Abstract
Vacuum degree inside vacuum interrupter (VI) deteriorates due to cracks from long-term operation of VI, gas emitted from internal arc heat, leakage through the joint, etc. Partial discharge occurs between the two contacts inside the VI or between the contact and floating shield, which leads to dielectric breakdown and electrical accidents of high voltage apparatus. In this paper, the study on the vacuum degree monitoring of distribution class vacuum interrupter according to non-contact method of coupling capacitor based on partial discharge was performed. In order to monitor the partial discharge between two contacts inside VI with high accuracy, a partial discharge sensing electrode (PDDE) was designed using the 3D finite element method (FEM). In addition, after calculating the internal capacitance according to the structure and size characteristics inside VI, the capacity of the coupling capacitor to detect the signal was calculated. The partial discharge characteristics according to the vacuum degree were analyzed by applying PDDE and a coupling capacitor. As results, it was found that the partial discharge characteristics inside VI differ depending on the voltage type. In addition, it was confirmed that even if VI has the same internal structure and size, the partial discharge characteristics appear differently. Based on the experimental results, we proposed maintenance criteria for VI for each voltage type.
Keywords:
VI; partial discharge; AC; DC; direct-contact method; non-contact method; vacuum degree; detection; distribution class; FEM 1. Introduction
Sulfur hexafluoride (SF6), the gas mainly used for dielectric insulation material in high voltage apparatus, has high electron affinity, high dielectric strength compared to air, and high thermal conductivity [1]. However, because its Global Warming Potential (GWP) is about 23,900 times higher than that of CO2, the regular use of SF6 has become a serious environmental problem and has been designated as a greenhouse gas by the Kyoto Protocol, and its use is restricted [2]. Current trends in the global electric power market are toward eco-friendly policies such as the Green New Deal and carbon neutrality [3,4]. Accordingly, research and development on renewable power is actively progressing. To replace SF6 gas, research and development on alternative eco-friendly insulations are steadily being carried out.
To reduce the use of SF6 gas inside high voltage apparatus in the power system and to improve reliability, several more eco-friendly gases are being utilized such as methods of applying an eco-friendly gas such as air, dry-air, N2, O2, CO2, CF4, CF3I, hydrofluoroolefins, perfluorocarbons, C4F10O, Novec 4710, and gas mixtures or solid insulation such as epoxy resin are being utilized. However, eco-friendly insulations can neither secure the dielectric strength nor supply the arc breaking performance demonstrated by SF6 gas. Accordingly, by installing VI inside an eco-friendly insulated high voltage apparatus, dielectric strength and arc breaking performance are secured. Figure 1 shows the VI structure and partial discharge. As shown Figure 1, VI is maintained in a high vacuum of 10−7 torr and has excellent dielectric strength and arc breaking performance [5]. The moving contact, fixed contact and floating shield are enclosed in a ceramic chamber, which performs current interruption by causing the arc discharge to extinguish naturally in the vacuum [6]. The arc discharge is generated upon opening an electrical path between the electrodes [7]. The high vacuum condition inside VI deteriorates due to cracks from long term operation, gases released from internal arc heat, and leakage through joints. Problems such as insulation resistance and AC withstand voltage test failure occur due to cracks incurred during normal operation and manifest when inspecting high voltage apparatus. Accordingly, partial discharge occurs between the two contacts or between the contact and floating shield, and eventually leads to dielectric breakdown, resulting in electrical accidents of high voltage apparatus. If the vacuum degree inside VI is reduced to about 10−3 torr, the dielectric strength will drop sharply [8,9,10,11,12]. Therefore, it is very important to check the vacuum degree inside the VI in real time. There is currently no method to check for real-time vacuum degree abnormality inside VI for high voltage apparatus installed in the power system. The vacuum degree inside VI, can only be checked before and after a single product or high voltage apparatus in the power system. Moreover, most of the studies were conducted under AC voltage rather than DC voltage, and there are no maintenance criteria for when the vacuum degree of VI installed in high voltage apparatus is deteriorated. Prior to the research [13,14,15,16,17,18,19,20,21,22,23,24,25,26], one of the methods to check the vacuum degree inside VI was to measure the DC leakage current between the two contacts inside the VI. However, this method is applicable only when the VI exists outside its normal operation. Other methods include electromagnetic wave, discharge light intensity, and discharge sound, but can be applied only at the lowest pressure of about 1 Pa. Methods used in the power system, AC withstand voltage test, antenna, magnetron, spectrometer and temperature, register sensor are widely used in the field to determine the insulation failure of VI. However, these methods do not elucidate the specific vacuum degree, and should only be performed after disassembly from the power system or shutdown of operation. Devices such as coupling capacitor and detecting resistor are being studied for improving the accuracy of signal detection. The coupling capacitor is installed in VI, thus the voltage between contacts and floating shield is higher than the voltage between the floating shield and the external ground. Therefore, the electric field intensity between contacts and floating shield is increased, and the accuracy of the partial discharge signal is improved. Previous studies have not conducted in the high vacuum range and voltage type. Especially, in case of non-contact of coupling capacitor, the study on the electrode shape design for signal detecting and the distance between VI and electrode was not conducted or disclosed.
Figure 1.
VI structure and partial discharge.
There are two ways to contact the coupling capacitor to VI: direct-contact and non-contact. Figure 2 shows the difference in coupling capacitor contact method. As shown Figure 2, the non-contact method is to install the coupling capacitor at a certain distance from VI. Prior to research [6,7,8,9,10,11,12,13,14,15,16,17,18,19,20,21,22,23,24,25,26], as shown Figure 2, direct-contact method of coupling capacitor was applied to VI. Especially. The results of previous studies on direct-contact method [18,19] show that a partial discharge having a large apparent charge is detected as the vacuum degree decrease. However, if the direct-contact method of coupling capacitor is applied to high voltage apparatus, electrical accidents such as interface discharge between VI and gas or solid insulation, partial discharge, and dielectric breakdown occur. Accordingly, it is very difficult to commercialize the product. Various companies and research institutes are conducting various studies, but related technologies are still in the early stages. Moreover, to commercialize the vacuum checking technology is quite difficult because electrical accidents occur in high voltage apparatus. Solid insulation high voltage apparatus applied VI are very difficult to detect signals such as partial discharge inside vi due to epoxy. Also, if the technology is applied to solid insulation high voltage apparatus, various insulation accidents such as dielectric breakdown, creepage discharge, and partial discharge will occur. Therefore, several companies are working on the technology in its early stages. Table 1 shows the difference between the previous research and this paper. As shown Table 1, previous studies have mainly been conducted to detect signals generated when the vacuum degree inside VI is decreased under AC voltage by applying antennas, magnetron, spectrometer, temperature, coupling capacitors, and registers. In addition, insulation problems that arise when the technology is applied to high voltage power devices were not considered, and studies on when maintenance should be performed when the degree of vacuum inside VI decreases have not been conducted. Therefore, research should be conducted on the non- contact method, which has better electrical stability than the direct-contact method. Further, even if the vacuum degree inside VI can be detected through non-contact of coupling capacitor, there are no criteria for efficient maintenance. There is pressing need for both vacuum degree measurement in real-time and tailored criteria for efficient maintenance. In this paper, the study on the vacuum degree monitoring of distribution class VI using non-contact method coupling capacitor based on AC and DC partial discharge. First, for detecting the partial discharge between two contacts inside VI with high accuracy, PDDE was designed by 3D FEM. Also, the partial discharge characteristics were analyzed with respect to vacuum degree and voltage type through designed PDDE. At this time, the coupling capacitor was calculated according to the structure characteristics of distribution class VI.
Figure 2.
Different coupling capacitor contact methods.
Table 1.
Difference between the previous research and this paper.
2. Shape Design of PDDE
2.1. Safty Factor Calculation for Design Margin
When utilizing the non-contact of coupling capacitor, the PDDE is designed to improve the accuracy of partial discharge signal detection. Safety factor (SF) is calculated to apply the design margin for efficient design of the PDDE [27]. The SF is expressed by the Equation (1).
SF = ECRITERIA/EDESIGNED
In Equation (1), ECRITERIA means the maximum electric field intensity of insulation material applied to the high voltage apparatus, and EDESIGNED means the maximum electric field intensity of design model calculated through FEM analysis. SF is based on 1, and if it is large, it means stable, if it is small, it means unstable. If SF is much higher than 1, the device is overdesigned, and the SF should be reconsidered for efficient design. For calculation of SF, the standard of lighting impulse test in the dielectric test of IEC 62271-1 [28] was used. In IEC 62271-1, if discharged twice out of a total of fifteen times, the experiment failed. For high reliability of shape design, a SF of 7% (1/15 = 0.0666… = 0.07 → 7%) adopted by setting the acceptable discharge frequency to one time out of fifteen rather than two times out of fifteen.
2.2. Design of PDDE
For efficient shape design of PDDE, design factor and process have been established according to Figure 3. In Figure 3, “Factor A: Distance Between VI–Signal Detecting Electrode” means the distance between VI and PDDE. “Factor B: Diameter of Signal Detecting Electrode” means the diameter of PDDE. “Factor C: Rounding of Signal Detecting Electrode” means the rounding of edge in PDDE. “Factor D: Thickness of Signal Detecting Electrode” means the thickness of PDDE. As shown Figure 3, the shape design and process were carried out through a total of 4 design factors, and the shape design of PDDE proceeds from Factor A to Factor D. Figure 4 shows the 3D base model of PDDE and conditions. As shown in Figure 4, for efficient shape design, the base model of PDDE was set to have a distance between PDDE and VI of 0.5 mm and a diameter of 20 mm. Also, the distances between base model and VI were analyzed from 1 mm. VI is in the closed state. Accordingly, the moving contact and the fixed contact are in contact with each other, and 13.2 kV is applied to the contacts. In addition, the floating shield was floating condition and the PDDE was grounded. In order to confirm the maximum electric field strength of VI, the mesh was applied very small between the VI internal contact point and the floating shield, between VI and PDDE, and the surface of PDDE. Table 2 shows the FEM conditions for shape design of PDDE. ECRITERIA of 2.79 kV/mm considered SF of 7% was applied for shape design of PDDE.
Figure 3.
Design factor and process of PDDE.
Figure 4.
3D base model of PDDE and Conditions.
Table 2.
FEM Conditions for Shape Design of PDDE.
Figure 5 shows the FEM results through design factor and process. In Figure 5, the red rectangles mean the values selected through FEM analysis. Figure 6 shows the final model of PDDE. As shown in Figure 5 and Figure 6, calculation resulted in factor A: 4 mm, factor B: 60 mm, factor C: 5 mm, factor D: 1 mm. Table 3 shows the FEM results and electrical characteristics on shape design. As shown Table 3, the SF exceeded 1, and the electrical characteristics is very safe. The PDDE was designed using a ECRITERIA reflecting SF. SF has different unique values for each company, and it is not disclosed to the outside because it is a unique technology. In this paper, SF is higher than 1 as possible, but the design was carried out as close as possible to 1.
Figure 5.
FEM Results through Design Factor and Process.
Figure 6.
Final Model of PDDE.
Table 3.
FEM results and electrical characteristics on shape design.
3. Partial Discharge Characteristics According to Vacuum Degree
3.1. Experimental Set-Up and Method
In this paper, the study on the vacuum degree detection technology of distribution class VI with non- contact of coupling capacitor based on partial discharge. Figure 7 shows the AC and DC partial discharge experiment set-up. As shown in Figure 7, an AC power supply with a cut-off current of 25 mA and capacity of 50 kV, and a DC power supply with a cut-off current of 50 mA and capacity of 100 kV are used, respectively. An insulating spacer made by MC nylon is installed to prevent electrical accident between the vacuum sensor and VI. Vacuum sensor uses the PKR 251, which can measure up to ~10−9 torr at Pfeiffer Vacuum Co., Ltd. (Asslar, Germany). The diffusion pump is the HiPace 300, which can create a vacuum of up to 3.75 × 10−10 torr at Pfeiffer Vacuum Co., Ltd. (Asslar, Germany). AC and DC partial discharge measurement systems use the LDS-6 of Doble Lemke Co., Ltd. (Marl, Germany) and PDMS of SM&D Co., Ltd. (Seoul, Republic of Korea), respectively. LDS-6 has a measurement frequency range of 30~470 Hz, a single pulse resolution of ≤100 kHz, and the Phase Resolved Partial Discharge (PRPD) method was applied because the partial discharge characteristics were analyzed under AC voltage. Moreover, LDS-6 is in accordance with IEC 60270 [29]. However, DC partial discharge was not clearly defined in the IEC 60270. Accordingly, related research on DC partial discharge [19,29], and DC partial voltage was measured by the Pulse Sequence Analysis (PSA) method, which is a method for analyzing the correlation between sequentially generated pulses. Figure 8 shows the comparative analysis between time and apparent charge of partial discharge through PSA. Table 4 shows the basic parameters of PSA. As shown Figure 8 and Table 4, the four methods of measuring DC partial discharge through PSA are qn vs. ∆tpre, qn vs. ∆tsuc, ∆tpre vs. ∆tsuc, and ∆qpre vs. ∆qsuc [19,30]. In this paper, the ∆qpre vs. ∆qsuc method of the four methods was adopted. The capacity of coupling capacitor is calculated when non-contact method of coupling capacitor is applied to AC and DC partial discharge experiments. To calculate the capacity of coupling capacitor, the capacitance between contact and floating shield inside VI should be calculated because it is necessary to install a coupling capacitor with capacity greater than the capacitance between the contact and the floating shield [31]. The capacitance between contact and floating shield inside VI is expressed by Equation (2) [31].
Ca = (2 × π × ε0 × H)/(ln(R2/R1))
Figure 7.
AC and DC Partial Discharge Experiment Set-up.
Figure 8.
Comparative analysis between time and apparent charge of partial discharge through PSA.
Table 4.
Basic parameters of PSA.
In Equation (2), H is the contact length. R1 and R2 are the outside diameter of the contact and the inner diameter of the metal shield respectively. ε0 is the relative permittivity of a vacuum. The capacitance between the contact and floating shield is approximately 26 pF. Partial discharge characteristics for each capacity of various coupling capacitors were analyzed for efficient capacity calculation of coupling capacitor. Figure 9 shows the partial discharge experiment method under AC and DC voltage. As shown in Figure 9, turn off the rotary pump and diffusion pump after turning VI into high vacuum of 10−6 torr. the calibration of the partial discharge measurement system was performed before the experiment, and the background noise was set to 1 pC after installing a PDDE. The vacuum degree inside the VI was gradually decreased to 10−2 torr, and the partial discharge was measured. Moreover, the waveform of the induced voltage flowing through the coupling capacitor was checked with an oscilloscope. An experiment was performed for 50 min in which the vacuum degree was maintained from 10−5 torr to 10−2 torr. Also, the experiment for each VI was performed a total of 5 times. Figure 10 shows the partial discharge and vacuum degree according to the capacity of coupling capacitor. The partial discharge was detected from 10−2 torr when 32 pF was applied with a capacity larger than 26 pF. However, the highest partial discharge amount was detected at a vacuum degree of 10−3 torr from 38 pF, and it was found that the partial discharge amount and vacuum degree were saturated at capacities above that. Therefore, in this paper, a coupling capacitor with a capacitance of 38 pF from CeramTec was selected.
Figure 9.
Partial Discharge Experiment Method under AC and DC voltage.
Figure 10.
Apparent Charge and Vacuum Degree according to Capacity of Coupling Capacitor.
3.2. AC Partial Discharge Characteristics
The distances between VI and PDDE were selected according to the diameter of PDDE. Figure 11 shows the AC partial discharge characteristics according to the distance when the vacuum degree inside VI is decreased. As shown in Figure 11, as the distances between VI and PDDE decreased, the partial discharge signal was detected at the previous vacuum degree. The partial discharge was detected from 10−2 torr at a distance of 8 to 30 mm, but partial discharge was detected at 9 × 10−3 torr at 4 mm. Through this, the distance between the VI and PDDE was selected as 4 mm. Figure 12 shows the AC partial discharge characteristics according to decrease of vacuum degree. Figure 13 shows the AC induced voltage waveform. As shown in Figure 12 and Figure 13, AC partial discharge did not occur in the range from 10−5 torr to 10−4 torr. However, the AC partial discharge occurred from 1 × 10−2 torr, and then flashover is generated. Therefore, as the diameter of PDDE increased, the partial discharge signal was detected at the previous vacuum degree. For accurate analysis of AC partial discharge characteristics at distances between VI and PDDE, a total of 5 additional experiments were performed for each VI. Figure 14 shows the AC partial discharge characteristics of VI. In Figure 14, “Experiments 1~5” mean the number of experiments for each VI, and “VI 1 and 2” means two VIs with the same structural and electrical properties. As shown in Figure 14, the partial discharge was not detected from 10−5 to 10−4 torr, but the partial discharge was generated from 7~9 × 10−3 torr. After that, flashover occurred between the contact and floating shield inside VI at 1.5~2 × 10−2 torr, and the AC power supply tripped. Through this, like the direct-contact method [20,21], the apparent charge of partial discharge is different for each vacuum degree, and it can be seen that the partial discharge characteristics differ according to each VI and experiment. Moreover, as the diameter of PDDE increased, it was found that partial discharge and induced voltage were measured at the previous vacuum degree. Table 5 shows the maximum and minimum apparent charge amount of partial discharge for each VI and experiment under AC voltage. As shown in Table 5, in case of VI 1, the maximum apparent charge was 1053 pC, which was generated in the fourth experiment, and the minimum apparent charge was 119 pC, which was generated in the third experiment. In case of VI 2, The maximum apparent charge was 1185 pC, which was generated in the second experiment, and the minimum apparent charge was 58 pC, which was generated in the third experiment. Figure 15 shows the apparent charge according to the partial discharge occurrence point inside VI. As shown Figure 15, it can be seen that apparent charge between the contact and floating shield and the occurrence point are different each time the discharge occurs. Therefore, even if a partial discharge experiment is performed under the same experimental method and conditions as well as VI having the same electrical and mechanical characteristics, different apparent charge and patterns are always generated. To select the maintenance criteria of VI when non-contact method is applied, it is very important to select the vacuum degree before or immediately after occurrence of partial discharge. Moreover, the trigger value for detecting partial discharge should be set as the minimum value rather than the maximum value. To detect AC partial discharge in non-contact method of coupling capacitor, the trigger values for AC partial discharge are 58.
Figure 11.
AC Partial discharge Characteristics according to the distance when the vacuum degree inside VI is decreased.
Figure 12.
AC Partial Discharge characteristics according to decrease of vacuum degree.
Figure 13.
AC induced voltage waveform.
Figure 14.
AC Partial Discharge Characteristics of VI.
Table 5.
Maximum and Minimum Apparent Charge amount of Partial Discharge each VI and Experiment under AC voltage.
Figure 15.
Apparent charge according to the partial discharge occurrence point inside VI.
3.3. DC Partial Discharge Characteristics
Figure 16 shows the DC partial discharge characteristics according to the distance. As shown in Figure 16, like with AC partial discharge, In case of positive polarity, the partial discharge was detected from 1.5 × 10−2 torr from distance of 12 mm. In case of negative polarity, the partial discharge was detected from 1.3 × 10−2 torr as the distance is 4 mm. Figure 17 shows the DC partial discharge characteristics according to decrease of vacuum degree. Figure 18 shows the DC induced voltage waveform. As shown Figure 17 and Figure 18, regardless of voltage polarity, DC partial discharge was not detected in the range from 10−5 torr to 10−3 torr. Moreover, the partial discharge in negative polarity was detected faster than in positive polarity. Therefore, it was found that the partial discharge characteristics differ according to the polarity of DC voltage. Like AC partial discharge experiments, a total of 5 additional experiments were performed for each VI and diameter of PDDE. Figure 19 shows the DC partial discharge characteristics of VI when polarity is positive. As shown Figure 19, regardless of each VI, partial discharge was not detected from 10−5~10−3 torr, but flashover occurred between contact and floating shield inside VI immediately after partial discharge occurred at 1.5~1.7 × 10−2 torr. Figure 20 shows the DC partial discharge characteristics of VI when polarity is negative. As shown Figure 20, like DC partial discharge characteristics for positive polarity, the partial discharge was not detected from 10−5~10−3 torr. However, the partial discharge occurred from 1.3~1.5 × 10−3 torr. After that, flashover occurred between the contact and floating shield inside VI at maximum 1.7 × 10−2 torr, and the DC power supply tripped. Therefore, like AC partial discharge characteristics, the apparent charge of partial discharge is different for each vacuum degree, and it can be seen that the partial discharge characteristics are different according to each VI, experiment, and voltage polarity. Since the time interval of DC voltage is much shorter than that of AC voltage, it is very important to select the trigger value. Table 6 and Table 7 show the maximum and minimum apparent charge amount of partial discharge for each VI and experiment under DC voltage according to voltage polarity. As shown in Table 6 and Table 7, in case of VI 1, when the DC voltage is positive polarity, regardless of each experiments, the maximum and minimum apparent charge of partial discharge are 1410 pC were constant at 10−2 torr. When the DC voltage is negative polarity, like with positive polarity, regardless of each experiments, the maximum apparent charge of partial discharge is 1410 pC were constant at 10−2 torr. However, the minimum apparent charge was 36 pC, which was generated in the fourth experiment. In case of VI 2, when the DC voltage is positive polarity, like VI 1, regardless of each experiments, the maximum and minimum apparent charge of partial discharge is 1410 pC were constant at 10−2 torr. When the DC voltage is negative polarity, like positive polarity, regardless of each experiments, the maximum apparent charge of partial discharge is 1410 pC and was constant at 10−2 torr. However, the minimum apparent charge was 55 pC, which was generated in the first experiment. Accordingly, like AC partial discharge, to select the maintenance criteria of VI when non-contact method is applied, it is very important to select the vacuum degree before or immediately after the occurrence of partial discharge. The trigger value for detecting partial discharge should be set as the minimum value rather than the maximum value. The partial discharge in positive polarity has a consistent value of 1410 pC, the partial discharge characteristics in negative polarity were mainly applied to present maintenance criteria. To detect DC partial discharge according to voltage polarity in non-contact method of coupling capacitor, the trigger values for DC partial discharge is 36.
Figure 16.
DC Partial Discharge Characteristics according to the distance.
Figure 17.
DC partial discharge characteristics according to decrease of vacuum degree.
Figure 18.
DC induced voltage waveform.
Figure 19.
DC Partial Discharge Characteristics of VI when the polarity is positive.
Figure 20.
DC Partial Discharge Characteristics of VI when the polarity is negative.
Table 6.
Maximum and Minimum Apparent Charge amount of Partial Discharge each VI and Experiment under DC voltage of positive polarity.
Table 7.
Maximum and Minimum Apparent Charge amount of Partial Discharge each VI and Experiment under DC voltage of negative polarity.
3.4. Maintenance Criteria Proposal for VI by Voltage Type
In this paper, through the AC and DC partial discharge characteristics, the efficient maintenance criteria of VI was proposed. Figure 21 shows the difference between AC voltage and DC voltage. As shown Figure 21, the difference of partial discharge characteristics between AC voltage and DC voltage is due to electric field change and charge accumulation. In the AC voltage, the polarity of the voltage changes periodically due to the frequency, and the direction of the electric field changes periodically, resulting in repeated discharge. As a result, the vi internal insulation performance is rapidly reduced from 10−3 torr. However, since the DC voltage does not have a frequency, the polarity of the voltage is constant and the direction of the electric field is constant. As a result, electric charges are continuously accumulated and electrically stabilized. Even if it becomes 10−3 torr, partial discharge does not occur due to the accumulation of electric charges in a high vacuum state. However, if the vacuum degree decreases further to 10−2 torr, insulation breakdown occurs along with partial discharge. Accordingly, it can be seen that maintenance of VI is more difficult to DC voltage than at AC voltage. If partial discharge has already occurred inside VI, it means that the vacuum degree has been greatly lowered. To select the maintenance criteria of VI when non-contact method is applied, it is very important to select the vacuum degree before or immediately after the occurrence of partial discharge. Therefore, the probability of an electrical accident increases due to the rapid deterioration of the insulation performance. Figure 22 shows the maintenance criteria proposal for VI by voltage type. As shown in Figure 22, the AC partial discharge occurs before the DC partial discharge and is maintained for a longer period of time. Moreover, in DC voltage, the time interval between the partial discharge and flashover was much shorter than that of AC voltage. When the trigger value is detected, it means that the vacuum degree inside VI is decreasing. Therefore, the maintenance criteria are proposed as 5 × 10−3 torr for AC voltage, and 9 × 10−3 torr for DC voltage.
Figure 21.
Difference of partial discharge between AC voltage and DC voltage.
Figure 22.
Maintenance criteria proposal for VI by voltage type.
4. Conclusions
In this paper, the study on the vacuum degree detection technology of distribution class VI according to non-contact of coupling capacitor based on AC/DC partial discharge. For detecting the partial discharge between two contacts inside VI with high accuracy, the PDDE was designed by 3D FEM. Also, the partial discharge characteristics were analyzed according to vacuum degree and voltage type through the designed PDDE. The coupling capacitor was calculated according to the structure characteristics of distribution class VI. The results of this study are as follows:
- Partial discharge characteristics are detected differently voltage type for each experiment and each VI because the point at which discharge occurs between the contact and floating shield is different.
- Although the AC partial discharge occurs at a higher vacuum degree than the DC partial discharge, the time interval between partial discharge and flashover in DC voltage was much shorter than that of AC voltage.
- Maintenance criteria are proposed as 5 × 10−3 torr for AC voltage, and 9 × 10−3 torr for DC voltage.
- The trigger value of AC voltage was 58, and the trigger value of DC voltage was 36 because the partial discharge characteristics of negative polarity were mainly used to present maintenance criteria.
- In the future, we will conduct a study on a vacuum degree monitoring of VI inside a gas-insulated high voltage apparatus pressurized by pressure other than solid insulation.
Author Contributions
Conceptualization, S.B.; investigation, C.R. and S.B.; software, S.B.; writing/original draft, S.B.; supervision, B.-W.L.; writing—review and editing, B.-W.L. All authors have read and agreed to the published version of the manuscript.
Funding
This work was supported by Korea Institute of Energy Technology Evaluation and Planning (KETEP) grant funded by the Korea Government (MOTIE) (20224000000160, DC Grid Energy Innovation Research Center).
Data Availability Statement
Data is contained within the article.
Conflicts of Interest
The authors declare no conflicts of interest.
References
- Bang, S.; Lee, O.; Kim, J.; Kang, J.O.; Lee, H.; Ko, T.; Kang, H. Analysis on the Dielectric Characteristics of Gaseous Nitrogen for Developing Eco-Friendly High Voltage Apparatus. Trans. KIEE 2014, 63, 356–360. [Google Scholar] [CrossRef] [Scilit]
- Use of Gas in Magnesium Industry and Global Warming. J. Korean Foundrymen’s Soc. 2003, 23, 107–113.
- Zhang, Y.; Zhou, Q.; Zhao, L.; Ma, Y.; Lv, Q.; Gao, P. Dynamic Reactive Power Configuration of High Penetration Renewable Energy Grid Based on Transient Stability Probability Assessment. In Proceedings of the 2020 IEEE 4th Conference on Energy Internet and Energy System Integration (EI2), Wuhan, China, 30 October–1 November 2020; IEEE: Piscataway, NJ, USA; pp. 3801–3805. [CrossRef] [Scilit]
- Lamnadi, M.; Trihi, M.; Boulezhar, A. Study of a hybrid renewable energy system for a rural school in Tagziry Morocco. In Proceedings of the 2016 International Renewable and Sustainable Energy Conference (IRSEC), Marrakech, Morocco, 14–17 November 2016. [Google Scholar] [CrossRef] [Scilit]
- Schellekens, H.; Devismes, M.F.; Nicolle, C. Vacuum Interrupter: Design Optimisation requires Reliable Experimental Data. In Proceedings of the 2011 1st International Conference on Electric Power Equipment-Switching Technology, Xi’an, China, 23–27 October 2011; IEEE: Piscataway, NJ, USA; pp. 56–59. [CrossRef] [Scilit]
- Yokomichi, S.; Kozako, M.; Hikita, M.; Sato, K.; Moriyama, T.; Urai, H.; Nakaoka, T.; Tsuchiya, K. Development of Diagnostic Methods for Vacuum Leakage from Vacuum Interrupter by Partial Discharge Detection. In Proceedings of the 2016 27th International Symposium on Discharges and Electrical Insulation in Vacuum (ISDEIV), Suzhou, China, 18–23 September 2016. [Google Scholar] [CrossRef] [Scilit]
- Mei, Y.; Yuan, H.; Wang, X.; Wang, X.; Wang, W. Study on the change tendency of electro-magnetic signal under different vacuum degree for 10 kV vacuum chamber. In Proceedings of the TENCON 2015—2015 IEEE Region 10 Conference, Macao, China, 1–4 November 2015. [Google Scholar] [CrossRef] [Scilit]
- Habibie, A.; Hikita, M.; Kozako, M.; Nakano, Y.; Suwarno; Khayam, U. Detecting Vacuum Degree Condition of Vacuum Interrupter by Partial Discharge Measurement. In Proceedings of the 2019 5th International Conference on Electric Power Equipment-Switching Technology (ICEPE-ST), Kitakyushu, Japan, 13–16 October 2019. [Google Scholar] [CrossRef] [Scilit]
- Reeves, R.; Falkingham, L. The effect of magnetron discharge pressure measurement on the actual pressure in vacuum interrupter. In Proceedings of the 2015 3rd International Conference on Electric Power Equipment–Switching Technology (ICEPE-ST), Busan, Republic of Korea, 25–28 October 2015. [Google Scholar] [CrossRef] [Scilit]
- Nakano, Y.; Kozako, M.; Tanaka, T.; Kobayashi, M. Estimation of Internal Pressure of Vacuum Interrupter by Measuring Partial Discharge Current. In Proceedings of the 28th International Symposium on Discharges and Electrical Insulation in Vacuum (ISDEIV), Greifswald, Germany, 23–28 September 2018. [Google Scholar] [CrossRef] [Scilit]
- Abe, J.; Tanabe, T.; Yano, T.; Yoshida, S.; Inoue, N. The Electric Discharge Detection Method in the Low Vacuum Region of Vacuum Interrupter. Electron. Commun. Jpn. 2017, 100, 59–66. [Google Scholar] [CrossRef] [Scilit]
- Deng, X.; Li, W.; Liu, B. Discharge Properties and Diagnosis of Gas Pressure in Vacuum Interrupter. In Proceedings of the 2011 IEEE Power Engineering and Automation Conference, Wuhan, China, 8–9 September 2011. [Google Scholar] [CrossRef] [Scilit]
- Jin, X.; Shi, Z.; Mo, Y.; Sun, J. Numerical Investigation on the Detection of Vacuum Interrupter Pressure Based on Pirani Method. In Proceedings of the 2025 31st International Symposium on Discharges and Electrical Insulation in Vacuum (ISDEIV), Chengdu, China, 21–26 September 2025. [Google Scholar] [CrossRef] [Scilit]
- Wu, F.; Zhang, F.; Yuan, H.; Yang, A.; Wang, X.; Rong, M. On-Line Vacuum Degree Detection of Vacuum Circuit Breaker Based on Laser-Induced Breakdown Spectroscopy Combined with WTD-RF. In Proceedings of the 2024 7th International Conference on Electric Power Equipment-Switching Technology (ICEPE-ST), Xiamen, China, 10–13 November 2024. [Google Scholar] [CrossRef] [Scilit]
- Yoon, J.; Kwon, J.; Jung, J.; Jeon, H.; Kim, M. Prediction of Vacuum Circuit Breaker Condition Based Arcing Energy. In Proceedings of the 2024 10th International Conference on Condition Monitoring and Diagnosis (CMD), Gangneung, Republic of Korea, 20–24 October 2024. [Google Scholar] [CrossRef] [Scilit]
- Cao, P.; Wang, L.M.; Zhou, G.; Zhao, H.; Lu, Y.; Hu, J. Research on Vacuum Degree Detection Technology for Vacuum Circuit Breakers Using High-Frequency High-Voltage Pulse Power Supply. In Proceedings of the 2025 31st International Symposium on Discharges and Electrical Insulation in Vacuum (ISDEIV), Chengdu, China, 21–26 September 2025. [Google Scholar] [CrossRef] [Scilit]
- Cao, P.; Zhou, G.; Hu, Z.; Li, X.; Jin, S.; Hu, J. Detection Method for Vacuum Degree in Vacuum Circuit Breakers Based on Electron Multiplication. In Proceedings of the 2025 31st International Symposium on Discharges and Electrical Insulation in Vacuum (ISDEIV), Chengdu, China, 21–26 September 2025. [Google Scholar] [CrossRef] [Scilit]
- Bang, S.; Lee, H.-W.; Lee, B.-W. Real-Time Monitoring of the Vacuum Degree Based on the Partial Discharge and an Insulation Supplement Design for a Distribution Class Vacuum Interrupter. Energies 2021, 14, 7891. [Google Scholar] [CrossRef] [Scilit]
- Bang, S.; Lee, H.-W.; Lee, B.-W. Comparison of AC and DC partial Discharge by Monitoring of Vacuum Degree in a Distribution Class Vacuum Interrupter. IEEE Access 2022, 10, 36254–36267. [Google Scholar] [CrossRef] [Scilit]
- Duan, X.Y.; Li, F.; Dong, E.; Liao, M.; Guo, Y.; Zou, J. Study on inner vacuum pressure measurement system of vacuum circuit breakers. In Proceedings of the 2017 4th International Conference on Electric Power Equipment-Switching Technology (ICEPE-ST), Xi’an, China, 22–25 October 2017. [Google Scholar] [CrossRef] [Scilit]
- Saito, H.; Matsui, Y.; Sakaki, M. Discharge Properties in Low Vacuum and Vacuum Monitoring Method for Vacuum Circuit Breakers. In Proceedings of the 2006 International Symposium on Discharges and Electrical Insulation in Vacuum (ISDEIV’06), Matsue, Japan, 25–29 September 2006. [Google Scholar] [CrossRef] [Scilit]
- Kamarol, M.; Ohtsuka, S.; Hikita, M.; Saitou, H.; Sakaki, M. Determination of gas pressure in vacuum interrupter based on partial discharge. IEEE Trans. Dielectr. Electr. Insul. 2007, 14, 593–599. [Google Scholar] [CrossRef] [Scilit]
- Lee, G.Y.; Kil, G.S.; Kim, S.W. Partial discharge Characteristics for Internal Defects of Vacuum Interrupters. J. Korean Soc. Railw. 2021, 24, 274–279. [Google Scholar] [CrossRef] [Scilit]
- Sung, J.K.; Park, C.B.; Choi, G.H.; You, J.H.; Hong, H.W. A Study on determination of live line for the distribution switchgear depending on VI’s vacuum level. In KIEE Proceedings; KIEE: Seoul, Republic of Korea, 2021; pp. 210–211. [Google Scholar]
- Youn, Y.W.; Hwang, D.H.; Sun, J.H.; Song, K.D.; Koh, H.R.; Kim, Y.I. Development of measuring and analysis method for monitoring the vacuum degree in VI. In KIEE Proceedings; KIEE: Seoul, Republic of Korea, 2013; pp. 1370–1371. [Google Scholar]
- Lee, H.W.; Bang, S.; Lee, B.W. Study on Vacuum Degree Prediction Technology of Vacuum Interrupter through AC/DC Partial discharge Measurement. In KIEE Proceedings; KIEE: Seoul, Republic of Korea, 2021; pp. 12–13. [Google Scholar]
- Bang, S.; Kim, H.-S.; Koo, J.-H.; Lee, B.-W. Consideration of the Insulation Design Method on a ±200 kV Converter Valve Unit in an HVDC Converter Hall. Energies 2021, 14, 2296. [Google Scholar] [CrossRef] [Scilit]
- IEC 62271-1:2017; High-Voltage Test Switchgear and Controlgear—Part 1: Common Specifications for Alternating Current Switchgear and Controlgear. IEC: Geneva, Switzerland, 2017.
- IEC 60270:2000; High-Voltage Test Techniques–Partial Discharge Measurements. IEC: Geneva, Switzerland, 2000.
- Oh, D.H.; Kim, H.S.; Lee, B.W. A novel Diagnosis Method for Void Defects in HVDC Mass-Impregnated PPLP Cable Based on Partial Discharge Measurement. Energies 2021, 14, 2052. [Google Scholar] [CrossRef] [Scilit]
- Zhang, X.; Liu, X.; Fan, X.; Huang, Z.; Fan, J.; Liang, C. A high accurate sensor research and its application for VCB’s internal pressure on-line condition monitor. In Proceedings of the 2012 25th International Symposium on Discharges and Electrical Insulation in Vacuum (ISDEIV), Tomsk, Russia, 2–7 September 2012. [Google Scholar] [CrossRef] [Scilit]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2026 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.