Abstract
As part of the EduClimAir project, this study aimed to improve indoor comfort conditions by experimentally evaluating acoustic, thermal, and visual comfort, as well as indoor air quality, in two classrooms with different ventilation types (natural and mechanical) at the Department of Mechanical Engineering, University of Coimbra. Both classrooms are part of a living-lab setup where indoor environmental quality (IEQ) parameters (air temperature Ta, relative humidity RH, carbon dioxide CO2 and particulate matter PM concentrations, A-weighted equivalent continuous sound pressure level LAeq) are continuously monitored. Representative data across one semester (September through December) is presented in two phases and one day, highlighting the teaching period timeframe, LAeq_Work_P. One phase is a chronological sequence of one week of non-occupancy and one week of occupancy. Results during occupancy showed LAeq_Work_P reached up to 60 dBA (room 3.3) and 65 dBA (room 6.3) in the first phase, and up to 55 dBA (room 3.3) and 57 dBA (room 6.3) in the second phase. Noise was suboptimal, though considered moderate and tolerable in a university setting. During non-occupancy, LAeq_Work_P remained broadly within WHO/ANSI S12.60 limits in the first phase but often exceeded 40 dBA in the second phase due to heating, ventilation, and air conditioning (HVAC) systems operating during unoccupied days, a gap in energy management. An evaluation of noise, Ta, CO2, and PM interactions in one day suggests IEQ gaps. The study revealed HVAC management and IEQ gaps otherwise be missed outside a continuous monitoring and multidomain assessment approach.
1. Introduction
When assessing indoor environmental quality (IEQ) in school buildings (SBs), acoustic comfort is a crucial aspect [1]. Acoustic comfort is relevant across built environments, including offices [2], residential homes [3], medical and health facilities [4], land transport cabins [5], air transport cabins [6], and SBs [7], although the requirements may differ for SBs [2]. As students spend long hours daily in SBs [3], they require a conducive environment for optimal learning; the need to evaluate and improve acoustic comfort cannot be overemphasized [4]. In SBs, unwanted sound can be considered noise [5], and the higher the sound level, the greater the risk of negative impact on the acoustic comfort. Poor acoustic performance in SBs may degrade speech clarity and impede communication, placing an extra burden on cognitive processing [6]. Noise levels play a significant role in students’ retention and concentration, whether as annoyance or interference [7,8], not to mention the potential health impacts of prolonged exposure, such as cases of students experiencing impaired memory during spoken lectures [9]. Other studies have noted the higher impact of noise on children [10] and second-language learners [11]. The school location is also important, as higher external noise exposure can negatively impact students’ cognitive function [12]. Students are more likely to be distracted by intermittent noise than constant noise [13], with different noise sources having different impacts [14], ranging from irritation due to environmental noise sources [15] to noise annoyance caused by infiltration from neighboring classrooms [16]. Although the associated impact of noise levels on students’ performance has been reported in many studies [17], a study by Xie et al. [18] did not find a significant link between noise levels and academic performance. The impact of noise exposure in SBs is not limited to students; studies have revealed hearing impairments among teachers linked to long-term exposure [19]. To achieve adequate acoustic comfort, it is essential to reduce noise levels by identifying and mitigating noise sources while accounting for other influencing parameters [20]. Other influencing parameters and their effects on occupants’ perception and overall comfort have been investigated in a few studies [21,22,23]. Lin et al. [24] observed that the acoustic environment in an outdoor setting influenced thermal sensation, such that reducing excessive noise levels could improve thermal comfort. Guan et al. [25] also reported that the acoustic environment plays a role in thermal comfort with an effect size of 0.3, which in turn affects total comfort. Noting that the type of sound affects people’s subjective perception, the authors suggested the use of music to improve indoor satisfaction. This presents an energy-saving possibility as less energy may be required to improve occupants’ satisfaction. On the interaction between air quality and acoustic comfort, de la Hoz-Torres et al. [26] evaluated different strategies to improve ventilation rates in four naturally ventilated university classrooms. They observed a negative impact on acoustic comfort when varying air change rates across scenarios were implemented, given a rise in background noise. Ballerini et al. [27] similarly highlighted an increase in background noise after the installation of a controlled mechanical ventilation unit to improve air quality in a high school classroom in Italy. The outcomes of these studies provide valuable insight into the influencing relationship between parameters. Multidomain approach and correlational evaluation of IEQ parameters remain largely underexplored [28], especially in the context of educational buildings. With increasing recognition that IEQ must be treated as an interacting system, including the need for a multidomain approach to IEQ assessments [29,30], the current study focuses on sound equivalent levels in an everyday classroom setting, examining interactions among indoor climate parameters, including air temperature (Ta), relative humidity (RH), CO2, and PM (PM2.5 and PM10) during occupancy to identify corresponding IEQ gaps and to provide useful insights for optimal IEQ management and energy efficiency for the assurance of adequate comfort, reduced health risks, and learning conditions in educational settings. To effectively address these objectives, there is a need to characterize the ‘business as usual’ for the development and implementation of pragmatic interventions that leverage continuous smart monitoring and emerging technologies, including AI, in line with the EduclimAir project goals for educational settings.
1.1. The EduClimAir Project
This study is part of the Artificial Intelligence Tools for Improved Indoor Environmental Quality in School Buildings project, EduClimAir. The EduClimAir project aims to improve IAQ in SBs in the central region of Portugal (RCP). It focuses on optimizing indoor air quality by introducing a resilient ventilation mode for exceptional critical situations, seeking the best balance between energy consumption and environmental comfort [31]. The project conducted at the University of Coimbra is not limited to IAQ but overall IEQ in school buildings, with results that align with the RIS3 objectives (Research and Innovation Strategies for Smart Specialization strategy) for the RCP and SDGs (Sustainable Development Goals) 3, 7, and 11, with monitoring systems set up in three locations at the Department of Mechanical Engineering at the University of Coimbra, Polo II campus (DEM-FCTUC), during the previously concluded 3SqAir project [32]. The monitored locations include two classrooms, including room 3.3, which is mechanically ventilated, and room 6.3, which is naturally ventilated, and a corridor with outdoor-air circulation. The monitoring system collects data for carbon dioxide (CO2), volatile organic compounds (VOCs), formaldehyde, nitrogen dioxide (NO2), and particulate matter (PM10, PM4, PM2.5, PM1) to characterize air quality, and then air temperature and relative humidity (RH) data to describe thermal comfort conditions, while sound pressure level and illuminance were also measured to characterize acoustic and visual indoor conditions. Preliminary results on indoor climate quality were adequately reported by Ogundiran et al. [33]. This study primarily focuses on indoor acoustic conditions, based on monitoring and evaluation of Leq10min in rooms 3.3 and 6.3 during the first semester. An analysis of Leq in two phases, during occupancy and non-occupancy, is presented, highlighting differences in sound equivalent levels due to occupancy and the varying ventilation systems in use. Moreover, a combined analysis of the noise level indicator Leq10min and other human-occupancy-related indoor environmental parameters (air temperature, relative humidity, CO2, VOCs, and PM concentrations) has been conducted. Acoustic and energy management gaps have been identified, and provisional recommendations have been suggested for approval and implementation within the EduClimAir framework, while monitoring continues at an IEQ living lab at the DEM-FCTUC [34].
1.2. Research Contribution and Article Structure
This study contributes to the existing body of work on noise and acoustic comfort requirements in SBs by investigating sound equivalent levels in two classrooms with different ventilation types and their influence on classroom acoustics. The study provides further insight into long-term noise-level assessments in classrooms during both unoccupied and occupied periods, highlighting energy management gaps during non-occupancy. In addition, the study explores the unique and interesting interactions between noise level and other IEQ parameters during a specific occupancy period and the possible influence of these interactions on occupants’ perception. With a continuous monitoring approach, the impact of the implemented recommendations can be analyzed alongside a subjective survey to enable real-time progress monitoring. This work is a key part of a comprehensive study aimed at improving IEQ in school buildings by developing sustainable interventions, including the integration of artificial intelligence (AI) solutions to address IEQ gaps, within the framework and defined objectives of the EduClimAir Project. The study is divided into five Sections. Section 1 serves as the introduction, and Section 2 describes the materials and methods used in the study, including a detailed description of the classrooms evaluated and their locations. Section 3 presents the results, in which the time evolutions of the monitored environmental variables are reported for occupied and unoccupied periods, and the discussion section is in Section 4. Section 5 concludes the study and recaps the findings, including gaps and future work.
2. Materials and Methods
2.1. Case Study Area
The IEQ living lab at DEM-FCTUC was used for this study. The DEM-FCTUC is one of the buildings at the Polo II campus of the University of Coimbra, built in 1995. It comprises classrooms, offices, meeting rooms, laboratories, administrative rooms, a library, a cafeteria/bar, and a parking lot, with an estimated occupancy of about 1000 students, 100 teachers and researchers, and 10 administrative and nontechnical workers. It covers 7000 m2. Within the didactic block, two classrooms (rooms 3.3 and 6.3) and one corridor on the first floor are the monitored areas. The classrooms were selected for monitoring for the following reasons;
- Both classrooms match the typical classroom conditions found across the didactic block with practical access and minimal disruption to monitoring activities.
- Both classrooms reflect the dominant classroom typology found at the DEM-FCTUC in terms of floor area and layout, volume, orientation, lighting, external exposure, and classroom arrangement. Room 3.3 reflects the typical size of the smaller classroom stock found on the ground floor, while room 6.3 reflects the typical size of the larger classrooms on the first floor.
- The classrooms operate with different ventilation types, mechanical or natural ventilation, either of which is found in most classrooms at the DEM-FCTUC.
Given their physical and operational alignment with most classrooms, they are considered representatives of the classroom stock. Figure 1 shows an aerial view of the DEM-FCTUC location, with the red arrow pointing towards the monitored area in the didactic block.
Figure 1.
Aerial view of DEM-FCTUC at Polo II with the red arrow pointing at the monitored area.
2.1.1. Room 3.3
This is a classroom located on the ground floor of the didactic block, with an area of 42 m2, measuring 6.5 m by 6.5 m. It has a west-facing entrance door and five windows on the east facade. Room 3.3 has a total glazed area of 8 m2. It uses a mechanical ventilation system and an all-air heating, ventilation, and air conditioning (HVAC) System. Figure 2a shows room 3.3.
Figure 2.
Monitored rooms (a) 3.3, (b) 6.3.
2.1.2. Room 6.3
This classroom is located on the first floor of the didactic block, measuring 60 m2 (6 m by 10 m). It has a west-facing entrance door and an east-facing window façade with four windows. It has a total glazed area of 10 m2. In room 6.3, cooling is assured by a total recirculation HVAC split system and heating by warm-water radiators supplied by a centralized natural-gas boiler. The space is ventilated naturally through windows and/or door openings. Figure 2b shows room 6.3 and the windows facing the east façade of the building.
2.1.3. Monitored Corridor
A cluster corridor area on the first floor of the didactic block is also monitored. This corridor features a semi-open architectural design, allowing it to be open to the outdoor environment. Room 6.3 opens in this corridor. Figure 3a,b show the monitored corridor on the first floor.
Figure 3.
(a,b) The monitored corridor from different views.
2.1.4. External Environment of Monitored Zones
The monitored zones are located in the east wing of the DEM-FCTUC building, as highlighted by a red rectangle in Figure 4a. This side of the building is bordered by 3 access roads leading into and through the Polo II campus. Road 1 and Road 3, as highlighted in Figure 4a, pass through the front and back of the DEM-FCTUC building, respectively. Due to the low traffic density along 1 and 3, road traffic noise infiltration from these two sources is minimal. Additionally, their distance from the monitored zone reduces external noise exposure in the classrooms being monitored. On the other hand, Road 2 is closer to the monitored zone, exposing the rooms to environmental noise because the windows of both classrooms open onto this road, as seen in Figure 4b. Although it is not a high-density traffic route, its topography is slightly sloping, and it is part of the Municipal Urban Transport Services of Coimbra (SMTUC) bus route. It is also an access route for a few construction-heavy vehicles, such as Tipper trucks, delivering supplies to ongoing building sites.
Figure 4.
The DEM-FCTUC. (a) Aerial view and surrounding roads 1, 2, 3 highlighted in red across, while the red rectangle is the monitored zone. (b) East facade of monitored rooms.
2.2. Methods
The study used objective measurement methods to assess room conditions. Field monitoring of the corridor and rooms was carried out. To characterize IAQ, the concentrations of carbon dioxide (CO2), volatile organic compounds (VOC), formaldehyde (HCHO), nitrogen dioxide (NO2), and particulate matter (PM10, PM4, PM2.5, and PM1) were measured. Thermal comfort conditions were assessed using air temperature (Ta) and relative humidity (RH). For acoustic and visual conditions, sound equivalent level and illuminance were measured. All measured parameters were collected at 10 min intervals. In addition, outdoor weather data, including air temperature, wind speed and direction, precipitation, relative humidity, solar radiation, etc., were collected using a weather station mounted on the DEM-FCTUC premises.
2.2.1. Experimental Setup
Two types of monitoring devices were used: the Catie IEQ station box and the GreenMe cube. The Catie IEQ box was developed by CATIE—Center Aquitain des Technologies de l’Information et Electroniques, Talence, France (https://www.catie.fr/en/home/, accessed on 3 December 2025). The Catie IEQ box is well described in [33]. It collects data for Ta, RH, CO2, and PM using built-in sensors such as Zest_sensor_P-T-RH, Zest_sensor_CO2, and Zest_sensor_Dust. Four Catie boxes were installed in the 3 locations as measurement_system_5–8. Figure 5a shows a Catie IEQ box used.
Figure 5.
(a) Catie box, (b) GreenMe cube.
The GreenMe cube is the second device, developed by a French startup company (GreenMe, Paris, France), as shown in Figure 5b. It is a Rubik’s Cube-looking device that measures approximately 10 environmental parameters, including sound pressure. Two GreenMe cubes, identified as Cube_42 and Cube_35, were used alone in rooms 3.3 and 6.3. This study focuses on Leq measured from the GreenMe cubes.
A Supervisory Control and Data Acquisition (SCADA) control system was employed for both supervision and visualization of the monitoring system. For outdoor weather measurements, Vantage Pro2™ (6152, 6153) and Vantage Pro2™ Plus (6162, 6163) Wireless Weather Stations by Davis Instruments, Hayward, CA, USA (www.davisinstruments.com accessed on 10 February 2026), were used.
The calibration and quality assurance/quality control (QA/QC) test was conducted on the sensors [33], yielding the following R2 values: 0.88–0.93 for PM10, 0.91–0.94 for PM2.5, and 0.94–0.98 for CO2. And the sensor’s cost-to-quality ratio was also confirmed satisfactory.
The SPL was measured as A-weighted equivalent continuous sound level over a 10 min step, as used in [35], allowing for the values of LAeq_10mins (dBA). The LAeq during the school teaching period, LAeq_Work_P, is evaluated using Equation (2), derived from Equation (1), for the case where a continuous analog signal is converted to a discrete one via the data acquisition system’s sampling procedure. The LAeq_Work_P is defined broadly based on the teaching schedules of the monitored classrooms, covering the period from 8:00 to 20:00.
where
- LA(t) is the instantaneous A-weighted sound level in dB at time t
- T is the total measurement duration
Alternatively, with a sampling time step of 10 min, Equation (1) can be written as:
where N is the number of samples, and LA,i is the A-weighted sound level for the i-th 10 min interval, where i = index of the intervals. LAeq_Work_P replaces LAeq in Equation (2) to estimate the sound equivalent levels in the day (8–20 h).
To validate the acceptability of LAeq_10mins (dBA) readings obtained from the installed long-term monitoring devices, Cubes 35 and 42, a verification test was conducted using a calibrated Class II sound meter, the Trotec SL400 (Trotec GmbH, Heinsberg, Germany), as the reference device. The reference device was verified using the sound level calibrator 8930 (IEC 60942:2018 class II standard) by AZ Instrument Corp. (Taichung City, Taiwan). Moreover, an ISO-TECH (SLM-1353, TES Electrical Electronic Corp., Taipei City, Taiwan) integrating a sound level meter was employed to validate the accuracy of the installed GreenMe cube alongside the Trotec SL400, as shown in Figure A1. The aim is to evaluate the accuracy and reliability of the installed cubes by comparing their measurements with those of the calibrated reference device operating under similar classroom conditions.
The Trotec SL400 was placed side-by-side with Cube 42 in room 3.3 when the room was unoccupied, with the door and windows closed during a regular school day. The test was conducted for about 90 min, with both devices taking readings simultaneously. The reference device (Trotec SL400) was set to a 1 s sampling rate and a sound level range of 30 to 130 dBA in slow mode, while the installed device sampled at 10 min intervals. A Floor Fan placed on a desk about 1 m away from the monitoring systems was utilized as a constant noise source for about 30 min in the room. The reading from the reference device, collected at 1 s A-weighted SPL, is then computed to a 10 min LAeq interval and compared with the LAeq_10mins from the installed long-term device to assess their agreement using linear regression and root mean square error (RMSE). Upon calibration, correction, and verification, an acceptable value of R2 = 0.9921 and RMSE = 1.27, with a combined standard uncertainty of 1.45 dB and an expanded uncertainty of ±2.9 dB at a 95% confidence level, was obtained.
2.2.2. Sensor Placements
To ensure comprehensive monitoring, 6 measuring stations were deployed across the monitored areas. They were strategically positioned to capture environmental parameters at the front and back of the classrooms. In room 3.3, two stations were deployed. One Catie IEQ box, Measurement_system_7 (M_s_7), is placed at the back of the classroom beside the cabinet at a height of 1 m. One GreenMe cube, Cube_42, is placed on the lecturer’s desk in front of the classroom at 0.73 m from the floor. Figure A2a shows the layout of room 3.3 and sensor placement. The rectangular black box labeled 1 is Cube_42, while M_s_7 is labeled 2. Given the size of room 6.3, three stations were deployed, including two Catie IEQ boxes—Measurement_system_5 (M_s_5), placed in front of the classroom at a height of 1 m, and Measurement_system_6 (M_s_6), placed at the back of the classroom beside the cabinet at a similar height. One GreenMe cube, Cube_35, is also placed on the lecturer’s desk in front of the classroom at a height of about 0.73 m. Figure A2b shows the room layout for room 6.3. The black rectangular boxes labeled 1, 2, and 3 are monitoring devices. M_s_5 is labeled 1, M_s_6 is 3, while Cube_35 is labeled 2. Finally, Measurement_system_8 was placed 3 m above the ground in the measured corridor.
The monitoring systems were installed in June 2022, and continuous data monitoring has been ongoing since that time.
2.3. Study Campaign Period
This study evaluated the Leq10min data measured during the first semester of the academic session. Teaching activities for the first semester started on 12 September until 17 December [36]. Representative periods have been selected within the semester to characterize sound equivalent levels in the measured rooms during occupancy and non-occupancy periods. The occupancy period is between 8:00 and 20:00 during the weekday, which broadly matches the teaching activity period based on the timetable. Similarly, the unoccupied period is defined within the same timeframe but without teaching activity. Information regarding the occupancy level in each class session was recorded and collected via the marked online attendance register after class. This information is extracted and saved against the lesson time in a Microsoft Excel sheet document (Microsoft Excel version 2606, build 20131.20126).
3. Results
The results are presented for two time periods. The first phase is 4–17 September. This is one week before school resumption, the period of non-occupancy, and one week during teaching activities, the period of occupancy. The second phase is 11–25 December. This includes one week of classroom activities as the occupancy period and one week during the Christmas break as a non-occupancy period. These periods were selected as representative periods for the following reasons:
- They both present a unique opportunity to show both periods of occupancy and non-occupancy in a continuous format.
- These periods also present an opportunity to analyze sound equivalent levels in the classrooms during different weather conditions. The average daily outdoor temperature in September is about 23 °C, while in December it is about 16 °C.
The one-week period used to characterize each of the periods (occupied and non-occupied) allows for obtaining a good number of samples to reduce the influence of the sampling strategy (time step of 10 min) on the uncertainty of LAeq [37].
3.1. First Phase
Given that the first week was a pre-resumption week, the classroom doors and windows are expected to be shut, and the lighting and HVAC systems are expected to be off. On the other hand, during teaching activities, HVAC systems and other utilities are expected to be turned on as required or on a preset schedule. The LAeq_10mins is plotted against date (mm-dd). The CO2 concentration is also shown on the graph as an indicator of human presence in the classrooms.
In Figure 6a,b, the gray continuous line represents LAeq_10mins, the black horizontal lines represent the average sound equivalent level during the daily working period (LAeq_Work_P), and the brown continuous line indicates CO2 concentration evolution during the day, intended for teaching activities. The low CO2 level from 4 to 11 September suggests the absence of occupants in the classrooms; a temporal rise in CO2 is a good indicator of occupancy [38]. During occupied periods after resumption, CO2 concentration had daily peaks up to 2500 ppm. During non-occupancy in room 3.3, the noise average during the working period, LAeq_Work_P, is mostly within the ≤35 dBA WHO/ANSI S12.60 limit [39], while it is mainly between 35 and 37 dBA in room 6.3. On 5 September, LAeq_Work_P was unusually above 45 dBA in both rooms. During occupancy days, LAeq_Work_P ranges from 50 to 60 dBA in room 3.3 and from 50 to 65 dBA in room 6.3. The presence of occupants tends to add 15–25 dBA to the sound equivalent levels in room 3.3 and 15–30 dBA in room 6.3. This difference is consistent with the fact that room 6.3 has twice the capacity of room 3.3. In addition, we observe that on days with higher CO2 concentrations (>1200 ppm), the maximum LAeq_10mins is generally 5–10 dBA higher than on days with lower CO2 concentrations, particularly in Figure 6b. This is also reflected in the LAeq_Work_P, where days with higher CO2 have higher mean noise levels, highlighting the influence of occupants and occupancy density on noise levels.
Figure 6.
LAeq_10mins, LAeq_Work_P, and CO2 in September. (a) Room 3.3, (b) room 6.3.
3.2. The Second Phase
The second phase in December comprises the final teaching week from 11 to 17 December, followed by a one-week Christmas holiday with no occupancy from 18 to 25 December, as shown in Figure 7 below.
Figure 7.
LAeq_10mins, LAeq_Work_P, and CO2 in December. (a) Room 3.3, (b) room 6.3.
3.3. Statistical Analysis
Simple descriptive statistics and Analysis of Variance (ANOVA) using the built-in Microsoft Excel Analysis ToolPak (Microsoft Excel version 2606, build 20131.20126) have been employed to assess the statistical significance of acoustic parameters derived from physical measurements in the two rooms. The descriptive statistic is first used to characterize the distribution and variability of the data. To understand the effect of occupancy on the noise level and its interaction across phases, two independent variables, Period (occupied vs. unoccupied) and Phase (September vs. December), have been chosen. A two-factor ANOVA with replication is selected to estimate the main effects within variables and the interaction across variables. To reduce the effect of autocorrelation that may be inherent in the raw noise data, the daily average values are used. This method assumes independence in daily averages, while limiting the sample count to 5 for each period.
The descriptive statistics for the noise level measurements in room 3.3, as shown in Table A1a, show a higher mean noise level in the occupied condition than in the unoccupied condition. They also reveal a greater occupancy-related increase in September than in December (September: occupied mean = 55.4, median = 55.8, SD = 2.2, and unoccupied mean = 37.3, median = 34.8, SD = 6.1, n = 5), (December: occupied mean = 49.3, median = 47.3, SD = 3.8, and unoccupied mean = 42.9, median = 42.4, SD = 1.3, n = 5).
In Table 1, no significant main effect of the phase (Sept vs. Dec) was observed on the daily noise level based on the data samples used. There was a significant main effect with occupancy, with p-value = 2.28 × 10−6 and F(1, 16) = 51.223, indicating that noise levels differed between occupied and unoccupied days. Also, the interaction between phase and occupancy is significant, with p-value = 0.00329 and F(1, 16) = 11.910, implying that the degree of noise-level difference between occupied and unoccupied days depended on the phase. The mean difference between occupied and unoccupied in September, 18.14, is higher than the mean difference in December, 6.33.
Table 1.
Anova: Two-factor with replication of noise measurements in room 3.3 for September and December during occupied and unoccupied periods.
Descriptive statistics for the noise level measurement in room 6.3, as shown in Table A1b, also reveal higher mean noise levels during the occupied period and a higher occupancy-related increase in September than in December. The mean noise difference in September is 18.8 and 14.6 in December (September: occupied mean = 57.4, SD = 4.3, and unoccupied mean = 38.6, SD = 4.7, n = 5), (December: occupied mean = 55.2, SD = 1.7, and unoccupied mean = 40.6, SD = 2.7, n = 5).
In room 6.3, as presented in Table 2, no significant main effect of the phase (Sept vs. Dec) was observed on the daily noise level, based on the data samples but a significant main effect of occupancy was found (p = 1.42 × 10−8; F(1, 16) = 109.913), indicating that noise levels differed between occupied and unoccupied days. The interaction between phase and occupancy is not significant, suggesting that the magnitude of the noise-level difference between the occupied and unoccupied days did not differ between phases (p-value = 0.208; F(1, 16) = 1.723).
Table 2.
ANOVA: Two-factor with replication of noise measurements in room 6.3 for September and December during occupied and unoccupied periods.
Notably, the descriptive statistical evaluation of the LAeq for non-occupancy periods in room 3.3 versus 6.3 suggests slightly higher penetration of exterior noise, perhaps due to the larger glazed area facing the road, which has inclined topography (impacting the propagation of ambient traffic noise), positioning room 3.3 in a more shielded position from the traffic noise. Moreover, several studies have highlighted the risks of poor IAQ and noise associated with classrooms located near roads [40,41]. Within the scope of this study, indoor–outdoor relationships for IEQ parameters are not primary but are important to consider, since we are evaluating classrooms at a tertiary institution. Elevated noise levels can impair speech intelligibility [42], while myriad health risks, including hearing loss, performance, and comfort among students/teachers, have been linked to exposure to poor IEQ due to adverse ambient outdoor conditions.
4. Discussion
The results presented above are the findings on the sound equivalent levels in each room, observed during occupancy and non-occupancy periods in warm (September) and cool (December) conditions. During non-occupancy before school resumption, the objective is to obtain representative background sound levels with windows shut and HVAC systems not in use. This is to help characterize the indoor acoustic conditions in each room [43] and to identify potential gaps before occupation.
4.1. First and Second Phases
In the first phase, before didactic activities began, the results show sound equivalent levels are minimal in both rooms. Notably, on Monday, 5 September, the noise average, LAeq_Work_P, rose to about 47 dBA in each room. The SPL profile suggests a transient noise event, possibly from an external source, as both rooms have windows facing the building’s east facade. Aside from this, LAeq_Work_P in room 3.3 remained ≤35 dBA, an expected level for an unoccupied classroom and a good learning environment [44]. Background noise is slightly higher in room 6.3; LAeq_Work_P exceeded the recommended ≤35 dBA by at least 2 dBA on a few occasions. Although the difference in background noise between the rooms is slight, an instructor in room 6.3 may respond to this difference by speaking with a slightly higher voice compared to in room 3.3 [45]. In situations with higher background noise, teachers or instructors are at greater risk of vocal fatigue [46,47]. As this is during non-occupancy, the noise level reflects conditions with no operational equipment, ventilation, or HVAC systems running in the rooms. During occupancy, the measured SPL is higher due to noise generated from students and teaching activities, working HVAC system noise, and noise infiltration from external sources. Room 3.3 uses a mechanical ventilation system with an all-air HVAC system, while room 6.3 uses a natural ventilation system, a total-recirculation HVAC split system, and a heating system based on warm-water radiators supplied by a central natural-gas boiler. These systems contribute operational noise to each classroom [40,41], and it is typically part of the background noise during occupancy periods. In room 3.3, LAeq_Work_P is between 50 and 60 dBA, and 50 and 65 dBA in room 6.3. As mentioned earlier, the estimated LAeq_Work_P will include background noise during occupancy, classroom activity noise, the instructor’s voice, and other external sources. With LAeq_Work_P ranging from 50 to 60 and 50 to 65 dBA in the rooms, these are not optimal levels of a learning environment, as a decline in learning efficiency is observed when SPL exceeds 50 dBA [48]. The adequacy of the acoustic conditions will depend on the Signal-to-Noise ratio (SNR), the instructor’s speech level relative to the background noise [49]. SNR should be +15 dB for effective communication [50,51]. For each corresponding day, LAeq_Work_P is higher in room 6.3 than in room 3.3, except on Friday. Classroom size and occupancy density also influence the sound equivalent levels. Average classroom occupancy density during the first week of teaching activities was about 33% in room 3.3 and about 30% in room 6.3. To better understand the interactions among noise level, occupancy, and other parameters, a cursory evaluation of a day of occupancy data was conducted.
In the second phase, during the classroom activity period, the noise average, LAeq_Work_P, is 45–55 dBA in room 3.3 and 52–57 dBA in room 6.3. Like the occupied week in September, LAeq_Work_P is higher in room 6.3 than in room 3.3. Comparing the acoustic conditions in September and December, we observe that sound equivalent levels are higher in September; this was also seen from the statistical analysis of measured parameters in both rooms. Occupancy data also revealed that occupancy density was far lower in December, with some days recording just one student during classroom activity, especially in room 3.3. The low occupancy is also reflected in the CO2 profile during the occupancy period, as shown in Figure 7a,b. During the Christmas holiday, beginning on 17 December, LAeq_Work_P values were higher than expected in both rooms. In room 3.3, the estimated LAeq_Work_P is 34–49 dBA until 24–25 December and above 42 dBA on every weekday during the holiday period. The LAeq_10mins profile in Figure 7a describes a nearly even elevation for weekdays. In room 6.3, the LAeq_Work_P is also slightly elevated, at 36–45 dBA; specifically, during weekdays, noise levels remained at 38–45 dBA. Similarly, the LAeq_10mins profile in Figure 7b appears to be from a continuous noise source rather than a transient noise event. Compared to September, when LAeq_Work_P during non-occupancy was ≤35 (±2) dBA, values of >40 dBA suggest an additional noise source in the rooms, especially in 3.3, with days such as 17 and 18 December, with LAeq_Work_P as high as 49 dBA. These elevated sound equivalent levels during the Christmas break are consistent with HVAC systems being operational in the absence of occupants. The SCADA control system for monitoring HVAC in the rooms is usually programmed with specific settings and timing for the academic year. This monitors and controls the on/off times of the HVAC systems and other units in the building. Careful observation of the SCADA system revealed a gap in the settings that may not have accounted for the Christmas break as a period without teaching activities. This suggests the HVAC and ventilating systems had continued to run during the day, as though regular classroom activities were ongoing, accounting for the elevated background noise in the studied rooms. The above findings reveal potential gaps in system monitoring and energy management aimed at ensuring adequate IEQ. Further investigation is required to characterize its prevalence and determine whether it is a one-off or a recurring situation. Upon confirmation, its scale and impact on energy use and cost can be evaluated.
Given that the evaluated LAeq_Work_P during the occupied period in both rooms includes speech level during the class and other noise sources, noise levels in the rooms are within the range found in university classrooms from other studies [52,53]. Although the observed conditions were less than optimal, the noise levels appear generally tolerable for university settings. However, risks remain, considering the exposure of students who may have hearing impairments [54], for whom continual exposure could adversely affect their performance [52]. The higher noise level observed in room 6.3 may be associated with classroom capacity, the number of students, and external noise infiltration, given its use of natural ventilation, where windows are more likely to be opened to improve air quality. Notably, a limitation of the study was that the opening and closing of windows/doors were left to occupants’ discretion and were outside this study’s scope. During the unoccupied period in December, background noise is higher in room 3.3 than in 6.3 due to possible additional noise contribution from the mechanical ventilation system in the room, as in some cases, augmented background noise has been linked to the use of mechanical ventilation systems [55]. As both rooms have windows opening towards a road, the influence of environmental noise [56] is assumed to be similar and also minimal, given the low-density traffic and the DEM-FCTUC’s countryside location.
4.2. Sound Equivalent Levels and Other IEQ Parameters in the Rooms During Occupancy
Room 3.3 has a seating capacity of 30 people over a usable area of 42 m2, while room 6.3 has a seating capacity of 60 people over a usable area of 60 m2. For the analyzed period, the average weekly occupancy density is below 40% in each room. Figure 8a,b and Figure 9a,b present graphical representations of the interaction among the noise thermal comfort parameters as measured by the integrated monitoring devices. Figure 8a,b show the IEQ parameters for both rooms during 4–17 September under occupied and unoccupied conditions, while Figure 9a,b show the 11–25 December period under the same conditions. The LAeq_10mins is the gray line; LAeq_occupied_period is the black line; Ta is the red line; and RH is the blue line.
Figure 8.
Noise level interaction with thermal comfort parameters in both rooms in the first phase (a) room 3.3 (b) room 6.3.
Figure 9.
Noise level interaction with thermal comfort parameters in both rooms in the second phase (a) room 3.3 (b) room 6.3.
In September, occupied periods in both classrooms, as shown in Figure 8a,b, show distinct increases in LAeq_10mins, reflecting teaching activities, student movement, and verbal communication. These LAeq_10mins peaks coincide mostly with periods when indoor air temperature (Ta) rises above background levels, indicating the combined influence of occupancy and metabolic heat gains. Simultaneously, RH tends to fluctuate inversely with Ta, a common indoor response in which warmer air reduces RH despite moisture generation from occupants. Room 3.3 appears to exhibit stronger daytime variability in both noise and thermal conditions. LAeq_10mins variations during occupied periods are more pronounced, suggesting greater acoustic activity or reduced sound attenuation. The concurrent increase in temperature indicates limited dilution of occupant-generated heat. These conditions may contribute to reduced acoustic comfort and increased cognitive fatigue, particularly when elevated noise persists during teaching periods. Room 6.3 showed similar occupancy signatures but with comparatively smoother Ta and RH profiles. This suggests either a lower occupancy density, better ventilation effectiveness, or a more stable thermal environment. The weaker coupling between noise peaks and thermal excursions suggests that the studied classroom is acoustically active without experiencing equivalent thermal loading.
During December, as shown in Figure 9a,b, lower ambient temperatures alter the relationship among the parameters. Occupied periods continue to generate clear noise peaks in both classrooms, confirming that classroom activity remains the dominant driver of acoustic conditions. However, temperature variations appear less pronounced than in September, likely due to heating control and lower outdoor temperatures limiting daily thermal amplitudes. RH generally increases during cooler periods and is more stable than in September. In occupied intervals, modest temperature rises are again accompanied by slight decreases in relative humidity, maintaining the expected inverse relationship between the two variables. The most notable observation in December is the persistence of elevated noise events without corresponding large thermal responses. This divergence suggests that acoustic stressors can remain significant even when thermal conditions are relatively acceptable. Considering IEQ, satisfactory temperature control does not necessarily imply good overall environmental quality if noise exposure remains high. Additionally, although the effects of seasonality are not a primary concern of the current study, the correlational analyses highlight variability that warrants further assessment, especially for other IAQ and thermal comfort parameters in the classroom, given that the studied living lab employed continuous monitoring campaigns.
Meanwhile, across both phases and classrooms, noise is the parameter most directly linked to occupancy, while temperature and humidity respond more gradually. The strongest correlation observed is between occupancy-related noise peaks and temperature increases, indicating that human presence is a common driver. RH generally exhibits an inverse relationship with temperature rather than a direct relationship with noise. Comparatively, room 3.3 appears more sensitive to occupancy effects, as evidenced by higher variability and larger simultaneous fluctuations in noise and thermal conditions. Room 6.3 demonstrates greater stability in IEQ conditions, particularly in temperature and humidity.
Moreover, in terms of health and well-being, recurrently elevated noise levels pose a primary concern. Sustained classroom noise can impair speech intelligibility, concentration, learning performance, and perceived comfort [57]. When noise coincides with elevated temperatures, the combined burden may further increase discomfort and cognitive fatigue. Conversely, given that RH levels showed less variability in both classrooms (within 40–80%), being near the optimal range of 40–60% helps deactivate airborne viruses [58], suggesting a lower risk of IAQ and moisture-related health concerns during the monitored periods. Overall, noise level management appears to be the key priority for improving IEQ, with a better chance of improved productivity and performance, given the risk of long-term exposure for teachers and students in classrooms.
Finally, concerning noise and the main IAQ parameters surveyed, a cursory evaluation of a selected day in October has been presented and analyzed, highlighting critical findings and discussions. Figure 10 below shows a visualization of the interactions between sound equivalent levels and other IEQ parameters during occupancy on 12 October, over the course of one day within the semester.
Figure 10.
Noise level interaction with (a) Temp, RH, (b) CO2, (c) PM2.5, and PM10 in room 3.3 in one day.
Indoor air temperature (Ta), RH, CO2, PM2.5, and PM10 in room 3.3 on 12 October are shown in Figure 10a–c. The chart shows occupied and unoccupied periods, with occupied periods characterized by rising CO2 concentration. The legends for LAeq_10mins, LAeq_occupied_period, Ta, and RH are as previously used, while CO2 is the brown continuous line; PM2.5 and PM10 are the broken brown line and orange dotted line, respectively. Didactic activities included two class sessions with varying occupancy density. Occupancy density during the first period is about 30%, with nine students in class. LAeq_occupied_period is 63 dBA for the entire occupied period. As shown in Figure 10a, Ta rises gradually after an initial drop in temperature; a similar trend is shown on the RH profile. When the temperature rose to about 25 °C, we observed a negative correlation between Ta and RH throughout the occupancy period. As expected, CO2 builds up slowly, likely due to low occupancy and ventilation; see Figure 10b. A drop in LAeq_10mins during a short break or class transition is observed in the CO2 and Ta profiles, without an observable influence on RH. During the second class period, we observed faster CO2 buildup, including Ta, as occupancy increased to 19 students. RH decreases with increasing Ta during this period, approaching 25 °C. At the end of the class, CO2 temporal decay occurs, with a corresponding drop in noise levels and Ta. RH appears fairly stable outside the occupation period. At the end of the day, most parameters return to pre-occupation levels. For PM, as shown in Figure 10c, there is a rise in PM10 levels, with a more gradual rise in PM2.5. The initial high PM10 displacement, linked to door opening and students’ entry to the room, is replaced by smaller undulations found in the PM2.5 profile. With fewer activities during the first period since there were only nine occupants, both particles exhibit similar small displacements. At the beginning of the second class, a large PM10 displacement appears before returning to a uniform undulation. PM2.5 particles appear less affected by increased occupancy or other activities in the room, reinforcing the suggestion that smaller particles are less affected by occupancy than larger particles [59]. The infiltration, settlement, and resuspension of these particles appear to be influenced by several environmental factors, including outdoor sources [60,61].
Similarly, Figure 11a–c show what happened in the naturally ventilated room 6.3 on the same day. During the first class, occupancy density was 45%, with about 27 students. We notice LAeq_10mins begins to rise from 7 am, and by 8 am, it is nearly 60 dBA. The LAeq_occupied_period is 62 dBA. Indoor temperature rises quickly to about 24 °C, and CO2 rises to 2200 ppm. We also see an initial rise in RH, followed by a fairly stable level as Ta exceeded 23 °C. A short break or class transition is observed, characterized by a temporal decay in CO2, and during this period, LAeq_10mins drops by 10 dBA; a similar trend is seen in the Ta profile. During the next class, occupancy density is reduced to 28% with 17 students. LAeq_10mins rises again to the previous levels, and Ta gradually rises above 25 °C, while CO2 levels rise above 3000 ppm. RH also rises in this period. A moderate-to-strong positive correlation is observed between RH and Ta (r = 0.77), unlike the relationship observed between Ta and RH in room 3.3 (r = 0.17). A positive correlation (r = 0.9) is also observed between RH and CO2. At the end of the class, Ta and CO2 peaked and declined steadily as expected. For PM2.5 and PM10, before occupancy, both particle sizes were at similar levels and relatively stable; at the beginning of the class, an obvious infiltration and/or resuspension occurred. PM10 particles appear to be more widely distributed and to have higher amplitudes. In the first period, with 27 students, the profiles of both particles were more turbulent, associated with more classroom activities, and the door/window open condition, as the room is naturally ventilated. During the second class with fewer students, PM10 showed more uniform displacement, whereas PM2.5 showed less disturbance. PM10 is significantly more influenced by classroom activities than PM2.5. The highest PM2.5 and PM10 levels were measured outside occupied areas, possibly due to door and/or window openings during cleaning activities.
Figure 11.
Noise level correlation with (a) Temp, RH, (b) CO2, (c) PM2.5 and PM10 in room 6.3 in one day.
4.3. How Does This Impact Occupants’ Comfort?
In room 3.3, the noise average level is about 63 dBA, thermal comfort parameters are: Ta between 21 and 25 °C range with RH between 55 and 61%, while air quality is CO2 < 1300 ppm, PM2.5 at 4–11 μg/m3, and PM10 at 4–22 μg/m3. The ambient PM concentrations are good, as they are within the WHO 24 h average guideline for short-term exposure [62]. Indoor air temperatures are also within the acceptable range [63], while CO2 gradually builds up to 1300 ppm. In room 6.3, the average noise level was about 62 dBA, Ta is 21–26 °C, and RH is 52–60%. PM concentration did not exceed WHO guidelines for short-term exposure averages: PM2.5 is 6–16 μg/m3, PM10 is 8–24 μg/m3, and CO2 is between 500 and 3500 ppm. Although CO2 is not a toxic gas, it is considered a good indicator of air quality degradation in indoor spaces when elevated [64]. At the start of the first class, after initial acclimatization, typically after the first 20 min in the room [65], occupants are less likely to express discomfort regarding the indoor conditions. But during the class, as some IEQ parameters begin to degrade, the perception of the indoor conditions is influenced. A few studies suggest that at indoor temperatures between 20 and 25 °C, occupants’ perception of thermal comfort or thermal sensation is not noticeably affected when sound equivalent levels are ≤65 dBA [66,67]. But at higher temperatures, such as 30 °C, the noise level would have a more noticeable effect on their thermal comfort and thermal sensation perception. As Ta is between 22 and 26 °C, References [66,67] suggest that the average sound equivalent levels in both rooms would have no noticeable effect on the occupants’ thermal comfort perception. On the other hand, the effect of temperature on acoustic perception may be more influenced, as noise is perceived more poorly at lower or higher temperatures [67,68]. Both gender and thermal conditions in the room influence how loudness or annoyance is perceived, even when the noise level is neutral [67]. Therefore, as temperatures rise, occupants’ tendency to perceive 60 dBA sound equivalent levels as annoying increases. In another study, the authors observed that at thermal neutrality (24 °C), occupants find the sound equivalent levels more unpleasant than at 18 or 30 °C, when the room is considered cooler or warmer [69]. Given the temperature ranges recorded in the current study, which are close to thermal neutrality, occupants may be adversely affected by the sound equivalent levels in the rooms studied. In this study, subjective evaluation of noise perception and gender distribution across classes were not considered. To holistically evaluate acoustic comfort in the rooms and its interaction with indoor temperature and other parameters, a subjective sampling of occupants’ perceptions is suggested. A measure of the reverberation time would also offer a better understanding of the acoustic quality and gaps in each room. As observed, the deterioration in air quality in rooms, where CO2 concentrations rise to 3500 ppm, is due to saturation of the human olfactory system. To address this situation, CO2 traffic light sensors have been installed in each room, with a notice on how to properly interpret the signals and the actions to take based on them. The effect of this is currently being evaluated.
This study is a preliminary investigation of the sound equivalent levels in two classrooms with different ventilation systems. Our findings showed that the sound equivalent levels in both rooms during occupancy were moderate and tolerable but not optimal. In the mechanically ventilated room 3.3, average sound equivalent levels (LAeq_Work_P) ranged from 50 to 60 dBA with some infrequent spikes; the acoustic conditions could be interpreted as moderate. While the noise levels in the naturally ventilated room 6.3 are also moderate, they are consistently higher than those in room 3.3. The average sound equivalent levels were 50–65 dBA, and in a higher-learning environment, these levels are tolerable. The higher noise levels observed in room 6.3 may be linked to more students in the classroom, a larger glazed area with the possibility of more external noise permeation, etc. Room 6.3 consistently had more students during most of its classroom activities. This may be in relation to its size, as courses with a higher number of registered students tend to be assigned to the classroom with more capacity. In addition, although both classrooms have their windows facing the same direction, the noise impact may vary given the difference in ventilation type. Room 6.3, the naturally ventilated room, may depend more on open window conditions to improve indoor quality, while this increases the possibility of outdoor noise intrusion. Furthermore, both rooms are on different floors; the design and inclination of the road beside the rooms is such that it is more than 30 cm below the surrounding ground level, creating a barrier-like effect at the sides of the road which may obstruct the propagation of sound generated from the road and its effect on the classroom on the lower level while having little to no impact on the sound propagated to the higher-floor classroom, room 6.3. During non-occupancy in December, it was observed that the HVAC system’s monitoring and management may not have been set to adequately account for the Christmas break, as it appeared to be in operation even outside teaching activity days. Furthermore, if the observed condition of continuous operation of the HVAC systems persists in all holidays, which, for the University of Coimbra, spans approximately 23 to 27 days per academic year, including holidays and non-teaching weekdays that interrupt the academic periods, this accounts for about 13–15% of an estimated 160-plus teaching and exam days. Such a situation may result in increased energy consumption and financial repercussions for the institution. Moreover, this study’s findings regarding the interaction between indoor air temperature and occupants’ noise perception suggest the need to bring noise levels to optimal levels. Therefore, acoustic quality and energy management in both rooms can be improved through interventions in each room, especially from statutory sources such as HVAC systems, windows (using soundproofing windows), and wall and surface finishes (incorporating noise dampers). Provisional recommendations are provided for improvements while ongoing monitoring continues.
4.4. Provisional Recommendations
- The revaluation of the SCADA system settings to ensure optimal use of HVAC systems during and outside occupancy in both rooms. The current settings have not appropriately taken into consideration the out-of-school period in December, and possibly Easter break and similar in-between-semester breaks. As commencement dates may vary, these settings should be adjusted at the beginning of each academic year.
- Immediate and routine servicing of HVAC systems to reduce undue operational noise. At the start of the heating season, the operational noise by the heating system based on warm water radiators supplied by a central natural gas boiler in room 6.3 becomes elevated, a situation associated with a long period of non-use or service due. Background operational noise can be kept at a minimal level with timely servicing.
- The implementation of an in-class noise management strategy to minimize noise due to student activities, table and chair movements during occupation or transition. This may include replacing damaged or broken furniture glides or rubber leg dampers on chairs and tables. Applicable to both room 3.3 and room 6.3.
- The installation of some noise-absorbing materials/acoustic panels to help reduce loud noise impact. These acoustic panels can be installed on the walls that are between classrooms. This will help address noise contributions generated from neighboring classrooms.
- The implementation of noise impact awareness and management campaigns to encourage behavioral change, improve noise awareness among students and staff, and address possible difficulties that might be experienced by second-language learners.
- Implementation of classroom noise traffic lights like the already implemented CO2 traffic lights in both rooms. A notice to help interpret the notification on the traffic light will also be installed, including suggested actions to help reduce in-class noise levels.
4.5. Study Limitations
The authors identify and highlight the following limitations of the current study:
- Data from only two classrooms were analyzed and used as representative data for classrooms at the DEM-FCTUC.
- The subjective evaluation of the occupant’s perception was not included in the results of this study; therefore, the conclusions derived from this study are limited to results obtained from physical measurements during the highlighted period.
- Reverberation time and speech transmission index (STI) for evaluated rooms were not included in the results of this study. Although the estimated noise averages obtained from each room throughout the evaluated period did not exceed 65 dBA, a measure of the reverberation time and STI will help reinforce the acceptability of the acoustic conditions of the rooms.
- Given that this is a long-term investigation of indoor environmental quality values in the rooms, the data analyzed were limited to a few weeks within the first semester of an academic year. The limitation of the analyzed period to a timeframe at the beginning and the end of the semester may not have fully described the classroom occupancy pattern in the middle and within the semester, which may have introduced some level of bias to the analyzed data.
A re-evaluation of sound equivalent levels in each room will be carried out after the provisional recommendations are implemented. This will include measuring reverberation time in each room. The results and progress will be duly communicated.
5. Conclusions
This study was conducted as part of the EduClimAir project at the Department of Mechanical Engineering, University of Coimbra, Polo II campus (DEM-FCTUC). Two classrooms were investigated during the first semester of the academic session, across two phases: one mechanically ventilated room (3.3) and one naturally ventilated room (6.3). In each phase, one in September and the other in December, an evaluation of both occupied and non-occupied periods is presented weekly to describe each phase.
Results during the non-occupancy period in the first phase showed that background sound equivalent levels, evaluated during the day (8:00–20:00) (LAeq_Work_P), in room 3.3 are generally within the WHO/ANSI S12.60 limits of ≤35 dBA, while in room 6.3, it was slightly higher, 35–37 dBA. During this period, the HVAC system and other units were turned off because the school was not in session. During occupancy after resumption, average sound equivalent levels (LAeq_Work_P) in room 3.3 were between 50 and 60 dBA, and in room 6.3 were between 50 and 65 dBA for the first phase. And in the second phase, LAeq_Work_P ranged from 45 to 55 dBA in room 3.3 and from 52 to 57 dBA in room 6.3. In summary, sound equivalent levels were higher in September than in December, possibly due to higher occupancy density. While the sound equivalent levels in both rooms appear moderate and tolerable for a university setting, they were consistently higher in room 6.3. This can be linked to a higher average number of students in room 6.3 due to the larger classroom size and capacity. A closer examination of sound equivalent levels over one day and their interactions with other IEQ parameters reveals interdependence among occupancy, thermal comfort, air quality, and acoustic conditions. The interaction between indoor temperature and noise appears to be more notable for this study’s focus.
A significant increase (often >40 dBA) in LAeq_Work_P was observed during non-occupancy in December. Our findings indicate that HVAC systems operate even during school breaks, highlighting a gap in supervisory and management oversight. Further investigation is recommended regarding the HVAC management and controls, as there is potential for energy savings when HVAC systems are used on a need-to-use basis, including opportunities that may extend to other IEQ parameters like lighting. A holistic IEQ and energy assessment can impact the overall energy consumption and costs paradigm in the studied context.
With CO2 concentration rising to about 3500 ppm, CO2 traffic light sensors have been installed in each room, and their effects are currently being evaluated. Noise and energy management in both rooms can be improved with some interventions. Provisional recommendations have been suggested for improvements while ongoing monitoring continues. Subjective evaluations of occupants’ perceptions of sound equivalent levels and other IEQ parameters are required to provide more holistic recommendations for adequate interventions. This study contributes to existing research on classroom noise and uniquely examines the complex interactions among sound equivalent levels, indoor temperature, air quality, and occupancy. Although the study was limited by the lack of a subjective survey on noise perception and an assessment of reverberation time in the rooms, the findings provide insights and “first-aid-like” interventions for education stakeholders to address IEQ gaps in educational building settings. This is part of an ongoing experimental work to improve IEQ in school buildings.
Author Contributions
Conceptualization, J.O., J.-P.K.B.N., J.O.O., H.M. and M.G.d.S.; methodology, J.O. and J.O.O.; validation, J.O., J.O.O. and B.C.; formal analysis, J.O.; investigation, J.O., J.-P.K.B.N., J.O.O. and B.C.; data curation, J.O.; writing—original draft preparation, J.O.; writing—review and editing, J.O., J.-P.K.B.N., J.O.O., B.C., H.M. and M.G.d.S.; visualization, J.O.; supervision, H.M. and M.G.d.S.; project administration M.G.d.S.; funding acquisition, M.G.d.S. All authors have read and agreed to the published version of the manuscript.
Funding
This research was funded in whole or in part by the Fundação para a Ciência e a Tecnologia, I.P. (FCT, https://ror.org/00snfqn58 accessed on 10 February 2025) under Grant (FCT)—IUDB/50022/2025, DOI: https://doi.org/10.54499/UID/50022/2025, LA/P/0079/2020, DOI: https://doi.org/10.54499/LA/P/0079/2020 and EduClimAir (COMPETE) 2030-FEDER-00931400-14662. The author J.O. holds a grant as follows: J.O., grant Ref: 2024.18455.PRT, https://doi.org/10.54499/2024.18455.PRT. For the purpose of Open Access, the author has applied a CC-BY public copyright license to any Author‘s Accepted Manuscript (AAM) version arising from this submission.
Institutional Review Board Statement
Not applicable.
Informed Consent Statement
Not applicable.
Data Availability Statement
The raw data supporting the study are available in Zenodo (https://doi.org/10.5281/zenodo.20539838) with restricted access during peer review; access will be granted to reviewers/editors upon request.
Acknowledgments
This research was funded in part by the Fundação para a Ciência e a Tecnologia, I.P. (FCT) (ROR: https://ror.org/00snfqn58 (accessed on 14 June 2026)) through the projects UID/50022/2025 (DOI: https://doi.org/10.54499/UID/50022/2025), LA/P/0079/2020 (DOI: https://doi.org/10.54499/LA/P/0079/2020), and EduClimAir (COMPETE2030-FEDER-00931400-14662 accessed on 27 February 2026). The main author was supported by the FCT doctoral grant 2024.18455.PRT (DOI: https://doi.org/10.54499/2024.18455.PRT). For the purpose of Open Access, the author has applied a Creative Commons Attribution (CC BY) licence to any Author Accepted Manuscript (AAM) version arising from this submission. This work was also carried out within the framework of the EnviroSense project (Ref. PT0058.A.12.D), funded by the Santander Portugal Foundation under the 6th Edition of the “Seed Projects for Interdisciplinary Research” call promoted by the University of Coimbra. The authors acknowledge the support of the Energy for Sustainability Initiative of the University of Coimbra and ADAI—Associação para o Desenvolvimento da Aerodinâmica Industrial, integrated into the Associate Laboratory of Energy, Transports and Aeronautics (LAETA) (https://ror.org/05gh16g69 accessed on 10 February 2025).
Conflicts of Interest
The authors declare no conflicts of interest.
Abbreviations
The following abbreviations are used in this manuscript:
| ANSI | American National Standards Institute |
| CATIE | Center Aquitain des Technologies de l’Information et Electroniques |
| CO2 | Carbon Dioxide |
| DEM-FCTUC | Department of Mechanical Engineering, University of Coimbra |
| HCHO | Formaldehyde |
| HVAC | Heating, Ventilation, and Air-Conditioning |
| IAQ | Indoor Air Quality |
| IEQ | Indoor Environmental Quality |
| LAeq_Work_P LAeq_occupied_period | Equivalent Continuous Sound Level for the Period 8:00–20:00 (a period meant for teaching activity at the DEM-FCTUC) |
| NO2 | Nitrogen Dioxide |
| PM | Particulate Matter (of different sizes 1, 2.5, 4, and 10 micrograms) |
| QA/QC | Quality Assurance and Quality Control |
| RCP | Central Region of Portugal |
| RH | Relative Humidity |
| RIS3 | Research and Innovation Strategies for Smart Specialization strategy |
| SBs | School Buildings |
| SDGs | Sustainable Development Goals |
| SMTUC | Serviços Municipalizados de Transportes Urbanos de Coimbra |
| SNR | Signal-to-Noise Ratio |
| STI | Speech Transmission Index |
| Ta | Air Temperature |
| VOCs | Volatile Organic Compounds |
| WHO | World Health Organization |
| 3SqAir project | Sustainable Smart Strategy for Air Quality Assurance in Classrooms |
Appendix A
Appendix A.1
Figure A1.
Calibration and verification of acoustic devices.
Appendix A.2
Figure A2.
Layout of classrooms, and the numbers 1, 2, 3 indicate the location of the monitoring devices. (a) Room 3.3, (b) room 6.3.
Appendix A.3
Table A1.
(a) Descriptive statistics of noise data in room 3.3 between September and December. (b) Descriptive statistics of noise data in room 6.3 between September and December.
References
- Yan, S.; Zhang, L.; Liu, Z.; Wang, H. Acoustic Optimization of Classroom Environments Using Oriented Strand Board Panels: Layout Strategy and Simulation Validation. Buildings 2026, 16, 2159. [Google Scholar] [CrossRef] [Scilit]
- Hamida, A.; Zhang, D.; Ortiz, M.A.; Bluyssen, P.M. Indicators and methods for assessing acoustical preferences and needs of students in educational buildings: A review. Appl. Acoust. 2023, 202, 109187. [Google Scholar] [CrossRef] [Scilit]
- Fang, Y.; Luo, X.; Lu, J. A review of research on the impact of the classroom physical environment on schoolchildren’s health. J. Build. Eng. 2023, 65, 105430. [Google Scholar] [CrossRef] [Scilit]
- Mealings, K. The Effect of Classroom Acoustic Treatment on Listening, Learning, and Well-being: A Scoping Review. Acoust. Aust. 2023, 51, 279–291. [Google Scholar] [CrossRef] [Scilit]
- Erickson, L.C.; Newman, R.S. Influences of Background Noise on Infants and Children. Curr. Dir. Psychol. Sci. 2017, 26, 451–457. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- McCreery, R.W.; Stelmachowicz, P.G. The Effects of Limited Bandwidth and Noise on Verbal Processing Time and Word Recall in Normal-Hearing Children. Ear Hear. 2013, 34, 585–591. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- Boman, E.; Enmarker, I. Factors affecting pupils’ noise annoyance in schools: The building and testing of models. Environ. Behav. 2004, 36, 207–228. [Google Scholar] [CrossRef] [Scilit]
- Kjellberg, A.; Landström, U.; Tesarz, M.; Söderberg, L.; Akerlund, E. The Effects of Nonphysical Noise Characteristics, Ongoing Task, and Noise Sensitivity on Annoyance and Distraction Due to Noise at Work. J. Environ. Psychol. 1996, 16, 123–136. [Google Scholar] [CrossRef] [Scilit]
- Ljung, R.; Sörqvist, P.; Kjellberg, A.; Green, A.-M. Poor Listening Conditions Impair Memory for Intelligible Lectures: Implications for Acoustic Classroom Standards. Build. Acoust. 2009, 16, 257–265. [Google Scholar] [CrossRef] [Scilit]
- Klatte, M.; Hellbruelr, J.; Seidel, J.; Leistner, P. Effects of Classroom Acoustics on Performance and Well-Being in Elementary School Children: A Field Study. Environ. Behav. 2017, 42, 659–692. [Google Scholar] [CrossRef] [Scilit]
- Goldschagg, P.; Bekker, T. Effects of Classroom Noise on Learning: Perceptions of Grade 10–12 Girl Learners. Afr. Educ. Rev. 2020, 17, 46–64. [Google Scholar] [CrossRef] [Scilit]
- Baek, K.; Park, C.; Sakong, J. The Impact of Aircraft Noise on the Cognitive Function of Elementary School Students in Korea. Noise Health 2023, 25, 83–91. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- Astolfi, A.; Pellerey, F. Subjective and objective assessment of acoustical and overall environmental quality in secondary school classrooms. J. Acoust. Soc. Am. 2008, 123, 163–173. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- Ljung, R.; Sorqvist, P.; Hygge, S. Effects of road traffic noise and irrelevant speech on children′s reading and mathematical performance. Noise Health 2009, 11, 194–198. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- Zannin, P.H.T.; Engel, M.S.; Fiedler, P.E.K.; Bunn, F. Characterization of environmental noise based on noise measurements, noise mapping and interviews: A case study at a university campus in Brazil. Cities 2013, 31, 317–327. [Google Scholar] [CrossRef] [Scilit]
- Zannin, P.H.T.; Marcon, C.R. Objective and subjective evaluation of the acoustic comfort in classrooms. Appl. Ergon. 2007, 38, 675–680. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- Zhang, B.; Navejar, R. Effects of Ambient Noise on the Measurement of Mathematics Achievement for Urban High School Students. Urban Educ. 2018, 53, 1195–1209. [Google Scholar] [CrossRef] [Scilit]
- Xie, H.; Kang, J.; Tompsett, R. The impacts of environmental noise on the academic achievements of secondary school students in Greater London. Appl. Acoust. 2011, 72, 551–555. [Google Scholar] [CrossRef] [Scilit]
- Sjödin, F.; Kjellberg, A.; Knutsson, A.; Landström, U.; Lindberg, L. Noise exposure and auditory effects on preschool personnel. Noise Health 2012, 14, 72–82. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- Yang, Y.-N.; Zhou, J.; Song, J.-R.; Wang, X.-P.; Xu, X.-H.; Li, Y.-X.; Zeng, J.-C.; Sa, Y.; Jiang, W. Architectural Physical Acoustic Environmental Design Transformation of Academic Lecture Halls in the Universities—Taking the Hall of School of Architecture and Urban Planning of Yunnan University as an Example. Buildings 2024, 14, 1583. [Google Scholar] [CrossRef] [Scilit]
- Seyedrezaei, M.; Awada, M.; Becerik-Gerber, B.; Lucas, G.; Roll, S. Interaction effects of indoor environmental quality factors on cognitive performance and perceived comfort of young adults in open plan offices in North American Mediterranean climate. Build. Environ. 2023, 244, 110743. [Google Scholar] [CrossRef] [Scilit]
- Bourikas, L.; Gauthier, S.; En, N.K.S.; Xiong, P. Effect of thermal, acoustic and air quality perception interactions on the comfort and satisfaction of people in office buildings. Energies 2021, 14, 333. [Google Scholar] [CrossRef] [Scilit]
- Torresin, S.; Albatici, R.; Aletta, F.; Babich, F.; Kang, J. Assessment methods and factors determining positive indoor soundscapes in residential buildings: A systematic review. Sustainability 2019, 11, 5290. [Google Scholar] [CrossRef] [Scilit]
- Lin, D.; Li, T.; Chen, Z.; Li, L. Effects of interactions between thermal and acoustic environments on subjective comfort evaluations in outdoor public spaces. J. Asian Arch. Build. Eng. 2025, 24, 367–382. [Google Scholar] [CrossRef] [Scilit]
- Guan, H.; Hu, S.; Lu, M.; He, M.; Mao, Z.; Liu, G. People’s subjective and physiological responses to the combined thermal-acoustic environments. Build. Environ. 2020, 172, 106709. [Google Scholar] [CrossRef] [Scilit]
- de la Hoz-Torres, M.L.; Aguilar, A.J.; Ruiz, D.P.; Martínez-Aires, M.D. Analysis of impact of natural ventilation strategies in ventilation rates and indoor environmental acoustics using sensor measurement data in educational buildings. Sensors 2021, 21, 6122. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- Ballerini, V.; Coccagna, M.; Bisi, M.; Volta, A.; Droghetti, L.; di Schio, E.R.; Valdiserri, P.; Mazzacane, S. The Role of Mechanical Ventilation in Indoor Air Quality in Schools: An Experimental Comprehensive Analysis. Buildings 2025, 15, 869. [Google Scholar] [CrossRef] [Scilit]
- Al Jumaili, T.; Sabbagh, M. Systematic Review for the Assessment of Indoor Environment Quality Factors and Sub-Indicators of Classrooms. Int. J. Sustain. Dev. Plan. 2024, 19, 3255–3263. [Google Scholar] [CrossRef] [Scilit]
- Brink, H.W.; Loomans, M.G.L.C.; Mobach, M.P.; Kort, H.S.M. A systematic approach to quantify the influence of indoor environmental parameters on students’ perceptions, responses, and short-term academic performance. Indoor Air 2022, 32, e13116. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- Di Loreto, S.; Falone, M.; Pierantozzi, M.; Montelpare, S. Field Measurements of Indoor Environmental Quality in School Buildings Post-COVID-19: Systematic Review. Appl. Sci. 2025, 15, 5692. [Google Scholar] [CrossRef] [Scilit]
- Compete 2030 and EduClimAIr. ‘Artificial Intelligence Tools for Improved Indoor Environmental Quality in School Buildings’. Available online: https://www.compete2030.gov.pt/operacoes/listagem/COMPETE2030-FEDER-00931400/ (accessed on 15 December 2025).
- Interreg Sudoe. ‘3SqAir Project’. Available online: https://www.3sqair.com/ (accessed on 18 March 2026).
- Ogundiran, J.; Nyembwe, J.-P.K.B.; Ogundiran, J.O.; Santos, R.A.d.S.; Pereira, L.D.; da Silva, M.G. 3SqAir Project: A Living Lab Towards Sustainable Smart Strategy for Indoor Climate Quality Assurance in Classrooms. Atmosphere 2025, 16, 584. [Google Scholar] [CrossRef] [Scilit]
- Pereira, L.D.; Carrilho, J.D.; Brito, N.S.; Gomes, M.R.; Mateus, M.; Chenari, B.; da Silva, M.G. Teaching and researching the indoor environment: From traditional experimental techniques towards web-enabled practices. Sustain. Cities Soc. 2016, 26, 543–554. [Google Scholar] [CrossRef] [Scilit]
- Vilcekova, S.; Meciarova, L.; Burdova, E.K.; Katunska, J.; Kosicanova, D.; Doroudiani, S. Indoor environmental quality of classrooms and occupants’ comfort in a special education school in Slovak Republic. Build. Environ. 2017, 120, 29–40. [Google Scholar] [CrossRef] [Scilit]
- University of Coimbra. ‘Academic Calendar’, UC Services and Academic Information. Available online: https://www.uc.pt/en/academicos/regulamentos/calendario (accessed on 6 December 2025).
- Mateus, M.; Carrilho, J.A.D.; da Silva, M.C.G. Assessing the influence of the sampling strategy on the uncertainty of environmental noise measurements through the bootstrap method. Appl. Acoust. 2015, 89, 159–165. [Google Scholar] [CrossRef] [Scilit]
- Franco, A.; Leccese, F. Measurement of CO2 concentration for occupancy estimation in educational buildings with energy efficiency purposes. J. Build. Eng. 2020, 32, 101714. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- Schwela, D.H. The new World Health Organization guidelines for community noise. Noise Control Eng. J. 2001, 49, 193. [Google Scholar] [CrossRef] [Scilit]
- Amato, F.; Rivas, I.; Viana, M.; Moreno, T.; Bouso, L.; Reche, C.; Àlvarez-Pedrerol, M.; Alastuey, A.; Sunyer, J.; Querol, X. Sources of indoor and outdoor PM2.5 concentrations in primary schools. Sci. Total Environ. 2014, 490, 757–765. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- Nyembwe, J.P.K.B.; Takizala, J.F.M.; Muangala, S.K.; Nyembwe, O.K.; Ogundiran, J.O.; da Silva, M.G. Assessment of Indoor Air Quality in Primary School Classrooms: A Case Study in Mbuji Mayi and Lubumbashi, Democratic Republic of Congo. Buildings 2025, 15, 730. [Google Scholar] [CrossRef] [Scilit]
- Murgia, S.; Webster, J.; Cutiva, L.C.C.; Bottalico, P. Systematic Review of Literature on Speech Intelligibility and Classroom Acoustics in Elementary Schools. Lang. Speech Hear. Serv. Sch. 2023, 54, 322–335. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- Tran, M.T.; Wei, W.; Dassonville, C.; Martinsons, C.; Ducruet, P.; Mandin, C.; Héquet, V.; Wargocki, P. Review of Parameters Measured to Characterize Classrooms’ Indoor Environmental Quality. Buildings 2023, 13, 433. [Google Scholar] [CrossRef] [Scilit]
- World Health Organization. ‘Noise’, World Health Organization. Available online: https://www.who.int/europe/news-room/fact-sheets/item/noise (accessed on 2 July 2025).
- Durup, N.; Shield, B.; Dance, S.; Sullivan, R. An Investigation into Relationships between Classroom Acoustic Measurements and Voice Parameters of Teachers. Build. Acoust. 2015, 22, 225–241. [Google Scholar] [CrossRef] [Scilit]
- Kristiansen, J.; Lund, S.P.; Persson, R.; Shibuya, H.; Nielsen, P.M.; Scholz, M. A study of classroom acoustics and school teachers’ noise exposure, voice load and speaking time during teaching, and the effects on vocal and mental fatigue development. Int. Arch. Occup. Environ. Health 2014, 87, 851–860. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- Durup, N.; Shield, B.; Dance, S.; Sullivan, R.; Gomez-Agustina, L. How classroom acoustics affect the vocal load of teachers. Energy Procedia 2015, 78, 3084–3089. [Google Scholar] [CrossRef] [Scilit]
- Liu, C.; Zang, Q.; Li, J.; Pan, X.; Dai, H.; Gao, W. The effect of the acoustic environment of learning spaces on students’ learning efficiency: A review. J. Build. Eng. 2023, 79, 107911. [Google Scholar] [CrossRef] [Scilit]
- Nelson, B.P.; Soli, D.S.; Seltz, A. ‘Acoustical Barriers To Learning’. 2002. Available online: https://acousticalsociety.org/wp-content/uploads/2018/02/classroom_acoustics_11.pdf (accessed on 24 November 2025).
- Hodgson, M. Experimental investigation of the acoustical characteristics of university classrooms. J. Acoust. Soc. Am. 1999, 106, 1810–1819. [Google Scholar] [CrossRef] [Scilit]
- Reich, R.; Bradley, J. Optimizing Classroom Acoustics Using Computer Model Studies. Can. Acoust. 1998, 26, 15–21. [Google Scholar]
- Alqahtani, A.Y.; Makki, A.A.; Alidrisi, H.M. Revealing factors influencing classroom noise in the universities teaching and learning environment: A design of experiments approach. J. Eng. Res. 2023, 11, 100009. [Google Scholar] [CrossRef] [Scilit]
- Bhandari, N.; Tadepalli, S.; Gopalakrishnan, P. Investigation of acoustic comfort, productivity, and engagement in naturally ventilated university classrooms: Role of background noise and students’ noise sensitivity. Build. Environ. 2024, 249, 111131. [Google Scholar] [CrossRef] [Scilit]
- Reinten, I.; De Ronde-Brons, I.; Houben, R.; Dreschler, W. Measuring the Influence of Noise Reduction on Listening Effort in Hearing-Impaired Listeners Using Response Times to an Arithmetic Task in Noise. Trends Hear. 2021, 25, 23312165211014437. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- Aguilar, A.J.; de la Hoz-Torres, M.L.; Costa, N.; Arezes, P.; Martínez-Aires, M.D.; Ruiz, D.P. Indoor acoustic quality of educational buildings in South West Europe: Influence of current ventilation strategies. J. Build. Eng. 2023, 80, 108012. [Google Scholar] [CrossRef] [Scilit]
- Wen, X.; Lu, G.; Lv, K.; Jin, M.; Shi, X.; Lu, F.; Zhao, D. Impacts of traffic noise on roadside secondary schools in a prototype large Chinese city. Appl. Acoust. 2019, 151, 153–163. [Google Scholar] [CrossRef] [Scilit]
- Rabelo, A.T.V.; Santos, J.N.; Oliveira, R.C.; Magalhães, M.d.C. Effect of classroom acoustics on the speech intelligibility of students. CoDAS 2014, 26, 360–366. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- Davidse, A.; Zare, R.N. Effect of Relative Humidity in Air on the Transmission of Respiratory Viruses. Mol. Front. J. 2021, 5, 5–16. [Google Scholar] [CrossRef] [Scilit]
- Qian, J.; Hospodsky, D.; Yamamoto, N.; Nazaroff, W.W.; Peccia, J. Size-resolved emission rates of airborne bacteria and fungi in an occupied classroom. Indoor Air 2012, 22, 339–351. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- Almeida, S.M.; Ramos, C.A.; Almeida-Silva, M. Exposure and inhaled dose of susceptible population to chemical elements in atmospheric particles. J. Radioanal. Nucl. Chem. 2016, 309, 309–315. [Google Scholar] [CrossRef] [Scilit]
- Kovacevic, R.; Tasic, V.; Zivkovic, M.; Zivkovic, N.; Djordjevic, A.; Manojlovic, D.; Jovasevic-Stojanovic, M. Mass concentrations and indoor-outdoor relationships of PM in selected educational buildings in Niš, Serbia. Chem. Ind. Chem. Eng. Q. 2015, 21, 149–158. [Google Scholar] [CrossRef] [Scilit]
- WHO. WHO Global Air Quality Guidelines: Particulate Matter (PM2.5 and PM10), Ozone, Nitrogen Dioxide, Sulfur Dioxide and Carbon Monoxide; World Health Organization: Geneva, Switzerland, 2021; Available online: https://iris.who.int/server/api/core/bitstreams/551b515e-2a32-4e1a-a58c-cdaecd395b19/content (accessed on 18 November 2025).
- Babich, F.; Torriani, G.; Corona, J.; Lara-Ibeas, I. Comparison of indoor air quality and thermal comfort standards and variations in exceedance for school buildings. J. Build. Eng. 2023, 71, 106405. [Google Scholar] [CrossRef] [Scilit]
- Pereira, L.D.; Raimondo, D.; Corgnati, S.P.; da Silva, M.G. Assessment of indoor air quality and thermal comfort in Portuguese secondary classrooms: Methodology and results. Build. Environ. 2014, 81, 69–80. [Google Scholar] [CrossRef] [Scilit]
- Mishra, A.; Derks, M.; Kooi, L.; Loomans, M.; Kort, H. Analysing thermal comfort perception of students through the class hour, during heating season, in a university classroom. Build. Environ. 2017, 125, 464–474. [Google Scholar] [CrossRef] [Scilit]
- Guan, H.; Hu, S.; Liu, G.; Zhang, L. The combined effects of temperature and noise on the comfort perceptions of young people with a normal Body Mass Index. Sustain. Cities Soc. 2020, 54, 101993. [Google Scholar] [CrossRef] [Scilit]
- Yang, W.; Moon, H.J.; Kim, M.-J. Combined effects of short-term noise exposure and hygrothermal conditions on indoor environmental perceptions. Indoor Built Environ. 2018, 27, 1119–1133. [Google Scholar] [CrossRef] [Scilit]
- Nagano, K.; Horikoshi, T. New comfort index during combined conditions of moderate low ambient temperature and traffic noise. Energy Build. 2005, 37, 287–294. [Google Scholar] [CrossRef] [Scilit]
- Pellerin, N.; Candas, V. Effects of steady-state noise and temperature conditions on environmental perception and acceptability. Indoor Air 2004, 14, 129–136. [Google Scholar] [CrossRef] [Scilit] [PubMed]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2026 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.