Research on an Intelligent Sealed Neutral Point Protection Device for High-Altitude Transformers
Abstract
1. Introduction
2. Overall Design Concept
3. Key Component Design
3.1. Design of Enclosed Discharge Gap
3.1.1. Discharge Gap
- When nitrogen or dry air was used as the insulation medium, with 56.7 kV applied to the high-voltage end of the discharge gap, active breakdown of the discharge gap could be achieved via pulse control by adjusting the gap distance in both cases.
- When SF6 or the gas mixture was used as the insulation medium, the active breakdown control of the discharge gap could not be achieved due to the arc-quenching properties of SF6.
- For SF6 and the gas mixture, even after multiple adjustments of the discharge gap distance and gas pressure, it was difficult to simultaneously meet both the power frequency withstand voltage of approximately 75 kV and the power frequency discharge voltage of 56.7 kV (with pulse intervention).
- Moreover, given that dry air contains complex components such as oxygen, rapid oxidation of the discharge gap can occur under high temperatures during discharge.
3.1.2. Cylindrical Shell Design
3.2. Design of Intelligent Active Breakdown Device
3.2.1. Neutral Point Overvoltage Signal Acquisition Module
3.2.2. Pulse Triggering Module
4. Test Verification
4.1. Prototype Overview and Test Setup
4.2. Test Results
- Figure 10a displays the voltage waveform for Scenario A. The voltage (60 kV) exceeds Vth, but decays before the preset tth (500 ms). As predicted by the logic, no breakdown command was issued, demonstrating immunity to short-duration transients.
- Figure 10b,c display the voltage waveform for Scenario B. The voltage (53 kV) persists for a long duration (>3 s) but remains below Vth. Despite the extended time, no breakdown occurred, confirming stability under low-amplitude, long-duration stress.
- Figure 10d–f display a representative voltage waveform for Scenario C. The voltage equals Vth (70 kV) and is maintained beyond the preset duration, at which point the active breakdown is successfully triggered (the precise moment of trigger command output is marked). This verifies the correct protective operation.
4.3. Discussion and Comparative Analysis
- Enhanced Discharge Voltage Stability: unlike conventional gaps whose breakdown voltage is highly susceptible to environmental factors (altitude, pollution, humidity), the sealed N2 environment and fixed geometry of our device ensure stable and reproducible operation. This is evidenced by the consistent performance at the precise thresholds of 56.7 kV and 60 kV in our tests, effectively eliminating environmentally induced maloperation or failure-to-trip [22].
- Superior Transient Overvoltage Response and Selectivity: the active dual-criteria logic represents a fundamental shift from the passive, single-criterion (voltage-only) operation of traditional gaps. By requiring a sustained overvoltage (both V ≥ Vth and t ≥ tth), our device inherently raises its effective withstand voltage for fast transients (e.g., lightning surges) to approximately 3–4 times the steady-state value. This creates a decisive coordination margin with surge arresters, preventing maloperation during transients—a failure mode common in conventional systems where the transient breakdown voltage is fixed at about twice the steady-state value [23]. The successful non-operation in Scenario A (60 kV/300 ms) experimentally confirms this advancement
- Inherent High-Altitude Suitability: the comparative advantage is most pronounced in high-altitude applications. The sealed design directly solves the core environmental vulnerability of open gaps, making the device inherently immune to low pressure, sandstorms, and contamination [24]. This directly fulfills the research objective presented in the Introduction.
5. Conclusions
Author Contributions
Funding
Data Availability Statement
Acknowledgments
Conflicts of Interest
References
- National Energy Administration. DL/T 1848-2018; Technical Specification for Overvoltage Protection of 220 kV and 110 kV Transformer Neutral Points. China Electric Power Press: Beijing, China, 2018. Available online: https://d.wanfangdata.com.cn/standard/DL/T%201848-2018 (accessed on 3 February 2026).
- Standardization Administration of the People’s Republic of China. GB/T 16927.1-2011; High-Voltage Test Techniques—Part 1: General Definitions and Test Requirements. Standards Press of China: Beijing, China, 2011. Available online: https://std.samr.gov.cn/gb/search/gbDetailed?id=3E68F26FAE44386AE06397BE0A0A6860 (accessed on 3 February 2026).
- National Energy Administration. DL/T 620-1997; Overvoltage Protection and Insulation Coordination for AC Electrical Installations. China Electric Power Press: Beijing, China, 1997. Available online: https://d.wanfangdata.com.cn/standard/Ch9TdGFuZGFyZE5ld1NvbHI5UzIwMjYwMTI4MTY1NTM2Eg1ETC9UIDYyMC0xOTk3GghxZXA1bWR1Mw%3D%3D (accessed on 3 February 2026).
- Standardization Administration of the People’s Republic of China. GB/T 50064-2014; Code for Design of Overvoltage Protection and Insulation Coordination for AC Electrical Installations. China Architecture & Building Press: Beijing, China, 2014. Available online: https://d.wanfangdata.com.cn/standard/Ch9TdGFuZGFyZE5ld1NvbHI5UzIwMjYwMTI4MTY1NTM2Eg9HQi9UIDUwMDY0LTIwMTQaCDV2eHBiM2Ri (accessed on 3 February 2026).
- Li, Y.; Liu, J.; Kuang, S.; Xie, W. Overvoltage of 110 kV, 220 kV Transformer Neutral Point and Its Protection Analysis. In Proceedings of the Asia-Pacific Power and Energy Engineering Conference, Shanghai, China, 27–29 March 2012; pp. 1–4. [Google Scholar]
- Helac, V.; Smaka, S.; Grebovic, S.; Oprasic, N. Power Transformer Neutral Point Grounding Methods: Analysis of Fault Characteristics. In Proceedings of the IEEE PES Innovative Smart Grid Technologies Europe (ISGT-Europe), Novi Sad, Serbia, 10–12 October 2022; pp. 1–5. [Google Scholar]
- Liu, M.Z.; Han, R.; Zheng, Y.K.; Yin, Z.; Wu, J.; Wang, H.; Tian, J.J. Breakdown Characteristics and Gap Distance Standardization of Neutral Point Gap in 110 kV and 220 kV Transformers. In Proceedings of the International Conference on Power System Technology: Carbon Neutrality and New Type Power System, Haikou, China, 8–9 December 2021; pp. 2295–2300. [Google Scholar]
- Dai, H.L. Analysis and Protection of 110kV Transformer Neutral Point Overvoltage. Master’s Thesis, Changsha University of Science & Technology, Changsha, China, 2017. Available online: https://d.wanfangdata.com.cn/thesis/Ch1UaGVzaXNOZXdTb2xyOVMyMDI2MDExNzA4NTkxNhIIWTM0NDQ2MjUaCG96enMzMzI1 (accessed on 3 February 2026).
- Wang, J.; Ma, L.T.; Wang, X.T.; Xue, J.; Wang, S.; Zhao, Z.X.; Guo, J. Study on the coordination characteristics of an arrester with parallel gap for 110 kV transformer neutral point. High Volt. Appar. 2020, 56, 228–232+238. [Google Scholar] [CrossRef]
- Zhang, K.Y.; Du, S.Q.; Yuan, D.; Wu, Y.S.; Zhang, F.; Cui, J.J.; Cao, W. Research on the improvement of overvoltage measurement method based on capacitive voltage transformer. Electr. Power Energy 2024, 45, 480–485+501. [Google Scholar]
- IEC 60071-1:2019; Insulation Co-Ordination—Part 1: Definitions, Principles and Rules. International Electrotechnical Commission: Geneva, Switzerland, 2019.
- Wang, P.F. Study of Ball Gap Triggered Discharge Characteristics of Transformer Neutral Point Protection. Master’s Thesis, Harbin University of Science and Technology, Harbin, China, 2023. [Google Scholar] [CrossRef]
- Xu, M.C. Study on Controlled Gap of 110kV Transformer Neutral Point. Master’s Thesis, North China Electric Power University, Beijing, China, 2016. Available online: http://dx.chinadoi.cn/10.7666/d.Y3115145 (accessed on 3 February 2026).
- Wang, J.; Xiao, Q.M.; Chen, X.L.; Wang, H.B.; Wu, Z.Y.; Xu, M.C.; Nie, H.Y.; Zhang, H.Y.; Wei, X.L. Triggering Controlled Discharge Gap Used for Protection of Neutral Point of Power Transformer in 110 kV Power System. J. Harbin Univ. Sci. Technol. 2013, 18, 57–62. Available online: http://dx.chinadoi.cn/10.3969/j.issn.1007-2683.2013.02.011 (accessed on 3 February 2026). (In Chinese)
- Nie, H.; Wang, P.; Chen, Q.; An, Z.; Li, Z. Maximum Working Voltage Range of the Ball Gap Spark Switch. IEEE Access 2024, 12, 183999–184009. [Google Scholar] [CrossRef]
- Gustavsen, B.; Longva, K. Neutral Point Overvoltages in Wye-Wye Connected Distribution Transformer Caused by Lightning Current in Low-Voltage Winding. IEEE Trans. Power Deliv. 2021, 36, 2851–2860. [Google Scholar] [CrossRef]
- Nishikori, Y.; Kojima, S.; Kouno, T. A Study of the Field Utilization Factor and the Maximum Electric Field at Sparkover of the Standard Sphere Gaps. Electr. Eng. Jpn. 2002, 139, 26–32. [Google Scholar] [CrossRef]
- Qiu, Z.; Wu, Z.; Song, Y. Sphere Gap Breakdown Voltage Prediction Based on ISSA Optimized BP Neural Network and Effective Electric Field Feature Set. IEEJ Trans. Electr. Electron. Eng. 2023, 18, 506–514. [Google Scholar] [CrossRef]
- Li, X.; Kang, J.; Li, J.; Zhou, S.; Wang, F.; Ma, G.; Qin, Z.; Dong, H.; Zhang, Y.; Yang, J.; et al. Research on the Design of Enclosed Protective Discharge Gap for Transformer Neutral Point Based on Energy Aggregation Characteristics. J. Phys. Conf. Ser. 2023, 3012, 012032. [Google Scholar] [CrossRef]
- Yang, Z.Y. Research on Analysis of Overvoltage Based on Neutral Point of Power Transformer and Technology of Insulation Protection. Master’s Thesis, Shandong University of Technology, Zibo, China, 2022. [Google Scholar] [CrossRef]
- Liu, C.; He, L.H.; Cui, X.Y.; Li, C.S.; Ma, X.W. Research on zero-sequence protection device arrangement method of neutral point of 110 kV transformer. Power Syst. Prot. 2010, 38, 114–117. Available online: http://dx.chinadoi.cn/10.3969/j.issn.1674-3415.2010.02.028 (accessed on 3 February 2026).
- Jiang, Y.J.; Chen, S.Q.; Zhang, X.; Deng, X.D.; Xu, Y.F.; Meng, H.J. Research and design of an intelligent protection device for 110kV transformer neutral point. Transformer 2020, 57, 42–44+48. [Google Scholar] [CrossRef]
- Han, A.Z. Comprehensive lightning protection measures for power transformers. Transformer 2010, 47, 61–63. Available online: https://d.wanfangdata.com.cn/periodical/CiBQZXJpb2RpY2FsQ0hJU29scjkyMDI2MDIwMjE0MTYxMhIMYnlxMjAxMDAyMDIwGgg1cjZqeTV4Yg%3D%3D (accessed on 3 February 2026).
- Ma, H.; Guo, X.L.; Lu, D.F. Causes and countermeasures for transformer neutral breakdown and adjacent line maloperation due to single-phase grounding. High Volt. Eng. 2001, 27, 58–59. Available online: http://dx.chinadoi.cn/10.3969/j.issn.1003-6520.2001.z1.037 (accessed on 3 February 2026).
- Li, B.J. Study on Parallel Protection of the Air-Water Gap and the Arrester for Neutral Points of Power Transformers. Ph.D. Thesis, Wuhan University, Wuhan, China, 2014. Available online: https://kns.cnki.net/kcms2/article/abstract?v=dKcr_PZ1zcuG83uvbRsFtQPaMX7GM4y07ExPMHNntLJTqclsHnce3B6v5L7hcl2Apg_wjMW0fpIsEb_TVaOrKkMeciI-iVg8hQ9zOGcG-T1OEmK-3mXNM1AQo57NUMSSWQXz-J_uqJmjGpoNk48O_45VHXDyiEo__USIe03xMpoWKX1eT8kyqZhufbD4CZJ-&uniplatform=NZKPT&language=CHS (accessed on 3 February 2026).
- Liu, Z.Y. The Research of Flexible Measures to Limit the Neutral Point Over-Voltage of 110kV–220kV Transformer. Master’s Thesis, North China Electric Power University, Beijing, China, 2017. Available online: http://dx.chinadoi.cn/10.7666/d.Y3263961 (accessed on 3 February 2026).
- Yan, Y.T.; Lu, H.L.; Wang, Y.Z.; Zhu, Z.G.; Chen, R.Z.; Wen, X.S. A new rod-plate-rod combined protection gap for 110 kV transformer neutral point. High Volt. Eng. 2015, 41, 699–704. Available online: http://dx.chinadoi.cn/10.13336/j.1003-6520.hve.2015.02.050 (accessed on 3 February 2026).
- Lin, Y.Z.; Chen, X.J.; Chen, W.J.; Yan, X.L.; Ge, D.; Zhang, C.X.; Ye, K. A protection scheme for ungrounded neutral points of 110 kV and 220 kV power transformers. Power Syst. Technol. 2012, 36, 256–259. Available online: https://d.wanfangdata.com.cn/periodical/CiBQZXJpb2RpY2FsQ0hJU29scjkyMDI2MDIwMjE0MTYxMhINZHdqczIwMTIwNDA0NhoIY3l4ajQzYzg%3D (accessed on 3 February 2026).










| Test Scenario | Purpose | Applied Voltage | Applied Duration | Preset tth | Gap Action |
|---|---|---|---|---|---|
| Scenario A | Anti-maloperation (transient/short-duration) | 60 kV | 300 ms and 400 ms | 500 ms | No breakdown |
| Scenario B | Stability (prolonged low-level) | 53 kV | >3 s | 300 ms and 500 ms | No breakdown |
| Scenario C | Correct protection (sustained fault) | 70 kV | 100, 300, 500 ms | 100, 300, 500 ms | Breakdown |
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2026 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.
Share and Cite
Yan, W.; Li, X.; Wang, F.; Dong, H.; Zhao, Z.; Gao, J.; Han, X. Research on an Intelligent Sealed Neutral Point Protection Device for High-Altitude Transformers. Energies 2026, 19, 906. https://doi.org/10.3390/en19040906
Yan W, Li X, Wang F, Dong H, Zhao Z, Gao J, Han X. Research on an Intelligent Sealed Neutral Point Protection Device for High-Altitude Transformers. Energies. 2026; 19(4):906. https://doi.org/10.3390/en19040906
Chicago/Turabian StyleYan, Wen, Xiaohui Li, Fujie Wang, Huifang Dong, Zhongqi Zhao, Jinpeng Gao, and Xutao Han. 2026. "Research on an Intelligent Sealed Neutral Point Protection Device for High-Altitude Transformers" Energies 19, no. 4: 906. https://doi.org/10.3390/en19040906
APA StyleYan, W., Li, X., Wang, F., Dong, H., Zhao, Z., Gao, J., & Han, X. (2026). Research on an Intelligent Sealed Neutral Point Protection Device for High-Altitude Transformers. Energies, 19(4), 906. https://doi.org/10.3390/en19040906
