Abstract
Autonomous island power systems face inherent vulnerability to severe contingency events, yet current N-1 frameworks and thermal-only criteria systematically underestimate operational risk in grids with high renewable penetration. This paper presents an integrated 24 h N-2 contingency assessment explicitly combining transmission line outages with generator failures in a 6-bus island system, using PowerWorld Simulator (GOS Education 21) to evaluate 24,192 contingency cases across four load–RES operating scenarios. Results reveal a critical dual-channel risk structure. Thermal violations and network islanding represent mechanistically distinct failure modes that do not co-occur predictably. Critically, relying solely on thermal criteria misses adequacy impacts equivalent to 638 MWh/day in worst-case conditions. The time-dependent nature of vulnerability underscores the inadequacy of static snapshot analyses. These findings establish that N-2 contingency frameworks for autonomous grids must treat thermal security and islanding outcomes as co-equal metrics, fundamentally challenging conventional deterministic planning approaches.