Abstract
This study presents a detailed numerical analysis of impinging propane flames within confined enclosures using the Fire Dynamics Simulator (FDS, v6.5.3). Two archetypal configurations were examined: (i) free buoyant plumes in unconfined environments, and (ii) ceiling-impinging flames under both open and confined conditions. The investigation encompassed a range of heat release rates (0.5–18.6 kW) and five degrees of ventilation confinement. The simulation results confirm that FDS reliably reproduces flame height evolution under free plume conditions, exhibiting strong consistency with Heskestad’s empirical correlation and available experimental benchmarks. Under ceiling impingement, confinement markedly influences the thermal field, the distribution of major gas species (O2, CO2, C3H8), and the accumulation of unburnt gas. Distinct from previous works primarily centered on unconfined plume dynamics, the present study systematically characterizes the onset of auto-ignition through combined lower flammability limit (LFL) and auto-ignition temperature (AIT) criteria for confined propane combustion. The highest auto-ignition risk was identified in partially confined configurations (Conf. 2 and Conf. 3) at an HRR of 18.6 kW, where unburnt propane concentrations locally exceeded the LFL (≈0.2%) and ceiling temperatures surpassed the AIT of propane (455 °C). The findings elucidate critical trade-offs between ventilation and safety. They also contribute to a validated FDS-based methodology for evaluating fire-induced flow structures, combustion behavior, and ignition hazards in confined spaces.
1. Introduction
The rapid pace of urbanization and the increasing complexity of building structures and industrial systems have substantially amplified the challenges associated with fire safety engineering, rendering it a critical and continuously evolving field of research. Understanding flame behavior, particularly turbulent diffusion flames impinging on ceilings within various confined configurations (e.g., buildings, tunnels, pipelines, vehicles), is critical due to its direct impact on flame spread, thermal loading, structural integrity, and occupant safety [1,2,3].
The high cost, logistical constraints, and inherent safety risks of conducting large-scale fire experiments in confined or complex environments have progressively shifted research efforts toward advanced numerical modeling. Among these, computational fluid dynamics (CFD) simulations have emerged as indispensable tools for analyzing fire-driven flows, combustion dynamics, and heat transfer phenomena under realistic conditions [4,5,6]. Unlike simplified zone models, CFD approaches resolve detailed spatial distributions of temperature, species, and flow fields essential for complex geometries and airflow patterns prevalent in modern structures [7,8].
Considerable progress has been achieved in modeling fire plumes and ceiling jet dynamics in open or weakly confined conditions [9,10] For instance, Chatterjee [11] employed Large Eddy Simulation (LES) to investigate ceiling flow driven by strong plumes of rack-storage fires. It is shown that the predicted temperature, radial velocity profiles, and ceiling layer depths agreed well with the experimental data and empirical correlation. Similarly, Hara and Kato [12] validated the accuracy and reliability of numerical simulation in predicting ceiling jets induced by fire plumes using a standard k-ε turbulence model. Meanwhile, Pchelintsev et al. [13] experimentally and numerically investigated the heat transfer and temperature correlations of a steel beam under a ceiling that was exposed to a localized fire source. In their work, the numerical simulation was carried out by a finite volume code CV-FEM and the general-purpose finite element code ANSYS 5.0. Moreover, comparisons between zone and field (CFD) models further highlighted CFD’s superiority in capturing phenomena like smoke filling in atria [14] and complex flow patterns, such as smoke backflow in tunnels under specific ventilation conditions [15,16].
Among CFD tools, the Fire Dynamics Simulator (FDS) has become widely adopted in fire research and has been validated for fundamental fire plume behavior. Wang et al. [17] presented a numerical study on the vertical flame height and horizontal flame extension of a pool fire under the ceiling using FDS. They used the stoichiometric mixture fraction to define the continuous flame height and compared the predicted vertical and horizontal flame heights against existing correlations and experimental results. It was found that the predicted horizontal flame extension agreed well with correlations in which the continuous flame height is about three-fifths of the experimental mean flame height. Moreover, this correlation obtained reasonable agreement to the experimental data of Gross et al. [18]. Y. Lattimer and Hughes [19] carried out experiments and simulations on a flame impinging a ceiling to highlight the effects of the ceiling on the centerline temperature and vertical velocities of fire plume. Simulation results by FDS do compare reasonably well with experiment results.
However, while substantial work exists on free plumes or fires under open ceilings [20], numerical investigations specifically focused on flames impinging on ceilings within significantly confined spaces remain comparatively limited. This scenario is highly relevant to tunnels and compartment fires in fire safety engineering. FDS has been continually used in the simulation of turbulent flames under ceilings in confined configurations. In the work of Hurley and Munguia [21], the predictions of the ceiling temperature and detector response of FDS models were compared to full-scale experimental results. Huang et al. [22] conducted FDS models to study the effects of the entrance sealing ratio on fire dynamics in tunnel fires. The previous correlations predicting temperature distribution under ceilings were modified by taking the sealing ratio into account. Wang et al. [23] used FDS to conduct a series of simulations of full-scale inclined tunnels to study the effect of tunnel width and slope on ceiling gas temperature. It was shown that the results of FDS fit well with small-scale and full-scale experiments.
Furthermore, in confined or under-ventilated spaces, the interaction of flames with the ceiling and the development of a hot smoke layer can lead to extreme hazards such as local extinction of gas-phase flames, accumulation of unburnt combustible gases, and subsequent backdraft or smoke explosions [24]. The underlying mechanisms of these phenomena are closely tied to the limiting conditions for gas-phase ignition and extinction. Considerable research has been conducted in recent years on backdraft, smoke explosions, and auto-ignition of gaseous fuels. For example, studies on backdraft experiments and FDS simulations have provided detailed insights into the conditions and dynamics of backdraft occurrence [25,26]. Similarly, other investigations have explored the risk of auto-ignition for combustible gas layers exposed to hot surfaces or pilot sources under varied ventilation conditions [27,28]. These studies underscore the critical importance of the coupled analysis of temperature and flammable gas concentration fields for assessing fire transition and extreme risks in confined spaces.
As mentioned above, FDS has been increasingly applied to model turbulent flames under ceilings in confined configurations. Yet, a critical research gap persists. Specifically, understanding fire safety in confined compartments critically depends on elucidating flame–ceiling interactions and the associated high-risk phenomena like unburnt gas auto-ignition. However, few studies have systematically correlated confinement and ventilation conditions with the potential for auto-ignition using coupled gas concentration and temperature criteria to assess flammability risks, which forms a crucial link between fire dynamics and fundamental research on gas-phase ignition/extinction.
The present study aims to bridge this gap by conducting a systematic numerical investigation of ceiling-impinging propane flames under varying confinement and ventilation levels. Using Large Eddy Simulation (LES) via the Fire Dynamics Simulator (FDS v6.5.3), heat release rates ranging from 0.5 to 18.6 kW are examined across configurations spanning from fully open to fully confined enclosures, with a primary focus on the comparative effects of confinement on overall fire dynamics and gas accumulation. Building upon previous experimental findings [29,30], the study introduces an integrated methodology combining temperature and concentration-based criteria (LFL + AIT) to delineate auto-ignition thresholds under confinement.
This paper is structured as follows: Section 2 details the numerical simulation methodology for the fire plumes in open and impinging flames under a ceiling. Section 3 systematically presents and analyses the numerical results, focusing on confinement effects on the impinging condition and on the temperature distribution, ventilated conditions and combustion regimes, gas analysis and unburnt fuel accumulation, and auto-ignition risk assessment. Finally, Section 4 summarizes the principal conclusions and suggests future research directions. This work establishes a validated approach for simulating confined fire dynamics and provides insights linking ventilation design directly to auto-ignition hazard mitigation.
2. Numerical Modeling
2.1. Solution Methodology and Numerical Framework
2.1.1. Software Selection and Overall Numerical Approach
The open-source computational framework Fire Dynamics Simulator (FDS, version 6.5.3) was employed to perform the numerical simulations conducted in this study. This version was selected based on its extensive validation for fundamental fire plume and enclosure fire dynamics. While subsequent releases contain improvements in sub-models, the core Large Eddy Simulation (LES) solver for buoyancy-driven flow and combustion in version 6.5.3 is well-established and provides a robust, stable foundation for the present study, which focuses on flame impingement and ceiling jet dynamics in a confined enclosure. The LES approach was adopted as it offers an optimal balance between computational cost and physical fidelity for fire-driven flows, explicitly resolving the large, energy-carrying eddies while modeling the effects of smaller, dissipative scales.
2.1.2. Numerical Framework and Solution Procedure
The overall computational workflow is illustrated in Figure 1. The process begins with the definition of the computational geometry and mesh, followed by the specification of the boundary and initial conditions. The core FDS solver then advances the solution in time. The primary outputs for analysis are the transient and time-averaged flow and temperature fields.
Figure 1.
The overall computational workflow in the simulation of FDS.
FDS solves an approximate form of the Navier–Stokes equations, appropriate for low-Mach number (Ma < 0.3), buoyancy-driven flows. This formulation filters out acoustic waves, allowing for large variations in temperature and density while treating the pressure as elliptical, consistent with low-speed thermal convection [31]. The governing equations are discretized on a rectilinear grid using a finite-volume method. Pressure–velocity coupling is handled via a SIMPLE-type predictor–corrector algorithm. The associated linearized equation systems are solved using a preconditioned conjugate gradient method. Within each time step, the solution procedure is iterated until the scaled residuals for all transported variables (momentum, energy, and chemical species) fall below 10−6, ensuring strict iterative convergence.
2.1.3. Governing Equations and Physical Models
The adopted conservation equations are described in the following [32]:
Mass conservation:
Momentum conservation:
Species conservation:
Energy conservation:
In the LES framework, closure for the subgrid-scale (SGS) stresses and scalar fluxes is required. FDS employs the gradient diffusion hypothesis, with turbulent transport coefficients derived from a turbulent viscosity, μt. The turbulent Prandtl and Schmidt numbers are taken as constant (Prt = Sct = 0.5). Based on this definition of turbulent viscosity, FDS incorporates five turbulence models: the Smagorinsky model, the Deardorff model (default), the Vreman model, the Renormalization Group (RNG) model, and the Wall-Adapting Local Eddy-viscosity (WALE) model.
For the present study, the Wall-Adapting Local Eddy-viscosity (WALE) model [32] was selected instead of the default Deardorff model. The WALE model provides a more accurate scaling of the turbulent viscosity in the near-wall region (μt ∝ y3), which is crucial for resolving the confined ceiling jet development. The model defines the dynamic turbulent viscosity as follows:
where
The strain and rotation tensors are given by the following:
Nicoud and Ducros [33] have suggested the range of the model constant: . In FDS, is used based on the results for decaying isotropic turbulence [34].
In the present simulations, combustion was modeled using a two-step finite-rate reaction mechanism for propane. The first reaction (R1) describes the incomplete oxidation of propane: C3H8 + 1.5 O2 → 2 CO + 2 H2O, with a critical flame temperature of 700 °C (CRITICAL_FLAME_TEMPERATURE = 700.). The second reaction (R2) describes the oxidation of carbon monoxide: CO + 0.5 O2 → CO2, using an Arrhenius rate with a pre-exponential factor of 1.5 × 109 and an activation energy of 41,840 kJ/kmol.
The radiative fraction was set to 0.35 (RADIATIVE_FRACTION = 0.35), and a soot yield of 0.015 (SOOT_YIELD = 0.015) was specified for propane. The chosen radiative fraction serves as a lower bound to mitigate uncertainties in radiation calculations arising from temperature field inaccuracies. While a formal sensitivity analysis of this parameter was not conducted, the study focused on a comparative analysis of confinement and ventilation effects under a consistent modeling setup.
2.1.4. Simulation Configuration and Computational Details
The burner was modeled as a circular vent with a radius of 2.5 mm, centered at (0.2 m, 0.3 m, 0 m). A propane mass flux of 5.1 kg m−2 s−1 was prescribed at the burner surface (MASS_FLUX = 5.1, SPEC_ID = “PROPANE”). The heat of combustion of propane was equal to 46.45 × 103 kJ/kg. The ambient temperature was specified as 20 °C.
A nominal time step was specified as 0.01. During the simulations, the actual time step was dynamically reduced wherever required to ensure the Courant–Friedrichs–Lewy (CFL) constraint < 1, particularly in high-velocity regions near the flame. The iterative sequence within each time step was as follows: (i) solve momentum equations using the current pressure field; (ii) solve the pressure-correction equation from the continuity constraint; (iii) update velocity and pressure fields; (iv) solve transport equations for energy and chemical species. This loop repeated until convergence criteria were met.
All simulations were executed on the ARTEMIS high-performance computing (HPC) cluster, provided by the Région Centre-Val de Loire (France). The simulations exploited FDS’s parallel computing capabilities via the Message Passing Interface (MPI), with the computational domain decomposed into 24 subdomains distributed across CPU cores. This parallelization strategy was crucial for reducing computation time while maintaining numerical stability and efficient convergence.
2.2. Modeling of Fire Plume in Open
2.2.1. Computational Setup and Boundary Conditions
For the open fire case, open boundary conditions were applied at all domain boundaries except for the floor. In the Fire Dynamics Simulator (FDS), an “OPEN” boundary condition defines a pressure boundary that permits fluid to freely enter or exit the computational domain.
To mimic the experiment, the fire source was modeled by propane injected with a uniform velocity through a centrally placed circular vent with a 5 mm diameter on the solid wall. A Cartesian mesh was used in FDS, so the circular burner was “stair-stepped” from a scare area. The heat release rate (HRR) varied from 0.5 kW to 18.6 kW. The required HRR was produced by specifying the total mass flow rate per unit area (kg/(m2∙s) via the parameter MASS_FLUX of the burner. Thus, the HRRs in the simulations were determined by multiplying the mass flow rate per unit area, area of the burner, and the heat of combustion of the fuel. All simulation cases ran for 10 s of simulation with the last 5 s for steady state averaging.
2.2.2. Mesh Sensitivity Analysis
For any CFD analysis, mesh size is an important consideration since it can significantly influence the simulation results, as FDS is based on Large Eddy Simulation, of which the mesh should be fine enough to allow the formation of eddies that are responsible for the mixing [35]. With a finer grid, more relevant length scales are resolved directly and fewer are modeled in FDS. Consequently, the predictions are much closer to the measurements.
In general, a good CFD software should provide a relatively constant result in a certain range of mesh size. Baum et al. [36] suggested that 10 × 10 grids over the burner surface can correctly characterize it. However, this empirical rule is not enough when dealing with a wide range of fire intensity. Thus, FDS provides a widely used characteristic fire diameter that considers the effects of fire size, burner diameter, etc. The reference range of mesh sizes in simulation can be obtained by the following equations [35]:
In each series of experiments, eight different heat release rates (HRRs) were considered: HRR = {0.5, 1.2, 2.3, 4.6, 9.3, 14.0, 16.3, 18.6} kW, corresponding to the mass flow rates of fuel: {0.01, 0.025, 0.05, 0.1, 0.2, 0.3, 0.35, 0.4} g/s, respectively. To maintain consistency with the experimental datasets, these HRRs were also implemented in the numerical simulations. Considering the minimum HRR of 0.5 kW, the estimated grid size, computed using Equations (1) and (2), ranged from 0.7 mm to 1 cm. Consequently, six distinct mesh resolutions, 8 mm, 6 mm, 5 mm, 4 mm, 3 mm, and 2.5 mm, were systematically employed to evaluate mesh sensitivity on the simulation outcomes. A summary of the mesh configurations is provided in Table 1.
Table 1.
Summary of mesh descriptions.
The computational domain, measuring 0.3 m × 0.3 m × 0.25 m, was defined in a rectangular Cartesian coordinate system with its origin at the center of the fire source. To adequately resolve the critical flame region near the burner (radius = 2.5 mm), the grid size in its immediate vicinity was constrained to ≤2.5 mm. Accordingly, a non-uniform mesh was implemented using the TRNX and TRNY stretching functions in FDS. This created a refined subdomain of 0.06 m × 0.06 m centered on the burner, within which a constant, high-resolution mesh spacing of 2.5 mm was maintained. Outside this region, the grid was gradually stretched towards the domain boundaries, where a coarser uniform mesh was applied to enhance computational efficiency. This hybrid approach ensures sufficient resolution in areas with high gradients while managing the total cell count effectively.
Figure 2 presents the cross-sectional mesh images of fire plumes at 8.0 s for simulations with the following mesh sizes: (a) M1; (b) M2; (c) M3; (d) M4; (e) M5; (f) M6. The figure also illustrates the computational domain, the non-uniform mesh layout, and the refined region near the burner. As shown, the simulated flame morphology becomes progressively clearer with decreasing mesh size.
Figure 2.
Cross-sectional mesh images of fire plumes at 8.0 s for simulations with following mesh sizes: (a) M1; (b) M2; (c) M3; (d) M4; (e) M5; (f) M6.
Figure 3 illustrates the influence of grid resolution on centerline temperature and velocity. It is observed that the peak centerline temperature increases with coarser grids, and, at a given height along the centerline, temperature values also rise with increasing grid size. The convergence of temperature profiles is noted between the M5 and M6 meshes, indicating that further grid refinement does not significantly alter the results. Similarly, the centerline velocity exhibits analogous trends with grid refinement. Based on these sensitivity analyses, the M5 mesh (grid size of 3 mm) was selected for subsequent simulations, as it provides grid-independent results while optimizing computational cost.
Figure 3.
The effect of grid size on (a) temperature; (b) velocity in the centerline.
2.2.3. Selection of Computational Domain
In the numerical simulation, the computational domain plays an important role for the accuracy of the simulation results [37]. In order to choose a suitable computational domain, three numerical simulations were carried out in three computational domains with different dimensions and the maximum HRR of 18.6 kW was used as the input fire power. As presented in Table 2, the dimensions of three computational domains are 0.1 m × 0.1 m × 1.2 m, 0.3 m × 0.3 m × 1.2 m, and 0.5 m × 0.1 m × 1.2 m, respectively. In consideration of the fire plume in the small domain, the fire plume was obviously limited by the boundary of the computational domain so that it is necessary to increase the computational domain. In consideration of the fire plume in the medium domain and large domain, the dimensions of the computational domain had little effect on the flame shape.
Table 2.
Summary of computational domains.
The sensitivity of the simulation results to the size of the computational domain was investigated. The predicted centerline temperature and velocity for three domain sizes are compared in Figure 4. The results demonstrate that the centerline velocity profiles for the medium and large domains converge perfectly (Figure 4b). As the velocity field is the primary indicator of established plume dynamics in buoyancy-driven flows, this convergence provides strong evidence that the medium domain is sufficiently large to avoid confinement effects and capture the core physics of the fire plume. Minor differences in centerline temperature are observed, predominantly in the fluctuating flame tip region above ~0.8 m (Figure 4a). These local discrepancies are attributed to the inherent unsteadiness of the turbulent flame in this zone, which leads to a greater sensitivity to the specifics of the time-averaging procedure over the 10 s simulation. Crucially, the temperature profiles in the well-developed, persistent region of the plume are in close agreement. While a longer averaging window could further smooth the results in the intermittent region, the computational cost for the large domain was approximately three times greater than for the medium domain. Given the exact agreement on the fundamental flow variable (velocity) and the good engineering agreement on temperature for the parametric study undertaken, the medium computational domain was selected. This choice represents an optimal balance, ensuring the accurate resolution of key plume dynamics while maintaining computational efficiency for the extensive simulation matrix required in this work.
Figure 4.
The effects of computational domain on (a) temperature; (b) velocity in the centerline.
2.2.4. Validation
In the present study, a temperature threshold of 520 °C was adopted to define the flame height, such that the flame height corresponds to the region where the temperature exceeds this value [38]. Figure 5 presents the comparison of dimensionless flame height obtained by FDS, experimental, and Heskestad’s correlations.
Figure 5.
Comparison of dimensionless flame height obtained by FDS, experimental, and Heskestad’s correlations.
FDS predictions demonstrate excellent agreement with Heskestad’s correlation at lower heat release rates (HRRs). However, as the HRR increases, a slight overprediction of flame height by FDS becomes apparent, indicating a potential limitation of the model under more intense fire conditions. Despite this discrepancy at higher HRRs, the overall agreement is strong, with the predicted flame heights fitting the correlation remarkably well, evidenced by a minimal relative gap (RG) of only 3.84%.
In contrast to the numerical results, the experimental data exhibit a larger overall discrepancy from Heskestad’s correlation, with a relative gap (RG) of 13.45%. A detailed examination reveals that this discrepancy is primarily driven by the low HRR conditions, where measured flame heights are consistently higher than the theoretical predictions. At higher HRRs, however, the agreement is satisfactory. The systematic overestimation at low HRRs is likely attributable to a minor underestimation of the fuel mass flow rates during experimentation, potentially resulting from the limited precision of the flowmeter employed.
2.3. Modeling of Impinging Flame Under a Ceiling
Based on the refined mesh and computational domain described in Section 2.2, a more complex scenario involving an impinging flame under a ceiling within an enclosure was modeled.
2.3.1. Computational Domain, Mesh, and Configurations
As shown in Figure 6, a cuboidal computational domain measuring 0.6 m (length) × 0.8 m (width) × 0.3 m (height) was established for the study of ceiling-impinging flames. To accurately simulate the open environment for Configuration 1 (open ceiling) and to improve the numerical stability and outflow conditions for the confined configurations, an extension domain was added around the primary region of interest [37,39].
Figure 6.
Schematic of the computational setup (a) in open; (b) in confined enclosure.
As shown in Figure 6b, the compartment geometry is based on a 1:10 scale model of a typical student compartment in France. The detail dimension of the small-scale compartment was 0.6 m (length) × 0.4 m (width) × 0.24 m (height). The dimension of the window was 0.15 m (height) × 0.15 m (width) while the dimension of the door was 0.2 m (height) × 0.09 m (width).
To accurately resolve the flow and thermal boundary layers at the ceiling, a uniform Cartesian mesh with a cell size of 2.5 mm (i.e., ) was employed throughout the domain, resulting in a total of 9.216 million cells. A prior mesh sensitivity analysis confirmed that this resolution adequately captures the key flow and thermal features of interest.
To align with the experimental setup, five configurations were examined. Configuration 1 (Conf. 1) represented a flame impinging on a ceiling in an open environment, with a burner-to-ceiling height of 0.24 m. Configurations 2 through 5 (Conf. 2–5) involved the flame impinging on a ceiling within a confined compartment, with varying levels of confinement achieved by different window and door states: both open (Conf. 2), window open/door closed (Conf. 3), window closed/door open (Conf. 4), and both closed (Conf. 5). Consequently, the degree of confinement increased progressively from Conf. 2 to Conf. 5.
In all simulated cases, the fire source was positioned centrally on the floor, directly beneath the center of the ceiling. A series of heat release rates (HRRs) were investigated. For the open environment case (Configuration 1), six HRRs—{0.5, 2.3, 4.6, 9.3, 14.0, 18.6} kW—were simulated to validate the modeling approach. Given the open boundary conditions, the fire reached a steady state rapidly; therefore, a simulation time of 10 s was sufficient, with the quasi-steady condition typically established after the initial 2 s.
For the confined compartment cases (Configurations 2 to 5), three representative HRRs were selected: 0.5 kW (minimum), 4.6 kW (medium), and 18.6 kW (maximum), corresponding to the experimental range. To allow the compartment fire to fully develop and reach a thermally steady state, a longer simulation time of at least 30 s was employed for each confined configuration.
2.3.2. Boundary Conditions and Material Properties
To accurately model the open atmosphere and improve numerical stability, an extension domain was added surrounding the primary region of interest. On all external surfaces of this extension domain (except the floor), an OPEN boundary condition was applied. This condition was also used for the physical door and window openings in Configurations 2 and 3.
In FDS, the OPEN boundary fixes the static pressure to the ambient reference pressure (approximately 1 atm), allowing for fully bi-directional flow driven by buoyancy and internal pressure gradients. No velocity or mass flow rates are prescribed. Inflowing fluid is assigned ambient properties (20 °C, 21 vol% O2). Consequently, the airflow through these openings emerges naturally from the simulation rather than being a predefined input.
The material properties were specified to reflect common construction. The compartment walls were modeled as CONCRETE with the following properties: density = 2200 , thermal conductivity = 1.2 and specific heat = 0.88 The ceiling of the compartment was made of steel with a density of 7850 , a thermal conductivity of 46 , a specific heat of 0.5 , and an emissivity of 0.9.
2.3.3. Data Monitoring and Output
A strategic data acquisition plan was implemented, targeting specific locations to capture the key physical processes of the compartment fire. Monitoring was configured for three primary purposes: quantifying boundary thermal loads, resolving interior vertical profiles, and visualizing spatial distributions.
To capture the effects of flame impingement on the ceiling, Boundary File (BNDF) outputs were configured on the ceiling surface. These files record the spatial distribution of heat release rate per unit volume (HRRPUV) and net heat flux, enabling detailed visualization and quantification of the corresponding thermal loads on the ceiling boundary.
As shown in Figure 7 (left), a series of point probes were placed along a vertical line at the compartment’s center, extending from the burner surface to the ceiling to capture transient gas-phase properties and plume stratification. Using DEVC files, this array recorded time-history data for temperature and the concentrations of O2, CO2, and unburnt propane.
Figure 7.
Source location or plane of the output data.
To visualize the two-dimensional structure of the fire plume and species distribution, key monitoring planes were defined on the vertical mid-plane of the compartment, as shown in Figure 7 (right). Using SLCF files, these planes captured contour data for temperature, O2, and CO2 concentrations.
This combination of surface, point, and planar diagnostics provides a comprehensive, multi-dimensional dataset for analyzing the compartment fire’s behavior.
2.3.4. Validation with Flame Height
In order to validate numerical FDS modeling for flames under a ceiling, the flame extension length under the ceiling was compared to the experimental data. Figure 8 presents the comparison of predicted dimensionless flame height against dimensionless heat release rate with experiment data, with a relative gap (RG) of 9.3%. It shows that the predictions of FDS can agree well with the experimental data, despite minor deviations. The dimensionless flame height exhibits a linear relationship with the dimensionless heat release rate to the power of 0.4. Thus, FDS modeling can be used in the predictions of flame extension length under the ceiling.
Figure 8.
Comparison of predicted dimensionless horizontal flame extension length with experiment data.
2.4. Risk Assessment Methodology
To assess the auto-ignition risk of unburnt gas in the confined compartment, two critical parameters were considered: the concentration of unburnt gas near the ceiling and the smoke temperature in the same region. These parameters were then compared against the flammability limit and the auto-ignition threshold of the fuel present in the smoke.
The concentrations of total unburnt gas in confined enclosure at three different HRRs were calculated with the following:
Table 3 lists the values of , , and of CO, H2, and propane [40] at ambient temperature and pressure. Flammability limits can be extended into a wide range of temperatures using the Burgess-Wheeler law [41]:
where and represent the lower flammable limit at the temperature of and , respectively, and and represent the upper flammable limit at the temperature of and respectively.
Table 3.
Values of , , and of CO, H2, and propane [40].
In consideration of the flammable gas mixture, Le Chatelier [42] proposed an empirical equation to predict the lower and upper flammability limits using the following equations:
where are the percentage composition, lower flammable limit, and upper flammability limit of the th component, respectively, considering only combustible species.
3. Results and Discussion
3.1. Confinement Effect on the Impinging Condition and Temperature Distribution
3.1.1. Impinging Condition on the Ceiling
Figure 9 depicts the flame impingement condition on the ceiling at heat release rates (HRRs) of 4.6 kW and 18.6 kW, showing (a) the 3D distribution of smoke via HRRPUV and (b) the corresponding net heat flux. As illustrated in Figure 9a, at the lower HRR of 4.6 kW, the flame generates a circular impingement zone on the unconfined ceiling, reflecting the axisymmetric nature of the vertical flame and uniform entrainment of ambient air. In contrast, at the maximum HRR of 18.6 kW, the flame extends nearly to the ceiling dimension, producing a broader and more concentrated impingement region characterized by intensified thermal interaction with the ceiling surface.
Figure 9.
Flame impinging condition on the ceiling: (a) 3D smoke of HRRPUV; (b) net heat flux.
Figure 9b demonstrates that the net heat flux to the ceiling increases substantially as the HRR rises from 4.6 kW to 18.6 kW. This pronounced enhancement is attributable to the increased flame intensity and augmented thermal output under higher HRR conditions, which amplify both convective and radiative heat transfer mechanisms at the ceiling interface. The figure further illustrates the relative growth in net ceiling heat flux with elevated HRRs. It should be noted that the absolute values, particularly at the stagnation point, may be underpredicted by the default convection model employed here [43]. Nevertheless, the spatial trends and comparative differences between configurations remain informative for assessing the thermal load distribution.
To further elucidate the spatial evolution of the ceiling-adjacent flame, Figure 10 presents the centerline temperature profiles beneath the ceiling for HRRs of 4.6 kW and 18.6 kW, providing a quantitative representation of flame spreading and thermal stratification along the ceiling surface.
Figure 10.
Temperature filled in the centerline of the flame at HRR = 4.6 kW and HRR = 18.6 kW.
3.1.2. Temperature Distribution in the Confined Compartment
Figure 11 presents the centerline temperature distributions for confined compartment configurations at three representative heat release rates (HRRs): (a) 0.5 kW, (b) 4.6 kW, and (c) 18.6 kW. At the lowest HRR of 0.5 kW, semi-confined configurations exhibit similar vertical temperature profiles, consistent with well-ventilated combustion conditions. In contrast, the fully confined configuration (Conf. 5) demonstrates a marked temperature decay toward the ceiling, indicative of under-ventilated or oxygen-limited combustion.
Figure 11.
Centerline temperature distribution for confined configurations at (a) HRR = 0.5 kW; (b) HRR = 4.6 kW; (c) HRR = 18.6 kW.
As the HRR increases from 0.5 kW to 18.6 kW, a general reduction in peak gas temperature is observed across all configurations. This trend reflects the progressive limitation of available oxygen within the compartment: despite higher thermal power, the restricted ventilation reduces combustion efficiency, leading to lower local gas temperatures. It is noted that this behavior diverges from typical experimental observations, likely due to the absence of leakage or infiltration flows in the numerical model.
Figure 12 illustrates the instantaneous temperature fields (at t = 1.5 s) for HRR = 4.6 kW across Configurations 2 to 5. In Conf. 2, characterized by an open door and window, a coherent flame plume with well-defined smoke stratification is observed, confined to the upper portion of the compartment. With increasing confinement from Conf. 3 to Conf. 5, the smoke layer progressively descends, culminating in full volumetric smoke filling in the fully enclosed configuration. This evolution demonstrates the transition from ventilation-controlled to ventilation-limited combustion regimes.
Figure 12.
Instantaneous (t = 1.5 s) temperature fields at HRR = 4.6 kW: (a) Conf. 2; (b) Conf. 3; (c) Conf. 4; (d) Conf. 5.
These thermal and smoke dynamics highlight how increasing confinement transforms the internal compartment environment from one exhibiting distinct stratification to one dominated by homogeneous smoke filling and suppressed peak temperatures. Such insights provide a critical foundation for understanding the subsequent gas accumulation, flammability hazards, and auto-ignition potential within confined compartments.
3.2. Ventilated Conditions and Combustion Regimes
The analysis of combustion regimes in this section builds upon the equivalence ratio (φ) framework established in prior experimental studies of confined impinging flames [29,30]. While φ remains a key underlying parameter governing the transition from well-ventilated to under-ventilated conditions, the present numerical analysis focuses on quantifying the resultant macroscopic effects, such as heat release rate stability, gas accumulation, and thermal stratification, across the defined ventilation configurations (Conf. 2–Conf. 5).
To evaluate the flame behavior under varying confinement levels, the numerically obtained heat release rates (HRRs) for four confined configurations are analyzed across specified fire powers ranging from 0.5 kW to 18.6 kW. Figure 13a illustrates the evolution of actual HRR over time at a theoretical HRR of 0.5 kW. For Conf. 2, 3, and 4, the actual HRR remains stable at 0.5 kW, indicating well-ventilated combustion. In contrast, Conf. 5, the fully confined configuration, exhibits significant HRR fluctuations due to under-ventilated conditions.
Figure 13.
Actual HRRs’ evolution against time in confined configurations with theoretical HRRs at (a) 0.5 kW; (b) 4.6 kW; (c) 18.6 kW.
At a theoretical HRR of 4.6 kW (Figure 13b), the actual HRR in semi-confined configurations (Conf. 2 and Conf. 3) remains close to the specified value, though with increased instability, while in Conf. 4, a highly confined and under-ventilated case, the combustion becomes markedly unsteady. In Conf. 5, the flame is completely quenched at approximately 1.5 s. When the theoretical HRR increases to 18.6 kW (Figure 13c), semi-confined configurations (Conf. 2 and Conf. 3) show a gradual increase in actual HRR. Eventually, it stabilizes near the specified value, which is a pattern typical of under-ventilated combustion. In Conf. 4, stronger fluctuations are observed, whereas in Conf. 5, flame quenching occurs around 0.5 s.
The actual HRR evolution depicted in Figure 13 serves as key evidence for understanding the transition in combustion states: from well-ventilated to ventilation-controlled and ultimately to flame quenching as confinement increases. Configurations can be categorized as follows: Conf. 2 and Conf. 3 (marginally under-ventilated but with sustained combustion due to openings), Conf. 4 (highly confined and under-ventilated with unstable combustion), and Conf. 5 (extremely confined, leading to rapid flame quenching).
It should be noted that the simulation accuracy is limited under highly confined and under-ventilated conditions (e.g., Conf. 4 and Conf. 5), where FDS is known to be less reliable [44]. Future work should focus on improving predictive accuracy and addressing this inherent limitation of FDS. Nevertheless, these limitations do not undermine the validity of the analysis for semi-confined configurations (Conf. 2 and Conf. 3), where sustained combustion leads to significant unburnt gas accumulation and high temperature risks.
3.3. Gas Analysis and Unburnt Fuel Accumulation
In this section, the gas analysis will be discussed involving the concentration distributions of O2 and CO2 as well as propane.
Figure 14 plots the oxygen concentration in the centerline for four confined configurations with the following: (a) HRR = 0.5 kW; (b) HRR = 4.6 kW; (c) HRR = 18.6 kW. At HRR = 0.5 kW, oxygen concentration increases from the floor to the ceiling, implying a well-ventilated condition. At HRR = 4.6 kW and HRR = 18.6 kW, for Conf. 2, Conf. 3, and Conf. 4, oxygen concentration decreases to about 0.5% along the height from the floor to the ceiling, implying an under-ventilated condition. In consideration of the complete confined configuration, i.e., Conf. 5, oxygen concentration is always larger than in other confined configurations and it is above 0.1 (mol/mol) even at HRR = 18.6 kW. However, the flame is quenched rapidly in Conf. 5 because the temperature is lower than the specified temperature in combustion models.
Figure 14.
Oxygen concentration in the centerline for four confined configurations with (a) HRR = 0.5 kW; (b) HRR = 4.6 kW; (c) HRR = 18.6 kW.
Figure 15 depicts the instantaneous (t = 1.5 s) oxygen concentration field at HRR = 4.6 kW: (a) Conf. 2; (b) Conf. 3; (c) Conf. 4; (d) Conf. 5. It is observed that for less confined configurations, i.e., Conf. 2, Conf. 3, and Conf. 4, the oxygen layer is thinner in the upper domain with the consumption of the combustion. In complete confined configuration, i.e., Conf. 5, just the oxygen near the burner is consumed while the oxygen is abundant in the whole compartment. It can be further induced that the oxygen concentration is not the determined parameter for combustion in the current numerical modeling.
Figure 15.
Instantaneous (t = 1.5 s) oxygen concentration field at HRR = 4.6 kW: (a) Conf. 2; (b) Conf. 3; (c) Conf. 4; (d) Conf. 5.
Figure 16 plots the CO2 concentration in the centerline for four confined configurations: (a) HRR = 0.5 kW; (b) HRR = 4.6 kW; (c) HRR = 18.6 kW. At HRR = 0.5 kW, the evolution of CO2 concentration in the less confined configurations, i.e., Conf. 2, Conf. 3, and Conf. 4, firstly increases and then decreases from the floor to the ceiling, owing to the fire plume being lower than the ceiling. While HRR = 4.6 kW and HRR = 18.6 kW, the CO2 concentration firstly increases and then maintains constant near the ceiling, owing to the steady smoke layer near the ceiling. The concentration of CO2 in Conf. 5 is constantly lower than in other confined configurations, because of the under-ventilated conditions. In the combination of the instantaneous (t = 1.5 s) CO2 concentration field at HRR = 4.6 kW presented in Figure 17, smoke stratifications are clearly presented in less confined configurations while the whole compartment is filled with smoke in the complete configuration, i.e., Conf. 5. These agree with the discussions previously.
Figure 16.
CO2 concentration in the centerline for four confined configurations: (a) HRR = 0.5 kW; (b) HRR = 4.6 kW; (c) HRR = 18.6 kW.
Figure 17.
Instantaneous (t = 1.5 s) CO2 concentration field at HRR = 4.6 kW: (a) Conf. 2; (b) Conf. 3; (c) Conf. 4; (d) Conf. 5.
Figure 18 illustrates the propane concentration in the centerline for four confined configurations: (a) HRR = 0.5 kW; (b) HRR = 4.6 kW; (c) HRR = 18.6 kW. At HRR = 0.5 kW, the propane concentration in all configurations drops rapidly to zero along the centerline approaching the ceiling. A similar trend is observed at 4.6 kW, though the concentration stabilizes at a low but non-zero value near the ceiling. A notable shift occurs at 18.6 kW, where a significant accumulation of unburnt propane is observed near the ceiling, particularly in the semi-confined configurations (Conf. 2 and Conf. 3), with concentrations reaching approximately 0.2%. This value, while below the lower flammability limit (LFL) of 2.1 mol% in absolute terms, indicates a clear trend toward hazardous accumulation under high HRR conditions. Such propane buildup is absent in both the more open Conf. 1 and the fully confined Conf. 5.
Figure 18.
Unburnt propane concentration in the centerline for four confined configurations: (a) HRR = 0.5 kW; (b) HRR = 4.6 kW; (c) HRR = 18.6 kW.
This phenomenon arises from the combined effect of the confined geometry, the under-ventilated yet partially open conditions that allow limited gas exchange, and the sufficiently high fire power. Together, these factors promote incomplete combustion and lead to the local enrichment of unburnt fuel in upper compartment regions, highlighting a distinct gas accumulation risk in partially confined fire scenarios.
3.4. Auto-Ignition Risk Assessment
In the scope of risk analysis, to estimate the risk with more warranty, the minimum value of the LFL and AIT are being considered. In our risk assessment methodology, we adopted a conservative, worst-case criterion. Among the primary flammable gases present (CO, H2, C3H8), propane has the lowest individual lower flammability limit (LFL = 2.1 mol%). Therefore, to ensure a stringent safety assessment, we used the LFL of propane as the threshold for the total unburnt gas mixture.
Thus, the concentrations of total unburnt gas (CO, H2, C3H8) calculated via Equation (10) in the confined enclosure at three different HRRs are compared to the LFL value of propane. The ceiling temperature in each configuration at three HRRs, in Figure 11, is also compared to the auto-ignition temperature (AIT) of propane. Therefore, the auto-ignition risk in four confined configurations at three HRRs can be evaluated with the concentration of unburnt gas and temperature, which is summarized in the following Table 4, Table 5 and Table 6.
Table 4.
Auto-ignition risk in four confined configurations at HRR = 0.5 kW.
Table 5.
Auto-ignition risk in four confined configurations at HRR = 4.6 kW.
Table 6.
Auto-ignition risk in four confined configurations at HRR = 18.6 kW.
It can be seen in Table 4 that there is not an auto-ignition risk in the four confined configurations associated with the HRR = 0.5 kW where the conditions highlight low temperatures and no production of unburnt gas. For this case, there is no risk because the environment can be associated with a very well-ventilated medium due to an equivalence ratio lower than 1.
For HRR = 4.6 kW, in Table 5, the temperature is shown as one of the criteria which reaches the condition of an auto-ignition, but the concentration of the total unburnt gas stays lower than the flammability domain. As a consequence, it can be considered that there is no risk of auto-ignition in the case with HRR = 4.6 kW. Moreover, this case represents an environment which becomes under-ventilated with an equivalence ratio equaling to about 1.
As indicated in Table 6, at an HRR of 18.6 kW, the risk of auto-ignition is most pronounced in Conf. 2 (compartment with open door and window) and Conf. 3 (compartment with open window). This elevated risk stems from the substantial accumulation of unburnt gases combined with high temperatures near the ceiling. In contrast, more confined configurations such as Conf. 4 exhibit a reduced auto-ignition potential, primarily due to ceiling temperatures falling below the auto-ignition temperature (AIT).
A key insight revealed by this analysis is that the highest risk does not occur in fully open or fully sealed environments, but rather in specific semi-confined configurations. Under such conditions, restricted ventilation leads to the accumulation of unburnt fuel beneath the ceiling, while the presence of openings creates the potential for sudden air mixing, for instance, when a door is opened, thereby triggering auto-ignition or backdraft explosions. This represents an important and quantitatively demonstrated phenomenon in this study.
Such semi-confined scenarios are commonly encountered in real-world settings, such as rooms with slightly open doors or partially open windows, or in equipment compartments, where the associated fire risk is often overlooked. It should be emphasized that the risk assessment method employed in this study offers a valuable approach for evaluating such hazards; however, its accuracy remains subject to further experimental validation.
4. Conclusions
In this study, the numerical simulation of ceiling-impinging flames in confined enclosures was conducted using the computational fluid dynamics (CFD) code Fire Dynamics Simulator (FDS). The simulation methodology was first established and validated for free plumes, where predicted flame heights showed good agreement with Heskestad’s correlation and available experimental data. A systematic mesh and domain sensitivity analysis confirmed that the selected numerical setup was sufficient to capture the key physical processes without significant grid or domain dependence.
The study then focused on confined enclosure configurations with different ventilation openings. FDS simulations provided detailed insight into temperature fields, gas species distributions (O2, CO2, C3H8), and the accumulation of unburnt fuel under varying degrees of confinement. The results highlight that confinement strongly alters the thermal structure and gas composition near the ceiling, particularly under higher heat release rates (HRRs).
A principal fiding is that the highest auto-ignition risk does not occur in fully open or fully sealed compartments, but in partially confined configurations (e.g., Conf. 2 and Conf. 3) at an HRR of 18.6 kW. Under these conditions, concentrations of total unburnt gas exceeded the lower flammability limit of propane (LFL ≈ 2.1 mol%) while ceiling temperatures surpassed the auto-ignition temperature of propane (455 °C). This dual criterion, combining fuel concentration and temperature thresholds, provides a practical, simulation-based method for assessing auto-ignition hazards in confined propane fires.
The outcomes offer relevant insights for safety-oriented ventilation design. In compartments with high fire loads, partially open configurations may inadvertently promote hazardous fuel accumulation and elevated temperatures near the ceiling. Designs should therefore consider either ensuring sufficient ventilation to prevent under-ventilated combustion or fully sealing the compartment to limit oxygen supply and flame persistence.
In light of the present findings and inherent modeling assumptions, the following pathways are proposed for future investigation to extend and refine this work:
First, critical cases should be re-simulated using the latest stable version of FDS to evaluate the sensitivity of the core conclusions to ongoing improvements in combustion, turbulence, and radiation sub-models. A subsequent systematic sensitivity analysis of key modeling parameters (e.g., radiative fraction, subgrid-scale model constants) should then be conducted to better quantify their influence on the predictions.
Second, the physical modeling approach could be advanced in targeted areas. Employing finite-rate chemistry models would better capture local extinction and re-ignition processes in highly under-ventilated conditions. Furthermore, implementing specialized convective heat transfer models (e.g., for impinging jets) would refine the prediction of localized thermal loads on surfaces.
Finally, the steady state framework established here provides a foundation for exploring dynamic fire scenarios. Future work should examine transient phenomena, such as fires following sudden door openings or time-varying ventilation conditions, to better represent real-world compartment fire dynamics.
Author Contributions
Conceptualization, B.M. and K.C.; methodology, B.M.; software, B.M.; validation, A.W. and B.M.; formal analysis, A.W., B.M., and W.Z.; investigation, A.W. and N.G.; resources, K.C. and W.Z.; data curation, A.W.; writing—original draft preparation, A.W.; writing—review and editing, N.G. and B.M.; visualization, A.W.; supervision, K.C. and W.Z.; project administration, K.C. and N.G.; funding acquisition, N.G. and W.Z. All authors have read and agreed to the published version of the manuscript.
Funding
This research received no external funding.
Data Availability Statement
The original contributions presented in this study are included in the article. Further inquiries can be directed to the corresponding author.
Acknowledgments
The authors thank the reviewers for their valuable comments on the initial version of this paper.
Conflicts of Interest
The authors declare that they have no known competing financial interests or personal relationships that could have appeared to influence the work reported in this paper.
Nomenclature
| diffusion coefficient | |
| characteristic fire diameter | |
| activation energy | |
| acceleration of gravity | |
| h | enthalpy |
| length | |
| burning rate of fuel | |
| pressure | |
| Prandtl number | |
| fire power | |
| dimensionless heat release rate | |
| radius | |
| Reynolds number | |
| Schmidt number | |
| temperature | |
| time | |
| velocity | |
| volume | |
| mass fraction of species | |
| dynamic viscosity | |
| equivalence ratio | |
| radiative flux to a solid surface | |
| thermal conductivity | |
| density | |
| absorption coefficient | |
| Stephan-Boltzmann constant | |
| excess temperature | |
| combustion heat of fuel | |
| S | strain tensor |
| rotation tensor |
References
- Gao, Z.; Li, C.; Yan, W.; Fan, Y.; Jiang, L. Experimental Study on the Flame Characteristics of Ceiling Jet with Various Air Entrainment Conditions and Vertical Fire Positions. Int. J. Heat Mass Transf. 2025, 238, 126467. [Google Scholar] [CrossRef] [Scilit]
- Tang, F.; Peng, X.; Palacios, A. Flame Characteristics and Heat Flux Profile of a Tank Surface Caused by Horizontal Gas Leak Jet Fire Impingement. Fire Saf. J. 2022, 134, 103709. [Google Scholar] [CrossRef] [Scilit]
- Wang, C.; Ji, J. Experimental Study of Fire Plume Temperature and Radiant Heat Flux of a Horizontal Jet Flame Impinging a Wall. Fire Saf. J. 2022, 129, 103550. [Google Scholar] [CrossRef] [Scilit]
- Liu, C.; Dai, X.; Ming, X.M.; Welch, S. CFD Predictions of Fire Spread over Wood Cribs in Large Open-Plan Compartments: New Insights. Fire Saf. J. 2025, 156, 104443. [Google Scholar] [CrossRef] [Scilit]
- Wen, J.X. Fire Modelling: The Success, the Challenges, and the Dilemma from a Modeller’s Perspective. Fire Saf. J. 2024, 144, 104087. [Google Scholar] [CrossRef] [Scilit]
- Kim, H.; Lee, C.-H.; Choi, J.-H.; Han, K.-H.; Ha, T.; Park, M.J. Computational Methodology for Investigating the Fire Behavior of Modular Steel Buildings Using Full-Scale Testing and Coupled CFD-FEM Analysis. Fire Saf. J. 2025, 156, 104476. [Google Scholar] [CrossRef] [Scilit]
- Maragkos, G.; Beji, T. Review of Convective Heat Transfer Modelling in CFD Simulations of Fire-Driven Flows. Appl. Sci. 2021, 11, 5240. [Google Scholar] [CrossRef] [Scilit]
- Chen, Q.; Yuen, A.C.Y.; Chen, T.B.Y.; Cao, R.F.; Liu, H.; Yeoh, G.H. A Large-Eddy Simulation Study on the Effect of Fuel Configuration and Pan Distance towards Chemical Species for under-Ventilated Compartment Fire Scenario. Int. J. Heat. Mass. Transf. 2022, 184, 122306. [Google Scholar] [CrossRef] [Scilit]
- Zhang, T.; Wang, G.; Li, J.; Wu, K.; Wang, L. Modelling the Maximum Ceiling Temperature with Bifurcated Plume in Tunnel Fires. Fire Saf. J. 2024, 150, 104249. [Google Scholar] [CrossRef] [Scilit]
- Wei, J.; Zhang, C. A Refined Cylinder Fire Model for Thermal Radiation Calculation from Localized Fire to Exposed Horizontal Surface. Int. J. Heat Mass Transf. 2024, 227, 125539. [Google Scholar] [CrossRef] [Scilit]
- Chatterjee, P.; Meredith, K.V.; Ditch, B.; Yu, H.Z.; Wang, Y.; Tamanini, F. Numerical Simulations of Strong-Plume Driven Ceiling Flows. In Proceedings of the Fire Safety Science, Christchurch, New Zealand, 10–14 February 2014; International Association for Fire Safety Science: London, UK, 2014; Volume 11, pp. 458–471. [Google Scholar]
- Hara, T.; Kato, S. Numerical Simulation of Fire Plume-Induced Ceiling Jets Using the Standard k-ε Model. Fire Technol. 2006, 42, 131–160. [Google Scholar] [CrossRef] [Scilit]
- Pchelintsev, A.; Hasemi, Y.; Wakarnatsu, T.; Yokobayashi, Y. Experimental and Numerical Study on The Behaviour of A Steel Beam Under Ceiling Exposed to A Localized Fire. Fire Saf. Sci. 1997, 5, 1153–1164. [Google Scholar] [CrossRef] [Scilit]
- Rho, J.S.; Ryou, H.S. A Numerical Study of Atrium Fires Using Deterministic Models. Fire Saf. J. 1999, 33, 213–229. [Google Scholar] [CrossRef] [Scilit]
- Vauquelin, O. Experimental Simulations of Fire-Induced Smoke Control in Tunnels Using an “Air-Helium Reduced Scale Model”: Principle, Limitations, Results and Future. Tunn. Undergr. Space Technol. 2008, 23, 171–178. [Google Scholar] [CrossRef] [Scilit]
- Yang, G.S.; An, Y.L.; Peng, L.M.; Zhang, J.H. Simulation of Smoke Flow and Longitudinal Ventilation in Tunnel Fire. Trans. Nonferrous Met. Soc. China (Engl. Ed.) 2006, 16, 741–746. [Google Scholar] [CrossRef] [Scilit]
- Wang, Y.; Vouros, A.; Zhang, J.; Delichatsios, M.A. Numerical and Experimental Validation Study of Flame Extent of a Pool Fire under the Ceiling. J. Loss Prev. Process Ind. 2017, 49, 652–659. [Google Scholar] [CrossRef] [Scilit]
- Gross, D. Measurement of Flame Lengths under Ceilings. Fire Saf. J. 1989, 15, 31–44. [Google Scholar] [CrossRef] [Scilit]
- Wasson, R.; Nahid, M.N.; Lattimer, B.Y.; Thomas, E. Influence of a Ceiling on Fire Plume Velocity and Temperature. Fire Technol. 2015, 52, 1863–1886. [Google Scholar] [CrossRef] [Scilit]
- Zhang, X.; Dghim, M.; Qi, D.; Wang, L.; Fellouah, H. Similarity Analysis between Helium and Fire Smoke in Sub-Scale Wind Tunnel Test for Investigation of Smoke Spread during Photovoltaic Roof Fires. Int. J. Heat. Mass. Transf. 2023, 209, 124156. [Google Scholar] [CrossRef] [Scilit]
- Hurley, M.J. Analysis of FDS Thermal Detector Response Prediction Capability; National Institute of Standards and Technology: New York, NY, USA, 2009. [Google Scholar]
- Huang, Y.; Li, Y.; Dong, B.; Li, J.; Liang, Q. Numerical Investigation on the Maximum Ceiling Temperature and Longitudinal Decay in a Sealing Tunnel Fire. Tunn. Undergr. Space Technol. 2018, 72, 120–130. [Google Scholar] [CrossRef] [Scilit]
- Wang, Z.; Ding, L.; Wan, H.; Ji, J.; Gao, Z.; Yu, L. Numerical Investigation on the Effect of Tunnel Width and Slope on Ceiling Gas Temperature in Inclined Tunnels. Int. J. Therm. Sci. 2020, 152, 106272. [Google Scholar] [CrossRef] [Scilit]
- Karlsson, B.; Quintiere, J.G. Enclosure Fire Dynamics; CRC Press LLC: London, UK, 2000. [Google Scholar]
- Ashok, S.G.; Echekki, T. A Numerical Study of Backdraft Phenomena under Normal and Reduced Gravity. Fire Saf. J. 2021, 121, 103270. [Google Scholar] [CrossRef] [Scilit]
- Myilsamy, D.; Oh, C.B.; Jeon, J. Large Eddy Simulations of Pool Fires and Backdraft in a Compartment Using FDS and FireFOAM. Case Stud. Therm. Eng. 2025, 72, 106337. [Google Scholar] [CrossRef] [Scilit]
- Manescau, B.; Courty, L.; Acherar, L.; Coudour, B.; Wang, H.-Y.; Garo, J.-P. Effects of Ventilation Conditions and Procedures during a Fire in a Reduced-Scale Room. Process Saf. Environ. Prot. 2020, 144, 263–272. [Google Scholar] [CrossRef] [Scilit]
- Dong, H.Q.; Magnognou, B.; Garo, J.P.; Coudour, B.; Wang, H.Y. Fully Coupled CFD Simulation of the Ignition Risk of Unburnt Gases in an Exhaust System Connected to a Mechanically Ventilated Enclosure Fire. Fire Technol. 2019, 55, 149–174. [Google Scholar] [CrossRef] [Scilit]
- Wang, A.J.; Manescau, B.; Chetehouna, K.; De Izarra, C.; Rudz, S. Experimental Investigation of the Confinement Effect on a Flame Impinging a Ceiling in an Enclosure. Fire Saf. J. 2021, 122, 103344. [Google Scholar] [CrossRef] [Scilit]
- Wang, A.; Manescau, B.; Chetehouna, K.; Rudz, S.; Lamoot, L. Experimental Study on the Flame Extension and Risk Analysis of a Diffusion Impinging Flame in Confined Compartment. J. Fire Sci. 2021, 39, 285–308. [Google Scholar] [CrossRef] [Scilit]
- Rehm, R.G.; Baum, H.R. The Equations of Motion for Thermally Driven, Buoyant Flows. J. Res. NBS 1978, 83, 297–308. [Google Scholar] [CrossRef] [Scilit]
- McGrattan, K.; Hostikka, S.; McDermott, R.; Floyd, J.; Weinschenk, C.; Overholt, K. Mathematical Model. In Fire Dynamics Simulator Technical Reference Guide; NIST Special Publication: Gaithersburg, MD, USA, 2017; Volume 1. [Google Scholar]
- Nicoud, F.; Ducros, F. Subgrid-Scale Stress Modelling Based on the Square of the Velocity Gradient Tensor. Flow Turbul. Combust. 1999, 62, 183–200. [Google Scholar] [CrossRef] [Scilit]
- McGrattan, K.; McDermott, R.; Weinschenk, C.; Forney, G. Fire Dynamics Simulator, Technical Reference Guide, 6th ed.; Special Publication: Gaithersburg, Maryland, USA, 2013. [Google Scholar]
- McGrattan, K.; Hostikka, S.; McDermott, R.; Floyd, J.; Weinschenk, C.; Overholt, K. Fire Dynamics Simulator User’s Guide; NIST Special Publication: Gaithersburg, Maryland, USA, 2017. [Google Scholar]
- Baum, H.R.; Mcgrattan, K.B.; Rehm, R.G. Three Dimensional Simulations of Fire Plume Dynamics. Fire Saf. Sci. 1997, 5, 511–522. [Google Scholar] [CrossRef] [Scilit]
- He, Y.; Jamieson, C.; Jeary, A.; Wang, J. Effect of Computation Domain on Simulation of Small Compartment Fires. Fire Saf. Sci. 2008, 9, 1365–1376. [Google Scholar] [CrossRef] [Scilit]
- Zhao, G.; Beji, T.; Merci, B. Application of FDS to Under-Ventilated Enclosure Fires with External Flaming. Fire Technol. 2016, 52, 2117–2142. [Google Scholar] [CrossRef] [Scilit]
- Zhang, X.; Yang, M.; Wang, J.; He, Y. Effects of Computational Domain on Numerical Simulation of Building Fires. J. Fire Prot. Eng. 2010, 20, 225–251. [Google Scholar] [CrossRef] [Scilit]
- Zlochower, I.A.; Green, G.M. The Limiting Oxygen Concentration and Flammability Limits of Gases and Gas Mixtures. J. Loss Prev. Process Ind. 2009, 22, 499–505. [Google Scholar] [CrossRef] [Scilit]
- Zabetakis, M.G.; Lambiris, S.; Scott, G.S. Flame Temperatures of Limit Mixtures. Symp. Int. Combust. 1959, 64, 484–487. [Google Scholar] [CrossRef] [Scilit]
- Coward, H.F.; Carpenter, C.W.; Payman, W. The Dilution Limits of Inflammability of Gaseous Mixtures. Part III. The Lower Limits of Some Mixed Inflammable Gases with Air. Part IV. The Upper Limits of Some Gases, Singly and Mixed, in Air. J. Chem. Soc. 1919, 115, 27–36. [Google Scholar] [CrossRef] [Scilit]
- Hodges, J.L.; Hughes, J.; McDermott, R.J. Convective Heat Transfer from Impinging Flames. In Proceedings of the ire and Evacuation Modeling Technical Conference (FEMTC), Kansas, MI, USA, 18–20 September 2024. [Google Scholar]
- Betting, B.; Varea, E.; Gobin, C.; Godard, G.; Lecordier, B.; Patte-Rouland, B. Experimental and Numerical Studies of Smoke Dynamics in a Compartment Fire. Fire Saf. J. 2019, 108, 102855. [Google Scholar] [CrossRef] [Scilit]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |