Abstract
Courtrooms are tall rooms in which cold glazing, radiator plumes and stratification shape winter comfort. We combined infrared thermography with steady CFD including surface radiation and a coupled envelope (OpenFOAM, cross-checked with Ansys Fluent) to assess window replacement and wall insulation in three courtrooms in Iași, Romania, at −18 °C outdoors. The model was verified on three meshes and tested against a downdraught correlation and measured air temperatures; after calibration of the unknown heat input, it underestimated the air temperature of two further periods by 1.2–1.7 K. The mean PMV stayed between −0.07 and 0.04 and the mean draught rate below 8%, but the radiators did not prevent downdraught: the ankle-level draught rate in the first seat row reached 24–29%, above the 20% limit of category B, and 18–24% after wall insulation. Window replacement cut the transmission loss by 13–21%, and, with wall insulation, by 39–75%, after which ventilation becomes the largest loss. Supply air at 12 °C after heat recovery caused draught in a fifth of the occupied zone. Envelope retrofit should therefore come with demand-controlled ventilation, enthalpy recovery and supply air reheated close to room temperature.