yield inaccurate conclusions. Reference [12] investigates the impact of the interaction between the PLL and the current loop on the transient stability of GFL converters. The conclusion demonstrates that this interaction can degrade system stability. Reference [13] employs the perturbation-averaging method to investigate the effects of both hard limiter and circular limiter nonlinearities on the transient stability of GFL converters, thereby deriving the large-disturbance synchronization stability boundary of the system. An investigation into the effect of PLL filter delay in Reference [14] reveals its detrimental impact on the transient stability of GFL converters, showing that increased delay leads to performance deterioration. In [15], the transient stability of a GFL-PV converter grid-connected system is evaluated, considering control switching delays, based on the existence of the equilibrium point and the transient energy balance. Reference [16] qualitatively identifies the key control loops responsible for transient instability across different time scales. However, it does not establish the multi-time-scale dynamic equations, thus failing to quantitatively characterize the system’s transient stability margin. The aforementioned studies have explored the transient stability of GFL converter grid-connected systems from perspectives such as multi-loop interactions, control saturations, and time delays. However, existing research has rarely accounted for the impact of active power recovery dynamics after fault clearing on the transient stability of GFL-PV converter grid-connected systems.
To the end, in the research on the transient stability of GFL-PV converter grid-connected systems during the whole fault process, two main research gaps are currently encountered:
(1)
The lack of transient stability analysis models in previous research for the whole fault process makes it difficult to characterize the transient characteristics of the system during the fault recovery period.
(2)
The impact mechanism of active power recovery control on system transient stability remains unclear, which may lead to misjudgment of stability analysis results and an overly conservative design of system fault clearance.
To address the aforementioned research gaps, this paper focuses on fault process modeling and transient stability analysis of GFL-PV converter grid-connected systems. The main contributions of this paper are as follows:
(1)
A piecewise linear description method is utilized to approximate the dynamic characteristics of the phase difference between the PCC voltage and the grid voltage during the fault recovery process, thereby establishing a mapping relationship between the phase difference and time. A mathematical model capable of characterizing the system transient stability throughout the whole fault process is proposed.
(2)
The influence mechanism of active power recovery control on the transient stability of the GFL-PV converter system is revealed. The influence of the active power recovery rate on the transient stability of the system is analyzed.
(3)
Based on the proposed model, the critical fault clearing time (CCT) of the system is calculated, which reduces the conservatism in previous methods.
The paper is organized as follows: In Section 2, the control strategy of the GFL-PV converter grid-connected system in the whole process of fault is analyzed. In Section 3, the transient model of the whole fault process is established. In Section 4, the transient stability of the whole fault process is analyzed by using the EAC. In Section 5, the CCT calculation model is established to quantify the stability margin. Section 6 simulates the theory proposed in this paper. Section 7 is our conclusion.

2. Control Strategy of GFL-PV Converter Grid-Connected System in the Whole Process of Fault

2.1. The Main Circuit Structure and Control Strategy of GFL-PV Converter

It can be seen from Figure 1 that the photovoltaic array is connected to the grid through the converter, filter, and grid impedance. Among them, idc is the DC side current, udc is the DC side voltage, ugabc is the grid voltage, uabc is the grid-connected point voltage, iabc is the grid-connected current, C1 is the DC capacitor, L1 is the filter inductance, Lg is the grid inductance, and Rg is the grid resistance. udcref and idq0ref denote the DC-side voltage reference and the dq-axis current references, respectively. idq0 are the dq axis current components of iabc. u*dq are the dq axis components of the converter terminal voltage. θPLL is the output phase angle of PLL. ut denotes the per-unit value of the point of common coupling (PCC) voltage. In and Pn denote the rated current and power of the system.
The GFL-PV converter should have a certain low voltage ride through (LVRT) capability, which injects dynamic reactive current into the system to support the grid operation after the fault occurs [17]. The LVRT capability requirements of the photovoltaic converter are shown in Figure 2.
The specific meaning of the assessment curve in Figure 2 is as follows: (1) When the PCC voltage drops to 0 p.u., the photovoltaic converter needs to ensure grid-connected operation for 0.15 s. (2) When the PCC voltage is restored to 0.2 p.u. after 0.15 s, the GFL-PV converter needs to continue to ensure grid-connected operation to 0.65 s. (3) In the range of 0.65 s to 2 s, the PCC voltage needs to be restored from 0.2 p.u. to 0.9 p.u. After the fault, if the PCC voltage is in the area above the assessment curve, the GFL-PV converter must be continuously connected to the grid; if the PCC voltage is in the area under the assessment curve, the converter is allowed to be off-grid.
In addition, according to the LVRT standard of the State Grid Corporation of China, after the fault is cleared, the active power needs to be restored to the steady state with a power change rate of at least 30% of the rated power per second [17], as shown in Figure 3. In general, the PCC voltage can be restored to the amplitude before the fault immediately after the fault is cleared. Therefore, the active power recovery requirement is essentially a requirement on the recovery rate of the active current reference idref.
At present, there is no uniform standard for the recovery rate of the active current reference idref by different GFL-PV converter manufacturers. In addition, the characteristics of active current recovery are also different, mainly including one-stage recovery and two-stage recovery. The recovery characteristics of active current and reactive current during the fault recovery period are shown in Figure 3. In order to simplify the subsequent modeling and stability analysis, this paper uses a one-stage model of active current recovery. Therefore, the control strategy and current reference value of the whole fault process can be obtained, as follows.
(1)
Control strategy during non-fault period
When the system is operating in the non-fault period, the GFL-PV converter must operate at its maximum available active power. Therefore, the reactive current reference value iqref during the non-fault period is 0, and the active current reference value idref is given by the DC voltage outer loop control. The active current and reactive current reference values during the non-fault period are expressed as
i dref = k pdc ( u dcref u dc ) + k idc ( u dcref u dc ) d t i qref = 0
where kpdc and kidc are the proportional coefficient and integral coefficient of the DC voltage outer loop PI controller, respectively. udc and udcref are the measured and reference values of the DC side voltage of the GFL-PV converter, respectively.
(2)
Control strategy during fault duration period
Upon detection of a grid voltage dip below 0.9 p.u. at the PCC, the GFL-PV converter activates its LVRT control strategy. Meanwhile, iqref is determined by the PCC voltage, and its expression varies with the depth of the voltage dip. The expression of the iqref fault duration period is shown in Equation (2).
i qref = 0 u > 0.9 1.5 I n ( 0.9 u ) 0.2 u 0.9 1.05 I n u < 0.2
where In is the rated current of the GFL-PV grid-connected system. u is the PCC voltage per unit value.
During fault duration period, there is a risk that increasing only iqref without reducing idref will cause a system overcurrent and trigger the protection. Therefore, to ensure stable grid-connected operation of the GFL-PV converter, the active current reference idref must be determined by iqref. Therefore, the expression of idref during the fault duration is
i dref = 1.1 I n 2 ( i qref ) 2
(3)
Control strategy during fault recovery period
In this paper, the one-stage model of active current recovery is adopted. Therefore, the expression of idref during the fault recovery period is
i dref = k ( t t 1 ) I n + i dref _ fau , P < P n i d _ nor , P P n
where k is the active current recovery rate. t1 is the fault clearing time. idref_fau is the active current value at the fault clearing time. idref_nor is the active current value during the non-fault period. P is the power measurement value of the fault recovery period. Pn is the rated power of the GFL-PV grid-connected system.
In summary, to ensure LVRT capability of the GFL-PV converter, appropriate control strategies must be deployed in accordance with the specific fault phase, as outlined in Figure 1.

2.2. Impact of Active Power Recovery Control on Transient Stability of the System

Research on the transient stability of GFL-PV converter grid-connected systems has rarely accounted for the influence of active power recovery control. To evaluate the impact of active power recovery control on transient stability, comparative simulation models of a GFL-PV grid-connected system, with and without this control, were developed. The simulation was configured with the parameters in Table 1, introducing a voltage drop to 0.9 p.u. at t = 1.2 s for a duration of 95 ms. The simulation results are shown in Figure 4.
A comparison of the results in Figure 4 reveals that, for the same fault clearing time, the system without active power recovery control becomes transiently unstable, whereas the system with the control maintains stability. Since most GFL-PV converters in practical engineering incorporate active power recovery control, it is imperative to study its impact on transient stability. Such research is crucial for guiding stability analysis and determining critical fault clearing times in the GFL-PV converter grid-connected system, ultimately reducing the conservatism and enhancing the accuracy of stability assessments.
Furthermore, the above observations indicate that the traditional transient stability modeling and analysis neglecting active power recovery control are no longer applicable, thereby motivating the establishment of a comprehensive modeling and analysis study covering the whole fault process.

3. Transient Modeling of a GFL-PV Converter Grid-Connected System in the Whole Fault Process

According to Section 2, the control block diagram of the GFL-PV converter grid-connected system in the whole fault process can be obtained, as shown in Figure 1. The GFL-PV converter control strategy includes PLL, voltage outer loop, current loop, and LVRT. The PLL takes the PCC voltage uabc as the input signal and outputs the phase θPLL, which provides the angle for the coordinate transformation of currents and voltages. The grid-connected current iabc is transformed to the dq-axis current components idq through the Park transformation. Using idq and idqref as inputs, the current loop employs a PI controller to generate the dq-axis reference voltage udqref for the converter terminals. Finally, the switching signals for the power devices are generated through the inverse Park transformation and Pulse Width Modulation (PWM).
Compared with the PLL, the current loop has a larger bandwidth. Thus, in studies of transient stability for photovoltaic grid-connected systems, the influence of the current loop’s dynamic characteristics is often neglected [16,18]. This simplification is achieved by assuming that idq = idqref. The dq-axis current reference value idqref has different values in different fault periods, such as the non-fault period, fault duration, and fault recovery period. In particular, during the recovery period, the d-axis reference idref is defined as a function of time, a dependency that notably complicates the transient stability analysis of the PV grid-connected system throughout the whole fault sequence.
In this section, the transient model of the GFL-PV converter grid-connected system in the whole fault process will be established. This model provides the foundation for the subsequent transient stability analysis. Prior to establishing the model, two assumptions were adopted [15,16].
(1)
The time difference between the fault clearing instant t1 and instant t2 when the phase difference reaches its maximum is sufficiently small, allowing higher-order residual terms in the Taylor expansion to be neglected.
(2)
The current loop exhibits high bandwidth, thereby enabling the neglect of its dynamic characteristics.

3.1. Transient Modeling During Non-Fault Period

According to the main circuit structure of the GFL-PV converter grid-connected system in Figure 1, the expression of the PCC voltage can be obtained as
u abc = u gabc + L g d i abc d t + R g i abc
where uabc = UtcosθPLL and Ut is the PCC voltage amplitude. ugabc = Ugncosθg, Ugn is the grid voltage amplitude during the non-fault period, and θPLL and θg are the PCC voltage phase and the grid voltage phase, respectively. iabc = ItcosθPLL, and It is the amplitude of grid-connected current.
By applying the Park transformation to Equation (5), the dq-axis component of the PCC voltage is obtained as
u d = U gn cos δ ω PLL L g i q + R g i d u q = U gn sin δ + ω PLL L g i d + R g i q
where δ = θPLLθg is the phase difference between the PCC voltage and the grid voltage. ωPLL is the angular frequency of the PCC voltage.
During the non-fault period, the q-axis current component is iqref = 0. Therefore, Equation (6) can be simplified as
u q = U gn sin δ + ω PLL L g i d
According to the control structure of PLL in the yellow frame of Figure 1, the dynamic equation of PLL can be obtained as
θ PLL = ( ω g + k pPLL u q + k iPLL u q d t ) d t
where ωg is the angular frequency of the grid voltage. kpPLL and kiPLL are the proportional coefficient and integral coefficient of the PLL’s PI controller, respectively.
Combining Equations (7) and (8), the transient model of the GFL-PV grid-connected system during the non-fault period can be obtained
δ ˙ = Δ ω PLL = ω PLL ω g J nor δ ¨ = T m_nor T e_nor D nor δ ˙
J nor = 1 k pPLL L g i dref T m_nor   =   k iPLL ω g L g i dref T e_nor   =   k iPLL U gn sin δ D nor = k pPLL U gn cos δ k iPLL L g i dref
where ΔωPLL is the angular frequency deviation of the PLL output, Jnor is the equivalent inertial time constant during the non-fault period, Tm_nor is the equivalent mechanical torque during the non-fault period, Te_nor is the equivalent electromagnetic torque during the non-fault period, and Dnor is the equivalent damping during the non-fault period [13]. In addition, idref is determined by Equation (1).

3.2. Transient Modeling During Fault Duration

It can be seen from Section 2.1 that the q-axis current reference value iqref is determined by the LVRT control during the fault duration period. At this time, iqref depends on the amplitude of the PCC voltage.
Compared with the non-fault period, the iqref during the fault duration period becomes non-zero. At this time, the q-axis component of the PCC voltage is consistent with Equation (6). Therefore, combined with Equations (6) and (8), the transient model of the system during the fault duration period can be obtained as
δ ˙ = ω PLL ω g J dur δ ¨ = T m_dur     T e_dur     D dur δ ˙
J dur = 1 k pPLL L g i dref T m_dur   =   k iPLL ( ω g L g i dref + R g i qref ) T e_dur   =   k iPLL U gf sin δ D dur = k pPLL U gf cos δ + k iPLL L g i dref
where Ugf is the grid voltage amplitude during the fault duration period, Jdur is the equivalent inertia time constant during the fault duration period, Tm_dur is the equivalent mechanical torque during the fault duration period, Te_dur is the equivalent electromagnetic torque during the fault duration period, and Ddur is the equivalent damping during the fault duration period. In addition, the dq axis current reference values idref and iqref are determined by Equations (2) and (3). The value of δ is [δ0, δc].

3.3. Transient Modeling During Fault Recovery Period

It can be seen from Section 2.1 that the d-axis current reference value idref is determined by Equation (4) during fault recovery period, and the q-axis current reference value iqref is 0. During the fault recovery period, the time required for the system to reach transient stability is shorter than that for the d-axis current to reach its rated value. Therefore, when establishing the transient model during the fault recovery period, it is sufficient to consider the i_dref expression only under the condition P < Pn.
By combining Equations (4) and (7), the q-axis component of the PCC voltage during the fault recovery period is obtained as follows:
u q = U gn sin δ + ω PLL L g ( k ( t t 1 ) + i dref _ fau )
Furthermore, combined with Equations (8) and (13), the transient model of the system during the fault recovery period can be obtained as
δ ˙ = ω PLL ω g J cut δ ¨ = T m_cut     T e_cut   D cut δ ˙
J cut = 1 k pPLL L g ( k ( t t 1 ) + i dref _ fau ) T m_cut   =   k iPLL ω g L g ( k ( t t 1 ) + i dref _ fau ) + k pPLL k ω g L g T e_cut   =   k iPLL U gn sin δ D cut = k pPLL U gn cos δ k iPLL L g ( k ( t t 1 ) + i dref _ fau )
where Jcut is the equivalent inertial time constant during fault recovery period, Tm_cut is the equivalent mechanical torque during fault recovery period, Te_cut is the equivalent electromagnetic torque during fault recovery period, and Dcut is the equivalent damping during fault recovery period. idref_fau is the d-axis current reference at fault clearance.
Equations (14) and (15) show that the transient model of the GFL-PV grid-connected system during the fault recovery period contains a time variable t. Existing stability analysis methods cannot be directly applied to this model due to its time-dependent nature. The phase difference δ between the PCC voltage and the grid voltage evolves as a function of time, i.e., δ = f(t), as shown in Figure 5. Therefore, by providing the analytical expression for f(t) and employing a variable substitution for time t, Equation (17) can be transformed into a second-order system. This allows for the application of methods like the EAC to analyze the system’s transient stability.
As shown in Figure 5, the system operates during the non-fault period in [0, t0], and the initial phase difference is δ0. The voltage drop fault occurs in the system at t0. In [t0, t1], the system operates during the fault duration period, and the phase δ increases under the LVRT control strategy of the GFL-PV converter. The system clears the fault at t1, and the t1 corresponds to the fault clearing angle δc. In [t1, t4], the system operates during the fault recovery period. The system reaches the maximum phase difference δmax at t2. Meanwhile, the system reaches the minimum phase difference δmin at t3. The system’s phase difference converges to δ0 at t4, when the d-axis current reference reaches its rated value, marking the end of the fault recovery period, as shown in Figure 5.
As observed in Figure 5, constructing a detailed mapping between phase δ and time t is challenging. Furthermore, since the system’s transient stability is primarily governed by the maximum phase difference δmax, a direct focus on this critical value is more pertinent. The system is transiently stable if δmax remains below the unstable equilibrium point (UEP), and becomes unstable if δmax exceeds it. It is established that the dynamic characteristics within [t2, t4] are associated with the system’s equivalent damping and exert minimal influence on the transient stability. Consequently, the mapping relationship between δ and t over this interval is excluded from the scope of this study.
Establishing the mapping relationship between δ and t is a crucial step in developing the transient model for the fault recovery process. Common approaches include data-driven methods and piecewise linear approximation [19,20]. The former relies on experimental and measured datasets to build a data-driven model using intelligent algorithms, offering a novel solution for systems where analytical models are difficult to establish. Nevertheless, this method imposes high requirements on technical schemes and hardware specifications. The latter employs model reduction strategies through simplified linear models to approximate complex nonlinear dynamics, enabling high local accuracy within specific operational ranges. To capture the dynamics of δ in [t1, t2], this paper approximates its dynamics using a linear function, adopting a piecewise linearization approach [20].
A key issue in this paper is determining the appropriate linear function. By combining Equations (8) and (13), the expression for the phase difference δ as a function of time t during the fault recovery period can be derived as
δ = k pPLL ω g L g ( i dref _ fau k t 1 I n ) t + ω g L g k I n 2 t 2 + U gn sin δ d t + k iPLL ω g L g ( i dref _ fau k t 1 I n ) 2 t 2 + ω g L g k I n 6 t 3 + ( U gn sin δ d t ) d t
By applying a Taylor series expansion to Equation (16) at the fault clearing point (t1, δc), the expression can be obtained as
δ = f ( δ , t ) = f ( δ c , t 1 ) + f ˙ ( δ c , t 1 ) ( t t 1 ) + 1 2 ! f ¨ ( δ c , t 1 ) ( t t 1 ) 2 + R n ( t ) f ˙ ( δ c , t 1 ) = k pPLL [ ω g L g i dref _ fau U gn sin δ c ] + k iPLL ω g L g ( i dref _ fau 1 2 k I n t 1 ) t 1 f ¨ ( δ c , t 1 ) = k pPLL ω g L g k I n + k iPLL ω g L g i dref _ fau U gn sin δ c
Given that the PLL operates on an electromagnetic transient timescale with exceptionally fast dynamics, the time difference between fault clearance and the maximum phase difference (t = t2t1) is very short. This brevity justifies neglecting second-order and higher-order terms. Consequently, the phase difference δ can be linearized as a function of time t in [t1, t2] as follows:
δ = f ( t ) = δ c + k 1 ( t t 1 ) = δ c + f ˙ ( δ c , t 1 ) ( t t 1 )
By integrating Equations (8), (13), and (18), the transient model for the GFL-PV grid-connected system during fault recovery is derived as
δ ˙ = ω PLL ω g J cut δ ¨ = T m_cut     T e_cut   D cut δ ˙
J cut = 1 k pPLL L g ( k k 1 ( δ δ c ) + i dref _ fau ) T m_cut   =   k iPLL ω g L g i dref _ fau + k iPLL ω g L g k k 1 ( δ δ c ) T e_cut   =   k iPLL U gn sin δ D cut = k pPLL U gn cos δ + k iPLL L g ( k k 1 ( δ δ c ) + i dref _ fau ) + k pPLL ω g L g k k 1
where δ the value is [δc, π].

4. Transient Stability Analysis of GFL-PV Converter Grid-Connected System

The transient model of the GFL-PV converter grid-connected system during the whole fault process, established in Section 3, is a second-order differential equation, which has certain similarity with the synchronous generator swing equation.
Therefore, the transient stability of the system can be analyzed by the EAC [13,14,15,16]. Based on the proposed model, this section applies the EAC to evaluate the system’s transient stability during the whole fault process.

4.1. Transient Stability Analysis During Non-Fault Period

According to Equations (9) and (10), a schematic diagram of transient stability analysis during non-fault period can be drawn, as shown in Figure 6.
From Figure 6, it can be seen that the equivalent mechanical torque Tm_nor is equal to the equivalent electromagnetic torque Te_nor during the non-fault period, and the phase δ is δ0. Since the q-axis component of the PCC voltage uq = 0 during the non-fault period, the initial phase δ0 can be derived from Equation (7) as
δ 0 = arcsin ω PLL L g i dref U gn
where idref is determined by Equation (1).

4.2. Transient Stability Analysis During Fault Duration Period

After the fault occurs, the dynamic balance of the GFL-PV converter grid-connected system is disrupted, causing the phase δ to increase [21]. According to Equations (11) and (12), a schematic diagram of transient stability analysis during the fault duration period can be drawn, as shown in Figure 7.
According to Figure 7, after the voltage drop fault occurs, the equivalent mechanical torque of the system changes from Tm_nor to Tm_dur, and the equivalent electromagnetic torque changes from Te_nor to Te_dur. When the voltage drop fault is more serious, the GFL-PV grid-connected system will lose the static equilibrium point (SEP). At this time, Since Tm_dur consistently exceeds Te_dur, the resulting torque difference causes an angular frequency deviation of PLL. The angular frequency deviation ΔωPLL continues to increase, which eventually leads to the transient instability of the system, as shown in Figure 7a.
When there is an SEP in the system after the fault occurs, the operating point of the system moves from point A to point B. At this time, Tm_dur > Te_dur, and the torque difference will drive the PLL output. The ΔωPLL increases until Tm_dur = Te_dur, and the phase of the system increases from δ0 to δSEP1. At this time, the area of the operating point trajectory ABC is the acceleration area S+. The acceleration area S+ can be given as follows:
S + = δ 0 δ c ( T m _ dur T e _ dur ) d δ
When the system operating point reaches C, the ΔωPLL > 0 causes the phase angle difference δ to continue increasing. When the operating point moves from C to D, Tm_dur < Te_dur creates a decelerating torque difference ΔωPLL. At this time, the area formed by the operating point trajectory CD is the deceleration area S. The deceleration area S can be given as follows:
S = δ c δ max ( T e _ nor T m _ nor ) d δ
Therefore, the transient stability criterion during the fault duration period is as follows: when S+ < S, the system is transiently stable. When S+ > S, the system is transiently unstable [13].
After the fault occurs, if the GFL-PV converter grid-connected system operates in the S+ > S condition of Figure 7b or Figure 7a; it is imperative to ensure timely fault clearance to maintain normal system operation.

4.3. Transient Stability Analysis During Fault Recovery Period

This paper investigates the transient stability of the GFL-PV converter grid-connected system during the fault recovery period, using the static equilibrium point as a representative case. According to Equations (19) and (20), a schematic diagram of transient stability analysis during fault recovery period can be drawn, as shown in Figure 8.
From the analysis of Section 4.2, it can be seen that phase δ increases after the fault occurs. When the phase increases from δ0 to δc, the system clears the fault. At this time, the equivalent mechanical torque changes from Tm_dur to Tm_cut, and the equivalent electromagnetic torque changes from Te_dur to Te_cut. As shown in Figure 8, the system operating point first traverses rightward from B1 along the Te_dur curve, then undergoes a jump to C1 at δc, and finally follows the path C1D1F1. It can be seen from Figure 8 that the acceleration area is S1+, and the deceleration area is Scut− = S1− + S2−. The deceleration area S can be given as follows:
S cut = δ c δ max ( T e _ cut T m _ cut ) d δ = δ c δ max ( T e _ cut T m _ nor ) d δ S 1 + δ c δ max ( T m _ nor T m _ cut ) d δ S 2
Therefore, the criterion during the fault recovery period is as follows: when S1+ < S1− + S2−, the system transiently stable; when S1+ > S1− + S2−, the system is transiently unstable.
The condition for critical stability is equality between the acceleration and deceleration areas, i.e., S+ = S. The corresponding fault clearing time and power angle are known as CCT and the Critical Clearing Angle (CCA) δcr.
By comparing Equation (23) with Equation (24), it can be observed that the active power recovery control leads to an increase in the system’s deceleration area. Consequently, active power recovery control enables the system to accommodate a larger acceleration area, thereby permitting higher values for both the CCT and CCA. This observation reveals the underlying reason for the conservatism inherent in traditional transient stability analysis models.

4.4. Impact of Active Power Recovery Rate k on System Transient Stability

Following Equations (19) and (20), Figure 9 shows the transient stability analysis diagram under different active power recovery rates k. In Figure 9, Tm_cut1 corresponds to the largest value of k, while curve Tm_cut3 corresponds to the smallest. It can be seen from Figure 9 that when the equivalent electromagnetic torque is Tm_cut1, the system deceleration area is S1− + S21−; when the equivalent electromagnetic torque is Tm_cut2, the system deceleration area is S1− + S21− + S22−; and when the equivalent electromagnetic torque is Tm_cut3, the system deceleration area is S1− + S21− + S22− + S23−. Comparing the deceleration areas under different k, it can be concluded that a smaller k corresponds to a larger deceleration area, which improves the system’s transient stability.

5. Quantitative Calculation of CCT

The above research established a transient model for the whole fault process and employed EAC to analyze the impact of active power recovery control on transient stability. This section focuses on the quantitative calculation of CCT.
By combining Equations (9)–(12), (22), and (23), the previous CCT calculation model can be derived, as shown in Equation (24).
δ cr 1 = arccos ( A + B + C 1 U gn U gf ) A = U gn cos δ max U gf cos δ 0 B = ( ω g L g i dref _ fau + R g i qref _ fau ) ( δ c δ 0 ) C 1 = ω g L g i dref ( δ max δ c )
By integrating Equations (9), (10), (19), (20), (22), and (24), the CCT calculation model that accounts for active power recovery control can be derived, as shown in Equation (25).
δ cr 2 = arccos ( A + B + C 2 U gn U gf ) A = U gn cos δ max U gf cos δ 0 B = ( ω g L g i dref _ fau + R g i qref _ fau ) ( δ c δ 0 ) C 2 = n ω g L g i dref ( δ max δ c ) n = k k 1 ( δ max δ c ) 2 + i dref _ fau i dref
where n the value is [0, 1].
The CCT calculation model is given as follows [13]:
CCT =   t 1 t 0 = δ c δ 0 0.5 S + J dur
By applying the Newton–Raphson method to solve Equation (26), the CCA can be obtained. This result is then substituted into Equation (27) to determine the CCT that accounts for active power recovery control.
A comparison of Equations (25) and (26) shows that the proposed CCT model, which considers active power recovery control, features an additional coefficient n in the C2 term. Furthermore, since the CCA calculation model is a decreasing function, C2C1 always holds, which necessarily implies δcr2δcr1. According to Equation (27), this condition results in a larger CCT when active power recovery control is considered. Therefore, the proposed model in this paper offers the dual advantage of higher accuracy and lower conservatism.
When the recovery rate k is sufficiently high, n approaches 1. Under this condition, the CCT models with and without active power recovery control become identical. This demonstrates that the previous CCT calculation model, which neglects recovery dynamics, constitutes a special case of the proposed CCT calculation model.

6. Simulation Verification

In order to verify the accuracy of the proposed transient model and theory, according to the circuit structure and control strategy of the photovoltaic converter grid-connected system in Figure 1, the simulation model is built in PSCAD/EMTDC. Table 1 gives the parameters of the system. The grid voltage amplitude drop fault is set at 1.2 s, and the drop amplitude is 0.9 p.u.

6.1. Validity Assessment of Transient Model

This paper establishes two case scenarios to assess the validity of the proposed transient model. In Case 1, the fault clearing time is set at 88 ms. In Case 2, the fault clearing time is set at 110 ms. The output results from the proposed model, the previous model, and the simulation model are presented in Figure 10.
As shown in Figure 10a, after fault clearance, both the proposed model and the simulation model indicate that the system remains transiently stable, whereas the previous model predicts transient instability. From Figure 10b, it can be observed that the proposed model, the previous model, and the simulation model all demonstrate transient instability. Therefore, the proposed model in this paper can be effectively applied to assess the transient stability of the system and to calculate a less conservative CCT.

6.2. Transient Stability Analysis Considering Active Power Recovery Control Strategy

Based on the proposed transient model, the critical fault clearing time of 99.9 ms is obtained by using the CCT calculation model in Section 5. In this paper, the fault clearing time of the photovoltaic converter grid-connected system is 99 ms (within CCT) and 103 ms (outside CCT), respectively. The simulation results are shown in Figure 11. Table 2 shows the calculation results of the acceleration and deceleration area of the system with different fault clearing times.
From Figure 11, it can be seen that the fault clearing within CCT can maintain the transient stability of the system, which proves the accuracy of the proposed model. By using the previous model without considering the active power recovery, the CCT is shown in Table 3.
As shown in Table 3, the error between the CCT calculated by the proposed model and the simulated CCT is 2.92%, compared to 12.14% for the previous model. This result demonstrates a significant reduction in the conservativeness of the proposed model.

6.3. Impact of Active Power Recovery Rate k on System Transient Stability

In order to verify the impact of the active power recovery rate k on the transient stability of the system, this section uses the fault condition parameters in Table 1, and the fault clearing time is set to 99 ms. The active power recovery rate k is selected as 3 p.u./s, 30 p.u./s and 300 p.u./s, respectively. Based on the simulation model of the photovoltaic converter grid-connected system considering active power recovery control, the transient stability analysis is performed. The simulation results are shown in Figure 12.
It can be seen from Figure 12 that the higher active power recovery rate k after fault clearing adversely affects the transient stability of the system. When the rate k is high enough, it can be regarded as the system not having active power recovery control. Therefore, for the same fault clearing time, the system is more susceptible to transient instability.
Furthermore, CCTs under different active power recovery rates were quantitatively calculated using the proposed model, as presented in Table 4. These values were then compared against those from the simulation model to analyze the impact of the active power recovery rate on the system’s transient stability. As observed in Table 4, a higher active power recovery rate leads to a shorter CCT, a trend that is consistently validated by both the proposed and simulation models. However, as the recovery rate increases, the error in CCT between the proposed model and the simulation results also becomes more pronounced.

7. Conclusions

This paper investigates the transient stability of grid-following photovoltaic converter grid-connected systems during the whole fault process. It reveals the influence mechanism of active power recovery control on system transient stability and characterizes the system stability boundary. The specific conclusions are as follows:
(1)
A transient stability analysis model considering the whole fault process is proposed based on the piecewise linear description method. This model addresses the existing gap in characterizing transient behavior throughout the whole fault duration.
(2)
The active power recovery control reduces the equivalent mechanical power during the fault recovery period, thereby increasing the decelerating area and enhancing the system’s transient stability.
(3)
The faster the active power recovery rate, the worse the system’s transient stability; conversely, the slower the recovery rate, the better the transient stability.
(4)
Based on the proposed model, the CCT exhibits lower conservatism, which enhances the accuracy of system transient stability assessment.
The model proposed in this paper can provide a theoretical foundation for transient stability analysis of grid-following photovoltaic converter grid-connected systems and guide fault-clearing operations. For photovoltaic power stations, the electrical distances from individual units to the collection bus vary significantly. Therefore, transient stability modeling, analysis, and control of PV power stations considering active power recovery control will be a key focus of future research.

Author Contributions

Conceptualization, Z.W., T.X. and J.M.; methodology, Z.W., L.C., Y.W. and N.C.; formal analysis, Z.W. and L.G.; resources, Z.W. and X.D.; writing—review and editing, Z.W. and X.D.; funding acquisition, L.C. All authors have read and agreed to the published version of the manuscript.

Funding

This work was supported by Science and Technology Project of SGCC (Transient support for high proportion of new energy at UHVDC sending/receiving end Key Technology Research) 5100-202306384A-2-3-XG.

Data Availability Statement

The data are contained within the article.

Conflicts of Interest

Author Lin Cheng was employed by the company Northwest Branch of State Grid Corporation of China, authors Tao Xu and Jianan Mu were employed by the company National Electric Power Dispatching and Control Center and authors Ning Chen and Luming Ge were employed by the company China Electric Power Research Institute. The remaining authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.

References

  1. Xiao, X.; Zheng, Z. New power systems dominated by renewable energy towards the goal of emission peak and carbon neutrality: Contribution, key techniques, and challenges. Adv. Eng. Sci. 2022, 54, 47–59. [Google Scholar]
  2. Hu, B.; Xie, K.; Shao, C.; Pan, C.; Lin, C.; Zhao, Y. Review and prospect of frequency stability analysis and control of low-inertia power systems. Autom. Electr. Power Syst. 2023, 47, 1–15. [Google Scholar]
  3. Wen, Y.; Yang, W.; Lin, X. Review and prospect of frequency stability analysis and control of low inertia power systems. Electr. Power Autom. Equip. 2020, 40, 211–222. [Google Scholar]
  4. Yang, P.; Liu, F.; Jiang, Q.; Mao, H. Large-disturbance stability of power systems with high penetration of renewables and inverters: Phenomena, challenges, and perspectives. J. Tsinghua Univ. (Sci. Technol.) 2021, 61, 403–414. [Google Scholar]
  5. Zhang, D.; Chen, X. Overview of Broadband Oscillation Mitigation of New Energy Generation Power System Based on Impedance Perspective. Proc. CSEE 2024, 44, 9672–9691. [Google Scholar]
  6. Liu, J.; Du, X.; Guan, B.; Zhang, B. Impedance Modeling and Stability Analysis for Grid-connected Inverter Containing Operating Point Variables. Power Syst. Technol. 2022, 46, 3642–3650. [Google Scholar]
  7. Song, S.; Wei, Z.; Lin, Y.; Liu, B.; Liu, H. Impedance modeling and stability analysis of PV grid-connected inverter systems considering frequency coupling. CSEE J. Power Energy Syst. 2020, 6, 279–290. [Google Scholar] [CrossRef]
  8. Geng, H.; He, C.; Liu, Y.; He, X.; Li, M. Overview on Transient Synchronization Stability of Renewable-rich Power Systems. High Volt. Technol. 2022, 48, 3367–3383. [Google Scholar]
  9. Zhang, Y.; Zhan, M. Dominant Transient Unstable Characteristics of PLL-based Grid-connected Converters. Proc. CSEE 2023, 43, 9285–9297. [Google Scholar]
  10. Jiang, K.; Liu, D. Transient stability enhancement strategy for grid-following inverter based on improved phase-locked loop and energy dissipation. Electronics 2025, 14, 3520. [Google Scholar] [CrossRef]
  11. Luo, Y.; Yao, J.; Chen, Y.; Liu, Y.; Li, X.; Yang, D.; Jin, R.; Zhao, L. Transient stability analysis for Grid-Connected PLL Based VSC during Asymmetric Grid Faults. In Proceedings of the 2024 4th International Conference on Energy, Power and Electrical Engineering (EPEE), Wuhan, China, 20–22 September 2024; pp. 877–880. [Google Scholar]
  12. Wu, C.; Lyu, Y.; Wang, Y.; Blaabjerg, F. Transient Synchronization Stability Analysis of Grid-Following Converter Considering the Coupling Effect of Current Loop and Phase Locked Loop. IEEE Trans. Energy Convers. 2024, 39, 544–554. [Google Scholar] [CrossRef]
  13. Wu, T.; Xie, X.; He, J.; Jiang, Q. Synchronization Stability Issues of Grid-tied Converters with Saturation Nonlinearities. Proc. CSEE 2025, 45, 6886–6896. [Google Scholar]
  14. Zhang, C.; Chen, J.; Si, W. Analysis of Phase-Locked Loop Filter Delay on Transient Stability of Grid-Following Converters. Electronics 2024, 13, 986. [Google Scholar] [CrossRef]
  15. Pei, J.; Yao, J.; Liu, Y.; Chen, S.; Sun, P.; Huang, S. Modeling and transient synchronization stability analysis for PLL-based renewable energy generator considering sequential switching schemes. IEEE Trans. Power Electron. 2022, 37, 2165–2179. [Google Scholar]
  16. Zhu, D.; Ma, Y.; Hu, J. Multi-timescale Transient Stability Issues and Research Status of Renewable Energy Grid-connected Systems During Grid Faults. Proc. CSEE 2025. [Google Scholar] [CrossRef]
  17. GB/T 19964-2012; Technical Specifications for the Integration of Photovoltaic Power Stations into Power Systems. Quality Inspection Press: Beijing, China, 2012.
  18. Hu, Q.; Fu, L.; Ma, F.; Wang, G.; Liu, C.; Ma, Y. Impact of LVRT control on transient synchronizing stability of PLL-based wind turbine converter connected to high impedance AC grid. IEEE Trans. Power Syst. 2023, 38, 5445–5458. [Google Scholar] [CrossRef]
  19. Sun, Z.; Wang, X.; Han, T.; Wang, L.; Zhu, Z.; Huang, H.; Ding, J.; Wu, Z. Pipeline deformation prediction based on multi-source monitoring information and novel data-driven model. Eng. Struct. 2025, 337, 120461. [Google Scholar] [CrossRef]
  20. Liu, Q.; Dong, C.; Wu, Y.; Zhang, Y.; Peng, S.; Shen, J. Characteristic Description and Transient Overvoltage Suppression of Doubly-fed Wind Turbines with LCC-HVDC Commutation Failure. Autom. Electr. Power Syst. 2022, 46, 29–38. [Google Scholar]
  21. Li, X.; Tang, Y.; Tian, Z.; Zha, X.; Sun, J.; Li, Y. Synchronization stability analysis of grid-connected inverter based on improved equal area criterion. Autom. Electr. Power Syst. 2022, 46, 208–215. [Google Scholar]
Figure 1. Circuit structure and control strategy of GFL-PV converter.
Figure 1. Circuit structure and control strategy of GFL-PV converter.
Electronics 14 04827 g001
Figure 2. GFL-PV converter low voltage ride through capability requirements.
Figure 2. GFL-PV converter low voltage ride through capability requirements.
Electronics 14 04827 g002
Figure 3. GFL-PV converter power requirements during fault recovery stage.
Figure 3. GFL-PV converter power requirements during fault recovery stage.
Electronics 14 04827 g003
Figure 4. When the fault clearing time is 95 ms, the simulation results of the system without active power recovery control. (a) Without active power recovery control. (b) With active power recovery control.
Figure 4. When the fault clearing time is 95 ms, the simulation results of the system without active power recovery control. (a) Without active power recovery control. (b) With active power recovery control.
Electronics 14 04827 g004
Figure 5. Response curve of phase difference between the PCC voltage and the grid voltage.
Figure 5. Response curve of phase difference between the PCC voltage and the grid voltage.
Electronics 14 04827 g005
Figure 6. Transient stability analysis diagram during non-fault period.
Figure 6. Transient stability analysis diagram during non-fault period.
Electronics 14 04827 g006
Figure 7. Transient stability analysis diagram during fault duration. (a) There is no static equilibrium point. (b) There is a static equilibrium point.
Figure 7. Transient stability analysis diagram during fault duration. (a) There is no static equilibrium point. (b) There is a static equilibrium point.
Electronics 14 04827 g007
Figure 8. Transient stability analysis diagram during fault recovery.
Figure 8. Transient stability analysis diagram during fault recovery.
Electronics 14 04827 g008
Figure 9. Transient stability analysis diagram during fault recovery period under different active power recovery rates k.
Figure 9. Transient stability analysis diagram during fault recovery period under different active power recovery rates k.
Electronics 14 04827 g009
Figure 10. Output results of different models. (a) Different models in Case 1. (b) Different models in Case 2.
Figure 10. Output results of different models. (a) Different models in Case 1. (b) Different models in Case 2.
Electronics 14 04827 g010
Figure 11. Simulation results of photovoltaic grid-connected system. (a) The fault clearing time is 99 ms. (b) The fault clearing time is 103 ms.
Figure 11. Simulation results of photovoltaic grid-connected system. (a) The fault clearing time is 99 ms. (b) The fault clearing time is 103 ms.
Electronics 14 04827 g011
Figure 12. Simulation results of system under different active power recovery rates k.
Figure 12. Simulation results of system under different active power recovery rates k.
Electronics 14 04827 g012
Table 1. Photovoltaic grid-connected system parameters.
Table 1. Photovoltaic grid-connected system parameters.
Parameter NameSignValue
Nominal powerS0.1 MW
Rated AC side voltageU0.4 kV
Rated angular frequencyωg100π rad/s
Filter inductanceLf2.5 mH
Grid inductanceLg2 mH
Grid resistanceRg0.2 Ω
Active current recovery slopek3
Phase-locked loop proportional gainKpPLL0.2221
Phase-locked loop integral gainKiPLL9.9
Table 2. Calculation results of acceleration and deceleration area of system with different fault clearing times.
Table 2. Calculation results of acceleration and deceleration area of system with different fault clearing times.
CCTFault Clearing TimeAcceleration/Deceleration AreaStability Analysis Results
within CCT99 msS+ = Stransient stability
without CCT103 msS+ > Stransient instability
Table 3. CCT calculation results using different models.
Table 3. CCT calculation results using different models.
Calculation ModelCCTCCT in SimulationError
Proposed model99.9 ms102.9 ms2.92%
Previous model90.4 ms102.9 ms12.14%
Table 4. CCT calculation results with different k.
Table 4. CCT calculation results with different k.
Active Power Recovery RateCCT Using Proposed ModelCCT in SimulationError
399.9 ms102.9 ms2.92%
3096.5 ms100.5 ms3.98%
30090.4 ms98.4 ms8.13%
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Wei, Z.; Xu, T.; Wang, Y.; Mu, J.; Cheng, L.; Chen, N.; Ge, L.; Du, X. Fault Process Modeling and Transient Stability Analysis of Grid-Following Photovoltaic Converter Grid-Connected System. Electronics 2025, 14, 4827. https://doi.org/10.3390/electronics14244827

AMA Style

Wei Z, Xu T, Wang Y, Mu J, Cheng L, Chen N, Ge L, Du X. Fault Process Modeling and Transient Stability Analysis of Grid-Following Photovoltaic Converter Grid-Connected System. Electronics. 2025; 14(24):4827. https://doi.org/10.3390/electronics14244827

Chicago/Turabian Style

Wei, Ze, Tao Xu, Yan Wang, Jianan Mu, Lin Cheng, Ning Chen, Luming Ge, and Xiong Du. 2025. "Fault Process Modeling and Transient Stability Analysis of Grid-Following Photovoltaic Converter Grid-Connected System" Electronics 14, no. 24: 4827. https://doi.org/10.3390/electronics14244827

APA Style

Wei, Z., Xu, T., Wang, Y., Mu, J., Cheng, L., Chen, N., Ge, L., & Du, X. (2025). Fault Process Modeling and Transient Stability Analysis of Grid-Following Photovoltaic Converter Grid-Connected System. Electronics, 14(24), 4827. https://doi.org/10.3390/electronics14244827

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop