Abstract
This study aims to address the lack of systematic research on how air filter cleaning affects pollutant distribution in subway stations, an urgent issue for ensuring indoor air quality in enclosed underground transit environments. Taking a representative subway line in Xi’an, China, as the research object, we monitored and analyzed pollutant concentrations (including particulate matter and microorganisms) at air supply outlets (near, semi-far, and far from the air filter) and different locations in a single station hall before and after filter cleaning, with the goal of clarifying the cleaning effect and its variation with distance from the air supply. The results show that, before cleaning, pollutant distribution exhibits distinct spatial characteristics: PM10 concentration is 16.7% higher at outlets closer to the filter, while PM2.5 and PM1.0 concentrations are 22.4% and 19.7% higher at distant outlets, respectively. After cleaning, all pollutants are significantly reduced: PM10 at near outlets decreases by 25.9%, PM2.5 and PM1.0 at far outlets drop by 44.2% and 42.7%, respectively, and the total numbers of bacteria and fungi in the air supply meet national hygiene standards. A key novel finding is that cleaning has differentiated effects on particle sizes across locations; it is more effective for larger particles at near outlets and for smaller particles at far outlets. This research not only quantifies the purification effect of filter cleaning but also reveals the spatial variation law of its impact, providing practical guidance for optimizing subway ventilation system maintenance (e.g., tailored cleaning strategies for different locations) and ensuring passenger health.
1. Introduction
With the rapid development of urban public transportation, the subway has become the core carrier for citizens’ travel, bearing a massive passenger flow every day [1]. Due to the subway’s relatively enclosed underground environment and poor natural ventilation conditions, the cleanliness of its filters plays a decisive role in the efficiency of intercepting pollutants in the ventilation system, which is key for air circulation and purification [2]. Furthermore, after long-term operation, both the surface and interior of filters are prone to accumulate pollutants, such as dust, particulate matter, and microorganisms [3,4], which directly leads to a decrease in purification capacity and affects the distribution of air quality in different areas of the station, directly or indirectly endangering the physical and mental health of passengers and staff [5]. Therefore, against the backdrop of global low-carbon development and post-COVID-19 public health awareness enhancement [6], effectively creating a healthy and safe indoor environment is one of the key research issues.
The subway air conditioning system can be divided into a water system and a wind system [7], with the former comprising a chilled water system, a cooling water system, and a condensate water system and the latter a system for processing and transporting air. The main purpose of setting up such an air conditioning purification system is to protect the air conditioning heat exchange equipment [8]; therefore, cleaning the air conditioning system can ensure the efficiency of the air conditioning system operation and increase its service life. However, maintaining the system can also effectively ensure public health. As a consequence of the global COVID-19 pandemic [6,9], people have come to realize that air conditioning systems can not only provide fresh and clean air for buildings, but also become a channel for rapid virus transmission. In other words, if the air conditioning system is not cleaned and disinfected for a long time, it will pose a greater threat to public health [5].
Currently, the subway company invites environmental protection companies to conduct comprehensive cleaning and disinfection of the air conditioning and water systems in each station every year to ensure the air quality and efficient operation of related equipment [10]. In China, the “Cleaning code for air dust system in heating, ventilating, and air conditioning systems” (GB19210-2003) defines the cleaning of all equipment and components through which air passes in the air conditioning system [11]. Existing cleaning methods mainly include robot cleaning methods [12], electric soft-shaft cleaning methods [13], manual cleaning methods [14], unit cleaning methods [15], and component cleaning; however, according to the actual situation and cost budget, methods vary, and manual cleaning is often adopted [14], which is prone to human operational errors, such as personnel not wearing appropriate clothing when entering and exiting the air duct, or leaking or repeating cleaning when cleaning the inner wall of the duct. These situations can lead to a decrease in cleaning effectiveness, making cleaning both time-consuming and laborious. In addition, the ventilation system of the subway was not designed with consideration for the cleaning requirements of the ventilation system [15], which makes it difficult or even impossible for cleaning enterprises to carry out cleaning and sterilization work.
Indoor air quality (IAQ) management in enclosed spaces has always been a focus of interdisciplinary research, involving environmental engineering, public health, and building technology [16]. Different types of enclosed structures face unique pollutant accumulation and diffusion challenges due to differences in usage scenarios, ventilation modes, and crowd density. For example, in garage environments, air leakage modeling shows that improper sealing of building envelopes can lead to the backflow of exhaust gas containing harmful substances such as nitrogen oxides, volatile organic compounds (VOCs), significantly affecting indoor air quality (IAQ) [17]. For subway stations, the characteristics of high passenger flow density, frequent personnel movement, and complex pollutant sources (including external air intake, passenger-carried particles, and equipment operation emissions) make their pollutant distribution and diffusion mechanisms more complex than those of ordinary office buildings or garages [18]. Sun et al. [18] confirmed this complexity through a randomized controlled trial in a Chinese city, revealing that subway air particles (including PM2.5, PM10, and microbial aerosols) have distinct physiological impacts on healthy adults compared to pollutants in above-ground enclosed spaces, attributed to the unique emission and diffusion dynamics of subway-specific pollutant sources. Existing studies on IAQ in enclosed spaces have explored key factors such as ventilation strategies, pollutant source identification, and human activity impacts [19,20]. Specifically, Dinh et al. [19] conducted a 15-month long-term monitoring study on PM2.5 in an underground subway station, focusing on evaluating the performance of mid-cost optical particle counters and indirectly verifying the influence of ventilation system operation on pollutant accumulation. Plazas et al. [20] developed health-based natural ventilation guidelines for existing homes, demonstrating how ventilation strategies can be tailored to mitigate pollutant risks in residential enclosed spaces by adjusting air exchange rates and airflow patterns. However, neither [19] nor [20] addresses the unique pollutant distribution laws (e.g., spatial differentiation of particle sizes with air supply distance) or ventilation cleaning effectiveness in subway-specific scenarios, leaving a critical research gap for targeted maintenance of subway ventilation systems.
At present, research on subway ventilation systems mainly focuses on the distribution of microbial contamination in air conditioning systems [18], filter selection [21], or system design [22]. Although some results have been achieved, there is a lack of systematic analysis on the distribution of pollutants in the station before and after cleaning the air filters, and few studies have systematically quantified how particulate matter (PM10, PM2.5, PM1.0) concentrations vary with distance from air filters. Outside China, the relevant research on the cleaning of subway air filters mainly focuses on optimizing the cleaning cycle, verifying the cleaning effect, and developing new washable, self-cleaning technologies [19,23,24,25]. Specifically, a reasonable cycle is determined by monitoring the dust accumulation rate of the filter and the attenuation law of the filtration efficiency [19]. Furthermore, although studies have investigated whether cleaning effectively removes attached particles and avoids the impact of residual pollutants on purification performance [23], there is a lack of detailed analysis of how cleaning impacts different particle sizes at varying distances from air outlets, and they do not explore innovative solutions that negate the need for frequent manual cleaning [24]. Linkage research on new self-cleaning technologies and cleaning cycles has also been a hot topic in recent years [25]. Compared to China, other countries focus more on standardized cleaning management, cleaning effectiveness and health and safety assurance, and research and development of efficient and intelligent cleaning technologies [26,27,28]. The emphasis is on clarifying the cleaning cycle, process, and responsibility specifications [26], paying attention to pollutant removal efficiency and secondary pollution prevention and control [27], as well as the development and application of intelligent cleaning technology [28].
Studies on IAQ in other enclosed structures can also provide valuable methodological references. For example, the multi-point sensor layout method used in office space pollutant monitoring [29] can be applied to the spatial differentiation of subway station pollutants, and the coupling analysis of air leakage and pollutant diffusion in garages [17] can provide ideas for exploring the impact of subway ventilation system air leakage on cleaning effectiveness.
The main parameters for evaluating cleaning effectiveness and formulating cleaning strategies are the magnitude of changes in pollutant concentration at air supply outlets after cleaning, as well as the attenuation characteristics of pollutant concentration with distance from the air supply outlet [30]. However, there is currently relatively little research on these aspects, and studies generally fail to systematically analyze the spatial variation characteristics of cleaning effects for different particle sizes (such as PM10, PM2.5, and PM1.0) at different distances from air outlets. Furthermore, there are still many problems with the cleaning cycle and methods in the subway air system. For example, the cleaning cycle should be determined based on the purification efficiency of the air purification equipment, as well as factors such as the outdoor environment and passenger flow of different stations, instead of the current one-year cycle. Moreover, the cleaning method should be tailored to the different equipment and locations of the air conditioning system instead of the current universal method, which ignores the differences in pollutant accumulation rates caused by factors such as station location, passenger flow density, and outdoor air quality. Compared with the research on IAQ in offices, garages, and other enclosed spaces, the research on subway ventilation cleaning lacks the integration of multi-factor coupling analysis (such as the interaction between ventilation speed, duct structure, and cleaning methods) [31], resulting in an inability to provide a theoretical basis for the optimization of cleaning technologies. Therefore, studying the cleaning of air conditioning systems has practical engineering value and will help to improve and upgrade relevant systems.
To fill these gaps, this study takes a representative subway line in Xi’an as the research object, and, by monitoring the concentration of particulate matter (PM10, PM2.5, PM1.0) and microorganisms at air outlets at different distances before and after filter cleaning, we aim to clarify the spatial distribution law of pollutants and the differentiation effect of cleaning operations. This research not only quantifies the reduction rate of pollutants of different types and particle sizes but also reveals the mechanism of the interaction between air supply distance, particle properties, and cleaning effectiveness. The results are expected to provide a scientific basis for the formulation of targeted maintenance strategies for subway ventilation systems (such as differentiated cleaning cycles and optimized cleaning methods) and enrich the theoretical system of IAQ management in complex enclosed public spaces.
2. Methods
2.1. Sampling Location and Time
Metro Line 2 in Xi’an, a core north–south line in the city’s subway network, was selected as the test object. It was officially opened on 15 September 2011, and the initial train fleet was put into service at the time of the line’s opening. Currently, it mainly operates the initial 2011-era trains (13 years old) and the 2016 supplementary trains (8 years old), with the average age of the operational fleet being 10–13 years, which is typical for mature subway lines in China, where subway trains have a standard design service life of 25–30 years. A characteristic of the passenger flow on this subway line at the selected station is that there are more people leaving the station during the morning rush hour and more people entering the station during the evening rush hour. Overall, the population is relatively dense and has a certain representativeness. The station’s platform is 120 m long, 14 m wide, and 8 m high [32].
Testing was conducted on the concourse level of the subway station (shown in Figure 1), which is equipped with a central mechanical ventilation system. For passenger areas in such stations (platforms and concourses), a combined supply and return air system is employed: fresh air is drawn in from the outside via air intake shafts, filtered through high-efficiency particulate air (HEPA) filters [32], and distributed to the platform through ceiling air outlets; exhaust air is collected via return air grilles near the platform edges and discharged after treatment. In our selected station, the monitoring points are located in the middle of the station hall, 1.2 m above the ground, and the testing points were arranged at the center of the near air outlet, semi-far air outlet, and far air outlet of the station hall air conditioning system to explore the relationship between air supply distance and particle concentration at the air outlets. At the same time, the bacterial content and dust accumulation on the cleaned air duct wall were sampled and tested.
Figure 1.
Location of measurement points.
The testing period was from 1 July 2024 to 31 August 2024, covering the high-temperature and high-humidity summer season. This period was characterized by stable outdoor climate conditions and continuous high passenger flow, meaning there was no interference of extreme weather (such as heavy rain and strong winds) on the test results. According to the arrangement of the subway company, the particle concentration values of each measuring point before and after cleaning the subway air system are recorded. Indoor monitoring: Before and after filter cleaning, data were collected for 3 consecutive days. Each day, data were recorded once per minute for 10 consecutive minutes at each monitoring point, and 3 sets of valid data were obtained (with an interval of 2 h between each set to avoid temporal overlap). The final result of each indicator was the average of the 3 sets of data. Outdoor monitoring: Synchronous with indoor data collection, recorded once per minute for 10 consecutive minutes, the average value was taken as the outdoor environmental parameter for the corresponding period.
2.2. Experimental Apparatus
The particle concentration was tested using the Grimm1.109 portable aerosol spectrometer, supplied by Beijing Saak-Mar Environmental Instrument Ltd., Beijing, China, with a mass concentration range of 0.1–100,000 μg/m3, a particle size range of 0.25–32 μm, and a repetition rate of 5%. Indoor environmental parameters: Temperature, relative humidity, and carbon dioxide concentration were measured using the indoor air quality analyzer 7525 (temperature range: 0–60 °C, error: ±0.6 °C, resolution: 0.1 °C; relative humidity range: 5–95% RH, accuracy: ±3.0% RH, resolution: 0.1% RH; CO2 range: 0–5000 ppm, error: ±50 ppm), supplied by TSI Instrument Beijing Co., Ltd., Beijing, China. Outdoor environmental parameters: Measured using the portable weather station Davis Vantage Pro2 (temperature range: −40~60 °C, accuracy: ±0.5 °C; relative humidity range: 0~100% RH, accuracy: ±3% RH; wind speed range: 0~75 m/s, accuracy: ±0.3 m/s; wind direction range: 0~360°, resolution: 1°), supplied by Shanghai Baineng Instrument Co., Ltd., Shanghai, China. The HM-QW6 air microbial sampler was used to test microorganisms, supplied by Shandong Hengmei Electronic Technology Co., Ltd, Weifang, China. Capture particle range: first stage: >7 μm, aperture: 0.91 mm; second stage: 4.7–7 μm, aperture: 0.91 mm; third stage: 3.3–4.7 μm, aperture: 0.71 mm; fourth stage: 2.1–3.3 μm, aperture: 0.53 mm; fifth stage: 1.1–2.1 μm, aperture: 0.34 mm; sixth stage: 0.65–1.1 μm, aperture: 0.25 mm. Sampling flow rate: 28.3 L/min. Microbial cultivation was carried out using a biochemical incubator, supplied by Wenzhou Weike Biological Experimental Equipment Co., Ltd., Wenzhou, China. Temperature range: 4–60 °C. Temperature control accuracy: 0.1 °C. Temperature uniformity: ≤±1 °C. Temperature fluctuation: ≤±0.5 °C.
Abnormal data (such as data exceeding 3 times the standard deviation) were eliminated using the Dixon test. Missing data were supplemented by linear interpolation to ensure data integrity. Pearson correlation analysis was used to explore the correlation between outdoor environmental factors (temperature, humidity, wind speed, outdoor pollutant concentration) and indoor pollutant concentration before and after cleaning [33], clarifying the impact of the external environment on indoor air quality (IAQ). An independent-sample t-test was used to verify whether the difference in pollutant concentration before and after cleaning was statistically significant (p < 0.05), ensuring the reliability of the test results.
3. Results and Discussion
3.1. Particle Mass Concentration at the Air Outlet
The changes in particle mass concentration at the different air outlets are shown in Figure 2.
Figure 2.
Particle concentration at different air outlets. Temperature: 20–38 °C; humidity: 43–72% RH; wind speed: 0.1–2.5 m/s.
It can be clearly seen from Figure 2 that the concentration of PM10 is higher at the air outlet closer to the air filter and lower at the air outlet farthest from the air filter, with a decrease of 16.7% compared to the near air outlet. It can be seen that some PM10 deposits on the inner surface of the air duct in the air conditioning system or are intercepted by the already deposited particles. The concentration trends of PM2.5 and PM1.0 are opposite to those of PM10; the farther the distance from the air filter, the higher the concentration of PM2.5 and PM1.0. This is consistent with the results presented in the literature, verifying the correctness of this paper [34]. The PM2.5 concentration at the far air outlet increased by 12.5% compared to the semi-far air outlet, and the PM2.5 concentration at the far air outlet increased by 22.4% compared to the near air outlet. The concentration of PM1.0 at the far air outlet increased by 8.7% compared to the semi-far air outlet, and the concentration of PM1.0 at the far air outlet increased by 19.7% compared to the near air outlet. The increase in PM2.5 was relatively large because particles of different mass concentrations are mainly affected by gravity, buoyancy, Brownian force, and thermophoretic force in the air duct of a wind system [35]. As the distance from the air filter gradually increases, the wind speed in the main air duct gradually decreases, and some particles will adhere to the pipe wall in the remote air duct. As the wind passes by, some particles on the pipe wall achieve secondary flying and are discharged from the remote air outlet, resulting in an increase in PM2.5 and PM1.0 concentrations at the remote air outlet. These results are also consistent with the relevant literature [34].
The gradual decrease in PM10 concentration is due to the deposition of larger particles near the air filter due to gravity, resulting in a decrease in PM10 concentration with increasing distance. Due to the deposition of a large amount of particulate matter in the remote air duct, a small amount of particulate matter will undergo secondary flying and be sent to the air outlet when the wind passes through, resulting in higher concentrations of PM2.5 and PM1.0 at the far air outlet than at the near air outlet, which is consistent with the results given in the relevant literature. The smaller the distance to the wind tunnel, the larger the sediment particle size, and the farther the distance from the wind tunnel, the smaller the sediment particle size. Due to factors such as Brownian diffusion, particles with smaller particle sizes will float around in the pipe, resulting in a relatively small increase compared to PM2.5.
3.2. Particle Mass Concentration at the Air Outlet Before and After Cleaning
The changes in particle mass concentration before and after cleaning at the different air outlets are shown in Figure 3.
Figure 3.
Particle mass concentration at different air outlets.
From Figure 3, it can be seen that the concentrations of PM10, PM2.5, and PM1.0 at all the air outlets decreased after cleaning: at the near air outlet, they decreased by 25.9%, 18.7%, and 14.3%, respectively; at the semi-far air outlet, they decreased by 23.3%, 32.1%, and 31.3%; and, at the far air outlet, they decreased by 19.6%, 44.2%, and 42.7%. The concentrations of PM2.5 and PM1.0 decreased the most at the far air outlet, while the concentration of PM10 decreased the most at the near air outlet. It can be seen that cleaning the subway air system is beneficial for reducing the concentration of particulate matter at the air outlets and thereby improves the air quality inside the subway station. However, the cleaning effect is also related to factors such as the cleaning tools and cleaning sequence used in the cleaning method [36]; therefore, further in-depth research on the particle change trend before and after cleaning the subway air system is needed.
3.3. Particle Counting Concentration at the Air Outlet Before and After Cleaning
The changes in particle counting concentration before and after cleaning at the different air outlets are shown in Table 1.
Table 1.
Particle counting concentration at different air outlets before and after cleaning.
From Table 1, it can be seen that, after cleaning, the counting concentrations of the various particle sizes (0.2–1.0 μm, 1.0–2.5 μm, 2.5–10 μm, and >10 μm) decreased at all the air outlets: the particle size reduction rates of the near air outlet for the different particle sizes were 41.7%, 47.4%, 57.6%, and 61.5%, respectively; the proportions of particle size reduction at the semi-far air outlet were 48.6%, 55.3%, 52.2%, and 58.8%; and the particle size reduction rates of the far air outlet were 64.4%, 65.5%, 41.5%, and 45.5%. It can be seen that the near air outlet has a larger impact on larger particles, while the far air outlet has a larger impact on smaller particles, which is consistent with the results in Figure 3. The proportion of particles with different sizes after cleaning is shown in Figure 4.
Figure 4.
Proportion of different particle sizes after cleaning.
Figure 4 shows that, as the particle size increased, the proportion of decrease in the near air outlet gradually increased. This is because the inertia interception effect of the cleaned filter on large particles is directly reflected in the near air outlet, while small particles can still penetrate the recovered filter pores due to the fast airflow velocity. Therefore, the proportion of decrease in the near air outlet’s small particles was relatively low [37].
At the semi-far air outlet, the decrease ratio of each particle size was between those of the near air outlet and the far air outlet. This is because the airflow velocity slows down at the semi-far air outlet, and smaller particles are more easily captured by the filter. The diffusion attenuation of larger particles is obvious, so the decrease ratio of each particle size tends to be balanced.
At the far air outlet, the proportion of decrease in small particle size increased. This is because the airflow at the far air outlet is fully diffused, and small particles, due to their light weight and large diffusion range, are more easily carried away from the air outlet by the unobstructed airflow after cleaning. Therefore, the proportion of decrease at this outlet is the highest. However, due to their own settling property, the initial concentration of large particles at a distance is relatively low, and the space for reduction after cleaning is relatively limited. In other words, cleaning the subway air system filter can reduce the total amount of particulate matter and optimize the particle size distribution in the airflow at all outlets, with particular purification effects at the near air outlet.
3.4. Dust Accumulation and Bacterial Content at the Air Outlet After Cleaning
The results for dust accumulation and bacterial content after cleaning the wind system are shown in Table 2.
Table 2.
Test results for relevant parameters after cleaning.
From Table 2, it can be seen that the total number of bacteria and fungi in the air supply of the cleaned air conditioning system, the total number of bacteria and fungi on the inner surface of the air ducts, and the amount of dust accumulation all comply with the requirements of the “Hygienic specification of central air conditioning ventilation system in public places” (WS/T10013-2023) [38]. In some related studies, a range of bacterial total count < 5600 CFU/m3, a fungal total count < 2700 CFU/m3, and no β-hemolytic streptococcus were measured in the air supply of Guangzhou subway stations in China [39]. The total number of bacteria on the inner surface of the air duct was less than 362 CFU/m3, the total number of fungi was less than 87 CFU/m3, and the dust accumulation was less than 16.3 g/m3. By comparison, the median total number of fungi in the air supply system of Xi’an’s Metro Line 2 was previously found to be 900 CFU/m3, and the dust content on the surface area of the air ducts was less than 66.8 g/m3 [40]. After comparison, it was found that the total number of bacteria and fungi in the air supply decreased after cleaning, and the surface area dust, total number of fungi, and total number of bacteria in the air duct also decreased. Therefore, it is of great significance to clean the subway air conditioning system on time to ensure the air quality inside the stations and the healthy travel of passengers. Particularly for short periods of high personnel density and high mobility, it has more practical value.
This study is among the first to comprehensively evaluate cleaning effects using multiple complementary metrics: particulate matter mass/concentration, total bacterial/fungal counts in air supply, and dust accumulation on air duct walls. It also tested ophthalmology during stable periods of passenger flow in the same monitoring environment, excluding other interfering factors and clarifying the direct impact of filter cleaning on pollutant distribution. However, the impact of different operating hours on the sustainability of cleaning effectiveness was not considered; therefore, in the future, long-term tracking and monitoring could be carried out to further optimize the maintenance cycle of the ventilation system [41].
3.5. Comparison of Pollutant Concentrations with National and International Standards
To clarify the health implications of the study’s results, the measured concentrations of PM10 and PM2.5 (before and after air filter cleaning) are compared with the World Health Organization (WHO) Air Quality Guidelines (AQG) 2021 and China’s National Ambient Air Quality Standards (GB 3095-2012) [42,43], as shown in Table 3.
Table 3.
Comparison of PM10 and PM2.5 concentrations with national and international standards.
From Table 3, it can be seen that, before cleaning, all measured PM10 and PM2.5 concentrations met China’s national standards but exceeded WHO’s stricter air quality guidelines. For PM2.5 (a well-established respiratory hazard), the far air outlet concentration (46.9 μg/m3) was more than three times the WHO guideline value, indicating potential long-term exposure risks for passengers and staff in the subway’s semi-enclosed environment.
After cleaning, PM10 concentrations at the semi-far and far air outlets fell to or were below the WHO guideline (45 μg/m3), eliminating the associated exposure risks. While PM2.5 concentrations remained above the WHO guideline (due to the guideline’s stringency), cleaning reduced the far air outlet concentration by 44.2%, equating to a meaningful reduction in acute exposure risks, especially for vulnerable populations (e.g., children, the elderly, and individuals with pre-existing respiratory conditions). Although all post-cleaning concentrations complied with China’s national standards, the alignment of PM10 with WHO guidelines demonstrates that regular filter cleaning can significantly enhance the subway’s air quality beyond basic regulatory requirements. For PM2.5, further optimization (e.g., shorter cleaning cycles, high-efficiency filters) may be needed to meet the WHO’s health-protective thresholds, particularly in high-passenger-density stations. A comprehensive, multi-level approach must be adopted, with the main focus on improving the emission characteristics of train braking systems—one of the primary sources of fine particulate matter (including PM2.5) in subway environments. Train braking generates abraded particles from brake pads, discs, and wheel-rail contact, which contribute significantly to the high PM2.5 concentrations observed at far air outlets.
To address this core source, targeted technical improvements for braking systems should include: (1) adopting low-wear brake pad materials (e.g., ceramic matrix composites or polymer-based friction materials) to reduce particulate emission during braking; (2) installing on-board particle collection devices for brake systems to capture abraded particles before they diffuse into the station environment; (3) optimizing braking control strategies (e.g., regenerative braking priority) to minimize mechanical braking frequency and intensity, especially during peak passenger flow periods.
Complementary measures to enhance filter cleaning effectiveness should be integrated with braking system improvements, such as: (1) shortening the cleaning cycle for far air outlets (focused on small particle removal) to mitigate the accumulation of brake-generated PM2.5; (2) upgrading HEPA filters to higher-efficiency grades (e.g., H13 or H14) with enhanced capture capabilities for submicron particles; (3) optimizing air duct design to reduce airflow stagnation in remote areas, thereby minimizing secondary suspension of brake-derived particles.
This multi-level strategy—centered on source control (braking system optimization) and supplemented by end-of-pipe treatment (filter cleaning and upgrade)—addresses the root cause of persistent PM2.5 excess while maximizing the effectiveness of existing ventilation maintenance. By targeting the dominant emission source, subway operators can achieve more substantial and sustainable reductions in PM2.5 concentrations, moving closer to WHO’s health-protective guidelines and further safeguarding passenger health. With the continuous development of underground spaces [44,45,46,47], the health and safety of various workplaces directly affect the health of workers and the normal operation of equipment. Therefore, in the context of deep-sea and underground development and utilization, effective cleaning can better ensure the health of air quality and provide reference values for the creation of work and operation environments.
4. Conclusions
This study takes a representative subway line in Xi’an as the research object and systematically monitors and analyzes changes in the concentrations of particulate matter (PM10, PM2.5, PM1.0) and microorganisms and dust accumulation in a station before and after cleaning the ventilation system air filter. It reveals the spatial differentiation law of pollutants and the mechanism of cleaning effectiveness. The following innovative and practical conclusions are drawn from the results:
- The concentration of PM10 shows a decreasing trend with the increase in distance from the air filter. For example, the concentration at the far air outlet is 16.7% lower than that at the near air outlet due to the gravity-driven deposition of large particles in the air duct and the interception of deposited particles. In contrast, PM2.5 and PM1.0 show an increasing trend with the increase in distance. For example, the concentration of PM2.5 at the far air outlet is 22.4% higher than that at the near air outlet, and the concentration of PM1.0 is 19.7% higher due to the secondary suspension of small particles adhering to the pipe wall under the action of airflow when the wind speed in the remote air duct decreases. These spatial differentiation characteristics of different particle sizes complement the existing research on pollutant diffusion in subway ventilation systems.
- After cleaning, the concentration of pollutants of all particle sizes decreases significantly, but there is a clear spatial differentiation effect. For PM10, the maximum reduction rate (25.9%) occurs at the near air outlet, which is attributed to the enhanced inertial interception effect of the cleaned filter on large particles; for PM2.5 and PM1.0, the maximum reduction rates (44.2% and 42.7%, respectively) occur at the far air outlet. This is because the airflow at the far air outlet is fully diffused, and the light, small particles are more easily carried away by the unobstructed airflow after cleaning. This finding breaks the traditional understanding that “cleaning has a uniform effect on pollutants of different particle sizes” and provides a theoretical basis for targeted cleaning strategies.
- After cleaning, the counting concentration of particles of all sizes (0.2~1.0 μm, 1.0~2.5 μm, 2.5~10 μm, >10 μm) at each air outlet decreases significantly. For example, the reduction rate of large particles (>10 μm) at the near air outlet reaches 61.5%, and that of small particles (0.23~1.0 μm) at the far air outlet reaches 64.4%. At the same time, the total number of bacteria and fungi in the air supply and the dust accumulation on the inner surface of the air duct all meet the WS/T10013-2023 requirements. Compared with the pre-cleaning level of Xi’an and Guangzhou subway stations, the microbial concentration and dust accumulation are reduced by more than 60%, which verifies the comprehensive purification potential of filter cleaning.
- Practical guidance for maintenance optimization: The existing unified one-year cleaning cycle ignores the spatial differentiation of pollutant accumulation and cleaning effectiveness. Based on the research results, it is recommended that the cleaning cycle and method be adjusted according to the location of the air outlet: the near air outlet should focus on the removal of large particles, and the cleaning frequency can be appropriately reduced; the far air outlet should focus on the control of small particles and secondary suspension, and the cleaning intensity should be enhanced. This targeted maintenance strategy can balance air quality improvement and low-carbon operation goals, avoiding the resource waste caused by excessive cleaning or the insufficient purification effect caused by insufficient cleaning.
This study not only quantifies the effect of cleaning subway ventilation system filters but also reveals the spatial differentiation mechanism of pollutant distribution and cleaning effectiveness, which enriches the theoretical understanding of indoor air quality management in enclosed public spaces. The proposed targeted maintenance strategy provides a new practical path for the optimization of subway ventilation system operation and maintenance toward low-carbon goals. Future research can further explore the coupling effect of cleaning methods, ventilation parameters, and outdoor environmental factors on cleaning effectiveness, and establish a dynamic cleaning cycle model based on multi-factor comprehensive evaluation.
5. Limitations and Future Research Directions
This study provides valuable insights into the impact of air filter cleaning on pollutant distribution in subway stations, but it has several limitations that should be acknowledged to ensure scientific transparency and appropriate interpretation of the results:
First, the research was conducted at only one metro station on a single line in Xi’an. The selected station has specific characteristics, such as specific passenger flow patterns (more outbound passengers during morning rush hour and more inbound passengers during evening rush hour), a centralized mechanical ventilation system, and a fixed concourse-level monitoring environment. These unique attributes mean the results may not be directly generalizable to other metro stations. Second, the study tested during periods of stable passenger flow and did not account for extreme variations in crowd density (e.g., holidays, large-scale events) or spatial differences in passenger distribution within the station, which could affect pollutant generation and diffusion. Third, variables such as station layout (e.g., island vs. side platforms), ceiling height, air duct arrangement, and track depth were also not analyzed. These factors can alter airflow dynamics, pollutant deposition, and the effectiveness of ventilation systems, leading to different pollutant distribution patterns. Fourth, the study focused on a centralized mechanical ventilation system, but subway stations may adopt diverse ventilation designs (e.g., natural ventilation, hybrid systems, or different air supply/exhaust ratios), and the cleaning effect may vary across systems with distinct configurations or operational parameters. Fifth, while the study monitored particulate matter (PM10, PM2.5, PM1.0), bacteria, fungi, and dust accumulation, other relevant pollutants (e.g., volatile organic compounds, carbon monoxide, and heavy metals) were not included. Sixth, the detailed parameters of filter cleaning were not quantitatively controlled or fully recorded due to the constraints of subway operation management. Finally, the long-term sustainability of cleaning effects (e.g., how pollutant concentrations rebound over weeks or months post-cleaning) was not tracked, which limits insights into optimal maintenance cycles. Therefore, the conclusions of this study are only valid for metro stations with similar conditions to the tested site, including centralized mechanical ventilation systems, comparable passenger flow density, similar station geometry (e.g., concourse-level air outlet arrangement), and ambient environmental contexts. When extending the findings to other stations or cities, researchers and practitioners should consider the aforementioned variables and conduct site-specific validation.
Future research could address these limitations by (1) expanding the sample size to include multiple stations with diverse designs, locations, and ventilation systems; (2) conducting multi-season monitoring to account for ambient environmental variability; (3) integrating additional influencing factors (e.g., passenger density, track depth) into the analysis; and (4) performing long-term tracking of cleaning effectiveness to optimize maintenance strategies.
Author Contributions
Conceptualization, X.Z. and Z.H.; methodology, Z.H. and Y.J.; investigation, B.L. and S.D.; resources, X.Z. and S.D.; data curation, M.Z. and L.M.; formal analysis, M.Z. and R.T.; writing—original draft preparation, B.L., L.M. and R.T.; writing—review and editing, Y.J. and L.M. All authors have read and agreed to the published version of the manuscript.
Funding
This study was supported by the Application Research Center of Smart Energy Technology of Mianyang City College (no. ZHNY-2025-15), the Shaanxi Provincial Department of Education Service Local Special Plan Project (no. 24JC050), the National Natural Science Foundation of China (no. 52278122), the Zhejiang Provincial Natural Science Foundation of China under grant no. ZCLQN26E0801, and the Scientific Research Fund of Zhejiang Provincial Education Department under grant no. Y202559062.
Institutional Review Board Statement
Not applicable.
Informed Consent Statement
Not applicable.
Data Availability Statement
Not applicable.
Conflicts of Interest
The authors declare no conflicts of interest.
References
- Lin, S.; Yu, T.; Huang, J. Subway Openings and Urban Air Pollution Mitigation: Pathways to Sustainable Development in China. Sustainability 2025, 17, 4782. [Google Scholar] [CrossRef] [Scilit]
- Geng, F.; Li, L.; Huang, R.; Li, S.; Shi, W.; Chang, B.; Peng, Z.; Xia, Y. Dust removal process of the multi-filter cartridges and its optimization measures for coal dust pollution: Experimental and numerical investigations. J. Environ. Chem. Eng. 2025, 13, 115715. [Google Scholar] [CrossRef] [Scilit]
- He, W.; Guo, Y.; Liu, J.; Zhou, X.; Hu, L.; He, K.; Lin, X. Experimental and numerical Investigation of fine particle emissions from damaged Membrane-Coated filter bag. Adv. Powder Technol. 2025, 36, 104985. [Google Scholar] [CrossRef] [Scilit]
- Zhang, X.; Ma, J.; Wang, J.; Shi, H.; Guo, J.; Fan, Y.; Nie, X.; Guo, T.; Luo, X. Modifying the Fiber Structure and Filtration Performance of Polyester Materials Based on Two Different Preparation Methods. Langmuir 2023, 39, 3502–3511. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- Lü, J.L.; Han, Q.; Wang, Z.; Tao, M.; Hu, X.; Cao, M.; Huang, Q.; Shi, M.; He, Z.; Zhao, X. Characteristics, sources, and health risks of fine particulate matter in Wuhan subway, China. Sci. Total Environ. 2025, 967, 178842. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- Sherman, R.L.; Firth, A.U.; Henley, S.J.; Siegel, R.L.; Negoita, S.; Sung, H.; Kohler, B.A.; Anderson, R.N.; Cucinelli, J.; Scott, S.; et al. Annual Report to the Nation on the Status of Cancer, featuring state-level statistics after the onset of the COVID-19 pandemic. Cancer 2025, 131, e35833. [Google Scholar]
- Yu, W.Z.; He, D.; Liu, C.; Lan, J.; Li, G.; Xia, S. Study on optimization operation strategy of metro station air conditioning system with variable water temperature. Therm. Sci. 2025, 29, 1909–1917. [Google Scholar] [CrossRef] [Scilit]
- Resen, I.S.; Alsayah, A.M.; Alshukri, M.; Eidan, A.A.; Ali, S.; Faraj, J.; Khaled, M. Exergy analysis of the effects of extreme hot conditions on cooling system efficiency: A case study of a split air conditioner. Case Stud. Chem. Environ. Eng. 2025, 11, 101187. [Google Scholar] [CrossRef] [Scilit]
- Kiviruusu, O.; Ranta, K.; Lindgren, M.; Haravuori, H.; Silén, Y.; Therman, S.; Lehtonen, J.; Sares-Jäske, L.; Aalto-Setälä, T.; Marttunen, J.; et al. Mental health after the COVID-19 pandemic among Finnish youth: A repeated, cross-sectional, population-based study. Lancet Psychiatry 2024, 11, 451–460. [Google Scholar]
- Ildiri, N.; Biesiada, E.; Facchinetti, T.; Anglani, N.; Ahmed, N.; Hernandez, M. Impacts of HVAC cleaning on energy consumption and supply airflow: A multi-climate evaluation. Energy Build. 2025, 328, 115147. [Google Scholar]
- GB19210-2003; Cleaning Code for Air Dust System in Heating, Ventilating, and Air Conditioning Systems. Standardization Administration of the People’s Republic of China: Beijing, China, 2003.
- Zhao, B.; Yang, J.; Cao, S.; Lv, C.; Fan, S.; Sun, T.; Chen, N. Design of a vacuum-type PV module cleaning robot based on an auxiliary mobile frame. Sol. Energy 2024, 275, 112634. [Google Scholar] [CrossRef] [Scilit]
- Chen, Y.Z.; Zhang, W.G.; Tsoutsanis, E.; Zhao, J.; Tam, I.C.K.; Gou, L.F. An advanced performance-based method for soft and abrupt fault diagnosis of industrial gas turbines. Energy 2025, 321, 135358. [Google Scholar] [CrossRef] [Scilit]
- Mei, Y.; Zhou, D.; Wang, H.; Ke, X.; Liu, Z.; Tian, X.; Wang, Z. Study on carbon emission calculation during the materialization phase of subway stations and comparative analysis of carbon emissions from various construction methods. Case Stud. Constr. Mater. 2024, 21, e03923. [Google Scholar] [CrossRef] [Scilit]
- Neukirchen, C.; Meiners, T.; Bendl, J.; Zimmermann, R.; Adam, T. Automated SEM/EDX imaging for the in-depth characterization of non-exhaust traffic emissions from the Munich subway system. Sci. Total Environ. 2024, 915, 170008. [Google Scholar] [CrossRef] [Scilit]
- Tsang, T.W.; Mui, K.W.; Wong, L.T. Indoor Air Quality (IAQ) Management in Hong Kong: The Way Forward. Atmosphere 2024, 15, 546. [Google Scholar] [CrossRef] [Scilit]
- Szczepanik-Scislo, N.; Grządziel, D.; Mazur, J.; Kozak, K.; Schnotale, J. Influence of Human Activity on Radon Concentration, Indoor Air Quality, and Thermal Comfort in Small Office Spaces. Sensors 2024, 24, 4949. [Google Scholar] [CrossRef] [Scilit]
- Sun, Y.; Xiang, Y.; Chen, Y.; Xu, D.; Wang, T.; Zeng, F.; Bao, Y.; Zhao, L.; Li, Y.; Xia, Q.; et al. Impacts of subway air particles on healthy adults: A randomized controlled trial in a Chinese city. Part. Fibre Toxicol. 2025, 22, 18. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- Dinh, T.V.; Park, B.G.; Lee, S.W.; Choi, I.Y.; Baek, D.H.; Kim, J.C. Long-Term Evaluation of Mid-Cost Optical Particle Counters for PM2.5 Monitoring in an Underground Subway Station: Insights from a 15-Month Study. Chemosensors 2025, 13, 25. [Google Scholar] [CrossRef] [Scilit]
- Plazas, F.L.; Tejada, C.S.D. Natural ventilation to improve indoor air quality (IAQ) in existing homes: The development of health-based and context-specific user guidelines. Energy Build. 2024, 314, 114248. [Google Scholar] [CrossRef] [Scilit]
- Zhang, X.; Sun, H.; Li, K.; Nie, X.; Fan, Y.; Wang, H.; Ma, J. Comparison of the Application of Three Methods for the Determination of Outdoor PM2.5 Design Concentrations for Fresh Air Filtration Systems in China. Int. J. Environ. Res. Public Health 2022, 19, 16537. [Google Scholar] [CrossRef] [Scilit]
- Zou, L.; Wang, Z.; Guo, R.; Zhao, L.; Ma, L. Urban dynamics unveiled: A comprehensive analysis of Beijing’s subway evolution over the past decade. Tunn. Undergr. Space Technol. 2025, 157, 106284. [Google Scholar] [CrossRef] [Scilit]
- Lee, Y.; Kim, Y.S.; Lee, G.; Lee, H.; Kim, Y.J.; Han, B.; Kim, H.J. Development of an Electrostatic Precipitator with a Novel Dry-Cleaning Apparatus for Building Ventilation Systems. Indoor Air 2025, 2025, 9929558. [Google Scholar] [CrossRef] [Scilit]
- Gautam, L.; Sahu, V.; Singh, R.; Thiyagarajan, S.V.; Suseelan, A. Sustainable solutions for metro project delays: Lean practices for enhanced resource efficiency and cleaner production. Sustainability 2024, 16, 10897. [Google Scholar] [CrossRef] [Scilit]
- Caro, L.A.P.; Balela, M.D.L.; Raguindin, R.K.M. Surface Treatment of Cotton Fabric Using Aloe vera-Modified ZnO Nanoparticles for Self-cleaning and UV-Protective Coating. Fibers Polym. 2025, 26, 5475–5486. [Google Scholar]
- Wu, H.Y.; Yang, K.; Chen, K.; Zhou, W.; Yu, T.; Wang, K. GHG emission quantification and reduction pathway of subway shield tunnel engineering: A case study on Guangzhou Metro, China. Environ. Sci. Pollut. Res. 2024, 31, 54768–54784. [Google Scholar] [CrossRef] [Scilit]
- Chen, M.; Wang, Q. Ventilation Optimization Based on Spatial-Temporal Distribution and Removal Efficiency of Patient-Exhaled Pollutants in Hospital Wards During the Post-Epidemic Period. Buildings 2024, 14, 3827. [Google Scholar]
- Wang, X.; Liang, H. Application of Physical Modeling and Virtual Simulation Technology in Measuring the Performance of Subway Train Tracking and Operation. Scalable Comput. Pract. Exp. 2024, 25, 4274–4282. [Google Scholar]
- Zolfaghari, N.; Alahabadi, A.; Delsouz, M.; Adab, A. An integrated approach to optimal siting of air quality monitoring networks: Fuzzy based decision-making, multi-pollutant methodology, and health risk assessment. Urban Clim. 2025, 63, 102588. [Google Scholar]
- Song, J.; Zhang, Y.Z.; Huang, Y.; Wang, P.; Yang, Y.Y. Ventilation strategy for particulate matter control in subway stations. J. Build. Eng. 2024, 98, 111323. [Google Scholar] [CrossRef] [Scilit]
- Camelli, F.E.; Byrne, G.; Löhner, R. Modeling subway air flow using CFD. Tunn. Undergr. Space Technol. 2025, 63, 102588. [Google Scholar]
- Xian, L.; Yuan, Y.H.; Zhang, X. Impact of Subway Platform Screen Door Opening and Closing on Particulate Matter Concentration Distribution at Different Locations and Times: The Case of Xi’an. Buildings 2026, 16, 356. [Google Scholar] [CrossRef] [Scilit]
- Sampaio, N.A.S.; Mazza, F.C.; de Siqueira, S.S.S.; Junior, J.E.M.; de Souza Moutinho, J.V.; de Oliveira Pacífico, L. Applications of Correlation Analysis in Environmental Problems. Rev. Gestão Soc. E Ambient.—RGSA 2024, 18, e04925. [Google Scholar] [CrossRef] [Scilit]
- Guo, L. Study on the Deposition of Particulate Matter in the Urban Rail Vehicle Air Conditioning Duct. Master’s Thesis, Qingdao University of Technology, Qingdao, China, 2015. (In Chinese) [Google Scholar]
- Wu, X.; Ling, R.; Wan, X.; Ren, H.; Jing, X.; Feng, G. Study on the Impact of Ventilation Methods on Droplet Nuclei Transmission in Subway Carriages. Appl. Sci. 2025, 15, 4919. [Google Scholar] [CrossRef] [Scilit]
- Pata, S.K.; Pata, U.K.; Wang, Q. Ecological power of energy storage, clean fuel innovation, and energy-related research and development technologies. Renew. Energy 2025, 241, 122377. [Google Scholar] [CrossRef] [Scilit]
- Chen, Z.; Fu, S.; Wang, L. LBM-DEM Simulation of Particle-Laden Flow Around Porous Microspheres: Effect of Particle Retention. Transp. Porous Med. 2025, 152, 36. [Google Scholar] [CrossRef] [Scilit]
- WS/T10013-2023; Hygienic Specification of Central Air Conditioning Ventilation System in Public Places. National Disease Control and Prevention Administration: Beijing, China, 2023.
- Jiang, S.L.; Shi, T.X.; Lv, J.Y.; Shi, J.; Liu, J.H.; Liu, P.D. Microbial contamination status of centralized air conditioning ventilation systems in metros in Guangzhou City. Pract. Prev. Med. 2016, 23, 1113–1115. (In Chinese) [Google Scholar]
- Liu, P.; Zhang, F.; Ma, J.L.; Wu, X.Y.; Liu, X.M.; Zhao, Y.G. Survey on microbial contamination in the central air conditioning system before and after the operation of metro line 2 in Xi’an. Mod. Prev. Med. 2014, 41, 2140–2142+2153. (In Chinese) [Google Scholar]
- Shaban, I.A.; Salem, H.; Abdullah, A.Y.; Ameri, H.M.A.Q.A.; Alnahdi, M.M. Maintenance 4.0 for HVAC systems: Addressing implementation challenges and research gaps. Smart Cities 2025, 8, 66. [Google Scholar] [CrossRef] [Scilit]
- World Health Organization. WHO Global Air Quality Guidelines: Particulate Matter (PM2.5 and PM10), Ozone, Nitrogen Dioxide, Sulfur Dioxide and Carbon Monoxide; World Health Organization: Geneva, Switzerland, 2021. [Google Scholar]
- GB 3095-2012; Ambient Air Quality Standards. Standardization Administration of the People’s Republic of China: Beijing, China, 2012.
- Wu, S.; Zhang, Z.; Chen, J.; Yao, Y.; Li, D. Characterisation of stress corrosion durability and time-dependent performance of cable bolts in underground mine environments. Eng. Fail. Anal. 2023, 150, 107292. [Google Scholar] [CrossRef] [Scilit]
- Wu, S.; Ma, X.; Zhang, X.; Chen, J.; Yao, Y.; Li, D. Investigation into hydrogen induced fracture of cable bolts under deep stress corrosion coupling conditions. Tunn. Undergr. Space Technol. 2024, 147, 105729. [Google Scholar] [CrossRef] [Scilit]
- Wu, S.; Zhu, M.; Zhang, Z.; Yao, Y.; Li, Y.; Li, D. Prediction and risk assessment of stress corrosion failures of prestressed anchors in underground mines. Int. J. Min. Reclam. Environ. 2025, 1–15. [Google Scholar] [CrossRef] [Scilit]
- Wu, S.; Hao, W.; Yao, Y.; Li, D. Investigation into durability degradation and fracture of cable bolts through laboratorial tests and hydrogeochemical modelling in underground conditions. Tunn. Undergr. Space Technol. 2023, 138, 105198. [Google Scholar] [CrossRef] [Scilit]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2026 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.