Experimental Dataset for Rapid Monitoring of Concentration and Scaling Tendency in Recirculating Cooling Water Using Paper-Based Colorimetric Tests

,
,
,
and
Institute Agroecology and Land Management, National University of Water and Environmental Engineering, 33028 Rivne, Ukraine
*
Author to whom correspondence should be addressed.

Abstract

Recirculating cooling systems require reliable control of water concentration to limit scaling while avoiding unnecessary water losses associated with excessive blowdown and make-up water demand. This study developed and evaluated a paper-based colorimetric approach for rapid monitoring of concentration and scaling conditions in recirculating cooling water. The experimental validation was performed using make-up water from the cooling-water system of the Rivne Nuclear Power Plant and a laboratory-scale installation simulating progressive water concentration by controlled evaporation. Test A was used for chloride determination and subsequent calculation of the concentration factor (CF), whereas Test B was used for total hardness (TH) determination. The proposed measurements were validated against ISO 9297 and ISO 6059, respectively, and the concentration–hardness precipitation index (CPI) was calculated from the expected and measured TH values. In addition, the Langelier Saturation Index (LSI) and Ryznar Stability Index (RSI) were calculated to provide complementary scaling assessments. The colorimetric tests showed strong agreement with the reference methods, with Pearson correlation coefficients of 0.996 for Cl−, 0.997 for TH, and 0.9996 for CF (p < 0.0001). CPI, LSI, and RSI showed a consistent shift towards increasing scaling tendency with increasing CF. The proposed approach therefore provides a simple screening tool for operational control of recirculating cooling water and may support more efficient water use and circular water management.
Dataset: https://doi.org/10.5281/zenodo.21979693, accessed 26 August 2026.
Dataset License: Creative Commons Attribution 4.0 International (CC BY 4.0)

1. Summary

The dataset was generated as part of a continuing research programme concerned with the chemical composition, treatment, operational monitoring, and environmental management of recirculating cooling-water systems at Nuclear Power Plants (NPPs). Previous investigations conducted by the authors have addressed the complementary aspects of this system, including phosphorus compounds within the influence zone of nuclear power plant water discharge into the water body, sulfuric-acid stabilization treatment of the main condenser cooling circuit, transformation of carbonate-system components during liming of NPP cooling water, operational control of power-oil contamination in recirculating cooling-water systems, and the contribution of dispersed particles to suspended-solids discharge from the cooling system into a natural water body [1,2]. Hydrochemical state of recirculating cooling water is governed by the combined effects of water concentration, chemical treatment, operational conditions, and the accumulation or transformation of dissolved and particulate constituents [3,4,5]. Consequently, routine assessment of parameters associated with concentration and mineral precipitation is required for maintaining an adequate water-chemical regime and for identifying changes that may increase the tendency towards scale formation. Against this background, the present dataset was generated during the development and validation of two paper-based colorimetric test systems designed for rapid operational determination of chloride concentration (Cl−), total hardness (TH), and concentration factor (CF) in recirculating cooling water. Test A was developed for the colorimetric determination of Cl− and subsequent estimation of CF, whereas Test B was designed for the determination of TH. Moreover, the Concentration–Hardness Precipitation Index (CPI) was introduced as a screening indicator of deviation from the expected hardness concentration and potential precipitation tendency during progressive water concentration. The calculated CPI values are additionally compared with the Langelier Saturation Index (LSI) [6] and Ryznar Stability Index (RSI) [7], thereby providing a comparative assessment of the proposed operational indicator against established indices used for evaluating calcium-carbonate scaling and water stability. The experimental data were obtained using a laboratory-scale installation simulating the progressive concentration of water in a recirculating cooling system. Samples collected during the concentration process were subjected to parallel determination using the proposed colorimetric tests and standardized reference procedures. Cl− concentrations determined using Test A were validated against the argentometric titration procedure specified in ISO 9297:1989 [8], while TH determined using Test B was compared with the complexometric ethylenediaminetetraacetic acid (EDTA) titration method specified in ISO 6059:1984 [9]. In addition to the primary analytical measurements, the dataset contains the calculated parameters required for assessment of scaling tendency, including CF, CPI, LSI, and RSI. These derived data enable examination of the relationship between progressive concentration of the recirculating water, changes in total hardness, and the resulting calculated scaling tendency. Accordingly, it can be used to reproduce the reported statistical comparisons, independently recalculate CF and the scaling-related indices, evaluate the agreement between colorimetric and standardized analytical measurements, and investigate alternative approaches for rapid monitoring of recirculating cooling-water chemistry.

2. Data Description

2.1. Structure of the Dataset

The dataset was structured to provide a complete and traceable record of the experimental and calculated data generated during the validation of the proposed paper-based colorimetric approach for monitoring concentration factor (CF) and assessing scaling tendency in recirculating cooling water. The dataset includes reference measurements, colorimetric determinations obtained with the proposed Test A and Test B systems, calculated CF values, and the hydrochemical parameters required for the subsequent assessment of calcium-carbonate scaling using the proposed CPI and the established LSI and RSI indices. The complete dataset is available in the Zenodo repository: https://doi.org/10.5281/zenodo.21979693.
The dataset comprises six data sheets/worksheets Excel-file containing the numerical records used for method validation, scaling assessment, and comparative interpretation of the resulting indicators. Sheet/worksheet 1 contains the reference dataset for Cl− and TH measurements and includes reference concentration levels covering ten experimental series and seven concentration levels within each series CFs. These data provide the standardized analytical basis against which the colorimetric responses of Test A and Test B were evaluated. Sheet/worksheet 2 presents the comparative validation dataset for the proposed colorimetric tests, the result obtained with Test A, and the corresponding reference value determined according to [8] and the results obtained with Test B are compared with the reference TH values determined according to [9] and are additionally presented in Table 1 for clarity. The Sheet/worksheet 2 also includes the CF values calculated from the colorimetric determinations. Pearson’s correlation coefficient (r), the coefficient of determination (R2), and the corresponding p-values are provided as statistical descriptors of the relationships between the proposed and reference measurements. Sheet/worksheet 3 contains the dataset used for assessment of the proposed concentration-based scaling indicator, CPI. For each CF level, the dataset includes the expected total hardness (THexp), measured total hardness (THmeas), the difference between these quantities (ΔTH), the calculated CPI value, and the corresponding scaling interpretation. Sheet/worksheet 4 contains the dataset used for calculation and assessment of the LSI and organized by CF and replicate number, with ten replicate observations provided for each CF level. The recorded hydrochemical variables include pH, temperature, Ca2+ concentration, total alkalinity (TA) expressed as CaCO3, and total dissolved solids (TDS). The dataset additionally contains the calculated saturation pH (pHs) and the resulting LSI value for each replicate. Sheet/worksheet 5 contains the corresponding dataset for calculation of the RSI. As in the LSI dataset, the observations are organized according to CF and replicate number and include pH, temperature, Ca2+ concentration, TA, and the calculated saturation pH (pHs). The resulting RSI values are provided for each replicate. Sheet/worksheet 6 provides a summary comparison of the scaling interpretations obtained from CPI, LSI, and RSI for CF values ranging from 1 to 7. The table allows the progression of the three indicators to be compared across the same concentration-factor gradient CF.
Table 1. Validation of Cl− and TH measurements and determination of CF using the proposed colorimetric tests.

2.2. Colorimetric Response Data

The paper-based test systems used to generate the colorimetric dataset were prepared by immobilizing the respective analytical reagent compositions within a cellulose paper matrix. Test A was designed for the determination of Cl−, using silver nitrate (AgNO3, CAS 7761-88-8, ≥99.9%, p.a.) and potassium dichromate (K2Cr2O7, CAS 7778-50-9, ≥99.5%, p.a.) as the principal reagents. In contrast, Test B was designed for TH determination and incorporated Eriochrome Black T (CAS 1787-61-7, indicator grade) together with sodium tetraborate decahydrate, ammonium chloride, and aqueous ammonia, which provided the alkaline buffer environment required for the analytical response. All solutions used for preparation of the reagent compositions were prepared with deionized water having a specific electrical resistivity of at least 18.2 MΩ·cm at 25 °C. A laboratory-grade ashless cellulose filter paper (Whatman Grade 1; 180 μm thick, with an average pore diameter of 11 μm) was used as the supporting matrix. The respective reagent compositions were introduced into the paper matrix by impregnation, after which excess solution was removed and the impregnated material was dried at 40 ± 2 °C until constant mass. Following drying, the reagent-containing paper was processed into uniform discs (10–12 mm in diameter), which were transferred and fixed onto a polymer adhesive backing to form the individual test strips. The assembled test systems were subsequently dried at room temperature and stored in hermetically sealed, light-protected packages containing a desiccant until use. Thus, the same prepared test systems were used both to establish the reference colorimetric scales and to obtain the experimental responses subsequently evaluated against the standardized analytical procedures.
The reference colorimetric scale for Test A was established using model chloride solutions containing 0, 25, 50, 75, 100, 125, 150, and 175 mg/L Cl−. A 1000 mg/L Cl− stock solution was prepared by dissolving 1.6480 g of previously dried sodium chloride (NaCl, CAS 7647-14-5, ≥99.5%, p.a.) in deionized water and making the volume up to 1.000 L. The calibration solutions were prepared by appropriate dilution of this stock solution to obtain the required Cl− concentrations. For a final volume of 100 mL, aliquots of 0, 2.50, 5.00, 7.50, 10.00, 12.50, 15.00, and 17.50 mL of the stock solution were transferred and diluted with deionized water to volume, respectively. Each concentration level was applied under the same experimental conditions to the prepared Test A system, and the resulting color responses were used to construct the sequence of reference fields presented in Figure 1. For Test B, the reference colorimetric scale was established using model solutions with TH values of 0, 1, 2, 3, 5, 7, 10, and 15 mmol/L. A 100 mmol/L TH stock solution, expressed as CaCO3 equivalent, was prepared from calcium carbonate (CaCO3, CAS 471-34-1, ≥99.0%, primary standard) using hydrochloric acid (HCl, CAS 7647-01-0, analytical grade) and deionized water. The required calibration solutions were obtained by appropriate dilution of the stock solution. For a final volume of 100 mL, aliquots of 0, 1.00, 2.00, 3.00, 5.00, 7.00, 10.00, and 15.00 mL of the stock solution were transferred and diluted with deionized water to volume, respectively. After preparation of the corresponding stock solutions, the required TH levels were obtained by appropriate dilution, and each solution was applied to Test B under controlled conditions to produce the reference color responses shown in Figure 1. The underlying Test A and Test B results and the corresponding reference measurements are reported in Appendix D of the dataset.
Figure 1. Colorimetric scales of the paper-based test systems.
For each determination, a 20 µL aliquot of the water sample was transferred onto the reagent-containing area of the paper-based test using a calibrated micropipette. The sample was applied directly to the centre of the analytical zone, ensuring complete wetting of the reagent-containing paper area. No sample pretreatment or dilution was applied unless otherwise specified for a particular experimental series. After sample application, the test was allowed to develop under controlled laboratory conditions. The colour response was recorded after a predefined reaction time of 2 min, which was kept constant for all calibration standards and experimental samples. Measurements were performed at 25 ± 5 °C. The test was not mechanically mixed after sample application. The colour response was evaluated visually by comparison with the corresponding reference colour scale (Figure 1). The concentration assigned to each sample corresponded to the closest matching colour field on the calibration scale. Measurements were accepted when the colour response was clearly developed within the predefined reaction time and could be assigned unambiguously to one of the reference colour fields. Measurements showing incomplete wetting, non-uniform colour development, or an ambiguous colour response were repeated. For quality control, the same paper-test preparation, sample volume, application procedure, reaction time, temperature, and visual assessment conditions were maintained throughout the experiment. The reference colour scales and experimental measurements were generated using the same prepared test systems and under the same experimental conditions.
The analytical paper matrix consisted of Whatman Grade 1 cellulose paper (180 μm thickness; average pore diameter 11 μm). The reagent-containing material was impregnated, dried at 40 ± 2 °C to constant mass, cut into uniform discs, and stored in hermetically sealed, light-protected packages with desiccant. Batch-to-batch variability, long-term shelf-life, humidity/light stability, and inter-operator variability were not systematically investigated in the present study and should be addressed in subsequent validation studies.

2.3. Reference-Method Validation Data

The results of the comparative assessment of the proposed colorimetric tests and the corresponding reference determinations are presented in Table 1. For Cl−, Test A was compared with the values determined according to ISO 9297:1989 [8], whereas Test B was evaluated against TH determined according to ISO 6059:1984 [9]. In addition, the CF values obtained from the proposed colorimetric measurements were compared across the investigated concentration range. For Cl−, the responses obtained with Test A increased from 25 to 175 mg/L as the concentration level increased from 1 to 7 and the corresponding reference values ranged from (mean ± SD) 24.2 ± 2.4 to 172.4 ± 17.2 mg/L (Table 1). Thus, the colorimetric response generally followed the increase observed in the reference measurements. Although some differences were observed at individual concentration levels, the overall trend was consistent throughout the investigated range. Furthermore, the r between Test A and the reference Cl− measurements was 0.996, with R2 = 0.992 and (p < 0.0001). These results indicate a strong and statistically significant linear relationship between the proposed colorimetric response and the reference determination. Similarly, Test B produced TH responses between 1.0 and 3.0 mmol/L, while the corresponding reference measurements ranged from (mean ± SD) 1.05 ± 0.11 to 3.36 ± 0.34 mmol/L (Table 1).
The proposed test therefore reproduced the general variation in TH across the experimental concentration range. However, because Test B is based on discrete visual colour categories, several different reference TH values were assigned to the same colorimetric level. Nevertheless, the relationship between the Test B response and the reference TH values remained strong, with (r = 0.997), (R2 = 0.993), and (p = 0.0001). The CF values calculated from the proposed colorimetric measurements likewise increased with the experimental concentration level. Consequently, the proposed approach reproduced the progressive concentration of the recirculating water across the investigated range. The relationship between the CF values and the corresponding experimental levels was very strong, with r = 0.9996, p < 0.0001 and R2 = 0.9922.

2.4. Scaling Assessment Using CPI, LSI and RSI

The scaling tendency of the recirculating cooling water was assessed using the CPI and, for comparison, the established LSI [6] and RSI [7]. The corresponding datasets are presented in Table 2, Table 3 and Table 4, respectively. The results demonstrate a consistent change in the calculated scaling indicators with increasing CF. THexp increased progressively with CF, from 1.05 mmol/L at CF = 1 to 7.35 mmol/L at CF = 7 (Table 2). This increase reflects the theoretical concentration of TH expected from progressive evaporation of the recirculating water in the absence of hardness removal. In contrast, THmeas increased only from 1.00 mmol/L at CF = 1 to 3.00 mmol/L at CF = 4 and subsequently decreased to 2.00 mmol/L at CF = 6 and 1.00 mmol/L at CF = 7. Consequently, the difference between THexp and THmeas increased markedly with increasing CF. Specifically, ΔTH increased from 0.05 mmol/L at CF = 1 to 0.10 and 0.15 mmol/L at CF = 2 and 3, respectively. At CF = 4, the difference increased to 1.20 mmol/L and subsequently reached 2.25, 4.30, and 6.35 mmol/L at CF = 5, 6, and 7, respectively. Thus, the divergence between THexp and THmeas became increasingly pronounced at higher CFs. This pattern indicates that the measured hardness did not increase proportionally with the theoretical concentration of the water and is consistent with the removal of hardness-forming constituents from the aqueous phase, potentially through mineral precipitation. CaCO3 precipitation may represent a plausible mechanism; however, direct characterization of the precipitated phase was not performed in this study. The CPI values showed a pronounced increase as the CF increased from 1 to 7. At CF values of 1, 2, and 3, CPI remained low, with values of 4.76%, respectively, and all three conditions were classified as showing no scaling. At CF = 4, CPI increased to 28.57%, corresponding to slight scaling. A further increase in concentration resulted in CPI values of 42.86% at CF = 5 and 68.25% at CF = 6, which were classified as moderate and high scaling, respectively. At CF = 7, CPI reached 86.39% and was classified as extreme scaling. Thus, the CPI demonstrated a progressive transition from no apparent scaling at low CF to increasingly pronounced scaling at higher concentration levels.
Table 2. Experimental data and calculated values used for assessment of the CPI.
Table 3. Experimental hydrochemical parameters and calculated LSI values at different CF.
Table 4. Experimental hydrochemical parameters and calculated RSI values at different CF.
The LSI results showed a similar concentration-dependent pattern (Table 3). At CF = 1, the LSI value was −0.637 ± 0.020, indicating no scaling tendency. With increasing CF, the LSI progressively increased, reaching −0.161 ± 0.020 at CF = 2 and −0.083 ± 0.021 at CF = 3, which remained within the no-scaling range. At CF = 4, the LSI increased to +0.296 ± 0.021, corresponding to a slight scaling tendency. Further increases in CF resulted in LSI values of +0.644 ± 0.021 at CF = 5, indicating moderate scaling, and +1.050 ± 0.021 at CF = 6, corresponding to a high scaling tendency. At CF = 7, the LSI reached its highest value of +1.144 ± 0.021 and remained within the high scaling tendency category. Therefore, although the numerical scale of LSI differs from that of CPI, both indicators showed a consistent shift towards increasingly favourable conditions for scaling with increasing CF.
In contrast, the RSI exhibited an overall decreasing trend with increasing CF (Table 4). At CF = 1, the RSI was 8.78 ± 0.02, corresponding to stable conditions. As the concentration factor increased, the RSI decreased to 7.62 ± 0.02 at CF = 2 and 7.11 ± 0.02 at CF = 3, corresponding to generally stable and slight scaling tendency conditions, respectively. At CF = 4, the RSI decreased further to 6.40 ± 0.02, corresponding to a scaling tendency. The RSI remained within the scaling-tendency range at CF = 5, 6, and 7, with values of 6.22 ± 0.02, 6.18 ± 0.02, and 6.69 ± 0.02, respectively. Although the RSI showed a slight increase at CF = 7, the value remained within the scaling-tendency range.

2.5. Integrated Comparison of Scaling Assessment Approaches

The scaling interpretations obtained using CPI, LSI, and RSI are summarized in Table 5 and Figure 2. Although the three indices are based on different calculation principles, their classifications demonstrate a generally consistent shift from stable or non-scaling conditions at low concentration factors towards increasingly pronounced scaling tendency as the recirculating water becomes progressively concentrated. At CF = 1, both CPI and LSI indicated no scaling, whereas RSI classified the water as stable. Similarly, at CF = 2, CPI and LSI remained within the no-scaling category, while RSI indicated generally stable conditions. Thus, all three approaches characterized the water as being outside a pronounced scaling regime at the two lowest concentration factors. At CF = 3, CPI and LSI continued to indicate no scaling; however, RSI showed a slight scaling tendency. This difference suggests that RSI may respond to changes in water stability before the corresponding threshold is reached according to CPI or LSI.
Table 5. Summary of scaling interpretation according to the CF.
Figure 2. Assessment of scaling tendency according to the CF: (a) CPI, (b) LSI, and (c) RSI.
A clearer transition was observed at CF = 4, and CPI indicated slight scaling, LSI indicated a slight scaling tendency, and RSI classified the water as having a scaling tendency. Consequently, all three approaches identified a shift towards conditions favourable to scale formation, although the terminology and classification boundaries differed.
The practical difference between the proposed and traditional approaches is set out in Appendix A, Table A1. The proposed paper-based tests are directly linked to the concentration process and can therefore provide a rapid indication of changes in chloride and hardness during recirculation. The resulting CPI additionally reflects the divergence between expected and measured hardness. Standardized analytical methods, however, provide quantitative reference measurements with greater analytical resolution and remain necessary when detailed hydrochemical characterization or confirmation of scaling mechanisms is required. Nevertheless, the results presented in this study indicate that the proposed approach has a complementary role in scaling-risk assessment. The progressive change in CPI with increasing CF was accompanied by corresponding changes in LSI and RSI, while the paper-based tests supplied the basic measurements required for rapid calculation of CF and CPI. The simultaneous decrease in dissolved hardness and Ca2+ at higher CF values, together with the increase in pH and LSI, is consistent with a precipitation-related process. However, because the precipitated phase was not collected and characterized, these observations do not by themselves establish that CaCO3 was the precipitated. Thus, the proposed approach can be considered a screening-level monitoring tool, whereas standardized analytical methods and established scaling indices remain appropriate for detailed assessment and confirmation.

3. Methods

The parameters required for the assessment of scaling tendency were determined independently using the analytical procedures summarized in Table 6. The validation experiment was conducted using a laboratory-scale installation in which the concentration process of recirculating cooling water was simulated by controlled evaporation (Appendix B). The laboratory-scale installation consisted of a circulation water tank, a circulation pump and an electric heating element, which ensured continuous water circulation and simulated the evaporation conditions typical of industrial recirculating cooling systems (Appendix B, Figure A1). During the experiment, samples of the circulating water were periodically taken to determine the concentration of chloride ions, total hardness and the concentration factor, and to assess the risk of scale formation using the proposed colorimetric test system and reference laboratory methods.
Table 6. Standard analytical methods used for validation and calculation of scaling indices.
The experiment comprised 10 independent experimental runs, within each run, water samples were collected at seven concentration-factor levels (CF = 1–7). The water temperature was maintained at 25–45 °C, circulation was continuous, and water concentration was achieved through controlled evaporation. The initial physicochemical composition of the make-up water used in the laboratory experiment is provided in Appendix B, Table A2. The reference measurements included pH, temperature, Ca2+ concentration, TH, TA, TDS, and Cl− concentration. In addition, Cl− and TH were determined as reference parameters for the validation of Test A and Test B, respectively. The corresponding analytical results were subsequently used to calculate the CF and the scaling indices. CF was calculated from Cl− according to Equation (1), whereas CPI was calculated according to Equation (2) using the CF and TH data obtained with the proposed test systems. THexp at each concentration factor was calculated from the initial total hardness of the make-up water, assuming proportional concentration of dissolved hardness-forming constituents during evaporation and no removal of hardness from the aqueous phase according to Equation (3). The difference between the theoretically expected and experimentally measured total hardness (ΔTH) was subsequently calculated according to Equation (4). In addition, the measured pH, temperature, Ca2+, alkalinity, and TDS values, together with the calculated saturation pH (pHs), were used to determine the LSI according to [6]. The RSI was calculated from pH, temperature, Ca2+, alkalinity, and pHs according to [7]:
CF = CCl−,rec/CCl−,make−up
CPI = [(THexp − THmeas)/THexp] · 100
THexp = THmake−up · CF
ΔTH = THexp − THmeas
where CCl−,re and CCl−,make−up denote the chloride concentrations in the recirculating and make-up waters, respectively; THexp represents the theoretically expected total hardness at the corresponding CF, whereas THmeas denotes the total hardness measured in the recirculating water using Test B; THmake−up is the initial total hardness of the make-up water at CF = 1.
Statistical analysis was performed to characterize the variability of the experimental observations and to quantify the relationships between the proposed colorimetric determinations and the corresponding reference analytical measurements. Descriptive statistics were expressed as the arithmetic mean ± SD. Furthermore, the linear association between the proposed and reference determinations was evaluated using r, and was calculated separately for the relationship between Test A and the reference Cl− concentrations, Test B and the reference TH values, and the CF values obtained using the proposed approach and the corresponding reference CF values according to [15]. The R2 was additionally calculated to quantify the proportion of variance in the reference measurements explained by the respective linear relationship according to [16]. Thus, r was used to characterize the strength and direction of the linear association, whereas R2 provided a measure of the explanatory capacity of the fitted relationship. In addition, the statistical significance of each p was assessed using the corresponding two-tailed p-value, and p-value < 0.05 was considered statistically significant [17].

4. User Notes

For routine operational monitoring, Test A should be performed first to determine the CF and the corresponding scaling tendency, after which Test B is used to assess scale formation based on the measured TH. The results of both tests should be interpreted together when making decisions regarding the operation of the cooling-water system. Detailed instructions for sample application, colour development, result interpretation, and the sequential use of Tests A and B are provided in Appendix C.
The present dataset was generated using a single make-up-water matrix obtained from a recirculating cooling-water system and a laboratory-scale concentration setup based primarily on controlled evaporation. Consequently, the dataset does not represent the full range of hydrochemical compositions, operational conditions, chemical treatment regimes, and hydrodynamic processes encountered in industrial cooling systems. The results should therefore be interpreted as a laboratory-scale proof of concept rather than as direct validation across different cooling-water matrices. Further validation using waters with different hardness, alkalinity, ionic composition, treatment additives, and operational histories, including samples collected at different stages of industrial operation, would be required to establish broader applicability. Future research should include direct quantification and characterization of the precipitated material using techniques such as gravimetric analysis, SEM/EDS, and XRD, together with an assessment of the relationship between CPI and independent precipitation measurements. Comparison with published CaCO3 data could further clarify the potential role of CaCO3 precipitation in the observed hardness depletion.
The practical significance of the proposed approach is also related to the efficient management of water in recirculating cooling systems. Maintaining the concentration factor within an appropriate operating range while limiting excessive scale formation may help retain more water in circulation and, consequently, reduce the need for frequent blowdown and make-up water replenishment. This principle is consistent with circular water management, which promotes the efficient use, reuse, and retention of water within industrial processes [18,19]. Furthermore, timely detection of an increasing scaling tendency may allow operating conditions to be adjusted before substantial deposits develop [20,21,22]. Such control may help maintain heat-transfer performance while avoiding unnecessary water losses. In this context, the proposed paper-based tests may provide a practical means of routine screening of concentration and scaling conditions. Their use could support operational decisions on the management of recirculating water, particularly where rapid measurements are preferable to more time-consuming laboratory analyses. The proposed approach may have potential for supporting more informed management of blowdown and make-up water by providing rapid screening of concentration and potential scaling conditions. However, reductions in blowdown or make-up water demand were not experimentally evaluated in the present study.

Author Contributions

Conceptualization, P.K., V.M., O.B., A.K., S.M., and V.M.; methodology, P.K., V.M., O.B., A.K., S.M., and V.M.; software, P.K., O.B. and V.M.; validation, S.M., A.K., and V.M.; formal analysis, P.K. and O.B.; investigation, P.K., V.M., O.B., A.K., S.M., and V.M.; resources, P.K.; data curation, O.B.; writing—original draft preparation, P.K., O.B., A.K., S.M., and V.M.; writing—review and editing, P.K., V.M., O.B., A.K., S.M., and V.M.; visualization, P.K., O.B., and A.K.; supervision, P.K.; project administration, O.B.; funding acquisition, A.K. All authors have read and agreed to the published version of the manuscript.

Funding

This research was carried out within the framework of the HORIZON grant project (HORIZON-WIDERA-2023-ACCESS-07) ID 101184151 The Waterwise Hub: An Excellence Hub on Water in the Circular Economy.

Institutional Review Board Statement

Not applicable.

Data Availability Statement

The dataset is available in the open access repository Zenodo with the following digital object identifier: https://doi.org/10.5281/zenodo.21979693, accessed 26 August 2026.

Acknowledgments

The authors used Grammarly, an AI-powered writing assistant, to support grammar and language corrections during the preparation of this manuscript. All content was subsequently reviewed and approved by the authors to ensure accuracy and appropriateness.

Conflicts of Interest

The author declares no conflicts of interest.

Abbreviations

The following abbreviations are used in this manuscript:
CFConcentration Factor
THTotal Hardness
THexpExpected Total Hardness
THmeasMeasured Total Hardness
ΔTHDifference between Expected and Measured Total Hardness
CPIConcentration–Hardness Precipitation Index
LSILangelier Saturation Index
RSIRyznar Stability Index
TATotal Alkalinity
TDSTotal Dissolved Solids
SDStandard Deviation
rPearson correlation coefficient
R2Coefficient of Determination
pp-value
ISOInternational Organization for Standardization
EDTAEthylenediaminetetraacetic Acid
AgNO3Silver Nitrate
K2Cr2O7Potassium Dichromate
NaClSodium Chloride
CaCO3Calcium Carbonate
HClHydrochloric Acid
CASChemical Abstracts Service Registry Number
p.a.pro analysis
NPPsNuclear Power Plants
MAEMean absolute error
RSDRelative Standard Deviation

Appendix A. Comparative Assessment of Analytical Approaches

This appendix provides additional methodological information supporting the comparison between the proposed paper-based approach and conventional analytical methods used for the assessment of scaling tendency in recirculating cooling water.
Table A1. Comparative assessment of the proposed paper-based tests and conventional analytical methods for scaling-risk evaluation.

Appendix B. Laboratory-Scale Installation for Simulated Recirculating Cooling Conditions

Figure A1. Laboratory-scale installation for testing under simulated recirculating cooling conditions: (1) circulating-water tank, (2) pump power supply, and (3) heating element.
Table A2. Initial physicochemical characteristics of the make-up water (July 2026).

Appendix C. Operational Procedure for Paper-Based Colorimetric Tests A and B

Figure A2. Interpretation of scale formation risk based on the color responses of Tests A and B.

Appendix D. Additional Agreement and Uncertainty Assessment for Tests A and B

Because the paper-based tests provide discrete colorimetric responses, additional agreement metrics were calculated to complement Pearson’s correlation coefficient and the coefficient of determination. Test A was evaluated against the chloride concentration determined according to ISO 9297:1989, whereas Test B was evaluated against total hardness determined according to ISO 6059:1984. The calculations were based on the seven experimental concentration levels reported in Table A3.
The mean absolute error (MAE) was calculated as the arithmetic mean of the absolute differences between the colorimetric result and the corresponding reference-method mean formula (A1). Bias was calculated as the mean signed difference between the colorimetric and reference-method results formula (A2). Because both paper-based tests use discrete colour fields, categorical agreement was assessed in addition to continuous error metrics. For each experimental level, the reference-method result was assigned to the nearest predefined colorimetric category. The percentage of observations within ±1 category (P±1) was then calculated using Formula (A3). The concentration range represented by each colour category was assessed from the calibration scales used to construct the paper-based tests. Uncertainty per category was characterized using the standard deviation reported for the corresponding reference-method determination. These values describe the variability of the reference measurements and should not be interpreted as an experimentally determined measurement uncertainty of the paper-based tests. The latter could not be independently estimated from the available dataset because a dispersion estimate for repeated colorimetric readings at each individual calibration category was not reported. The reference measurements showed approximately 10% relative standard deviation across the investigated concentration range:
MAE = 1/n∑ ∣Ci −Ri∣
Bias = 1/n∑ ∣Ci −Ri∣
P±1 = N±1/N ×100
where Ci is the value assigned by the paper-based test, Ri is the corresponding mean value obtained by the reference method, and n = 7 is the number of experimental concentration levels, N±1 is the number of observations for which the difference between the observed colorimetric category and the category corresponding to the reference value was no greater than one category, and N is the total number of observations.
Table A3. Additional quantitative and categorical agreement characteristics of the paper-based Tests A and B.

References

  1. Kuznietsov, P.; Tykhomyrov, A.; Biedunkova, O.; Zaitsev, S. Improvement of Methods for Controlling Power Oil of Cooling Tower Recycling Water Supply Units at Rivne Nuclear Power Plant. Sci. Horiz. 2022, 25, 69–79. [Google Scholar] [CrossRef] [Scilit]
  2. Kuznietsov, P.; Biedunkova, O. Evaluating the Impact of Dispersed Particles in the Water of a Power Plant Recirculating Cooling System on the Discharge of Suspended Solids into a Natural Water Body. East.-Eur. J. Enterp. Technol. 2023, 6, 6–16. [Google Scholar] [CrossRef] [Scilit]
  3. Alimah, S.; Mellawati, J.; Ariyanto, S.; Haifani, A.M.; Salimy, D.H.; Indrawati, Y.; Khotimah, K. Challenges and mitigations of corrosion and scale in nuclear cogeneration desalination systems: A case study from West Kalimantan. Nucl. Eng. Technol. 2025, 58, 104100. [Google Scholar] [CrossRef] [Scilit]
  4. Guo, J.; Yang, W.; Wu, S.; Wei, X.; Wang, R.; Ma, R.; Xu, H. Scaling-risk early warning in industrial cooling-water systems: A chemically regularized machine-learning framework using routine water-quality data. J. Water Process Eng. 2026, 92, 110828. [Google Scholar] [CrossRef] [Scilit]
  5. Chen, X.; Wang, L.; Yu, Z.; Chen, X.; Sun, W.; Yang, Z.; Liu, G. Synergistic scale inhibition mechanisms in electrochemical water softening coupled with temperature-responsive star-shaped inhibitors. Chem. Eng. Sci. 2026, 333, 124242. [Google Scholar] [CrossRef] [Scilit]
  6. Langelier, W.F. The Analytical Control of Anti-Corrosion Water Treatment. J. Am. Water Works Assoc. 1936, 28, 1500–1521. [Google Scholar] [CrossRef] [Scilit]
  7. Ryznar, J.W. A new index for determining amount of calcium carbonate scale formed by a water. J.-Am. Water Works Assoc. 1944, 36, 472–483. [Google Scholar] [CrossRef] [Scilit]
  8. ISO 9297:1989; Water Quality—Determination of Chloride—Silver Nitrate Titration with Chromate Indicator (Mohr’s Method). International Organization for Standardization (ISO): Geneva, Switzerland, 1989. Available online: https://www.iso.org/standard/16952.html (accessed on 26 August 2026).
  9. ISO 6059:1984; Water Quality—Determination of the Sum of Calcium and Magnesium—EDTA Titrimetric Method. International Organization for Standardization (ISO): Geneva, Switzerland, 1984. Available online: https://www.iso.org/standard/12258.html (accessed on 26 August 2026).
  10. ISO 10523:2008; Water Quality—Determination of pH. International Organization for Standardization (ISO): Geneva, Switzerland, 2008. Available online: https://www.iso.org/standard/51994.html (accessed on 26 August 2026).
  11. ISO 6058:1984; Water Quality—Determination of Calcium Content—EDTA Titrimetric Method. International Organization for Standardization (ISO): Geneva, Switzerland, 1984. Available online: https://www.iso.org/standard/12257.html (accessed on 26 August 2026).
  12. ISO 7888:1985; Water Quality—Determination of Electrical Conductivity. International Organization for Standardization (ISO): Geneva, Switzerland, 1985. Available online: https://www.iso.org/standard/14838.html (accessed on 26 August 2026).
  13. ISO 9963-1:1994; Water Quality—Determination of Alkalinity—Part 1: Determination of Total and Composite Alkalinity. International Organization for Standardization (ISO): Geneva, Switzerland, 1994. Available online: https://www.iso.org/standard/17868.html (accessed on 26 August 2026).
  14. ISO 5667-14:2014; Water Quality—Sampling—Part 14: Guidance on Quality Assurance and Quality Control of Environmental Water Sampling and Handling. International Organization for Standardization (ISO): Geneva, Switzerland, 2014. Available online: https://www.iso.org/standard/55452.html (accessed on 26 August 2026).
  15. Benavides-Bolaños, J.A.; Echeverri-Sánchez, A.F.; Reyes-Trujillo, A.; del Mar Carreño-Sánchez, M.; Jaramillo-Llorente, M.F.; Rivera-Caicedo, J.P. In Situ Hyperspectral Reflectance Sensing for Mixed Water Quality Monitoring: Insights from the RUT Agricultural Irrigation District. Water 2025, 17, 1353. [Google Scholar] [CrossRef] [Scilit]
  16. Granata, F.; Papirio, S.; Esposito, G.; Gargano, R.; De Marinis, G. Machine Learning Algorithms for the Forecasting of Wastewater Quality Indicators. Water 2017, 9, 105. [Google Scholar] [CrossRef] [Scilit]
  17. Kyritsi, M.A.; Mouchtouri, V.A.; Katsioulis, A.; Kostara, E.; Nakoulas, V.; Hatzinikou, M.; Hadjichristodoulou, C. Legionella Colonization of Hotel Water Systems in Touristic Places of Greece: Association with System Characteristics and Physicochemical Parameters. Int. J. Environ. Res. Public Health 2018, 15, 2707. [Google Scholar] [CrossRef] [Scilit] [PubMed]
  18. Fernandes, E.; Cunha Marques, R. Review of Water Reuse from a Circular Economy Perspective. Water 2023, 15, 848. [Google Scholar] [CrossRef] [Scilit]
  19. Mannina, G.; Gulhan, H.; Ni, B.-J. Water Reuse from Wastewater Treatment: The Transition towards Circular Economy in the Water Sector. Bioresour. Technol. 2022, 363, 127951. [Google Scholar] [CrossRef] [Scilit] [PubMed]
  20. Karmil, F.Z.; Naribi, Z.; El Messaoudi, N.; Hassoune, J.; Georgin, J.; Al-Msiedeen, A.M.; El Alaoui-Belghiti, H. Electrocoagulation for water reclamation from industrial equipment cleaning wastewater: Purification, reuse, sludge management, and Corrosivity trade-off. Sep. Purif. Technol. 2026, 394, 137591. [Google Scholar] [CrossRef] [Scilit]
  21. Jana, S.; Subramanian, V.K. Effect of EDTA on Calcium Carbonate Scale Formation, Polymorphism, and Photocatalytic Performance on stainless steel (SS 304) at 60 °C. J. Alloys Compd. Commun. 2026, 100227. [Google Scholar] [CrossRef] [Scilit]
  22. Luo, J.; Zhan, Z.; Li, W.; Lei, Y. Coupling adsorption and electrochemically mediated precipitation for enhanced water softening and antiscalant recovery. Sep. Purif. Technol. 2025, 377, 134264. [Google Scholar] [CrossRef] [Scilit]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Article Metrics

Citations

Article Access Statistics

Multiple requests from the same IP address are counted as one view.