Abstract
We evaluated the indoor environmental quality of the administrative office at University Medical Center Ho Chi Minh City branch 2 and implemented a multi-stage engineering control strategy to optimize occupational health conditions. A cross-sectional assessment monitored important air quality parameters, including carbon dioxide (CO2), fine particulate matter (PM2.5 and PM10), humidity, and illumination. Following baseline measurements, an integrated system was deployed to address pollutant mass balance, consisting of High-Efficiency Particulate Air (HEPA) filtration units for mechanical particle scrubbing, ceiling-mounted axial fans to induce forced convection, and ultraviolet-C germicidal lamps for photochemical disinfection. Post-intervention results demonstrated significant gains in system removal efficiency. CO2 concentrations decreased by over 60% due to enhanced volumetric air exchange, while PM2.5 levels decreased by more than 40% through interception and diffusion mechanisms within the HEPA media. Furthermore, UVC irradiation achieved a 90% reduction in viable airborne microbial colonies. The results of this study show that low-cost, scalable environmental engineering controls and fluid dynamic optimizations effectively mitigate indoor air pollution and enhance workplace stability in healthcare administrative settings.