Abstract
To investigate the reverse frequency overshoot and transient oscillations that may arise in an islanded hydro-storage microgrid using conventional P–ω virtual synchronous control under specific parameter settings, this paper analyzes the active-power–frequency dynamic external characteristics of the microgrid under P–ω2 virtual synchronous control. An active-power–frequency dynamic model coupling the physical inertia of the hydro-turbine synchronous generator and the virtual inertia of the grid-forming energy-storage converter is established. The power–frequency regulation characteristics of P–ω and P–ω2 control are compared, and the effects of virtual inertia and virtual damping on the active-power–frequency dynamic external characteristics are analyzed. A joint inertia–damping parameterization is then formulated, and the effects of parameter scaling and load-disturbance magnitude on the active-power–frequency dynamic external characteristics of the microgrid are evaluated using the maximum frequency deviation, rate of change of frequency, and dynamic recovery time. PSCAD/EMTDC simulation results show that, compared with conventional P–ω control, P–ω2 control mitigates reverse frequency overshoot and transient oscillations during the recovery process. The inertia–damping parameter combination and load-disturbance magnitude significantly affect the system frequency dynamics, thereby validating the established model and the corresponding external-characteristic analysis.
1. Introduction
With the increasing penetration of renewable energy generation and the widespread application of power-electronic interfaced resources, modern power systems are gradually evolving toward converter-dominated systems. The growing proportion of power-electronic interfaced resources has reduced the share of synchronous generators, thereby weakening system rotational inertia and frequency-support capability. Consequently, power systems become more susceptible to significant frequency variations under load disturbances and renewable power fluctuations [1,2,3,4]. This issue is particularly critical in islanded microgrids, where support from the main grid is unavailable and source–load power imbalances directly affect system frequency. Therefore, improving inertial support and frequency-regulation capability has become essential for ensuring the stable operation of islanded microgrids.
To address these challenges, grid-forming converters and virtual synchronous generator (VSG) control have been developed to reproduce the rotor-motion, inertia, and damping characteristics of synchronous generators, enabling power-electronic interfaced resources, such as energy storage systems, to provide active frequency support [5,6,7]. Conventional VSGs generally establish active-power–frequency regulation relationships based on angular-speed or frequency deviations. Previous studies have investigated the dynamic equivalence between virtual synchronous machines and frequency-droop control, compared the dynamic characteristics of VSG and droop-controlled converters, and developed transfer-function-based models to describe VSG responses under active-power and frequency disturbances [8,9,10]. Furthermore, improvements to active-power–frequency control loops and the operating characteristics of parallel-connected virtual synchronous machines have been investigated [11,12]. These studies provide an important foundation for the application of grid-forming converters in microgrid frequency regulation. However, the influence of different power–frequency regulation laws themselves on transient active-power responses and frequency recovery processes warrants further investigation.
In addition to the power–frequency control structure, virtual inertia and virtual damping are key parameters governing the dynamic performance of VSG-based systems. Existing studies have shown that virtual inertia predominantly affects the initial frequency response following a disturbance, whereas virtual damping is more closely associated with oscillation attenuation and dynamic recovery [13,14]. Further investigations have examined the effects of parameter variations on system dynamic performance from the perspectives of coordinated inertia–damping regulation and the stability of low-inertia systems [15,16]. These findings indicate that inertia and damping play different but interrelated roles in the frequency-response process. Increasing either parameter independently does not necessarily improve the frequency nadir, rate of change of frequency (RoCoF), and recovery time simultaneously. Therefore, the matching relationship and overall scaling of inertia and damping parameters should be jointly considered when evaluating the active-power–frequency dynamic external characteristics of microgrids.
In islanded hydro-storage microgrids comprising hydro-turbine synchronous generators and grid-forming energy-storage converters, the two types of sources exhibit substantially different dynamic timescales. Synchronous generators provide physical inertia through their rotating masses, whereas grid-forming energy-storage converters provide virtual inertial support through rapid active-power regulation. Previous studies have investigated frequency stability in systems containing synchronous generators and grid-forming converters, the transient behavior of microgrids with parallel synchronous generators and VSGs, and the associated power–frequency dynamic interactions [17,18,19]. Recent studies have further investigated the modeling and small-signal stability of islanded microgrids with hybrid grid-forming sources comprising synchronous machines and converters [20], as well as transient overload mitigation and coordinated operation of grid-forming inverters and synchronous generators [21]. Meanwhile, studies on hydropower–storage coordination have demonstrated that the rapid active-power response of energy storage can effectively complement the frequency-support capability of hydropower units [22,23,24]. Research has also addressed coordinated frequency regulation in isolated microgrids while considering battery state-of-charge (SOC) constraints [25]. Nevertheless, most existing studies are primarily based on conventional VSG or linear P–ω power–frequency control frameworks, with comparatively limited attention given to the nonlinear reconstruction of the power–frequency regulation law itself. Since the kinetic energy stored in a synchronous-generator rotor is directly related to the square of its angular speed, this physical relationship provides a theoretical basis for constructing a nonlinear power–frequency regulation law using the squared-angular-speed deviation. Therefore, the active-power–frequency dynamic external characteristics of hydro-storage microgrids under P–ω2 virtual synchronous control, together with the effects of physical inertia, virtual inertia, virtual damping, and load disturbances, require further investigation.
Accordingly, this paper investigates the active-power–frequency dynamic external characteristics of an islanded hydro-storage microgrid consisting of a hydro-turbine synchronous generator and a grid-forming energy-storage converter under P–ω2 virtual synchronous control. Unlike conventional P–ω control, the proposed P–ω2 control does not achieve improved performance by increasing the first-order small-signal regulation gain around the rated operating point. Instead, it establishes the power–frequency regulation relationship based on the physical relationship between synchronous-generator rotor kinetic energy and the square of angular speed, introducing a quadratic nonlinear regulation term that varies with frequency deviation. This approach maintains comparable first-order regulation characteristics around the rated operating point while modifying the transient power-regulation process under finite frequency deviations. Under the investigated conditions, this nonlinear regulation reshapes the converter power response during frequency recovery, thereby mitigating reverse frequency overshoot and transient oscillations while maintaining comparable initial inertial support.
On this basis, an active-power–frequency dynamic model coupling the physical inertia of the synchronous generator and the virtual inertia of the energy-storage converter is established, and the power–frequency regulation characteristics of conventional P–ω and P–ω2 control are comparatively analyzed. Furthermore, the effects of virtual inertia, virtual damping, and their combined parameter configurations on system frequency dynamics are investigated. A joint inertia–damping parameterization is subsequently developed to evaluate the effects of parameter scaling and load-disturbance magnitude on the dynamic external characteristics of the hydro-storage microgrid using time-domain indices, including maximum frequency deviation, RoCoF, and dynamic recovery time. Finally, an electromagnetic transient model of the islanded hydro-storage microgrid is established in PSCAD/EMTDC to validate the theoretical model and the corresponding dynamic external-characteristic analysis under different control strategies, inertia–damping parameter combinations, and load-disturbance conditions.
2. Modeling of the Active-Power–Frequency Dynamic External Characteristics of the Hydro-Storage Microgrid
2.1. System Configuration and Active-Power Balance of the Hydro-Storage Microgrid
As shown in Figure 1, the islanded hydro-storage microgrid mainly consists of a hydro-turbine synchronous generator, a grid-forming energy-storage converter, and AC loads. The hydro-turbine synchronous generator is operated through governor and excitation systems and provides physical inertia through its rotating mass. The energy-storage converter adopts P–ω2 virtual synchronous control and provides inertial support through virtual inertia and a fast active-power response. Because the governor dynamics of the hydro unit are considerably slower than the inertial response immediately after a disturbance, these slow dynamics are neglected in the subsequent simplified model, and only the synchronous-generator rotor dynamics are retained.
Figure 1.
System topology of the islanded hydro-storage microgrid.
In islanded operation, no bulk-grid frequency support is available, and a change in load power directly produces an active-power imbalance. The hydro-turbine synchronous generator and the energy-storage converter jointly accommodate the load-power variation. Their active-power balance is expressed as
Here, PG and PVSG represent the active-power contributions from the hydro-turbine synchronous generator and the energy-storage converter, respectively, whereas PL represents the active-power demand of the AC load.
When a load disturbance occurs, small-signal analysis of Equation (1) gives
The quantities ΔPG and ΔPVSG correspond to the changes in active power provided by the hydro-turbine synchronous generator and the energy-storage converter, respectively, while ΔPL represents the change in active-power demand resulting from the load disturbance.
Equation (2) indicates that the hydro-turbine synchronous generator and the energy-storage converter jointly respond to the load-power variation. The synchronous generator contributes physical inertia through its rotating mass, whereas the energy-storage converter provides an emulated inertial response through virtual synchronous control. The interaction of these two responses determines the frequency dynamics of the islanded hydro-storage microgrid.
2.2. Active-Power–Frequency Dynamic Model of the Hydro-Turbine Synchronous Generator
As shown in Figure 2, a simplified active-power–frequency model of the hydro-turbine synchronous generator is adopted to describe the fast frequency dynamics during the initial stage following a load disturbance. Stator electromagnetic transients and excitation-system dynamics are neglected, and the electromagnetic power Pe is approximated by the active-power output of the synchronous generator. Under these assumptions, the rotor-motion equation is written as
Figure 2.
Simplified active-power–frequency dynamic model of the hydro-turbine synchronous generator.
Under these assumptions, the rotor-motion equation is written as
Here, JG represents the equivalent rotational inertia of the shaft system of the hydro-turbine synchronous generator, while ΔωG denotes the generator angular-speed deviation. The quantities ΔPm and ΔPe correspond to the variations in mechanical input power and electromagnetic output power, respectively, and DG denotes the damping coefficient of the synchronous generator.
Rearranging Equation (3) yields
Applying the Laplace transform to Equation (4) gives the synchronous-generator frequency-response relationship
Equation (5) reveals the different dynamic roles of JG and DG in the synchronous-generator frequency response. The shaft inertia JG primarily governs how rapidly the frequency begins to vary after a load disturbance, while the damping coefficient DG mainly influences the subsequent attenuation of the frequency deviation.
2.3. Active-Power–Frequency Model of Conventional P–ω Virtual Synchronous Control
To establish a common basis for comparing different active-power–frequency regulation laws, the conventional P–ω virtual synchronous control model is first formulated, as shown in Figure 3.
Figure 3.
Active-power–frequency regulation block diagram of conventional P–ω virtual synchronous control.
Conventional P–ω control directly uses the virtual-rotor angular-speed deviation to construct the active-power regulation law. The corresponding virtual mechanical-power command is expressed as
Here, represents the virtual mechanical-power command generated by conventional P–ω control. Pref denotes the active-power reference of the energy-storage converter, and Kω is the corresponding proportional gain. The variables ωVSG and ωn refer to the virtual-rotor angular speed and the nominal system angular speed, respectively.
The virtual-rotor angular-speed deviation is defined as
Equation (6) can therefore be rewritten as
To reproduce the inertial and damping behavior of a synchronous-generator rotor, the energy-storage converter is described by the following virtual-rotor dynamic equation.
Here, Jv represents the virtual inertia assigned to the energy-storage converter, Dv denotes its virtual damping coefficient, and PVSG,e is the electromagnetic power output of the converter.
Substituting Equation (8) into Equation (9) gives the virtual-rotor dynamic relationship under conventional P–ω control
Equation (10) indicates that, in the first-order simplified model, the P–ω proportional coefficient Kω and the virtual damping Dv jointly act on the frequency-deviation feedback path and therefore jointly influence the active-power–frequency dynamic response of the energy-storage converter.
2.4. Active-Power–Frequency Model of P–ω2 Virtual Synchronous Control
On the basis of the conventional P–ω control model, P–ω2 virtual synchronous control is constructed using the angular-speed-squared deviation. The corresponding control structure is shown in Figure 4.
Figure 4.
Active-power–frequency regulation block diagram of P–ω2 virtual synchronous control.
The kinetic energy stored in the rotor of a synchronous generator can be expressed as
Taking the operating state corresponding to the nominal angular speed ωn as the reference, the rotor kinetic-energy deviation is
These relationships show that the squared-angular-speed deviation ω2-ω2n is directly associated with the variation in rotor kinetic energy relative to the nominal operating state. This relationship provides a physically interpretable basis for employing the squared-angular-speed deviation in the virtual mechanical-power regulation law, yielding
where denotes the virtual mechanical-power command under P–ω2 control, and Kp is the corresponding proportional gain.
The angular-speed-squared deviation is defined as
According to Equation (7), the virtual-rotor angular speed can be expressed as
Substituting Equation (15) into Equation (14) gives
Hence, the virtual mechanical-power command of P–ω2 control can be further written as
The above equation shows that the power-regulation action of P–ω2 control consists of a first-order linear term and a second-order nonlinear term. To quantify the contribution of the nonlinear term relative to the first-order regulation term, the relative nonlinear contribution is defined as
where ΔP1 and ΔP2 denote the first-order linear term and the second-order nonlinear term in the power-regulation relationship, respectively.
It can therefore be seen that the smaller the frequency deviation relative to the nominal frequency, the weaker the contribution of the nonlinear term and the more accurate the first-order approximation of the P–ω2 power-regulation law. As the frequency deviation increases, the contribution of the quadratic term becomes progressively more significant. For quantitative illustration, if 5% is adopted as a reference threshold for the relative nonlinear contribution, the corresponding condition is
For a system with a nominal frequency of 50 Hz, this corresponds to
It should be emphasized that this range is used only to characterize the relative influence of the quadratic term in the linearization approximation and does not represent an allowable operating-frequency range or a system-stability criterion.
Under small-signal conditions around nominal operation, the angular-speed deviation is sufficiently small that the second-order term can be neglected. Equation (17) can therefore be approximated as
P–ω2 control adopts the same virtual-rotor dynamic structure as conventional P–ω control, i.e.,
Substituting Equation (21) into Equation (22) yields the following linearized dynamic equation
Equations (17) and (23) show that P–ω2 control constructs the active-power regulation law using the angular-speed-squared deviation. Near the nominal operating point, the dominant linear regulation gain is determined by 2Kpωn. As the frequency deviation increases, the contribution of the quadratic term becomes more pronounced, giving P–ω2 control a nonlinear power-regulation characteristic distinct from that of conventional P–ω control.
When conventional P–ω control and P–ω2 control satisfy Kω = 2Kpωn, the two methods have the same first-order small-signal active-power–frequency regulation gain around the nominal operating point. As the frequency deviation increases, however, the quadratic term in P–ω2 control becomes increasingly influential, resulting in different nonlinear power-regulation characteristics.
Accordingly, the key distinction of P–ω2 control is not an enhancement of the first-order small-signal regulation gain around the nominal operating point, but rather the nonlinear power-regulation characteristic introduced by the squared-angular-speed deviation under finite frequency deviations.
2.5. Formation Mechanism of the Active-Power–Frequency Dynamic External Characteristics
The hydro-turbine synchronous generator and the grid-forming energy-storage converter are connected to the common AC bus through their respective AC branches. Neglecting the branch resistance and adopting a reactance-dominated approximation, the active power exchanged between the (i)-th source and the common bus can be expressed as
where Ei and Vb denote the internal-voltage magnitude of the source and the common-bus voltage magnitude, respectively; Xi is the equivalent branch reactance; and δi and δb are the phase angles of the source and the common bus, respectively.
Assuming that the voltage-magnitude variations are negligible over the frequency-response timescale considered here, linearizing the above power–angle relationship around the steady-state operating point gives
where Ks,i represents the synchronizing coupling coefficient between the source and the common bus. Meanwhile, the relative phase-angle dynamics are governed by
Therefore, under sufficiently strong AC coupling and synchronized operation, the relative phase-angle deviation remains small and bounded. For the low-frequency electromechanical dynamics considered in this study, the hydro-turbine synchronous generator and the grid-forming energy-storage converter can therefore be treated as approximately frequency coherent, i.e.,
It should be noted that this frequency-coherency approximation is mainly applicable when the AC-network coupling is sufficiently strong, the relative phase-angle deviation remains small, and synchronized operation is maintained. When the branch impedance increases and the electrical coupling becomes weak, when large relative phase-angle excursions occur, or when the converter enters sustained current limiting or the system experiences a severe fault, noticeable frequency differences may arise between the synchronous generator and the converter. Under such conditions, the higher-order network, electromagnetic, and converter inner-loop dynamics should be retained.
According to Equations (3) and (22), the inertial-response terms of the hydro-turbine synchronous generator and the energy-storage converter are, respectively,
The equivalent inertia of the hydro-storage microgrid can therefore be expressed as
According to Equation (23), the frequency-deviation feedback coefficient introduced by P–ω2 control around the nominal operating point is 2Kpωn. Considering the synchronous-generator damping DG and the converter virtual damping Dv, the system equivalent damping can be expressed as
Accordingly, when the slow governor dynamics, converter inner loops, and higher-order network transients are neglected, the simplified inertia–frequency dynamic equation of the islanded hydro-storage microgrid can be written as
where ΔP denotes the net active-power imbalance acting on the common system-frequency dynamics.
Applying the Laplace transform to Equation (31) gives
Further consideration of the reduced-order inertia–frequency model shows that its characteristic root can be expressed as s = −Deq/Jeq. Therefore, the transient component of the frequency deviation decays toward the post-disturbance steady state when Deq/Jeq > 0. Within the physically meaningful parameter range considered in this study, Jeq > 0 and Deq > 0 provide a sufficient condition for stable decay. According to the expressions for the equivalent inertia and damping, these conditions can be written as JG + Jv > 0 and DG + Dv + 2Kpωn > 0. Since JG, DG, Kp, and ωn are positive, positive Jv and Dv satisfy the above conditions. Therefore, the reduced-order model is locally asymptotically stable within the positive-parameter region considered in this study.
It should be emphasized that this condition represents only the local stability property of the reduced-order model. It does not constitute the complete stability region of the full system when converter inner-loop dynamics, power-limiting effects, and energy-storage operating constraints are taken into account.
Within this reduced-order framework, Equations (29)–(32) separate the reduced-order frequency dynamics into an inertial term and a frequency-deviation term. The coefficient of the derivative term combines the physical inertia JG of the hydro-turbine generator with the virtual inertia Jv contributed by the energy-storage converter, thereby defining the aggregate inertia level. The frequency-deviation term incorporates the generator damping DG, converter damping Dv, and the local linear contribution 2Kpωn introduced by P–ω2 control. Consequently, the post-disturbance frequency response results from the combined effects of physical inertia, virtual inertia, damping, and P–ω2 power–frequency regulation.
As a low-order representation of the microgrid external response, the analytical model neglects slow governor dynamics, converter inner-loop and power-measurement dynamics, and higher-order electrical-network effects.
3. Active-Power–Frequency Dynamic External-Characteristic Analysis of the Hydro-Storage Microgrid Under P–ω2 Virtual Synchronous Control
When a load-power disturbance occurs in an islanded hydro-storage microgrid, the balance between generation and demand is immediately disturbed, leading to a transient active-power mismatch. The resulting frequency dynamics are governed jointly by the rotor response of the hydro-turbine synchronous generator and the virtual synchronous control implemented in the energy-storage converter. Based on the inertia–frequency relationship, virtual inertia has its strongest influence during the early stage of the disturbance, when the system frequency begins to change. After a noticeable frequency deviation has developed, virtual damping together with the P–ω2 active-power regulation contributes more significantly to the subsequent recovery process. These mechanisms are reflected through the transient active-power output of the energy-storage converter and collectively determine the active-power–frequency dynamic external characteristics of the hydro-storage microgrid.
3.1. Dynamic Roles of Virtual Inertia and Virtual Damping
Immediately after a load disturbance, the system frequency deviation is still small, and the regulation associated with the frequency deviation is therefore limited. The inertia–frequency dynamic relationship in Equation (31) can be approximated as
As indicated by Equation (33), under an identical load disturbance, a larger equivalent inertia JG + Jv results in a lower initial rate of frequency variation. Therefore, increasing Jv enhances the total inertia of the system and suppresses the rapid frequency change immediately after the disturbance, thereby improving the initial inertial-support capability. When the load increases, the energy-storage converter responds by promptly raising its active-power output through virtual-inertia action, which helps offset the instantaneous power shortage and restrain the frequency drop. For a load decrease, the converter produces the corresponding response in the opposite direction.
As the disturbance evolves, the frequency deviation gradually develops and the associated power-regulation effect becomes increasingly significant. According to Equation (23), the frequency-deviation regulation on the storage side is jointly formed by the virtual damping Dv and the 2Kpωn regulation term introduced by P–ω2 control around the nominal operating point. The system frequency dynamics therefore evolve from an inertia-dominated initial stage to a stage in which inertia response and frequency-deviation regulation act together.
Thus, Jv primarily influences the rate of frequency change during the initial disturbance stage, whereas Dv mainly affects the subsequent recovery after the frequency deviation has developed. The two parameters therefore exert their dominant effects at different stages of the frequency-response process.
3.2. Transient Active-Power Response Characteristics of the Energy-Storage Converter
The effects of inertia and damping are ultimately manifested in the transient active-power output of the energy-storage converter. The virtual-rotor motion equation gives
Near the nominal operating point, the variation in the virtual mechanical power under P–ω2 control is expressed as
Substituting Equation (35) into Equation (34) gives the transient active-power response of the energy-storage converter
Equation (36) indicates that the transient active-power response of the energy-storage converter consists of two components. The first is associated with the rate of change of angular speed and represents the inertial-power response produced by virtual inertia. The second is associated with the angular-speed deviation and represents the frequency-deviation response jointly formed by virtual damping and P–ω2 active-power–frequency regulation.
Immediately after a load increase, the rate of change of angular speed is large while the frequency deviation remains small; therefore, the inertial-power component participates first in restoring the active-power balance. As the frequency deviation develops, the regulation associated with ΔωVSG becomes increasingly significant. Consequently, the transient active-power response of the energy-storage converter gradually transitions from rapid inertial support to frequency-deviation regulation.
The transient active-power response of the energy-storage converter provides the pathway through which virtual inertia and virtual damping influence the microgrid dynamics. Their combined effects determine the rate of frequency variation, the magnitude of the frequency deviation, and the subsequent recovery process, and consequently shape the active-power–frequency dynamic external characteristics of the microgrid under load disturbances.
3.3. Effect of Load-Disturbance Magnitude on Dynamic External Characteristics
In addition to the control parameters, the load-disturbance magnitude is an important factor affecting the frequency dynamics of the islanded hydro-storage microgrid. According to Equation (33), when the system parameters are fixed, the initial rate of frequency change is related to the net active-power imbalance as follows
Therefore, as the load-disturbance magnitude increases, the instantaneous active-power imbalance becomes larger and, for the same equivalent inertia, produces a higher rate of frequency change and a larger frequency deviation.
Equation (36) further gives the transient power component associated with virtual inertia as
where ΔPJ denotes the inertial-power component of the energy-storage converter.
Equations (37) and (38) show that, when the control parameters are fixed, a larger load disturbance requires a stronger inertial-power response from the energy-storage converter. At the same time, the larger frequency deviation strengthens the power response associated with virtual damping and P–ω2 active-power regulation.
Hence, the underlying inertia–frequency mechanism remains unchanged under different load-disturbance magnitudes. However, as the active-power imbalance increases, both the frequency excursion and the transient support requirement of the energy-storage converter increase, and the active-power–frequency dynamic external characteristics of the microgrid change accordingly. The load-disturbance magnitude is therefore an important factor affecting the system dynamic external characteristics.
4. Effects of Inertia–Damping Parameters on the Active-Power–Frequency Dynamic External Characteristics of the Hydro-Storage Microgrid
The previous analysis indicates that virtual inertia and virtual damping dominate different stages of the frequency-response process. Virtual inertia has a stronger influence on the initial frequency variation, whereas virtual damping becomes more significant during the later recovery after the frequency deviation has developed. Their combined parameter setting determines the transient active-power response of the energy-storage converter and consequently affects the active-power–frequency dynamic external characteristics of the hydro-storage microgrid. To examine how these characteristics vary with different parameter settings, a unified joint parameterization is adopted to preserve the relative inertia–damping relationship while changing the overall parameter scale. The resulting changes in the system frequency response are then evaluated using representative time-domain indices.
4.1. Joint Inertia–Damping Parameterization
Let Jv0 and Dv0 denote a baseline pair of virtual inertia and virtual damping parameters for the energy-storage converter. To characterize their relative matching relationship, the inertia–damping ratio is defined as
To vary the overall parameter scale while preserving the relative inertia–damping relationship, a scaling factor k is introduced, such that
which gives
Equations (40)–(42) show that varying the scaling factor k synchronously adjusts the magnitudes of virtual inertia and virtual damping while preserving their relative matching relationship. This parameterization uses a unified scaling factor to describe the synchronous variation of the two parameters and provides a consistent representation for analyzing the active-power–frequency dynamic external characteristics of the microgrid under different parameter combinations.
Substituting Equations (40) and (41) into the expressions for the equivalent inertia and equivalent damping gives
Equations (43) and (44) show that the parameter scaling simultaneously changes the system equivalent inertia and equivalent damping. The system frequency dynamics under different parameter combinations therefore reflect the combined effects of inertia and damping rather than the effect of either parameter alone.
4.2. Effect of Inertia–Damping Parameter Scaling on Dynamic External Characteristics
For the first-order inertia–frequency model, the equivalent dynamic time constant of the system is defined as
Substituting Equations (43) and (44) yields
Equation (46) describes the characteristic time scale of the frequency response resulting from the simultaneous influence of inertia and damping. Varying k changes both the equivalent inertia and the equivalent damping at the same time. Nevertheless, these two quantities do not scale in isolation, because the system response also depends on the inherent inertia JG and damping DG of the hydro-turbine synchronous generator, as well as the supplementary frequency-regulation contribution associated with P–ω2 control. Consequently, the equivalent dynamic time constant varies with k rather than remaining unchanged.
Even when the inertia–damping parameters retain the same relative configuration, different parameter scales can produce different rates of frequency change, frequency nadirs, and recovery processes. At a small parameter scale, the contribution of the energy-storage converter to the system inertia and damping is relatively limited. As k increases, the contribution of the converter to the system frequency response becomes more pronounced, and the levels of inertial support and damping regulation rise simultaneously, while the overall dynamic timescale changes accordingly.
Therefore, the influence of inertia–damping parameter variations on the system dynamic external characteristics cannot be fully reflected by the parameter ratio or any single dynamic index alone; a comprehensive evaluation based on the complete time-domain response is required.
4.3. Dynamic External-Characteristic Evaluation Based on Time-Domain Indices
The dynamic external characteristics associated with different inertia–damping parameter combinations are assessed using three representative time-domain measures: the maximum frequency deviation, the rate of change of frequency (RoCoF), and the dynamic recovery time. These measures respectively reflect the extent of the frequency excursion, the system capability to restrain rapid frequency variation during the early disturbance stage, and the recovery behavior after the disturbance.
- (1)
- Maximum frequency deviation
The maximum frequency deviation quantifies the largest departure of the system frequency from its nominal value after a load disturbance and is expressed as
where Δf(t) = f(t) − fn is the system frequency deviation and fn is the nominal system frequency.
The absolute value is adopted to consistently evaluate the maximum frequency excursion for both load-increase and load-decrease disturbances, while the sign of Δf only indicates the direction of the frequency deviation.
For a load-increase disturbance that causes a frequency drop, the frequency nadir fmin can also be used to characterize the frequency-support performance. Under the same disturbance, a smaller maximum frequency deviation or a higher fmin generally indicates stronger frequency-support capability.
- (2)
- Rate of change of frequency
The rate of change of frequency is used to characterize how rapidly the system frequency changes following a load disturbance and is expressed as
The absolute value of RoCoF is adopted to characterize the maximum rate of frequency variation regardless of its direction. Under the same load-disturbance condition, a smaller maximum RoCoF generally corresponds to a higher equivalent inertia level and stronger initial frequency-support capability.
- (3)
- Dynamic recovery time
The dynamic recovery time characterizes the time required for the system frequency to return from the disturbed state to a stable state. Let f∞ denote the post-disturbance steady-state frequency and ε denote the steady-state error-band limit. The recovery criterion is considered satisfied when |f(t) − f∞| ≤ ε and the system frequency remains within this band thereafter. The first instant at which this criterion is satisfied is denoted by tr. If the disturbance occurs at t0, the dynamic recovery time is defined as
A smaller ts indicates faster frequency recovery. However, the recovery time alone does not fully characterize the smoothness of the recovery process. When reverse frequency deviation or transient oscillation occurs, the overshoot magnitude and oscillation-decay characteristics should also be considered.
Accordingly, the dynamic performance of different inertia–damping parameter combinations should be evaluated using the maximum frequency deviation, RoCoF, and dynamic recovery time together with the overshoot and transient-oscillation characteristics during frequency recovery. In this way, the active-power–frequency dynamic external characteristics can be assessed from both inertial-support capability and dynamic-recovery performance.
4.4. Inertia–Damping Parameter Matching Characteristics
Based on the preceding inertia–damping parameterization and time-domain dynamic indices, the influence of inertia–damping parameters on the active-power–frequency dynamic external characteristics of the hydro-storage microgrid can be analyzed in terms of their relative matching relationship and overall parameter scale. Let (Jv0, Dv0) denote the baseline virtual inertia and virtual damping parameters.
With the relative matching relationship held constant, the virtual inertia and virtual damping are synchronously adjusted through the scaling factor k, i.e.,
Different values of k correspond to different levels of virtual inertia and virtual damping and consequently modify the system equivalent inertia, equivalent damping, and the active-power–frequency dynamic external characteristics under load disturbances.
As the parameter scale increases, the system equivalent inertia increases, suppressing the initial rate of frequency change and improving the frequency nadir. Meanwhile, the synchronous increase in virtual damping also affects the dynamic recovery after the frequency deviation has developed. Therefore, even when the relative inertia–damping matching relationship is kept unchanged, varying the overall parameter scale leads to different maximum frequency deviations, RoCoF values, and dynamic recovery times. At a small parameter scale, the inertia and damping effects contributed by the energy-storage converter are relatively limited, resulting in greater frequency sensitivity to load disturbances. As the parameter scale increases, the initial frequency response improves, whereas the recovery process remains jointly influenced by the equivalent dynamic timescale of the system.
The frequency response is influenced by virtual inertia and virtual damping in different stages of the transient process. Virtual inertia has a stronger effect on the early frequency variation, particularly the initial RoCoF and the frequency nadir, while virtual damping contributes more prominently to the subsequent recovery once a noticeable frequency deviation has developed. Hence, both the relative proportion and the overall magnitude of the inertia–damping parameters affect the active-power–frequency dynamic behavior of the hydro-storage microgrid during load disturbances. Their influence can be evaluated through time-domain measures including the maximum frequency deviation, RoCoF, and dynamic recovery time.
5. Simulation Validation
An electromagnetic transient model of the islanded hydro-storage microgrid is implemented in PSCAD/EMTDC to verify the preceding external-characteristic analysis. The simulation system consists of a hydro-turbine synchronous generator, a grid-forming energy-storage converter, and AC loads. The influence of the main factors on the system dynamic external characteristics is investigated through three groups of cases: a comparison between conventional P–ω and P–ω2 control, variations in the inertia–damping parameter combinations, and load disturbances with different magnitudes.
5.1. Simulation Model and Parameter Settings
A PSCAD/EMTDC electromagnetic transient model is developed for the islanded hydro-storage microgrid. The modeled system mainly consists of a hydro-turbine synchronous generator, a grid-forming energy-storage converter, and AC loads. The hydro-turbine synchronous generator provides the inherent physical inertia of the system, while the energy-storage converter participates in active-power–frequency regulation through virtual synchronous control. To preserve the transient characteristics of the practical converter control system, the voltage–current dual-loop control and the associated converter dynamics are retained in the simulation model. The main simulation parameters are listed in Table 1.
Table 1.
Main simulation parameters of the hydro-storage microgrid.
All simulation cases use the same system configuration, initial operating condition, and data-processing procedure. Only the control strategy, inertia–damping parameter combination, or load-disturbance magnitude is varied according to the objective of each case, thereby ensuring comparability among the investigated conditions. For the comparison between conventional P–ω and P–ω2 control, the same virtual inertia Jv and virtual damping Dv are adopted, and the first-order active-power–frequency regulation gains around the nominal operating point are matched according to Kω = 2Kpωn. The two control strategies are therefore compared under similar small-signal regulation strength.
5.2. Frequency-Response Comparison Between Conventional P–ω and P–ω2 Control
To compare the influence of the two active-power–frequency control strategies on the transient frequency response, a load-step disturbance is applied at t = 200 s under the same initial operating condition and load-disturbance magnitude. The resulting system frequency responses are shown in Figure 5.
Figure 5.
System frequency responses under conventional P–ω and P–ω2 control.
As shown in Figure 5, the system frequency decreases rapidly after the load disturbance under both control strategies, and the initial frequency-drop trajectories are very similar. This indicates that, when the virtual inertia, virtual damping, and power–frequency regulation gains around the nominal operating point are matched, the two control strategies provide comparable initial inertial support.
As the frequency deviation develops, clear differences emerge in the recovery process. Under conventional P–ω control, the frequency rapidly recovers and subsequently exhibits a pronounced reverse overshoot followed by damped oscillations, with a peak of approximately 50.33 Hz. Under P–ω2 control, the frequency recovery is smoother, and both the reverse excursion and subsequent oscillatory rebound are markedly reduced.
These differences arise from the distinct nonlinear active-power–frequency regulation characteristics of the two control strategies. Conventional P–ω control uses a linear mapping of the angular-speed deviation, whereas P–ω2 control retains a comparable first-order regulation characteristic around the nominal operating point while introducing an increasingly significant angular-speed-squared contribution as the frequency deviation grows. This nonlinear term reshapes the converter active-power regulation during the frequency-recovery stage.
These results demonstrate that, under the investigated parameter and load-disturbance conditions, P–ω2 control can improve the frequency-recovery process while maintaining comparable initial inertial support. In particular, it mitigates the pronounced reverse overshoot and transient oscillations observed under conventional P–ω control and thereby improves the active-power–frequency dynamic external characteristics of the microgrid.
5.3. Frequency-Response Analysis Under Different Inertia–Damping Parameter Combinations
Under P–ω2 control, the overall parameter scale is varied while the relative inertia–damping configuration is preserved in order to assess the influence of the parameter combination on the active-power–frequency dynamic external characteristics of the microgrid. Three inertia–damping parameter combinations are defined, as listed in Table 2. The same load-step disturbance is applied at t = 200 s, and the resulting frequency responses are shown in Figure 6.
Table 2.
Inertia–damping parameter combinations at different scales.
Figure 6.
System frequency responses under different inertia–damping parameter combinations.
As shown in Figure 6, with the relative inertia–damping relationship held constant, proportionally increasing Jv and Dv raises the frequency nadir from 48.37 Hz to 48.54 Hz and 48.72 Hz, respectively, thereby reducing the frequency drop. This trend indicates that increasing the parameter scale enhances the initial frequency-support capability under the load disturbance. All three cases eventually return to a stable state without sustained oscillations, and the time required for the frequency to recover to the vicinity of the nominal value becomes shorter as the parameter scale increases, indicating that, under the present joint scaling law, a larger parameter scale improves both the frequency nadir and the recovery speed.
From the perspective of the underlying mechanism, increasing the parameter scale raises the virtual inertia and therefore increases the overall equivalent inertia of the system, slowing the rapid frequency variation immediately after the disturbance and improving the frequency nadir. At the same time, the virtual damping increases proportionally, strengthening the damping action after the frequency deviation has developed and helping maintain a stable recovery. Because inertia and damping are varied simultaneously, the overall dynamic timescale also changes. In the parameter range investigated here, the increase in virtual damping outweighs the effect of the larger inertia, so that stronger initial frequency support and faster frequency recovery are obtained together. This behavior should not be extended to independent variations of the virtual inertia and the virtual damping, for which a longer recovery time may result.
Overall, increasing the inertia–damping parameter scale enhances the frequency-response capability during the initial disturbance stage, and the improvements in the frequency nadir and in the recovery speed are obtained simultaneously under the joint scaling law adopted in this study. This indicates that parameter scaling simultaneously changes the system inertia level, damping action, and overall dynamic timescale. The simulation results provide further evidence that variations in the inertia–damping parameter scale significantly influence the active-power–frequency dynamic external characteristics of the hydro-storage microgrid.
5.4. Frequency Response Under Different Load-Disturbance Magnitudes
With the P–ω2 control strategy and the inertia–damping parameter combination held fixed, load-step disturbances with different magnitudes are applied to investigate how different levels of active-power imbalance affect the active-power–frequency dynamic external characteristics of the microgrid. The operating conditions are listed in Table 3, and the corresponding system frequency responses are shown in Figure 7.
Table 3.
Operating conditions under different load-step disturbances.
Figure 7.
System frequency responses under different load-disturbance magnitudes.
As shown in Figure 7, with P–ω2 control and the inertia–damping parameters held constant, the frequency nadir decreases markedly as the load-disturbance magnitude increases. For ΔPL = 150, 300, and 450 kW, the corresponding frequency nadirs are approximately 48.55, 47.01, and 45.43 Hz, respectively. Thus, a larger load disturbance leads to a more pronounced frequency drop. All three cases nevertheless recover to stable operation, and the frequency-recovery trajectories exhibit broadly similar trends.
Taking the 450 kW load-disturbance case as an example, the minimum system frequency is approximately 45.43 Hz, corresponding to a maximum negative frequency deviation of approximately 4.57 Hz relative to the nominal frequency of 50 Hz. According to the relative nonlinear contribution defined above, the maximum contribution of the second-order nonlinear term relative to the first-order regulation term is approximately 4.57%. Meanwhile, the corresponding relative frequency deviation is approximately 9.14%, which remains within the 10% relative-frequency-deviation range corresponding to the adopted 5% nonlinear-contribution threshold.
These results indicate that, under this disturbance condition, the contribution of the quadratic nonlinear term remains smaller than that of the first-order regulation term, although its influence should not be neglected as the frequency deviation becomes larger. It should be emphasized that this relative contribution coefficient is used only to quantify the relative magnitude of the second-order term in the power-regulation relationship and does not directly represent the frequency-response prediction error of the linearized model.
The influence of neglecting the second-order term on the predicted power response can be further explained based on the control law. For a load-increase disturbance accompanied by a frequency drop, the full nonlinear control law produces a smaller positive power-support command than the first-order approximation. Consequently, the linearized model tends to overestimate the converter’s power-support capability and predict a higher frequency nadir than the nonlinear P–ω2 control law. Conversely, under a load-decrease disturbance, neglecting the quadratic term underestimates the magnitude of the negative power-regulation command and may lead to an overestimation of the frequency overshoot. These discrepancies become more pronounced as the frequency deviation increases.
The active-power balance relationship shows that increasing the load-step magnitude directly enlarges the instantaneous active-power deficit. With the system inertia unchanged, a larger power imbalance produces a faster initial frequency variation and a lower frequency nadir. At the same time, the larger frequency excursion requires the energy-storage converter to provide stronger transient active-power support to compensate for the increased power deficit. The load-disturbance magnitude therefore directly affects the system inertial-support requirement.
These results indicate that, with the control parameters fixed, the load-disturbance magnitude primarily determines the severity of the frequency drop and the transient inertial-support requirement, whereas the fundamental recovery dynamics remain governed by the specified inertia–damping parameter combination. The simulations under different disturbance conditions further show that the established inertia–frequency dynamic model can effectively characterize the influence of power-disturbance magnitude on the active-power–frequency dynamic external characteristics of the microgrid.
Finally, the capability of the reduced-order model used in this study should be clarified. The model reproduces the initial rate of change of frequency and the frequency nadir, as well as their dependence on the inertia–damping parameters and on the load-disturbance magnitude, which is consistent with the responses in Figure 5, Figure 6 and Figure 7. Being first order with respect to the frequency deviation, however, the model cannot reproduce a reverse overshoot, because its step response is monotonic; the overshoot observed under conventional P–ω control therefore originates from the interaction between the converter power response and the governor and converter inner-loop dynamics that are not retained in the reduced-order model. The model should thus be regarded as a tool for characterizing the dominant time scale and the parameter trends of the external characteristics, rather than as a waveform-level predictor of the overshoot and oscillatory components.
6. Conclusions
This study investigates the active-power–frequency dynamic external characteristics of an islanded hydro-storage microgrid under P–ω2 virtual synchronous control through theoretical modeling and time-domain analysis. An active-power–frequency dynamic model coupling the physical inertia of the hydro-turbine synchronous generator and the virtual inertia of the energy-storage converter is established. The effects of different power–frequency control strategies, inertia–damping parameter combinations, and load-disturbance magnitudes on the system dynamic external characteristics are analyzed and validated using a PSCAD/EMTDC electromagnetic transient model. The main conclusions are summarized as follows:
- (1)
- The physical inertia of the hydro-turbine synchronous generator and the virtual inertia of the energy-storage converter jointly constitute the equivalent inertia of the islanded hydro-storage microgrid. Around the nominal operating point, P–ω2 control can provide a first-order active-power–frequency regulation characteristic comparable to that of conventional P–ω control, whereas the squared-angular-speed term introduces a distinct nonlinear power-regulation characteristic as the frequency deviation increases. Under identical inertia and damping parameters and comparable small-signal regulation gains, P–ω2 control mitigates the reverse overshoot and transient oscillations observed during the recovery process under conventional P–ω control, thereby improving the frequency-recovery characteristics of the microgrid.
- (2)
- Virtual inertia and virtual damping exert different but interrelated effects on the active-power–frequency dynamic external characteristics of the hydro-storage microgrid. Virtual inertia mainly affects the initial frequency variation following a disturbance, whereas virtual damping contributes more significantly to the subsequent recovery process. With the relative inertia–damping configuration held constant, proportionally increasing the virtual inertia and virtual damping raises the frequency nadir from 48.37 Hz to 48.54 Hz and 48.72 Hz, respectively. This indicates that increasing the parameter scale enhances the initial frequency-support capability, and, under the joint scaling law adopted in this study, also shortens the time required for the frequency to recover to the vicinity of the nominal value. Therefore, the inertia–damping parameters should be coordinated by jointly considering the frequency nadir, RoCoF, and dynamic recovery time.
- (3)
- The load-disturbance magnitude directly affects the active-power imbalance and the transient inertial-support requirement of the hydro-storage microgrid. With the inertia–damping parameters fixed, the frequency nadirs under load disturbances of 150, 300, and 450 kW are approximately 48.55, 47.01, and 45.43 Hz, respectively. As the disturbance magnitude increases, the frequency drop becomes more pronounced and a stronger transient active-power response is required from the energy-storage converter. No sustained oscillation or response divergence is observed in the three investigated cases, and the system eventually returns to stable operation. These results verify the capability of the established model to characterize the active-power–frequency dynamic external response under different disturbance magnitudes.
- (4)
- The developed reduced-order inertia–frequency model is primarily applicable under sufficiently strong AC-network coupling and synchronized operation without sustained converter current limiting. Under weak coupling, severe faults, large phase-angle excursions, or sustained current limiting, higher-order network, electromagnetic, and converter-control dynamics should be retained.
In addition, the frequency nadirs obtained under different load-disturbance conditions indicate that large power disturbances may impose more stringent requirements on frequency-security and protection coordination in islanded hydro-storage microgrids. Since specific protection thresholds and engineering limits are not considered in the present study, future work will investigate the coordination among frequency nadir, RoCoF, under-frequency protection, converter operating limits, and staged under-frequency load shedding based on load priority. Hardware-in-the-loop and experimental validation will also be conducted to further evaluate the applicability of the reduced-order model and P–ω2 virtual synchronous control.
Finally, the scope of the present assessment should be clarified. This study does not explicitly assess converter current limiting, DC-side dynamics, or the state-of-charge and power constraints of the energy-storage system; the conclusions drawn above are therefore restricted to the operating conditions and parameter ranges considered here.
Author Contributions
Conceptualization, Y.H. and D.Z.; methodology, Y.H. and D.Z.; software, N.W., Z.L. and Y.Z. (Yuanyi Zhang); validation, Y.Z. (Yongjun Zhou), X.Z. and Y.Q.; investigation, Y.H. and X.Z.; writing—original draft preparation, Y.H.; writing—review and editing, Y.H., D.Z., N.W., Y.Z. (Yongjun Zhou), X.Z. and Y.Q.; visualization, Z.L., Y.Z. (Yuanyi Zhang) and Y.Z. (Yongjun Zhou); supervision, Y.Z. (Yuanyi Zhang) and X.Z.; project administration, Y.H. All authors have read and agreed to the published version of the manuscript.
Funding
This work is supported by the Science and Technology Project of State Grid Jibei Electric Power Co., Ltd. (Research and Application of Source-Load-Storage Optimal Regulation Technology for Microgrids Based on Multi-Agent Collaboration, No. B3016K26Z00F).
Data Availability Statement
Data is contained within the article.
Conflicts of Interest
Authors Y.H., N.W., D.Z., and Z.L. are employed by the State Grid Jibei Electric Power Company Limited Smart Distribution Network Center. Authors Y.Z. (Yuanyi Zhang) and Y.Z. (Yongjun Zhou) are employed by the Chengde Power Supply Company, State Grid Jibei Electric Power Co., Ltd. Authors X.Z. and Y.Q. are employed by the School of Electrical and Electronic Engineering at Shandong University of Technology. The remaining authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.
References
- Ulbig, A.; Borsche, T.S.; Andersson, G. Impact of Low Rotational Inertia on Power System Stability and Operation. IFAC Proc. Vol. 2014, 47, 7290–7297. [Google Scholar] [CrossRef] [Scilit]
- Tielens, P.; Van Hertem, D. The Relevance of Inertia in Power Systems. Renew. Sustain. Energy Rev. 2016, 55, 999–1009. [Google Scholar] [CrossRef] [Scilit]
- Gu, Y.; Green, T.C. Power System Stability With a High Penetration of Inverter-Based Resources. Proc. IEEE 2023, 111, 832–853. [Google Scholar] [CrossRef] [Scilit]
- He, C.; Geng, H.; Rajashekara, K.; Chandra, A. Analysis and Control of Frequency Stability in Low-Inertia Power Systems: A Review. IEEE/CAA J. Autom. Sin. 2024, 11, 2363–2383. [Google Scholar] [CrossRef] [Scilit]
- Lasseter, R.H.; Chen, Z.; Pattabiraman, D. Grid-Forming Inverters: A Critical Asset for the Power Grid. IEEE J. Emerg. Sel. Top. Power Electron. 2020, 8, 925–935. [Google Scholar] [CrossRef] [Scilit]
- Zhong, Q.C.; Weiss, G. Synchronverters: Inverters That Mimic Synchronous Generators. IEEE Trans. Ind. Electron. 2011, 58, 1259–1267. [Google Scholar] [CrossRef] [Scilit]
- Khan, M.; Wu, W.; Li, L. Grid-Forming Control for Inverter-Based Resources in Power Systems: A Review on Its Operation, System Stability, and Prospective. IET Renew. Power Gener. 2024, 18, 887–907. [Google Scholar] [CrossRef] [Scilit]
- D’Arco, S.; Suul, J.A. Equivalence of Virtual Synchronous Machines and Frequency-Droops for Converter-Based Microgrids. IEEE Trans. Smart Grid 2014, 5, 394–395. [Google Scholar] [CrossRef] [Scilit]
- Liu, J.; Miura, Y.; Ise, T. Comparison of Dynamic Characteristics Between Virtual Synchronous Generator and Droop Control in Inverter-Based Distributed Generators. IEEE Trans. Power Electron. 2016, 31, 3600–3611. [Google Scholar] [CrossRef] [Scilit]
- Chen, J.; O’Donnell, T. Analysis of Virtual Synchronous Generator Control and Its Response Based on Transfer Functions. IET Power Electron. 2019, 12, 2965–2977. [Google Scholar] [CrossRef] [Scilit]
- Cheema, K.M.; Milyani, A.H.; El-Sherbeeny, A.M.; El-Meligy, M.A. Modification in Active Power-Frequency Loop of Virtual Synchronous Generator to Improve the Transient Stability. Int. J. Electr. Power Energy Syst. 2021, 128, 106668. [Google Scholar] [CrossRef] [Scilit]
- González-Cajigas, A.; Roldán-Pérez, J.; Bueno, E.J. Design and Analysis of Parallel-Connected Grid-Forming Virtual Synchronous Machines for Island and Grid-Connected Applications. IEEE Trans. Power Electron. 2022, 37, 5107–5121. [Google Scholar] [CrossRef] [Scilit]
- Soni, N.; Doolla, S.; Chandorkar, M.C. Improvement of Transient Response in Microgrids Using Virtual Inertia. IEEE Trans. Power Deliv. 2013, 28, 1830–1838. [Google Scholar] [CrossRef] [Scilit]
- Li, D.; Zhu, Q.; Lin, S.; Bian, X.Y. A Self-Adaptive Inertia and Damping Combination Control of VSG to Support Frequency Stability. IEEE Trans. Energy Convers. 2017, 32, 397–398. [Google Scholar] [CrossRef] [Scilit]
- Rathore, B.; Chakrabarti, S.; Srivastava, L. ARI and ARID Control of Virtual Synchronous Generator for Frequency Response Improvement. IET Renew. Power Gener. 2021, 15, 664–675. [Google Scholar] [CrossRef] [Scilit]
- Markovic, U.; Stanojev, O.; Aristidou, P.; Vrettos, E.; Callaway, D.S.; Hug, G. Understanding Small-Signal Stability of Low-Inertia Systems. IEEE Trans. Power Syst. 2021, 36, 3997–4017. [Google Scholar] [CrossRef] [Scilit]
- Tayyebi, A.; Groß, D.; Anta, A.; Kupzog, F.; Dörfler, F. Frequency Stability of Synchronous Machines and Grid-Forming Power Converters. IEEE J. Emerg. Sel. Top. Power Electron. 2020, 8, 1004–1018. [Google Scholar] [CrossRef] [Scilit]
- Shi, K.; Song, W.; Ge, H.; Xu, P.; Yang, Y.; Blaabjerg, F. Transient Analysis of Microgrids With Parallel Synchronous Generators and Virtual Synchronous Generators. IEEE Trans. Energy Convers. 2020, 35, 95–105. [Google Scholar] [CrossRef] [Scilit]
- Kenyon, R.W.; Sajadi, A.; Bossart, M.; Hoke, A.; Hodge, B.M. Interactive Power-to-Frequency Dynamics Between Grid-Forming Inverters and Synchronous Generators in Power Electronics-Dominated Power Systems. IEEE Syst. J. 2023, 17, 3456–3467. [Google Scholar] [CrossRef] [Scilit]
- Li, C.; Huang, Y.; Wang, Y.; Monti, A.; Wang, Z.; Zhong, W. Modelling and Small Signal Stability for Islanded Microgrids with Hybrid Grid-Forming Sources Based on Converters and Synchronous Machines. Int. J. Electr. Power Energy Syst. 2024, 157, 109831. [Google Scholar] [CrossRef] [Scilit]
- Westman, J.; Hadidi, R. Overload Mitigation for Grid-Forming Inverters in Islanded Microgrids with Synchronous Generators. Electr. Power Syst. Res. 2025, 239, 111231. [Google Scholar] [CrossRef] [Scilit]
- Ojo, Y.; Alam, S.M.S.; Balliet, W.H.; Mosier, T.M. Frequency Response Improvement in a Standalone Small Hydropower Plant Using Battery Storage. IEEE Trans. Energy Convers. 2024, 39, 2701–2717. [Google Scholar] [CrossRef] [Scilit]
- Reigstad, T.I.; Uhlen, K. Variable Speed Hydropower for Provision of Fast Frequency Reserves in the Nordic Grid. IEEE Trans. Power Syst. 2021, 36, 5476–5485. [Google Scholar] [CrossRef] [Scilit]
- Vasudevan, K.R.; Ramachandaramurthy, V.K.; Venugopal, G.; Guerrero, J.M.; Agundis Tinajero, G.D. Synergizing Pico Hydel and Battery Energy Storage With Adaptive Synchronverter Control for Frequency Regulation of Autonomous Microgrids. Appl. Energy 2022, 325, 119827. [Google Scholar] [CrossRef] [Scilit]
- Faragalla, A.; Abouzeid, S.I.; Abdel-Rahim, O.; Orabi, M.; Abdelhameed, E.H. Adaptive and Coordinated Load Frequency Control for Isolated Microgrids Considering Battery State of Charge Dynamics. J. Energy Storage 2025, 112, 115467. [Google Scholar] [CrossRef] [Scilit]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2026 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.