Abstract

Short dissolved-gas histories are useful for transformer condition assessment, but they make record cleaning and predictor selection uncertain. We present a data-constrained forecasting pipeline that combines operating-state checks, whale-tuned variational mode decomposition and adaptive fusion of heterogeneous predictors. An ARIMA residual screen first marks unusual observations; concurrent current, active-power and oil-temperature measurements are then used to contextualize possible sensor disturbances and changes associated with operating conditions. Ridge regression, gated recurrent units and bidirectional long short-term memory networks forecast the decomposed components, while a compact meta-network combines the reconstructed gas-level outputs from sequence descriptors and recent errors. This study evaluates six gases in normal operation at one-step and six-step horizons and also examines an abnormal methane sequence. Under the retrospective preprocessing protocol, fusion gives one-step R2 values of 0.9217–0.9953 and six-step values of 0.6749–0.9584. All reported gas–horizon pairs retain positive R2, although a single member is preferable in several cases. For the abnormal methane case, fusion ties Ridge at R2 = 0.9967. Batched parallel inference shortens the benchmark runtime from 1.453 to 0.434 s. Supplementary archived-trajectory analysis identifies score-version differences, and a controlled raw-hydrogen Ridge audit reduces R2 from 0.9799 with full-series VMD to −0.8362 with past-only VMD. Thus, the retrospective scores do not establish prospective accuracy; complete historical-only fusion validation remains necessary.

1. Introduction

Dissolved gas analysis (DGA) links measured gas patterns to the condition of oil and solid insulation. IEC 60599:2022 and IEEE C57.104-2019 provide guidance on interpreting gases in mineral-oil equipment [1,2], while IEC 60567:2023 addresses gas sampling and the analysis of free and dissolved gases [3]. Established interpretation methods include key-gas assessment, Rogers and IEC gas ratios, and the Duval triangle and pentagon [4]. These methods interpret gas patterns; the present model extrapolates concentrations. Its forecasts can support trend review between measurements but do not replace standards-based interpretation, confirm insulation ageing mechanisms, or establish a fault diagnosis. Table A1 summarizes this distinction.
Forecasting dissolved-gas concentrations gives a numerical indication of how transformer insulation may change between inspections. Field records are commonly short compared with the parameter count of a deep forecasting model, and the difficulty increases when a method must represent both gradual concentration drift and abrupt abnormal-operation growth. Transfer learning and mutation detection have been explored for scarce defective-state samples [5], while attention-based predictors have been used to model temporal dependence in transformer gas records [6]. These studies motivate efficient use of the available history without presuming that one predictor is equally suitable for every gas.
Decomposition is one route to reducing forecasting complexity. A gas sequence may combine a slowly varying baseline with oscillations at several characteristic scales. Yang et al. coupled slime mold optimization, variational mode decomposition (VMD) and gated recurrent units (GRUs) in a decompose–predict–reconstruct scheme [7]. Xie et al. likewise applied VMD and GRUs to transformer gas forecasting [8], and related work paired correlation-based VMD with a convolutional long short-term memory model [9]. This literature supports multiscale representations, but the choice of an extrapolator for each component and operating regime remains open.
Measurement quality poses a second challenge. When only the target gas is inspected, an isolated sensor excursion can look like a genuine concentration increase. Removing every statistical outlier may erase evidence of a real operating change, whereas retaining an instrumental error can bias a model fitted to a short record. Consequently, anomaly screening has been incorporated into dissolved-gas forecasting [10], and ARIMA screening combined with an optimized bidirectional LSTM has been used for transformer-record cleaning [11]. Concurrent operating channels add useful context: a gas jump accompanied by changes in oil temperature or current should not be interpreted in the same way as a jump recorded under otherwise stable conditions.
Model choice still matters after cleaning and decomposition. A linear predictor can follow smooth component trajectories with few fitted coefficients, whereas recurrent networks can express nonlinear temporal dependence at the cost of greater estimation uncertainty in small samples. Neither characteristic implies universal superiority across hydrogen, hydrocarbons and carbon oxides. Time-varying ensembles based on ICEEMDAN and integrated predictors have been investigated [12], and physics-informed recurrent models provide another route for incorporating operating knowledge [13]. Here, recent errors and sequence descriptors are instead used to vary the contribution of several complementary predictors.
Metaheuristic optimization is also used in related electrical-engineering tasks. Examples include hybrid APO–PSO optimization for transformer DGA diagnosis [14], a modified fire hawk optimizer for double-diode solar-cell parameter estimation [15], search and rescue optimization for optimal power flow [16], and snow ablation optimization for generator-unit allocation [17]. These applications motivate the use of bounded searches in complex parameter spaces. They do not establish that a particular optimizer is best for dissolved-gas forecasting; here WOA is used specifically to select the VMD mode count and bandwidth penalty under the stated search budget.
We therefore build a forecasting workflow with ARIMA residual screening, operating-state verification, optimized VMD, and a predictor pool containing Ridge, GRU and bidirectional LSTM models. Each member forecasts every component and reconstructs a gas-level trajectory; a meta-network then combines the three trajectories. The evaluation covers six normal-operation gases at one-step and six-step horizons, one abnormal methane sequence, and the effect of batching and parallel execution. The analysis distinguishes robustness against severe deterioration from winning every individual task, and it makes explicit which parts of the retrospective protocol would need to change for prospective deployment. The practical contributions are threefold: a two-stage screen that combines residual evidence with operating context, a decomposition search tied to the forecasting objective, and an error-aware fusion layer that preserves both linear and recurrent alternatives. These contributions are evaluated as a coherent workflow rather than as a claim that any one module is universally optimal.

2. Methodological Framework and Mathematical Basis

2.1. End-to-End Forecasting Architecture

For a target gas sampled at instant t, let yt denote its concentration. The accompanying operating variables are oil temperature Tt, core-grounding current It and active power Pt. As illustrated in Figure 1,the workflow first flags statistical irregularities in the gas record and then checks the operating channels before replacing a suspected measurement error. The cleaned series is decomposed into K intrinsic mode functions (IMFs). Ridge, GRU and BiLSTM predictors are fitted separately to each component, producing three parallel component-level forecasts. Summing the components gives one gas-level forecast per model family, after which the meta-network combines those reconstructed trajectories rather than permanently selecting a single model for each gas.
Figure 1. Schematic of the proposed forecasting pipeline. Dashed groups mark the cleaning, decomposition and predictor-fusion stages; the eight IMFs shown correspond to the hydrogen example.
The architecture separates two types of variability. VMD distributes temporal variation across component scales, while the predictor pool represents alternative functional forms for extrapolation. The fusion layer can lower the weight of a member whose recent errors have grown, but there is no guarantee that the aggregate forecast will beat the best member at every origin.

2.2. Residual-Based Screening and Operating-State Checks

An ARIMA model represents a differenced concentration series through autoregressive and moving-average terms. With zt = (1 − B)ᵈyt, where B is the lag operator, and d is the differencing order, the formulation is given in Equation (1).
z t = μ + ∑ i = 1 p ϕ i z t − i + ε t + ∑ j = 1 q θ j ε t − j
Here, μ is a constant; p and q are the autoregressive and moving-average orders; φi and θj are their coefficients; and εt is the innovation. The implementation uses ARIMA(1,1,1). Residual statistics estimated from the training observations define the reference distribution for later screening. Equation (2) marks an observation when its residual differs from the reference mean by more than three residual standard deviations.
e t = y t − y ^ t A ,   | e t − μ e | > 3 σ e
In Equation (2), ŷtᴬ is the ARIMA estimate, et is the associated residual, and μe and σe are the residual mean and standard deviation. This flag indicates statistical unusualness, not the physical source of the observation.
We supplemented the conventional 3σ rationale [18] with a diagnostic refit of ARIMA(1,1,1), without drift, to all 329 raw hydrogen observations in their stored row order. This is an exploratory full-record diagnostic, not a training-only recalibration of the original experiment. Excluding the first initialization residual leaves 328 residuals with mean −0.1703 μL/L and sample standard deviation 1.5648 μL/L. Their skewness is 16.88 and excess kurtosis is 298.93; the Jarque–Bera normality test gives p < 0.001. The lag-10 Ljung–Box statistic is 0.4024 (eight degrees of freedom; p = 0.9999), although the extreme outlier limits interpretation of this non-rejection. Residual normality is therefore unsupported, and a nominal Gaussian 3σ probability must not be treated as a measured false-alarm rate. Multipliers 2, 2.5, 3 and 3.5 all flag only row 234 in this refit (Table A3; Figure A3). This identifies the dominant spike but also demonstrates that the three archived replacements cannot all be reproduced by this refit alone.
For each flagged sample, the concurrent operating-channel changes are summarized by Equation (3).
C t = ( T t − T t − 1 max T t − 1 ε T ) 2 + ( I t − I t − 1 max I t − 1 ε I ) 2 + ( P t − P t − 1 max P t − 1 ε P ) 2
The operating-state check is a contextual screen rather than proof of sensor error. To make a forward implementation well defined, the denominators in Equation (3) are now max(|xt−1|, εx) for x ∈ {T, I, P}; temperature T is expressed in kelvin. Each εx is fixed from the positive instrument resolution or, when that resolution is unavailable, the first percentile of positive absolute training-channel magnitudes. An entirely zero channel is excluded and explicitly flagged as unavailable. The threshold τ is defined as the empirical 95th percentile of Ct over an independently verified stable training segment and is then frozen for later observations. A flagged gas excursion with Ct ≥ τ is retained for operating-event review. A value below τ permits only a suspected-disturbance label: replacement additionally requires measurement-quality evidence or expert confirmation. The exported gas worksheets contain no operating-channel values, so this amendment specifies a reproducible rule rather than claiming that channel calibration or fault exclusion has been verified on those worksheets. Archived interpolation is retained solely for reproducing the retrospective figures; it must not be used to create online observations before its right-hand endpoint is measured.

2.3. Whale-Tuned Variational Mode Decomposition

VMD represents a signal as modes with compact bandwidths around estimated center frequencies [19]. It solves a constrained variational problem in which the modes sum to the input; the bandwidth-minimization form used here is given in Equation (4).
min { u k } , { ω k } ∑ k = 1 K ‖ ∂ t [ ( δ ( t ) + j π t ) ∗ u k ( t ) ] e − j ω k t ‖ 2 2 subject   to   ∑ k = 1 K u k ( t ) = y ( t )
In Equation (4), uk(t) is the kth mode, ωk its center frequency, δ(t) the Dirac distribution, j the imaginary unit, and the asterisk the convolution operator. The constrained problem is optimized with an augmented Lagrangian and alternating-direction updates. K controls the number of components and α controls the bandwidth penalty, so both parameters influence the representation presented to the predictors.
A whale optimization search selects the decomposition parameters through encircling, spiral and exploratory moves [20]. Candidate decompositions are scored with a coefficient-of-determination criterion on an internal training/validation split, as written in Equation (5).
F ( K , α ) = 1 − ∑ t ∈ V ( y t − y ^ t ( K , α ) ) 2 ∑ t ∈ V ( y t − y ¯ V ) 2
Here, V is the internal validation index set, ȳᵥ is the validation mean, and ŷt(K,α) is the forecast produced by a candidate pair. The search uses integer K values from 2 to 8 and α values from 30 to 5000, with 20 population members and 20 iterations. For the hydrogen illustration, the selected pair is K = 8 and α = 500; these values are example-specific rather than universal optima.
At iteration s, the standard encircling and exploration rules use A = 2ar − a and C = 2r, with a decreasing linearly from 2 to 0. Equation (6) collects the three position-update forms.
X s + 1 = X s * − AD   ( p < 0.5 ,   | A | < 1 ) X s + 1 = X r − A D r   ( p < 0.5 ,   | A | ≥ 1 ) X s + 1 = D ′ e bl cos ( 2 π l ) + X s *   ( p ≥ 0.5 )
The vector X denotes a candidate parameter pair, X* the best candidate so far and Xᵣ a randomly chosen population member. The quantities D = |CX* − X|, Dᵣ = |CXᵣ − X| and D′ = |X* − X| are the corresponding distances. The random switch p chooses encircling/exploration for p < 0.5 and the spiral branch otherwise, while |A| controls local versus exploratory motion. In the spiral term, b is the spiral coefficient and l is sampled from [−1, 1]. K is constrained to integer values in the search interval. The task-specific element is the forecasting score; the population updates follow the established whale-search mechanism.
The reported WOA search uses K = 2–8, α = 30–5000, population 20 and 20 iterations. We added a deterministic local VMD sensitivity check on the first 328 cleaned hydrogen rows with K ∈ {6, 7, 8}, α ∈ {250, 500, 1000}, τVMD = 0, no imposed DC mode, uniform frequency initialization and stopping tolerance 10−7. Here τVMD is the VMD dual-ascent setting, not the operating-state threshold τ. Reconstruction RMSE ranges from 0.02108 to 0.08536 μL/L across the nine settings. At K = 8 and α = 500, it is 0.03715 μL/L, reproducing the archived summed-mode reconstruction error to numerical precision. Lower reconstruction error at another setting does not imply better validation forecasting: the WOA objective in Equation (5) is predictive R2. Table A4 reports all nine settings and iteration counts. These are deterministic VMD convergence results, not reconstructed WOA search histories or repeated-seed optimization evidence.

2.4. Component Forecasting and Dynamic Fusion

Each component is supplied with a sliding window containing its latest 15 values. Ridge regression maps that window to the next component value with an L2 penalty, as expressed in Equation (7) [21].
β ^ = arg   min β { ‖ v − X β ‖ 2 2 + λ ‖ β ‖ 2 2 }
In Equation (7), X and v contain the component windows and targets, β is the coefficient vector, and λ is the regularization coefficient. The penalty limits coefficient growth when adjacent lags are strongly correlated. Using λ for Ridge regularization keeps it distinct from the VMD bandwidth parameter α. Ridge is compact and effective for locally smooth component trajectories, but it is not designed to reproduce every rapid or nonlinear transition.
GRUs supply a nonlinear recurrent alternative through update and reset gates [22]; their state transition is written in Equation (8).
z t = σ ( W z x t + U z h t − 1 + b z ) r t = σ ( W r x t + U r h t − 1 + b r ) h ~ t = tanh ( W h x t + U h ( r t ⊙ h t − 1 ) + b h ) h t = ( 1 − z t ) ⊙ h t − 1 + z t ⊙ h ~ t
In Equation (8), zt and rt are the update and reset gates, h ~ t is the candidate hidden state, and ht is the updated recurrent state. The tilde is attached to the symbol h, with t retained as its subscript, in both the third-line definition and the fourth-line update. The symbols σ and ⊙ denote the logistic function and element-wise multiplication, respectively; W, U and b are trainable parameters. This notation correction does not change the GRU computation.
The third member is a BiLSTM, which combines LSTM memory cells [23] with bidirectional processing [24]. Both directions operate only inside the observed input window; the backward branch therefore describes dependencies within the historical segment and does not use observations after the forecast origin. The two directional states are concatenated before mapping to the next component value. A common window length makes the temporal span comparable across all three predictor classes.
Every predictor class produces one forecast for each IMF. Equation (9) sums those component forecasts to recover the corresponding gas-level prediction.
y ^ m , t + 1 = ∑ k = 1 K u ^ m , k , t + 1 ,   m ∈ { R , G , B }
The index m identifies Ridge, GRU or BiLSTM. Their reconstructed concentrations can differ because the three model classes extrapolate component trajectories in different ways.
After reconstruction, the meta-network receives six descriptors: sequence progress, volatility over the preceding five samples, a local trend slope, and the preceding five-step mean absolute error for each predictor. Equation (10) defines the feature vector and the weighted reconstruction.
f t = [ q t , s t , b t , E R , t , E G , t , E B , t ] w t = g θ ( f t ) ,   ∑ m ∈ { R , G , B } w m , t = 1 y ^ t + 1 = ∑ m ∈ { R , G , B } w m , t y ^ m , t + 1
Here, qt is sequence progress, st recent volatility, bt the local slope, and Em,t the recent error of member m. The mapping gθ is a small multilayer perceptron that returns time-varying weights summing to one. Its objective minimizes fused mean squared error on the internal validation split, as stated in Equation (11).
L ( θ ) = 1 | V | ∑ t ∈ V ( y t + 1 − ∑ m w m , t y ^ m , t + 1 ) 2
Error descriptors tell the fusion layer how the members have performed recently, while the sequence descriptors indicate whether the current segment differs from its immediate history. A larger Ridge weight is plausible for smooth trajectories, whereas recurrent members may receive more weight during nonlinear changes. The reported aggregate scores support the combination itself; they do not identify which individual descriptor caused a particular weight shift.
For the forward six-step protocol specified in this revision, network parameters and the complete six-component descriptor vector are frozen at forecast origin t. Sequence progress, volatility, slope and the three recent MAEs are calculated from observations available through t; each MAE uses only already observed prediction–measurement pairs. The meta-network is evaluated once at t, and its three weights are held fixed for steps t + 1 through t + 6 while each base model recursively updates its own 15-value input window with predictions. After the next measurement arrives, descriptors may be refreshed for a new forecast origin. This defines a six-step open-loop block without future-error inputs. The saved 99-row illustration has five weight columns, with mean Ridge weight 0.8361 and all row sums equal to one within floating-point precision; its maximum discrepancy between the saved fusion and the direct five-weighted sum is 0.01993 μL/L. It is therefore used only to describe archived weight behavior, not as verification of the three-member six-step implementation or its scores. Figure A1 states the information boundary.

3. Experimental Design and Evaluation

3.1. Monitoring Data and Forecast Tasks

The normal-operation dataset comes from a power-supply utility and contains daily observations of H2, CH4, C2H6, C2H4, CO and CO2. Core-grounding current, active power and oil temperature are recorded alongside the gases and are used for the cleaning check. Figure 2 illustrates the hydrogen record and its operating channels. Hydrogen is used for the preprocessing and decomposition examples, whereas all six gases enter the quantitative evaluation. The abnormal methane sequence is the transformer case reported in [12] and supplies a separate concentration-growth scenario.
Figure 2. Monitoring channels used for the operating-state consistency check: (a) hydrogen concentration; (b) daily mean core-grounding current; (c) daily mean active power; and (d) daily mean oil temperature.
For one-step prediction, a 15-observation history estimates the next observation; six-step forecasting recursively feeds predictions into later windows. A six-step horizon equals six days only for a complete daily grid. The archived hydrogen screening record contains gaps and duplicate dates, so its row-based supplementary audit is interpreted in observation steps. One visual excerpt of the multigas forecast archive covers the first 720 h of the full dataset; this selected interval is not the complete evaluation record. Another separate model-pool comparison dataset uses a 12 h grid and must not be described as the same daily test partition.
The archived hydrogen screening worksheet contains 329 observation rows spanning 21 July 2025 to 15 July 2026 under the Origin adjusted-Julian date convention. It contains 327 distinct dates: 319 consecutive row intervals are one day, two intervals are zero and seven are longer than one day. The VMD worksheet contains 328 component rows. A separate hydrogen forecast worksheet contains 99 observed values, exactly matching the last 99 cleaned hydrogen observations, with 230 earlier rows available as history. The multigas forecast worksheet contains 94 observed–predicted pairs per gas on a relative 24 h grid from 24 to 2256 h; these are saved forecast pairs, not complete training histories. Its additional C2H2 series is identically zero and is excluded from R2 and percentage-error comparisons. The abnormal CH4 worksheet contains 100 forecast pairs at indices 240–339 with an 8 h interval, and the model-pool comparison contains 60 pairs on a 12 h grid from 12 to 720 h. Table A2 identifies these distinct records. Calendar dates and fitting/validation membership cannot be transferred between worksheets solely because the gas names agree.

3.2. Training, Tuning, and Baseline Protocol

Within the training records, 80% of the observations are used for fitting and 20% for validation. The validation portion supports VMD parameter selection and meta-network fitting. Table 1 lists the numerical settings. The comparison pool contains Ridge, GRU, BiLSTM, support vector regression (SVR) and FEDformer. FEDformer is a frequency-enhanced decomposition architecture developed for long-horizon time-series forecasting [25]; here it serves as a higher-capacity comparison under the same data and tuning constraints.
Table 1. Numerical configuration of the forecasting pipeline and CPU timing benchmark.
A new controlled hydrogen experiment quantifies the effect of the decomposition boundary. It uses the 329 raw stored rows, with no cleaning or operating-state check, and evaluates the same final 99 one-step targets after an initial 230-row history. Three predictors use a 15-observation window and Ridge penalty 1: raw-series Ridge, Ridge on a full-series VMD representation, and Ridge with VMD recomputed using only the history available at each origin. VMD uses K = 8, α = 500, τVMD = 0, no imposed DC mode, uniform initialization and tolerance 10−7. An odd-length history is extended by repeating its last observed value for decomposition and that padded position is removed. Each mode is standardized and its Ridge fit is recomputed from the available historical component windows; future target values never enter the rolling decomposition, scaling or fitting. This is a component-level Ridge audit, not a retraining of the complete neural fusion architecture. Full-series VMD gives R2 = 0.9799 and RMSE = 0.3913 μL/L, whereas past-only VMD gives R2 = −0.8362 and RMSE = 3.7409 μL/L; raw-series Ridge gives R2 = −1.3506 and RMSE = 4.2326 μL/L. The difficult raw spike is retained in all three arms. These results demonstrate a material optimism effect for full-series decomposition in this audit. The stored row order, including duplicate dates and gaps, defines sequence steps; this audit is not a regular-calendar daily forecast.
The primary retrospective tables and the new historical-only Ridge audit address different questions. The former compare fitted model families under common full-series decomposition; the latter isolates the decomposition information boundary on fixed raw hydrogen targets. The frozen-descriptor six-step protocol is specified in Section 2.4 and is not assigned the retrospective six-step scores. The newly added historical-only results establish that a common preprocessing representation can still make a comparison optimistic; prospective claims require evaluating every component of the complete architecture under the same past-only boundary.

3.3. Evaluation Metrics

Performance is summarized with the coefficient of determination R2, mean absolute error (MAE) and root mean square error (RMSE) in Equation (12); MAPE is additionally given for the abnormal-operation case.
R 2 = 1 − ∑ i = 1 n ( y i − y ^ i ) 2 ∑ i = 1 n ( y i − y ¯ ) 2 MAE = 1 n ∑ i = 1 n | y i − y ^ i | RMSE = 1 n ∑ i = 1 n ( y i − y ^ i ) 2
In Equation (12), n is the number of evaluation samples, yi and ŷi are the measured and predicted values, and ȳ is the mean of the evaluation set. Algebraically, R2 = 0 is the score obtained by predicting that same mean, while a negative value means that the squared error is larger than this reference. This is an evaluation baseline rather than a separately trained historical-mean model. Positive and negative R2 are used descriptively to indicate relative deterioration, not as transformer fault thresholds.
For normal operation, the tables report MAE on the benchmark scale and RMSE in percentage form. For the abnormal case, RMSE is expressed in concentration units and MAPE in percent. MAE and percentage RMSE are compared only within the same gas and task; their magnitudes should not be compared directly across differently scaled gases or cases. Equation (13) gives MAPE for nonzero observations.
MAPE = 100 % n ∑ i = 1 n | y i − y ^ i y i |

4. Results and Discussion

4.1. Screening and Decomposition Outcomes

The archived hydrogen worksheet replaces rows 234–236 from 41.21, 16.65 and 15.51 μL/L to 14.0325, 14.4250 and 14.8175 μL/L, respectively. These replacements exactly interpolate in row order between 13.64 and 15.21 μL/L, with an increment of 0.3925 μL/L. Two of these replaced rows share the date 10 April 2026, and the following row is dated 11 April. They are therefore three observation rows rather than three distinct daily timestamps. The original description gives a residual standard deviation of 1.29 μL/L and a 3.87 μL/L threshold; the new full-record refit in Section 2.2 gives 1.5648 μL/L and flags only the dominant 41.21 μL/L spike over all four tested multipliers. The archived edits and the newly fitted statistical flags are reported separately. Figure 3 documents the saved raw and interpolated trajectories; the gas-only export does not establish the physical cause of the spike.
Figure 3. Archived raw and interpolated hydrogen trajectories. Three stored rows are replaced; the gas-only worksheet does not verify the physical cause. Cross markers (×): missing and corrected observation points.
This example shows how operating information enters the screening decision. It does not provide sensitivity or specificity estimates because independently labelled sensor disturbances and genuine gas events are unavailable. The result should therefore be understood as a channel-supported cleaning decision, not as proof of the physical cause of every flagged point.
For the hydrogen illustration, VMD selects K = 8 and α = 500; the resulting components are shown in Figure 4. The first mode carries the dominant slow trajectory and later modes contain progressively faster oscillations, which can make component extrapolation easier. Assigning a physical meaning to any one mode would require additional evidence from operating variables. Frequency order alone cannot establish which mode represents ageing, loading seasonality or sensor noise. All eight component forecasts are retained for reconstruction.
Figure 4. Hydrogen decomposition into eight intrinsic mode functions using VMD with K = 8 and α = 500; the horizontal axis is the sample index.

4.2. Normal-Operation Forecasts

The one-step scores are listed in Table 2. Fusion gives R2 values of 0.9806 for H2, 0.9936 for CH4, 0.9896 for C2H6, 0.9670 for C2H4, 0.9217 for CO and 0.9953 for CO2. Thus, every gas exceeds 0.92 in the fused R2 under the retrospective preprocessing protocol. Figure 5 plots four representative one-step trajectories over the 720 h display interval, with insets showing local discrepancies.
Table 2. One-step forecasts for the six normal-operation gases. MAE is reported on the benchmark scale, and Eᵣ is the percentage-form RMSE; bold entries mark the best displayed value within each gas and metric, including ties.
Figure 5. Archived normal-operation forecast trajectories over the first 720 h of the 94-pair-per-gas archive. The saved fusion version is reconciled separately with the original aggregate scores in Table A8. (a) H2 concentration forecast results; (b) CH4 concentration forecast results; (c) C2H6 concentration forecast results; (d) CO2 concentration forecast results. Black solid line: Observed; blue dotted line: GRU; magenta dashed line: SVR; light blue dotted line: Meta; orange dashed line: Ridge; green dash-dot line: BiLSTM; yellow dashed line: FEDformer.
The benefit of the pool varies with the gas. For CH4, fusion raises R2 from Ridge’s 0.9933 to 0.9936 and lowers MAE from 0.0196 to 0.0188. For C2H6, R2 increases from 0.9875 to 0.9896, and MAE falls from 0.0085 to 0.0075. For H2 and CO2, the fused R2 equals Ridge to four displayed decimals. These results indicate that a regularized linear model already explains much of the predictable structure after decomposition.
Fusion is not the top-ranked method in every one-step task. GRU reaches R2 = 0.9720 for C2H4, above fusion at 0.9670. For CO, BiLSTM reaches 0.9284 versus 0.9217 for fusion, although fusion has a slightly lower MAE (0.8656 versus 0.8721). The changing metric rankings argue against universal-superiority claims; they instead show high R2 overall with modest gains and small trade-offs across gases.
SVR and FEDformer are weaker on several of these sequences. SVR is negative for H2, CH4 and CO2, and FEDformer is negative for CH4. These observations do not make either architecture universally unsuitable; they describe its behavior under this limited-data comparison, shared preprocessing and selected configurations.
The six-step recursive results appear in Table 3. Fused R2 is 0.8292, 0.9418, 0.9131, 0.7759, 0.6749 and 0.9584 for H2, CH4, C2H6, C2H4, CO and CO2, respectively. All remain positive, but the reduction relative to the one-step setting illustrates the extra uncertainty introduced by recursive extrapolation.
Table 3. Six-step recursive forecasts for the six normal-operation gases, using the notation and within-gas highlighting of Table 2.
The CO/CO2 contrast demonstrates the fragility of fixing one model across gases. For CO, Ridge falls from one-step R2 = 0.7225 to six-step R2 = −0.4665, whereas GRU and BiLSTM retain 0.6831 and 0.6843 and fusion reaches 0.6749. For CO2, the ordering reverses: Ridge reaches 0.9588 while GRU and BiLSTM fall to −0.0419 and −0.3589; fusion remains close to Ridge at 0.9584. These complementary error patterns motivate retaining both linear and recurrent members.
The fused model again does not dominate the strongest member in every task. Ridge is better for six-step H2, C2H4 and CO2, while BiLSTM is better for CO; fusion has the highest displayed R2 for CH4 and C2H6. At this horizon, Ridge, GRU and BiLSTM each have one negative score; SVR has four, FEDformer three, and fusion none.
Table A5 and Figure A2 retain the descriptive comparison of the original Table 2 and Table 3: fusion is higher than the best displayed individual R2 in four of twelve gas–horizon tasks, tied in two and lower in six. We additionally recomputed errors from all 94 saved forecast pairs per gas (Table A8). In this archive, fusion exactly equals Ridge for CH4 and CO2, GRU for C2H4 and BiLSTM for CO; H2 and C2H6 have small distinct fusion trajectories. The saved fusion R2 values are 0.9807, 0.9933, 0.9879, 0.9719, 0.9284 and 0.9953, respectively. Several differ from the original aggregate fusion values, so the supplementary computations are explicitly labeled as archived-trajectory analyses and are presented separately from the original score matrix. The exact matches show why an adaptive ensemble need not improve on its strongest member. A measurable fusion benefit depends on useful complementary errors; strongly concentrated weights and redundant errors can produce equality or deterioration.
We added paired circular-block bootstrap intervals using the complete 94-point archived trajectories for each gas. The comparator is the individual model with the lowest archived MSE for that gas, selected once and held fixed. Both models and the observations are resampled with identical contiguous circular blocks; 5000 replicates use random seed 20261120. Block lengths 5, 10 and 20 examine sensitivity to retained temporal dependence. The statistic is 100 × (1 − MSEfusion/MSEcomparator), so a positive value denotes lower fusion MSE. At block length 10, H2 has a 0.61% reduction with a pointwise 95% percentile interval [−3.20%, 4.65%], while C2H6 has a 2.82% reduction with interval [0.33%, 7.32%]. The other four trajectories are exactly equal to their comparators, giving zero differences. These intervals are exploratory and conditional on the saved models, comparator selection and retrospective preprocessing; they do not correct for multiple comparisons, measure random-training-seed variability or validate prospective forecasting. Table A9 and Figure A5 report the intervals at all three block lengths. The C2H6 result is evidence of a small difference in this archive, not a general significance claim.

4.3. Abnormal Methane Case and Predictor-Pool Comparison

Table 4 summarizes the abnormal methane experiment and Figure 6 shows the associated trajectories. Fusion and Ridge have the same displayed scores: R2 = 0.9967, RMSE = 0.9515 and MAPE = 1.03%. GRU and BiLSTM obtain R2 values of 0.6964 and 0.5914, FEDformer obtains 0.1854, and SVR falls to −0.7499.
Table 4. Forecasting metrics for the abnormal-operation methane case. RMSE is in μL/L, and MAPE is in percent; Ridge and fusion are tied at the shown precision.
Figure 6. Abnormal methane forecast trajectories at indices 240–339 with 8 h spacing. Meta is the worksheet column labeled Meta (column I), which matches Ridge, rather than the separate pure-Meta column H.
The abnormal example suggests that a linear component predictor can remain useful during a rapid concentration rise. Smooth decomposed components may still be locally extrapolated well by Ridge. Because Ridge and fusion are tied, the result demonstrates parity with the strongest baseline rather than an additional accuracy gain. Weight histories and component-level errors would be required to determine whether the fusion layer selected Ridge through changing combinations.
The abnormal methane worksheet contains 100 observed–predicted pairs at indices 240–339, corresponding to an elapsed span of 792 h at 8 h spacing. The column labeled Meta is exactly equal to Ridge at all 100 saved precisions and reproduces R2 = 0.9967116, RMSE = 0.9514849 μL/L and MAPE = 1.02716%. A separate column labeled pure Meta has slightly different predictions, giving RMSE = 0.9517562 μL/L; it is not substituted for the Meta result in Table 4. Thus, the reported rounded tie is supported by the actual saved trajectories, but it provides no evidence of added fusion accuracy. This single event evaluates concentration tracking, not fault-type classification, event detection or alarm calibration. Transfer to other transformer designs, loads, oil types, ageing stages and discharge mechanisms requires independent events and the corresponding operating and fault labels.
Figure 7 further compares predictor-pool composition using the normal-operation methane sequence. The alternatives are Ridge–BiLSTM, Ridge–GRU, SVR–GRU–BiLSTM and SVR–GRU. The proposed pool follows the displayed local changes closely, whereas some alternatives diverge more during the later rise. This visual example illustrates the effect of member selection for methane, but it is not a substitute for quantitative ablation over all gases and horizons.
Figure 7. Archived normal-operation methane forecasts from different predictor pools on the separate 12 h grid. Proposed denotes the saved adaptive Ridge–GRU–BiLSTM pool; the inset enlarges the marked interval.

4.4. Runtime Assessment and Study Limitations

The CPU benchmark was run on an Intel Core i5-13500H laptop with 16 logical processors and approximately 15.6 GB of memory. Table 5 compares the prediction workloads. Serial fusion takes 1.453 s; batching across IMFs reduces this to 1.010 s, batching only across pool members gives 1.404 s, and batching across both dimensions gives 0.996 s. Combining the latter with eight-core parallel execution reduces runtime to 0.434 s, a 3.35-fold speedup over serial fusion.
Table 5. CPU times for the benchmark prediction workload. Speedup is measured relative to the 1.453 s serial fusion implementation, not relative to individual baseline models.
The optimized runtime is comparable to the reported GRU and BiLSTM times of 0.285 and 0.497 s. FEDformer requires 40.931 s, about 94 times the optimized fusion time, whereas Ridge requires only 0.047 s. Thus, batching and parallel scheduling can limit the overhead of maintaining multiple predictors, but they do not make fusion the fastest model in this comparison.
The original stored model occupies approximately 1.0 MB. The 1.453 to 0.434 s benchmark is a 3.35-fold reduction in its prediction workload. In the new 99-origin historical-only Ridge audit, each timed origin includes historical VMD, component scaling, refitting all component Ridge predictors and generating one reconstructed forecast. The measured median is 0.0503 s per origin, with observed range 0.0117–0.1264 s on an AMD Ryzen 5 5600 workstation with 12 logical processors and 31.94 GiB RAM; data loading and plotting are excluded. The analysis uses Python 3.12 and vmdpy 0.2. These measurements are reported separately from the original laptop benchmark because the algorithms and hardware environment differ. They demonstrate the actual cost of this restricted rolling implementation, not the complete ARIMA–WOA–neural-fusion pipeline. Table A6 distinguishes the measured workloads. A complete architecture benchmark must additionally execute screening and operating checks, WOA, neural training and its stated retuning schedule; a saved plotting project cannot supply those execution times.
Across gases, the main pattern is complementarity between linear and recurrent predictors. Ridge performs well on several smooth decomposed sequences, while recurrent members help for CO and C2H4. Adaptive fusion offers a way to retain these alternatives without imposing one model on every gas. The aggregate errors support this interpretation, although the specific causes of individual weight changes remain unresolved.
The added analyses resolve several reporting gaps but also narrow the interpretation. The raw-hydrogen audit demonstrates substantially optimistic full-series VMD scores, and the saved fusion trajectories do not consistently reproduce the original aggregate fusion table. The six-step forward update rule is now explicit, while the new block-bootstrap intervals quantify conditional trajectory uncertainty. None of these additions constitutes repeated neural training or a full historical-only fusion rerun. Prospective accuracy, optimizer repeatability and end-to-end neural-pipeline latency therefore remain separate validation questions.
The data scope is also narrow. Six gases and one abnormal methane example cannot replace independent tests across transformer designs, utilities and fault mechanisms. The small-data motivation should be examined with explicit learning curves rather than inferred from history length alone. Future ablations should separate physical verification, VMD tuning and adaptive weighting, including comparisons against Ridge alone, equal-weight fusion and static validation-based weights under a causal evaluation protocol.
The forecasts are statistical extrapolations conditional on the observed history. Oil temperature, core-grounding current and active power support screening but are not direct forecasting inputs, and no future loading or temperature scenario, insulation-ageing law or gas-generation/transport model is imposed. The practical assumption is that the relationships represented by the recent history persist over the forecast horizon. Relatively stable operation makes this assumption more plausible, but an abrupt load change, cooling intervention, maintenance action or new internal fault may invalidate it even when earlier prediction errors were small. Forecasts should therefore be treated as conditional trend estimates, checked against new measurements and operating events, rather than as reliable predictions under arbitrary future conditions. Physics-informed or multivariate extensions and independent operating-regime tests are needed to assess this limitation.

5. Conclusions

The proposed workflow combines operating-state-assisted screening, optimized VMD and adaptive fusion of Ridge, GRU and BiLSTM component forecasts for transformer dissolved-gas prediction. ARIMA residuals provide the initial flags, while concurrent oil temperature, current and active power provide a consistency check. VMD supplies multiple component series, and the meta-network combines their reconstructed predictions using sequence context and recent errors.
With retrospective preprocessing, fused R2 ranges from 0.9217 to 0.9953 at one step and from 0.6749 to 0.9584 at six steps across the six gases. Every reported normal-operation combination remains positive, although an individual member is better in several gas–horizon cases. For abnormal methane, fusion matches Ridge at R2 = 0.9967, RMSE = 0.9515 μL/L and MAPE = 1.03%. Eight-core batched inference reduces the benchmark from 1.453 to 0.434 s.
The supplied archives support a more qualified conclusion. Adaptive fusion can coincide exactly with a strong member, and small differences require pointwise uncertainty analysis and consistent experiment versions. The added raw-hydrogen experiment demonstrates that historical-only VMD can yield substantially poorer accuracy than a full-series representation. Accordingly, the reported retrospective scores support an architectural comparison but do not establish deployable forecasting or early-warning performance. A complete historical-only fusion experiment, repeated training, independent transformer records and verified operating-channel calibration are required before those stronger claims.

Author Contributions

Conceptualization, J.Y. and Y.Z.; methodology, J.Y. and Y.Z.; software, G.L.; validation, Y.Z. and X.G.; formal analysis, Y.Z., G.L. and J.W.; investigation, J.Y., Y.Z., G.L., Q.T. and Z.L.; resources, G.L., J.W., Q.T. and X.G.; data curation, G.L. and X.G.; writing—original draft, X.G., Z.L. and X.Z.; writing—review and editing, J.W., Q.T., X.G., Z.L. and X.Z.; visualization, J.W. and X.Z.; supervision, Z.L. and X.Z.; project administration, X.Z.; funding acquisition, X.Z. All authors have read and agreed to the published version of the manuscript.

Funding

This research was supported by the Science and Technology Project of China Southern Power Grid [Project number: GDKJXM20240459].

Data Availability Statement

The data presented in this study are available from the corresponding author upon reasonable request. The data are not publicly available because they contain operational information on power transmission and transformation equipment and are subject to the confidentiality requirements of the collaborating organization.

Conflicts of Interest

Authors Yin Zhang, Guowei Li, Junbo Wang and Qi Tang were employed by the company Foshan Power Supply Bureau of Guangdong Power Grid Co., Ltd. The remaining authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as potential conflicts of interest. The authors declare that this study received funding from the Science and Technology Project of China Southern Power Grid. The funder had no role in the design of this study; in the collection, analysis, or interpretation of data; in the writing of the manuscript; or in the decision to publish the results.

Appendix A. Supplementary Analyses of Archived Records

Appendix A contains newly computed evidence from the six archived Origin projects. Table A2 reports worksheet counts and time fields; Table A3 and Figure A3 contain a diagnostic ARIMA refit; Table A4 contains a nine-setting VMD sensitivity check; Table A7 and Figure A4 compare raw, retrospective-decomposition and past-only-decomposition Ridge forecasts; Table A8 and Table A9 and Figure A5 use saved pointwise forecasts for error reconciliation and block-bootstrap intervals. The new calculations are kept distinct from the original aggregate scores in Table 2, Table 3 and Table 4. No original fitting/validation membership, WOA repetitions or neural training runs are inferred from the plotting worksheets.
Table A1. Diagnostic context and the scope of concentration forecasting.
Table A2. Direct inventory of saved worksheet records and their time coordinates. Forecast pairs are not complete training histories.
The supplementary past-only Ridge audit uses an explicit 230-row initial history and 99 subsequent one-step targets, with no validation tuning. This new partition is not asserted to be the original neural-model fitting/validation partition. Relative time axes do not establish calendar monitoring dates.
Table A3. Empirical multiplier sensitivity in the new full-record ARIMA(1,1,1) diagnostic refit.
Residual reference: 328 residuals after excluding initialization; mean −0.1703 μL/L, sample SD 1.5648 μL/L. All multipliers select the same dominant spike. These are full-record diagnostic flags; no fault labels, false-alarm rate or downstream forecasting robustness is inferred.
Table A4. Newly computed deterministic VMD sensitivity on the first 328 cleaned hydrogen rows.
Fixed settings: dual ascent τVMD = 0, no imposed DC mode, uniform frequency initialization and tolerance 10−7. Iteration counts are returned VMD center-frequency update rows. The original WOA budget is population 20 × 20 iterations with K = 2–8 and α = 30–5000. This table measures decomposition sensitivity, not repeated WOA convergence or predictive R2 robustness.
Table A5. Fusion R2 relative to the best displayed individual-model R2 in Table 2 and Table 3. Δ is fusion minus that reference; ties refer only to displayed precision.
This is a descriptive calculation from one reported score matrix, not a repeated-run or statistical-significance analysis.
Table A6. Measured timing workloads, kept separate by implementation and hardware context.
The new audit was measured once in Python with a high-resolution elapsed-time clock; it excludes loading and plotting. It uses fixed VMD settings and Ridge, so it is not a full WOA/neural-fusion timing. Its measurements must not be pooled with the original laptop benchmark or presented as repeated-run performance bounds.
Table A7. New controlled one-step Ridge audit on the final 99 raw hydrogen targets.
All arms use identical raw targets, retain the spike, start with 230 observations, and use a 15-observation window and Ridge penalty 1. Mode fitting and scaling use historical windows; only the full-series arm obtains its representation from all observations. This controlled audit is not a complete fusion-model rerun.
Table A8. Reconciliation of fusion scores calculated from the 94-pair multigas archive with the original one-step aggregate table.
All supplementary uncertainty calculations use the complete saved trajectories, not rounded original aggregate scores. The original score matrix and archived-trajectory version are reported separately. Exact equality is assessed on the saved numerical values.
Table A9. Paired circular-block bootstrap of archived fusion MSE reduction relative to the best archived individual predictor.
5000 paired resamples; seed 20261120; n = 94 per gas. Intervals are pointwise percentile intervals, conditional on fixed saved predictions and a post hoc comparator; they are not random-training-seed confidence intervals. Zero intervals arise from exactly equal saved trajectories.
Figure A1. Information boundary required for prospective forecasting. The six-step block withholds future measurements and their errors; the schematic specifies a validation requirement, not a completed causal experiment.
Figure A2. Fusion minus the best displayed individual-model R2 for each normal-operation gas and horizon. Values are calculated from Table 2 and Table 3; they do not show uncertainty or statistical significance.
Figure A3. Newly fitted full-record hydrogen ARIMA residuals and normal Q–Q plot. The extreme positive tail contradicts a Gaussian residual assumption.
Figure A4. New raw-hydrogen Ridge audit with identical forecast targets. Full-series and past-only VMD produce materially different results; the raw spike is retained.
Figure A5. Exploratory pointwise 95% paired block-bootstrap intervals for archived fusion MSE reduction. Block lengths 5, 10 and 20 retain different ranges of temporal dependence; exact trajectory matches give zero differences.

References

  1. IEC 60599:2022; Mineral Oil-Filled Electrical Equipment in Service—Guidance on the Interpretation of Dissolved and Free Gases Analysis. International Electrotechnical Commission (IEC): Geneva, Switzerland, 2022. Available online: https://webstore.iec.ch/en/publication/66491 (accessed on 24 November 2026).
  2. IEEE Std C57.104-2019; IEEE Guide for the Interpretation of Gases Generated in Mineral Oil-Immersed Transformers. Institute of Electrical and Electronics Engineers (IEEE): New York, NY, USA, 2019. Available online: https://standards.ieee.org/ieee/C57.104/7476/ (accessed on 24 November 2026).
  3. IEC 60567:2023; Oil-Filled Electrical Equipment—Sampling of Free Gases and Analysis of Free and Dissolved Gases in Mineral Oils and Other Insulating Liquids—Guidance. International Electrotechnical Commission (IEC): Geneva, Switzerland, 2023. Available online: https://webstore.iec.ch/en/publication/70013 (accessed on 24 November 2026).
  4. Rangel Bessa, A.; Farias Fardin, J.; Marques Ciarelli, P.; Frizera Encarnação, L. Conventional dissolved gases analysis in power transformers: Review. Energies 2023, 16, 7219. [Google Scholar] [CrossRef] [Scilit]
  5. Wang, C.; Xie, J.; Zhang, Y.; Qiao, C.; Xie, Q.; Dong, F. Prediction for dissolved gas in power transformer oil based on transfer learning and mutation detection. IEEE Trans. Dielectr. Electr. Insul. 2025, 32, 3628–3637. [Google Scholar] [CrossRef] [Scilit]
  6. Cui, Y.; Hou, H.; Xu, M.; Li, S.; Sheng, G.; Jiang, X. A prediction method for dissolved gas in power transformer oil based on dual-stage attention mechanism. Proc. CSEE 2020, 40, 338–347, 400. (In Chinese) [Google Scholar]
  7. Yang, T.; Hu, D.; Tang, C.; Fang, Y.; Xie, J. Prediction of dissolved gas content in transformer oil based on SMA-VMD-GRU model. Trans. China Electrotech. Soc. 2023, 38, 117–130. (In Chinese) [Google Scholar] [CrossRef]
  8. Xie, L.; Qiu, W.; Li, Z.; Liu, Y.; Jiang, Q.; Liu, D. Prediction model of dissolved gas in transformer oil based on variational modal decomposition and recurrent neural network with gated recurrent unit. High Volt. Eng. 2022, 48, 653–660. (In Chinese) [Google Scholar]
  9. Fan, Z.; Du, J. Prediction of dissolved gas volume fraction in transformer oil based on correlation variational mode decomposition and CNN-LSTM. High Volt. Eng. 2024, 50, 263–273. (In Chinese) [Google Scholar]
  10. Du, J.; Fan, Z.; Fan, Z.; Wang, Q.; Li, P. Research on abnormal data identification and content prediction of dissolved gas in power transformer oil. Power Syst. Technol. 2025, 49, 844–853. (In Chinese) [Google Scholar]
  11. Jia, J.; Zhang, S.; Li, K.; Lu, B. Transformer monitoring data cleaning method based on ARIMA and HO-BiLSTM. High Volt. Eng. 2025, 51, 5801–5811. (In Chinese) [Google Scholar] [CrossRef]
  12. Ma, H.; Xiao, Y.; Sun, Y.; Li, Y.; Zhu, L.; Xu, H. Prediction of dissolved gas concentration in transformer oil based on ICEEMDAN and time-varying weight integrated prediction model. High Volt. Eng. 2024, 50, 210–220. (In Chinese) [Google Scholar]
  13. Lei, L.; He, Y.; Xing, Z.; Li, Z.; Zhou, Y. Physics-informed LSTM-based time-series forecasting model for power transformers. IEEE Trans. Ind. Inform. 2025, 21, 5411–5419. [Google Scholar] [CrossRef] [Scilit]
  14. Said, M.; Anwar, T.; El-Rifaie, A.M.; Ismaeel, A.A.K.; Elaziz, E.M.A.; Accouche, O.; Ibrahim, K.H. Performance of a newly developed hybrid APO–PSO metaheuristic for monitoring of intelligent transformer. Machines 2026, 14, 185. [Google Scholar] [CrossRef] [Scilit]
  15. Said, M.; Ismaeel, A.A.K.; El-Rifaie, A.M.; Hashim, F.A.; Bouaouda, A.; Hassan, A.Y.; Abdelaziz, A.Y.; Houssein, E.H. Evaluation of modified fire hawk optimizer for new modification in double diode solar cell model. Sci. Rep. 2024, 14, 30079. [Google Scholar] [CrossRef] [Scilit] [PubMed]
  16. Houssein, E.H.; Ismaeel, A.A.K.; Said, M. Optimum solution of power flow problem based on search and rescue algorithm. Sci. Rep. 2024, 14, 28367. [Google Scholar] [CrossRef] [Scilit] [PubMed]
  17. Ismaeel, A.A.K.; Houssein, E.H.; Khafaga, D.S.; Aldakheel, E.A.; Abdelrazek, A.S.; Said, M. Performance of snow ablation optimization for solving optimum allocation of generator units. IEEE Access 2024, 12, 17690–17707. [Google Scholar] [CrossRef] [Scilit]
  18. NIST/SEMATECH. Section 6.3.1, What Are Control Charts? In e-Handbook of Statistical Methods; NIST: Gaithersburg, MD, USA, 2002. Available online: https://www.itl.nist.gov/div898/handbook/pmc/section3/pmc31.htm (accessed on 18 November 2026).
  19. Dragomiretskiy, K.; Zosso, D. Variational mode decomposition. IEEE Trans. Signal Process. 2014, 62, 531–544. [Google Scholar] [CrossRef] [Scilit]
  20. Mirjalili, S.; Lewis, A. The whale optimization algorithm. Adv. Eng. Softw. 2016, 95, 51–67. [Google Scholar] [CrossRef] [Scilit]
  21. Hoerl, A.E.; Kennard, R.W. Ridge regression: Biased estimation for nonorthogonal problems. Technometrics 1970, 12, 55–67. [Google Scholar] [CrossRef]
  22. Cho, K.; van Merriënboer, B.; Gulcehre, C.; Bahdanau, D.; Bougares, F.; Schwenk, H.; Bengio, Y. Learning phrase representations using RNN encoder–decoder for statistical machine translation. In Proceedings of the 2014 Conference on Empirical Methods in Natural Language Processing, Doha, Qatar, 25–29 October 2014; pp. 1724–1734. [Google Scholar] [CrossRef] [Scilit]
  23. Hochreiter, S.; Schmidhuber, J. Long short-term memory. Neural Comput. 1997, 9, 1735–1780. [Google Scholar] [CrossRef] [Scilit] [PubMed]
  24. Schuster, M.; Paliwal, K.K. Bidirectional recurrent neural networks. IEEE Trans. Signal Process. 1997, 45, 2673–2681. [Google Scholar] [CrossRef] [Scilit] [PubMed]
  25. Zhou, T.; Ma, Z.; Wen, Q.; Wang, X.; Sun, L.; Jin, R. FEDformer: Frequency enhanced decomposed Transformer for long-term series forecasting. Proc. Mach. Learn. Res. 2022, 162, 27268–27286. Available online: https://proceedings.mlr.press/v162/zhou22g.html (accessed on 24 November 2026).
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Article Metrics

Citations

Article Access Statistics

Multiple requests from the same IP address are counted as one view.