Abstract
High-transformation-ratio DC transformers are key equipment for large-capacity DC collection and transmission systems, where high transformation ratio, power capability, and economic performance must be considered simultaneously. This paper investigates the steady-state modeling and coordinated control of a hybrid face-to-face high-ratio DC transformer (HFTF) composed of a low-voltage current-source converter (CSC), a medium-frequency isolation transformer, and a high-voltage modular multilevel converter (MMC). A steady-state model considering the CSC two-degree-of-freedom fundamental-frequency modulation and AC filter is established, and the operating region is derived by incorporating DC-voltage and MMC constraints. Based on this model, a CSC control scheme with outer-loop regulation, feedforward decoupling, and dq-axis current control is developed, together with a full-power-range reactive power droop strategy for CSC-MMC coordination. The results show that the proposed method maintains stable DC-voltage regulation and reactive power sharing over a wide power range, while reducing the overall cost by about 15% compared with the conventional MMC-FTF scheme. Electromagnetic transient simulations and low-power prototype experiments further verify the effectiveness and feasibility of the proposed HFTF and its coordinated control strategy.
1. Introduction
The global energy and power sectors are undergoing profound transformation, with renewable energy becoming a major driving force in the development of future power systems. As the generation costs of wind and solar power continue to decline [1,2], the global energy transition is accelerating [3,4]. Driven by China’s carbon-peaking and carbon-neutrality targets, renewable energy development is progressing simultaneously onshore and offshore. Large-scale wind and photovoltaic bases in desert, Gobi, and arid regions are continuing to expand, with a planned installed capacity of 450 GW by 2030 [5]. Meanwhile, far-offshore wind power is becoming an important direction for large-scale renewable energy development because of its stable wind resources and limited land occupation [6,7]. As the capacity and collection range of renewable energy bases continue to increase, conventional AC collection and step-up transmission schemes face challenges associated with weak-grid stability, reactive power compensation, and submarine-cable charging power. Therefore, DC collection and step-up transmission has become an important option for long-distance and large-capacity renewable energy delivery [8,9]. As a key component in DC collection and transmission systems, the DC transformer (DCT) performs DC voltage conversion, power transmission, and power regulation [10,11]. For example, in large-scale far-offshore wind power transmission systems, the transmission-side DC voltage may reach several hundred kilovolts, whereas the collection-side voltage is generally much lower because of the insulation limitations of wind turbine terminals [12]. Therefore, DCTs for single-stage DC step-up transmission are required to simultaneously achieve a high transformation ratio, large power capacity, and favorable economic performance.
According to their circuit structures, DCTs can generally be classified into non-isolated and isolated types. In non-isolated DCTs, the high- and low-voltage sides are directly electrically connected, and internal AC/DC power transfer paths are usually constructed using submodule-based converter arms. A direct autotransformer-type DCT was proposed in [13], while a three-phase parallel configuration was further adopted in [14] to improve its power-transfer capability. Although such topologies have relatively simple structures, additional filtering equipment is required to suppress AC components on the DC side, and the low-voltage side current stress becomes significant under high transformation ratio conditions. The autotransformer-type DCT with an AC transformer branch in [15] can reduce the filtering requirement but introduces additional transformer equipment. Capacitive-energy-transfer topologies [16] realize an “input–storage–output” energy transfer process using submodules without an intermediate AC transformer; however, device voltage balancing and synchronized control become challenging at high transformation ratios [17]. The switched-capacitor autotransformer DCT based on two-port submodules in [18] can reduce the required filter inductance but increases submodule complexity and device count. In general, non-isolated DCTs feature high device utilization and compact structures, but their device electrical stress and direct electrical coupling between the high- and low-voltage sides become increasingly pronounced under high transformation ratio conditions [19].
Isolated DCTs generally employ a DC–AC–DC power conversion process and use an intermediate AC transformer to provide electrical isolation and voltage matching, making them more suitable for high transformation ratio applications [20]. Existing studies have mainly focused on improving transformer connection schemes and converter structures. For example, the voltage level can be increased by connecting the high-voltage sides of multiple transformers in series [21], or the transformer windings can be connected in series [22] or in parallel [23] with submodule-based converter arms to reduce the number of power semiconductor devices. Converter arms can also be reconstructed by combining fully controlled devices with submodules to reduce converter cost [24]. These approaches can improve the voltage adaptability of isolated DCTs; however, under large capacity conditions, they still generally require a large number of fully controlled devices and consequently exhibit relatively high conversion losses and equipment costs [25]. Therefore, high transformation ratio and large capacity DCTs require not only optimized voltage conversion structures but also appropriate converter configurations according to the different voltage and current stresses on the high- and low-voltage sides.
To overcome the performance limitations of converters based on a single converter type, recent studies have explored hybrid configurations combining power units or semiconductor devices with different characteristics. Reference [26] combines dual active bridge and resonant modules to balance controllability and operating efficiency, although the overall structure is more suitable for modular medium- and low-voltage applications. Reference [27] combines different types of converter arms to reduce the number of fully controlled devices, but this also increases the complexity of the operating mechanism and control system. These studies indicate that configuring different converter units according to the electrical stresses and functional requirements of different ports is an effective approach to improving the overall performance of DCTs [28].
Based on the above considerations, this paper investigates a hybrid face-to-face high transformation ratio DC transformer (HFTF) consisting of a low-voltage side current source converter (CSC), a medium-frequency isolation transformer, and a high-voltage side modular multilevel converter (MMC), targeting high transformation ratio DC conversion characterized by high current on the LV side and high voltage on the HV side. A steady-state model considering the dual-degree-of-freedom fundamental-frequency modulation of the CSC and the influence of the AC filter is established, and the DC voltage constraint and overall operating region are analyzed. Based on this model, a CSC DC voltage control method and a full power range CSC–MMC reactive power coordination strategy are developed, and the cost and operating efficiency of the proposed topology are evaluated. Finally, electromagnetic transient simulations and low-power prototype experiments are performed to verify the effectiveness of the proposed model and control method.
2. Materials and Methods
2.1. HFTF Topology
Figure 1 shows the topology of the hybrid face-to-face high transformation ratio DC transformer (HFTF). The topology consists of a low-voltage current source converter (CSC), an intermediate-frequency AC transformer, and a high-voltage modular multilevel converter (MMC). The low-voltage CSC and high-voltage MMC are connected face-to-face through the intermediate-frequency AC link to realize voltage conversion, power transmission, and electrical isolation between the low- and high-voltage DC ports.
Figure 1.
Topology of the HFTF DC transformer.
The low-voltage CSC is composed of a three-phase six-arm converter valve. A DC smoothing reactor Ldc is connected in series on the DC side to suppress low-voltage DC current ripple. The CSC AC side is equipped with a filter capacitor Cf and a filter inductor Lf. The capacitor Cf supports CSC commutation, while Lf and Cf form the AC filter, which attenuates valve-side current harmonics and improves the quality of the AC current injected into the transformer. The high-voltage side employs a three-phase MMC.
The MMC provides modular scalability and controllability, whereas the CSC offers high current-carrying capability and comparatively low power loss, making it suitable for the large current stress on the low-voltage side. Coupled through the intermediate-frequency AC transformer, the two converters are well suited to high transformation ratio, large-capacity DC voltage conversion applications such as renewable energy DC collection and transmission.
2.2. Basic Operating Principle
In the HFTF-DCT, input power from the low-voltage DC side is converted by the CSC into intermediate-frequency AC power, filtered and stepped up through the intermediate-frequency transformer, and then rectified by the high-voltage MMC into high-voltage DC power.
The CSC primarily regulates the low-voltage DC voltage and the reactive power of the intermediate-frequency AC link. In renewable energy DC collection systems, upstream renewable energy converters typically operate under MPPT or power control modes, so the collection bus voltage must be maintained by the downstream DC transformer. The CSC therefore regulates its AC output current to keep the low-voltage DC-port voltage at its reference value. Meanwhile, it adjusts reactive power output according to the reactive power demand of the intermediate-frequency AC system, thereby limiting the reactive power flowing into the MMC and reducing MMC current stress and operating loss.
The MMC primarily establishes and maintains the intermediate-frequency AC voltage, providing the voltage support required for CSC commutation and power transfer. Consequently, the HFTF adopts the basic coordinated operating principle of “MMC establishes the AC voltage, while CSC regulates the AC current,” as illustrated in Figure 2.
Figure 2.
Power transfer and control function allocation of the HFTF.
3. Steady-State Modeling and Operating Region Analysis of the HFTF
3.1. Dual-Degree-of-Freedom Fundamental-Frequency Modulation Model of the CSC
To enhance the power-regulation capability of the HFTF, a dual-degree-of-freedom fundamental-frequency modulation method is adopted. The CSC valve-side fundamental current is jointly regulated by the phase-shift angle and the arm shoot-through compensation angle, thereby reducing switching frequency and loss while retaining sufficient control freedom. Taking phase A and arms 1 and 4 as an example, the switching signals and output-current waveforms are shown in Figure 3.
Figure 3.
Dual-degree-of-freedom fundamental-frequency modulation waveforms of the CSC.
The angle α is defined as the phase-shift angle of the CSC valve-side current, and θ is defined as the arm shoot-through compensation angle. The angle α mainly changes the phase of the valve-side current, whereas θ determines the shoot-through interval of the converter arm. During shoot-through, the upper and lower arms of one phase conduct simultaneously, so no current is delivered to the AC side; this interval is used to regulate the amplitude of the current fundamental component. The key switching instants in Figure 3 are listed in Table 1.
Table 1.
Key switching instants in Figure 3.
Let Idc,L denote the steady-state low-voltage DC current of the CSC. Under dual-degree-of-freedom fundamental-frequency modulation, the three-phase fundamental components of the CSC valve-side current can be expressed as:
where ipa1, ipb1, and ipc1 are the fundamental components of the three-phase CSC valve-side currents, and ω is the angular frequency of the intermediate-frequency AC link. Applying the dq transformation to the CSC valve-side fundamental currents gives:
where ipd and ipq are the d- and q-axis components of the CSC valve-side fundamental current, respectively, and md and mq are the corresponding d- and q-axis components of the CSC current modulation index, expressed as:
The equivalent CSC current modulation index is further defined as:
Therefore, α determines the direction of the CSC valve-side fundamental-current vector in the dq frame, whereas θ determines its magnitude. This model directly links the CSC modulation angles to the valve-side current fundamental components and forms the basis for the subsequent power transfer model.
3.2. CSC Power Transfer Model
To establish the relationship between the CSC modulation variables and the AC side power of the HFTF, the low-voltage CSC, AC filter, intermediate-frequency transformer, and high-voltage MMC are represented in a unified dq reference frame.
The HFTF AC port voltage vector is aligned with the d-axis, yielding:
where Us is the amplitude of the fundamental phase voltage at the CSC AC port. According to the equivalent circuit in Figure 4, the CSC valve-side current and the filtered current satisfy:
usd = Us,usq = 0
Figure 4.
Steady-state equivalent circuit of the HFTF in the dq reference frame.
The above relationship shows that the filter capacitor introduces a reactive current component on the q-axis that is associated with the AC voltage, while the filter inductor affects the magnitude of the filtered current through the factor 1 − ω2LfCf. Therefore, the AC filter not only determines harmonic attenuation but also modifies the steady-state reactive power distribution of the HFTF.
By combining usd = Us and usq = 0 and substituting the CSC valve-side fundamental-current model derived in Section 3.1, the AC-side active and reactive powers of the HFTF can be expressed as:
Define the initial reactive power component introduced by the AC filter as:
Then:
Qac = Q0 − Pactanα
This relationship indicates that, for a fixed phase-shift angle α, the HFTF AC-side operating point lies on a straight line in the P-Q plane. Varying α changes the slope of this line, which is referred to as the α-constraint.
Alternatively, eliminating α gives:
where
Thus, θ determines the radius of the power vector that can be produced by the CSC. As θ increases, the power-transfer capability decreases; this boundary is referred to as the θ-constraint. In summary, α mainly determines the direction of the AC power vector, whereas θ mainly determines the available power-regulation range. The AC filter affects the CSC-side operating characteristics through the reactive power offset Q0 and the current amplification factor, as shown in Figure 5a.
Figure 5.
Power operating range of the CSC.
Changes in intermediate electrical parameters will further affect the operating range of the CSC, as shown in Figure 5b. Increasing Cf enlarges the power-boundary radius and shifts its center upward, enhancing the CSC’s reactive power output across the operating range. Increasing Lf has a relatively minor effect on the center position, while progressively enlarging the power boundary radius.
3.3. DC-Voltage Constraint
In the HFTF, the CSC must maintain the low-voltage-side DC voltage. Therefore, α and θ cannot be selected solely according to the AC-side active- and reactive power demands; they must also satisfy the low-voltage DC-port voltage constraint. Neglecting converter losses, the low-voltage DC power and AC-side active power satisfy:
Udc,LIdc,L = Pac
Substituting the expression for Pac gives the low-voltage DC voltage as:
The above expression shows that, once us and the filter parameters are fixed, the low-voltage DC voltage is jointly determined by α and θ. Under constant low-voltage DC-voltage operation, α and θ satisfy:
This relationship shows that when both the transmitted power and the low-voltage DC voltage are fixed at 1 p.u., α and θ are not independent. Increasing θ reduces the equivalent CSC AC-side output capability; therefore, α must be reduced accordingly to maintain Udc,L. If θ becomes too large, sin(π/6−θ) is insufficient to satisfy the DC-voltage requirement, and no feasible steady-state operating point exists. The feasible range of θ can also be derived from the DC-voltage constraint. Accordingly:
It follows that an increase in the low-voltage DC-voltage reference, or a decrease in the AC voltage Us, narrows the feasible range of θ and reduces the CSC power regulation margin.
3.4. Overall Operating Region Considering MMC Constraints
The steady-state operation of the HFTF is also limited by the capability of the high-voltage MMC. Because the MMC must establish the intermediate-frequency AC voltage while carrying AC current, its operating range is constrained mainly by the modulation index, rated current, arm current, and submodule voltage. Combining these MMC limits with the CSC operating constraints derived in Section 3.2 and Section 3.3, the final steady-state operating region is given by their intersection, as shown in Figure 6.
Figure 6.
Overall steady-state operating region of the HFTF.
As shown in Figure 6, the overall operating range of the HFTF is jointly determined by the CSC-side and MMC-side constraints. At low active power, the CSC DC-voltage constraint and the reactive power offset introduced by the AC filter have a more pronounced influence on the operating point. Near rated active power, the CSC current-modulation capability and MMC rated-current limit jointly determine the maximum transferable power. It should be noted that, as a DC transformer, the external operating characteristic of the HFTF corresponds to the projection of this operating region onto the P-axis, while internal reactive power balance supports the stability of the intermediate AC voltage. From a control perspective, the overall operating region provides the constraint boundary for command limiting and operating-point selection in the coordinated-control strategy developed below.
4. Control Method of the HFTF
4.1. CSC DC-Voltage and Reactive Power Control
The low-voltage CSC of the HFTF maintains the low-voltage DC voltage and regulates AC-side reactive power according to its reference. The low-voltage DC-voltage outer loop generates the d-axis AC-current reference, while the reactive power outer loop generates the q-axis AC-current reference. With the AC-port voltage vector aligned with the d-axis:
Accordingly, the CSC outer loops can be expressed as:
where i*sd and i*sq are the d- and q-axis AC-port current references, respectively; i*sd0 and i*sq0 are the steady-state feedforward values; and GU(s) and GQ(s) are the DC-voltage controller and reactive power controller, respectively. When Udc,L exceeds its reference, the DC-voltage loop increases i*sd to increase the active power transferred to the high-voltage side; the opposite action is taken when Udc,L falls below its reference.
According to the AC-filter relationship derived in Section 2, the valve-side current references can be obtained from the AC-port current references through feedforward compensation:
The feedforward term compensates for the influence of the AC filter on current magnitude and reactive-current components. On this basis, closed-loop dq current correction is introduced to obtain the CSC valve-side current references:
where Gid(s) and Giq(s) are the d- and q-axis current controllers, respectively. The current loops compensate for model mismatch, AC-voltage disturbances, and filter dynamic deviations, thereby improving CSC current-tracking performance. The CSC current-modulation components are then obtained from the valve-side current references:
The equivalent current modulation index is further given by:
According to the CSC dual-degree-of-freedom fundamental-frequency modulation model, the modulation-angle references are:
To ensure realizable modulation commands, the current references and modulation index must be limited so that the operating point satisfies:
where ΩHFTF is the overall steady-state operating region obtained in Section 2, and mmax is the maximum allowable CSC current modulation index. Thus, the CSC controller combines steady-state-model-based feedforward decoupling with current-loop dynamic correction, providing stable low-voltage DC-voltage control and reactive power regulation. The overall control structure is shown in Figure 7.
Figure 7.
CSC DC-voltage and reactive power control block diagram.
4.2. MMC AC-Voltage Control
The high-voltage MMC of the HFTF primarily establishes the intermediate-frequency AC voltage required for CSC commutation. In this paper, the MMC adopts V-f control to maintain constant AC-voltage magnitude and frequency. With the AC-voltage vector aligned with the d-axis, the control objective can be expressed as:
where U*s is the reference magnitude of the intermediate-frequency AC voltage and f*s is the reference AC frequency. The HFTF therefore adopts a coordinated operating mode in which the MMC maintains the intermediate-frequency AC-voltage magnitude and frequency, while the CSC regulates active and reactive power under this voltage support. The MMC control objective is illustrated in Figure 8.
Figure 8.
MMC AC-voltage V-f control block diagram.
4.3. CSC Reactive Power Reference Droop and Coordination with the MMC
As shown in Section 2, the CSC AC filter introduces an initial reactive power component Q0 into the intermediate-frequency AC link. At high transmitted power, the CSC has strong reactive power regulation, allowing the CSC to adjust its own reactive power output such that the MMC-side reactive power approaches zero, thereby reducing MMC current stress. At low active power, however, the CSC reactive power regulation range is reduced by the DC-voltage constraint and current-modulation limits. If zero MMC reactive power is still enforced, the CSC modulation angles may exceed their allowable range or the operating point may leave the feasible region. Therefore, the MMC must absorb part of the reactive power at low power and gradually withdraw from reactive power balancing as active power increases.
Define Q*CSC,0(Pac) as the CSC reactive power reference required to make the MMC reactive power zero. When Q*CSC,0(Pac) lies within the feasible CSC reactive power range:
The MMC reactive power reference is then:
At low active power, Q*CSC,0(Pac) exceeds the CSC reactive power regulation range, and the MMC absorbs the remaining reactive power. Its reference can be expressed as:
To avoid abrupt transitions between operating regions, a reactive power droop strategy varying with active power is adopted. Let Pq denote the critical active power at which MMC reactive power decreases to zero and let Pmin denote the minimum continuous operating power. In the low-power region, the MMC reactive power reference can be set as:
where QM0 is the reactive power to be absorbed by the MMC at the minimum-power operating point, and PN is the rated active power. The CSC reactive power reference is correspondingly modified according to AC-side reactive power balance as:
Accordingly, the CSC and MMC jointly balance reactive power in the low-power region. Once active power reaches Pq, the CSC has sufficient reactive power capability; the MMC reactive power reference falls to zero, and the system enters a CSC-dominated reactive power-compensation region. The coordinated characteristic is shown in Figure 9.
Figure 9.
Full power range reactive power reference coordination characteristic.
The essence of the CSC–VSC coordination is that the establishment of a stable AC voltage causes the LC filter to generate the initial reactive power Q0. Under low-power operation, the CSC has limited regulation capability, and the two converters therefore jointly balance the intermediate reactive power. In practical control, QMMC can also be directly used as the CSC outer-loop reference to simplify the computation. The above droop strategy can be embedded in the CSC reactive power outer loop in Section 4.1, with the droop block generating the CSC reactive power outer-loop reference according to the real-time active power Pac. The overall HFTF control structure is shown in Figure 10.
Figure 10.
CSC-MMC coordinated control structure.
With this coordinated strategy, the HFTF can account for both CSC modulation capability and MMC current margin over the full power range. At low power, the MMC absorbs part of the reactive power introduced by the filter and AC link, thereby preventing the CSC reactive power command from exceeding its feasible range. At high power, the CSC provides the main reactive power compensation, allowing the MMC to operate close to unity power factor.
5. Key Technical Specifications and Economic Evaluation
5.1. Key Technical Specifications
To evaluate the technical and economic performance of the HFTF in high-transformation-ratio DC collection and transmission applications, the key technical specifications used in this paper are listed in Table 2.
Table 2.
Key technical specifications of the HFTF.
These specifications provide a common basis for the subsequent cost and efficiency calculations. For a fair comparison, the MMC-FTF scheme is evaluated using the same DC-voltage levels, rated capacity, and intermediate AC frequency.
5.2. Cost Analysis
The costs of the HFTF and MMC-FTF are estimated under identical voltage levels, rated power, and operating frequency, based on preliminary quotations from electrical equipment manufacturers and cost data from relevant engineering projects. The assessment includes converter valves, valve control and cooling systems, DC reactors, AC LC filters, and the intermediate-frequency isolation transformer. Station auxiliary power systems, civil works, installation, station-level control and protection systems, and operation and maintenance costs are excluded. All costs are normalized to the total cost of the listed equipment in the MMC-FTF scheme, taken as 1 p.u. The device types and quantities used in the HFTF are listed in Table 3.
Table 3.
Device types and quantities of the HFTF.
Based on the above device configuration, the cost comparison between the HFTF and MMC-FTF is given in Table 4. The total cost of the MMC-FTF is normalized to 1 p.u., and the low-voltage-side, high-voltage-side, and total cost components are listed separately.
Table 4.
Cost comparison between the HFTF and MMC-FTF.
The resulting cost composition is shown in Figure 11.
Figure 11.
Cost-composition comparison between the HFTF and MMC-FTF.
Table 4 and Figure 11 show that the main cost difference between the HFTF and MMC-FTF is concentrated on the low-voltage side. The MMC-FTF employs an MMC on the low-voltage side, and the combined cost of the low-voltage MMC valve and its valve-control/cooling system is 0.356 p.u. After replacing the low-voltage MMC with a CSC, the HFTF introduces a DC reactor, CSC valve, and LC filter, but the total low-voltage-side cost still decreases to 0.206 p.u. Accordingly, the low-voltage-side cost of the HFTF is reduced by approximately 42%, while the total cost is reduced by 15.0%. This result indicates that replacing the MMC valve and its auxiliary systems with the CSC valve group and associated equipment is the primary source of the HFTF cost advantage.
5.3. Efficiency Analysis
To evaluate the efficiency of the proposed HFTF topology, a comparative loss analysis is conducted against the conventional MMC-FTF topology under identical operating conditions. The loss calculation considers semiconductor conduction and switching losses, snubber circuit losses, reactor and capacitor losses, and transformer losses. Specifically, semiconductor losses are calculated based on the device characteristics and operating conditions; reactor and capacitor losses are evaluated using their equivalent resistances and RMS currents; and transformer losses are evaluated based on winding copper losses only. For a consistent comparison, the semiconductor losses of both topologies are calculated using device characteristics at a reference junction temperature of approximately 125 °C, without considering temperature variations or cooling-system auxiliary losses. The total power loss and overall efficiency are expressed as
where Pout is the output power, and the six loss terms represent conduction, switching, snubber circuit, reactor, capacitor, and transformer losses, respectively.
Ploss = Pcond + Psw + Psnub + Preact + Pcap + Ptr
Figure 12 presents the efficiency characteristics and loss distributions of the two topologies under different loading conditions. As shown in Figure 12a, the HFTF consistently achieves higher efficiency than the MMC-FTF over the investigated load range, with the efficiency advantage becoming more pronounced at higher loads. At the rated power of 2 GW, the total losses of the HFTF and MMC-FTF are 50.958 MW and 62.000 MW, respectively, corresponding to efficiencies of approximately 97.52% and 96.99%. The HFTF thus reduces the total power loss by 11.042 MW, or approximately 17.8%. This improvement is primarily attributed to the reduced converter losses on the low-voltage side, where the conventional MMC is replaced by a high-current-capability CSC. As illustrated in Figure 12b, the overall semiconductor conduction losses decrease from 15.81 MW to 8.84 MW, while the switching losses decrease from 34.84 MW to 30.36 MW. The combined reduction in semiconductor losses reaches 11.45 MW. Meanwhile, the reactor losses decrease from 4.62 MW to 3.07 MW, whereas the transformer losses remain identical at 6.16 MW. These results demonstrate that the proposed hybrid topology effectively improves conversion efficiency by reducing semiconductor losses, particularly those associated with the low-voltage converter, while maintaining the high-voltage conversion capability.
Figure 12.
Efficiency and power loss comparison between HFTF and MMC-FTF.
Together with the cost analysis in Section 5.2, these results show that the HFTF can reduce both the amount and cost of fully controlled devices on the low-voltage side and the conversion losses in the low-voltage, high-current power path, thereby improving the overall economic performance of the DC transformer.
6. Simulation and Experimental Verification
6.1. Simulation Analysis
An electromagnetic-transient model of the 2 GW HFTF was established in MATLAB/Simulink R2022a (The MathWorks, Inc., Natick, MA, USA). The rated system specifications are listed in Table 2, while the key circuit parameters of the simulation model are given in Table 5. The model was used to verify the operating characteristics of the intermediate-frequency AC link, the transient response under active-power steps, and the effectiveness of the full-power-range coordinated control.
Table 5.
Key circuit parameters of the 2 GW HFTF simulation model.
The operating characteristics of the intermediate-frequency AC link are shown in Figure 13. In Figure 13a, the stepped CSC valve-side currents become nearly sinusoidal after LC filtering, while the filter-capacitor voltage remains stable. In Figure 13b, the CSC valve-side DC voltage pulsates with arm commutation, whereas the DC reactor maintains a stable low-voltage DC voltage. Substituting the steady-state modulation angles and circuit parameters into Equation (7) gives Pac = 2021.1 MW and Qac = 382.5 Mvar, compared with simulated values of 1995.3 MW and 395.1 Mvar. The corresponding relative errors, referenced to the analytical values, are 1.28% and 3.29%.
Figure 13.
Steady-state operating waveforms of the HFTF.
As shown in Figure 14a, following the 200 MW and 300 MW power steps, the low-voltage DC voltage decreases to 0.92 p.u. (8% deviation) and 0.86 p.u. (14% deviation), respectively, and recovers within approximately 1.19 s and 1.46 s. Here, the settling time is defined as the interval from the power-step instant until the DC voltage returns to and remains within ±2% of its reference value. The larger voltage deviation during the 300 MW step is primarily attributed to the increased transient power imbalance. Due to the current rate-of-change limitation imposed by the CSC DC smoothing reactor and the finite bandwidths of the voltage outer loop and current inner loops, the transferred power cannot respond instantaneously to the command change, resulting in a greater temporary voltage deviation and a longer recovery time. Nevertheless, the DC voltage returns to approximately 1 p.u. with negligible steady-state error after both disturbances, demonstrating the effectiveness of the proposed control strategy. As shown in Figure 14b, the CSC and MMC reactive powers undergo brief transient adjustments, after which the MMC reactive power returns to approximately zero, confirming the coordinated reactive-power regulation capability.
Figure 14.
HFTF operating waveforms under an active-power step.
Finally, the active-power command is continuously varied to evaluate the coordinated-control performance over the full operating range, as shown in Figure 15. Figure 15a shows that, as active power gradually increases from a low-power operating point, the low-voltage DC voltage remains close to its reference and the adjustment of the reactive-power reference causes no significant disturbance to the DC voltage. Figure 15b illustrates the reactive-power sharing between the CSC and MMC. In the low-power region, the CSC cannot fully provide the required reactive-power compensation and the MMC must absorb part of the reactive power. The reactive-power outer-loop reference was set as Q*MMC = (1200 − Pac)/4 for Pac < 1200, and Q*MMC = 0 for Pac > 1200, with active and reactive power expressed in MW and Mvar, respectively. In the simulation, at 800 MW the CSC supplied 148 Mvar while the MMC absorbed 103 Mvar; at 1200 MW, these values were 183 and 7 Mvar, respectively, showing the transition to CSC-dominated reactive-power compensation, as shown in Figure 15b, thereby verifying the proposed reactive power droop and coordinated-control strategy.
Figure 15.
HFTF coordinated operating waveforms over the full power range.
6.2. Experimental Verification
To further verify the feasibility of the HFTF operating principle and control method, a low-power scaled experimental platform is constructed. A two-level VSC is used to emulate the external characteristics of the MMC. The overall experimental platform is shown in Figure 16. Its key parameters are listed in Table 6. The equipment used for the experimental platform was supplied by Beijing Yinfei Xinye Technology Co., Ltd. (Beijing, China).
Figure 16.
Overall structure of the experimental platform.
Table 6.
Key specifications of the experimental platform.
The steady-state experimental results are shown in Figure 17. The symmetrical filter-capacitor line voltages and nearly sinusoidal filtered currents in Figure 17a, together with the stable DC voltage and current in Figure 17b, demonstrate steady power transfer. Substituting the extracted steady-state modulation angles and prototype circuit parameters into Equation (7) gives Pac = 1399.6 W and Qac = 303.2 Var, compared with measured steady-state averages of 1351.2 W and 287.1 Var. The respective relative errors are 3.46% and 5.31%, supporting the steady-state model at the prototype scale. The slightly larger reactive-power error is mainly associated with its higher sensitivity to voltage–current phase deviations and AC-filter parameter uncertainties, including sensor and sampling-filter errors and component tolerances. In addition, parasitic impedances and nonideal switching characteristics, which are simplified in the fundamental-frequency analytical model, may contribute to the observed discrepancy. These results demonstrate that the prototype can achieve stable DC-voltage conversion and power transfer, verifying the feasibility of steady-state HFTF operation.
Figure 17.
Steady-state operating waveforms of the experimental prototype.
The dynamic experimental results are shown in Figure 18. During changes in the power command, the magnitudes of the intermediate-frequency AC voltage and current vary smoothly with the operating point, while the low-voltage DC current changes in accordance with the transmitted power. After the power step, the DC current peaks at 22.6 A, exceeding its 20 A reference by 2.6 A (13%). It reaches a new steady-state after approximately 0.687 s at 19.2 A, corresponding to a steady-state error of −0.8 A (−4%). The CSC active and reactive powers and the MMC reactive power transition smoothly to their new steady-state values. The experimental results confirm that the proposed control method can maintain stable AC and DC operation while achieving coordinated power regulation.
Figure 18.
Dynamic operating waveforms of the experimental prototype.
The two-level VSC used in the 1.5 kW prototype reproduces the AC-voltage-support function of the high-voltage MMC required for the investigated steady-state CSC control and coordinated operation. However, it does not reproduce MMC-specific submodule voltage balancing, circulating-current and arm-energy dynamics, or the insulation and thermal constraints of a 2 GW implementation. Consequently, the prototype validates the CSC modulation, fundamental power-transfer mechanism, and coordinated-control principle, whereas full-scale converter losses and MMC internal performance are assessed separately through the 2 GW model and engineering-level calculations.
7. Conclusions
This paper investigates the steady-state modeling and coordinated control of a hybrid face-to-face DC transformer (HFTF) for high-transformation-ratio, large-capacity DC collection and transmission applications. The main conclusions are as follows:
- A steady-state HFTF model considering CSC dual-degree-of-freedom fundamental-frequency modulation and the influence of the AC filter is established. The relationships among the modulation angles, AC/DC voltages, and active/reactive powers are clarified, and the overall operating region is obtained by combining the DC-voltage and MMC constraints.
- A CSC control method based on outer-loop control, model-based feedforward decoupling, and dq-axis current inner loops is developed. A full-power-range reactive-power-reference droop and CSC-MMC coordinated-control strategy is further proposed to maintain the low-voltage DC voltage and achieve appropriate reactive-power sharing at different power levels.
- Cost and efficiency analyses show that replacing the low-voltage MMC with a CSC reduces converter-equipment cost and low-voltage-side conversion loss. The total cost of the HFTF is approximately 15% lower than that of the MMC-FTF.
Finally, electromagnetic transient simulations of the 2 GW system verified the operating characteristics of the proposed topology and control method. Experiments on a small-scale prototype further demonstrated the feasibility of the CSC modulation method, the operating principle of the DC transformer, and the overall control method.
Author Contributions
Conceptualization, C.G.; methodology, Z.L., C.W. and C.G.; validation, C.W., C.L. and K.C.; formal analysis, C.W. and K.C.; investigation, C.W. and C.L.; data curation, C.W.; writing—original draft preparation, C.W.; writing—review and editing, C.W., C.L. and Z.L. and Y.W.; project administration, C.G., Y.W. and K.C.; funding acquisition, C.G., Z.L. and Y.W. All authors have read and agreed to the published version of the manuscript.
Funding
This research was funded by the Self-funded Science and Technology Project of the China Electric Power Research Institute: “Research on Topology and Control Methods of High Transformation Ratio and Large Capacity DC Transformers”, grant number 525500230006.
Data Availability Statement
The original contributions presented in this study are included in the article. Further inquiries can be directed to the corresponding author.
Conflicts of Interest
The authors, Chenyang Wei, Zhiguang Lin, Chong Gao, Chi Liu, Yanan Wu and Kailong Chen, were employed by China Electric Power Research Institute. The authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as potential conflicts of interest.
Abbreviations
The following abbreviations are used in this manuscript:
| CSC | current source converter |
| MMC | modular multilevel converter |
| FTF | face-to-face |
| NLM | nearest level modulation |
| DFFM | dual-degree-of-freedom fundamental-frequency modulation |
| HV | high voltage |
| LV | low voltage |
References
- Energy Transitions Commission. Power Systems Transformation: Delivering Competitive, Resilient Electricity in High-Renewable Systems; Energy Transitions Commission: London, UK, 2025; Available online: https://www.energy-transitions.org/publications/power-systems-transformation/ (accessed on 20 August 2026).
- International Renewable Energy Agency. Renewable Power Generation Costs in 2024; International Renewable Energy Agency: Abu Dhabi, United Arab Emirates, 2025; Available online: https://www.irena.org/Publications/2025/Jun/Renewable-Power-Generation-Costs-in-2024 (accessed on 20 August 2026).
- Guterres, A. A Moment of Opportunity: Supercharging the Clean Energy Age. United Nations, 22 July 2025. Available online: https://china.un.org/en/298453-op-ed-%E2%80%9C-moment-opportunity-supercharging-clean-energy-age%E2%80%9D (accessed on 30 July 2025).
- International Energy Agency. Renewables 2024: Analysis and Forecasts to 2030; IEA: Paris, France, 2024; Available online: https://www.iea.org/reports/renewables-2024 (accessed on 20 August 2026).
- Wang, Y.; Jiang, C.; Song, S.; Yang, P.; Xiong, L.; Liu, M. Transmission scheme for large-scale renewable energy bases in Gobi desert and other arid areas based on integration of source, grid, DC and storage. Autom. Electr. Power Syst. 2025, 49, 126–134. [Google Scholar] [CrossRef]
- Edwards, E.C.; Holcombe, A.; Brown, S.; Ransley, E.; Hann, M.; Greaves, D. Evolution of floating offshore wind platforms: A review of at-sea devices. Renew. Sustain. Energy Rev. 2023, 183, 113416. [Google Scholar] [CrossRef] [Scilit]
- Lakshmanan, P.; Sun, R.; Liang, J. Electrical collection systems for offshore wind farms: A review. CSEE J. Power Energy Syst. 2021, 7, 1078–1092. [Google Scholar] [CrossRef] [Scilit]
- Tang, G.; Luo, X.; Wei, X. Multi-terminal HVDC and DC-grid technology. Proc. CSEE 2013, 33, 8–17. [Google Scholar] [CrossRef]
- Timmers, V.; Egea-Àlvarez, A.; Gkountaras, A.; Xu, L. Multi-objective optimization and comparison of DC/DC converters for offshore wind turbines. IEEE Access 2024, 12, 81236–81251. [Google Scholar] [CrossRef] [Scilit]
- Wei, C.; Tang, G.; Wu, Y.; Lin, Z.; Gao, C.; He, Z. Overview and prospect of topology research on high voltage and large capacity DC transformer. Proc. CSEE 2024, 44, 6940–6959. [Google Scholar] [CrossRef]
- Páez, J.D.; Frey, D.; Maneiro, J.; Bacha, S.; Dworakowski, P. Overview of DC–DC converters dedicated to HVdc grids. IEEE Trans. Power Deliv. 2019, 34, 119–128. [Google Scholar] [CrossRef] [Scilit]
- Wang, X.; Tang, G.; He, Z.; Wei, X.; Ma, C.; Zhang, S.; Xiao, X. Topology research of DC/DC converters for offshore wind farm DC collection systems. Proc. CSEE 2017, 37, 837–847. [Google Scholar] [CrossRef]
- Wang, J.; Burgos, R.; Boroyevich, D. Switching-cycle capacitor voltage control for the modular multilevel DC/DC converters. In Proceedings of the 2015 IEEE Applied Power Electronics Conference and Exposition (APEC), Charlotte, NC, USA, 15–19 March 2015; pp. 377–384. [Google Scholar] [CrossRef] [Scilit]
- Norrga, S.; Ängquist, L.; Antonopoulos, A. The polyphase cascaded-cell DC/DC converter. In Proceedings of the 2013 IEEE Energy Conversion Congress and Exposition (ECCE), Denver, CO, USA, 15–19 September 2013; pp. 4082–4088. [Google Scholar] [CrossRef] [Scilit]
- Lin, W.; Wen, J.; Cheng, S. Multiport DC–DC autotransformer for interconnecting multiple high-voltage DC systems at low cost. IEEE Trans. Power Electron. 2015, 30, 6648–6660. [Google Scholar] [CrossRef] [Scilit]
- Li, B.; Zhang, S.; Zhao, X.; Yang, J.; Xu, D. Capacitive energy transfer principle based high-voltage high-power DC/DC converters. Proc. CSEE 2021, 41, 1103–1114. [Google Scholar]
- Yang, X.; Zheng, Q.; Lin, Z.; Xue, Y.; Wang, Z.; Yao, L.; Chen, B. Survey of high-power DC/DC converter for HVDC grid application. Power Syst. Technol. 2016, 40, 670–677. [Google Scholar] [CrossRef]
- Chen, Y.; Wang, H.; Zhu, M.; Ma, J.J.; Cai, X. Autotransformer-type modular DC transformer based on switched-capacitor two-port submodule. High Volt. Eng. 2021, 47, 2457–2468. [Google Scholar] [CrossRef]
- Kish, G.J. On the emerging class of non-isolated modular multilevel DC–DC converters for DC and hybrid AC–DC systems. IEEE Trans. Smart Grid 2019, 10, 1762–1771. [Google Scholar] [CrossRef] [Scilit]
- Kenzelmann, S.; Rufer, A.; Dujic, D.; Canales, F.; de Novaes, Y.R. Isolated DC/DC structure based on modular multilevel converter. IEEE Trans. Power Electron. 2015, 30, 89–98. [Google Scholar] [CrossRef] [Scilit]
- Cui, S.; Hu, J.; De Doncker, R.W. Control and experiment of a TLC-MMC hybrid DC–DC converter for the interconnection of MVDC and HVDC grids. IEEE Trans. Power Electron. 2020, 35, 2353–2362. [Google Scholar] [CrossRef] [Scilit]
- Parida, N.; Das, A. Modular multilevel DC–DC power converter topology with intermediate medium frequency AC stage for HVDC tapping. IEEE Trans. Power Electron. 2021, 36, 2783–2792. [Google Scholar] [CrossRef] [Scilit]
- Jin, H.; Chen, W.; Wang, Y. A series-arm modular multilevel DC/DC converter with variable duty cycle quasi-square-wave modulation for ZVS operation. IEEE Trans. Power Electron. 2024, 39, 12185–12199. [Google Scholar] [CrossRef] [Scilit]
- Merlin, M.M.C.; Green, T.C.; Mitcheson, P.D.; Trainer, D.R.; Critchley, R.; Crookes, W.; Hassan, F. The alternate arm converter: A new hybrid multilevel converter with DC-fault blocking capability. IEEE Trans. Power Deliv. 2014, 29, 310–317. [Google Scholar] [CrossRef] [Scilit]
- Jamshidi Far, A.A.; Hajian, M.; Jovcic, D.; Audichya, Y. High-power modular multilevel converter optimal design for DC/DC converter applications. IET Power Electron. 2016, 9, 247–255. [Google Scholar] [CrossRef] [Scilit]
- Yuan, D.; Yuan, Y.; Jia, Y.; Xiao, X.; Chen, W.; Yao, J. An ISOP hybrid DC transformer. Power Syst. Technol. 2021, 45, 179–188. [Google Scholar] [CrossRef]
- Li, B.; Wang, N.; Zhao, X.; Li, L.; Xu, D. High-voltage large-capacity DC transformer based on flexible commutation for full-DC offshore wind farm. Autom. Electr. Power Syst. 2022, 46, 129–141. [Google Scholar] [CrossRef]
- Yao, J.; Chen, W.; Xue, C.; Yuan, Y.; Wang, T. An ISOP hybrid DC transformer combining multiple SRCs and DAB converters to interconnect MVDC and LVDC distribution networks. IEEE Trans. Power Electron. 2020, 35, 11442–11452. [Google Scholar] [CrossRef] [Scilit]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2026 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.