Abstract
In cooling-dominated countries, energy codes rate windows by area-weighted U-values and solar gain, and the heat flow at the joint between the window and the wall is ignored. This paper quantifies that missing term for Gulf-type masonry walls. A 2-D COMSOL Multiphysics model was used to analyse 85 installation details (three walls, three frames, five installation depths, three insulation-return levels and three insulation thicknesses), and more than 500 further simulations addressed the questions left open by this first set. For the ISO 10211 benchmarks, the largest temperature deviation was 0.05 K and the heat-flow deviation was below 0.1%. In the mesh study, the linear thermal transmittance of the installation, ψinst, on the production mesh was 1.6% above the Richardson-extrapolated value (0.1423 against 0.1400 W/(m·K)), and it changed by at most 0.0003 W/(m·K) for the extreme details. ψinst was 0.015–0.024 W/(m·K) when the mid-plane of the frame was aligned with the mid-plane of the insulation, and 0.3–0.65 W/(m·K) when the frame sat in the uninsulated reveal. This long-standing alignment principle, written here as a simple closed-form expression, located the optimum position within |Δp| ≤ 0.022 (about 5 mm at most) for eight walls and two parameter grids, including walls that were not used to derive it. The results were not sensitive to the block and XPS conductivities or to the frame-cavity assumptions. A 20 mm insulation lip over the frame reduced ψinst by 56–62% for deep installations. In a transient design-day simulation for Madinah, the daily heat gain through the junction of the externally insulated wall was 6–8% lower than the steady estimate; for the cavity-wall optimum, where the gain is close to zero, the transient result was slightly negative (−3.2 Wh/m) and the steady estimate slightly positive (+6.3 Wh/m). The frame type controls the interior surface temperature. In the cooling case, the aligned joint is the coolest point (25.4–26.6 °C); condensation was not simulated. Measurements of ψinst for the same details are still needed.
1. Introduction
Cooling is a primary energy consumer in buildings in the Gulf region. In summer, air-conditioning in Saudi Arabia accounts for about 70% of total residential electricity consumption, and national electricity consumption has been increasing by 7% per year [1]. The building envelope determines the load the air-conditioning plant must carry, and envelope measures are an important means of reducing it. Regional studies indicate that the effect varies with the changes made. Wall insulation provided the greatest cooling benefits in an apartment in Al Ain (UAE).
In the same study, the solar heat gain coefficient of the glazing was more important than its U-value [2]. Insulation decreased energy demand by about 2–14% across five climate zones in Saudi Arabia; however, in Abha, a highland city in Saudi Arabia, it increased cooling demand in a few cases [3]. Window-to-wall ratio limits have been suggested for Riyadh and Abha [4]. A comparison of four GCC codes for a house in Bahrain showed that the Abu Dhabi ESTIDAMA 1 requirements reduced the energy use by 24.4%, against 14.6% for the Saudi code [5].
Most national codes, such as the Saudi Building Code [6], still determine the U-value and solar heat gain coefficient of windows on an area-weighted basis. The joint where the window frame meets the wall does not appear as a separate term in that calculation. We demonstrated in a recent regulatory review [7] that SBC 601, ASHRAE 90.1 and the IECC do not require a linear thermal transmittance, ψ, although standardised numerical tools exist to calculate it. This review was based on literature values and a simple analytical scenario, without calculating any junction.
Thermal bridges are known to be significant, but their magnitude is unclear. In a full-scale test room, infrared (IR) thermography revealed that nine types of thermal bridges increased envelope heat loss by approximately 9% [8]. European countries use multiple approaches to treat thermal bridges in energy calculations, as reported in [9], a survey of compliance procedures. In renovated apartment buildings, the thermal transmittance of the entire wall varied significantly with junction type [10]. Researchers now typically quantify these junctions using finite element analysis (FEA), and energy-use increases from thermal bridging in windows are approximately 5–30% [11,12].
Wall-level bridges have been documented in hot climates. Zedan et al. [13] coupled a 2-D dynamic heat-transfer model with a whole-building model and found that mortar-joint bridges in insulated walls increased the annual cooling load of a Riyadh villa by approximately 3–11%. Al-Awadi et al. developed steady- and dynamic 2-D bridge models for four wall types in a hot climate using COMSOL Multiphysics. They found that external insulation (EIFS) performed best [14]. Alayed et al. demonstrated that uninsulated concrete elements lost more than twice as much heat as the insulated walls, that neglecting solar radiation on a west-facing façade may result in errors exceeding 50%, and that external insulation of 40–80 mm could reduce the bridging effect by up to 73% [15].
Windows have been widely studied. Finite-volume models of PVC frames validated against reference examples provided by the ISO 10077-2 and hot-box measurements show that the frame transmittance is most sensitive to the air-gap properties [16], and hot-box measurements of high-performance frames agree well overall with finite-volume and CFD models [17]. For hot climates, parametric simulations for Dhahran and Abha indicate that non-metallic frames reduce the frame U-value much more than increasing aluminium thickness or adding cavity insulation. Optimised frames can save up to 9% and 8% of annual cooling energy [18]. Researchers have also explored the climatic optimisation of glazing combinations, for example, for Slovenia [19].
Less attention has been paid to the frame-to-wall junction. Ibrahim et al. showed that windows set back from the wall face create thermal bridges corresponding to 2–8% of the total house load, and that a thin insulating coating reduces this load by 24–50% for a French house [20]. In Greece, measured and simulated heat flux at the frame–floor joint differed by about 7% (1250 W/m2 vs. 1168 W/m2) for an aluminium-framed baseline, and insulating barriers reduced the leakage [21]. Misiopecki et al. simulated five wall constructions and two windows to find the most energy-efficient window position and concluded that the best position can reduce ψ by more than 50% [22]. Gendelis et al. optimised the mounting position for insulated retrofit walls and reported about 0.02 W/(m·K) for a frame installed in the insulation layer, with further reductions from frame extenders and insulation overlap [23]. Šadauskienė et al. analysed a new high-performance installation with 2-D and 3-D models and separated the linear contribution from the point contribution of the fasteners [24]. Pomada et al. proposed an installation system that eliminates the linear bridge and compared their numerical model with wall-surface temperatures measured on a building [25]. A good detail can have a large effect, as shown by the 96% reduction in ψ reported for the best of five patented slab-front designs [26]. Table 1 summarises these studies.
Table 1.
Selected studies on thermal bridges at window and wall junctions and in hot climates, and the position of the present study.
Four gaps remain. First, most installation studies come from heating climates and deal with Central-European masonry and timber walls; how the same details behave in Gulf masonry walls, where the frames are commonly unbroken aluminium, has not yet been mapped. Second, researchers typically investigate installation depth separately for each wall; it is unclear whether the optimal depth varies by wall type and, if so, whether a general rule exists. Third, most numerical studies verify their models on a few selected details only, and few measurements of ψinst itself are available [27]. Fourth, the connection between the junction ψ and the cooling-season conduction gain (important in the Gulf) is rarely stated explicitly.
It should be stated clearly what is already known. That a frame placed in the insulation plane gives the lowest ψ, and that an insulation overlap reduces the bridge, has been shown for heating-climate walls [22,23]. In those studies, the optimum was located by sweeping the position for each wall. The present study does not claim the principle. Instead, it adds (i) a practical, closed-form expression of this long-standing principle, which gives the position from the layer dimensions alone instead of a position sweep for each wall; (ii) a blind test of that rule on walls that were not used to derive it; (iii) the quantification for Gulf masonry, including the uncertainty from mesh, material conductivities and frame-cavity assumptions; and (iv) the hot-climate side of the problem, i.e., the dynamic cooling-season gain with solar load and the temperature of the joint as an indicator of condensation risk in hot–humid cities.
To fill these gaps, this paper presents a parametric 2-D heat-conduction analysis of the window-to-wall junction. It mainly provides the following:
- •
- A catalogue of 85 verified junction details for three masonry wall types, three frames, five installation depths and three insulation returns, with ψinst and the minimum interior surface temperature of each case;
- •
- A practical alignment rule (Equation (8)), i.e., the known alignment principle written in closed form, that gives the lowest-ψinst position from the wall section, checked by a fine position sweep and by a blind test on four further walls, and confirmed on continuous parameter grids;
- •
- Verification of the COMSOL model against the ISO 10211 benchmarks, a mesh-convergence study that includes extreme details, the heat balance of all cases, and a sensitivity analysis of the material and cavity assumptions;
- •
- A hot-climate interpretation: A transient design-day simulation for Madinah with solar load; the conductive gain through the joint for Madinah, Riyadh and Jeddah; the interior hot spot caused by the frame type; and the joint temperature compared with indicative outdoor dew points.
The problem and the numerical method, including the transient model and the variance decomposition, are presented in Section 2. Section 3 reports the verification and what is and is not verifiable. The results are given in Section 4; the comparison with the literature, construction feasibility, hygrothermal behaviour and code implications are discussed in Section 5; and Section 6 concludes. The workflow is shown in Figure 1.
Figure 1.
Methodology of this study. The numbered stages (1–5) run from the code gap to the design rule; the boxes below each stage list the work done; the amber box is the experimental context used to judge the model, and the dashed box is the feedback loop through which the additional checks of this revision were fed back into the model.
2. Materials and Methods
2.1. Junction Details and Parameters
The model is a vertical section through the window head or sill region, with the window glazing running along the vertical axis, so that the geometry is a 2-D slice through a wall of thickness, t, and a window frame of depth of Df = 60 mm (Figure 2 and Figure 3). The wall extends lw = 1.0 m below the opening, which satisfies the ISO 10211 cut-off rule of at least one metre or three wall thicknesses [28], and the glazing extends 190 mm above the frame. Both cut planes are adiabatic.
Figure 2.
Wall types, exterior on the left: (a) W1, 20 mm render + 200 mm hollow block + 20 mm render (t = 240 mm); (b) W2, 20 mm render + 50 mm XPS (EIFS) + 200 mm block + 20 mm render (t = 290 mm); and (c) W3, 20 mm render + 100 mm block + 50 mm XPS + 100 mm block + 20 mm render (t = 290 mm). The horizontal axis is the distance from the exterior wall face and the vertical axis is the distance from the reveal (y = 0), negative along the wall and positive along the glazing, both in metres and identical in all panels. The 60 mm frame is shown at the mid-depth position of p = 0.5.
Figure 3.
Frame types, drawn in the (u, v) plane of the junction: (a) F1, aluminium without thermal break; (b) F2, aluminium with a 24 mm polyamide break; (c) and F3, five-chamber uPVC. All three carry a double-glazing unit (6/12/6 mm) with EPDM gaskets, and the unventilated cavities are replaced with equivalent conductive solids.
We varied five factors (Table 2). The installation position is expressed as the dimensionless depth,
where xf is the distance from the exterior wall face to the exterior face of the frame, so p = 0 puts the frame flush with the exterior face, and p = 1 puts it flush with the interior face. The insulation return is a 20 mm XPS lining of the reveal, with an optional 20 or 40 mm lip that overlaps the frame; it applies to the external-insulation wall W2. The complete matrix has 85 cases: 3 walls × 3 frames × 5 positions with no return (45 cases), 2 extra return levels for the 15 W2 combinations (30 cases) and 2 extra insulation thicknesses for W2 with the F2 frame at five positions (10 cases).
Table 2.
Parameter matrix of this study (85 cases).
The hollow block is represented by an equivalent conductivity of 1.0 W/(m·K). This value stands for a 200 mm two-cell hollow concrete block laid in cement mortar, the most common masonry unit in residential buildings of the region; it lumps the concrete webs, the air cells and the mortar joints into one homogeneous layer and gives a 1-D transmittance of 2.35 W/(m2·K) for the uninsulated wall, W1. The exact value depends on block geometry and density, so it was varied from 0.5 to 1.4 W/(m·K) in Section 4.4. In Table 3, the block, the gas layer of the glazing unit and the frame cavities (Equation (4)) are equivalent model parameters, while the other values are tabulated properties of real materials [29,30]. The three walls represent the uninsulated block wall, the block wall with external insulation (EIFS) and the sandwich wall with insulation between two block leaves, which are the wall types commonly built in the region.
Table 3.
Material conductivities used in all models; (e) marks equivalent model parameters, all other values are properties of real materials. Frame cavities use the equivalent conductivity of Equation (4).
2.2. Governing Equations and Boundary Conditions
Heat flow is steady and conductive, with no heat generation:
The exterior and interior surfaces exchange heat through combined convective-radiative film coefficients, h = 1/Rs, with Rsi = 0.13 and Rse = 0.04 m2·K/W from ISO 6946 [31]:
Two boundary sets were run. The ISO set uses Ti = 20 °C and Te = 0 °C and serves as the basis for ψinst. The cooling set uses Ti = 24 °C and Te = 45 °C, a typical Gulf design condition where 45 °C is an exterior sol-air-type temperature (outdoor air of about 40–43 °C plus the absorbed solar term αI·Rse). Because the model is purely conductive with temperature-independent properties, heat flow scales exactly with the temperature difference, so ψinst is the same in both sets; only the heat-flow magnitude and surface temperatures change. We checked this numerically (Section 3).
Combining a sol-air temperature with the standard surface resistance is an approximation, because the solar part is then exchanged through the same film coefficient as the air temperature. For the steady analysis, this has no effect on ψinst, which is independent of the boundary temperatures; the cooling set only illustrates the magnitude of the heat flow and the surface temperatures. Where the exterior boundary matters, i.e., for the energy figures, the transient model of Section 2.5 applies the outdoor air temperature and the absorbed solar flux separately.
Unventilated frame cavities were replaced by solid blocks with an equivalent conductivity from ISO 10077-2 [29],
where the convective part is ha = max(C1/d, C2 ΔT1/3) (C1 = 0.025 W/(m·K), C2 = 0.73 W/(m2·K4/3), ΔT = 10 K), radiative part is hr = 4σTm3EF, mean temperature is Tm = 283 K, emissivity is 0.9 on both faces and F is the rectangular-cavity view factor. The cavity depth d is taken in the heat-flow direction, and b is the cavity width. The gas layer of the glazing unit was modelled with k = 0.0271 W/(m·K); no spacer is modelled, which is a simplification discussed in Section 5.
These cavity assumptions (ΔT = 10 K, ε = 0.9 and Tm = 283 K) follow ISO 10077-2 for heating conditions. Their influence was checked for hot conditions in Section 4.4 by varying ΔT from 5 to 20 K, the emissivity to 0.3 (bare aluminium) and the mean temperature to 313 K.
2.3. Linear Thermal Transmittance and Surface Temperature
For each case, we integrated the total heat flow, Φ, through the interior boundary. The linear coupling coefficient is then Ltot = Φ/(Ti − Te), as in ISO 10211 [28]. The installation transmittance is the part of Ltot that is neither the 1-D wall nor the window on its own:
where Uw is the 1-D transmittance of the wall, and Lwin is the coupling coefficient of the window frame and glazing modelled alone with the same cut planes. Lwin was obtained from separate models of each frame: 0.794, 0.484 and 0.389 W/(m·K) for F1, F2 and F3 with the glazing unit. The frame transmittances Uf then follow the same models, with an insulating panel in place of the glazing, as in ISO 10077-2: Uf = 7.39, 2.81, and 1.19 W/(m2·K). The frame–glazing edge term of the window alone, ψg = Lwin − Ug lg − Uf bf, is 0.046, 0.011 and 0.014 W/(m·K), but it cancels out of ψinst because it appears in both Ltot and Lwin. Surface-temperature risk is expressed with the temperature factor.
Because ψinst is a difference, it can be slightly negative. This happens when the installed assembly loses less heat than the sum of the two references, for example, when an insulation lip covers the exterior face of the frame and lengthens the heat-flow path compared with the isolated window; the total heat flow, Φ, itself remains positive.
where Tsi,min is the lowest temperature on the interior surface; the corresponding mould criterion of ISO 13788 [32] for 20 °C and 50% relative humidity with an 80% surface limit is fRsi ≥ 0.63. In the cooling case, the quantity of interest is the opposite: the highest interior surface temperature, Tsi,max, which marks a hot spot.
2.4. COMSOL Implementation
The COMSOL Multiphysics 5.6 model [33] uses the standard Heat Transfer in Solids interface and a stationary study. The geometry is built from rectangles, with material assignment by named selections; exterior boundaries are split into exterior and interior groups at the frame mid-depth plane x = xf + Df/2, and the two cut planes are excluded. The mesh is a free triangular mesh with quadratic Lagrange elements, a maximum element size of 5 mm and a minimum of 0.25 mm (about 35,000 elements per case). The heat balance between the exterior and interior boundary integrals is closed to better than 10−9 in all 85 cases.
At the frame–wall interface, the 10 mm polyurethane foam joint is in perfect thermal contact with the reveal and the frame, and no contact resistance is applied. The same joint, the same split of the exposed boundaries at the frame mid-depth and the same adiabatic cut-off planes are used for the three frames, so that the frames differ only in their sections. The surfaces of the joint and the reveal that face the opening are exterior surfaces when they lie on the exterior side of the frame mid-plane and interior surfaces otherwise.
The COMSOL plots (mesh, temperature, and heat flux) show the base case W2/F2 with p = 0.5 and a 20 mm lip, which best illustrates the mechanism (Figure 4).
Figure 4.
COMSOL results for the base case (W2 wall, F2 frame, p = 0.5, 20 mm lip), ISO set 20/0 °C, zoomed in on the junction: (a) free triangular mesh, refined in the frame and at the reveal corner; (b) temperature with isotherms (°C); and (c) logarithm of the heat-flux magnitude (W/m2) with heat-flow lines, showing the concentration of flow at the corner between the uninsulated reveal and the frame.
2.5. Transient Design-Day Model
To check the cooling-season figures against a more realistic exterior condition, four installed details (W2/F2 at p = 0, at p = 1 without and with a 20 mm lip, and W3/F2 at p = 0.5), the two walls alone and the F2 window alone were solved with the time-dependent Heat Transfer in Solids interface. The exterior surfaces exchange heat with the outdoor air through Rse, and the absorbed solar flux is applied separately as an inward heat flux, −k ∂T/∂n = (T − Tair(t))/Rse − αsI(t), so that no sol-air temperature is needed. A Madinah July design day was used for a west façade: Tair(t) = 36.5 + 7 cos(2π(t − 15)/24) °C, with t in hours, and a clear-sky irradiance I(t) = 700 sin(π(t − 12)/7) W/m2 between 12:00 and 19:00, and zero otherwise, with αs = 0.6 [34]. The interior is held at 24 °C through Rsi. All materials have their real density and specific heat (ISO 10456 [30]); five periodic days were computed and the fifth day is evaluated. The daily heat gain through the junction is the integral of qj(t) = Qinst(t) − Qwall(t) − Qwin(t) over 24 h, i.e., the transient counterpart of Equation (5).
2.6. Variance Decomposition
The relative influence of the factors (Section 4.5) is expressed by a descriptive decomposition of the variance of the deterministic results, not by an inferential analysis of variance; no significance levels are implied. For a factor A with levels l, the main-effect sum of squares is SSA = Σl nl(ȳl − ȳ)2, where ȳl is the mean ψinst of the nl cases at level l, and ȳ is the mean of the subset. The share reported for A is SSA/SST, with the total sum of squares SST = Σi(yi − ȳ)2 of the same full-factorial subset as denominator. Because each subset is a complete factorial, the main effects are orthogonal and the remainder 1 − ΣSSA/SST is the sum of all interaction terms. The shares depend on the levels chosen and are used only to rank the factors within the studied ranges.
3. Verification and Experimental Context
3.1. ISO 10211 Benchmark Cases
ISO 10211 Annex C gives two reference cases with tabulated temperatures and heat flow [28]. Case 1 is a 2-D half-square column with prescribed temperatures (28 comparison points). Case 2 is a 2-D thermal bridge with a metal sheet, a wood block, and concrete (9 temperature points and total heat flow), with conductivities spanning 0.029 to 230 W/(m·K). The largest temperature deviation was 0.048 K for Case 1 and 0.039 K for Case 2, both under the 0.1 K criterion. The Case 2 heat flow was 9.492 W/m against 9.5 W/m (Figure 5a,b; Table 4).
Figure 5.
Verification of the COMSOL model. (a) COMSOL against ISO 10211 Annex C reference temperatures (Case 1: 28 points; Case 2: 9 points). (b) Deviation at each point with the ±0.1 K criterion. (c) Mesh study of ψinst for the base case with the Richardson-extrapolated value; labels give the element count.
Table 4.
Summary of verification evidence.
3.2. Mesh Convergence
The base case was solved on five meshes whose maximum size was halved each time, from 20 mm (8759 elements) to 1.25 mm (478,842 elements). With the three finest meshes, the observed order and the Richardson-extrapolated value follow Roache [35]:
where f1 is the finest-mesh value, r = 2 is the refinement ratio and q is the observed order of convergence. The coupling coefficient converged with q = 1.30, fext = 1.1514 W/(m·K), and a grid convergence index of 0.04% on the finest pair (Figure 5c). For ψinst, the production mesh (35,046 elements, 5 mm) gives 0.1423 W/(m·K), the finest mesh gives 0.1404 W/(m·K), and the Richardson-extrapolated value is 0.1400 W/(m·K) (Table 4). The production mesh is therefore 0.0023 W/(m·K), i.e., 1.6%, above the extrapolated value, and the finest mesh is 0.3% above it. Because ψinst is a small difference between large numbers, the absolute error in the production runs is about 0.002–0.003 W/(m·K) for a detail of this size; this should be kept in mind for values below 0.05 W/(m·K). To check this estimate where it matters most, the mesh study was repeated for five extreme details: the negative-ψinst case (W2/F1, p = 0, 40 mm lip), the cavity-wall optimum (W3/F2, p = 0.5), the deepest installation (W2/F2, p = 1) and the two lowest values of the thick EIFS wall (W2/F2, 100 mm, p = 0 and 0.25). For each mesh level the window-only reference was solved on the same mesh, so that both terms of Equation (5) carry consistent discretisation errors. Over 7600–558,000 elements, ψinst changed by at most 0.0003 W/(m·K) in all five cases (Figure 6), and the negative value of −0.0123 W/(m·K) was the same on all meshes. The direct uncertainty of ψinst is therefore about ten times smaller than the estimate above, and the optimum values (0.015–0.024 W/(m·K)) are 50–80 times larger than it. These two estimates are used as follows. The 1.6% production-mesh error corresponds to 0.002–0.003 W/(m·K) for the larger ψinst values, but near the optimum, where ψinst is 0.015–0.024 W/(m·K), the direct check gives U = 0.0003 W/(m·K). When two positions of the same wall are compared, the difference is ranked only if it exceeds 2U = 0.0006 W/(m·K); positions whose ψinst lies within this margin of the minimum are treated as numerically equivalent (Section 4.3).
Figure 6.
Mesh convergence of ψinst for five extreme details: deviation from the finest mesh (10−3 W/(m·K)) against the number of elements; the window-only reference is solved on the same mesh at every level.
3.3. Experimental Context and Limits of the Validation
Direct validation would compare the computed ψinst with a measurement of the same window detail in a hot box or via thermography. We searched for an open dataset that provides the full geometry and conductivities of a window-in-wall installation, along with a measured ψinst or heat flow, but did not find one. The closest studies are as follows. O’Grady et al. measured the thermal-bridge ψ-values of structural insulated panels with steel bridges in a calibrated hot box and compared them with finite-element and CFD models and with infrared thermography [27]; the panel is not a window installation, and the paper does not state the depth position of the steel sections, so it could not be reproduced here. The surface temperatures from their 2-D finite-element model agreed with thermocouple readings to 0.03–0.16 K at the warm point and 0.03–0.34 K at the cold bridge, against a thermocouple uncertainty of ±0.3 K, which is the uncertainty stated by the authors for their instrumentation [27]. Pomada et al. compared a numerical window-installation model with wall-surface temperatures measured on a building and found differences of 0.7–1.5 °C on average and about 3 °C at individual points, which they attributed to the heterogeneity of an old masonry wall [25]; no ψ or heat-flow values were measured there. Moumtzakis et al. measured the heat flux at the frame–floor junction of an aluminium-framed baseline as 1250 W/m2 against 1168 W/m2 simulated, that is, the model was about 7% lower than the measurement [21]. Baldinelli et al. validated a finite-volume frame model against the ISO 10077-2 reference examples and hot-box measurements [16], Gustavsen et al. compared five insulating frames in the hot box with ISO 10077-2 and CFD calculations and found good overall agreement with some areas needing improvement [17], and Bianchi et al. found that a transmittance-based prediction of heat-pump consumption with thermal bridges (5.258 kWh) was within 0.3% of the measured value (5.272 kWh) in a test room [8].
Table 4 collects the verification evidence. Three kinds of evidence should be kept apart: the deviation of this model from benchmark solutions (verification of the solver and of the model setup), the differences between other numerical models and measurements found in the literature (an indication of the agreement that a conduction model of this type can reach), and the measurement uncertainty itself. Figure 7a shows them as separate groups. The literature differences say nothing about our specific details. We therefore do not claim that the ψinst values of Section 4 are experimentally validated: they are verified against standard benchmarks, mesh-independent, closed in heat balance and insensitive to the main modelling assumptions (Section 4.4). They should be confirmed by a hot-box or thermography test of at least the base case before they are used as design values; the same limitation applies to all published numerical ψ catalogues for window installation that we are aware of.
Figure 7.
Experimental context. (a) Three separate kinds of evidence: verification deviations of this model against ISO 10211 (left), surface-temperature differences between finite-element results and thermocouple readings for two hot-box specimens from [27] (middle), and the thermocouple uncertainty of ±0.3 K stated in [27] (dashed line). (b) Ranges of ψ reported in the literature compared with the ranges found here; the definitions and reference dimensions differ (Table 5), so the comparison is one of order of magnitude only.
Table 5.
Definitions behind the ψ values compared in Figure 7b.
3.4. Comparability of Published ψ Values
The ψ values in Figure 7b come from studies with different junction geometries, reference dimensions and window references, and they are not directly comparable. Table 5 lists these differences. In this study, ψinst is defined against the 1-D wall and the coupling coefficient of the isolated window with the same cut planes (Equation (5)), which removes the frame–glazing edge term; other studies use the window U-value times its area, interior or exterior dimensions, or report the total junction loss. The comparison is therefore qualitative: well-placed details lie around 0.01–0.03 W/(m·K) and poor details around 0.2–0.6 W/(m·K) in all studies.
4. Results
4.1. Installation Depth Is the Dominant Factor
Figure 8 shows ψinst against position for the three walls without a lip. In the uninsulated wall, W1, ψinst is 0.16–0.26 W/(m·K) at every position and is slightly lower when the frame is near mid-depth. With a transmittance of 2.35 W/(m2·K), the 1-D wall is itself a poor insulator, and the junction adds a moderate amount on top of it. In the externally insulated wall, W2, the curve is steep: ψinst is 0.022–0.024 W/(m·K) for the F2 and F3 frames at p = 0, where the frame lies in the insulation plane, rises to 0.32–0.33 at p = 0.5, and reaches 0.58–0.60 W/(m·K) at p = 1. In the cavity-insulated wall W3, the minimum shifts to the wall’s centre. ψinst is 0.014–0.040 at p = 0.5 and about 0.30 W/(m·K) at p = 0, so the same frame in the same wall gives a more than 10-fold different result depending on the depth.
Figure 8.
Linear thermal transmittance, ψinst, against installation position, p (no insulation lip, 50 mm XPS): (a) W1, (b) W2 and (c) W3. F1, aluminium; F2, aluminium with polyamide break; F3, uPVC. The three frame curves nearly coincide in (b,c).
Figure 4c shows the physical reason. When the frame lies behind the insulation, the exterior half of the frame and the reveal in front of it are exposed to the outside film without insulation. The heat flow concentrates at the reveal corner where the exterior environment meets the interior wall surface. The deeper the frame sits, the more uninsulated reveal surface is exposed. Table 6 summarizes the results for the thermally broken aluminium frame (F2).
Table 6.
ψinst (W/(m·K)) and fRsi for the F2 frame (aluminium with thermal break), 50 mm XPS where present.
4.2. An Insulation Lip over the Frame Recovers Most of the Loss
For the W2 wall, extending the insulation over the frame by 20 mm cuts ψinst of the F2 frame at mid-depth from 0.325 to 0.142 W/(m·K) (−56%) and at p = 1 from 0.586 to 0.220 W/(m·K) (−62%); a 40 mm lip adds a further reduction of 0.01–0.02 W/(m·K) for the F2 and F3 frames and about 0.05 W/(m·K) for F1 (Figure 9). For the unbroken aluminium frame, F1, the 40 mm lip at p = 0 gives a slightly negative ψinst of −0.012 W/(m·K). As explained in Section 2.3, this means that the junction loses less heat than the 1-D wall plus the isolated window, while the total heat flow remains positive (L2D = 1.309 W/(m·K)); a similar effect of overlap was reported for insulated retrofits [23]. The value is stable on all five meshes of the extreme-case study (Figure 6) and is much larger than the numerical uncertainty. Below p = 0.25, the lip has little effect because the frame already sits in the insulation plane.
Figure 9.
Effect of the insulation lip over the frame on ψinst for the W2 wall (50 mm XPS): (a) F1, (b) F2 and (c) F3. The curves for 0, 20 and 40 mm converge at p = 0.
4.3. A Frame–Insulation Alignment Rule
The minima in Figure 8 sit where the frame lies in the insulation plane. This is the long-standing alignment principle of the heating-climate studies [22,23]; written in a form that can be applied directly, it gives a simple design rule: place the frame so its mid-depth coincides with the insulation layer’s mid-depth. In terms of Equation (1),
where xm is the distance from the exterior face to the mid-plane of the insulation layer. For W3, xm = 0.145 m and t = 0.29 m, so p* = 0.50. For W2, p* = 0.065, 0.108 and 0.143 for 50, 75 and 100 mm of XPS. The coarse sweep of Figure 8 (step 0.25) cannot locate the minimum, so the position was refined around p* with a step of Δp = 0.02 (59 additional cases), and the minimum was located with a parabola through the three lowest points (Figure 10, Table 7). In all four series, the minimum lies within |Δp| ≤ 0.020 of Equation (8), i.e., 2–5 mm in installation depth, and the penalty for placing the frame exactly at p* instead of at the computed minimum is at most 0.0005 W/(m·K). This penalty is smaller than 2U = 0.0006 W/(m·K), the smallest difference that the mesh study allows us to rank (Section 3). The minimum is also flat: estimated from the parabola, ψinst stays within 2U of ψinst,min over ±0.023 to ±0.038 in p (Table 7), which is wider than the offset between p* and pmin in every series. Within the numerical accuracy of the model, p* and the computed minimum are therefore equivalent positions; the offsets are reported, but they are not used to prefer one position over the other. The computed minimum, nevertheless, lies 2–5 mm on the exterior side of p* in all series of Table 7 and Table 8, except the thinnest EIFS wall, where the two coincide within 0.3 mm, which we tentatively attribute to the asymmetric surface resistances (Rse < Rsi). Equation (8) is therefore not a new optimisation method but a practical expression of the known alignment principle, proposed as a design guideline verified by simulation for the walls studied here; it is not a universally validated principle, and experimental confirmation remains necessary.
Figure 10.
Fine position sweep (Δp = 0.02, F2 frame, no lip): (a) W2 with 50, 75 and 100 mm XPS; and (b) W3. Dashed vertical lines mark p* from Equation (8); p* does not always coincide with a simulated position, and the minimum is located with a parabola through the three lowest points (Table 7).
Table 7.
Optimum installation position from the fine sweep (Δp = 0.02, F2 frame, no lip) against Equation (8). pmin is located with a parabola through the three lowest points; the offset in mm is |Δp| × (t − Df); the flat zone is the half-width in p within which ψinst stays within 2U = 0.0006 W/(m·K) of the minimum (U from the mesh study, Section 3).
Table 8.
Test of Equation (8) on walls and parameter values not included in the original parameter matrix (F2 frame, p step 0.05; ψinst in W/(m·K)). W2b–W5: blind-test walls; A: EIFS grid; B: sandwich grid with a 50 mm XPS layer in a 200 mm block. Sections are listed from exterior to interior without the 20 mm render on each face (*W5: exterior render only, 12.5 mm gypsum board inside). pmin is located with a parabola through the three lowest points of each series; the offset, the flat zone and U are defined as in Table 7.
Insulation thickness has a small main effect on the minimum. For W2 with the F2 frame and 50–100 mm of XPS, it explains under 0.01% of the variance of ψinst, while the position explains 99% (Table 9). This small share does not mean that thickness is unimportant: its influence appears almost entirely through the interaction with position. Thicker insulation moves the optimum inwards, i.e., towards the room (p* from 0.065 to 0.143), rather than changing its depth (0.015–0.021 W/(m·K)), and at p = 1 the order reverses (0.652 against 0.586 W/(m·K) for 100 and 50 mm), because a thicker insulation layer leaves more reveal exposed behind it.
Table 9.
Share of the variance of ψinst explained by each factor (main-effect sum of squares divided by the total sum of squares of each full-factorial subset, %; interactions are the remainder).
4.3.1. Blind Test on Walls Outside the Parameter Matrix
Equation (8) was derived from the walls of Table 2. To test it on walls it was not fitted to, four further walls were built with the same materials and solved with the F2 frame at 21 positions (Table 8): an EIFS wall with a thinner block and thicker insulation (W2b), an asymmetric sandwich wall with the insulation on the interior side of the centre (W3b), a sandwich wall with the insulation on the exterior side of the centre (W3c) and an internally insulated wall (W5). The predicted optima cover almost the whole depth, from p* = 0.105 to 0.966. In all four walls, the optimum found by COMSOL lies within |Δp| ≤ 0.021 of the prediction (2–5 mm; Table 8) (Figure 11 and Figure 12), and ψinst at the optimum (0.015–0.022 W/(m·K)) is 20–30 times lower than at the worst position (0.44–0.59 W/(m·K)). The temperature fields in Figure 11b,c show why: at the optimum, the isotherms cross the frame without bending around the reveal corner. Together with the four series of Table 7, the rule was thus checked on eight walls with |Δp| ≤ 0.021, in each case inside the flat zone of the minimum (±0.018 to ±0.038). Compared with the earlier optimisation studies, which located the optimum by sweeping positions for each wall [22,23], Equation (8) gives the position directly from the layer dimensions.
Figure 11.
Blind test of the alignment rule (the long-standing alignment principle written in closed form): (a) ψinst against p for the four new walls (logarithmic scale; dashed lines mark p* of Equation (8)); and (b) temperature field (°C) of W3b and (c) of W5 with the frame at the simulated position nearest to p*, ISO set 20/0 °C.
4.3.2. Continuous Parameter Grids and Field Maps
The test was extended to continuous ranges with two parameter grids of 231 COMSOL solutions: (A) the EIFS wall with XPS thicknesses of 30, 50, 75, 100, 125 and 150 mm and (B) a sandwich wall in which a 50 mm XPS layer is moved through a 200 mm block (exterior leaf of 40, 70, 100, 130 and 160 mm), each at 21 positions (Δp = 0.05). Because the grid step (0.05) is coarser than the offsets of interest, the minimum of each series was again located with a parabola through the three lowest points. In all eleven series, the refined minimum lies within |Δp| ≤ 0.022 of p* (at most 5.2 mm, for the most interior insulation layer), ψinst at p* exceeds the minimum by at most 0.0005 W/(m·K), and the offset is smaller than the half-width of the flat zone (±0.023 to ±0.049) (Table 8). Grid A at 50, 75 and 100 mm reproduces the fine sweeps of Table 7 within 0.003 in p. The predicted optima range from p* = 0.024 for the thinnest EIFS to p* = 0.761 for the most interior insulation layer. The valley is also wide: within ±0.05 of p*, ψinst stays below 0.035 W/(m·K) in every series, which leaves a practical installation tolerance of about ±10 mm. Figure 13 shows the mechanism with the temperature and heat-flux fields of the EIFS wall at three depths.
Figure 13.
Temperature (top, °C, isotherms every 2 K; blue line 12.6 °C, i.e., fRsi = 0.63) and logarithm of the heat-flux magnitude (bottom, W/m2, with heat-flow lines) for W2/F2 without lip: (a,d) p = 0; (b,e) p = 0.5; (c,f) p = 1. ISO set 20/0 °C, common colour scales, distances in m. At p = 0, the isotherms cross the frame almost undisturbed, while at p = 1, the uninsulated reveal draws the 12.6 °C isotherm deep into the wall and the heat flow concentrates at the reveal corner.
4.4. Sensitivity to Material Conductivities and Frame-Cavity Assumptions
The equivalent block conductivity was varied from 0.5 to 1.4 W/(m·K), which covers lightweight to dense hollow blocks, and the XPS conductivity from 0.030 to 0.040 W/(m·K) (Figure 14a,b). The position of the optimum and the ranking of the details did not change. For the aligned positions, ψinst stayed between 0.023 and 0.027 W/(m·K) for W2 and between 0.017 and 0.018 W/(m·K) for W3 over the whole block range. Only the poor details were sensitive: for W2 at p = 1, ψinst varied from 0.37 to 0.71 W/(m·K). In other words, a denser block makes a badly placed window worse, while a well-placed window is almost insensitive to the block. For the uninsulated wall, W1, the lowest ψinst moved from mid-depth to the interior face as the block conductivity increased, but the spread over the positions remained small (0.19–0.29 W/(m·K)).
Figure 14.
Sensitivity of ψinst (F2 frame, no lip): (a) equivalent conductivity of the hollow block; (b) conductivity of the XPS; and (c) change in Uf and ψinst from the base case for the cavity variants 1 (base), 2 (ΔT = 5 K), 3 (ΔT = 20 K), 4 (ε = 0.3) and 5 (Tm = 313 K).
The frame-cavity assumptions of Equation (4) were varied as described in Section 2.2 (Figure 14c). The frame transmittance is clearly affected: for F2, Uf fell from 2.81 to 2.00 W/(m2·K) with ε = 0.3 and rose to 3.10 W/(m2·K) at 313 K. ψinst, however, changed by at most 0.002 W/(m·K), because the frame appears both in L2D and in the window reference Lwin of Equation (5), and its effect cancels. This is the same mechanism that makes ψinst almost independent of the frame type (Section 4.5), and it means that the conclusions on installation depth do not depend on the details of the frame model.
4.5. The Frame Controls the Surface Temperature, Not ψinst
The descriptive variance decomposition of Section 2.6 gives the shares of the variance of ψinst in Table 9. In the 45 cases without a lip, installation depth accounts for 34%, the wall type for 10% and the frame type for 0.2%; the remaining 56% is the interaction of wall and depth. In the 45 W2 cases, depth explains 52%, the lip 30% and the frame 0.1%. These shares are descriptive and hold for the levels studied. The frame hardly changes ψinst because ψinst is the excess above the isolated wall and the isolated window, which already carry the frame difference in Lwin; the cavity study of Section 4.4 confirms this.
The frame does matter for the interior surface (Figure 15). The unbroken aluminium frame, F1, has fRsi of 0.25–0.32 in all walls, well below the 0.63 mould criterion in the ISO set (minimum interior surface temperature 5–6 °C at a 20 °C interior). The F2 and F3 frames reach 0.63–0.75 in the insulated walls when positioned within the insulation plane, but fall to 0.27–0.38 in the cavity wall W3 at p = 0 and 0.25, where the frame sits against the interior block leaf. In the cooling set, the interior surface of F1 reaches 38–39 °C, compared with 29–32 °C for F2 and F3 (24 °C interior; 45 °C exterior). Hence, the unbroken frame is also a visible hot spot and a comfort problem in the room. The surface-temperature criterion for a hot climate is therefore a frame criterion. In contrast, the ψinst criterion is an installation-depth criterion.
Figure 15.
Interior surface temperature indicators (50 mm XPS, no lip): (a) fRsi,min for W2 and (b) for W3, with the 0.63 mould criterion of ISO 13788; and (c) highest interior surface temperature in the cooling set (24 °C interior; 45 °C exterior) for W2.
4.6. Transient Design-Day Behaviour
Figure 16 shows the transient results of Section 2.5. The heat flow into the room follows the outdoor air with a delay, and the solar load on the west façade produces the afternoon peak (Figure 16a,c). The junction heat flow qj(t) is small for the aligned detail and for the cavity-wall optimum, but reaches 15 W/m at about 19:00 for the deep installation without a lip (Figure 16b), about two hours after the peak of the solar input. The daily junction gains are compared with the steady estimate, ψinst × ΔTsol-air,mean × 24 h, in Table 10. For the three W2 details, the transient daily gain is 6–8% lower than the steady estimate. For the cavity-wall optimum, the two approaches differ in sign: the transient model gives a small negative junction gain (−3.2 Wh/m per day, i.e., the junction slightly reduces the daily gain of the plain wall and window), whereas the steady estimate gives +6.3 Wh/m per day. At ψinst ≈ 0.017 W/(m·K), the junction term is the small difference between large dynamic heat flows, and its sign depends on the different time response of the heavy cavity wall and the light window, which a single steady coefficient cannot describe. The absolute difference, 9.5 Wh/m per day, is below 5% of the gain of the deep installation. The steady ψinst is therefore a sound basis for ranking the details and for the cooling-season figures of the poorly placed windows, provided that the exterior temperature includes the solar term, but it can differ from the dynamic result by up to 8%, and it should not be used to give the sign of a junction gain that is close to zero. Using the monthly mean air temperature alone, as in Section 4.7, gives about 176 Wh/m per day for the deep detail in July, i.e., 13% less than the transient value.
Figure 16.
Transient design day (Madinah, July, west façade): (a) heat flow into the room for the installed details and the references; (b) junction heat flow, qj(t); (c) outdoor air temperature and the equivalent sol-air temperature; and (d) temperature field (°C) of W2/F2 at p = 1 at 16:00.
Table 10.
Daily junction heat gain for the Madinah July design day (west façade): transient COMSOL result against the steady estimate.
4.7. Conductive Heat Gain Through the Joint in a Hot Climate
To put numbers on the cooling-season effect, the annual conductive heat gain through the installation joint per metre of window perimeter can be written, from monthly mean exterior temperatures, as
where L is the perimeter length in m, Tm is the monthly mean exterior temperature, Ti = 24 °C is the set-point and nm is the number of days. Table 1 of our earlier paper [7] gives the monthly means for Madinah, Riyadh and Jeddah, compiled from a published climate dataset [36]; they give 2343, 1910 and 2039 cooling degree-days above 24 °C. E is a conductive heat gain, not a cooling load and not air-conditioning electricity, which would also depend on internal gains, solar gains through the glazing, thermal storage, system efficiency and control. Because the monthly mean ignores daily swings and the solar load, E underestimates the junction gain of sunlit façades; for the west façade in July, the transient model gives 13% more (Section 4.6). The values below should be read as simplified steady-state conduction estimates.
Consider the 40-window façade from our earlier paper: 1.5 m × 1.5 m windows, 6 m of perimeter each, 240 m total, and the W2 wall with the F2 frame. Installed at p = 0 the joint adds 0.024 × 240 = 5.8 W/K of conductance, about 4% of the 161 W/K that the 90 m2 of windows already have at Uw = 1.79 W/(m2·K) [7]. Installed at p = 1 without a lip, it adds 141 W/K, nearly as much as all the windows put together. Over a year, this is 324 kWh at p = 0 and 7907 kWh at p = 1 in Madinah (6447 kWh in Riyadh and 6881 kWh in Jeddah) (Figure 17, Table 11). Madinah has the largest penalty because it has the most cooling degree-days, not because its peak temperature is the highest. Figure 17b shows the same four configurations as Table 11. The 20 mm lip cuts the p = 1 figure by 62%. These figures are conductive heat gains through the joint estimated from monthly mean temperatures; they show the order of magnitude of the installation effect, but they are not demonstrated savings in cooling energy, which would also depend on the air-conditioning plant and require a dynamic building simulation.
Figure 17.
Conductive heat gain through the installation joint, Equation (9), from monthly mean temperatures (simplified steady-state estimate): (a) gain per metre of perimeter against ψinst for three cities; and (b) a 40-window façade (240 m of perimeter) with the W2 wall and F2 frame for the four configurations of Table 11.
Table 11.
Annual conductive heat gain through the joint for the 240 m façade, estimated from monthly mean temperatures (kWh/year; W2 wall, F2 frame); not a dynamic building energy simulation and not air-conditioning electricity.
4.8. Joint Temperature in Hot–Humid Conditions
In the cooling set, the interior surfaces are warmer than the indoor air (29–39 °C), so they cannot condense. The relevant point is the installation joint, which is cooled from the inside and can be reached by humid outdoor air through imperfect seals. Figure 18 shows the minimum temperature in the polyurethane joint for all walls and frames. It lies between 25.4 and 31.8 °C, and the aligned positions are the coolest (25.4–26.6 °C) because the joint then lies at the interior side of the main insulation. Condensation itself was not simulated, so these temperatures can only be compared with indicative outdoor dew points. The dashed band in Figure 18 (25–28 °C) is shown for orientation only, as an indicative range of summer dew points on the Red Sea coast, and not as a design value. Where humid outdoor air reaches a joint that is colder than its dew point, condensation becomes possible; whether it occurs depends on air leakage, vapour diffusion and moisture storage, which are outside the present model. An exterior air and vapour seal is therefore suggested as a precaution for cities such as Jeddah, not as a result demonstrated here; this is the reverse of the usual cold-climate rule and is discussed in Section 5.3.
Figure 18.
Minimum temperature in the installation joint in the cooling set (24 °C interior; 45 °C exterior) for the three walls and frames, against the installation position; the dashed band (25–28 °C) is an indicative range of summer outdoor dew points on the Red Sea coast, shown for orientation only; condensation was not simulated.
5. Discussion
5.1. Comparison with Previous Studies
The parameter that governs ψinst is geometric: it is the position of the frame relative to the insulation layer. Our values for aligned details (0.015–0.024 W/(m·K)) agree with the value of about 0.02 W/(m·K) reported by Gendelis et al. for a frame installed in the insulation layer of a retrofit wall [23], and they are of the same order as the 0.007 W/(m·K) of a purpose-designed installation system [25]. Our values for poor details (0.3–0.65 W/(m·K)) are higher than the value of about 0.27 W/(m·K) reported for conventional mounting [23]. This is expected, because the reveal in our walls is left completely uninsulated behind a thick layer of external insulation, and because this study deliberately includes the extreme depths. For the same reason, the reduction from the worst to the best position is about 95–97% for the eight walls of Table 7 and Table 8, which is larger than the reduction of more than 50% found by Misiopecki et al. for typical positions [22]. These comparisons are of order of magnitude only, because the studies use different reference dimensions (Table 5).
Wall-level studies in hot climates point in the same direction. Zedan et al. found that mortar-joint bridges increased the cooling load of a Riyadh villa by 3–11% [13], Al-Awadi et al. found external insulation to be the best of four wall types [14], and Alayed et al. showed that 40–80 mm of external insulation removed up to 73% of the bridging effect [15]. Our results add the window junction to this picture. For the 240 m façade of Section 4.7, a well-aligned joint adds about 4% to the conductance of the windows, whereas a joint in the uninsulated reveal adds nearly as much conductance as all the windows together. For comparison, window-offset bridges accounted for 2–8% of the load of a heating-dominated French house [20], although the two figures have different bases and cannot be compared directly. The frame results agree with the hot-climate frame study of Da’as et al. [18], in which the frame material was the most effective measure for reducing the frame U-value. In our data, the frame type governs the interior surface temperature, whereas the installation depth governs ψinst. A thermally broken frame set deep in an uninsulated reveal therefore solves the first problem and leaves the second.
The physical principle is the same as in the earlier work [22,23]; the difference lies only in how the optimum is found. In [22,23], it was located by a position sweep for each wall, whereas Equation (8) gives it directly from the wall section. Equation (8) should therefore be read as a practical application of a long-standing principle, not as a new optimisation technique. For all walls and grid series tested, it located the optimum within |Δp| ≤ 0.022 (about 5 mm at most), which is inside the numerically flat zone of the minimum in every case.
5.2. Construction Feasibility of the Insulation Lip
The insulation lip is effective only if it can be built. A 20 mm lip over a 60 mm fixed frame leaves the sash, the gaskets and the drainage slots clear in typical frame systems, and can be formed by a reveal board that is notched over the frame. A 40 mm lip covers a larger part of the frame face and may obstruct the drainage or the opening sash, so it requires coordination with the frame supplier. In both cases the lip must be protected by the render or by a cover profile against impact and ultraviolet radiation; the frame should be fixed with brackets that pass behind the lip, so that the fixings do not perforate it; and the waterproofing membrane must run continuously from the frame to the wall behind the lip. Installation tolerances of a few millimetres are acceptable, because the parameter grids show that ψinst stays low within about ±10 mm of the optimum (Section 4.3.2).
5.3. Hygrothermal Behaviour in Hot Climates
The temperature factor, fRsi, and the ISO 13788 criterion of 0.63 relate to heating conditions. They remain relevant to the inland Gulf cities on winter nights, when Madinah and Riyadh have outdoor temperatures well below the indoor temperature, and the unbroken aluminium frame, F1, fails the criterion in all walls (Figure 15). In summer the situation is reversed. The risk is not on the interior surface but in the joint, which is cooled by the air-conditioned room while humid outdoor air may enter it (Section 4.8). In hot–humid cities an airtight and vapour-tight exterior seal of the joint, with an interior side that allows drying towards the room, is therefore advisable as a precaution. No coupled heat and moisture simulation was performed here: the present results show where the joint is coolest, but not whether or how often condensation occurs. A coupled simulation with hourly climate data for Jeddah is needed to quantify the risk.
5.4. Implications for Codes and Limitations
This has practical consequences for codes. An order-of-magnitude variation that depends on a choice made by the installer would be lost if a single default ψinst per window type were used, as in the simplified catalogue of ISO 14683 [37]. As a recommendation, which requires experimental confirmation and field experience before adoption, a short list of approved installation details with tabulated ψinst values, checked at the as-built stage, would be preferable for Gulf codes. This aligns with the phased approach proposed earlier [7], now supported by computed values.
Limitations. (i) The model is 2-D, so fasteners, corners and brackets are not captured; fasteners add a separate point contribution, for which 3-D models are required [24]. (ii) The walls are idealised and the frames are generic, not manufacturer-specific; the block is an equivalent homogeneous layer and the glazing unit has no spacer. The sensitivity studies of Section 4.4 show that these simplifications do not change the conclusions on installation depth, but they affect the absolute values of the poor details. (iii) The energy figures are conductive heat gains; the transient check covers one design day and one orientation, and moisture transport is not modelled. (iv) Most importantly, the results are not compared with a measured ψinst of the same details (Section 3.3). We recommend a hot-box test of the base case and of the extremes (p = 0 and p = 1) and a thermographic survey of the reveal.
6. Conclusions
The following are the findings directly supported by the simulations:
- •
- The COMSOL model reproduced the ISO 10211 Annex C benchmarks (maximum temperature deviations of 0.048 K and 0.039 K; heat-flow deviation below 0.1%) and closed the heat balance in all cases. On the production mesh, ψinst of the base case was 1.6% above the Richardson-extrapolated value (0.1423 against 0.1400 W/(m·K)), and ψinst of the extreme details changed by at most 0.0003 W/(m·K) over the mesh levels.
- •
- Installation depth is the dominant parameter, explaining 34–99% of the variance of ψinst in the studied subsets (descriptive decomposition); frame type explains less than 0.3%.
- •
- ψinst was lowest, 0.015–0.024 W/(m·K), when the frame mid-plane was aligned with the insulation mid-plane, and 0.3–0.65 W/(m·K) when the frame sat in the uninsulated reveal. Equation (8), a practical closed-form expression of the long-standing alignment principle, located the optimum within |Δp| ≤ 0.022 (at most about 5 mm) for eight walls and two parameter grids, four walls of which were not used to derive it; this offset lies inside the numerically flat zone of the minimum.
- •
- A 20 mm insulation lip over the frame reduced ψinst by 56–62% for deep installations in the externally insulated wall.
- •
- The conclusions were insensitive to the block conductivity (0.5–1.4 W/(m·K)), the XPS conductivity and the frame-cavity assumptions; the frame type controls the interior surface: unbroken aluminium gave fRsi of 0.25–0.32 and a 38–39 °C hot spot in the cooling set, against 0.63–0.75 and 29–32 °C for thermally broken aluminium and uPVC.
- •
- For a Madinah design day, the steady estimate exceeded the transient daily junction gain by 6–8% for the EIFS details, and for the near-zero cavity-wall optimum the two approaches gave opposite signs; the steady ψinst is suitable for ranking details but not for the sign of very small junction gains. For a 40-window façade, a deep, uninsulated-reveal installation adds an estimated 7900 kWh per year of conductive heat gain through the joints (monthly-mean estimate, not a simulated cooling-energy saving), against about 320 kWh for an aligned installation. In the cooling set, the aligned joint is the coolest point (25.4–26.6 °C); condensation was not simulated.
Recommendations for practice (to be confirmed experimentally):
- •
- Place the frame mid-plane at the insulation mid-plane (Equation (8)) as a design guideline; where this is not possible, add a 20 mm insulation lip. In hot–humid cities, an airtight and vapour-tight exterior seal of the joint is advisable as a precaution, because the aligned joint is the coolest point; the condensation risk itself needs a coupled heat and moisture analysis. Regional catalogues of approved details with tabulated ψinst would capture the effect of installation in energy codes. The ψinst values need confirmation by a hot-box or thermography test of the same details.
Future work should add 3-D fastener effects, coupled heat and moisture transport with hourly climate data, other orientations and measurements of at least the base detail.
Author Contributions
Conceptualization, M.T.N. and A.F.; methodology, M.T.N.; software, M.T.N.; validation, M.T.N.; formal analysis, M.T.N.; investigation, M.T.N.; resources, M.T.N.; data curation, M.T.N.; writing—original draft preparation, M.T.N. and A.F.; writing—review and editing, M.T.N. and A.F.; visualization, A.F.; supervision, A.F.; All authors have read and agreed to the published version of the manuscript.
Funding
This research received no external funding.
Institutional Review Board Statement
Not applicable.
Informed Consent Statement
Not applicable.
Data Availability Statement
The data presented in this study are given in Appendix A.
Acknowledgments
The authors thank the Islamic University of Madinah for access to the COMSOL Multiphysics license. During the preparation of this work, the authors used AI-based tools such as Grammarly, ChatGPT, Claude and Gemini for Language Editing. The authors reviewed and edited all content and take full responsibility for the publication.
Conflicts of Interest
The authors declare no conflicts of interest.
Abbreviations
The following abbreviations are used in this manuscript:
| AAC | Autoclaved aerated concrete |
| CDD | Cooling degree-days |
| EIFS | External insulation and finish system |
| EPDM | Ethylene propylene diene monomer (gasket) |
| GCC | Gulf Cooperation Council |
| GCI | Grid convergence index |
| IGU | Insulating glazing unit |
| PA | Polyamide (thermal break) |
| SBC | Saudi Building Code |
| uPVC | Unplasticised polyvinyl chloride |
| XPS | Extruded polystyrene |
| fRsi | Temperature factor at the interior surface |
| ψinst | Linear thermal transmittance of the window installation |
Appendix A. Complete Catalogue of ψinst
Table A1 lists the 85 COMSOL cases (ISO set, 20/0 °C; production mesh). Wall: W1, uninsulated block; W2, external insulation; W3, cavity insulation. Frame: F1, aluminium without break; F2, aluminium with polyamide break; F3, five-chamber uPVC. p is the installation position of Equation (1), d is the XPS thickness and lip is the insulation return over the frame.
Table A1.
Complete catalogue of the 85 simulated installation details.
References
- Alshahrani, J.; Boait, P. Reducing High Energy Demand Associated with Air-Conditioning Needs in Saudi Arabia. Energies 2019, 12, 87. [Google Scholar] [CrossRef] [Scilit]
- Elnabawi, M.H.; Saber, E.; Bande, L. Passive Building Energy Saving: Building Envelope Retrofitting Measures to Reduce Cooling Requirements for a Residential Building in an Arid Climate. Sustainability 2024, 16, 626. [Google Scholar] [CrossRef] [Scilit]
- Alyami, S.H.; Alqahtany, A.; Ashraf, N.; Osman, A.; Aldossary, N.A.; Almutlaqa, A.; Al-Maziad, F.; Alshammari, M.S.; Al-Gehlani, W.A.G. Impact of Location and Insulation Material on Energy Performance of Residential Buildings as per Saudi Building Code (SBC) 601/602 in Saudi Arabia. Materials 2022, 15, 9079. [Google Scholar] [CrossRef] [Scilit] [PubMed]
- Alwetaishi, M.; Benjeddou, O. Impact of Window to Wall Ratio on Energy Loads in Hot Regions: A Study of Building Energy Performance. Energies 2021, 14, 1080. [Google Scholar] [CrossRef] [Scilit]
- Elnabawi, M.H. Evaluating the Impact of Energy Efficiency Building Codes for Residential Buildings in the GCC. Energies 2021, 14, 8088. [Google Scholar] [CrossRef] [Scilit]
- SBC 601-2018; Saudi Building Code: Energy Conservation Requirements. Saudi Building Code National Committee: Riyadh, Saudi Arabia, 2018.
- Naqash, M.T.; Formisano, A. Regulatory Gap in Fenestration Thermal Performance: Integrating Linear Thermal Transmittance into Energy Codes. Sustainability 2026, 18, 6111. [Google Scholar] [CrossRef] [Scilit]
- Bianchi, F.; Pisello, A.L.; Baldinelli, G.; Asdrubali, F. Infrared Thermography Assessment of Thermal Bridges in Building Envelope: Experimental Validation in a Test Room Setup. Sustainability 2014, 6, 7107–7120. [Google Scholar] [CrossRef] [Scilit]
- Kuusk, K.; Kurnitski, J.; Kalamees, T. Calculation and Compliance Procedures of Thermal Bridges in Energy Calculations in Various European Countries. Energy Procedia 2017, 132, 27–32. [Google Scholar] [CrossRef] [Scilit]
- Ilomets, S.; Kuusk, K.; Paap, L.; Arumägi, E.; Kalamees, T. Impact of Linear Thermal Bridges on Thermal Transmittance of Renovated Apartment Buildings. J. Civ. Eng. Manag. 2017, 23, 96–104. [Google Scholar] [CrossRef] [Scilit]
- Curto, D.; Franzitta, V.; Guercio, A.; Martorana, P. FEM Analysis: A Review of the Most Common Thermal Bridges and Their Mitigation. Energies 2022, 15, 2318. [Google Scholar] [CrossRef] [Scilit]
- Alvur, E.; Cuce, P.M.; Cuce, E.; Bouabidi, A.; Soudagar, M.E.M. Thermal Bridging in Windows: A Critical Review on Mitigation Strategies for Enhanced Building Energy Efficiency. Sustain. Clean Build. 2024, 1, 176–193. [Google Scholar] [CrossRef] [Scilit]
- Zedan, M.F.; Al-Sanea, S.; Al-Mujahid, A.; Al-Suhaibani, Z. Effect of Thermal Bridges in Insulated Walls on Air-Conditioning Loads Using Whole Building Energy Analysis. Sustainability 2016, 8, 560. [Google Scholar] [CrossRef] [Scilit]
- Al-Awadi, H.; Alajmi, A.; Abou-Ziyan, H. Effect of Thermal Bridges of Different External Wall Types on the Thermal Performance of Residential Building Envelope in a Hot Climate. Buildings 2022, 12, 312. [Google Scholar] [CrossRef] [Scilit]
- Alayed, E.; O’Hegarty, R.; Kinnane, O. Solutions for Exposed Structural Concrete Bridged Elements for a More Sustainable Concrete Construction in Hot Climates. Buildings 2022, 12, 176. [Google Scholar] [CrossRef] [Scilit]
- Baldinelli, G.; Lechowska, A.; Bianchi, F.; Schnotale, J. Sensitivity Analysis of Window Frame Components Effect on Thermal Transmittance. Energies 2020, 13, 2957. [Google Scholar] [CrossRef] [Scilit]
- Gustavsen, A.; Talev, G.; Arasteh, D.K.; Goudey, H.; Kohler, C.; Uvsløkk, S.; Jelle, B.P. Experimental and Numerical Examination of the Thermal Transmittance of High Performance Window Frames. In Proceedings of the Thermal Performance of the Exterior Envelopes of Whole Buildings XI, Clearwater Beach, FL, USA, 5–9 December 2010. [Google Scholar]
- Da’as, S.; Alhazmi, M.; Mohammed, M.A.; Abdou, A.A.; Asif, M. Parametric Analysis of Window Frame Thermal Behavior and Energy Savings in Hot Climates. Appl. Therm. Eng. 2026, 297, 130837. [Google Scholar] [CrossRef] [Scilit]
- Prapotnik Brdnik, A. Thermal Performance Optimization of Double and Triple Glazing Systems for Slovenian Climate Conditions. Sustainability 2021, 13, 11857. [Google Scholar] [CrossRef] [Scilit]
- Ibrahim, M.; Biwole, P.H.; Wurtz, E.; Achard, P. Limiting Windows Offset Thermal Bridge Losses Using a New Insulating Coating. Appl. Energy 2014, 123, 220–231. [Google Scholar] [CrossRef] [Scilit]
- Moumtzakis, A.; Zoras, S.; Evagelopoulos, V.; Dimoudi, A. Experimental Investigation of Thermal Bridges and Heat Transfer through Window Frame Elements at Achieving Energy Saving. Energies 2022, 15, 5055. [Google Scholar] [CrossRef] [Scilit]
- Misiopecki, C.; Bouquin, M.; Gustavsen, A.; Jelle, B.P. Thermal Modeling and Investigation of the Most Energy-Efficient Window Position. Energy Build. 2018, 158, 1079–1086. [Google Scholar] [CrossRef] [Scilit]
- Gendelis, S.; Shamilov, P.; Jakovičs, A.; Biriukovych, P.; Khmelenko, S. Numerical Optimisation of Window Installation Thermal Bridges for Sustainable Buildings: The Impact of Mounting Position. Sustainability 2026, 18, 3474. [Google Scholar] [CrossRef] [Scilit]
- Šadauskienė, J.; Ramanauskas, J.; Krawczyk, D.A.; Klumbytė, E.; Fokaides, P.A. Investigation of Thermal Bridges of a New High-Performance Window Installation Using 2-D and 3-D Methodology. Buildings 2022, 12, 572. [Google Scholar] [CrossRef] [Scilit]
- Pomada, M.; Adamus, J.; Boruszewski, A. Numerical and Experimental Analysis of Heat Flow at Window-to-Wall Interface. Energies 2022, 15, 3837. [Google Scholar] [CrossRef] [Scilit]
- Bienvenido-Huertas, D.; Fernández Quiñones, J.A.; Moyano, J.; Rodríguez-Jiménez, C.E. Patents Analysis of Thermal Bridges in Slab Fronts and Their Effect on Energy Demand. Energies 2018, 11, 2222. [Google Scholar] [CrossRef] [Scilit]
- O’Grady, M.; Lechowska, A.A.; Harte, A.M. Application of Infrared Thermography Technique to the Thermal Assessment of Multiple Thermal Bridges and Windows. Energy Build. 2018, 168, 347–362. [Google Scholar] [CrossRef] [Scilit]
- ISO 10211:2017; Thermal Bridges in Building Construction—Heat Flows and Surface Temperatures—Detailed Calculations. ISO: Geneva, Switzerland, 2017.
- ISO 10077-2:2017; Thermal Performance of Windows, Doors and Shutters—Calculation of Thermal Transmittance—Part 2: Numerical Method for Frames. ISO: Geneva, Switzerland, 2017.
- ISO 10456:2007; Building Materials and Products—Hygrothermal Properties—Tabulated Design Values and Procedures for Determining Declared and Design Thermal Values. ISO: Geneva, Switzerland, 2007.
- ISO 6946:2017; Building Components and Building Elements—Thermal Resistance and Thermal Transmittance—Calculation Methods. ISO: Geneva, Switzerland, 2017.
- ISO 13788:2012; Hygrothermal Performance of Building Components and Building Elements—Internal Surface Temperature to Avoid Critical Surface Humidity and Interstitial Condensation—Calculation Methods. ISO: Geneva, Switzerland, 2012.
- COMSOL AB. COMSOL Multiphysics, Version 5.6; COMSOL AB.: Stockholm, Sweden, 2020. [Google Scholar]
- ASHRAE. ASHRAE Handbook—Fundamentals; Chapters 14 and 18; American Society of Heating, Refrigerating and Air-Conditioning Engineers: Atlanta, GA, USA, 2021. [Google Scholar]
- Roache, P.J. Perspective: A Method for Uniform Reporting of Grid Refinement Studies. J. Fluids Eng. 1994, 116, 405–413. [Google Scholar] [CrossRef] [Scilit]
- Ouzzane, M.; Naqash, M.T.; Harireche, O. Assessment of the Potential Use of Shallow Geothermal Energy Source for Air Heating and Cooling in the Kingdom of Saudi Arabia. Nat. Environ. Pollut. Technol. 2021, 20, 1923–1934. [Google Scholar] [CrossRef] [Scilit]
- ISO 14683:2017; Thermal Bridges in Building Construction—Linear Thermal Transmittance—Simplified Methods and Default Values. ISO: Geneva, Switzerland, 2017.
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2026 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.