Abnormal Failure Modes and Their Impact on HVDC Applications

and
1
Power Electronics, Svenska kraftnät, 172 24 Sundbyberg, Sweden
2
Electric Power Engineering, Luleå University of Technology, 931 87 Skellefteå, Sweden
*
Author to whom correspondence should be addressed.

Abstract

Detecting and disconnecting faults is of utmost importance in power systems to prevent damage, outages and limit the impact on the surrounding grid. However, there are faults that may not be detected by protective functions and therefore do not interrupt the operation. Such faults, which have not been considered during the design of an HVDC system despite causing negative operational impacts, are referred to as abnormal failure modes in this paper. Data from three cases of abnormal failure modes in point-to-point HVDC systems are presented. The first case regards a prolonged subsequential failure of a DC filter capacitor for an LCC-HVDC link. The second case presents a measurement disturbance resulting in power oscillations from a VSC-HVDC link. The third case shares details of an overload scenario of a grounding impedance due to DC voltage unbalance from asymmetric corona discharges. This study shares details from these failures and suggests recommendations based on the presented abnormal failure modes in HVDC applications, including multi-terminal HVDC systems.

1. Introduction

As renewable energy sources (RESs) have been rapidly integrated in the power system, new challenges have been introduced [1,2]. The inherent intermittency and geographical spread of RESs introduces a demand for controllable sources to maintain operational reliability [3].
High-voltage direct current (HVDC) transmission has been identified as promising technology to support and accelerate this transition [4]. Recently, the concept of multi-terminal HVDC (MTDC) has gained attention as it has additional benefits beyond traditional point-to-point HVDC systems. MTDC systems, where three or more converters share a common DC network, can offer a platform for applications, such as offshore wind farm hubs and power corridors [5].
Although MTDC grids already have been put into practice and have been studied for decades [6,7,8], technical challenges remain with enabling compatibility among converters. The term interoperability summarizes several challenges related to the compatibility of converters. It is expected that converters from various vendors will differ, for example, in main circuit scheme, control and protection strategies. To maintain high operational reliability with an MTDC grid where converters from multiple vendors are connected, it is important to find solutions to these interoperability challenges [9].
Understanding and managing events and variations at the DC side in MTDC grids, such as control actions, protective actions and converter modes/states, are essential for interoperability [9]. Abnormal states of converter equipment at the DC side can cause disturbances that propagate through the MTDC grid, resulting in power oscillations, cascading trips and personal danger. Knowledge and experience of such disturbances remain limited for multi-vendor MTDC grids in relation to AC grids.
This paper studies abnormal failure modes at the DC side in point-to-point HVDC systems and their possible implications for an MTDC grid. The studies in this paper are based on field measurements. The first part of the paper introduces the concept of abnormal failure modes, which is then followed by the three case studies. All cases start by presenting the main circuit and measurement arrangement, after which the results are presented. Lastly, analysis and discussion of each case are shared. The main findings of the paper are then summarized under Conclusions.

2. Abnormal Failure Modes

Multiple standards, including IEC 60050-192 [10] and IEC 61508-4 [11], have defined the terms “fault” and “failure”. In this paper, the definitions in [11], have been adopted. In summary, a fault is defined as a state of an item where it has lost its ability to perform as required, whereas a failure is defined as an event that results in a fault of an item. It should be noted that an item may also have a reduced ability to perform as required, while still performing within acceptable limits. In this paper, this degraded state will not be classified as a fault. Furthermore, the term “mode” will be used to describe one of the possible states, in this case of an HVDC system, throughout this paper.
For any power system, including HVDC systems, it is crucial to disconnect a fault to prevent further damage, personal injuries and unnecessary outages. For most cases, the protection system can detect a fault and initiate appropriate protective actions, such as tripping breakers to isolate the fault or raise an alarm. However, some faults may not be detected by the protection system which results in continued operation of the HVDC system. These undetected faults may cause immediate danger for personnel and severe stress on the electrical system and surrounding equipment [12].
For HVDC applications, certain faults will also increase the risk of undesired actions and control instabilities. Of particular interest are faults that, despite having a significant impact on system operation, have not been considered in system studies, real-time simulations or on-site testing. Failure events from such faults will be referred to as abnormal failure modes in this paper, i.e., one of the possible states, where a fault manifests itself and has not been considered in the design. Control systems and their respective transfer functions are designed such that they do not cause instabilities. However, they are reliant on correct input measurements and Boolean statuses to function correctly. Additionally, while variations such as grid topologies and control modes are considered in the design and tuning of the control system, certain changes in system dynamics are neglected. A change beyond what has been considered in the control system design can result in a model-plant mismatch where various outcomes are possible, including degraded performance and instabilities [13].
Given the vast number of possible abnormal failure modes and their consequences, complete and realistic modelling can be rather difficult. As some parts of the HVDC system may not be represented in simulation models, such as measurement circuits and their immunity, there will be uncertainties in the ability of the model to predict real-world behaviour. To reduce this uncertainty, data has been collected from events where abnormal failure modes have occurred in HVDC stations. To understand these abnormal failure modes, models were developed based on data from the events.

3. Case Study 1: Faulty DC Filter

3.1. Main Circuit and Measurements

A simplified diagram of the main circuit with measurement locations is shown in Figure 1. Pole line voltage, V d L , is measured with a resistive capacitive voltage divider with a bandwidth of 0 1 MHz [14]. The transducers measuring the pole line current, I d L , are based on the Hall effect, and have a bandwidth of 0–10 kHz [14]. These quantities were sampled by a fault recorder with a sampling frequency of 20 kHz.
Figure 1. Main circuit and measurement locations for Case 1.

3.2. Results

The DC filter capacitor bank connected to the high-voltage terminal in this specific case, consisted of two parallel strings. During this event, several capacitors malfunctioned over an extended period, subsequently resulting in repetitive flashovers. These flashovers were not sustained and occurred within the capacitor units, causing high frequency transients. Ultimately, a pole-to-ground fault occurs at 2.5 s in Figure 2, tripping the HVDC link.
Figure 2. Sequence of events for Case 1.

3.3. Analysis and Discussion

The voltage spectrum in Figure 3 shows a transient and a significant change in frequency contents at approximately 2.1 s. This change is, among others, in the form of a larger steady state ripple. After 0.4 s, a sustained pole-to-ground fault occurs over the filter. Prior to this change, the transients showed an amplified response at 500 Hz, which indicates that the filter was significantly detuned.
Figure 3. Spectrogram of the DC pole voltage.
In Figure 4, the simulated frequency dependent impedance magnitudes and phase angles are shown for the DC filter before and after the shift in resonant frequency from 500 to 600 Hz. Before the impedance shift, the 500 Hz transient implies that a significant number of capacitor units were faulty, increasing the total capacitance. However, to cause an immediate shift from 500 to 600 Hz, the total capacitance must be reduced by 36% in a step. Assuming a different number of faulty capacitors in the two individual strings, this step may be due to a discontinuation in one of the strings. The large steady-state voltage ripple that followed may be the consequence of a sustained arc related to the discontinuation which subsequently spread to a sustained pole-to-ground fault.
Figure 4. Pre- and post-fault frequency response of the filter.
There are multiple fault modes of apparatus such as reactors and surge arresters that can remain undetected while operation continues. Considering all possible deviations for all main circuit apparatus in all possible combinations and for all test scenarios will in practice be impossible. The extent to which deviations in the main circuit parameters should be considered is a major challenge. While some faults have an immediate impact on the HVDC system, others will only have an impact during a limited number of scenarios. However, considering a variation in the capacitance of high-voltage connected capacitors at the DC side may be relevant based on this case study. The presented case was regarding a DC filter on an LCC-HVDC scheme; however, the same applies for VSC-HVDC and MTDC grid schemes if DC capacitors are connected to the DC bus.
Capacitor banks connected to high-voltage terminals can consist of several capacitor units and capacitor elements, connected in both parallel and series to obtain the desired capacitance, voltage and current rating as shown in Figure 5. If one or more capacitor units and/or elements are faulty, the total capacitance will change. However, the voltage may still be within design limits, which results in continued operation of the HVDC system. A capacitor unit will typically tolerate an overvoltage of 30% for one minute [15], which may arise from other faulty capacitor units within the capacitor bank and/or faulty capacitor elements within the capacitor unit. This associated time frame is considered long during events, such as harmonic resonance or control interaction. Depending on the internal design of the capacitor unit, fault distribution within the bank and fault distribution within each unit, up to 30% change in capacitance may occur per standard. Moreover, as displayed in the case, a discontinuation in one series-connected string can occur, causing larger deviations than 30%. However, factors such as placement in the main circuit and capacitance rating must also be considered to assess the impact of a sudden change in capacitance value.
Figure 5. Unbalance current transformer (green), capacitor bank (red), capacitor unit (blue) and capacitor element (magenta).
Algorithms to detect such faults must be carefully designed to have the ability to distinguish a safe operational state from an unsafe operational state. For AC applications, faulty capacitors can be detected by known methods, such as configuring the capacitors in an H-bridge with an unbalanced current transformer, as shown in Figure 5 [16]. Any difference in capacitance between the four branches will cause an unbalanced current through the current transformer. Contrarily, for DC applications, a similar configuration is not effective as the DC current is blocked by the capacitors. As the DC side ripple is dependent on several converter dynamics, such as control modes and power level [17,18,19], measuring the AC current through a DC capacitor may not be a viable option either. Furthermore, as the DC voltage distribution is decided by grading resistors within the capacitor units [15], an H-bridge configuration with an unbalanced current transformer would also risk affecting the voltage distribution within the capacitor bank. If the capacitor bank is divided into two branches, it is possible to route the individual branches in opposite directions through a current transformer. However, if the ripple is of a small magnitude, detection will still be difficult and dependent on the operational state of the converter. In summary, detecting faulty capacitors in HVDC applications is more difficult than in AC applications and investing in additional apparatus for detecting these faults may not be a cost-effective solution. Time-based testing and verification of capacitors may be the most reliable option for capacitors without any real time unbalance detection implemented.

4. Case Study 2: Measurement Disturbances

4.1. Main Circuit and Measurements

A simplified main circuit with measurement abbreviations is shown in Figure 6. Similarly, as for Case 1, the positive and negative pole voltage measurements, V d P and V d N respectively, are obtained from resistive capacitive voltage dividers. However, the pole current measurements, I d P and I d N , are acquired from optical Faraday effect-based transducers with a reported bandwidth over 1 MHz [14]. To reduce the effect of measurement errors from the current transducers, the mean pole current, I d , displayed in the figures is calculated according to (1). The measured values were sampled by a fault recorder with a sampling frequency of 12.8 kHz.
I d P + I d N 2 = I d
Figure 6. Main circuit and measurement locations for Case 2 and Case 3.

4.2. Results

During this event, the inverter station tripped due to prolonged active power oscillations, mainly in the frequency range from 5 to 25 Hz, that had been present for several hours prior to the event. In several measurements from the disturbance recorders, oscillations can be observed as shown in Figure 7. Measurement quantities with subscript R and I are measured at the rectifier and inverter terminal, respectively.
Figure 7. Sequence of events for Case 2.

4.3. Analysis and Discussion

By comparing the negative pole voltage between the rectifier and inverter station, a distinct disturbance can be observed in the inverter station. Although variations are also visible in the rectifier’s negative pole voltage, they are less distinct and show much resemblance to those in the positive pole voltage. This indicates that the deviation in the inverter’s negative pole voltage likely is a disturbance in the secondary circuit, whereas the variations observed in the other measurements are a symptom of the converters’ direct response to the disturbances. As the inverter station also operated as the DC voltage controlling converter, the disturbance affecting the negative pole voltage also interfered with the DC voltage controller, causing oscillations with a magnitude of 0.05 p.u. in AC power, Pac. If a similar disturbance would affect the DC voltage measurements in the power controlling station, the transmitted power would remain unaffected as the inputs to such a controller are based on other measurement parameters [20,21].
Investigations found that this disturbance may originate from surge arresters in close proximity to the resistive capacitive voltage divider of the negative pole. The three parallel surge arrester legs were mounted in the triangle as shown in Figure 8. Each surge arrester consisted of two series-connected units. Due to the agricultural environment surrounding the station, asymmetric algae growth had developed on the three legs. As the middle sections were separated by 19 mm, this enabled potential differences between the middle sections of the three parallel columns. At rainy weather conditions, this potential difference increased due to the wet asymmetric algae growth further increasing the uneven voltage distribution between surge arresters. The potential difference between the columns charged through the asymmetric resistive algae growth until the potential difference exceeded the critical air insulation breakdown voltage. When this occurred, a flashover discharged the charged energy in the stray capacitance between the surge arrester columns. As the charging process immediately restarts after discharging and the arc has distinguished, this results in repetitive transients.
Figure 8. Surge arrester and voltage divider arrangement, including measuring cable (blue) and disturbance (red).
These repetitive transients caused radiated disturbances that were picked up by the secondary circuit of the voltage divider. After tripping the inverter at 2 s (see Figure 7), the DC voltage control is passed to the previous rectifier station. With healthy voltage measurements, the DC voltage is kept relatively constant at 0.5 p.u. The fact that the frequency of the disturbances increased with a more constant DC voltage strengthened the theory that the source of disturbances was from repetitive discharges. A detailed description and theoretical assessment will be shared using the simplified model of this circuit shown in Figure 9. The asymmetric algae growth on two surge arresters is modelled as resistors, R S A x , since the direct voltage only can be divided by resistors. The 19 mm gap between two surge arresters is modelled as a stray capacitance, C S A and a discharge circuit consisting of a switch and a fault resistance, R f . A potential difference in the middle section is only possible if (2) is fulfilled.
R S A 1 R S A 2 ≠ R S A 3 R S A 4
Figure 9. A simplified model of the charge and discharge circuit.
To create a detailed model of this case, a multiphysics simulation software is required, which is beyond the scope of this paper. A simplified assessment indicates that the transient discharge induces a current, I , into the secondary circuit according to (3).
I = C d V d t
where C is the capacitive coupling between the secondary cable and the disturbance source while d V / d t is the derivative of the voltage from the discharge.
To cause a flashover, the voltage between the surge arresters must be in the range of tens of kilovolts. In combination with the weak capacitive coupling between the surge arresters, C S A , the derivative of the voltage, d V / d t , during the discharge will be of a large magnitude according to (4).
d V d t = − V 0 R f C S A e − 1 R f C S A t
where V 0 is the total air insulation breakdown voltage between the two surge arresters and R f is the arc resistance.
The high-frequency content of the induced current spreads mostly through capacitive couplings to ground as shown in Figure 10. This current also adds a transient voltage drop which introduces an error in the voltage measurement.
Figure 10. Simplified secondary circuit including disturbance source and induced currents (blue).
Ideally, the HVDC control and protection system is immune against disturbances. If this system is affected, it should be able to distinguish between a disturbance in the measurement system and a disturbance in the primary signal. Despite designing the HVDC control and protection system accordingly, supported by normative standards such as IEC 60255 [22] and IEC 61000-6-5 [23], disturbances can affect the system as illustrated in this case. Disturbances can vary in frequencies, affecting measured values of DC currents, AC voltages, and semiconductor temperatures, to list a selection of examples. In combination with the respective control loop the measurand is input to, the converter response from disturbances will likewise exhibit variation. It is therefore not expected or recommended to predict and find solutions to all disturbance variations during the design of the HVDC system. However, it is recommended to expect oscillations in HVDC and MTDC schemes despite having stable control loop transfer functions. With additional converter stations in an MTDC grid, the risk of similar abnormal failure modes will increase. Furthermore, the complexity of finding the source of disturbances increases as additional converters affect the response of the MTDC grid.
In this point-to-point HVDC scheme, a protective function against power oscillations was implemented. However, a challenge with a similar function in an MTDC grid with mixed converter designs and tolerances would be to coordinate the protective function to only trip the source of the oscillations. The absence of standards has led to the development of various designs for power oscillation detection and protection [24,25,26]. This complicates coordination as the design variations, such as frequency range and signal processing, may be different. Therefore, it is preferrable that such a protective function in an MTDC grid is harmonized through standardization to simplify coordination.

5. Case Study 3: DC Voltage Unbalance

5.1. Main Circuit and Measurements

This case occurred on the same HVDC link as described in Case 2. Therefore, the corresponding main circuits are identical. In addition to the measurements described for Case 2, the current transducers for the grounding impedance currents, IG, are of Faraday types.

5.2. Results

The HVDC scheme consists of both overhead line (28%) and cable sections (72%). During rainy weather conditions, the RMS value of the current through the large grounding reactors increased until finally tripping due to reaching a designed thermal limit (1 p.u. in Figure 11). A majority of the current consisted of DC, but the current also contained a 150 Hz component from the third harmonic injection.
Figure 11. Sequence of events for Case 3.

5.3. Analysis and Discussion

While the amplitude of the 150 Hz component of the current was relatively constant, the DC component varied in magnitude including reversing in direction. Strong correlations were found between the DC component and rainfall and wind directions surrounding the overhead line section as shown in Figure 12. The rainfall affected the overall magnitude while the wind direction affected the direction of the DC component through the grounding impedance. The angle shown in Figure 12 is the wind direction relative to the direction of the overhead line. These combined findings suggest that asymmetric corona discharges between the poles at the overhead line section may cause uneven pole voltages [27,28]. This DC voltage unbalance results in a current through the grounding impedance. Since the conductors of the positive and negative poles are placed in a flat formation, this naturally results in a surplus of electrons on one of the poles, dependent on the wind direction.
Figure 12. DC component of the current through the grounding reactors (top) and metrological data (middle and bottom).
As presented in this case, a dynamic DC side conductance is expected for an HVDC system, especially with overhead lines due to the corona discharges. In large MTDC grids, there could be several overhead lines at geographically diverse locations. To estimate the sum of all unbalances will be challenging, as detailed meteorological data from the several overhead line sections must be considered and may not always be available. Additional information, such as tower design and conductor bundling, is required for an accurate assessment of the corona discharges. This creates a dynamic to the DC side conductance which will be difficult to accurately assess during the design of the HVDC system.
In Figure 13, a simplified DC voltage unbalance model is presented. For a symmetric monopole scheme, the DC voltage in the positive and negative pole, V d / 2 and − V d / 2 respectively, can be calculated according to (5) and (6).
V d 2 = V ^ a c ( t ) + V ^ u ( t ) + L d i ^ u d t
− V d 2 = V ^ a c ( t ) − V ^ l ( t ) − L d i ^ l d t
where V ^ a c ( t ) is the AC voltage, V ^ u ( t ) and V ^ l ( t ) are the upper and lower arm voltages and L d i ^ u / d t and L d i ^ l / d t are the voltage drops over the upper and lower phase arm reactors.
Figure 13. AC and DC side model (left) and simplified DC side model (right).
For static DC voltage unbalance, only DC voltage is to be considered. The upper and lower converter voltages can therefore be modelled as ideal DC voltage sources, according to (7) and (8).
V ^ u ( t ) = V d 2 − V ^ a c ( t ) − L d i ^ u d t ⇒ V ^ u = V d 2
V ^ l ( t ) = V d 2 − V ^ a c ( t ) − L d i ^ l d t ⇒ V ^ l = V d 2
Based on these simplifications and neglecting the direct voltage drop in the conductor, the steady state DC voltage unbalance can be calculated according to (9)–(11).
V d P = V d 2 R P R P + R G
V d N = ( − V d 2 ) R N R N + R G
V d Δ = V d P + V d N = V d 2 ( R P − R N ) R G ( R P + R G ) ( R N + R G )
where V d Δ is the DC voltage unbalance, R P and R N are the equivalent parallel resistance at the positive and negative poles respectively and R G is the resistance of the grounding impedance circuit. If R P and R N are much larger than R G , the DC voltage unbalance equation can be simplified to (12).
R N ≫ R G , R P ≫ R G ⇒ V d Δ = V d 2 ( R P − R N ) R G R P R N
According to (12), the steady-state DC voltage unbalance will be strongly dependent on the grounding resistance. Ideally, the absolute values of the DC pole voltages are equal. For a low resistance grounded HVDC scheme, the asymmetric corona will cause a minor DC voltage unbalance. Contrarily, for HVDC system with high resistive grounding, asymmetric corona can cause larger DC pole voltage unbalances with potential issues of overloading the grounding circuit.
For symmetric monopole configurations, the DC voltage is controlled pole-to-pole, while individual pole-to-ground voltages are not controlled [29]. Therefore, reducing the DC voltage may be the only operational alternative to avoid a trip from the overload protection of the grounding impedance. However, the maximum power transmission capacity will be reduced as a consequence.
To limit the wind-dependent DC voltage unbalance, there are other methods that can be applied. In earlier design stages, improved tower design can be a viable option. Although a tower design with vertical conductors can limit the effect of the wind direction, the unequal distance between the poles and ground will cause asymmetric corona discharges between the poles.
Another alternative is to transpose the lines. In contrast to AC transmission applications, where transposing the lines equalizes the inductance of the phases, transposing DC lines will equalize the corona discharges. However, as meteorologic conditions can vary along long distances, a DC overhead line may require more transpositions than an AC overhead line to minimize the effect of specific local weather conditions. Regardless of horizontal or vertical tower design, transposing the lines will increase symmetry in corona discharges.

6. Conclusions

Data from the presented cases show several abnormal failure modes, which all had a negative impact on the HVDC links’ operation. The presented cases are a limited selection of the vast number of potential scenarios with abnormal failure modes. However, given the difficulty of predicting abnormal failure modes and to what extent they should be considered, the main findings and recommendations from this paper can be summarized as follows:
  • Expect that instabilities will occur despite having stable control loops;
  • Consider variations in capacitance of capacitors connected to the DC system in stability studies;
  • Asymmetric corona influenced by metrological conditions can cause DC voltage unbalances and overloading of grounding impedances.
In MTDC systems, the probability of abnormal failure modes increases as the number of converter stations, switching stations, cables and/or overhead lines grow. Moreover, the difficulty in identifying the root cause will increase in larger MTDC systems where the dynamics of several converters affects the response of the entire system.
Beyond the limited scope of this paper, further research is needed on the following topics:
  • Mapping and classification of DC side disturbances;
  • Factors influencing DC side disturbances;
  • Impacts of DC side disturbances;
  • Additional variations in main circuit equipment and their effect on converter dynamics;
  • Standardization of detection mechanisms and coordination strategies in the case of sustained DC side oscillations.
Addressing these topics will be important to enable reliable MTDC grids with a diverse set of converters.

Author Contributions

Conceptualization, M.P. and M.B.; methodology, M.P.; software, M.P.; validation, M.P.; formal analysis, M.P.; investigation, M.P.; resources, M.P.; data curation, M.P.; writing—original draft preparation, M.P.; writing—review and editing, M.P. and M.B.; visualization, M.P.; supervision, M.B. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by Svenska kraftnät. Funding number: 50144138.

Data Availability Statement

The datasets presented in this article are not readily available because of security restrictions. Requests to access the datasets should be directed to the corresponding author.

Conflicts of Interest

Author Martin Pettersson was employed by the company Svenska kraftnät. The remaining authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest. The authors declare that this study received funding from Svenska kraftnät. The funder was not involved in the study design, collection, analysis, interpretation of data, the writing of this article or the decision to submit it for publication.

Abbreviations

The following abbreviations are used in this manuscript:
HVDCHigh-voltage direct current
VSCVoltage source converter
LCCLine commutated converter
RESRenewable energy sources
MTDCMulti-terminal HVDC

References

  1. Tiismus, H.; Maask, V.; Astapov, V.; Korõtko, T.; Rosin, A. State-of-the-Art Review of Emerging Trends in Renewable Energy Generation Technologies. IEEE Access 2025, 13, 10820–10843. [Google Scholar] [CrossRef] [Scilit]
  2. Bollen, M.; Hassan, F. Integration of Distributed Generation in the Power System; Wiley: Hoboken, NJ, USA, 2011. [Google Scholar]
  3. Nepomnyashcy, V.; Lomane, T.; Mahnitko, A.; Zicmane, I.; Timurs, K. Renewable Energy Sources And Reliability of the Electric Power System Operation. In Proceedings of the IEEE 63th International Scientific Conference on Power and Electrical Engineering of Riga Technical University (RTUCON), Riga, Latvia, 10–12 October 2022. [Google Scholar]
  4. European Union (EU). Commission Regulation (EU) 2016/1447; Official Journal of the European Union: Luxembourg, 2016. [Google Scholar]
  5. Moritz, M.; Jahn, I.; Ramos, J.C.; Kjaer, C.; Moore, J. WG4-Framing the European Energy System. READY4DC. 2023. Available online: https://www.ready4dc.eu/wp-content/uploads/WG4_D4.5_Whitepaper_Framing-the-European-energy-system-for-publication.pdf (accessed on 4 February 2026).
  6. Dougherty, J.J. Operating Characteristics of a Three-Terminal DC Transmission Line. IEEE Trans. Power Appar. Syst. 1970, 89, 775–780. [Google Scholar] [CrossRef] [Scilit]
  7. Foerst, R.; Heyner, G.; Kanngiesser, K.W.; Waldmann, H. Multiterminal Operation of HVDC Converter Stations. IEEE Trans. Power Appar. Syst. 1969, 88, 1042–1052. [Google Scholar] [CrossRef] [Scilit]
  8. Vaughan, R.L.; Bowles, J.P.; Dalzell, J. The control and performance of a series connected multiterminal HVDC transmission system. IEEE Trans. Power Appar. Syst. 1975, 94, 1868–1877. [Google Scholar] [CrossRef] [Scilit]
  9. CIGRE. TB 961—Interoperability in HVDC Systems Based on Partially Open Software; WG B4.85; CIGRE: Paris, France, 2025. [Google Scholar]
  10. IEC 60050-192; Dependability. International Electrotechnical Commission: Geneva, Switzerland, 2015.
  11. IEC 61508-4; Functional Safety of Electrical/Electronic/Programmable Electronic Safety-Related Systems—Part 4: Definitions and Abbreviations. International Electrotechnical Commission: Geneva, Switzerland, 2010.
  12. 242-2001; IEEE Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems. IEEE: New York, NY, USA, 2001.
  13. Yousefi, M.; Lu, Q.; Loewen, P.D.; Forbes, M.G.; Dumont, G.A. Detecting model-plant mismatch without external excitation. In Proceedings of the IEEE American Control Conference (ACC), Chigago, IL, USA, 1–3 July 2015. [Google Scholar]
  14. IEC/TR 61869-103; Instrument Transformers—The Use of Instrument Transformers for Power Quality Measurement. International Electrotechnical Commission: Geneva, Switzerland, 2012.
  15. IEC 61071; Capacitors for Power Electronics. International Electrotechnical Commission: Geneva, Switzerland, 2017.
  16. Long, Y.; Sun, Z.; Wang, D. The Calculation of HV Capacitor Unbalance Protection Settings for AC Filters in GeZhouBa Converter Station. In Proceedings of the IEEE International Conference on Power System Technology, Chongqing, China, 22–26 October 2006. [Google Scholar]
  17. Wang, S.; Teodorescu, R.; Chaudhary, S.K. Capacitor Voltage Ripple Reduction Methods of Modular Multilevel Converter under Unbalanced Fault Conditions: A Comparison. In Proceedings of the IEEE International Power Electronics and Application Conference and Exposition (PEAC), Shenzhen, China, 4–7 November 2018. [Google Scholar]
  18. CIGRE. TB 811—DC Side Harmonics and Filtering in HVDC Transmission Systems; WG B4.68; CIGRE: Paris, France, 2020. [Google Scholar]
  19. IEEE. 1124 IEEE Guide for Analysis and Definition of DC Side Harmonic Performance of HVDC Transmision Systems; IEEE: New York, NY, USA, 2003. [Google Scholar]
  20. Hannan, M.A.; Hussin, I.; Ker, P.J.; Hoque, M.M.; Lipu, M.S.H.; Hussain, A. Advanced Control Strategies of VSC Based HVDC Transmission System: Issues and Potential Recommendations. IEEE Access 2018, 6, 2169–3536. [Google Scholar] [CrossRef] [Scilit]
  21. Zhao, D.-D.; Li, Y.-X.; He, S.-Y.; Cui, L.; Guo, J.; Xing, Z.-X. Operating Characteristics and Control Strategy of HVDC Transmission with Controllable Line-Commutated Converter. In Proceedings of the IEEE 2nd Asia Power and Electrical Technology Conference (APET), Shanghai, China, 28–30 December 2023. [Google Scholar]
  22. IEC 60255; Measuring Relays and Protection Equipment. International Electrotechnical Commission: Geneva, Switzerland, 2022.
  23. IEC 61000-6-5; Electromagnetic Compatibility (EMC)—Part 6-5: Generic Standards—Immunity for Equipment Used in Power Station and Substation Environment. International Electrotechnical Commission: Geneva, Switzerland, 2015.
  24. Bergman, D.; Eriksson, R.; Alavijh, M.G. Evaluation of Forced Oscillation Detection Methods. In Proceedings of the IEEE PES Conference on Innovative Smart Grid Technologies—Middle East (ISGT Middle East), Abu Dhabi, United Arab Emirates, 12–15 March 2023. [Google Scholar]
  25. Wakode, S.; Sheikh, A.A.; Deshmukh, R.R.; Ballal, M.S. Oscillation Frequency Based Protection Scheme for Ring Type DC Microgrid. In Proceedings of the IEEE International Conference on Power Electronics, Smart Grid and Renewable Energy (PESGRE2020), Cochin, India, 2–4 January 2020. [Google Scholar]
  26. Ma, N.; Li, Y.; Liu, P.; Xin, G.; Li, H.; Xie, X. Protection Strategy of Sub-/Super-synchronous in Power Systems with High-Penetration Wind Power. In Proceedings of the 6th International Conference on Renewable Energy and Power Engineering (REPE), Beijing, China, 15–17 September 2023. [Google Scholar]
  27. Khalifa, M.M.; Morris, R.M. A Laboratory Study of the Effects of Wind on DC Corona. IEEE Trans. Power Appar. Syst. 1967, 86, 290–298. [Google Scholar] [CrossRef] [Scilit]
  28. Corbellini, U.; Pelacchi, P. Corona losses in HVDC bipolar lines. IEEE Trans. Power Deliv. 1996, 11, 1475–1481. [Google Scholar] [CrossRef] [Scilit]
  29. Wang, M.; Berteen, J.; Van Hertem, D. Pole Voltage Balancing in HVDC Systems: Analysis and Technology Options. In Proceedings of the 2019 IEEE Milan PowerTech, Milan, Italy, 23–27 June 2019. [Google Scholar]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Article Metrics

Citations

Article Access Statistics

Multiple requests from the same IP address are counted as one view.