Abstract
Waste Heat Recovery (WHR) has become a key technology for improving energy efficiency and reducing greenhouse gas emissions in energy-intensive sectors. Although large-scale industrial solutions are widely described in the literature, there is a significant gap regarding simple, low-cost systems dedicated to domestic applications, particularly those recovering low-grade waste heat (40–60 °C) from personal computers. This paper addresses this gap by presenting the design, development, and experimental validation of a novel immersion-based heat recovery system for home computers. The proposed solution employs dielectric oil as a cooling medium in a modular polypropylene tank, enabling direct utilization of waste heat for Domestic Hot Water (DHW) preparation without the need for heat pumps or complex installations. The system is characterized by simplicity, modularity, ease of installation, and low investment cost, making it suitable for single-family houses and apartments. The general system architecture, a patented oil-circulation solution, a microcontroller-based control algorithm, and preliminary laboratory tests are described. Validation experiments performed during cryptocurrency mining yielded directly measured thermal efficiencies ranging from 54% to 74%. The developed system fills an important research gap, offering an innovative, sustainable way to convert waste heat from household electronics into useful thermal energy. Empirical results show that the system can reduce conventional heating fuel consumption and associated energy costs in residential applications.
1. Introduction
Waste Heat Recovery (WHR) has emerged as a key branch of science and technology developed to improve energy efficiency and reduce greenhouse gas emissions in energy-intensive sectors of the economy [1,2]. In every such sector, this technology allows for the recovery of significant amounts of waste heat and its conversion into a useful source of thermal or electrical energy, with notable examples in the iron and steel, cement, chemical and glass industries [3].
Rapid technological development, particularly in the Information Technology (IT) sector, leads to the consumption of massive amounts of electrical energy. In Poland alone, the industrial sector consumes tens of TWh annually. It is estimated that the Artificial Intelligence (AI) industry will require over 150 TWh per year by 2027 [4]. This energy is converted mainly into heat, and this heat must be dissipated and released into the atmosphere to prevent equipment failure. Effective recovery and reuse of this waste heat, for instance by transferring it to nearby residential neighborhoods or employing Organic Rankine Cycle (ORC) systems, are increasingly recognized as critical steps toward improving the energy efficiency and reducing the carbon footprint of operations. Practical utilization of even 10% of this energy would significantly impact not only the financial balance but also the environment. Furthermore, the integration of such recovery systems into residential environments is now highly feasible due to the rapid advancement of Internet of Things (IoT) technologies and smart home frameworks [5].
Existing solutions typically focus on large-scale processes and industrial centers. The resources employed, and consequently their cost, are adapted to the scale of large investments such as computing centers. Immersion cooling technologies, widely used in data centers, offer significant benefits compared to traditional air cooling, making them a promising solution for home computers as well. Farhat et al. [6] emphasize that WHR is a key strategy for reducing energy consumption in various sectors, including residential construction, where heat recovery systems, such as Drain Water Heat Recovery (DWHR), can preheat Domestic Hot Water (DHW). Similarly, the present immersion system for heat recovery from home computers utilizes waste heat at 40–60 °C to heat DHW, aligning with the trend of simple and effective WHR solutions for households [6,7].
Wang et al. [8] indicate that immersion cooling is characterized by a high heat transfer coefficient, which allows for efficient heat dissipation from electronic components, reduction of the temperature difference between the device and the coolant, and improvement in server operational stability. Zhou et al. [9] add that immersion systems provide temperature uniformity, noise reduction, and the possibility of heat recovery at 40–60 °C, which is particularly important for domestic applications such as heating domestic hot water. The fundamental principles of heat transfer dictate that transitioning from air to liquid cooling significantly enhances the heat transfer coefficient, making immersion systems inherently more efficient for capturing low-grade waste energy [10]. Shah et al. [11] point out that in immersion heat recovery systems, dielectric oils such as paraffin oil or transformer oil are the preferred medium for cooling due to their high heat capacity, chemical stability, and low flammability potential, although their relatively low thermal conductivity remains a challenge. These studies suggest that immersive technologies can be adapted to home computers through simplified construction and the use of modular components.
Zhou et al. [9] analyze the direct utilization of waste heat for heating, which proves effective in regions with high heat demand, with an investment payback period below 5 years. In domestic conditions, heat at 40–60 °C can, in the simplest configurations, be directly used to heat water in buffer tanks, eliminating the need for complex systems such as heat pumps. Wang et al. [8] indicate that heat pumps are crucial for raising the temperature of waste heat to a useful level, achieving high efficiency in integration with heating systems. However, in the context of this work, the assumption of simplicity and low system cost excludes the possibility of using heat pumps.
The literature simultaneously points out several challenges and research gaps that are relevant to this study. Low-temperature waste heat (40–60 °C) limits the efficiency of more advanced technologies such as the ORC, which, according to Wang et al. [8] and Zhou et al. [9], achieves thermal efficiency of only 2–8% under such conditions, despite its successful implementation in other advanced applications like autonomous heat removal systems [12]. In the case of home computers generating relatively small amounts of heat, ORC is impractical due to high costs and complexity. There is also a lack of research on simple, modular WHR systems dedicated to domestic devices, which underscores the need for the research presented in this article. From the perspective of this study, two additional conclusions are important and required experimental verification. Shah et al. [11] draw attention to insufficient data on the long-term stability of dielectric oils, including in contact with plastics, which may affect the durability of polypropylene tanks. T’Joen et al. [13] indicate that polypropylene requires further research on thermal resistance in high-temperature applications, which is important for designing a reliable system.
In summary, none of the analyzed scientific works fully corresponds to the present study, which combines simplicity, modularity, low costs, and a specific material configuration in the context of immersion-based heat recovery from home computers. The most thematically similar works (Dogkas et al., [14]) concern heat storage in tanks under domestic conditions, but do not consider immersion cooling or computers as a heat source. The conducted research fills a significant gap in the literature, providing an innovative solution for sustainable utilization of waste heat in households, and equally importantly, according to Farhat et al. [6], the proposed WHR system can effectively substitute conventional heating fuels and lower related energy expenses.
The concept of using computational equipment as a heat source for residential buildings has already been investigated in the literature. For example, Antal et al. [15] proposed a distributed data center architecture where air-cooled servers are installed directly in homes to act as primary heaters, utilizing thermal-aware workload scheduling to meet residents’ heat demand. While this confirms that the general concept of household heat recovery from servers is not entirely new, the technical implementation presented in our manuscript fundamentally differs. Unlike air-cooled distributed nodes managed via complex computational scheduling, our solution employs direct immersion cooling tailored specifically for retrofitting existing home computers and cryptocurrency miners to transfer heat directly to domestic hot water systems without continuous software-level intervention.
Table 1 summarizes the existing heat recovery technologies discussed in the literature and highlights the distinct features of the proposed system.
Table 1.
Comparison of existing waste heat recovery solutions and concepts in the literature.
1.1. Motivation and Problem Definition
The current literature predominantly focuses on large-scale industrial solutions, with limited attention given to small-scale domestic applications. It is essential to recover waste heat not only from tens of thousands of industrial facilities, but also from hundreds of millions of electronic devices operating in the distributed network of many households. Effective heat recovery in this context offers significant benefits for both business and environmental protection. Among numerous large-scale systems, a limited number of preliminary technologies have emerged that are aimed at domestic users. These include methods such as recovering heat from water discharged into the sewage system. However, the literature review revealed no solutions for heat recovery from electronic devices adapted to the technical and financial realities of single-family homes, apartments, or small communities. Large-scale solutions, due to their required technical resources, are completely unsuitable for this purpose. Moreover, large industrial centers are oriented towards continuous operation and regulate their profitability through the price of services provided. Production and sales costs are usually well known and relatively stable over time. This is not always the case in domestic settings. Apart from using electronic devices for entertainment, individuals increasingly utilize high-performance computers (e.g., for cryptocurrency mining or AI rendering) for occasional income generation. This is associated with high profitability variance and requires specialized optimization measures.
The designed system should be characterized by the following features:
- (a)
- Heat recovery from high-load computing devices, such as specialized Personal Computers (PCs) and cryptocurrency miners;
- (b)
- Scale enabling adaptation to residential home conditions;
- (c)
- Ease of installation, comparable to that of standard heating appliances;
- (d)
- Low cost of the device and installation, resulting in a short investment payback period;
- (e)
- Simple, user-friendly operation requiring no specialized technical knowledge.
1.2. Work Objective
The primary objective of this work is to design and develop a low-cost, easy-to-install WHR solution that allows individual users to recover waste heat from personal computers directly into a building’s heating system. Unlike existing large-scale industrial systems, this work aims to provide a financially and technically accessible system for domestic adoption.
While large-scale industrial WHR systems are well-documented, household-level applications remain relatively unexplored. Therefore, this paper is explicitly positioned as a comprehensive proof-of-concept study. It aims to demonstrate the fundamental technical feasibility and practical applicability of adapting immersion cooling for distributed residential heating. By using cryptocurrency mining as a highly energy-intensive representative workload, this study provides a foundational framework and initial quantitative baseline for future research in domestic WHR technologies.
In this work, we propose a novel heat recovery system. The contributions of this work are the following:
- We outline the general structure of a heat recovery system to be used at home to regain heat from electronic devices, mainly computers.
- We describe the development details of the system, including energy-recovery hardware, a patented oil-circulation solution, and electronics.
- We also detail an original microcontroller-based control algorithm necessary to manage the operation of the system.
- We describe preliminary laboratory tests which helped to evaluate and verify different possible implementation directions and their efficiency.
- We report validation experiments on the efficiency of the proposed heat recovery system considering the energy-consuming task of cryptocurrency mining.
2. System Description
2.1. General Structure
The general diagram of the developed system is shown in Figure 1. A stack of n tanks is connected in parallel to the primary heat-transporting main. In these tanks, computing devices are placed, one per tank. The devices are immersed in a liquid that is responsible for receiving and transporting the generated heat. After the heat is absorbed from the devices, it is transported via valves and pumps to a common primary heating circuit shared by all tanks. This main serves as the connector between the WHR system and the building’s technical installation. The last section is the home heating system. The presented device can operate with various types of heating systems. For instance, it can be connected to a heat buffer or to the return line of the heating circuit upstream of a gas furnace or heat pump. The proposed structure allows for flexible adaptation to the requirements of a given building.
Figure 1.
Block diagram of the WHR system in a residential heating scenario, showing the flow of hot water supply to the radiators, cooled water return to the WHR units, and preheated water to the house heater.
Two different versions of the WHR system were designed and developed. The first of them is a minimalist solution based only on tanks and thermostatic valves. These valves simultaneously play the role of physical connector, temperature sensor, and controller. This integration of several functionalities into one mechanical part makes this version simpler in both operation and installation, as well as cheaper. It allows for simple integration with home heating systems and limits the need for user supervision and control to an absolute minimum. This version of the WHR system will hereinafter be referred to as the mechanical version.
Figure 2 shows the general diagram of a single tank in the mechanically controlled WHR system. The tank is filled with dielectric liquid, in which a computing device is immersed. In this version of the device, the heat exchanger is placed in the tank, thanks to which the dielectric liquid does not flow outside. The tank is connected to the thermal main, which is part of the building’s technical installation and is filled with the liquid used in the building. Upon reaching the appropriate temperature, the thermostatic valve opens, enabling the flow of liquid from the main through the internal exchanger in the tank and extracting the accumulated heat. Further, this heat is transported by the main to the place where it is utilized. When the temperature drops, the valve closes, and the flow of liquid from the building’s technical installation through the tank is shut off.
Figure 2.
Single tank diagram, mechanically controlled version of WHR.
The second version of the system is depicted in Figure 3. This version will hereinafter be referred to as the electronic version since it employs a microcontroller and additional sensors. It allows for full control over the heat recovery process, including the possibility of online control of multiple process parameters. The base of the electronically controlled WHR system is quite similar to the mechanically controlled one. The tank, the dielectric fluid, and the immersed computing device are the same as in the mechanical version. The primary difference in the diagram is that the heat exchanger is no longer a part of the tank. Individual heat exchangers for each tank were replaced with one heat exchanger for all tanks. The exchanger is connected on one side to the heating main and on the other side to the building’s heat installation. In this version, the hot dielectric fluid flows via the valves to the heating main and then to the exchanger, where the stored energy is transferred to the building’s installation. Consequently, this solution requires the dielectric fluid to flow outside the tank, creating a hydraulic connection between the fluid in the tanks. In the electronic version, the type of valves has been also changed. This version is equipped with solenoid valves. This change is necessary to enable precise flow control through the tank and is part of the advanced control and regulation system.
Figure 3.
Single tank diagram, electronically controlled version of WHR.
Figure 4 and Figure 5 illustrate the concept of controlling the WHR process. In the mechanical system, thermostatic valves serve as an integrated regulation system. Through its construction, the valve de facto incorporates a temperature sensor, regulator, and actuator. The entire flow of control signals is enclosed within a single mechanical device. However, in cases requiring precise process control, such a solution is not sufficiently flexible. For this reason, the second version of the WHR system employs a microprocessor system for control. Figure 5 shows that the tanks are equipped with external sensors, which provide essential information about the process to the main controller. Based on these data, the controller regulates the flow by making decisions regarding the activation or deactivation of the solenoid valves.
Figure 4.
Process control structure of WHR mechanically controlled system.
Figure 5.
Process control structure of WHR electronically controlled system.
The mechanical version, through the application of mechanical thermostatic valves, integrates the necessary sensors and controller into one inexpensive device. For this reason, the process regulation is extremely limited. The user only has the possibility to set the temperature at which the valve opens. The selection of this temperature is done experimentally by establishing a correlation between the temperature of the computing device, the temperature of the cooling liquid, and the temperature set on the thermostat. Once set, the parameters remain unchanged. The parameters cannot be automatically adjusted to unforeseen situations, which means that the computing devices themselves should have internal protection against overheating.
In contrast, the electronic version requires external sensors for proper operation. In the case of the electronic version, there are no restrictions regarding the types and kinds of sensors used. The only limitation is the hardware capabilities of the controller and the programming skills of the software creator. However, there is a minimum set essential for proper functioning. For the electronic version to operate correctly, temperature sensors are needed to monitor the device’s state inside the tanks. Also required are low- and high-level sensors for the liquid in which the computing devices are immersed. Since the tanks in the electronic version are hydraulically connected, the liquid naturally tends to flow from higher to lower tanks. The liquid level sensors enable the controller to compensate for any resulting fluid deficiencies during operation.
2.2. Energy-Recovery Hardware
The physical implementations of both system variants differ from each other in virtually every aspect, except for the general concept of placing computing devices in tanks and transporting the heat generated by them using the liquid in which they are immersed. Figure 6 shows examples of these tanks. The stainless steel tank of the electronically controlled version is equipped with various external hardware components. This hardware is necessary for proper system operation. First, two solenoid valves are attached to the front of the tank, along with their segment of the heating main. These valves are used to control the flow and regulate the temperature and fluid level in each tank. On the side of the tank, power supply and sensor connectors, as well as a vent valve necessary to handle pressure changes during operation, are placed. The mechanically controlled variant features significantly less external hardware. It typically requires only power and Ethernet connections, and can be connected directly to the primary main without external flow-control modules. While this limits parameter adjustability compared to the electronic version, it significantly reduces the overall cost and complexity of the system.
Figure 6.
Single tank of the WHR system: (a) electronically controlled version; (b) mechanically controlled version.
As the primary heat transfer medium, paraffin oil is utilized due to its excellent dielectric properties, high boiling and flash points, non-toxicity, and low cost. While the heat exchanger is enclosed within each individual tank in the mechanical version, the electronic version routes the hot oil to a common main and then to the heat exchanger.
Due to maintaining the oil circulation inside each tank separately, the tank of the mechanically controlled system can be much simpler in construction. The tank is made of Polypropylene (PP), a material selected for its excellent chemical resistance to mineral oils and sufficient thermal stability in temperatures up to 80–90 °C [18], butt-welded and reinforced with an additional overlay on all connection lines. This tank contains only the inlet and outlet for the heat-receiving liquid, as well as the power supply inlet and telecommunication inputs/outputs. Inside the tank, there is a stainless steel coil arranged in several loops attached one above the other to the tank walls. The outlet from the coil is connected directly to the common hydraulic main. The inlet, however, is separated from the main by a thermostatic valve. This valve is a completely mechanical solution. Upon reaching the set temperature of the liquid in the coil inside the tank, the valve opens, enabling the flow of hydraulic liquid and energy extraction. When the temperature drops, the valve closes and cuts off the flow. In this simplest possible way, regulation in the mechanical system is implemented.
Both systems were designed to operate either as standalone units or in a stacked configuration. Figure 7 presents the electronic and mechanical systems respectively in a multi-tank configuration. The electronic systems were designed such that the tanks are positioned directly on top of one another, forming a self-supporting structure. The mechanical system is equipped with a separate modular rack. Each rack module features a sliding drawer on which a single tank is placed. The use of a drawer mechanism allows individual tanks to be withdrawn for ease of maintenance and repair.
Figure 7.
WHR stack multi-tank configuration: (a) electronically controlled; (b) mechanically controlled.
To facilitate a quantitative assessment of the physical footprint, installation requirements, and practical feasibility of both designs, Table 2 summarizes the key engineering, geometric, and operating parameters of the electronically and mechanically controlled WHR variants. From a layout perspective, the vertical stacking architecture limits the required floor area to approximately 0.5 per stack (including a spill containment tray), allowing installation in standard residential boiler rooms or utility spaces alongside existing heating equipment. However, practical deployment must account for both floor loading and service access: a fully assembled stack filled with dielectric oil and computing hardware reaches a total operating mass exceeding 130 kg for the four-tank electronic variant and approaching 300 kg (excluding the rack) for the five-tank mechanical variant, and the mechanically controlled rack requires a frontal clearance of at least 1 m to permit full drawer extension during maintenance. In terms of implementation complexity, integrating the mechanical variant into an existing domestic heating circuit requires only standard plumbing connections (3/4″ return-line tie-in, water circulation pump, and 230 AC power supply per module), whereas the electronic variant additionally requires mounting the DIN-rail control cabinet, routing low-voltage sensor and solenoid harnesses, and provisioning a single-phase electrical feed scaled to the total installed computing load.
Table 2.
Key engineering, geometric, and operating parameters of the electronically and mechanically controlled WHR system variants.
2.3. Oil Circulation Necessity
In the designed heat recovery system, a significant challenge is the efficient removal of thermal energy from devices submerged in the medium, which during normal operation heat up to temperatures in the range of 60–70 °C. The choice of mineral oil as the heat transfer medium is fully justified by its excellent dielectric properties and high thermal capacity. However, from a thermodynamic standpoint, oil is characterized by a relatively high kinematic viscosity and a lower thermal conductivity than water, which imposes specific requirements on the cooling process.
Heat transfer from the surfaces of the heated devices to the oil occurs via convection. Under static conditions, without any additional forcing of fluid motion, natural (free) convection takes place, in which the movement of the liquid is driven solely by buoyancy forces arising from density differences in the temperature gradient. In the viscous oil environment, however, this mechanism proves too slow.
Forced convection provides considerably more effective heat transfer than natural convection [10], and in mineral oil immersion cooling, component temperatures depend strongly on the oil flow rate [19]. Without forced circulation, heat accumulates in the immediate vicinity of the submerged components, leading to local hot spots. This was confirmed in preliminary tests, in which the computing devices overheated under static oil conditions, whereas introducing active oil agitation stabilized their operating temperatures within the target range of 60–70 °C.
However, practical implementation presented several technical challenges. One of the main challenges encountered during the development of the system was ensuring the continuous circulation of hot oil. At the same time, finding a solution that is not only durable but also cost-effective is essential for the system’s practical implementation. The solution to this problem is described in Section 4.3.
2.4. Hardware Implementation of Electronic Control Device
The block diagram of the heat recovery system control unit is shown in Figure 8. The system utilizes a central control unit, based on the ATmega 1284P microprocessor [20]. This controller provides direct connections to the primary analog sensors and drives the main actuators of the system, including solenoid valves and relays.
Figure 8.
Controller architecture block diagram.
Given that the system manages multiple tanks requiring independent metering, the architecture adopts a scalable modular design. Industrial MODBUS modules, utilizing the robust master–slave architecture standard in industrial automation [21], are employed as expansion units, adding further inputs and outputs to the system. The choice of the MODBUS protocol is justified by its sustained prevalence in industrial automation and IoT gateway integration, owing to its operational simplicity and high interoperability with distributed physical layers [22]. These modules communicate with the master unit over a shared bus based on the Universal Synchronous and Asynchronous Receiver–Transmitter (USART) interface. The lower portion of the diagram illustrates the daisy-chain (series) interconnection of these devices.
Two primary types of expansion modules are used: digital output extension modules used to drive solenoid valves and power relays assigned to successive tank sections, and analog input extension modules used to acquire data from analog temperature and liquid level sensors located in each tank. This approach ensures that adding further tanks to the heat recovery system requires no modifications to the base unit.
The system interfaces with its environment through two independent communication channels. For local operation, a Human–Machine Interface (HMI) operator panel is connected to the central unit via a USART MODBUS bus, enabling the user to monitor the operating parameters of individual tanks in real time and to manually adjust the control algorithm setpoints. For remote supervision and data transmission to a Wide Area Network (WAN)/Internet network, a module based on the ESP32 System on a Chip (SoC), which natively supports Wi-Fi and Bluetooth connectivity [23], is employed. This module exchanges data with the master controller through a dedicated USART interface and operates as a lightweight, low-cost IoT network gateway [24,25,26]. Through this communication channel, the system can not only expose operational data to the user, but, more importantly, it can collect data from metering devices and market condition feeds, allowing the control intensity to be adjusted accordingly for optimized building energy management [27]. These data enable the controller to incorporate economic considerations into its decision-making process regarding system operation.
The physical implementation of the control system is shown in Figure 9, which illustrates the construction of the control panel in which the individual components are mounted on a standard DIN rail. The primary control unit (based on the ATmega processor), equipped with its own diagnostic display, is visible in the upper section of the assembly. Below it, alongside the protective apparatus and industrial power supply, the aforementioned MODBUS expansion modules (housed in green enclosures) are installed.
Figure 9.
The electronic controller: (a) basic configuration with MODBUS I/O modules; (b) expanded configuration with HMI manipulator.
A comparison of parts (a) and (b) in Figure 9 effectively demonstrates the intended modularity and scalability of the architecture. In the left photograph, showing the basic configuration, only two input/output modules are connected to the master unit. The right photograph presents the system operating in its expanded configuration, featuring a daisy-chain connection of five MODBUS modules. The illuminated Light-Emitting Diodes (LEDs) provide real-time indication of the status of individual inputs and outputs assigned to successive tanks. Furthermore, in the lower section of the right photograph, an external HMI touchscreen is shown connected and operational. It serves as the primary user interface, in accordance with the design assumptions outlined in the block diagram. In the upper portion of the same photograph, liquid level sensors prepared for connection can also be identified.
2.5. Microcontroller-Based Control Algorithm
The developed control system is based on a modular software architecture operating within a microcontroller environment. As illustrated in Figure 10, the base structure of the system comprises three main, interdependent blocks: the business optimization module (acting as the superordinate decision-making layer), the heat recovery process module, and the heat generation process module. The system operates in a closed feedback loop based on classic control theory principles [28], in which status information from the individual processes is continuously exchanged, enabling dynamic adaptation of the operating parameters.
Figure 10.
Software base structure diagram.
The business optimization module is responsible for collecting market information and analyzing it. On the basis of available data on attainable revenues and production costs, the module decides whether computing processes should be started and at what intensity. It also takes into account feedback from the remaining parts of the system. Information on the state of the heat recovery process and of the computing device is treated as potential constraints and is included in the assessment of the system’s economic viability.
The heat recovery process module supervises the entire hardware layer. It receives orders from the business optimization process, stores and analyzes information on the physical state of the system, and aggregates data received from the computing device itself. On this basis, the module decides whether, and to what extent, it is able to execute the order from the business optimization module, and then forwards the request to the computing device in the heat generation process module. The heat recovery process algorithm also analyzes data received from the computing device and, on that basis, determines the intensity of the heat recovery process.
The main decision loop of the business optimization algorithm, presented in Figure 11, is responsible for calculating system efficiency to maximize profitability. Following initialization, the program continuously acquires updated input data. A cost-effectiveness and efficiency calculation is then performed for the current heat generation process. In the subsequent step, the algorithm compares the setpoint with the actual state of the system. If the verification indicates that a correction of the operating parameters is required, the algorithm does not immediately issue a control command. A hardware–software interlock is implemented in the form of a protection status readout, which evaluates the condition of both the heat generation and heat recovery processes. Only after confirming that both processes are stable is a parameter change request generated and passed to the lower executive layer. In the event of instability or the absence of any required correction, the algorithm returns to the beginning of the loop, thereby preventing error propagation within the system.
Figure 11.
Business optimization: algorithm diagram.
The subordinate control loop, the main part of the heat recovery process, presented in Figure 12, acts as the primary safety mechanism against fault conditions. Following the readout of signals from the field sensors, the system verifies the validity of the machine state. Should any anomalies be detected, the algorithm proceeds to a sequential fault diagnostic routine. The first condition to be verified is the risk of overheating. Detection of this fault triggers a temperature level correction procedure and sets a protection system fault flag, after which a new input readout cycle is forced. If the temperature is within the nominal range, the coolant level is verified, and in the event of a fault, an analogous correction procedure is initiated.
Figure 12.
Heat recovery-process control algorithm.
When the physical state of the system is confirmed to be correct, i.e., no overheating is present and the fluid level is nominal, the protection flags are cleared. In this state, the algorithm is ready to accept and propagate requests from the superordinate optimization module, thereby completing a single loop cycle. This architecture ensures that hardware safety takes precedence over efficiency optimization directives.
The decision rules of both layers can be stated explicitly. The business optimization layer evaluates the profitability of the heat generation process as
where is the revenue from the computing task per unit time, and are the unit prices of electricity and of the heat replaced by the recovered heat, is the heat recovery efficiency, and P is the electrical power of the device. A change in the computing intensity is requested only if it increases and no fault flag is set. In the heat recovery layer (Figure 12), the oil temperature and the oil level in each tank are sampled at intervals of s, and the solenoid valves of tank i and the oil pump are switched according to a two-position law with hysteresis
where denotes open valves and k is the sampling instant. The default setpoints, adjustable from the HMI panel, are °C and °C, which corresponds to the operating range of 60–70 °C. If °C, the valves are opened regardless of the hysteresis state, a load reduction is requested, and a fault flag is set. If the oil level falls below the low-level sensor , the tank is refilled from the oil main until the high-level sensor is reached.
The thermal dynamics relevant for the control were identified in an additional test with the S9 device (1.25 kW) in the configuration of the second test bench, in which the device is switched on at . The difference between the temperature of the immersed boards and that of the water followed a first-order response, which can be described by
with K/W, min, and a dead time shorter than 1 min, i.e., below the reading interval (root-mean-square error of the fit 0.8 K). After a step change of the thermal load, the temperature therefore settles within approximately min. Since and are much shorter than T, the regulation accuracy is determined mainly by the hysteresis band (±5 K around 65 °C), and the short sampling interval limits the overshoot beyond this band. The mechanical version provides proportional, self-acting control with a setpoint fixed on the thermostatic head, but without level monitoring, overheating protection, or load control. A side-by-side quantitative comparison of both control methods was not performed, as the two versions were installed in different buildings.
The final level of the protection system is controlling the computing device. When necessary, this software permits a reduction in computational load or a complete shutdown of the device in situations where the remaining protection systems have failed. This software has been supplied by an external vendor and does not constitute the subject of the present research.
A loss of oil circulation, caused by a failure of the impeller or the oil pump, results in a local temperature rise. In the electronic version, it is detected by the temperature sensors and handled by the overheating rule; in the mechanical version, overheating protection is provided by the computing devices themselves, which reduce their power and shut down when their internal temperature limit is exceeded. Sensor failure, which can occur only in the electronic version, is detected through a signal plausibility check and treated as a fault. Oil leakage is detected by the level sensors in the electronic version, whereas in the mechanical version, it can be identified via visual inspection through the sight glass; a significant loss of oil leads to overheating and, consequently, to device shutdown. For residential installations, placing the tank stack in a spill containment tray (drip pan) and equipping the system, particularly the mechanical version, with an independent emergency thermal cutoff switch and standard electrical protection are recommended as basic safety measures.
3. Laboratory Investigations
To prove the utility of the proposed solutions, it is necessary to analyze and examine several elements. The most important of these is the efficiency of the technology used. In order to obtain the necessary data, several experiments were conducted, each of which was progressively closer to real operating conditions. These studies provided information on the financial potential of heat recovery from electronic devices. This, in turn, enabled the estimation of the profitability of the technology, including its payback period.
These experiments verified the system’s compatibility with standard residential heating installations and provided data on material durability. Extended multi-week observations allowed us to identify weak links, modify the design, and ultimately ensure the trouble-free, long-term operation of the recovery units.
The temperature of the heat-receiving medium was measured with digital thermometers with a stainless steel probe (accuracy ±1 °C, resolution °C), and the electrical energy supplied to the device was measured with a plug-in energy meter (accuracy ±2% of the reading). These are typical accuracies declared for this class of simple and widely available instruments, consistent with the low-cost character of the system. Since and were measured with the same probe, its offset error cancels out, and the uncertainty of the temperature rise is estimated at ± . The temperatures were read at intervals of approximately 15–25 min. The recovered energy is determined calorimetrically from the temperature rise of a known mass of the medium (Equation (6)). This method requires neither the oil and water flow rates nor the inlet and outlet temperatures of the heat exchangers, which were therefore not measured, and it avoids the considerable uncertainty of flow measurement for viscous oil at low flow rates. Each test started with the device switched off and the oil and water at the initial temperatures given in Table 3. The relative uncertainty of the efficiency is estimated according to the standard propagation of uncertainty method [29] as
assuming of 2–3% (filling volume) and of 0.5% for water and 5% for paraffin oil (spread of literature data). The resulting uncertainties, given in Table 3, do not exceed ±4 percentage points and do not affect the conclusions of the study. Each test bench was evaluated five times under the same conditions, and the reported efficiencies are the mean values of these runs.
Table 3.
Parameters of the test benches.
3.1. The First Test Bench: Uninsulated Oil Heating Test Bench
In all test benches, the heat recovery efficiency was evaluated from the energy balance over the test duration t. The electrical energy supplied to the computing device was measured with an electrical energy meter. Since the power P drawn by the device was constant during the tests (Figure 16), the supplied energy is equal to
The recovered thermal energy is determined from the temperature rise of the heat-receiving medium
where m and are the mass and specific heat of the medium, and and are its temperatures at the beginning and at the end of the test. In the first test bench, the heat-receiving medium is the paraffin oil (, 8 , ). In the second and third test benches, it is the water in the 19 and 100 tanks, respectively ( and 100 , ). The heat curve in Figure 16 is obtained by evaluating Equation (6) at successive measurement instants. The heat recovery efficiency is defined as
and the difference
comprises the heat losses to the environment, e.g., through the tank walls and pipelines, as well as the conversion losses of the power supplies located outside the tank. In the second and third test benches, also includes the heat accumulated in the oil and the tank structure at the end of the test; hence, the reported efficiency is a conservative estimate. The energy consumed by the oil circulation pump is not included in . If an assumed auxiliary power consumption of 60 W per tank for oil circulation were included in , the efficiencies of the second and third test benches would decrease to 58% and 71%, respectively; the first test bench relied on natural convection and had no auxiliary power demand. The effect is significant for the low-power device on the second test bench, whereas for the 1.25 kW device it amounts to approximately 3 percentage points. The values of , , and for all test benches are given in Table 4.
Table 4.
Test results for three versions of the test benches.
The first test was primarily aimed at determining the efficiency of heat recovery. For this purpose, a computing device called a cryptocurrency miner, model S1, was immersed in paraffin oil. Figure 13 shows the first test bench. It consisted of a polyethylene tank with the device placed inside along with the oil. The power supplies were connected to an electrical energy consumption meter. A display and a temperature probe were placed in the tank to measure the temperature. During the experiment, the operating time was measured. These parameters made it possible to determine the amount of thermal energy delivered to the oil and compare this result to the energy supplied.
Figure 13.
The first test bench.
3.2. The Second Test Bench: Test Bench for Heating 19 L of Water
The second research test bench was more advanced. Its purpose was not only to further test heat recovery, but also to bring laboratory conditions closer to the target operating conditions. It is presented in Figure 14. The first tank contained, as before, paraffin oil with a cryptocurrency miner immersed in it, this time an S3 model. The second tank contained 19 L of water together with a heat exchanger. The water tank was additionally insulated with 5 mm thick neoprene foam. Between the tanks there was a pipeline and a pump, which were responsible for transporting the hot paraffin oil to the heat exchanger, which then transferred the stored energy to the water. The pump used in the experiment was a common 12 V model used for pumping diesel fuel.
Figure 14.
The second test bench.
3.3. The Third Test Bench: Test Bench for Heating 100 L of Water
The final test bench, presented in Figure 15, was constructed to closely resemble the target application. It was also designed to enable long-term reliability testing of the system without the need for constant supervision. The tank in which the Antminer S9 cryptocurrency miner was placed was made of stainless steel and insulated with 20 mm thick neoprene foam. This tank was then connected to a 100 L boiler intended for preparing DHW. This boiler was equipped with an internal copper coil with a surface area of 0.5 , serving as a heat exchanger between the oil and water. This tank was connected to the domestic hot water installation of a single-family building, between the municipal cold water supply and the previously used 150 L DHW tank. The function of the test bench was to preheat the water before its further heating by a gas boiler in the larger tank.
Figure 15.
The third test bench.
Connecting the system to a real installation ensured continuous consumption of heated water and reduced the risk of overheating the computing device. However, to ensure the reliability of the system without supervision, tees with ball solenoid valves were installed on the pipeline connecting the tank and the boiler. A heat exchanger with fans was connected to these tees, which, in the absence of hot water consumption, dissipated heat to the environment. The emergency cooling system was controlled by a thermostat with a probe placed in the oil. In case of failure of the heat reception system, the entire setup was protected by a second emergency thermostat. Its task was to cut off power to the entire test bench in case of reaching a critical temperature, in this case 80 °C. The results of one of the conducted tests are presented in Figure 16. At time 0, the computing device, operating at a power of 1250 W, was switched on and operated for approximately 120 min. The operation of the device resulted in a systematic increase in the amount of heat accumulated in the tank. During the test, of heat was transferred to the water in the 100 tank. The obtained data were used to calculate the heat recovery efficiency.
Figure 16.
Collected data for the third test bench.
After completing the efficiency tests, this test bench was used for several more weeks. Further tests were conducted on it regarding the durability of the materials used as well as the stability of the process and its safety.
3.4. Discussion of Laboratory Investigations
The calculated efficiency results obtained for the three compared versions of the test bench are detailed in Table 4. The data demonstrate a progressive improvement in heat recovery efficiency, rising from 54% in the basic uninsulated setup to 74% in the fully integrated 100 L boiler system. Achieving over 50% heat recovery even in the simplest configuration confirms the system’s practical viability for residential applications.
The high recovery efficiency can be attributed primarily to the direct immersion of the heat-generating components in the cooling liquid, which provides an efficient heat transfer path and minimizes thermal resistance. Notably, the three experimental setups operated under different boundary conditions (e.g., varying thermal loads, system volumes, and insulation levels). This intentional variation reflects the progressive evolution of the prototype from a bare-bones laboratory concept to a fully integrated, real-world application. While this precludes a strict parametric comparison of isolated design variables, the consistent increase in efficiency clearly demonstrates that scaling up the system, increasing the thermal load, and applying proper insulation successfully minimize relative heat losses to the environment.
The laboratory phase also provided essential data on operational safety and material durability. In addition to information on achievable efficiencies, data on material durability were collected. All plastic and rubber elements that underwent degradation were redesigned. Electrical cables, whose insulation completely disintegrated after several weeks, were also remade using materials resistant to hot oil. Errors made in designing the tank seals were also identified and corrected. As a result, the basic design underwent modification and was adapted for further long-term testing.
The observed degradation concerned components that are not intended for continuous contact with hot oil. The insulation of standard electrical cables, typically made of plasticized Polyvinyl Chloride (PVC), becomes brittle as the plasticizers are extracted by the oil, while general-purpose rubbers swell, which also caused the failure of the circulation fans described in Section 4.3. Such material compatibility issues are known from immersion cooling of IT equipment. In the final design, they were eliminated by using only materials compatible with mineral oil: polypropylene and stainless steel tanks, a stainless steel coil, Nitrile Rubber (NBR) seals, cables with oil-resistant insulation, and neodymium magnets housed in a 3D-printed cage. After these modifications, no recurrence of the failures was observed during the subsequent long-term tests, which, including the field installations described in Section 4, lasted approximately two to three years. The operating temperature of the oil (60–70 °C) is far below its flash point, which for mineral insulating oils is at least 135 °C, and below the temperatures typical of power transformers, in which such oils operate for many years. Maintenance is therefore limited mainly to periodic inspection of the oil level, using the level sensors or a sight glass, and of the oil condition, which can be assessed according to the guidelines established for transformer oils.
Ease of integration with existing heating systems is the last element examined. The third test bench demonstrated how easy it is to connect the designed recovery system to existing hot water heating installations. A DHW tank with two coils is sufficient to be able to heat water both using a conventional heat source and using the proposed system. Based on the accumulated experience, a system was therefore designed in which the target system will be connected to both the hot water heating system and the building’s central heating system. This is achieved by connecting the device to the return line of the heating circuit from the heat exchangers in the rooms and before entering the heating device such as a gas boiler. As a result, the energy that would mainly heat the room in which the computing devices are located is distributed throughout the building or delivered in the form of hot water.
4. Investigations Under Real-World Conditions
Both of the designed heat recovery solutions were constructed and installed in the mechanical rooms of actual buildings. They were connected according to the same schematic, presented in Figure 1. In both cases, the tanks were installed on the return line of the primary heating bus, upstream of the heating device inlet. Two configurations were tested. The electronically controlled version, with a stack of three and later four tanks with a total power of 5.4 kW, was operated in a single-family house, and all long-term measurements of electricity and gas consumption refer to this installation. The mechanically controlled version, comprising four stacks of five tanks (20 tanks in total, approximately 20 kW), was operated in an office building in Warsaw (Section 4.2). This installation served to verify the operational reliability of the mechanical version at a larger scale, and its energy performance was not measured.
4.1. Electronically Controlled Version
For long-term testing under real-world conditions, a stack of 3 and 4 tanks was connected to the heating bus of a two-storey single-family house with a total floor area of approximately 300 . The building was constructed in the 1960s and has never undergone any thermal modernization. The total electrical power of the devices submerged in the tanks amounted to 5.4 kW. The equipment operated continuously in 24/7 mode, with brief interruptions for occasional corrections and modifications. The test stand is shown in Figure 17. Three tanks are arranged in a vertical stack. The tanks are hydraulically interconnected by a manifold leading to a plate heat exchanger located behind them. Adjacent to the tanks is the controller, to which all temperature and liquid level sensors are connected. This controller manages the entire process and ensures its safe operation. Behind the test stand, the existing building installation is visible, consisting of a 22 kW gas boiler and two domestic hot water vessels with a combined volume of 250 L.
Figure 17.
Long-term real-world investigation of electronically controlled version.
The test stand was in operation for over 12 months, during which it satisfied 100% of the occupants’ domestic hot water demand and approximately half of the space heating demand. During the summer period, the surplus heat not utilized for domestic hot water heating had to be redirected. For this purpose, a 17 swimming pool was installed to absorb the excess recovered energy. As a result, the pool water temperature was maintained throughout summer in the range of 25 to 32 degrees Celsius, depending on pool usage patterns and prevailing external conditions.
Table 5 presents the results of a statistical analysis based on average annual gas consumption recorded during system operation and over the three preceding years. The thermodynamic heat recovery efficiency (evaluated in Section 3) should be distinguished from the building-level energy substitution. The 54% value reported in Table 5 represents the empirical reduction in historical natural gas consumption rather than the direct thermodynamic efficiency of the tanks. Nevertheless, this building-level gas reduction confirms that the high thermal efficiencies observed in the laboratory successfully translate into tangible real-world heating energy substitution.
Table 5.
Energy consumption and gas consumption reduction.
The reduction in natural gas consumption given in Table 5 is calculated as
where is the average annual gas consumption in the reference period 2014–2016 (without WHR) and is the gas consumption in 2017 (with WHR). For the data in Table 5, . The electricity consumption of the building is given for reference only (its increase in 2017 reflects the energy supplied to the computing devices) and is not used in Equation (9). Unlike the efficiency defined in Equation (7), also depends on factors not related to the WHR system, such as outdoor weather conditions and domestic hot water demand.
The WHR system operated in 2017. During the entire analyzed period, the building was occupied by four residents. The annual Heating Degree Days (HDDs), calculated according to the Eurostat method (base temperature 18 °C, heating threshold 15 °C) from daily temperatures at the nearby Warszawa-Okęcie weather station, averaged 3093 in 2014–2016 (range: 2982–3149) compared to 3189 in 2017, yielding an HDD-normalized reduction in gas consumption of approximately 55%. The DHW and space-heating coverage values are estimates, as the heat delivered to the individual circuits was not metered. The 100% DHW coverage reflects the fact that in 2017 the DHW tank was heated exclusively by the WHR system, whereas the space-heating coverage of approximately 50% was estimated from the HDD-normalized gas consumption data after subtracting the typical DHW demand of a four-person household (approximately 4–5 MWh per year) from both the reference consumption and the gas savings.
To evaluate the economic viability of the system quantitatively, an incremental (retrofit) cost–benefit methodology is adopted. Under this system boundary, the computing hardware and its primary electrical energy consumption are attributed to the revenue-generating computational task (assumed to be self-funding), whereas only the Capital Expenditures () and annual Operating Expenditures () specifically required to recover and transfer waste heat are charged to the WHR installation.
Table 6 summarizes the complete , , net annual benefit, and simple payback period () for both four-tank variants. The comprises the tank assemblies with hydraulic fittings, electrical wiring, and magnetic impellers; the electronic control unit (electronic variant only); and the initial fill of dielectric oil plus on-site plumbing integration (excluding tank assembly labor for the hand-built prototypes). The annual consists of two components: (i) auxiliary electricity consumption priced at EUR/kWh, covering continuous operation of four oil impellers (, 2102 kWh/year, i.e., 294 EUR/year) plus the average power draw of the oil circulation pump and control electronics (assumed at 40 average, or 350 kWh/year, for the electronic variant, whereas the mechanical variant utilizes the building’s existing heating circulation pump and incurs no additional auxiliary electrical demand); and (ii) routine maintenance and consumables (periodic oil inspection/top-up, NBR gasket replacement, and occasional impeller servicing), conservatively estimated at 3% of the prototype per year. Note that charging 100% of the impeller electricity draw to is a conservative assumption, as it does not credit the avoided power consumption of the removed stock air-cooling fans of the immersed computing devices (typically 40–60 W per unit).
Table 6.
Quantitative CAPEX, OPEX, annual benefit, and simple payback period (SPB) breakdown for both four-tank WHR variants (prototype CAPEX based on 2018 gross prices at 4.26 PLN/EUR, excluding tank assembly labor; EUR/kWh, EUR/kWh).
With the measured annual natural gas savings of kWh and a baseline residential gas price of EUR/kWh, the gross annual heating benefit is EUR/year. Accounting for operating expenses, the net annual benefit and simple payback period are defined as
These baseline assumptions yield years for the electronically controlled prototype (for which was measured). The mechanically controlled prototype achieves years under the assumption of equivalent thermal recovery efficiency. Series production can reduce by a conservative 25% through bulk procurement and standardized manufacturing while keeping unchanged. This lowers the payback period to years for the electronic version and year for the mechanical version. Energy price sensitivity was evaluated by varying by (0.07–0.13 EUR/kWh). This variation shifts the prototype to 1.3–3.0 years for the electronic version and 1.0–2.1 years for the mechanical version. The corresponding ranges for series production are 1.0–2.3 years and 0.7–1.6 years. Operating the computing devices solely to generate heat without computational revenue is not economically viable. The additional 38 MWh of electricity would cost approximately 5400 EUR/year at EUR/kWh. This expense exceeds the gross annual gas savings by a factor of more than 2.5.
As in the economic analysis, the environmental balance assumes that computing is performed regardless of the heat demand, e.g., for revenue. The reference scenario therefore comprises the same computing workload and gas heating of the building, whereas in the WHR scenario, the heat released by the computing devices replaces part of the gas. The electricity consumed by the computing devices is the same in both scenarios and cancels out in the balance, irrespective of the grid emission factor. The net effect of the WHR system is thus the avoided combustion of 20,595 of natural gas per year, which corresponds to approximately 4 of per year for the default emission factor of / (approximately /).
Table 7 lists the components required to build a single tank of the mechanically controlled version and to connect it to an existing heating installation. Apart from the tank housing, all of them are standard plumbing, electrical, and PC parts or simple 3D-printed elements, which are inexpensive and readily available. The system does not require a heat pump or any other specialized equipment. The device mounting elements correspond to a GPU-based computing unit; for other computing devices, only this group of components changes. Component prices are not reported, as they vary considerably between suppliers and over time.
Table 7.
Components required to build a single tank of the mechanically controlled version and to connect it to the building’s heating installation.
The 5.4 kW continuous load, which translates to approximately 47 MWh of annual electricity consumption, represents a specific "prosumer" niche within the domestic market, such as enthusiasts engaged in cryptocurrency mining or distributed AI rendering. While this energy demand is significantly higher than that of an average household, it was deliberately selected for the case study to stress-test the system’s maximum capacity, reliability, and thermodynamic limits under continuous, heavy thermal loads. For a more typical residential user equipped with a high-end gaming PC, a workstation, or a home server (generating approximately 0.5 to 1.0 kW of waste heat), the proposed solution easily scales down to a single-tank configuration. While such a scaled-down setup would not cover the space heating demand of an entire building, a 1.0 kW heat source operating for 8 h a day yields 8 kWh of thermal energy. Accounting for the previously validated recovery efficiency (approximately 74%), this delivers nearly 6.0 kWh of recoverable heat, which is sufficient to substantially pre-heat a typical 100 L domestic hot water buffer, thereby providing tangible daily savings for standard households.
4.2. Mechanically Controlled Version
The mechanical version was likewise implemented under real-world conditions; however, the scale of this installation was considerably larger than that of the electronic variant. The mechanical version was installed in the mechanical room of a medium-size office building, where it was connected to the entire building’s heating system. The building was heated by a gas-fired boiler. As in the case of the single-family house, the heat recovery system was integrated into the return line of the primary heating bus, upstream of the boiler inlet. The test system consisted of 4 stacks of 5 tanks each. One such stack is shown in Figure 7b. The total installed electrical power of the assembly amounted to approximately 20 kW. Throughout the entire testing period, the heat recovery system itself functioned reliably and without any issues. Testing of this installation was discontinued before quantitative measurements could be carried out; consequently, it served primarily to verify operational reliability, and no energy performance data were recorded.
4.3. Patented Low-Cost Oil-Circulation Solution
One of the principal challenges encountered during the development of the system was ensuring adequate circulation of the hot oil. The objective, however, was to identify a solution that is not only durable but also cost-effective. Among the least expensive and most readily available options were axial fans. Unfortunately, a recurring problem was that the fans seized upon contact with the hot oil. After several days of operation, the fans would begin to slow down and operate intermittently, before ceasing to rotate altogether within a further few days. Upon disassembly of several units, it was found that the permanent magnets on the rotor are encapsulated in a rubber matrix. These magnets, as a result of prolonged contact with the hot oil, would swell, begin to make contact with the stator, and consequently prevent the rotor from turning.
In seeking a solution to both issues, the concept emerged of replacing the rubber-encapsulated magnets with a material resistant to hot oil. If successful, this approach would allow the use of inexpensive PC-grade cooling fans which, following modification, would provide sufficient oil agitation. Evidence that the forced circulation intensity would be adequate was provided by tests conducted with fans of this type: up to the point at which the fans began to seize, the computing devices did not overheat and their temperature remained stable.
To ensure reliable fan operation when submerged in oil, it was decided to replace the rubber-encapsulated magnets with high-performance NdFeB permanent magnets [30]. These magnets are housed in a purpose-designed cage, fabricated using Fused Deposition Modeling (FDM) 3D printing technology [31]. The cage design is presented in Figure 18, while Figure 19 shows one of the physically produced and tested implementations.
Figure 18.
3D model of the neodymium magnet cage for the oil impeller.
Figure 19.
Oil impeller for hot oil immersion. (Left) the original rubber-encapsulated magnet. (Right) the oil-resistant replacement version, with the cage and neodymium magnets visible.
To determine the appropriate number of magnets, their dimensions, and their spacing, a series of tests was conducted. The objective was to identify first a functional, and subsequently an optimal, configuration. The entire process was carried out using an iterative empirical approach. This process yielded a magnet and cage configuration that transformed a specific fan assembly into a durable, reliable, and highly cost-effective oil agitator. This agitator was employed throughout the long-term tests described in Section 4.
Figure 19, left, shows a fan rotor with the oil-swollen magnet visible inside.
The final oil agitation system consists of a mm fan powered at 12 V with a current draw of 5 A. The rotational speed of the fan in air is 7500 rpm, whereas when submerged in oil at a temperature of approximately 65 degrees Celsius, the rotational speed is reduced to approximately 90 rpm. The rotational speed is highly variable and dependent on the oil temperature. The rubber-encapsulated magnet is removed from each fan and replaced with a cage comprising four sections of four magnets each, as shown in Figure 18. The cage houses 16 neodymium magnets with dimensions of mm, arranged such that within each section all magnets are oriented with their magnetic fields aligned in the same direction. Fans constructed in this manner operated reliably throughout the entire testing period, and the complete solution was granted a patent (No. P1231PL00).
The electrical power consumption of a single modified fan is 60 W (12 V at 5 A). While this parasitic load is relatively small compared to the heat generated by the computing device (typically 1.25–1.5 kW), it becomes significant in large multi-tank configurations. However, since the fan is fully submerged, all electrical energy consumed by its motor is ultimately dissipated as heat directly into the oil, thereby contributing to the total recovered thermal energy. Nevertheless, optimizing the oil-circulation system to reduce this auxiliary power consumption constitutes an important area for future research.
4.4. System Scalability
While the presented case studies focus on single-family and office environments, the modular architecture of the proposed WHR system supports scaling from a single residential unit to multi-apartment buildings. In multi-unit configurations, the primary heating main of the WHR stacks connects to the building’s central domestic hot water buffer or a localized district heating substation. Due to the compact vertical stacking of the tanks, the installation fits into shared technical rooms or basements alongside existing Heating, Ventilation, and Air Conditioning (HVAC) infrastructure. The MODBUS-based architecture of the electronic control unit (Figure 8 and Figure 9) supports up to 20 tanks per master controller and enables integration with optional thermal energy meters on the shared bus. This capability allows building administrators or energy cooperatives to monitor per-module heat contribution and allocate thermal energy credits among residents.
Operational scalability at a multi-stack level was demonstrated by the mechanically controlled installation of 20 tanks in an office building (Section 4.2). Because individual tanks operate as independent modules connected in parallel to the return line of the heating circuit, scaling is constrained primarily by the building’s thermal demand rather than by hydraulic or control complexity. The decisive sizing limit occurs during summer when space heating is inactive and only DHW is required. Without an auxiliary heat-rejection sink such as a swimming pool or dry cooler, the continuous electrical load should not exceed , where is the minimum summer DHW thermal load and is the heat recovery efficiency.
Table 8 quantifies three representative scaling scenarios derived from the validated 74% thermal recovery efficiency and the baseline household DHW demand of 4–5 MWh/year per four-person household (Section 4.1). At the micro-scale, a single tank housing a 1.0 kW workstation operated for 8 h daily recovers approximately 5.9 kWh/day (2.2 MWh/year), covering roughly half of a household’s annual DHW demand. At the single-family house scale, the field-tested four-tank stack (5.4 kW) delivers approximately 4.0 kW of thermal power and replaced 20.6 MWh/year of natural gas, while requiring seasonal heat rejection for summer surplus. Scaling up to the 20-tank configuration (20 kW electrical load) yields approximately 14.8 kW of continuous thermal output (355 kWh/day or 130 MWh/year). Based on the 4–5 MWh/year household DHW benchmark, this output matches the year-round base-load DHW demand of approximately 26–32 four-person apartments without requiring summer heat dumping. For a nominal water temperature rise of 10 K across the heat exchangers, transferring 14.8 kW requires a primary-loop water flow rate of approximately 1.3 /h, which remains well within the operating range of standard building circulation pumps and DN25–DN32 piping.
Table 8.
Quantitative scaling scenarios for the proposed WHR system based on a 74% thermal recovery efficiency and a residential DHW demand of 4–5 MWh/year per four-person household.
5. Conclusions
This paper presents an innovative, low-cost system for waste heat recovery from home computing machines. This proof-of-concept study adapts industrial-scale immersion cooling for domestic waste heat recovery. The manuscript provides a quantitative analysis and technical characterization of the system, demonstrating its evolution from laboratory prototypes to fully functional field deployments. Unlike conventional WHR technologies aimed at large data centers, the proposed solution targets the distributed network of individual devices present in nearly every household. Its principal features are architectural simplicity, low manufacturing cost, and ease of integration with existing residential heating infrastructure.
The transition from theoretical modeling to real-world application confirmed the technology’s practical applicability, economic viability, and environmental benefits in the form of avoided emissions from natural gas combustion. Laboratory investigations confirmed a high thermodynamic heat recovery efficiency ranging from 54% to 74%. When tested continuously for over a year under real residential conditions, the implemented WHR system effectively satisfied 100% of the domestic hot water demand in a single-family house scenario. This real-world deployment yielded an overall 54% reduction in historical space and water heating requirements, successfully substituting over 20,000 kW h of natural gas annually. Extrapolating from these measured energy savings, the preliminary economic assessment projects a short return on investment of under two years. These empirical findings indicate that the system can achieve a reduction in emissions from residential heating of approximately 4 t per year. Furthermore, the bottleneck of continuous, low-cost oil agitation was successfully resolved by developing a patented, oil-resistant magnetic impeller cage, ensuring long-term reliability. By utilizing waste heat from energy-intensive tasks such as cryptocurrency mining, the system offers a practical step toward improving the energy efficiency of distributed computational nodes at the micro-scale. While the experimental validation relied on cryptocurrency miners to serve as a continuous, high-power stress test, the system’s modularity ensures it easily scales down to recover heat from standard high-performance household electronics with intermittent workloads, such as gaming PCs or home workstations.
Future research should address several areas to enable mass-market adoption. Key technical priorities include improving heat transfer efficiency and utilizing recovered energy for absorption cooling. In addition, long-term metered trials of multi-stack installations in multi-apartment and commercial buildings are needed to empirically validate the projected scaling scenarios. Extended safety testing with hot paraffin oil is also required to confirm material durability in commercial environments. Finally, future work should broaden hardware compatibility to devices such as AI-rendering GPUs and evaluate thermodynamic limits within clustered residential micro-grids.
Author Contributions
Conceptualization, M.Z. and M.Ł.; methodology, M.Z. and M.Ł.; software, M.Z.; validation, M.Z.; formal analysis, M.Z.; investigation, M.Z.; resources, M.Z. and M.Ł.; data curation, M.Z.; writing—original draft preparation, M.Z. and M.Ł.; writing—review and editing, M.Z. and M.Ł.; visualization, M.Z.; supervision, M.Ł.; project administration, M.Ł. All authors have read and agreed to the published version of the manuscript.
Funding
This research received no external funding.
Institutional Review Board Statement
Not applicable.
Informed Consent Statement
Not applicable.
Data Availability Statement
Dataset available on request from the authors.
Conflicts of Interest
The authors declare no conflicts of interest.
Abbreviations
The following abbreviations are used in this manuscript:
| AI | Artificial Intelligence |
| CAPEX | Capital Expenditures |
| DHW | Domestic Hot Water |
| DWHR | Drain Water Heat Recovery |
| FDM | Fused Deposition Modeling |
| GPU | Graphics Processing Unit |
| HDDs | Heating Degree Days |
| HMI | Human–Machine Interface |
| HVAC | Heating, Ventilation, and Air Conditioning |
| I/O | Input/Output |
| IoT | Internet of Things |
| IT | Information Technology |
| LED | Light-Emitting Diode |
| MODBUS | MODBUS (serial communications protocol) |
| NBR | Nitrile Rubber |
| NdFeB | Neodymium Iron Boron |
| OPEX | Operating Expenditures |
| ORC | Organic Rankine Cycle |
| PC | Personal Computer |
| PCIe | Peripheral Component Interconnect Express |
| PP | Polypropylene |
| PVC | Polyvinyl Chloride |
| SoC | System on a Chip |
| USART | Universal Synchronous and Asynchronous Receiver–Transmitter |
| WAN | Wide Area Network |
| WHR | Waste Heat Recovery |
References
- Jouhara, H.; Khordehgah, N.; Almahmoud, S.; Delpech, B.; Chauhan, A.; Tassou, S.A. Waste heat recovery technologies and applications. Therm. Sci. Eng. Prog. 2018, 6, 268–289. [Google Scholar] [CrossRef] [Scilit]
- Ononogbo, C.; Nwosu, E.; Nwakuba, N.; Nwaji, G.; Nwufo, O.; Chukwuezie, O.; Chukwu, M.; Anyanwu, E. Opportunities of waste heat recovery from various sources: Review of technologies and implementation. Heliyon 2023, 9, e13590. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- Pili, R.; Martínez, L.G.; Wieland, C.; Spliethoff, H. Techno-economic potential of waste heat recovery from German energy-intensive industry with Organic Rankine Cycle technology. Renew. Sustain. Energy Rev. 2020, 134, 110324. [Google Scholar] [CrossRef] [Scilit]
- de Vries, A. The growing energy footprint of artificial intelligence. Joule 2023, 7, 2191–2194. [Google Scholar] [CrossRef] [Scilit]
- Buyya, R.; Dastjerdi, A.V. Internet of Things: Principles and Paradigms; Elsevier: Amsterdam, The Netherlands, 2016. [Google Scholar]
- Farhat, O.; Faraj, J.; Hachem, F.; Castelain, C.; Khaled, M. A recent review on waste heat recovery methodologies and applications: Comprehensive review, critical analysis and potential recommendations. Clean. Eng. Technol. 2022, 6, 100387. [Google Scholar] [CrossRef] [Scilit]
- Wehbi, Z.; Taher, R.; Faraj, J.; Lemenand, T.; Mortazavi, M.; Khaled, M. Waste Water Heat Recovery Systems types and applications: Comprehensive review, critical analysis, and potential recommendations. Energy Rep. 2023, 9, 16–33. [Google Scholar] [CrossRef] [Scilit]
- Wang, N.; Guo, Y.; Huang, C.; Shao, S. Advances in direct liquid cooling technology and waste heat recovery for data center: A state-of-the-art review. J. Clean. Prod. 2024, 477, 143872. [Google Scholar] [CrossRef] [Scilit]
- Zhou, X.; Xin, Z.; Tang, W.; Sheng, K.; Wu, Z. Comparative study for waste heat recovery in immersion cooling data centers with district heating and organic Rankine cycle (ORC). Appl. Therm. Eng. 2024, 242, 122479. [Google Scholar] [CrossRef] [Scilit]
- Bergman, T.L.; Lavine, A.S.; Incropera, F.P.; DeWitt, D.P. Fundamentals of Heat and Mass Transfer, 7th ed.; John Wiley & Sons: Hoboken, NJ, USA, 2011. [Google Scholar]
- Shah, J.M.; Rizvi, S.H.I.; Kota, I.S.; Nagilla, S.R.; Thakkar, D.; Agonafer, D. Design Considerations Relating to Non-Thermal Aspects of Oil Immersion Cooling. In Proceedings of the ASME International Mechanical Engineering Congress and Exposition, Phoenix, AZ, USA, 11–17 November 2016; Volume 10, p. V010T13A054. [Google Scholar] [CrossRef] [Scilit]
- Tauveron, N.; Lhermet, G.; Payebien, B.; Caney, N.; Morin, F. An Experimental Study of an Autonomous Heat Removal System Based on an Organic Rankine Cycle for an Advanced Nuclear Power Plant. Energies 2024, 17, 5069. [Google Scholar] [CrossRef] [Scilit]
- T’Joen, C.; Park, Y.; Wang, Q.; Sommers, A.; Han, X.; Jacobi, A. A review on polymer heat exchangers for HVAC&R applications. Int. J. Refrig. 2009, 32, 763–779. [Google Scholar] [CrossRef] [Scilit]
- Dogkas, G.; Konstantaras, J.; Koukou, M.K.; Gr. Vrachopoulos, M.; Pagkalos, C.; Stathopoulos, V.N.; Pandis, P.K.; Lymperis, K.; Coelho, L.; Rebola, A. Development and experimental testing of a compact thermal energy storage tank using paraffin targeting domestic hot water production needs. Therm. Sci. Eng. Prog. 2020, 19, 100573. [Google Scholar] [CrossRef] [Scilit]
- Antal, M.; Cristea, A.A.; Pădurean, V.A.; Cioara, T.; Anghel, I.; Antal (Pop), C.; Salomie, I.; Saintherant, N. Heating Homes with Servers: Workload Scheduling for Heat Reuse in Distributed Data Centers. Sensors 2021, 21, 2879. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- Corigliano, O.; Algieri, A.; Fragiacomo, P. Turning Data Center Waste Heat into Energy: A Guide to Organic Rankine Cycle System Design and Performance Evaluation. Appl. Sci. 2024, 14, 6046. [Google Scholar] [CrossRef] [Scilit]
- Antal, M.; Cioara, T.; Anghel, I.; Gorzenski, R.; Januszewski, R.; Oleksiak, A.; Piatek, W.; Pop, C.; Salomie, I.; Szeliga, W. Reuse of Data Center Waste Heat in Nearby Neighborhoods: A Neural Networks-Based Prediction Model. Energies 2019, 12, 814. [Google Scholar] [CrossRef] [Scilit]
- Brydson, J.A. Plastics Materials, 7th ed.; Butterworth: London, UK, 1999. [Google Scholar]
- Eiland, R.; Fernandes, J.; Vallejo, M.; Agonafer, D.; Mulay, V. Flow Rate and Inlet Temperature Considerations for Direct Immersion of a Single Server in Mineral Oil. In Proceedings of the 14th IEEE Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), Orlando, FL, USA, 27–30 May 2014; pp. 706–714. [Google Scholar] [CrossRef] [Scilit]
- Microchip Technology Inc. ATmega164A/164PA/324A/324PA/644A/644PA/1284/1284P Datasheet, Rev. 40002070A. 2018. Available online: https://ww1.microchip.com/downloads/en/DeviceDoc/ATmega164A_PA-324A_PA-644A_PA-1284_P_Data-Sheet-40002070A.pdf (accessed on 3 September 2026).
- Modbus Organization, Inc. Modbus Application Protocol Specification V1.1b3. 2006. Available online: https://www.modbus.org/file/secure/modbusprotocolspecification.pdf (accessed on 3 September 2026).
- Arroyo-Valle, F.J.; Roger, S.; Saldana, J. Real-Time AI-Based Data Prioritization for MODBUS TCP Communication in IoT-Enabled LVDC Energy Systems. Electronics 2025, 14, 3681. [Google Scholar] [CrossRef] [Scilit]
- Espressif Systems. ESP32 Series Datasheet, Version 4.1. 2023. Available online: https://www.espressif.com/sites/default/files/documentation/esp32_datasheet_en.pdf (accessed on 3 September 2026).
- Serepas, F.; Papias, I.; Christakis, K.; Dimitropoulos, N.; Marinakis, V. Lightweight Embedded IoT Gateway for Smart Homes Based on an ESP32 Microcontroller. Computers 2025, 14, 391. [Google Scholar] [CrossRef] [Scilit]
- Zhang, T.; Huang, B.; Liu, X.; Fan, J.; Li, J.; Yue, Z.; Wang, Y. MCU Intelligent Upgrades: An Overview of AI-Enabled Low-Power Technologies. J. Low Power Electron. Appl. 2025, 15, 60. [Google Scholar] [CrossRef] [Scilit]
- Aghenta, L.O.; Iqbal, M.T. Low-Cost, Open Source IoT-Based SCADA System Design Using Thinger.IO and ESP32 Thing. Electronics 2019, 8, 822. [Google Scholar] [CrossRef] [Scilit]
- Mataloto, B.; Ferreira, J.C.; Cruz, N. LoBEMS—IoT for Building and Energy Management Systems. Electronics 2019, 8, 763. [Google Scholar] [CrossRef] [Scilit]
- Ogata, K. Modern Control Engineering, 5th ed.; Prentice Hall: Hoboken, NJ, USA, 2010. [Google Scholar]
- Holman, J.P. Experimental Methods for Engineers, 8th ed.; McGraw-Hill: New York, NY, USA, 2011. [Google Scholar]
- Gieras, J.F. Permanent Magnet Motor Technology: Design and Applications, 3rd ed.; CRC Press: Boca Raton, FL, USA, 2009. [Google Scholar] [CrossRef] [Scilit]
- Gibson, I.; Rosen, D.; Stucker, B.; Khorasani, M. Additive Manufacturing Technologies, 3rd ed.; Springer: Berlin/Heidelberg, Germany, 2021. [Google Scholar] [CrossRef] [Scilit]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2026 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.