Abstract
This paper presents the design, implementation, and preliminary experimental characterization of an IoT-enabled multi-sensor monitoring and control system integrated into a laboratory-scale biogas fermenter designed for dual-temperature operation (mesophilic: 35–40 °C; thermophilic: 50–60 °C). The platform acquires, time-aligns, and displays data streams from temperature (DS18B20), ultrasonic liquid-level (HC-SR04), and semiconductor gas (MQ2/MQ135) sensors within a distributed Master–Slave sensing and control architecture (ESP32/Arduino) and closes a PID temperature loop. The PID loop was tuned from experimentally identified first-order-plus-dead-time (FOPDT) process dynamics (Kr = 0.98 °C/%, L = 122 s, Tp = 5977 s). Closed-loop tests were performed with water as a thermal simulant at a single 37 °C setpoint (mesophilic range); thermophilic setpoints were not tested. After retuning from the Chien–Hrones–Reswick (CHR) values (KP = 28, KI = 0.005, KD = 350), the overshoot decreased from 2.9 °C to ≈0.6 °C and the DS18B20 reading settled within ±0.1 °C of the setpoint (setpoint-holding stability; the specified sensor accuracy is ±0.5 °C). A non-invasive ultrasonic communicating-vessels subsystem was tested with compressed air as a gas-volume surrogate, with a 10 mL volume-display resolution, while a cloud telemetry layer (15 s reporting interval) presents the multi-sensor data on a common time axis for remote monitoring and data export. The results demonstrate the operation of the hardware, control, and telemetry chain. The platform provides a basis for future validation and for systematic comparison of mesophilic versus thermophilic anaerobic digestion in laboratory-scale bioprocess monitoring.
1. Introduction
Anaerobic digestion (AD) has emerged as a cornerstone technology for renewable energy production and sustainable organic waste management, converting organic residues into methane-rich biogas while producing nutrient-dense digestate for agricultural applications [1]. The biological complexity underlying AD necessitates sophisticated research infrastructure capable of reproducing and investigating diverse organic substrates and operational conditions. Among the critical design considerations, temperature control fundamentally shapes microbial community structure, metabolic pathways, and gas quality [2,3].
Temperature significantly influences AD performance through three primary mechanisms: (1) reaction kinetics—higher temperatures accelerate hydrolysis and methanogenesis rates; (2) microbial community composition—thermophilic conditions selectively enrich Firmicutes and hydrogenotrophic methanogens while excluding temperature-sensitive acetoclastic methanogens; and (3) pathogen elimination—thermophilic digestion achieves 98.9–99.9% Escherichia coli reduction compared to mesophilic processes [4,5,6].
Thermophilic digestion has been reported to show superior methanogenic performance across diverse substrates. Studies on food waste AD revealed methane yields of 360–380 mL/g VS at 55 °C, representing 5.6–22.4% increases over mesophilic conditions (37 °C), with a remarkable 63% increase in methane production rates [4]. However, thermophilic systems exhibit greater sensitivity to environmental perturbations, including temperature fluctuations, organic overloading, and toxic compound introduction [7,8].
Despite these operational challenges, thermophilic digestion offers compelling advantages in methane production rates, substrate degradation kinetics, and pathogen reduction. The optimal temperature selection depends on substrate characteristics, treatment objectives, regulatory requirements, and economic context. Laboratory-scale fermenters capable of both mesophilic and thermophilic operation enable systematic investigation of these trade-offs, facilitating the development of advanced multi-stage digestion strategies and temperature-phased configurations [9,10].
While AD technology has advanced considerably, the research infrastructure for investigating temperature-dependent process dynamics remains limited. Most laboratory-scale systems operate at fixed temperatures, constraining comparative studies and mechanistic investigations. This paper addresses this gap by presenting the design and preliminary performance testing of a dual-temperature laboratory-scale biogas fermenter with integrated automation, which is intended to allow AD performance to be investigated across temperature regimes within a single experimental platform. Digestion experiments with real substrates are outside the scope of the present work.
Beyond anaerobic digestion research specifically, the broader field of intelligent sensors has advanced rapidly in recent years, combining embedded sensing, artificial intelligence, connectivity, and miniaturization to enable accurate, real-time data acquisition, signal processing, and decision-making across healthcare, environmental monitoring, agriculture, and industrial process control [11,12,13,14,15]. Bioprocess reactors such as anaerobic digesters are a natural application domain for such intelligent, multi-sensor architectures, since reliable process supervision requires the simultaneous acquisition and joint interpretation of thermal, volumetric, and gas-composition data together with networked (IoT) connectivity for remote decision support [16]. However, many reported laboratory-scale AD platforms rely on single-purpose instrumentation that tracks temperature or gas composition individually [17]. Recent low-cost IoT systems for biodigesters combine temperature and gas (MQ-type) sensing, in some cases with humidity or pressure measurement, with microcontroller-based logging or IoT platforms [18,19]. These systems are mainly monitoring-oriented and, to the best of the authors’ knowledge, do not combine closed-loop temperature control for two temperature ranges, non-invasive volumetric gas measurement, a local touch-screen HMI, and cloud logging in one laboratory unit. The contribution of this work is therefore the integration and preliminary characterization of such a platform (hardware, controller tuning procedure, and telemetry chain), and not a new data-fusion algorithm or digestion results. In this paper, “multi-sensor” refers to the joint acquisition, time alignment, and display of heterogeneous sensor streams (Section 2.6).
The objectives of this study are (i) to describe the design of the fermenter and its automation hardware; (ii) to identify the open-loop thermal dynamics, tune the PID controller, and test it at a 37 °C setpoint with water; (iii) to test the ultrasonic communicating-vessels volume measurement with compressed air; (iv) to verify the HMI and the ThingSpeak telemetry; (v) to examine, by simulation clearly labelled as such, how well the identified model reproduces the measured runs; and (vi) to state clearly which aspects (thermophilic control, real-substrate digestion, and gas-composition calibration) remain to be validated.
2. Materials and Methods
2.1. System Architecture and Functional Design
The laboratory-scale biogas fermenter was designed based on functional requirements derived from industrial AD installations operating under both mesophilic and thermophilic conditions. The system architecture comprises four interconnected subsystems (Figure 1 and Figure 2):
Figure 1.
Block diagram of the control and instrumentation architecture. The Master unit (ESP32-32U, Wi-Fi) reads the gas, air-quality, ultrasonic and two DS18B20 temperature sensors and drives the Peltier elements, fans, pump and solenoid valve through MOSFET/PWM modules. The Slave unit (Arduino Leonardo with TFT touch display) provides the HMI and communicates with the Master over a UART serial link (TX/RX; voltage-divider protection on the ESP32 RX line). The mixing motor is switched by a relay module from a separate 12 V/2 A supply (isolated circuit, common ground). All other circuits are powered from the ATX power supply (3.3, 5 and 12 V).
Figure 2.
Photograph of the assembled laboratory-scale fermenter: insulated 5 L bioreactor, communicating-vessels measuring column with the ultrasonic sensor, gas-conditioning vessel, ATX power supply, and the electronics enclosure with the touch-screen HMI.
- Bioreactor: A 5 L cylindrical vessel constructed from AISI 316L stainless steel (corrosion-resistant grade), featuring a level glass, ports for substrate introduction and digestate removal, and a copper serpentine heat exchanger integrated in the base.
- Heating System: A dual Peltier plate configuration (TEC1-12706) mounted on an aluminium heat exchanger with water-cooling blocks and processor radiators with active cooling fans. A diaphragm circulation pump circulates a glycol–water mixture (50:50) through the closed loop at 1.5–2 L/min.
- Mixing System: A DC motor (12 V, 2 A) with an elastic coupling and multi-level agitation blades, operating with a fully customizable on/off duty cycle to achieve proper homogenization without excessive energy consumption.
- Biogas Measurement System: A communicating-vessels arrangement with an ultrasonic distance sensor (HC-SR04, 2–400 cm range) monitoring liquid displacement. Biogas composition is monitored qualitatively using MQ2 (CH4-sensitive) and MQ135 (CO2-sensitive) semiconductor sensors after activated-carbon filtration for H2S removal (Section 2.5).
2.2. Automation and Control Hardware
The control system architecture follows a distributed Master–Slave topology with galvanic isolation between command and power circuits:
Master Unit (ESP32 microcontroller, dual-core Tensilica LX6):
WiFi/Bluetooth BLE connectivity for IoT integration;
Real-time PID control execution;
Sensor data acquisition via:
DS18B20 temperature sensors (±0.5 °C accuracy, −20 to 105 °C range; two probes: bioreactor and heating-agent supply) [20];
HC-SR04 ultrasonic distance sensor for level measurement [21];
MQ2 and MQ135 semiconductor gas sensors (indicative signals only; see Section 2.5);
PWM outputs for heating and cooling regulation;
Communication with the slave unit via a UART serial interface.
Slave Unit (Arduino Leonardo with ATmega32U4):
A 3.2” TFT resistive touch display (ILI9341);
HMI graphical interface with multi-page menus;
User input processing for setpoint selection and manual control;
Real-time data visualization.
Power and Actuation:
ATX power supply providing 5 V (20 A), 12 V (8 A), 3.3 V (10 A);
MOSFET-based PWM power amplifier modules for Peltier element control;
Relay modules for galvanically isolated mixing motor control;
Separate 12 V/2 A power supply for the mixing motor to minimize EMI.
2.3. Control Algorithm Development
The temperature control system implements a PID algorithm executing on the master unit with a 1 s sampling interval:
where e(t) is the error between the setpoint and the measured temperature, u(t) is the controller output (PWM duty cycle, %), and KP, KI, and KD are the proportional, integral, and derivative gains of the parallel (non-interacting) form implemented in the PID_v1 library.
PID parameters were determined using experimental open-loop identification. A step input perturbation (ΔU = 20%) was applied from thermal equilibrium (Section 2.4), and the system response was characterized as first-order plus dead time (FOPDT):
The Chien–Hrones–Reswick (CHR) tuning method [22,23], using the 0% overshoot rule for setpoint tracking, was applied:
For the PID_v1.h library implementation, gains were converted:
The PID_v1 library implements the parallel PID form with gains KP (% per °C), KI (% per °C·s), and KD (% · s per °C); it scales KI and KD internally by the sample time, which was 1 s, so that no further scaling is required. With the identified parameters , the CHR rules give KP = 0.6 × 5977/(0.98 × 122) = 30.0, Ti = 5977 s, and Td = 0.5 × 122 = 61 s, i.e., KI = 30.0/5977 = 5.0 × 10−3 and KD = 30.0 × 61 = 1.83 × 103. These calculated values are compared with the gains actually applied in the closed-loop tests in Section 3.2.
2.4. Experimental Procedure
Open-Loop Identification:
- The system stabilized at ambient temperature (16.8 °C);
- A step input applied: ΔU = 20% PWM duty cycle;
- The temperature response monitored at 1 s intervals;
- FOPDT parameters extracted from the response curve (the reported t63% = L + Tp is consistent with a two-point construction; the fit quality was not quantified).
Closed-Loop Validation:
Initial PID tuning: KP taken from the CHR equations; KI and KD set to starting values that differ from the direct CHR conversion;
- Step response to a setpoint of 37 °C (mesophilic), with water as the thermal simulant; no thermophilic setpoint was tested;
- Fine-tuning to eliminate overshoot while maintaining stability;
- Steady-state performance evaluation (maximum deviation of the DS18B20 reading from the setpoint).
Process Testing:
- •
- Thermal response characterization with a water substrate (water used as a thermal simulant; no substrate, inoculum, or biogas production);
- •
- Biogas volume measurement preliminary test using compressed-air injection as a gas-volume surrogate;
- •
- HMI functionality testing including all control pages;
- •
- IoT data transmission verification to the ThingSpeak platform (short logging sessions).
Replication: Each test condition (open-loop identification, initial and final closed-loop tuning, and air-injection test) is reported from a single recorded run. No replicates were performed, so run-to-run variability is not available.
2.5. Sensor Placement, Volume Calculation, and Calibration Status
Sensor placement. Two DS18B20 probes are used (Figure 1): one measures the bioreactor temperature, which is the controlled variable, and one measures the heating-agent (glycol–water) supply temperature (“Tur” channel in the dashboard). The exact immersion depth and radial position of the probes in the vessel are not reported here, so spatial temperature gradients are not characterized. The HC-SR04 is mounted above the free liquid surface of the transparent measuring column of the communicating-vessels arrangement and points vertically at the surface (Figure 2). The MQ2 and MQ135 sensors are located in the biogas line after the activated-carbon filter.
Volume calculation. The ultrasonic sensor measures the distance d(t) from its face to the liquid surface from the echo time te, d = c·te/2, where c ≈ 331.3 + 0.606·Tair m/s is the speed of sound in air (Tair in °C). Gas entering the arrangement displaces liquid, so the surface moves by Δh(t) = |d0 − d(t)|, with d0 the reference distance at the start of a measurement. Neglecting the small hydrostatic pressure change and gas solubility, the displaced liquid volume equals the gas volume:
where A is the internal cross-section of the measuring column. Measuring-column geometry. The measuring column of the communicating-vessels arrangement has a measured internal diameter D = 5.0 cm, which gives an internal cross-sectional area A = πD2/4 ≈ 19.6 cm2. One millimetre of surface displacement therefore corresponds to A × 0.1 cm ≈ 2.0 mL. Resolution and error sources. The smallest displayed volume step is ΔVmin = A·δh, where δh is the distance resolution of the sensor. With the nominal 3 mm ranging accuracy of the HC-SR04 [24], a 10 mL step corresponds to A ≈ 10 cm3/0.3 cm ≈ 33 cm2; larger cross-sections give coarser and smaller ones finer steps. A 10 mL resolution is consistent with the sensor specification only if A ≲ 33 cm2. The 10 mL value is therefore a resolution (the smallest displayed step), not a measurement accuracy. For the measured A, the 3 mm distance resolution of the sensor corresponds to a minimum volume step of A·δh ≈ 19.6 cm2 × 0.3 cm ≈ 5.9 mL. The displayed step of 10 mL (≈5.1 mm of surface displacement) is therefore coarser than the sensor-limited step, and the condition A ≲ 33 cm2 (D ≲ 6.5 cm for a cylindrical column) is satisfied. The area A was obtained from the measured diameter and was not verified against a reference volume (see below). Further error sources are the dependence of the speed of sound on air temperature (≈0.18% of the measured distance per °C if uncompensated; whether compensation was applied is not stated), echoes from the column walls, meniscus and surface ripples, and gas solubility in the displaced liquid.
Calibration and validation status. (i) Volume: no documented reference-volume calibration (reference device, volume steps, replicates, regression statistics, residuals) is available for this study; the subsystem is therefore described as a functional test with a display resolution, and no accuracy or linearity figure is claimed. (ii) Temperature: the reported temperatures are DS18B20 readings; no comparison with a reference thermometer is reported. (iii) Gas sensors: no calibration curves with reference CH4/CO2 gas mixtures, selectivity tests, or uncertainty estimates were obtained in this study; the MQ2 and MQ135 outputs are therefore treated as indicative relative signals (Section 3.4).
2.6. Data Acquisition, Time Alignment, and Scope of Sensor Fusion
The platform’s sensing layer combines three heterogeneous sensor streams (Table 1 and Figure 3). Thermal data from the DS18B20 probes feed the digital PID control loop for closed-loop temperature regulation (Section 2.3); ultrasonic distance data from the HC-SR04 sensor are converted into liquid height and, via the communicating-vessels geometry, into cumulative biogas volume (Section 2.5), while also triggering the automated purge cycle when a maximum-level threshold is reached; and semiconductor gas sensors (MQ2, MQ135) provide indicative CH4- and CO2-related relative signals after H2S removal by activated-carbon filtration. All three streams are sampled by the ESP32 master unit in the same acquisition cycle, displayed locally through the touch-screen HMI, and transmitted together at 15 s intervals to the ThingSpeak cloud platform, which assigns the time stamp on receipt and shows the streams on a common time axis and as structured CSV records (Section 3.3). In this work, “multi-sensor data fusion” is therefore used in a limited, system-level sense: synchronized acquisition, time alignment, joint visualization, and simple rule-based interlocks (level threshold → purge; temperature → PID). No filtering- or state-estimation-based fusion algorithm, combined state estimate, cross-sensor validation rule, or anomaly-detection method was implemented or evaluated. Learning-aided filters such as KalmanNet [25] keep a model-based filter structure and use a neural network to supply the part of the filter that is only partially known. Work on learning-aided equivariant filtering on the special Euclidean group SE(n) for underwater navigation [26] illustrates the same principle for a state space with known geometric structure: the group structure of the model is retained, and the learned component corrects only the uncertain part. The transferability of that work to the present platform is, however, limited. The underwater-navigation formulation assumes pose and velocity states on a Lie group, driven by inertial measurements and aided by velocity or depth sensors, with symmetry properties that make the filter error equivariant. The states of the fermenter are scalar quantities in Euclidean space (temperature, gas volume, uncalibrated gas signals) and have no group symmetry, so the equivariance assumptions do not apply and the filters of [26] cannot be used directly. What transfers is the design principle of retaining a physical model and learning only its residual, for example, the heat stored in the glycol loop that the single-lag model of Section 3.6 does not reproduce, or the drift of metal-oxide gas sensors [27]. This would require replicated and labelled reference data (reference thermometer, reference gas analyser) that were not collected in this study, and no performance claim is made. Learning-aided filtering [25,26], deep-learning-based multi-sensor fusion [28], unsupervised information-quality evaluation of sensor streams [29], and machine-learning-based soft sensing [11] are therefore listed only as possible future extensions, particularly for compensating the cross-sensitivity and drift of metal-oxide gas sensors [27].
Table 1.
Overview of the sensor suite and signal roles.
Figure 3.
Data flow and scope of the multi-sensor architecture: implemented functions (solid boxes) and functions not implemented or evaluated in this study (dashed box).
3. Results and Discussion
3.1. Open-Loop System Identification
From the step-response experiment, the following FOPDT parameters were determined from a single open-loop step test (ΔU = 20% PWM duty cycle; Table 2):
Table 2.
FOPDT model parameters from the open-loop response (single step test; Kr in °C per % PWM).
The process exhibits significant dead time (122 s) and a large time constant (approximately 100 min), characteristic of thermal systems with substantial thermal mass. The dead time is attributed mainly to the transport delay of the glycol–water mixture between the Peltier unit and the bioreactor and to the thermal inertia between the heat exchanger and the probe.
The parameters are internally consistent: ΔY = 36.4 − 16.8 = 19.6 °C gives Kr = ΔY/ΔU = 19.6/20 = 0.98 °C per % PWM, and t63% = L + Tp = 122 + 5977 = 6099 s, at which the response should reach 16.8 + 0.632 × 19.6 ≈ 29.2 °C (Figure 4). The identification is based on a single step test; the uncertainty of Kr, L, and Tp was not quantified, and a FOPDT model is only an approximation of a thermal system with several heat capacities (heat exchanger, glycol loop, vessel wall, and water mass). The model was identified between 16.8 and 36.4 °C at a 20% duty cycle and may differ at higher temperatures. Section 3.6 shows that a single-lag model does not reproduce the measured closed-loop overshoot, so a higher-order model may be needed.
Figure 4.
FOPDT model response reconstructed from the identified parameters in Table 2 for a 20% step, T(t) = Tinitial + KrΔU[1 − exp(−(t − L)/Tp)] for t > L. The curve is computed from the model and is not measured data.
3.2. PID Controller Tuning and Closed-Loop Performance at 37 °C
The gains used in the first closed-loop run (KP = 30, KI = 0.06, KD = 250) brought the water to the 37 °C setpoint but produced a 2.9 °C overshoot (peak ≈ 40 °C; Figure 5a). Table 3 compares these gains with those calculated from the CHR equations (Section 2.3): KP coincides with the calculated value, whereas the applied KI was about 12 times larger and the applied KD only about 14% of the calculated value. The large integral gain accumulates error during the slow rise (≈2 h in Figure 5a) and is consistent with the observed overshoot. While the temperature was stable after the overshoot (reading within ±0.1 °C of the setpoint), the overshoot was unacceptable for biological systems where temperature shocks can induce metabolic imbalances and volatile fatty acid accumulation [7,8].
Figure 5.
Closed-loop temperature response of the water-filled bioreactor at a 37 °C setpoint: (a) initial gains (KP = 30, KI = 0.06, KD = 250), overshoot 2.9 °C; (b) final gains (KP = 28, KI = 0.005, KD = 350), overshoot ≈ 0.6 °C (peak 37.6 °C). The runs started from different temperatures (see Table 3). Legend labels are in Romanian: “Evoluție temperatura Bioreactor” = bioreactor temperature evolution; “Temperatura bioreactor” = bioreactor temperature. Vertical axis: temperature (°C); horizontal axis: clock time (hh:mm).
Table 3.
CHR-calculated and applied PID gains and closed-loop results at the 37 °C setpoint (start temperatures read from the plots in Figure 5).
With the final gains (KP = 28, KI = 0.005, KD = 350), the second run (Figure 5b) showed:
- •
- Overshoot: ≈0.6 °C (peak 37.6 °C).
- •
- Setpoint-holding stability: The DS18B20 reading returned to 37.0–37.1 °C only at the end of the plotted interval, so the ±0.1 °C band is supported by a short window; steady-state statistics over a longer record were not collected.
- •
- Control tested at 37 °C only (water, single run).
A decision was made to reduce KP to 28 to soften the initial transient response, to decrease KI to 0.005 (equal to the CHR-calculated value) to limit integral windup during the slow rise time, and to increase KD to 350 to provide anticipatory damping. KD remains far below the CHR-calculated value (≈1.8 × 103) because a derivative term amplifies measurement noise: for an unfiltered derivative on a DS18B20 at its default 12-bit resolution (0.0625 °C) and a 1 s sample time, one quantization step would change the output by about 114% for KD ≈ 1.8 × 103 but by about 22% for KD = 350 (simulation in Section 3.6).
The ±0.1 °C value describes how closely the DS18B20 reading follows the setpoint (setpoint-holding stability); it is not the accuracy of the actual reactor temperature. The sensor is specified to ±0.5 °C, so the true temperature of the contents may differ from the displayed value by up to that tolerance, in addition to any gradient between the probe position and the bulk liquid. An absolute accuracy of ±0.1 °C therefore cannot be claimed without comparison with a reference thermometer. Because the two runs in Figure 5 started from different temperatures and are single runs, the reduction of the overshoot from 2.9 °C to ≈0.6 °C should be regarded as indicative; a like-for-like comparison from the same initial condition is planned.
3.3. Automation System Performance
Master–Slave Communication. The dual-microcontroller architecture operated stably during the tests reported here. Serial communication latency between the processing units averaged under 200 ms for full data packet transfers (the measurement method and number of samples are not documented, so these values are indicative). This rapid exchange rate ensured that critical parameters—including bioreactor temperature, fluid levels, gas concentrations, and overall system status—were continuously updated without bottlenecking the control algorithms. Furthermore, the local Human–Machine Interface (HMI) provided good responsiveness, with touch response times registering under 100 ms for button inputs on the TFT display, allowing for seamless local manual control.
IoT Integration and Data Telemetry. A core feature of the automation system is its Internet of Things (IoT) connectivity. Data transmission to the ThingSpeak cloud platform was configured to operate at 15 s intervals. This continuous data stream enabled comprehensive remote monitoring via a web interface, historical data storage, CSV data export capabilities, and real-time visualization of temperature profiles and biogas production trends.
Reporting interval and sampling terminology. Three quantities must be distinguished: (i) sensor sampling, i.e., the 1 s acquisition and PID cycle executed locally on the ESP32 master (Section 2.3); (ii) data reporting, i.e., the interval at which records are sent to ThingSpeak (15–17 s in the session of 7 March 2026 and 30–32 s in that of 19 March 2026); and (iii) the selection of training samples, a machine-learning notion that does not occur in this work. The reporting interval does not affect closed-loop control, because the PID loop runs locally at 1 s. For the thermal process it is short compared with the identified dynamics (Tp = 5977 s, L = 122 s; about 400 reports per time constant and eight per dead time at 15 s, and about 190 and four at 31 s), so it is adequate for monitoring the heating and holding phases in Figure 5 and Figure 6. This adequacy was not verified for faster events, such as level changes during gas release or gas-sensor transients, whose time scales were not characterized in this study.
Figure 6.
ThingSpeak cloud monitoring dashboard (labels in Romanian, see text).
Adaptive reporting, i.e., transmitting more often when the signals change quickly and less often otherwise, is a possible future extension. Temporal-evolution-aware adaptive sampling for open-set active learning [31] offers a methodological connection only in a limited sense: it selects, under a budget, which data points of a stream should be labelled for training a classifier, and it relies on labels and on a learned model that detects unknown classes. In the present context such labels would be costly offline analyses (for example, gas chromatography or volatile fatty acid measurements), and neither a classifier nor labelled data exist in this study. Selecting training samples [31], sampling the sensors, and reporting data to the cloud are different operations. A simple event-triggered reporting rule (for example, reporting when the temperature changes by more than a threshold, with a maximum silent period) would be the appropriate first step and would not require learning. No adaptive scheme was implemented or evaluated here.
For possible future transmission of high-dimensional features, semantic-aware group entropy and disentanglement-guided feature coding in split inference [32] could reduce the communication load when features computed at the edge are sent to a remote model. For the present telemetry this is not warranted: each record contains only a few scalar values (a few tens of bytes every 15 s), so compression or feature coding would add complexity without a measurable benefit. It would become relevant only if high-dimensional data, such as spectra, images, or raw gas-sensor transients, were processed jointly on an edge device and in the cloud.
As illustrated in the monitoring dashboard in Figure 6, the platform generates live charts tracking crucial system dynamics. The interface successfully visualizes the internal bioreactor temperature (Temperatura Bioreactor), the heating-agent temperature (Temperatura Tur), and the dynamic power output directed to the Peltier elements by the PID controller. (Romanian dashboard labels: Temperatura Bioreactor = bioreactor temperature; Temperatura Tur = heating-agent supply temperature).
To facilitate further analysis and advanced data processing, the system logs historical data, which can be exported in CSV format. The excerpt in Table 5 (26 consecutive records, ≈13 min, recorded on 19 March 2026) shows that data were received at intervals of 30–32 s (mean 31.0 s) between the Created_at time stamps (e.g., 10:37:06, 10:37:37, 10:38:08), with consecutive Entry_id values (17512–17537). The time stamp is assigned by the ThingSpeak server on receipt, so it includes network and server latency (round-trip times of 1–3 s have been reported for the REST interface [30]); the 2 s spread of the intervals within each session is consistent with this. The excerpt therefore shows that the transmission chain operated, but it does not establish strict synchronization between sensor sampling and time stamps, nor long-term reliability (packet loss, outages, or clock drift), which would require a multi-day record. The columns of the exported CSV file, which are the field labels of the ThingSpeak channel, are defined in Table 4. In the excerpt of Table 5, the temperature channels, the two Peltier PWM commands, the setpoint, and the gas volume are transmitted in the same record, i.e., with a common time stamp; the MQ2 and MQ135 signals are not included in the table. The excerpt was recorded during the warm-up of the water-filled bioreactor with a setpoint of 55 °C entered. Both Peltier outputs were saturated (PWM = 255), and the bioreactor temperature rose only from 40.7 to 41.5 °C within the ≈13 min window, so the setpoint was neither reached nor held; the excerpt documents the heating phase and the data pathway, not thermophilic control. The gas volume is constant (500 cm3) throughout the excerpt.
Table 4.
Definition of the ThingSpeak CSV fields (channel layout of the recorded excerpt in Table 5).
Table 5.
ThingSpeak data exported in CSV format (26 consecutive records, 19 March 2026, ≈13 min; the +00:00 offset of the time stamps is omitted; column definitions in Table 4).
3.4. Preliminary Evaluation of the Biogas Measurement Subsystem
The communicating-vessels volume measurement was tested with compressed air (not biogas) and gave:
- •
- Volume-display resolution: 10 mL (determined by the column cross-section and the distance resolution of the HC-SR04, Section 2.5; a resolution, not an accuracy).
- •
- Linearity: Not independently documented, so no R2 value is reported. If V is computed from the liquid height as V = A·Δh, a regression of V on h is linear by construction and does not validate the measurement; validation requires regressing the indicated volume on an independent reference volume (Section 2.5).
- •
- Automated purging cycle activated when liquid level reached maximum threshold (functional test).
- •
- Gas sensors: The MQ2 and MQ135 outputs are recorded after activated-carbon filtration but were not calibrated against reference gases (see below).
Accordingly, the MQ2/MQ135 readings are reported as indicative relative signals; no CH4 or CO2 concentration values are claimed. Metal-oxide sensors are cross-sensitive (e.g., MQ2 to H2, alcohols, and smoke; MQ135 to NH3 and volatile organic compounds), respond to humidity and temperature, drift over time [27], and rely on adsorbed oxygen, which is limited in an oxygen-free biogas atmosphere. Quantitative use would require calibration with reference CH4/CO2 mixtures, validation against a reference analyser (e.g., NDIR or gas chromatography), and an uncertainty estimate; simple data-quality indicators (drift, saturation, flat-lining, and inter-sensor consistency checks) could additionally flag the recorded signals [29]; these indicators grade the plausibility of a signal and do not substitute for calibration. For measurements with real biogas, the solubility of CO2 in the displaced liquid must also be considered.
Measurement reliability and information value for learning. Two properties of a sensor channel should not be confused. Measurement reliability concerns whether a signal is a valid, traceable estimate of the quantity of interest; it is established by calibration against reference gases, a reference analyser, and an uncertainty estimate, as described above, and the MQ2/MQ135 signals do not currently meet this requirement. Information value for learning concerns how much a channel, or a segment of a record, would contribute to a data-driven model, for example a soft sensor. Approaches that decouple the components of a signal without supervision and evaluate the information quality of each channel or time segment at a fine-grained level [34] could in principle be used to rank channels and temporal segments (for example, transients after feeding versus steady-state operation) by their contribution to such a model. The two properties can diverge: a metal-oxide channel can respond strongly to humidity, ammonia, or volatile organic compounds and thus carry much information for a learned model while being unreliable as a CH4 or CO2 measurement, and a reliable channel such as the temperature held at its setpoint can carry little discriminative information. Information-quality scores therefore cannot replace gas calibration, cannot remove bias or cross-sensitivity of the sensors, and presuppose a defined downstream task and, ultimately, reference data. They are mentioned only as a possible aid for future data selection after calibration and were not applied in this study.
3.5. Literature-Based Perspective on Mesophilic–Thermophilic Operation
The platform is designed to allow a comparison of thermophilic and mesophilic performance on identical substrates. No digestion experiment was performed with this apparatus; the statements below are taken from the literature and are not results of this work. Reported advantages of thermophilic operation for food waste are:
- •
- Methane production rates 63% higher [4];
- •
- Methane yields 5.6–22.4% higher for food waste [4];
- •
- Superior pathogen elimination (98.9–99.9% for E. coli) [4].
However, careful transition management is essential. Research indicates that during mesophilic–thermophilic shifts, volatile fatty acid accumulation can occur due to acidogenic bacteria adapting faster than methanogenic archaea [7]. The PID controller is expected to support gradual temperature transitions, and ramp-rate limiting is implemented in software, but its performance in a mesophilic–thermophilic transition was not tested here. The open-loop dynamics were identified between 16.8 and 36.4 °C; at 50–60 °C, heat losses and Peltier performance differ, so re-identification and retuning are required.
3.6. Model-Based Analysis (Simulation Only)
This subsection reports simulations, not measurements. The identified FOPDT model (Table 2) was combined with the logic of the PID_v1 library (1 s sample time, proportional action on the error, integral term clamped to the output limits, derivative on the measurement) in Python 3.15.2. Assumptions: A linear, time-invariant plant with Kr = 0.98 °C/%, L = 122 s, Tp = 5977 s, and Tamb = 16.8 °C; 0–100% actuator limits unless stated; no change of heat losses with temperature; measurement noise limited to quantization at 0.0625 °C where stated.
Comparison with the recorded runs. To reproduce the warm-up rate of run (a), an effective output limit of 25% was fitted (the actual limit is not documented). With this limit the model gives overshoots of about 0.15 °C for both gain sets (Figure 7), whereas 2.9 °C and ≈0.6 °C were measured (Figure 5). The FOPDT model therefore does not reproduce the closed-loop overshoot, and a single extra heater-side lag fitted to run (a) did not predict run (b) either (≈3 °C instead of ≈0.6 °C). A likely explanation is heat stored in the glycol loop and the heat exchanger, which a single-lag model cannot represent. The model is therefore not used to claim predicted controller performance; a higher-order model identified from replicated open-loop tests is planned.
Figure 7.
Simulation: closed-loop response of the identified FOPDT model (line) and key points read from the recorded runs in Figure 5 (markers). (a) Initial gains, start 24.3 °C; (b) final gains, start 33.4 °C. The output limit of 25% was fitted to the ramp of run (a) only.
Derivative term. With the measurement quantized at 0.0625 °C, each quantization step produces a one-sample derivative kick: for the CHR value KD ≈ 1829, the kick saturates the output at 0%; for KD = 350, it is about 22% of full scale (Figure 8). The kicks last 1 s and are thermally negligible for this slow plant, so the argument concerns actuator wear and noise rather than temperature accuracy; a low-pass-filtered derivative would be the usual remedy.
Figure 8.
Simulation (not measured data): controller output (left) and temperature (right) after a 36 → 37 °C setpoint step with the measurement quantized to 0.0625 °C, for KD = 1829 (CHR) and KD = 350 (final). KP = 28 and KI = 0.005.
Thermophilic setpoint. In the model, holding 37 and 55 °C requires steady heater duties of 20.6% and 39.0%, respectively ((Tset − 16.8)/0.98). A simulated setpoint step from 37 to 55 °C overshoots by about 2.2 °C with the final gains and 1.9 °C with the CHR gains, and settling within 0.5 °C takes about 2.8 h; doubling the dead time raises the overshoot to about 3.3 °C, whereas ±20% in Kr or changes of Tp between 0.7 and 1.5 times change it by less than 0.5 °C (Figure 9). Because heat losses and Peltier performance at 55 °C are not modelled, these numbers only indicate that gradual setpoint ramping and retuning will be needed; they do not show that the hardware can reach 55–60 °C.
Figure 9.
Simulation: setpoint step 37 → 55 °C. Left: final and CHR gains. Right: final gains with changed plant parameters (Kr ±20%, L ×2, Tp ×1.5 and ×0.7). Linear model, 100% output limit, heat-loss changes not modelled.
3.7. Scope and Limitations of the Present Validation
Table 6 summarizes which functions were tested in this study and which claims the present measurements do not support.
Table 6.
Validation status of the main functions of the platform.
4. Conclusions
This paper has presented the design, implementation, and preliminary experimental characterization of an IoT-enabled multi-sensor monitoring and control system for a laboratory-scale biogas fermenter designed for dual-temperature (mesophilic 35–40 °C; thermophilic 50–60 °C) operation. Temperature, ultrasonic-level, and gas-sensor streams are acquired by a Master–Slave (ESP32/Arduino) architecture and shown on a local HMI and a cloud dashboard. Closed-loop control was demonstrated with water at a 37 °C setpoint only; thermophilic control, digestion with real substrates, and validation of gas-composition measurements were not performed.
The main findings are:
Sensor-driven thermal control: Closed-loop PID regulation tuned from an identified FOPDT model (Kr = 0.98 °C/%, L = 122 s, Tp = 5977 s) reduced the overshoot at the 37 °C setpoint from 2.9 °C to ≈0.6 °C after retuning (KP = 28, KI = 0.005, KD = 350), with the DS18B20 reading settling within ±0.1 °C of the setpoint; the specified sensor accuracy is ±0.5 °C, and this limited overshoot is relevant for temperature-sensitive biological processes [7,8].
Multi-sensor acquisition architecture: Temperature, ultrasonic-level, and gas-sensor data are acquired in a common loop, displayed locally, and transmitted to the cloud; no data-fusion algorithm or anomaly detection was implemented.
Non-invasive volumetric sensing concept: An ultrasonic communicating-vessels subsystem was tested with compressed air (10 mL volume-display resolution); calibration against a reference and tests with real biogas remain to be done.
IoT-enabled monitoring: Cloud telemetry presents the sensor data on a common time axis and allows CSV export; reliability was verified only in short sessions.
The fermenter platform is designed to enable, after validation with real substrates, comparative studies of mesophilic versus thermophilic digestion, investigation of temperature-phased configurations, and development of optimized operational strategies. Beyond the anaerobic digestion domain, the acquisition and IoT architecture may also serve as a transferable template for sensor systems in other bioprocess and environmental monitoring applications, in line with multi-sensor deployments in precision agriculture [35], healthcare [15], and transportation infrastructure monitoring [36]. Laboratory infrastructure of this kind can support work toward circular-economy waste management and renewable-energy production; its actual value will depend on the validation steps listed below.
The main limitations of this study are: (i) closed-loop control was tested only at 37 °C, with water, in single runs; (ii) no anaerobic digestion experiment with a real substrate was performed; (iii) the MQ2/MQ135 signals were not calibrated against reference gases and are indicative only; (iv) the volume measurement was tested with compressed air only, and the cross-sectional area of the measuring column (A ≈ 19.6 cm2, from the measured diameter of 5.0 cm) was not verified against a reference volume; (v) telemetry was verified in short sessions, with a fixed reporting interval (15 s or 31 s, depending on the session) and without a long-term reliability assessment; and (vi) the identified FOPDT model does not reproduce the measured overshoot in simulation (Section 3.6). The comparison of mesophilic and thermophilic digestion in Section 3.5 is taken from the literature and was not measured with this platform.
The developed fermenter is intended to enable, once validated:
- •
- Fundamental research: Investigation of microbial community dynamics during temperature transitions, identification of metabolic pathway shifts, and determination of optimal thermal gradients for thermophilic enrichment.
- •
- Applied optimization: Co-digestion studies across temperature regimes to identify optimal conditions for specific substrate mixtures (agricultural waste, food residues, manure).
- •
- Process validation: Small-scale testing before industrial implementation, which may reduce the risks and costs associated with a full-scale thermophilic transition.
- •
- Educational applications: Practical demonstration of AD principles, the importance of automation, and renewable energy technologies in teaching laboratories.
Future work will focus on:
- •
- Automatic organic loading control via dosing pumps for continuous operation;
- •
- Self-tuning PID algorithms for adaptive control across temperature regimes;
- •
- Extended validation with real organic substrates over long-term operation;
- •
- Re-identification of the FOPDT model and retuning/validation of the PID controller at thermophilic setpoints (50–60 °C), with replicated runs and a reference thermometer;
- •
- Calibration and validation of the gas sensors (or their replacement by NDIR/infrared CH4 and CO2 sensors) against reference gas mixtures, including uncertainty and drift assessment;
- •
- Long-term (multi-day) telemetry tests, including packet-loss and time-synchronization analysis;
- •
- Identification of a higher-order thermal model from replicated open-loop tests, and execution of a defined measurement protocol (volume calibration against a reference volume, probe check against a reference thermometer, replicated closed-loop runs, and thermophilic tests with water);
- •
- Integration of additional sensors for pH, redox potential, and volatile fatty acid monitoring;
- •
- Application of machine-learning-based soft sensors and multi-sensor data-fusion algorithms (e.g., learning-aided filtering [25,28]) for predictive process-stability assessment and early anomaly detection [11];
- •
- Event-triggered or adaptive data reporting, evaluated against the fixed reporting interval for fast events such as gas release (no learning required initially);
- •
- After calibration: Information-quality assessment of channels and temporal segments [34] to support soft sensing.
Author Contributions
Conceptualization, C.R.P., N.M., M.I., and G.I.; methodology, C.R.P., N.M., M.I., and G.I.; software, C.R.P. and G.I.; validation, C.R.P., N.M., and G.I.; formal analysis, C.R.P., N.M., and G.I.; investigation, C.R.P., N.M., M.I., and G.I.; data curation, C.R.P., M.I., and G.I.; writing—original draft preparation, C.R.P., M.I., and G.I.; writing—review and editing, C.R.P., M.I., and G.I.; visualization, C.R.P., N.M., M.I., and G.I.; supervision, M.I. and G.I.; project administration, N.M.; funding acquisition, N.M. All authors have read and agreed to the published version of the manuscript.
Funding
This work was partially funded by the project “National Platform for Semiconductor Technologies”, contract no. G 2024-85828/390008/27.11.2024, SMIS code 304244, co-funded by the European Regional Development Fund under the Operational Program for Smart Growth, Digitization, and Financial Instruments (POCIDIF), Priority 1—Supporting and promoting an attractive and competitive CDI system in Romania, and partially supported by the Romanian Ministry of Education and Research, through the μNanoEl, Cod: 23 07 core Program.
Institutional Review Board Statement
Not applicable.
Informed Consent Statement
Not applicable.
Data Availability Statement
The data supporting the reported results (temperature records and ThingSpeak CSV exports) are available from the corresponding author upon reasonable request.
Acknowledgments
The authors have reviewed and edited the output and take full responsibility for the content of this publication.
Conflicts of Interest
The authors declare no conflicts of interest.
Abbreviations
The following abbreviations are used in this manuscript:
| AD | Anaerobic digestion |
| AISI | American Iron and Steel Institute |
| ATX | Advanced Technology eXtended (PC power-supply standard) |
| BLE | Bluetooth Low Energy |
| CHR | Chien–Hrones–Reswick (tuning method) |
| CSV | Comma-separated values |
| DC | Direct current |
| EMI | Electromagnetic interference |
| FOPDT | First-order plus dead time |
| HMI | Human–machine interface |
| IoT | Internet of Things |
| MOSFET | Metal–oxide–semiconductor field-effect transistor |
| NDIR | Non-dispersive infrared |
| PID | Proportional–integral–derivative |
| PWM | Pulse-width modulation |
| TFT | Thin-film transistor (display) |
| UART | Universal asynchronous receiver–transmitter |
| VS | Volatile solids |
References
- Angelidaki, I.; Treu, L.; Tsapekos, P.; Luo, G.; Campanaro, S.; Wenzel, H.; Kougias, P.G. Biogas upgrading and utilization: Current status and perspectives. Biotechnol. Adv. 2018, 36, 452–466. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- Labatut, R.A.; Angenent, L.T.; Scott, N.R. Conventional mesophilic vs. thermophilic anaerobic digestion: A trade-off between performance and stability? Water Res. 2014, 53, 249–258. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- Mao, C.; Feng, Y.; Wang, X.; Ren, G. Review on research achievements of biogas from anaerobic digestion. Renew. Sustain. Energy Rev. 2015, 45, 540–555. [Google Scholar] [CrossRef] [Scilit]
- Bi, S.; Wang, C.; Wang, H.; Du, Y.; Yu, X.; Wang, Y. Comparison of mesophilic and thermophilic anaerobic digestion of food waste: Focusing on methanogenic performance and pathogen removal. Renew. Energy 2024, 233, 121184. [Google Scholar] [CrossRef] [Scilit]
- Heeg, K.; Pohl, M.; Sontag, M.; Mumme, J.; Klocke, M.; Nettmann, E. Microbial communities involved in biogas production from wheat straw as sole substrate in a two-phase solid-state anaerobic digestion. Syst. Appl. Microbiol. 2014, 37, 590–600. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- Sahlström, L. A review of survival of pathogenic bacteria in organic waste used in biogas plants. Bioresour. Technol. 2003, 87, 161–166. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- Jiang, J.; He, S.; Kang, X.; Sun, Y.; Yuan, Z.; Xing, T.; Guo, Y.; Li, L. Effect of Organic Loading Rate and Temperature on the Anaerobic Digestion of Municipal Solid Waste: Process Performance and Energy Recovery. Front. Energy Res. 2020, 8, 89. [Google Scholar] [CrossRef] [Scilit]
- Chen, Y.; Cheng, J.J.; Creamer, K.S. Inhibition of anaerobic digestion process: A review. Bioresour. Technol. 2008, 99, 4044–4064. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- Mata-Alvarez, J.; Dosta, J.; Romero-Güiza, M.S.; Fonoll, X.; Peces, M.; Astals, S. A critical review on anaerobic co-digestion achievements between 2010 and 2013. Renew. Sustain. Energy Rev. 2014, 36, 412–427. [Google Scholar] [CrossRef] [Scilit]
- Weiland, P. Biogas production: Current state and perspectives. Appl. Microbiol. Biotechnol. 2010, 85, 849–860. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- Marycz, M.; Turowska, I.; Glazik, S.; Jasiński, P. Artificial intelligence in anaerobic digestion: A review of sensors, modeling approaches, and optimization strategies. Sensors 2025, 25, 6961. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- Cruz, I.A.; Andrade, L.R.; Bharagava, R.N.; Nadda, A.K.; Bilal, M.; Figueiredo, R.T.; Ferreira, L.F. An overview of process monitoring for anaerobic digestion. Biosyst. Eng. 2021, 207, 106–119. [Google Scholar] [CrossRef] [Scilit]
- Gazis, A.; Papadongonas, I.; Andriopoulos, A.; Zioudas, C.; Vavouras, T. A comprehensive review of sensor technologies, instrumentation, and signal processing solutions for low-power Internet of Things systems with mini-computing devices. Acad. Eng. 2025, 2, 1–20. [Google Scholar]
- Banaee, H.; Ahmed, M.U.; Loutfi, A. Data mining for wearable sensors in health monitoring systems: A review of recent trends and challenges. Sensors 2013, 13, 17472–17500. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- Mohamed, R.; Shaaban, E.; Benslimane, A. A survey on multi-sensor fusion techniques in IoT for healthcare. In Proceedings of the 2018 13th International Conference on Computer Engineering and Systems (ICCES), Cairo, Egypt, 18–19 December 2018; pp. 157–162. [Google Scholar]
- Cinar, S.; Cinar, S.O.; Wieczorek, N.; Sohoo, I.; Kuchta, K. Integration of artificial intelligence into biogas plant operation. Processes 2021, 9, 85. [Google Scholar] [CrossRef] [Scilit]
- Junus, M.; Rahman, A.D.; Shodiq, R.F. Micro-controller-based biogas production monitoring system. Indones. J. Electr. Electron. Eng. 2025, 8, 69–75. [Google Scholar]
- de Andrade, F.P.H.; Félix, J.H.S.; Andrade, F.H.L.; Paz, D.A.C.; Alcócer, J.C.A.; Pinto, O.R.O. Monitoring of biodigesters through a computerized system integrated to IoT platform. Int. J. Adv. Eng. Res. Sci. 2022, 9, 270–278. [Google Scholar] [CrossRef] [Scilit]
- Negara, I.G.A.; Anakottapary, D.S.; Widiantara, I.B.G.; Midiani, L.P.I.; Nindhia, T.G.T.; Santhiarsa, I.G.N.N. Integrated microcontroller MQ sensors for monitoring biogas: Advancements in methane and hydrogen sulfide detection. J. Teknosains 2024, 13, 140–151. [Google Scholar] [CrossRef] [Scilit]
- Elyounsi, A.; Kalashnikov, A.N. Evaluating suitability of a DS18B20 temperature sensor for use in an accurate air temperature distribution measurement network. Eng. Proc. 2021, 10, 56. [Google Scholar] [CrossRef] [Scilit]
- Haq, A.; Firdaus, R.A.; Khoiro, M.; Rahmawati, E.; Winarto, N. Accuracy of HC-SR04 ultrasonic servo in servo-scanned 2D ranging. Prism. Sains 2026, 14, 1417–1431. [Google Scholar] [CrossRef] [Scilit]
- Ziegler, J.G.; Nichols, N.B. Optimum settings for automatic controllers. Trans. ASME 1942, 64, 759–768. [Google Scholar] [CrossRef] [Scilit]
- Chien, K.L.; Hrones, J.A.; Reswick, J.B. On the automatic control of generalized passive systems. Trans. ASME 1952, 74, 175–185. [Google Scholar] [CrossRef] [Scilit]
- Elecfreaks. Ultrasonic Ranging Module HC-SR04, Datasheet. Available online: https://cdn.sparkfun.com/datasheets/Sensors/Proximity/HCSR04.pdf (accessed on 27 October 2026).
- Revach, G.; Shlezinger, N.; Ni, X.; Escoriza, A.L.; van Sloun, R.J.G.; Eldar, Y.C. KalmanNet: Neural network aided Kalman filtering for partially known dynamics. IEEE Trans. Signal Process. 2022, 70, 1532–1547. [Google Scholar] [CrossRef] [Scilit]
- Wen, J.; Wang, D.; He, J.; Xi, M.; Xiao, S.; Yang, J. Learning-aided equivariant filtering on the special euclidean group for underwater navigation sensor fusion. Eng. Appl. Artif. Intell. 2026, 178, 115050. [Google Scholar] [CrossRef] [Scilit]
- Vergara, A.; Vembu, S.; Ayhan, T.; Ryan, M.A.; Homer, M.L.; Huerta, R. Chemical gas sensor drift compensation using classifier ensembles. Sens. Actuators B Chem. 2012, 166–167, 320–329. [Google Scholar] [CrossRef] [Scilit]
- Marsh, B.; Sadka, A.H.; Bahai, H. A critical review of deep learning-based multi-sensor fusion techniques. Sensors 2022, 22, 9364. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- Liu, C. Multi-Sensor Information Fusion Algorithm Based on Edge Information. In Proceedings of the 2023 International Conference on Mechatronics, IoT and Industrial Informatics (ICMIII), Melbourne, Australia, 9–11 June 2023; pp. 466–470. [Google Scholar] [CrossRef] [Scilit]
- Viegas, V.; Dias Pereira, J.M.; Girão, P.; Postolache, O. Study of latencies in ThingSpeak. Adv. Sci. Technol. Eng. Syst. J. 2021, 6, 342–348. [Google Scholar] [CrossRef] [Scilit]
- Wu, J.; Xiao, S.; Zhang, Z.; Wen, J.; Li, B.; Meng, Q.; Lu, W.; Yang, J.; Gao, X. Temporal Evolution-Aware Adaptive Sampling for Open-Set Active Learning. IEEE Trans. Circuits Syst. Video Technol. 2026. [Google Scholar] [CrossRef] [Scilit]
- Yang, J.; Cao, C.; Gao, Y.; Lan, G.; Xiao, S.; Wen, J.; Lu, W.; Li, B.; Meng, Q.; Gao, X. SAGE: Semantic-Aware Group Entropy for Disentanglement Guided Feature Coding in Split-Inference Segmentation. IEEE Trans. Multimed. 2026, 28, 17130–17142. [Google Scholar] [CrossRef] [Scilit]
- ISO 8601-1:2019; Date and Time—Representations for Information Interchange—Part 1: Basic Rules. International Organization for Standardization: Geneva, Switzerland. 2019. Available online: https://www.iso.org/standard/70907.html (accessed on 18 September 2026).
- Wu, J.; Xiao, S.; Zhang, Z.; Wen, J.; Li, B.; Meng, Q.; Lu, W.; Yang, J.; Gao, X. Unsupervised component decoupling for fine-grained information quality evaluation. IEEE Trans. Image Process. 2026, 35, 10513–10528. Available online: https://hdl.handle.net/2134/33944923.v1 (accessed on 18 September 2026). [CrossRef] [Scilit] [PubMed]
- Mansoor, S.; Iqbal, S.; Popescu, S.M.; Kim, S.L.; Chung, Y.S.; Baek, J.-H. Integration of smart sensors and IoT in precision agriculture: Trends, challenges and future prospectives. Front. Plant Sci. 2025, 16, 1587869. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- Micko, K.; Papcun, P.; Zolotova, I. Review of IoT sensor systems used for monitoring the road infrastructure. Sensors 2023, 23, 4469. [Google Scholar] [CrossRef] [Scilit] [PubMed]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2026 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.