Reviewer 1 Report
Comments and Suggestions for AuthorsThe manuscript has potential for publication, provided that the following questions and concerns are adequately addressed:
The authors employ the standard (k-epsilon) turbulence model, coupled with the Boussinesq approximation, to represent airflow within the courtrooms. Although this approach is widely used in CFD simulations, I believe that a more detailed justification of its suitability for the problem under investigation is necessary, particularly because the flow is predominantly driven by natural convection, involves low velocities, and includes regions adjacent to heated and cooled surfaces. Under these conditions, the representation of thermal boundary layers and buoyancy effects may significantly influence the results. The authors should clarify the criteria underlying the selection of this turbulence model, provide information regarding the (y^+) values, and demonstrate the suitability of the wall functions employed. Furthermore, I consider it essential to discuss how the limitations of the turbulence model may affect velocity predictions and thermal discomfort indicators.
The authors determine the internal surface temperatures through a one-dimensional heat balance using Equation (3) and subsequently impose these values as boundary conditions in the CFD simulations. However, this approach requires further clarification, since the adopted surface thermal resistance incorporates heat transfer effects that are not fully represented in the numerical model, particularly considering the absence of an explicit treatment of radiative heat exchange between surfaces. Furthermore, the surface temperatures are calculated assuming a reference indoor temperature of 21 °C, whereas the numerical results indicate air temperatures of approximately 23–24 °C. Therefore, I question whether the prescribed thermal boundary conditions are consistent with the temperature field actually obtained from the simulations. I recommend that the authors provide a more comprehensive physical justification for this approach and conduct a sensitivity analysis to assess the influence of these assumptions on the results.
Another aspect that I consider important concerns the representation of radiators as volumetric heat sources distributed within a 0.1 m thick layer of air. Although this simplification may reduce computational costs, the authors do not sufficiently demonstrate that it adequately reproduces the physical heat transfer mechanisms associated with actual radiators, which involve both convection and radiation. This issue is particularly relevant because one of the main conclusions of the manuscript concerns the ability of radiators to counteract downward cold-air currents near windows. In this regard, the authors should justify the selection of the 0.1 m thickness and clarify whether this representation is supported by experimental findings or previous studies. I also recommend presenting a comparative analysis, even a simplified one, between the adopted approach and a representation of radiators as heated surfaces, in order to assess the influence of this assumption on the temperature and velocity fields.
Although the authors present a mesh sensitivity study using three different discretizations, I believe that the results do not demonstrate mesh independence with sufficient robustness for all the parameters investigated. As shown in Table 3, the head-to-ankle temperature difference decreases from 1.15 K for the 0.15 m mesh to 0.79 K for the 0.10 m mesh, representing a variation of approximately 31%. This difference is significant, particularly because this indicator is directly used in the thermal comfort assessment. Furthermore, the authors themselves acknowledge that the solution obtained with the finest mesh still exhibited variations during the final iterations. Therefore, I consider it insufficient to justify the use of the intermediate mesh solely on the grounds that it provides a conservative estimate. I recommend that the authors further investigate spatial convergence, preferably by considering additional mesh refinements in regions near the floor, windows, and radiators, and provide quantitative criteria supporting the selection of the mesh employed in the simulations.
I consider the authors' initiative to compare the results obtained using OpenFOAM and ANSYS Fluent to be a positive aspect of the study. However, it is important to emphasize that agreement between two computational codes does not, by itself, constitute physical validation of the model, particularly when both employ similar assumptions and turbulence models. Furthermore, the results presented in Table 3 reveal relevant differences between the two codes, especially regarding the vertical temperature difference, which reaches 1.15 K for OpenFOAM and 0.71 K for Fluent. The spatial correlation reported by the authors (r=0.64) also indicates appreciable discrepancies between the predicted thermal fields. Therefore, I consider it necessary to provide a more detailed discussion of the possible causes of these discrepancies and their implications for the reliability of the thermal comfort indicators. I recommend that the authors clearly distinguish between numerical verification and experimental validation, emphasizing that code-to-code comparisons cannot replace the assessment of numerical predictions against experimental measurements of temperature and velocity.
I consider one of the main limitations of the manuscript to be the exclusion of ventilation and infiltration from the CFD model, despite the authors themselves demonstrating in Section 3.5 that ventilation-related heat losses may reach approximately 6.9–7.0 kW, significantly exceeding the transmission losses through the building envelope. This simplification may directly influence the velocity distribution, thermal stratification, air temperature, and comfort indicators evaluated in the study. Furthermore, the radiator heating output is determined by considering only transmission heat losses and internal heat gains from occupants, while neglecting the losses associated with air renewal. Consequently, the conclusion that radiator heating becomes unnecessary during hearings under scenario DC-R6/S2 may not remain valid when realistic ventilation conditions are considered. I therefore question the extent to which the results obtained can support recommendations regarding thermal and energy performance under actual operating conditions. I strongly recommend that the authors perform at least one additional analysis incorporating ventilation under a representative scenario or, alternatively, revise their conclusions to explicitly restrict their validity to the idealized conditions considered in the simulations.
Author Response
Responses
Corresponding author: Dr. Florin-Emilian Țurcanu
Conventions: section, equation, table and figure numbers refer to the revised manuscript (tracked-changes version), unless "first version" is stated. Numbers in square brackets are the reference numbers of the revised manuscript; the references cited in this letter are listed at its end. Reviewer text is quoted verbatim in italics. Text newly added to the manuscript is quoted in blue under "Changes in the manuscript"; where a quotation is shortened, the omission is marked [...]. Where the manuscript text refers to a table or a case by name, we use the names of the manuscript (CA-R5, TR-R8, DC-R6; S0, S1, S2; M0, M1).
Dear Reviewer 1,
We thank the Reviewer for the detailed comments. They exposed real limitations of the first version, and the revision addresses them with new simulations, new verification and validation material, and a more restricted statement of what the conclusions support. The main changes are:
- Radiation and coupled boundary conditions. The model now includes surface-to-surface radiation (view-factor method, solved at every iteration), and the interior surfaces are no longer prescribed from a 1D balance at a fixed 21 °C. All envelope elements are coupled to the ambient on their other side through their thermal resistance, so the surface temperatures result from the solution. The mean radiant temperature is reported. The original model is kept as the reference model M0 and the revised model is M1 (Section 2.4).
- Validation. We added a benchmark against the Heiselberg downdraught correlation (V1) and a comparison of simulated and measured air temperature in four unoccupied quasi-steady periods of the 2025 monitoring campaign (two calibration points and two predictions, V2). The validation is partial and the manuscript says so. Code-to-code comparison is now presented as verification, not validation (Sections 2.6 and 3.6).
- Ventilation. Mechanical ventilation at the EN 16798-1 rate (146.5 and 148.2 l/s) is included in CFD cases with three supply temperatures (21, 18 and 12 °C: V-a, V-c, V-b), and the conclusions on the radiator demand were re-examined (Sections 2.4.4 and 3.8).
- Grid convergence. A grid convergence index (GCI) analysis on three meshes (0.15, 0.10, 0.075 m) for CA-R5 and on two meshes for DC-R6 replaces the two-mesh argument (Section 3.2).
- Turbulence model and radiator model. We added a justification of the turbulence model, y+ values, the limits of wall functions, a sensitivity study (six turbulence and wall-treatment variants in CA-R5, five in DC-R6), and a comparison between the volumetric radiator source and an isothermal heated-surface radiator (Section 3.5). The radiator source layer was one cell thick (0.15 m on the 0.15 m mesh), not 0.1 m as the first version stated; this was corrected.
- Code-to-code comparison. Fluent now ran all nine cases of the revised model and the existing state of CA-R5 and DC-R6 on the 0.075 m meshes (Section 3.3).
- Figures and presentation. Figures 3, 7 and 8 were redrawn with larger fonts, equations were retyped, mesh-quality metrics were added, and the Abstract, Introduction and Conclusions were revised. To keep the paper within a reasonable length, supporting details (GCI formulas, iterative convergence, mesh quality and y+, heat balance, the V1 table, the uncertainty budget) are in the Supplementary Materials (Tables S1–S6).
- Language. The text was revised by the authors for language.
- Correction of the draught rate. We found an error in our DR calculation, which changes the conclusion on local draught; it is described below the list and in the points concerned (R1.1, R1.3, R1.6).
Correction of the draught-rate calculation. While revising the post-processing we found that the comfort function object of OpenFOAM v2512, which we used for the draught rate DR in the first version, computes the turbulence intensity with an integer division (2/3 = 0 in C++), so that its value is zero, and that ISO 7730 requires it in per cent. All DR values of the first version therefore omitted the turbulence term. We now calculate DR in post-processing as in ISO 7730 [45] (speed clipped to 0.05–0.5 m/s, Tu = 100·√(2k/3)/max(v, 0.05) limited to 10–60 %, DR ≤ 100 %), with the local Tu from the RANS turbulent kinetic energy as the main result and Tu = 40 % as a sensitivity test (Section 2.5). For the original model (M0) the mean DR in the occupied zone changes from 2.2–6.5 % to 3.1–9.3 %, and the maximum at ankle level in the first row of seats (0.6–1.5 m from the façade) from 14–20 % to 18–30 % (DC-R6 S0 and S1: 28.9 and 30.2 %; CA-R5 S0: 24.5 %; TR-R8 S0: 25.5 %; 18.5–21.8 % after wall insulation). We therefore withdraw the statements that no cell exceeded DR = 20 % and that radiators prevent downdraught in the occupied zone. In the revised model M1 the mean DR is 3.0–7.9 % and the mean PMV is −0.07 to 0.04 (category A of ISO 7730 for PMV and mean DR in all nine cases), but the first-row ankle-level maximum is 23.6–28.6 % in S0 and S1, above the 20 % limit of category B, and 17.8–23.7 % in S2 (Table 10; Section 3.7). The Abstract, Sections 3.7 and 3.9 and the Conclusions were restated accordingly. DR computed from RANS k as a proxy for the turbulence intensity remains uncertain: with Tu = 40 % instead of the local value the first-row maximum in M1 is 29–52 % (Section 3.9).
We respond to each point below. The six comments are numbered R1.1–R1.6 in the order of the report. The assessment items of the report form are addressed in the final point (R1.7).
Comment R1.1
The authors employ the standard (k-epsilon) turbulence model, coupled with the Boussinesq approximation, to represent airflow within the courtrooms. Although this approach is widely used in CFD simulations, I believe that a more detailed justification of its suitability for the problem under investigation is necessary, particularly because the flow is predominantly driven by natural convection, involves low velocities, and includes regions adjacent to heated and cooled surfaces. Under these conditions, the representation of thermal boundary layers and buoyancy effects may significantly influence the results. The authors should clarify the criteria underlying the selection of this turbulence model, provide information regarding the (y^+) values, and demonstrate the suitability of the wall functions employed. Furthermore, I consider it essential to discuss how the limitations of the turbulence model may affect velocity predictions and thermal discomfort indicators.
Response: We agree that the choice of the standard k–ε model needed a justification, and the first version did not give one. The revision does the following.
Model suitability. The flow is slow and buoyancy-driven: the occupied-zone mean speed is 0.06–0.10 m/s and the peak speed along the cold walls 0.4–0.5 m/s. The largest surface-to-air difference of the existing state is about 16 K (inner glazing of DC-R6 at 7.8 °C against 23.7 °C air), which gives βΔT of about 0.05, so the Boussinesq approximation holds. The Rayleigh number based on room height is of the order of 1011 and the Reynolds number of the order of 104–105, so the wall layers and the radiator plumes are turbulent and the room core is weakly turbulent (orders of magnitude, not computed values). We chose steady RANS with the standard k–ε model and wall functions [36] because it is the most widely used model for room airflow, with documented behaviour in buoyant indoor flows [22,23,25]; because it is cheap enough for nine scenario cases and the sensitivity runs; and because a steady solution answers our question on mean occupied-zone conditions. Large-eddy simulation resolves more of the flow, but RANS remains accepted for indoor applications [24]. We also state that the standard k–ε model assumes fully turbulent flow and depends on the near-wall treatment, and that the ranking of RANS models depends on the flow case [25] and on the cold-window boundary layer [26]. The reporting follows the guidance for indoor CFD [29].
y+ and wall functions. We computed y+ from the solved fields for the nine cases of the revised model (M1). The area-weighted mean y+ over all walls was 76–116, the range 23–314, and at most 0.6 % of the wall area lay below y+ = 30. The windows have the highest values (area-weighted means 96–178). In the first model, y+ scales with cell size (area-weighted means 68, 105 and 139 for 0.10, 0.15 and 0.20 m cells in CA-R5). The log-law branch is therefore active on all meshes, but no mesh resolves the viscous sublayer. The wall treatment is stated in Section 2.3 (high-Reynolds-number wall functions for ν_t, ε and k, and the thermal wall function of Jayatilleke).
Limits. A y+ above 30 shows that the wall functions are used within their range of validity, not that they are accurate. The log law and the thermal wall function are calibrated on forced, near-equilibrium boundary layers, whereas the natural-convection layer along a cold wall peaks within millimetres to centimetres of the wall, below the first cell centre, which lies 0.075 m from the wall on the 0.15 m meshes. The convective heat transfer at glazing, walls and radiators, the ankle-level velocity near the façade and the draught rate there carry an uncertainty that mesh refinement cannot remove within the wall-function approach. The mean occupied-zone temperature and the mean PMV depend mainly on the global energy balance and are less sensitive.
Sensitivity to the turbulence model and wall treatment. We repeated CA-R5 and DC-R6 (existing state) with the standard k–ε model with and without buoyancy production of turbulence, the realizable and RNG k–ε models and the k–ω SST model, and in CA-R5 also with the standard instead of the Jayatilleke thermal wall function: six variants in CA-R5 and five in DC-R6 (Section 3.5, Table 8). Across the variants, the occupied-zone air temperature varied by 0.40 K (CA-R5) and 0.41 K (DC-R6) and the occupied-zone speed by at most 0.04 m/s. The head–ankle temperature difference was the most sensitive indicator: 1.32–2.12 K in CA-R5 and 2.09–3.20 K in DC-R6, highest with k–ω SST and with buoyancy production in the k–ε equations. The mean draught rate was 2.2–5.8 % (CA-R5) and 1.1–3.0 % (DC-R6); the variants with more stratification predicted less turbulence and therefore less draught. The peak near-façade speed (0.41–0.45 and 0.52–0.60 m/s) and the maximum draught rate at the ankles of the first row (24–26 % and 25–29 %) hardly changed: the downdraught is a robust feature of all variants. With wall functions at y+ of 30–300, k–ω SST behaves as a wall-function model rather than a low-Reynolds model, and we say so. We did not analyse further why the mixing is lower with k–ω SST. The spreads enter the uncertainty budget of Section 3.7.
Draught rate. The draught rate is the indicator most exposed to these limits. In addition, we corrected an error in its calculation (turbulence term omitted; see the opening of this letter). With the corrected DR, the first-row ankle-level maximum is 23.6–28.6 % in S0 and S1 of M1, and with Tu = 40 % instead of the local value it would be 29–52 %. Moreover, V1 (see R1.5 and R2.1) shows that the 0.15 m mesh underestimates the downdraught velocity of the Heiselberg correlation by about 20–40 % (ratio 0.61–0.83; 0.68–1.01 on the 0.10 m mesh), so the reported first-row draught is more likely to be underestimated than overestimated.
Consequence for the conclusions. We now treat the mean temperature and the mean PMV in the occupied zone as the robust quantities, and the near-façade velocity, the head–ankle difference and the draught rate as indicative (Section 4, "Validity").
Changes in the manuscript:
- Section 2.3 (paragraphs "Choice of turbulence model", "Schemes and wall treatment", "Limits of wall functions" and "Mesh quality"): new text with the criteria for the model choice, the estimates of βΔT, Ra and Re, the y+ statistics, and the explicit statement on the limits of wall functions for natural-convection boundary layers and on the affected indicators. The paragraph "Limits of wall functions" reads:
A y+ above 30 shows that the wall functions are used within their range of validity, not that they are accurate. They are calibrated on forced, near-equilibrium boundary layers, whereas the velocity of a natural-convection layer along a vertical wall peaks within millimetres to centimetres of the wall, below the first cell. The wall heat flux and the near-wall velocity therefore carry an uncertainty that mesh refinement cannot remove within the wall-function approach. [...] We bound the effect by the turbulence-model spread (Section 3.5) and by a comparison with the downdraught correlation of Heiselberg [3] (Section 3.6), and we read near-façade velocities and draught rates as indicative.
- Section 3.5 and Table 8 (paragraph "Turbulence model and wall treatment"): the variants and the spread of the indicators.
- Section 3.9 (item 5) and Section 4 ("Validity"): the indicators are classed as robust (mean temperature, heat flows, PMV, ranking of scenarios) or indicative (head–ankle difference, near-façade velocity, DR).
- References added: [22]–[26] and [29] (the first-version numbers [21] and [22] of Chen 1995 and Zhai 2007 are now [22] and [23]).
Comment R1.2
The authors determine the internal surface temperatures through a one-dimensional heat balance using Equation (3) and subsequently impose these values as boundary conditions in the CFD simulations. However, this approach requires further clarification, since the adopted surface thermal resistance incorporates heat transfer effects that are not fully represented in the numerical model, particularly considering the absence of an explicit treatment of radiative heat exchange between surfaces. Furthermore, the surface temperatures are calculated assuming a reference indoor temperature of 21 °C, whereas the numerical results indicate air temperatures of approximately 23–24 °C. Therefore, I question whether the prescribed thermal boundary conditions are consistent with the temperature field actually obtained from the simulations. I recommend that the authors provide a more comprehensive physical justification for this approach and conduct a sensitivity analysis to assess the influence of these assumptions on the results.
Response: The Reviewer is right on both points, and we changed the model instead of defending the old approach.
What was wrong. In the first version the interior surface temperatures came from a 1D steady balance (Eq. (3)) with a fixed indoor reference of 21 °C and the standard surface resistance [37]. That resistance includes a radiative part (about 5 of the 7.7 W/(m² K)) that the CFD model, which had no radiation, did not represent, so the approach was not self-consistent. In addition, the CFD air temperature (23–24 °C) differed from the 21 °C used to compute the surface temperatures, so the heat leaving through the envelope depended on the wall functions instead of the U-value. We acknowledge that the physical justification in the first version was insufficient.
What was done. (i) We added surface-to-surface radiation to the OpenFOAM model (grey, diffuse view-factor model with face agglomeration, solved at every iteration, non-participating air [39]; emissivity 0.90 for walls, floor, ceiling, doors and radiators, 0.84 for glass). (ii) The envelope elements now use a coupled boundary condition (Eqs. (4) and (5)): at every boundary face the flux that leaves the room by convection and radiation equals the flux through the element, which is represented by a conductive layer of resistance R_l = 1/U minus the surface resistances. Exterior elements are coupled to −18 °C (h_o = 25 W/(m² K)); interior elements (walls, doors, floor, ceiling) are coupled to neighbouring rooms at 21 °C (h_o = 7.69 W/(m² K)), with assumed transmittances of 1.8 W/(m² K) for walls and doors and 2.0 W/(m² K) for floor and ceiling, because no survey of the interior elements was available. The inner surface temperature is thus a result of the convective and radiative exchange with the room, and the inconsistency between 21 °C and the computed air temperature no longer arises in the surface temperatures. (iii) The original model of Eq. (3) is kept as the reference model M0 and compared with the revised model M1 (Section 3.4, Table 6). The simulated window surface temperature in M1 was 13.0, 13.1 and 8.9 °C (CA-R5, TR-R8, DC-R6) against the prescribed 12.9, 12.9 and 7.8 °C. In M0, 37–52 % of the heat input left by convection to interior surfaces held at 21 °C; in M1 the heat leaves through the windows (29–35 %) and the exterior walls (65–72 %), the net exchange with the neighbouring rooms is −2.0 to −0.1 % of the input and the global imbalance is at most 1.4 % (Table S4).
Main result of the comparison. Between M0 and M1 the occupied-zone air temperature changed by +0.1 / +0.2 / +0.1 K and the mean radiant temperature by 0.0 / +0.1 / 0.0 K (CA-R5 / TR-R8 / DC-R6), so the operative temperature changed by +0.1 / +0.2 / 0.0 K, and the PMV moved from −0.05, −0.01 and +0.02 to −0.02, +0.03 and +0.02. Radiation and the coupling therefore did not remove the high air temperature: the air in M1 stayed 2.2–2.8 K above 21 °C. With the interior boundary at 21 °C, this excess results from the radiator sizing of Eq. (6) and the occupant gains, not from the radiation treatment (see also R2.2).
Sensitivity analysis. We assessed the assumption about the reference temperature and the neighbouring spaces in two ways (Section 3.4, Table 7). In M0, raising the reference temperature of Eq. (3) and of the interior surfaces from 21 to 23 and 24 °C (cases CL-23 and CL-24) raised the occupied-zone air temperature almost one to one, by 2.0 and 3.0 K in CA-R5 and 2.0 and 2.9 K in DC-R6, and the window surface temperature by 1.3–2.4 K. In M1, neighbouring rooms at 23 °C instead of 21 °C (case CL-N23, CA-R5) raised the occupied-zone air temperature by 1.9 K (from 23.2 to 25.0 °C; PMV +0.39, head–ankle difference −0.03 K), raised the small heat gain from the neighbours from 2 to 86 W and raised the envelope loss by 5 %. The absolute air temperature thus follows the temperature assumed for the adjacent rooms, which was not measured. We report this as one of the largest uncertainties of the study, separately from the numerical uncertainty (Section 3.7), and the manuscript states the assumption (Section 3.9, item 2). The excess of the room air over the adjacent rooms (about 2.2 K in M1 at the design output) is the more robust quantity.
Mean radiant temperature. The mean radiant temperature is now computed in the model, as an area-weighted mean and locally at 9 points of the occupied zone (Figure 4). In M1 the area-weighted Tmrt in the occupied zone is 19.8–20.3 °C in S0, 20.1–20.5 °C in S1 and 20.5–20.9 °C in S2; the local values at 1.1 m are 19.4–20.9 °C, so the area-weighted value hides a spread of 1.0–1.5 K between the façade and the rear seats.
Changes in the manuscript:
- Sections 2.4.1 and 2.4.2: rewritten. Reference model M0 (Eq. (3)) with its two inconsistencies, the radiation model and emissivities ("Radiation"), the coupled wall boundary conditions (Eqs. (4), (5); "Coupled envelope") and the assumed interior transmittances. The text on M0 reads:
M0 has two inconsistencies. First, 1/Rsi = 7.7 W/(m² K) combines convection and radiation (about 5 W/(m² K) for ε = 0.9), but M0 has no radiation model, so the exchange was purely convective. Second, Eq. (3) assumes a room-side temperature of Tset, whereas the computed occupied-zone air was 23–24 °C, so the heat leaving through the envelope depends on the wall functions instead of the U-value. Both bias the air and radiant temperatures of M0.
- Tables 1 and 2: Table 1 areas replaced by the model areas; the Tsi columns of Table 2 are the prescribed M0 values, and in M1 the surface temperatures are results (Table 6).
- Section 3.4 (paragraphs "Air and radiant temperature", "Heat balance" and "Sensitivity to the 21 °C assumption"), Tables 6 and 7, Figure 4: M0 compared with M1, new sensitivity text and table (CL-23, CL-24, CL-N23).
- Section 3 (Sections 3.2–3.8): all indicators recalculated for M1; Tmrt and operative temperature added (Tables 6 and 10).
- Section 3.9 (item 2): the temperature of the neighbouring spaces is assumed, not measured; CL-N23 bounds the effect.
- References added: [39], and [27] and [28] for the spatial variation of Tmrt and for radiant asymmetry.
Comment R1.3
Another aspect that I consider important concerns the representation of radiators as volumetric heat sources distributed within a 0.1 m thick layer of air. Although this simplification may reduce computational costs, the authors do not sufficiently demonstrate that it adequately reproduces the physical heat transfer mechanisms associated with actual radiators, which involve both convection and radiation. This issue is particularly relevant because one of the main conclusions of the manuscript concerns the ability of radiators to counteract downward cold-air currents near windows. In this regard, the authors should justify the selection of the 0.1 m thickness and clarify whether this representation is supported by experimental findings or previous studies. I also recommend presenting a comparative analysis, even a simplified one, between the adopted approach and a representation of radiators as heated surfaces, in order to assess the influence of this assumption on the temperature and velocity fields.
Response: We agree that the radiator model needed justification and a comparison, and that the layer thickness in the manuscript was stated incorrectly.
Correction. The text said that the radiator heat was distributed in a 0.1 m thick layer. The source fills the cells whose centres lie in a box of nominal depth 0.1 m, which on the 0.15 m mesh used in the scenario runs is one cell layer, so its thickness was 0.15 m. In the revised model the box depth is 0.15 m: one cell layer on the 0.15 and 0.10 m meshes and two on the 0.075 m mesh, with the same total output. We corrected the text, and we thank the Reviewer for drawing attention to this part of the model.
Justification. Volumetric heat sources are used for radiators and heaters in room CFD [40], and they need no radiator geometry or water temperature, which our survey did not record. The simplification is acceptable for the purpose of this study if the total heat output is correct and if the effect of the missing radiative share is bounded. In the reference representation the source delivers all heat by convection, whereas a panel radiator emits 11–30 % by radiation: 20–30 % for a single panel and 11–14 % for a double panel [41], and about 30 % for a single-panel Type 10 [42]. Surface heat-transfer coefficients on radiators in rooms can also differ strongly from standard values [43]. We have no experimental data of our own for the radiators of these buildings, and the text says so. We therefore did not rely on the justification alone but tested the representation.
Comparison. We ran CA-R5 and DC-R6 (existing state) with two variants and compared them with the reference volumetric source (Section 3.5, Table 8). RAD-V places the source in two cell layers instead of one. RAD-S represents the radiator outline as an isothermal heated surface, whose temperature we adjusted until the surface delivered the design output and whose radiative fraction is a result. We first tried an imposed uniform heat flux on the radiator surface, but it was ill-posed on this mesh with wall functions (local surface temperatures of several hundred kelvin in stagnant cells), so that variant is not used and is not reported in the tables; the manuscript states this. The two representations bound real panel radiators: the volumetric source is purely convective, the isothermal flat surface mostly radiative.
- Thickness (RAD-V against one layer): doubling the depth changed the occupied-zone air temperature by 0.07 K (CA-R5) and the peak near-façade speed by 1 %, so the layer thickness of the first submission does not matter.
- Isothermal surface (RAD-S): the surface needed 81.9 °C (CA-R5) and 115.5 °C (DC-R6) to deliver the design output, with a radiative fraction of 78–84 %. It lowered the occupied-zone air temperature by 0.8 K (CA-R5) and 1.5 K (DC-R6), reduced the head–ankle difference from 1.32 and 2.09 K to 0.90 and 1.06 K, and weakened the rising plume, so the peak near-façade speed fell from 0.41 and 0.56 to 0.31 and 0.45 m/s (−24 % and −19 %). The maximum draught rate at the ankles of the first row did not change (25 and 28 %), because the radiators cover only the lower part of the façade and the downdraught from the glazing reaches the floor in both limits (Figure S1). Real panel radiators, with a larger emitting area and a radiative share of 11–30 %, lie between the two limits.
Effect on the conclusion. The air temperature and the stratification depend on the radiator representation; the draught at the first row does not. The conclusion that radiators counteract the cold downdraught is therefore not supported, and it is withdrawn. In M1 the radiator plumes rose in front of the windows, but the radiators did not prevent the downdraught: cold air from the glazing and from the uninsulated wall below the sills reached the floor and spread into the first row of seats. The maximum DR at the ankles of the first row is 23.6–28.6 % in S0 and S1, above the 20 % limit of category B, in all turbulence and wall-treatment variants and in both radiator representations; in S2 it is 17.8–23.7 %. The mean DR in the occupied zone is 3.0–7.9 % (category A), and less than 1.3 % of the occupied zone exceeds DR = 20 % (Section 3.7). The calculation error that led to the earlier statement is described at the opening of this letter. Because the 0.15 m mesh underestimates the downdraught velocity (V1), these first-row values are more likely too low than too high.
Changes in the manuscript:
- Section 2.4.3 (paragraph "Radiator representation"): thickness corrected; justification with [40]; radiative shares from [41] and [42]; statement on radiator heat-transfer coefficients [43]; the two variants; the failed flux variant. The new text reads:
The layer described as 0.1 m thick in the first submission was in fact one cell (0.15 m on the 0.15 m mesh), because the source fills the cells whose centres lie in a box of nominal depth 0.1 m. In M1 the box depth is 0.15 m: one cell layer on the 0.15 and 0.10 m meshes and two on the 0.075 m mesh, with the same total output. The source delivers all heat by convection, whereas a panel radiator emits 11–30 % by radiation [41,42], and it gives no surface temperature. We tested two variants (Section 3.5): a source two cell layers deep (RAD-V), and the radiator outline as an isothermal heated surface (RAD-S), whose temperature we adjusted until the surface delivered the design output and whose radiative fraction is a result. An imposed uniform heat flux on the radiator surface was also tried but was ill-posed on this mesh with wall functions (local surface temperatures of several hundred kelvin in stagnant cells), so it is not used.
- Section 3.5 and Table 8 (paragraph "Radiator representation"; Figure S1): comparison of the radiator representations.
- Section 3.7 (paragraph "Near-façade flow and local draught") and Section 4 (finding 2): the statement that radiators prevent downdraught is replaced by the first-row values above.
- Section 3.9 (item 4): heat sources (the radiator representations and the occupants).
- References added: [40], [41], [42], [43].
Comment R1.4
Although the authors present a mesh sensitivity study using three different discretizations, I believe that the results do not demonstrate mesh independence with sufficient robustness for all the parameters investigated. As shown in Table 3, the head-to-ankle temperature difference decreases from 1.15 K for the 0.15 m mesh to 0.79 K for the 0.10 m mesh, representing a variation of approximately 31%. This difference is significant, particularly because this indicator is directly used in the thermal comfort assessment. Furthermore, the authors themselves acknowledge that the solution obtained with the finest mesh still exhibited variations during the final iterations. Therefore, I consider it insufficient to justify the use of the intermediate mesh solely on the grounds that it provides a conservative estimate. I recommend that the authors further investigate spatial convergence, preferably by considering additional mesh refinements in regions near the floor, windows, and radiators, and provide quantitative criteria supporting the selection of the mesh employed in the simulations.
Response: We agree. A 31 % change between two meshes, in the indicator that classifies the comfort category, does not show mesh independence, and the argument that the medium mesh is conservative was not sufficient. The analysis of the first version is kept for reference (Table 3) and the new analysis does not confirm mesh independence of the 0.15 m mesh for all indicators; the manuscript says so.
Original model M0 (0.20, 0.15, 0.10 m). The GCI procedure of Celik et al. [32], applied to the first-version meshes, gives monotonic convergence for the occupied-zone temperature (R = 0.77, p = 1.7, extrapolated 22.89 °C, GCI = 0.45 %, U_num = 0.10 K) and for the room-mean temperature (R = 0.89, p = 1.3, GCI = 1.1 %, U_num = 0.25 K). The head–ankle difference, the mean draught rate and the PMV were outside the asymptotic range (R = 8.1, 2.8 and 1.4), so we give the range of the head–ankle difference, 0.79–1.20 K, instead of a GCI. The finest solution still drifted by 0.06 K over its last 500 iterations, so part of the 31 % decrease may be iteration noise.
Revised model M1: what was done. (i) We added a third mesh and a formal GCI analysis (Eq. (12), Section 3.2, Table 4) for CA-R5 in the existing state with meshes of 0.15, 0.10 and 0.075 m (134 904, 448 644 and 1 055 600 cells; refinement ratios 1.5 and 1.33, which the procedure allows for), and a two-mesh comparison (0.15 and 0.075 m) for DC-R6. The radiator source depth follows the mesh (one cell layer on the 0.15 and 0.10 m meshes, two on the 0.075 m mesh). (ii) Results for CA-R5, for which the indicators are in Table 4: the occupied-zone temperature converged monotonically (22.89, 22.90 and 23.17 °C on the 0.075, 0.10 and 0.15 m meshes; R = 0.00), the 0.10 and 0.075 m solutions coincide, and the 0.15 m mesh overestimates the extrapolated value by 0.27 K. The head–ankle difference also converged monotonically but slowly (0.74, 0.88 and 1.32 K; R = 0.31, p = 2.4, extrapolated 0.59 K, GCI of the fine grid 24 %), so the 0.15 m mesh overestimates it by about 0.7 K. The peak near-façade speed rose with refinement (0.41, 0.49 and 0.52 m/s; extrapolated 0.56 m/s), so the 0.15 m mesh underestimates it by about a quarter. The occupied-zone speed (0.087–0.094 m/s) and the mean draught rate (5.6–6.5 %) were not in the asymptotic range (R = 1.8 and 1.1), and we report their ranges instead of a GCI, as the procedure requires. In DC-R6 the refinement lowered the occupied-zone temperature by 0.59 K and the head–ankle difference from 2.09 to 1.22 K, and raised the peak near-façade speed from 0.56 to 0.63 m/s, the same trends as in CA-R5. (iii) Iterative convergence was improved. The existing-state cases ran for 6000 iterations with the fields averaged over iterations 4000–6000, so that the residual oscillation of the weakly unsteady flow does not affect the indicators. The retrofit and sensitivity cases started from the converged S0 field of the same room, ran for 8000 iterations with under-relaxation of 0.3 on the wall temperatures and were averaged over iterations 6000–8000. We required a global energy-balance error below 5 % and a drift of the occupied-zone air temperature below 0.05 K over the last 1000 iterations, and extended a case that missed either limit by 2000 iterations. The nine cases of Table 10 reached balance errors of 0.04–1.4 % and drifts of at most 0.02 K (Table S2). The 0.10 m case of CA-R5 converged slowly and needed 10,000 iterations; its energy balance closed within 1.9 % and the drift was 0.06 K, slightly above our limit, which we accept as part of its uncertainty. We acknowledge that the earlier solutions did not reach the residual limits of the solver settings; the first version reported only the closure of the global energy balance.
Selection of the mesh. The quantitative criteria are now stated and were set before the runs: the error of the 0.15 m mesh in the occupied-zone temperature must not exceed 0.5 K (the accuracy of the loggers), and for the head–ankle difference, the mean speed and the draught rate the convergence must be monotonic with a GCI of at most 20 %, or else the range of the three solutions is reported as an uncertainty band. These thresholds are our own choice; the procedure of [32] defines no threshold, and the manuscript says so. On these criteria the 0.15 m mesh fulfils the first criterion only in CA-R5 (error 0.27 K in CA-R5; 0.59 K in DC-R6 on two meshes) and does not fulfil the second, because the head–ankle difference converges slowly (GCI 24 %) and the speed and draught indicators are outside the asymptotic range. We nevertheless report the nine scenario cases and the sensitivity studies on this mesh, which made more than 60 runs affordable, and we attach to its results the mesh component of the uncertainty: 0.3–0.6 K for the occupied-zone temperature, 0.6–0.9 K for the head–ankle difference (which the 0.15 m mesh overestimates) and 0.07–0.11 m/s for the peak near-façade speed (which it underestimates) (Table S6, Section 3.7). The comparison between scenarios is less affected, because the mesh error has the same sign in all cases. We do not claim mesh independence of the working mesh for the head–ankle difference, the speed or the draught rate.
Local refinement. We did not apply local refinement near the floor, windows and radiators. Local refinement would vary the first-cell distance where the wall functions need a consistent value and push y+ below 30 (Table S3), and the uncertainty of the near-wall quantities depends on the wall treatment (see R1.1) and not only on the cell size. The global refinement to 0.075 m tests the wall heat transfer in the whole room. The argument against local refinement is ours and not taken from a reference.
The mesh-quality metrics are added in response to R2.6.
Changes in the manuscript:
- Section 2.6 (paragraphs "Iterative convergence" and "Mesh verification"): iterative convergence criteria, averaging windows, GCI procedure.
- Section 3.2 (3.2.1 Procedure and acceptance criteria; 3.2.2 Original model M0; 3.2.3 Revised model M1; 3.2.4 Mesh selection), Table 3 (M0, kept), Table 4 (three meshes, p, R and GCI), Eq. (12); Tables S1 and S2. The new text on the acceptance criteria and the local refinement reads:
We set two acceptance criteria for the 0.15 m mesh before the runs: a discretisation error of Tocc on that mesh, |φ3 − φext|, of at most 0.5 K (the logger accuracy), and, for ΔT1.1–0.1, uocc and DR, monotonic convergence with GCI ≤ 20 % or else the range of the three solutions as an uncertainty band. These thresholds are our own choice; [32] defines the procedure but no threshold. [...] We did not apply local refinement near the façade, because it would vary the first-cell distance where the wall functions need a consistent value and push y+ below 30 (Table S3).
- Section 3.9: the limits of the verification are stated.
- Reference added: [32].
Comment R1.5
I consider the authors' initiative to compare the results obtained using OpenFOAM and ANSYS Fluent to be a positive aspect of the study. However, it is important to emphasize that agreement between two computational codes does not, by itself, constitute physical validation of the model, particularly when both employ similar assumptions and turbulence models. Furthermore, the results presented in Table 3 reveal relevant differences between the two codes, especially regarding the vertical temperature difference, which reaches 1.15 K for OpenFOAM and 0.71 K for Fluent. The spatial correlation reported by the authors (r=0.64) also indicates appreciable discrepancies between the predicted thermal fields. Therefore, I consider it necessary to provide a more detailed discussion of the possible causes of these discrepancies and their implications for the reliability of the thermal comfort indicators. I recommend that the authors clearly distinguish between numerical verification and experimental validation, emphasizing that code-to-code comparisons cannot replace the assessment of numerical predictions against experimental measurements of temperature and velocity.
Response: We agree with the Reviewer on all three points: code-to-code agreement is verification and not validation, the differences in Table 3 deserve a discussion, and a model checked only against another code cannot support claims about the real rooms.
Terminology. The manuscript now separates verification (are the equations solved correctly) and validation (does the model represent the real room), following Roache [30] and Oberkampf and Trucano [31]. The definition is given once, in Section 2.6. The OpenFOAM–Fluent comparison is called verification throughout, and it is stated that both codes solve the same model.
More cases and finer meshes. Fluent now solved all nine cases of the revised model on the same 0.15 m meshes, with the same boundary conditions, sources and Boussinesq parameters, and the existing state of CA-R5 and DC-R6 also on the 0.075 m meshes (Section 2.6, Section 3.3, Table 5). Radiation in Fluent uses the surface-to-surface (S2S) model with view factors from ray tracing, which also cross-checks the view-factor radiation of OpenFOAM.
Magnitude and causes of the differences. In the first version (M0), Fluent gave occupied-zone and room-mean air temperatures 0.28 and 0.41 K lower than OpenFOAM and a better-mixed room (head–ankle difference 0.71 against 1.15 K; cell-by-cell r = 0.64, RMSE 0.51 K), and neither solution met the residual limits. For the revised model, both codes converge and agree on the global heat balance: the envelope heat loss differs by −10 to +21 W (at most 0.7 %), the area-weighted mean radiant temperature by −0.12 to +0.01 K and the mean window surface temperature by at most 0.5 K. The air is consistently cooler in Fluent: the occupied-zone air temperature by 0.17–0.40 K, the operative temperature by 0.09–0.23 K and the head–ankle difference by 0.38–0.64 K; the occupied-zone speed agrees within 0.03 m/s. In CA-R5 (S0) the cell-by-cell comparison of the mean temperature fields gives r = 0.80 and RMSE 0.55 K over the room, against r = 0.64 in the first version. For CA-R5 (S0) the head–ankle difference is 1.32 K in OpenFOAM and 0.82 K in Fluent. We acknowledge that the r of the first version and these remaining differences indicate appreciable discrepancies in the temperature field. On the 0.075 m meshes the codes converge towards each other: the difference in the head–ankle difference falls to 0.09 K (CA-R5) and 0.13 K (DC-R6), in the occupied-zone air temperature to 0.15 and 0.19 K, and in the operative temperature to 0.05 and 0.07 K, while the occupied-zone speed and the mean draught rate agree within 0.01 m/s and 0.8 percentage points. Most of the code-to-code difference on the 0.15 m mesh is therefore discretisation error, not a difference between the models; it is largest for the stratification, which depends on the thin, under-resolved layers near the floor, the windows and the radiators. The local flow near the façade remains code-dependent even on the finer mesh: the peak near-façade speed is 0.08–0.14 m/s lower in Fluent, and the radiator plume rises along the glazing in Fluent but separates from it at about 1 m in OpenFOAM. The thermal wall functions (Jayatilleke in OpenFOAM, the standard function in Fluent) and the pressure–buoyancy treatment differ between the codes and act mainly in these layers; we did not separate these factors with dedicated runs, and the text says so.
Implication for the comfort indicators. Both codes rank the scenarios identically: the occupied-zone air temperature falls from S0 to S1 to S2 in every room. The comparison supports the mean thermal state of the rooms and the ranking of the scenarios. The head–ankle difference and the near-façade velocities carry the largest numerical uncertainty, which we quantify in Section 3.7 together with the mesh and modelling effects (head–ankle difference ±0.8 K in CA-R5 and ±1.2 K in DC-R6). At their computed values all nine cases meet the 3 K limit of category B of ISO 7730 [45]; the existing DC-R6 lies at the 2 K limit of category A (2.09 K in OpenFOAM, 1.45 K in Fluent on the 0.15 m mesh), so for this case the category depends on the code and on the uncertainty band. We read the individual values of these indicators no more finely than this uncertainty.
Experimental validation. The first version contained no comparison with measurements. The revised version contains two partial validation steps, described in our response to R2.1: a comparison with the Heiselberg downdraught correlation (V1, velocity scale) and a comparison of the simulated air temperature with the logger measurements in unoccupied quasi-steady periods (V2). We could not validate velocity or temperature profiles, because no such measurements were made, and we state this explicitly. We do not claim a full validation, and the conclusions on stratification, velocity and draught are restricted accordingly.
Changes in the manuscript:
- Section 2.6 (introductory sentence and paragraph "Code-to-code comparison"): verification and validation defined; the Fluent comparison labelled verification. The new text reads:
Verification asks whether the equations are solved correctly; validation asks whether the model represents the physical room and needs measurements [30,31]. [...] This is verification: both codes solve the same model, so their difference measures implementation and discretisation effects and cross-checks the view-factor radiation of OpenFOAM.
- Section 3.3 and Table 5 (paragraphs "First model (M0)", "Revised model (M1), 0.15 m" and "Mesh refinement"), with the new figure of the OpenFOAM and Fluent sections: replaces the comparison paragraph of the first version; causes, magnitudes with the revised-model numbers, implication for the classification. The opening sentences read:
We solved all nine cases of the revised model (M1) with both OpenFOAM and Ansys Fluent on the same 0.15 m meshes, and the existing state of CA-R5 and DC-R6 also on the 0.075 m meshes (Table 5). This verifies the implementation of one model in two codes; it is not a validation (Section 3.6).
- Section 3.6: new validation paragraphs (V1, V2), Eq. (13), Table 9, Figures 5 and 6.
- Section 3.9 (item 6): the statement on the checks of the model was rewritten to say that validation is partial.
- References added: [30], [31].
Comment R1.6
I consider one of the main limitations of the manuscript to be the exclusion of ventilation and infiltration from the CFD model, despite the authors themselves demonstrating in Section 3.5 that ventilation-related heat losses may reach approximately 6.9–7.0 kW, significantly exceeding the transmission losses through the building envelope. This simplification may directly influence the velocity distribution, thermal stratification, air temperature, and comfort indicators evaluated in the study. Furthermore, the radiator heating output is determined by considering only transmission heat losses and internal heat gains from occupants, while neglecting the losses associated with air renewal. Consequently, the conclusion that radiator heating becomes unnecessary during hearings under scenario DC-R6/S2 may not remain valid when realistic ventilation conditions are considered. I therefore question the extent to which the results obtained can support recommendations regarding thermal and energy performance under actual operating conditions. I strongly recommend that the authors perform at least one additional analysis incorporating ventilation under a representative scenario or, alternatively, revise their conclusions to explicitly restrict their validity to the idealized conditions considered in the simulations.
Response: We agree with the Reviewer that this was the main limitation. The neglect of ventilation was, in the first version, inconsistent with our own estimate in Section 3.5 of the first version (now Section 3.8) of ventilation losses of 6.9–7.0 kW, and the conclusion that radiators are unnecessary in DC-R6/S2 during hearings was valid only for the idealised case without air renewal. We acknowledge this.
What was done. We added ventilation to the CFD model, as the Reviewer recommended (Section 2.4.4). The flow follows category II of EN 16798-1 [44] (Eq. (8): 12 persons at 7 l/s and 0.7 l/s per m² of floor), which gives 146.5 l/s (DC-R6) and 148.2 l/s (CA-R5), 1.2–1.5 air changes per hour. We simulated a mixing jet of 1.65–1.72 m/s from a 0.30 × 0.30 m grille on the interior east wall, with its top about 0.3 m below the ceiling, and the extract on the same wall; the inlet turbulence follows from a mixing length of 0.03 m. Three supply conditions were considered: (V-a) supply air heated to 21 °C by a central coil, with the radiators as in Table 2; (V-b) supply air after 75 % sensible heat recovery, T_sup = 12 °C at an outdoor temperature of −18 °C and an assumed extract temperature of 22 °C (Eq. (10)), without reheating; and (V-c) supply air reheated to 18 °C. In V-b and V-c the radiators cover the remaining sensible load, taken from the unclipped balance Q_rad = Q_trans + ρ·c_p·V̇·(T_set − T_sup) − Q_occ and set to zero only if the sum is negative (Eq. (11)). This gives 2726 W (V-b) and 1670 W (V-c) for CA-R5 (S0), and 1423 W (V-b) and 379 W (V-c) for DC-R6 (S2). The cases are DC-R6 in scenario S2 and CA-R5 in the existing state; they are representative cases, not the full scenario matrix, and the text says so. The CFD uses dry air and no infiltration, and the supply layout and the flow rate are our design assumptions, not measured data of these buildings (no mechanical ventilation is known in CA-R5, Section 3.8.2).
Results (Table 11). The design ventilation loss is 6.9–7.0 kW without recovery, 2.3–3.5 times the transmission loss of the existing rooms and 4–9 times that after the full retrofit; 75 % sensible recovery cuts it to about 1.7 kW (Eq. (9)). The CFD cases without ventilation, V-a, V-c and V-b gave the following (DC-R6 S2; CA-R5 S0):
- radiator output: 0 / 0 / 379 / 1423 W; 1117 / 1117 / 1670 / 2726 W;
- occupied-zone air temperature: 23.0 / 22.0 / 21.7 / 21.1 °C; 23.2 / 22.4 / 22.1 / 21.5 °C;
- head–ankle difference: 1.1 / 0.6 / 0.4 / 0.4 K; 1.3 / 0.9 / 0.7 / 0.6 K;
- mean draught rate: 3.6 / 9.0 / 12.4 / 13.6 %; 5.6 / 6.6 / 8.2 / 12.3 %;
- share of the occupied zone with DR > 20 %: 0 / 3.1 / 15.5 / 19.5 %; 0.2 / 0.5 / 2.1 / 19.2 %;
- maximum DR at the ankles of the first row: 17.8 / 24.8 / 32.2 / 31.4 %; 24.7 / 24.6 / 21.6 / 43.5 %.
With supply air at 21 °C (V-a) the occupied zone was 22.0–22.4 °C, the stratification fell to 0.6–0.9 K, and the mean DR rose to 6.6–9.0 % with at most 3.1 % of the occupied zone above DR = 20 %. With supply air at 12 °C after heat recovery and no reheating (V-b) the cool jet fell into the occupied zone: the mean DR rose to 12.3–13.6 %, 19 % of the occupied zone exceeded DR = 20 % and the operative temperature dropped to 20.7–20.8 °C, even though the radiators delivered 2.7 kW (CA-R5) and 1.4 kW (DC-R6). Reheating the supply air to 18 °C (V-c) was enough in CA-R5, where the radiators still deliver 1.7 kW along the façade (2.1 % of the zone above DR = 20 %), but not in the retrofitted DC-R6, where they deliver only 0.4 kW (15.5 % of the zone above 20 %). The draught indicators use the corrected DR (Section 2.5).
Radiator output and the DC-R6/S2 conclusion. The radiator output in the first version accounted for transmission losses and occupant gains only. The conclusion for DC-R6/S2 now reads: the no-ventilation result (no radiator output in S2, because the transmission loss of 733 W is below the occupant gain of 900 W) holds only for the idealised room without ventilation. With the supply air tempered to 21 °C (V-a) the radiators stay off, but the demand moves to the air-handling unit (about 7 kW without recovery and 1.7 kW with 75 % recovery at the design condition). With the supply air at 12 °C after recovery (V-b) the room needs 1.42 kW of radiator output in the CFD case (1.46 kW from the energy balance at 150 l/s, 733 + 1628 − 900 W), 69 % of the existing-state output of 2070 W, and the cool supply causes local draught. After a deep envelope retrofit the supply air should therefore be reheated close to room temperature or delivered through high-induction diffusers; reheating to 18 °C was not enough in the retrofitted room.
Part load. Because the measured overheating of the rooms bears on this question, we also ran the part-load cases listed under "Additional analyses" below (Section 3.8.1, "Part load").
Limits that remain. Infiltration is not modelled separately and would add to the load (Section 3.9, item 7). The ventilation cases use one supply layout, dry air and one flow rate, and the results should not be read as a ventilation design. The conclusions about thermal and energy performance in real operation are valid within these assumptions, and Section 4 ("Validity") now says so.
Changes in the manuscript:
- New Section 2.4.4 "Ventilation cases" (Eqs. (8)–(11)): ventilation layout, supply conditions V-a, V-b and V-c, assumptions. The text on the supply and on the radiator output in cases V-b and V-c reads:
The supply is a mixing jet of 1.65–1.72 m/s from a 0.30 × 0.30 m grille on the interior east wall, with its top about 0.3 m below the ceiling, and the extract on the same wall; the inlet turbulence follows from a mixing length of 0.03 m (10 % of the grille size). We ran three supply temperatures. In case V-a a central coil heats the supply air to Tset = 21 °C, so the radiators keep the output of Table 2. In case V-b the supply air enters at Tsup = 12 °C without reheating, and in case V-c it is reheated to 18 °C; in both, the radiators cover the remaining sensible load, [Eq. (11): QradV-b,c = max{0, Qtrans + ρ cp V̇ (Tset − Tsup) − Qocc}] where the clipping applies to the sum, not to the Table 2 value. This gives 2726 W (V-b) and 1670 W (V-c) for CA-R5 (S0), and 1423 W (V-b) and 379 W (V-c) for DC-R6 (S2). The CFD uses dry air, without infiltration.
- Section 3.8.1 (paragraphs "Ventilation", "Reassessment of the DC-R6 conclusion" and "Part load") and Table 11: results of V-a, V-b and V-c. The paragraph on the DC-R6 conclusion reads:
The first submission concluded that the fully retrofitted DC-R6 needed no radiator output during hearings. That holds only for the room without ventilation. With the supply air tempered to 21 °C (V-a) the radiators stay off, but the demand moves to the air-handling unit (about 7 kW without recovery and 1.7 kW with 75 % recovery at the design condition). With the supply air at 12 °C after recovery (V-b) the room needs 1.42 kW of radiator output (1.46 kW from the energy balance at 150 l/s), 69 % of the existing-state output, and the cool supply causes local draught. After a deep envelope retrofit the supply air should therefore be reheated close to room temperature or delivered through high-induction diffusers.
- Section 4 (finding 5, "Recommendation" and "Validity"): rewritten; the no-ventilation statement is restricted to the idealised case.
- Section 3.9 (item 7): ventilation and infiltration.
- Reference: [44] (already in the first-version list, number [27] there).
Comment R1.7 (assessment items of the report form)
Are the introduction, design, methods, results, conclusions, figures and tables adequate? Ratings by the Reviewer: Does the introduction provide sufficient background and include all relevant references? "Can be improved". Is the research design appropriate? "Can be improved". Are the methods adequately described? "Can be improved". Are the results clearly presented? "Can be improved". Are the conclusions supported by the results? "Can be improved". Are all figures and tables clear and well-presented? "Can be improved". Quality of English Language: The English is fine and does not require any improvement.
Response: We accept the ratings. All six items were rated "Can be improved", and the points above address the content they relate to. The Introduction was rewritten and extended with background on cold-window downdraught, radiator–window interaction, radiation and wall-treatment choices in indoor CFD, and verification and validation (see R2.10). The methods now describe the turbulence and wall treatment, the radiation model, the boundary conditions, the radiator model, the ventilation cases and the verification and validation procedure (R1.1–R1.6). The results are presented for the revised model with uncertainty estimates and with the limits of each indicator stated. The conclusions are restricted to what the verification, the partial validation and the ventilation cases support. The figures and tables were redrawn or replaced (see R2.7). The Reviewer found the English acceptable; the second Reviewer asked for improvement, so the text was nevertheless revised throughout for language by the authors (see R2.12).
Changes in the manuscript:
- Whole manuscript (tracked changes throughout); see R1.1–R1.6 and R2.7, R2.10, R2.12.
Additional analyses beyond the reviewers' requests
During the revision we added the following analyses, which no Reviewer asked for. We list them so that the Reviewers can see everything that changed.
- Correction of the DR implementation (Section 2.5; see the opening of this letter): all draught-rate values were recomputed, and the conclusion on local draught was restricted.
- Radiant asymmetry and local mean radiant and operative temperature. Maps and point values of Tmrt and Top at 1.1 m in the occupied zone, and the radiant temperature asymmetry towards the windows at the first row (Section 3.4, Figure 4): local Tmrt 19.4–20.9 °C; radiant asymmetry 1.6–5.8 K.
- Uncertainty budget. The mesh (difference between the 0.15 and 0.075 m solutions), turbulence-model (half-range), code (half-difference) and radiator-representation (half-difference) components were combined in a root sum of squares (Section 3.7, Table S6; Table 10 caption): ±0.5 K (CA-R5) and ±1.0 K (DC-R6) for the occupied-zone air temperature, ±0.8 and ±1.2 K for the head–ankle difference, and ±2.5 and ±1.1 percentage points for the mean DR. The effect of the neighbouring-room temperature (+1.9 K at 23 °C in CA-R5) is reported separately and is not in the sum.
- Part-load operation at milder outdoor temperatures (Section 3.8.1, "Part load"). At an outdoor temperature of 0 °C, radiators that keep the design output (no control) raised the occupied-zone air to 24.8 °C in CA-R5 (Qrad 1117 W, DR 5.0 %) and 26.1 °C in DC-R6 (2070 W, DR 1.7 %); with the output scaled with the indoor–outdoor temperature difference (weather compensation) the air was 23.6 °C (601 W, DR 6.3 %) and 24.2 °C (1115 W, DR 2.4 %). The retrofitted DC-R6 without radiator output reached 23.6 °C at 0 °C (DR 3.3 %). At the mean outdoor temperature of the heating season (4.5 °C) with weather compensation the air was 23.7 °C in CA-R5 (472 W, DR 7.0 %) and 24.2 °C in DC-R6 (876 W, DR 2.4 %). The rooms thus need a control that responds to the room temperature, not only to the outdoor temperature.
- Seasonal heating demand and indoor humidity over eight measured seasons (Section 3.8.2, Table 12, Figure 10). An hourly analytical model (no CFD) driven by the hourly METAR record of Iași airport for 2018/19–2025/26 gives, without heat recovery, 69, 86 and 87 kWh/m² per season for the existing state of CA-R5, TR-R8 and DC-R6; full retrofit with 75 % sensible recovery lowers it to 34, 43 and 22 kWh/m² (reductions of 51, 49 and 74 %). The modelled relative humidity during hearings at 21 °C had a median of 30 % and was below 30 % in 47 % of the hours without moisture recovery; with an assumed enthalpy exchanger (moisture efficiency 0.6) the median was 37–38 % and 17–20 % of the hours were below 30 %. The heat-recovery efficiencies and the moisture release of 50 g/h per person are assumptions (with 40–70 g/h and efficiencies of 0.5–0.7 the share of hours below 30 % ranged from 1 to 37 %). The modelled median humidity agrees with the median measured in CA-R5 in winter 2025 (22.8 % measured, 21.9 % modelled), but this agreement is partly coincidental, because no mechanical ventilation is known in the room.
- Extended Fluent cross-check of the revised model (Section 3.3, Table 5): nine cases on 0.15 m meshes and two on 0.075 m meshes; for CA-R5 S0, ΔTocc −0.34 K, ΔTmrt −0.01 K and ΔdT −0.50 K (Fluent minus OpenFOAM).
We thank the Reviewer again for the comments, which improved the manuscript.
Sincerely,
Florin-Emilian Țurcanu, on behalf of all authors
Author Response File:
Author Response.pdf
Reviewer 2 Report
Comments and Suggestions for AuthorsPeer Review Report
Manuscript Title: CFD Assessment of Thermal Comfort and Heating Demand in Courtrooms under Envelope Retrofit Scenarios
1. Overall Assessment & Recommendation
Recommended Decision: Major Revisions
Novelty & Originality: Good. The study applies computational fluid dynamics (CFD) to a complex and specific type of public space (tall, densely occupied courtrooms), contributing valuable insights within the framework of European energy performance directives (EPBD).
Key Strengths:
Practical integration of infrared thermography (IRT) with steady 3D CFD simulations using OpenFOAM, cross-checked against Ansys Fluent.
Clear focus on down-draught phenomena and the performance of perimeter radiators positioned beneath large windows.
Primary Flaws Preventing Immediate Acceptance: Over-simplification of thermal boundary conditions (neglecting explicit surface radiation exchange and fixing interior walls at 21∘C), a lack of direct quantitative experimental validation for air velocity/temperature profiles, and the exclusion of ventilation/infiltration from the baseline CFD runs.
2. Critical & Fatal Flaws (Must Be Addressed)
Lack of Direct Experimental Validation:
The authors mention monitoring data from winter 2025 as a general qualitative reference, but no quantitative numerical comparison (such as measured vs. simulated temperature or velocity profiles) is provided. A code-to-code verification between OpenFOAM and Ansys Fluent on the same mesh is insufficient on its own; actual field measurement data are required to validate the numerical model.
Simplifications in Thermal Boundary Conditions & Radiation:
Section 2.4 states that inner surface temperatures were prescribed via a 1D steady calculation, omitting explicit radiation exchange within the room and treating interior surfaces as isothermal at 21∘C. In tall courtrooms with extensive glazing, radiation plays a vital role in determining mean radiant temperature (Tmrt) and explains why simulated air temperatures run higher than reality.
Exclusion of Ventilation in Baseline CFD:
Ventilation and infiltration were omitted from the main CFD models and only discussed theoretically in Section 3.5 (noting a massive 6.9–7.0 kW load). Because real ventilation significantly impacts airflow patterns, thermal stratification, and comfort, decoupling it from the CFD framework limits the operational reliability of the conclusions.
3. Section-by-Section Comments
Abstract & Introduction:
The abstract is well-structured, but should explicitly emphasize that the evaluation targets the winter design condition (−18∘C).
Section 2 (Materials and Methods):
Equations (1) and (2) contain minor formatting overlaps in variable subscripts. Ensure clean mathematical typesetting.
Mesh details: Include mesh quality metrics such as maximum skewness and orthogonal quality to guarantee k-ϵ convergence stability.
Section 3 (Results and Discussion):
Figures 3 and 4: Font sizes on axis labels and legends are small and should be scaled up to meet international journal publication standards.
Table 4: PMV/PPD metrics are clear, but the implications of low indoor relative humidity (RH≈24%) on indoor air quality (IAQ) and mucosal health should be expanded.
Section 4 (Conclusions):
Streamline the conclusions to be more quantitatively driven, highlighting the engineering recommendation for integrating enthalpy recovery ventilation during deep envelope retrofits.
4. Acceptance Probability & Final Remarks
Current Acceptance Probability: ~40% in its present state due to the lack of direct experimental validation and simplified boundary approximations.
Potential Acceptance Probability After Revision: Can rise to 85%–90% if the authors incorporate field measurement validation data, enable an active surface-to-surface radiation model, and refine the visualization figures.
Author Response
Response to Reviewer 2
Corresponding author: Dr. Florin-Emilian Țurcanu
Conventions: section, equation, table and figure numbers refer to the revised manuscript (tracked-changes version), unless "first version" is stated. Numbers in square brackets are the reference numbers of the revised manuscript; the references cited in this letter are listed at its end. Reviewer text is quoted verbatim in italics. Text newly added to the manuscript is quoted in blue under "Changes in the manuscript"; where a quotation is shortened, the omission is marked [...]. Where the manuscript text refers to a table or a case by name, we use the names of the manuscript (CA-R5, TR-R8, DC-R6; S0, S1, S2; M0, M1).
Dear Reviewer 2,
We thank the Reviewer for the detailed comments. They exposed real limitations of the first version, and the revision addresses them with new simulations, new verification and validation material, and a more restricted statement of what the conclusions support. The main changes are:
- Radiation and coupled boundary conditions. The model now includes surface-to-surface radiation (view-factor method, solved at every iteration, with a Fluent S2S cross-check on all nine cases), and the interior surfaces are no longer prescribed from a 1D balance at a fixed 21 °C. All envelope elements are coupled to the ambient on their other side through their thermal resistance, so the surface temperatures result from the solution. The mean radiant temperature is reported. The original model is kept as the reference model M0 and the revised model is M1 (Section 2.4).
- Validation. We added a benchmark against the Heiselberg downdraught correlation (V1) and a comparison of simulated and measured air temperature in four unoccupied quasi-steady periods of the 2025 monitoring campaign (two calibration points and two predictions, V2). The validation is partial and the manuscript says so. Code-to-code comparison is now presented as verification, not validation (Sections 2.6 and 3.6).
- Ventilation. Mechanical ventilation at the EN 16798-1 rate (146.5 and 148.2 l/s) is included in CFD cases with three supply temperatures (21, 18 and 12 °C: V-a, V-c, V-b), and the conclusions on the radiator demand were re-examined (Sections 2.4.4 and 3.8).
- Grid convergence. A grid convergence index (GCI) analysis on three meshes for CA-R5 and two meshes for DC-R6 replaces the two-mesh argument (Section 3.2).
- Turbulence model and radiator model. We added a justification of the turbulence model, y+ values, the limits of wall functions, a sensitivity study with further RANS models, and a comparison between the volumetric radiator source and an isothermal heated-surface radiator (Section 3.5). The radiator source layer was one cell thick (0.15 m on the 0.15 m mesh), not 0.1 m as the first version stated; this was corrected.
- Figures and presentation. Figures 3, 7 and 8 were redrawn with larger fonts, equations were retyped, mesh-quality metrics were added, and the Abstract, Introduction and Conclusions were revised. Supporting details (GCI formulas, iterative convergence, mesh quality and y+, heat balance, the V1 table, the uncertainty budget) are in the Supplementary Materials (Tables S1–S6).
- Language. The text was revised by the authors for language.
- Correction of the draught rate. We found an error in our DR calculation, which changes the conclusion on local draught; it is described below the list and in the points concerned (R2.9, R2.11).
Correction of the draught-rate calculation. While revising the post-processing we found that the comfort function object of OpenFOAM v2512, which we used for the draught rate DR in the first version, computes the turbulence intensity with an integer division (2/3 = 0 in C++), so that its value is zero, and that ISO 7730 requires it in per cent. All DR values of the first version therefore omitted the turbulence term. We now calculate DR in post-processing as in ISO 7730 [45] (speed clipped to 0.05–0.5 m/s, Tu = 100·√(2k/3)/max(v, 0.05) limited to 10–60 %, DR ≤ 100 %), with the local Tu from the RANS turbulent kinetic energy as the main result and Tu = 40 % as a sensitivity test (Section 2.5). For the original model (M0) the mean DR in the occupied zone changes from 2.2–6.5 % to 3.1–9.3 %, and the maximum at ankle level in the first row of seats (0.6–1.5 m from the façade) from 14–20 % to 18–30 % (DC-R6 S0 and S1: 28.9 and 30.2 %; CA-R5 S0: 24.5 %; TR-R8 S0: 25.5 %; 18.5–21.8 % after wall insulation). We therefore withdraw the statements that no cell exceeded DR = 20 % and that radiators prevent downdraught in the occupied zone. In the revised model M1 the mean DR is 3.0–7.9 % and the mean PMV is −0.07 to 0.04 (category A of ISO 7730 for PMV and mean DR in all nine cases), but the first-row ankle-level maximum is 23.6–28.6 % in S0 and S1, above the 20 % limit of category B, and 17.8–23.7 % in S2 (Table 10; Section 3.7). The Abstract, Sections 3.7 and 3.9 and the Conclusions were restated accordingly. DR computed from RANS k as a proxy for the turbulence intensity remains uncertain: with Tu = 40 % instead of the local value the first-row maximum in M1 is 29–52 % (Section 3.9).
We respond to the points in the order of the report. The report groups several requests under single headings, and we split them into the numbered points R2.1–R2.13 (R2.10–R2.11 answer the assessment items of the report form, R2.12 the English-language item).
Comment R2.1
Lack of Direct Experimental Validation: The authors mention monitoring data from winter 2025 as a general qualitative reference, but no quantitative numerical comparison (such as measured vs. simulated temperature or velocity profiles) is provided. A code-to-code verification between OpenFOAM and Ansys Fluent on the same mesh is insufficient on its own; actual field measurement data are required to validate the numerical model.
Response: We agree that the first version had no quantitative comparison with measurements, and that comparing OpenFOAM with Fluent is verification and not validation. The revision includes a quantitative comparison where the data allow it, and states where they do not.
What data exist. The 2025 monitoring campaign recorded temperature and humidity with one logger per room (Testo 174H, accuracy ±0.5 K) at 1.1–1.5 m above the floor, every 5 minutes. Continuous records exist for CA-R5 and DC-R6. TR-R8 has no continuous record (only the night of 30/31 January and an afternoon of 28 March), so it was not used for validation. No air velocity or vertical air-temperature profile was measured, and the infrared images were used qualitatively. We therefore cannot validate velocity or temperature profiles against measurements, and we did not construct such a comparison. The monitoring was designed for the energy and indoor-climate assessment and not for CFD validation. The plan position of the loggers was not recorded; they stood on furniture, away from radiators, windows, doors and direct sun.
Validation V2: measured air temperature. We used four unoccupied quasi-steady periods (Table 9), in which the outdoor temperature and the room temperature varied slowly and the internal gains were close to zero: CA-R5 on 8–9 February 2025 (Te = −3.7 °C, Ti = 22.6 °C), 23 February (Te = −9.9 °C, Ti = 22.1 °C) and 15–16 March (Te = 3.9 °C, Ti = 24.9 °C), and DC-R6 on 8 February (Te = −3.7 °C, Ti = 20.7 °C). For each period, the outdoor temperature in the model was set to the measured mean, the occupant source was removed, and the neighbouring rooms were held at the measured room temperature. The radiator output was calibrated once per room, on the 8 February period, so that the simulated temperature at the logger matched the measurement, and the calibration was checked with a separate run at the calibrated output. The calibrated output was 713 W in CA-R5 and 1026 W in DC-R6, about 55 % of the transmission loss of Eq. (6) for that night (1277 and 1881 W); with the full transmission loss the simulated rooms were 1.4 and 2.1 K warmer than measured. The check runs gave 22.42 °C against the measured 22.6 °C in CA-R5 and 20.55 °C against 20.7 °C in DC-R6, so the residuals of the calibration are −0.18 and −0.15 K. The other two periods of CA-R5 (23 February and 15–16 March) are predictions with the calibrated output kept constant, as for uncontrolled radiators; an output scaled with the outdoor temperature (892 and 494 W) is given as a sensitivity. Only CA-R5 thus gives independent predictions, and the calibration periods are excluded from the statistics. Results at the logger (Table 9, Figure 6): for the two predictions with constant output the bias was −1.48 K, the mean absolute error 1.48 K and the RMSE 1.50 K (with weather-compensated output −1.38, 1.38 and 1.69 K), three times the logger accuracy of ±0.5 K. The model underestimated the measured temperature in both periods, by 1.2 K on 23 February and by 1.7 K on 15–16 March. Following the rule fixed before the runs, the neighbouring rooms of the 23 February prediction were set to the simulated room temperature, because it differed from the calibration value by more than 0.3 K; with the neighbours kept at 22.6 °C the error would have been −0.24 K. The prediction therefore depends mainly on two boundary conditions that were not measured, the heat actually supplied by the radiators and the temperature of the adjacent rooms, rather than on the flow model; on 15–16 March the simulated room would have needed about 0.7 kW more than the calibrated output to reach the measured 24.9 °C, which indicates a larger heat input than on 8 February (radiators not turned down in milder weather, or solar gains, which the model omits). We report this result as it is: V2 confirms the calibrated state but shows a limited predictive skill for the absolute air temperature, which is why the manuscript treats the absolute temperatures as uncertain and bases the conclusions on the comparison between scenarios.
The low calibrated output does not by itself identify its cause. Infiltration during the unoccupied nights, which the model omits, neighbouring rooms colder than the logger room, and transmittances higher than the assumed values would all require a smaller heat input to the model; we did not measure any of them. V2 therefore tests the predictive skill of the model under other outdoor conditions after the effective heat input has been calibrated, not its absolute heat balance. We state this in Section 3.6.2.
Validation V1: downdraught velocity. Because velocity data do not exist for these rooms, we benchmarked the velocity scale of the cold downdraught against the correlation of Heiselberg [3] (Eq. (13)), which is based on measurements. We simulated the CA-R5 room without heat sources at an outdoor temperature of −10 °C, so that the glazing (H = 2.55 m) was 7.6 K colder than the occupied-zone air (18.9 °C), with the mesh, turbulence model and wall treatment of the courtroom cases (meshes of 0.15 and 0.10 m). The correlation was derived in an empty room with a two-dimensional flow from a cold surface reaching the floor, and a heat load raises the maximum speed [49]; in the courtrooms the glazing starts 1.05 m above the floor, above a warmer parapet, so the correlation is an upper bound for the speeds of the real rooms. On the 0.15 m mesh the speed at 0.10 m above the floor was 0.61 (0.5–4.0 m from the façade) to 0.69 (0.5–2.0 m) of the correlation, and the maximum below 0.3 m 0.72 to 0.83 of it (Figure 5, Table S5). On the 0.10 m mesh these ratios rose to 0.68–0.83 and 0.87–1.01. The working mesh therefore underestimates the downdraught velocity by about 20–40 %, less on the finer mesh, and we read the simulated near-façade velocities and the draught rate at the first row of seats as lower estimates. Related CFD studies reproduced the same correlation [47,48]. The correlation has its own scatter and serves as a benchmark, not as a measurement.
Limits of this validation. The validation is partial. It covers the air temperature at one point per room in unoccupied conditions and the velocity scale in a benchmark geometry. Agreement at one point does not prove the correct flow, since errors in radiator output, envelope data and air distribution may compensate. Stratification (head–ankle difference), the draught rate and the effect of occupants are not validated against measurements. We therefore restricted the conclusions: the mean thermal state in the occupied zone is supported by the comparison, while the stratification and draught indicators and the differences between scenarios are presented as indicative, with the uncertainty from the grid, turbulence-model and code comparisons (Section 3.7). The Limitations state that measurements of the vertical profile and velocity are needed for a full validation, and the Conclusions propose them as future work.
Changes in the manuscript:
- Section 2.6 (paragraphs "Validation V1: downdraught correlation" and "Validation V2: measured air temperatures"): procedure, periods, calibration and prediction. The new text reads:
V1 and V2 test the velocity scale and one air temperature per room. They do not test the velocity field, the vertical profile or the draught rate, for which no measurements exist, and agreement at one point does not exclude compensating errors.
- New Section 3.6.2 "V2: measured air temperatures", Table 9 and Figure 6 (parity plot with the ±0.5 K band of the loggers).
- New Section 3.6.1 "V1: downdraught velocity against the correlation of Heiselberg", with Eq. (13), Figure 5 and Table S5.
- Section 3.9 (item 6) and Section 4 ("Validity"): the validation is stated as partial; the sentence on the checks of the model was rewritten. Section 4 (finding 4) gives the V2 result (MAE 1.5 K after calibration) and its main cause.
- References added: [47], [48], [49]; Heiselberg [3] was already in the list.
Comment R2.2
Simplifications in Thermal Boundary Conditions & Radiation: Section 2.4 states that inner surface temperatures were prescribed via a 1D steady calculation, omitting explicit radiation exchange within the room and treating interior surfaces as isothermal at 21∘C. In tall courtrooms with extensive glazing, radiation plays a vital role in determining mean radiant temperature (Tmrt) and explains why simulated air temperatures run higher than reality.
Response: The Reviewer is right about both the omission of radiation and the isothermal 21 °C interior surfaces. We changed the model on both points.
Explicit radiation. We added surface-to-surface radiation to the OpenFOAM model using the view-factor method (face agglomeration; grey diffuse surfaces; non-participating air, the usual assumption indoors [39]), solved at every iteration, with emissivity 0.90 for opaque surfaces and 0.84 for glass. It was used in all M1 cases. As a cross-check, we solved all nine M1 cases in Ansys Fluent with its S2S model (view factors from ray tracing) and equivalent boundary conditions (Section 3.3, Table 5). The codes agree on the global heat balance (envelope heat loss within −10 to +21 W, at most 0.7 %) and on the area-weighted mean radiant temperature (−0.12 to +0.01 K); for CA-R5 (S0) the difference in the occupied-zone temperature (Fluent minus OpenFOAM) is −0.34 K and in the head–ankle difference −0.50 K. No discrete-ordinates fallback was needed. The literature supports this change: ignoring radiation underpredicts the lower-level air temperature and overpredicts the heater surface temperature [39].
Interior surfaces. We did not follow the suggestion to fix the interior walls at 21 °C, and we explain why. Prescribing all interior surfaces at a fixed temperature removes the dependence of the surface temperatures on the room air and on radiation, which is exactly the effect the Reviewer describes. Instead, we coupled the envelope elements to their surroundings (Eqs. (4) and (5)): a thermal-resistance layer between the room-side surface and the outdoor air (−18 °C, h = 25 W/(m² K)) or the adjacent rooms (21 °C, h = 7.69 W/(m² K), with assumed transmittances for the interior elements), so that the inner surface temperatures result from the convective and radiative exchange. The 21 °C remains only as the assumed temperature of the neighbouring rooms, which were not measured, and its influence was tested: with neighbours at 23 °C the occupied-zone air temperature of CA-R5 rose by 1.9 K (case CL-N23, Table 7; see R1.2). The manuscript reports this sensitivity separately from the numerical uncertainty.
Mean radiant temperature. Tmrt is now computed from the radiation solution (area-weighted and locally at 9 points of the occupied zone; Figure 4), and the operative temperature and the PMV use it. In the occupied zone Tmrt is 19.8–20.3 °C in S0, 20.1–20.5 °C in S1 and 20.5–20.9 °C in S2, which in S0 is 2.8–3.9 K below the air temperature. The values for the original and the revised model are in Table 6 and for the nine cases in Table 10. The local values at 1.1 m are 19.4–20.9 °C and the radiant temperature asymmetry towards the windows at the first row is 1.6–5.8 K (Section 3.4).
Does radiation explain the higher simulated air temperature? The Reviewer states that radiation explains why the simulated air temperatures were higher than reality. We tested this with M0 and M1 and with the measurements (Sections 3.4, 3.6 and 3.8.1), and the data do not support this explanation as the main cause. Adding radiation and the coupled envelope changed the occupied-zone air temperature by only +0.1 K (CA-R5), +0.2 K (TR-R8) and +0.1 K (DC-R6), so the air stayed 2.2–2.8 K above 21 °C. With the interior boundary at 21 °C, this excess results from the radiator sizing of Eq. (6) and the occupant gains, not from the radiation treatment. Other evidence points to the heat supply: the calibration against the measurements (V2) needed only about 55 % of the transmission loss computed for the calibration night (residuals −0.18 and −0.15 K at the logger), and in part-load runs at an outdoor temperature of 0 °C radiators without control raised the air to 24.8 °C (CA-R5) and 26.1 °C (DC-R6). The simulated 23.2–23.8 °C in the existing state agrees with the 23.3–23.4 °C measured during the occupied hours of winter 2025, at much milder outdoor temperatures. In addition, the temperature assumed for the neighbouring rooms shifts the absolute air temperature almost one to one (see above). Radiation does change the radiant temperature and the surface temperatures, which is why it is now in the model, but it does not explain the high air temperature. The manuscript states this (Sections 3.4 and 3.7, and Conclusions, finding 3).
Changes in the manuscript:
- Section 2.4.2 (paragraphs "Radiation" and "Coupled envelope"): radiation model, emissivities, coupled boundary conditions; statement that the interior surfaces are not fixed at 21 °C. The new text reads:
We solved the radiative exchange with the grey, diffuse surface-to-surface model of OpenFOAM (viewFactor, face agglomeration, solved at every iteration) and a non-participating air, the usual assumption indoors [39]. The emissivity is 0.90 for walls, floor, ceiling, doors and radiators and 0.84 for the glazing. [...] Instead of fixing Tsi, we coupled each element to the ambient on its other side through its resistance: at every boundary face the flux that leaves the room by convection and radiation equals the flux through the element [Eq. (4)].
- Section 2.6 (paragraph "Code-to-code comparison") and Section 3.3, Table 5: the Fluent S2S cross-check and the results with radiation for both codes.
- Section 3.4 (paragraphs "Air and radiant temperature", "Heat balance" and "Sensitivity to the 21 °C assumption"), Tables 6 and 7, Figure 4: M0 compared with M1, Tmrt and operative temperature, the statement that radiation did not remove the high air temperature. Section 2.5 (Tmrt in M0 and M1) and Table 10 extended with Tmrt, Top and PPD.
- Abbreviations table: S2S, Tmrt, Top, M0, M1 added.
- References added: [39], [27] and [28] (Tmrt and radiant asymmetry).
Comment R2.3
Exclusion of Ventilation in Baseline CFD: Ventilation and infiltration were omitted from the main CFD models and only discussed theoretically in Section 3.5 (noting a massive 6.9–7.0 kW load). Because real ventilation significantly impacts airflow patterns, thermal stratification, and comfort, decoupling it from the CFD framework limits the operational reliability of the conclusions.
Response: We agree. As in our response to R1.6, ventilation was in the first version only discussed in Section 3.5 (now Section 3.8) and not simulated. In the revision, ventilation is part of the CFD model for representative cases: mixing ventilation at the EN 16798-1 category II rate [44] (146.5 l/s in DC-R6 and 148.2 l/s in CA-R5), for DC-R6 in scenario S2 and CA-R5 in the existing state, with three supply conditions: supply air at 21 °C (V-a), at 18 °C (V-c) and at 12 °C after 75 % sensible heat recovery without reheating (V-b). In V-b and V-c the radiator output is the unclipped balance of Eq. (11), Q_rad = Q_trans + ρ·c_p·V̇·(T_set − T_sup) − Q_occ, not less than zero: for CA-R5 (S0) 2726 W (V-b) and 1670 W (V-c), and for DC-R6 (S2) 1423 W (V-b) and 379 W (V-c). The supply layout and the airflow rate are assumptions (a single layout; a mixing jet of 1.65–1.72 m/s from a 0.30 × 0.30 m grille on the interior east wall, the extract on the same wall); the CFD uses dry air and no infiltration. Results (DC-R6 S2; CA-R5 S0; without ventilation / V-a / V-c / V-b, Table 11):
- occupied-zone air temperature: 23.0 / 22.0 / 21.7 / 21.1 °C; 23.2 / 22.4 / 22.1 / 21.5 °C;
- head–ankle difference: 1.1 / 0.6 / 0.4 / 0.4 K; 1.3 / 0.9 / 0.7 / 0.6 K;
- mean draught rate: 3.6 / 9.0 / 12.4 / 13.6 %; 5.6 / 6.6 / 8.2 / 12.3 %;
- share of the occupied zone with DR > 20 %: 0 / 3.1 / 15.5 / 19.5 %; 0.2 / 0.5 / 2.1 / 19.2 %;
- radiator output: 0 / 0 / 379 / 1423 W; 1117 / 1117 / 1670 / 2726 W.
The supply temperature therefore decides the local draught: at 21 °C the mean DR was 6.6–9.0 %, whereas the cool supply at 12 °C made 19 % of the occupied zone exceed DR = 20 %. The design ventilation load of 6.9–7.0 kW of the first version is kept (Eq. (9), Section 3.8.1) and is now consistent with the CFD cases; with 75 % sensible recovery it is about 1.7 kW. The runs without ventilation remain in the paper because they isolate the effect of the envelope, and they are labelled as the idealised case. Infiltration is not modelled separately (Section 3.9, item 7). Full details are in the response to R1.6.
Changes in the manuscript:
- New Section 2.4.4 "Ventilation cases" (Eqs. (8)–(11)); Section 3.8.1 with Table 11; Conclusions (finding 5); Limitations (Section 3.9, item 7). The text on the supply reads:
The supply is a mixing jet of 1.65–1.72 m/s from a 0.30 × 0.30 m grille on the interior east wall, with its top about 0.3 m below the ceiling, and the extract on the same wall; the inlet turbulence follows from a mixing length of 0.03 m (10 % of the grille size). We ran three supply temperatures. In case V-a a central coil heats the supply air to Tset = 21 °C, so the radiators keep the output of Table 2.
Comment R2.4
Abstract & Introduction: The abstract is well-structured, but should explicitly emphasize that the evaluation targets the winter design condition (−18∘C).
Response: Agreed. The Abstract now states that the three courtrooms are assessed at the winter design outdoor temperature of −18 °C, and that the validation against a downdraught correlation and measured air temperatures required a calibration of the heat input. The quantitative results are updated to the revised model: the mean draught rate (below 8 %), the mean PMV (−0.07 to 0.04), the first-row ankle-level draught rate (24–29 % in the existing state, 18–24 % after wall insulation) and the reductions of the transmission loss (13–21 % with window replacement, 39–75 % with wall insulation). The seasonal results (demand reduction of 49–74 %, hours below 30 % relative humidity reduced from 47 % to 17–20 % with enthalpy recovery) are kept out of the Abstract and given in Section 3.8.2 and in the Conclusions. The Conclusions and Section 4 ("Validity") repeat that the results hold for the design condition and the assumed envelope.
Changes in the manuscript:
- Abstract (first sentences): design condition (−18 °C) stated explicitly; limits and key quantitative results added. The new sentences read:
Courtrooms are tall rooms in which cold glazing, radiator plumes and stratification shape winter comfort. We combined infrared thermography with steady CFD including surface radiation and a coupled envelope (OpenFOAM, cross-checked with Ansys Fluent) to assess window replacement and wall insulation in three courtrooms in Iași, Romania, at −18 °C outdoors. The model was verified on three meshes and tested against a downdraught correlation and measured air temperatures; after calibration of the unknown heat input it underestimated the air temperature of two further periods by 1.2–1.7 K.
- Keywords: "surface radiation" and "downdraught" added.
Comment R2.5
Section 2 (Materials and Methods): Equations (1) and (2) contain minor formatting overlaps in variable subscripts. Ensure clean mathematical typesetting.
Response: Thank you. We retyped Equations (1) and (2) (now Eqs. (1a), (1b) and (2)) and corrected the overlapping subscripts. While doing so we found that several symbols were not defined (T_0, α, α_t, p_rgh, ν_t) and that Equation (1) had a stray comma. All symbols are now defined after the equations, and the abbreviations table was completed (ACH, DCV, ERV, GCI, IAQ, IRT, MAE, RANS, RMSE, S2S, Tmrt, Top, M0, M1).
Changes in the manuscript:
- Equations (1a), (1b) and (2) and the symbol definitions (Section 2.3, text after the equations); Abbreviations table. The symbol definitions read:
where U is the mean velocity; ρ0 = 1.2 kg/m³ the air density at T0 = 294.15 K (21 °C); β = 3.4·10−3 K−1; g the gravitational acceleration and r the position vector; prgh = p − ρ g·r the pressure without its hydrostatic part; ν = 1.5·10−5 m²/s and νt = Cμ k²/ε (Cμ = 0.09) the molecular and turbulent kinematic viscosities; h = cp T the sensible enthalpy (cp = 1005 J/(kg K)); α = ν/Pr and αt = νt/Prt the thermal diffusivities (Pr = 0.71, Prt = 0.85); and Sh the volumetric heat source of radiators and occupants (W/m³).
Comment R2.6
Mesh details: Include mesh quality metrics such as maximum skewness and orthogonal quality to guarantee k-ϵ convergence stability.
Response: Added. All meshes of the study are pure hexahedral grids of rectangular cells, checked with checkMesh (no failed check). The maximum non-orthogonality is 0°, the maximum skewness is of the order of 10−13 (zero for practical purposes) and the maximum aspect ratio is 1.03 (the cells are slightly stretched to fit the room dimensions). The Fluent-equivalent orthogonal quality is therefore 1.0 and the equiangle skewness 0.0. These two values are derived from the cell geometry and not computed in Fluent, and the text says so. Mesh quality is thus not a limiting factor for the convergence of k–ε, and the mesh-resolution error is addressed separately by the GCI analysis (R1.4). Table S3 gives the cell counts, the quality metrics, the first-cell distance and y+. For the finest mesh (0.075 m, CA-R5): 1 055 600 cells, maximum skewness 1.9·10−13, maximum aspect ratio 1.005. Convergence stability of k–ε also depends on the wall treatment and the solver settings, not only on the mesh quality; the iterative convergence criteria and the achieved balances and drifts are in Section 2.6 and Table S2.
Changes in the manuscript:
- Section 2.3 (paragraph "Mesh quality") and Table S3 in the Supplementary Materials (cells, maximum non-orthogonality, maximum skewness, maximum aspect ratio, first-cell distance, y+). The paragraph states that all meshes are pure hexahedral grids of rectangular cells; that checkMesh reports a maximum non-orthogonality of 0°, a maximum skewness of the order of 10−13 and a maximum aspect ratio of 1.03 with no failed check; and that the Fluent-equivalent orthogonal quality is 1.0 and the equiangle skewness 0.0 (derived from the cell geometry; Table S3), so that mesh quality does not limit the solution.
Comment R2.7
Section 3 (Results and Discussion): Figures 3 and 4: Font sizes on axis labels and legends are small and should be scaled up to meet international journal publication standards.
Response: Agreed. Figures 3 and 4 of the first version were redrawn with larger text: axis labels 9 pt, tick labels and legends 8 pt at the final printed width (single column 8.5 cm or full width 17 cm). In the revised manuscript the two profile figures (OpenFOAM against Fluent, and the three rooms) are merged into Figure 7, regenerated from M1 and including the Fluent profiles on both meshes, and the temperature and velocity sections of Figure 5 of the first version are Figure 3 (regenerated from M1). The new figures follow the same standard: Figure 4 (mean radiant temperature), Figures 5 and 6 (validation), Figure 8 (draught rate at ankle level), Figures 9 and 10 and Figures S1–S3.
Changes in the manuscript:
- Figures 3 and 7 (redrawn from M1); new Figures 4–6 and 8–10; Supplementary Figures S1–S3.
Comment R2.8
Table 4: PMV/PPD metrics are clear, but the implications of low indoor relative humidity (RH≈24%) on indoor air quality (IAQ) and mucosal health should be expanded.
Response: We expanded the discussion (Table 4 of the first version is now Table 10, which also has PPD columns). At the design condition of −18 °C, outdoor air holds about 0.65 g/kg of water vapour. Twelve seated persons release about 0.6 kg/h of moisture, which adds only about 1 g/kg at 150 l/s, so the indoor RH would be about 10 % at 22 °C, well below the winter mean measured in CA-R5 (24 %). The design condition is the extreme case: over eight seasons the modelled RH during hearings is higher (Section 3.8.2: median 30 % without moisture recovery, below 30 % in 47 % of the hours). Dry air affects the eyes, the airways and perceived air quality [51,52]. Low periocular RH thins the tear film and promotes eye irritation [53], and a controlled exposure at 10 % RH shortened the tear break-up time compared with 45 % RH [54]. A Cochrane review frames humidification against dryness symptoms [55]. Hearings last for hours and speakers use their voice continuously, so dryness of the mucous membranes is a plausible concern. These studies concern offices, laboratory exposures and educational settings, not courtrooms, so we use them to indicate the direction of the effect and not a quantitative risk. We did not find a verified reference for static electricity and virus survival, and the unsupported sentence was deleted. The statement that a lower ventilation rate raises the RH but worsens air quality and raises the infection risk rests on [19].
The discussion also covers mitigation: demand-controlled ventilation, enthalpy recovery (which returns room moisture to the supply air, unlike sensible-only exchangers [56,57]; frost limits the recovery in the cold [58]), and active humidification with its condensation risk. At 21 °C, the coldest part of the existing DC-R6 glazing (5.3 °C in the revised model, mean 8.9 °C) reaches the dew point at about 36 % RH (46 % for the mean), whereas the replaced glazing (14.4 °C minimum, 17.9 °C mean) tolerates about 66 % RH. The RH target therefore depends on the glazing.
Changes in the manuscript:
- Section 3.8.1 (closing paragraphs on relative humidity and air quality): new text on RH, indoor air quality and mucosal effects. The first paragraph reads:
At the design condition of −18 °C, outdoor air holds about 0.65 g/kg of water vapour. Twelve seated persons release about 0.6 kg/h of moisture, which adds only about 1 g/kg at 150 l/s, so the indoor relative humidity (RH) would be about 10 % at 22 °C, well below the winter mean measured in CA-R5 (24 %). The design condition is the extreme case: over eight seasons the modelled RH during hearings is higher (Section 3.8.2). Such dry air affects the eyes, the airways and perceived air quality [51,52]: low periocular RH thins the tear film [53], 10 % RH shortened the tear break-up time relative to 45 % RH [54], and humidification is a recognised measure against dryness symptoms [55]. Speakers use their voice for hours, so dryness of the mucous membranes is a plausible concern.
- Table 10 (caption and PPD columns).
- References added: [53], [54], [55], [56], [57], [58]; [51], [52] and [19] were already in the first-version list.
Comment R2.9
Section 4 (Conclusions): Streamline the conclusions to be more quantitatively driven, highlighting the engineering recommendation for integrating enthalpy recovery ventilation during deep envelope retrofits.
Response: Agreed. The Conclusions were restructured as five numbered findings, a recommendation and a statement of validity, all quantitative and taken from the revised model:
- Envelope: The glazing was the weakest element of the recent building. Window replacement cut the design transmission loss by 13–21 % and raised the mean glazing temperature to 16.6–17.9 °C; with wall insulation the loss fell by 39–75 %.
- Comfort and draught: In all nine cases the mean PMV was −0.07 to 0.04 and the mean draught rate 3.0–7.9 %. The head–ankle difference (1.0–2.1 K on the working mesh, 0.7–1.2 K on the finer mesh) met category B with the reference model, but reached 3.1–3.2 K in the existing DC-R6 with two of the turbulence models. The radiators did not prevent local draught: at the ankles of the first row the maximum DR was 24–29 % before and 18–24 % after wall insulation, in all turbulence models and both radiator representations, and probably higher in reality.
- Air temperature and heat supply: Radiation changed the occupied-zone air temperature by only 0.1–0.2 K; the air stayed 2.2–2.8 K above 21 °C. The measurements were reproduced with about 55 % of the computed transmission loss as heat input, and uncontrolled radiators overheated the rooms at part load (24.8–26.1 °C at 0 °C), so heating control comes before the envelope measures.
- Reliability: OpenFOAM and Fluent agreed on the heat balance and, on the finer meshes, on the air temperature within 0.2 K. The occupied-zone air temperature is uncertain by ±0.5–1.0 K, plus 1.9 K if the neighbouring rooms are at 23 °C; the working mesh underestimates the downdraught velocity by 20–40 %; after calibration of the heat input the model predicted the measured air temperature in two further periods with an MAE of 1.5 K, limited mainly by the unmeasured heat supply and temperature of the adjacent rooms.
- Ventilation: At the EN 16798-1 rate the ventilation loss (6.9–7.0 kW) is 4–9 times the transmission loss after full retrofit; 75 % sensible recovery cuts it to 1.7 kW. Supply air at 12 °C after recovery put 19 % of the occupied zone above DR = 20 % and still required 1.4 kW of radiator output in the retrofitted DC-R6; reheating to 18 °C was enough only where the radiators still heat the façade. Over eight seasons, full retrofit with sensible recovery lowered the demand by 49–74 %, and enthalpy recovery reduced the hearing hours below 30 % RH from 47 % to 17–20 %.
The engineering recommendation is that, in a deep envelope retrofit, ventilation should be addressed together with the envelope: demand-controlled ventilation with enthalpy heat recovery reduces the ventilation load and the drying of the air [56–58]. The CFD ventilation cases (Section 3.8.1) add a design condition to this recommendation. With supply air at 21 °C the mean DR was 6.6–9.0 % and at most 3.1 % of the occupied zone exceeded 20 %; with 12 °C after recovery and no reheating, 19 % of the zone exceeded 20 % in both rooms; with reheating to 18 °C the share was 2.1 % in CA-R5 S0, where the radiators still deliver 1.67 kW along the façade, but 15.5 % in the retrofitted DC-R6 S2, where they deliver only 0.38 kW. After a deep retrofit the supply air should therefore be reheated to about room temperature (21 °C) or delivered through high-induction diffusers. The recovery performance at −18 °C is limited by frost and defrost [58], and the recommendation is valid for the cases and assumptions simulated; "Validity" in Section 4 says so. The Conclusions also no longer state that radiators prevent downdraught: they state that the mean DR is in category A but that the first-row ankle-level maximum exceeds the 20 % limit in S0 and S1 (after the correction of the DR calculation, see the opening of this letter). The Conclusions also say that heating control, not only the envelope, has to remove the measured overheating.
Changes in the manuscript:
- Section 4, whole. The new recommendation reads:
Envelope retrofit alone is not enough, because ventilation becomes the largest loss and the main cause of dry air. Courtrooms need room-temperature control of the radiators and demand-controlled ventilation with enthalpy recovery, designed together with the envelope; after a deep retrofit the supply air should be reheated close to room temperature or delivered through high-induction diffusers, and wall insulation is needed where first-row draught matters.
- References added: [56], [57], [58].
Comment R2.10
Does the introduction provide sufficient background and include all relevant references? Rating: "Must be improved".
Response: We accept the rating. The Introduction was rewritten (about 600 words). It now gives the policy context (recast Energy Performance of Buildings Directive and Energy Efficiency Directive [1,2]); the physics of the cold downdraught and the role of perimeter radiators [3–8]; the use of CFD for rooms and open-source codes [9–12]; CFD studies of tall public rooms and churches [13,14], of retrofits of heritage and public buildings and of a judicial building [15–17]; courthouse studies on indoor quality, infection risk and energy use [18–21]; the modelling choices that matter for this problem (turbulence, wall treatment, radiation, radiant asymmetry [22–28]); and the guidance on quality control, verification and validation, and discretisation error [29–32]. The closing paragraph states the aims, the contribution and the limits (partial validation, assumed envelope data, winter design condition). The new references were checked for correct DOI and content.
Changes in the manuscript:
- Section 1, whole; new references in the reference list. The closing paragraph states:
The study adds three elements to existing work. First, it treats courtrooms as a building type with specific geometry, occupancy and winter operation. Second, it couples the room airflow with surface radiation and a thermally coupled envelope, and it compares the retrofit scenarios under this model, with ventilation cases. Third, it tests the model stepwise: grid and iterative verification, a code-to-code comparison, sensitivity to the turbulence model and the radiator representation, and a partial validation against a downdraught correlation and measured air temperatures. The validation is partial and the envelope data are assumed, so we treat the draught indicators as indicative and report their uncertainty (limits in Section 3.9).
Comment R2.11
Is the research design appropriate? Rating: "Must be improved". Are the methods adequately described? Rating: "Must be improved". Are the results clearly presented? Rating: "Must be improved". Are the conclusions supported by the results? Rating: "Must be improved". Are all figures and tables clear and well-presented? Rating: "Must be improved".
Response: We accept the ratings for the research design, methods, results, conclusions, and figures and tables, and we answer them with the specific changes listed above. The research design now includes validation steps, radiation, ventilation cases, a grid convergence study and sensitivity tests for the choices that were assumed (R1.2–R1.5, R2.1–R2.3). The methods are described in more detail: turbulence and wall treatment, boundary conditions, radiator model, mesh quality, verification and validation (R1.1–R1.5, R2.5, R2.6). The results are presented for the revised model with uncertainty estimates and with the limits of each indicator stated. The conclusions are quantitative and restricted to what the verification, the partial validation and the ventilation cases support (R2.9). The figures and tables were redrawn or replaced (R2.7).
The validation remains partial because velocity and profile measurements do not exist, and the conclusions on draught and stratification are restricted; this includes the correction of the DR calculation, which withdraws the claim that radiators prevent downdraught (opening of this letter). We also checked the internal consistency of the text, tables and figures and corrected the discrepancies found: the PPD values of Section 3.7 were not in the table (PPD columns added to Table 10, now with the existing state specified in the text); the mean DR quoted for the existing state differed from the larger values of the retrofit scenarios in the table (the text now names the scenario); the near-façade speeds in the text and in the table referred to different quantities (the maximum speed below 0.5 m near the façade and the maximum ankle-level speed in the first row are now defined in the caption of Table 10); the "floor-to-ceiling difference" of DC-R6 did not match the profile (it was a maximum-minus-minimum value) and the sentence was removed; the "about 2.5 times" heat-flux ratio of Section 3.1 now reads "more than twice"; the areas of Table 1 omitted the wall behind the radiators and were replaced by the model areas, so that Eq. (6) reproduces Table 2; and the description of the iterative convergence and of the Fluent schemes was corrected (Sections 2.6 and 3.3).
Changes in the manuscript:
- Whole manuscript (tracked changes throughout); Tables 1–11; Abbreviations table.
Comment R2.12
Quality of English Language: The English could be improved to more clearly express the research.
Response: We accept the comment. The text was revised throughout for language by the authors: sentences were shortened, terminology was made consistent, and repeated and unclear phrases were rewritten. The text added in this revision was written to the same standard. The changes are visible in the tracked version.
Changes in the manuscript:
- Whole manuscript (tracked changes throughout).
Comment R2.13
Current Acceptance Probability: ~40% in its present state due to the lack of direct experimental validation and simplified boundary approximations. Potential Acceptance Probability After Revision: Can rise to 85%–90% if the authors incorporate field measurement validation data, enable an active surface-to-surface radiation model, and refine the visualization figures.
Response: We thank the Reviewer for the clear statement of priorities. The three priorities were treated first: validation with field measurements, to the extent that the data allow, with an explicit statement of what cannot be validated (R2.1); active surface-to-surface radiation, with coupled boundary conditions instead of fixed interior temperatures (R2.2); and the figures (R2.7). Ventilation was added as well (R2.3). We do not claim a full validation: the measurements cover the air temperature at one point per room, and the manuscript says so.
Changes in the manuscript:
- See the changes under R2.1, R2.2, R2.3 and R2.7.
Additional analyses beyond the reviewers' requests
During the revision we added the following analyses, which no Reviewer asked for. We list them so that the Reviewers can see everything that changed.
- Correction of the DR implementation (Section 2.5; see the opening of this letter): all draught-rate values were recomputed, and the conclusion on local draught was restricted.
- Radiant asymmetry and local mean radiant and operative temperature. Maps and point values of Tmrt and Top at 1.1 m in the occupied zone, and the radiant temperature asymmetry towards the windows at the first row (Section 3.4, Figure 4): local Tmrt 19.4–20.9 °C; radiant asymmetry 1.6–5.8 K.
- Uncertainty budget. The mesh (difference between the 0.15 and 0.075 m solutions), turbulence-model (half-range), code (half-difference) and radiator-representation (half-difference) components were combined in a root sum of squares (Section 3.7, Table S6; Table 10 caption): ±0.5 K (CA-R5) and ±1.0 K (DC-R6) for the occupied-zone air temperature, ±0.8 and ±1.2 K for the head–ankle difference, and ±2.5 and ±1.1 percentage points for the mean DR. The effect of the neighbouring-room temperature (+1.9 K at 23 °C in CA-R5) is reported separately and is not in the sum.
- Part-load operation at milder outdoor temperatures (Section 3.8.1, "Part load"). At an outdoor temperature of 0 °C, radiators that keep the design output (no control) raised the occupied-zone air to 24.8 °C in CA-R5 (Qrad 1117 W, DR 5.0 %) and 26.1 °C in DC-R6 (2070 W, DR 1.7 %); with the output scaled with the indoor–outdoor temperature difference (weather compensation) the air was 23.6 °C (601 W, DR 6.3 %) and 24.2 °C (1115 W, DR 2.4 %). The retrofitted DC-R6 without radiator output reached 23.6 °C at 0 °C (DR 3.3 %). At the mean outdoor temperature of the heating season (4.5 °C) with weather compensation the air was 23.7 °C in CA-R5 (472 W, DR 7.0 %) and 24.2 °C in DC-R6 (876 W, DR 2.4 %).
- Seasonal heating demand and indoor humidity over eight measured seasons (Section 3.8.2, Table 12, Figure 10). An hourly analytical model (no CFD) driven by the hourly METAR record of Iași airport for 2018/19–2025/26 gives, without heat recovery, 69, 86 and 87 kWh/m² per season for the existing state of CA-R5, TR-R8 and DC-R6; full retrofit with 75 % sensible recovery lowers it to 34, 43 and 22 kWh/m² (reductions of 51, 49 and 74 %). The modelled relative humidity during hearings at 21 °C had a median of 30 % and was below 30 % in 47 % of the hours without moisture recovery; with an assumed enthalpy exchanger (moisture efficiency 0.6) the median was 37–38 % and 17–20 % of the hours were below 30 %. The heat-recovery efficiencies and the moisture release of 50 g/h per person are assumptions (with 40–70 g/h and efficiencies of 0.5–0.7 the share of hours below 30 % ranged from 1 to 37 %). The modelled median humidity agrees with the median measured in CA-R5 in winter 2025 (22.8 % measured, 21.9 % modelled), but this agreement is partly coincidental, because no mechanical ventilation is known in the room.
- Extended Fluent cross-check of the revised model (Section 3.3, Table 5): nine cases on 0.15 m meshes and two on 0.075 m meshes; for CA-R5 S0, ΔTocc −0.34 K, ΔTmrt −0.01 K and ΔdT −0.50 K (Fluent minus OpenFOAM).
We thank the Reviewer again for the comments, which improved the manuscript.
Sincerely,
Florin-Emilian Țurcanu, on behalf of all authors
Author Response File:
Author Response.pdf
Round 2
Reviewer 1 Report
Comments and Suggestions for AuthorsAfter verifying that all my points raised in the first revision have been addressed in the new version of the article, I am in favor of publishing it.
Reviewer 2 Report
Comments and Suggestions for AuthorsThe researchers have addressed most of the reviewers' comments.