Architectural Coordination of Wall Reflectance Zoning and Window Design in Deep-Plan University Classrooms

,
and
1
College of Art & Design, Nanjing Forestry University, Nanjing 210037, China
2
College of Architecture and Design, Tongmyong University, Busan 48520, Republic of Korea
*
Author to whom correspondence should be addressed.

Abstract

Interior reflectance is often treated as a uniform input in architectural daylight studies, leaving the effect of its spatial allocation unclear. This study tests whether wall reflectance zoning improves deep-plan classroom daylight when mean wall reflectance is held at 0.55. A 96-case annual Radiance experiment combines four window-to-wall ratios, four orientations, and six neutral diffuse-reflectance schemes in a Nanjing classroom. The high-reflectance rear wall scheme increased rear-zone daylight autonomy by 3.97 percentage points and median minimum-to-mean uniformity by 0.020, averaged across 16 matched aperture–orientation pairs. Its modeled lighting-demand reduction was 0.130 kWh m−2 y−1 under ideal sensor-level dimming. Supplementary analyses examine occupancy assumptions, grouped lighting control, threshold choices, room depth, shading, and numerical sensitivity. The results identify reflectance redistribution as a modest spatial refinement rather than a substitute for aperture or solar-control design. They do not establish improved occupant comfort, field-validated performance, or lower total building energy use. Architectural application requires checking the particular room, façade, finish specification, and lighting controls.

1. Introduction

A deep-plan classroom can receive ample daylight near its façade while its rear remains dependent on electric lighting. Architectural design must therefore address the distribution of admitted light as well as its quantity. Climate-based design research links daylight evidence to window geometry, orientation, room proportion, and interior specification [1,2,3,4]. The narrower question examined here is whether relocating a fixed reflectance budget among walls can improve the rear seating area without changing window area or increasing mean wall reflectance.
The distinction matters because daylight availability alone is not an observation of visual comfort or learning performance. Classroom studies associate the physical learning environment with student outcomes [5,6,7,8], while occupant responses also depend on views, glare, variability, and control [9]. This study evaluates simulated workplane daylight and comparative lighting demand. It does not measure occupants, glare, fatigue, or learning outcomes.
Throughout this paper, surface reflectance means the dimensionless diffuse visible reflectance assigned to a material. Reflectance zoning means the placement of different values on defined wall surfaces. The simulated surfaces are spectrally neutral, with equal RGB values. They represent the reflectance aspect of achromatic interior finishes; they are not measured CIELAB lightness, perceived brightness, hue, or chroma. Studies of wall luminance and perceived enclosure [10,11], corneal illuminance [12,13], reflectance-input sensitivity [14], and colored glazing [15,16] show why these quantities should not be conflated.
Annual metrics support comparison across weather conditions [17,18,19], but whole-room summaries can obscure local failure [20]. Recent classroom work combines quantitative indicators with subjective or field evidence [21,22,23]. Reflectance zoning calls for a spatially explicit outcome: rear-zone daylight autonomy and workplane uniformity are primary here; whole-room sDA, useful daylight illuminance (UDI), excessive illuminance, and idealized lighting demand provide context.
Related work addresses different controls. Reflectance-input sensitivity studies vary material values and assess the resulting metric uncertainty [14]. Façade studies manipulate aperture, optics, orientation, or shading [24,25,26,27,28,29], while classroom investigations examine light shelves and integrated window strategies [30,31,32,33,34,35,36,37,38]. Multi-objective studies add climate, thermal, and view objectives [39,40,41,42,43,44,45,46,47,48,49]. These designs establish that surfaces and envelopes matter, but a change in reflectance level or aperture does not identify a placement effect at constant mean wall reflectance. The discriminating comparison here therefore fixes aperture, orientation, and the area-weighted opaque wall mean within each pair, while reallocating reflectance among defined wall zones. The gap is framed relative to these cited designs, without claiming that no earlier study has ever examined reflectance placement.
Recent work makes the distinction more specific. Cheshmeh Noor and colleagues jointly examine wall reflection coefficient, WWR, and classroom plan geometry [50,51]. Their photopic, melanopic, and glare objectives differ from the present annual, equal-mean reflectance comparison. Angelaki and Besenecker treat light distribution as an architectural parameter through classroom observations and electric-lighting design [52]. Vidiyanti and colleagues examine daylight configuration, learning media, and visual fatigue in a real classroom [53]. These studies support attention to distribution and geometry, but their comfort or spectral findings cannot be inferred from an illuminance-only grid.
Against this background, the study asks: (RQ1) does spatial redistribution of equal-mean wall reflectance change rear-zone daylight and uniformity; (RQ2) how large is that change relative to the established effects of WWR and orientation; and (RQ3) how dependent is the design interpretation on schedule, lighting-control resolution, screening thresholds, geometry, shading, and numerical settings? The contribution is a controlled comparison of interior finish placement within a coordinated architectural model, not a new daylight metric or a demonstration of total-energy optimization. Fixed and dynamic solar control [54,55,56,57], daylight-responsive lighting [58,59,60], and broader health and view requirements [61,62,63] remain distinct design considerations.

2. Materials and Methods

2.1. Classroom Geometry and Surface Reflectance

The modeled classroom is 7.2 m wide, 9.0 m deep, and 3.3 m high, with a 64.8 m2 floor area. The front wall is the exterior wall containing the centered window; the opposite wall is the rear wall, and the two depthwise boundaries are side walls. This is an idealized design model, not a reconstruction of a surveyed classroom. Table 1 gives the geometry and optical assumptions. Figure 1 identifies these walls, the common depth coordinates, glazing, and overhang. Room depth, window geometry, and shading must be interpreted together [64,65,66].
Table 1. Geometric, optical, and operational assumptions of the baseline model.
Figure 1. Classroom geometry and reflectance schemes: (a) rotated plan; (b) section with the same depth direction and 2 m tick interval; (c) window wall elevation with four WWRs; and (d) side/rear wall reflectance zones. Neutral denotes equal RGB diffuse reflectance, not perceived lightness. Glazing is blue in plan and section. The overhang projects 0.60 m at z = 2.95 m, 0.05 m above the window head.
The depth-to-width ratio is 1.25, and depth divided by the window-head height above the workplane is 9.0/(2.90 − 0.75) = 4.19. These ratios explain the use of “deep-plan” as an analytical description of this side-lit model; the room is not a statistically representative sample of university classrooms. Changing head height alters light penetration and the visible sky, while multiple openings change lateral distribution. Neither alternative is equivalent to widening the centered opening and neither was simulated.
The windowsill and head are fixed at 0.90 and 2.90 m; WWR therefore changes window width only. Visible transmittance 0.70 is a transparent-glazing design assumption, not a measurement or an optimized product choice. A horizontal overhang of 0.60 m projection spans the window width. It is a controlled common baseline rather than equal-performing solar control for all orientations. Holding these inputs fixed isolates wall-reflectance placement; it does not establish that they are preferable to other glazing or shading options.
The controlled quantity is the area-weighted diffuse reflectance of the opaque walls only; glazing, ceiling, and floor are excluded. Let W, D, and H denote room width, depth, and height, and g denote WWR. The combined side and rear area is H(2D + W); the front opaque area is WH(1 − g). For side reflectance ρs, rear reflectance ρr, and front reflectance 0.55, the full opaque wall mean equals [2DHρs + WHρr + 0.55WH(1 − g)]/[2DH + WH + WH(1 − g)]. It is 0.55 when 2D(ρs − 0.55) + W(ρr − 0.55) = 0. For the rear wall scheme, this gives ρs = 0.55 − (ρr − 0.55)W/(2D), or 0.45 when ρr = 0.80, W = 7.2 m, and D = 9.0 m. Thus (0.45 × 59.4 + 0.80 × 23.76)/83.16 = 0.55. Reusing 0.45 without rebalancing at another depth would violate the control. Table 2 lists all six material assignments.
Table 2. Neutral diffuse wall-reflectance configurations with area-weighted mean 0.55.
The vertical schemes use lower/upper area weights 2/3 and 1/3: (2/3)0.45 + (1/3)0.75 = 0.55 and (2/3)0.65 + (1/3)0.35 = 0.55. The depthwise schemes split each side wall into equal areas, averaging 0.40 and 0.70 to 0.55, with the rear at 0.55. The front wall remains at 0.55 for all schemes. Across WWR 25–55%, total opaque wall area falls from 100.980 to 93.852 m2, a 7.06% reduction. Equal mean reflectance therefore controls material assignment within a matched aperture pair; it does not conserve reflected flux across apertures or fix the interreflection field. “Gradient” denotes two discrete zones, not a continuous coating.

2.2. Factorial Design and Matched Comparisons

A 4 × 4 × 6 full factorial combines WWRs of 25%, 35%, 45%, and 55%; south, east, west, and north orientations; and the six schemes. The 96 cases share all other baseline assumptions. Each zoned scheme is compared with the uniform 0.55 scheme at the same aperture and orientation. This matched contrast isolates the spatial allocation of reflectance within the tested design set. Room width and height are not experimental factors in the baseline. Orientation is a site/massing choice, WWR an elevation choice, overhang a section detail, and reflectance zoning an interior-elevation and finish-schedule choice.

2.3. Annual Simulation and Reliability Checks

Radiance 6.0.2 was selected because the placement effect is transmitted through interreflection, which its backward ray-tracing formulation resolves [67]. Annual work-plane illuminance was obtained by multiplying daylight coefficients by a Perez sky matrix [68]. Validation and method comparisons in the literature support engine selection and identify method-dependent uncertainties [69,70,71,72]; they do not validate this classroom. The 154 sensors lie at z = 0.75 m on an 11 × 14 grid with 0.60 m spacing. Settings are five ambient bounces, 4096 ambient divisions, 1024 super-samples, ambient resolution 256, accuracy 0.10, and limit weight 10−5. Figure 2 summarizes the architectural factors and checks.
Figure 2. Architectural factors, matched outcomes, and supplementary verification analyses. The supplementary room-depth and overhang tests are restricted to 45% WWR and two reflectance schemes; they are not an expanded full factorial.
The source Nanjing CSWD file, station 582380, was obtained from Climate.OneBuilding [73]. Its EPW metadata state latitude 32.83333° N, longitude 118.8000° E, UTC+8, and elevation 7.1 m; the supplied WEA rounds latitude and elevation. The archived workflow reads that WEA, filters 8 ≤ hour < 18, and calls gendaymtx -m 1 -r angle to generate 145 sky patches plus one ground patch. Although Radiance 6.0 added direct EPW support [74], this study did not use that alternative input path. The baseline contains ten one-hour bins per day, centered at 08:30 through 17:30, covering 08:00–18:00 and totaling 3650 h. These are standardized analysis bins, not an observed occupancy schedule.
The default combined gendaymtx output contains diffuse sky and solar contributions. Direct solar energy is distributed among the four nearest sky patches [75]; no separate high-resolution sun-coefficient correction was used. Consequently, the computation does not resolve the solar disk or sharp sun-patch boundaries as a dedicated direct-sun method would. The room remains fixed with its window outward normal along −Y; sky rotations of 0°, −90°, +90°, and 180° represent S, E, W, and N. Rotating the incident sky relative to a fixed room is the inverse-coordinate counterpart of rotating the entire room, window, overhang, and sensor system relative to a fixed sky. This equivalence relies on the uniform ground and absence of site-specific neighboring obstructions.
The 96 baseline arrays were regenerated during the preceding revision; they are retained unchanged for the present five-reviewer revision. Original submission metrics remain separate. Appendix A preserves the historical single-case check. Supplementary Data S7 contains the earlier paired 4096/8192 checks; new Data S13 targets two configurations near the sDA/high-UDI screening boundaries. Field validations and parameter studies inform the interpretation of numerical checks [76,77], but no direct classroom measurements were available. These exercises assess sensitivity, not measured accuracy.

2.4. Performance Metrics and Screening Criteria

Table 3 distinguishes the indicators by analytical role and research question. Rear-zone DA300 and median hourly minimum/mean uniformity are the primary spatial responses for RQ1. Mean DA300, sDA, UDI, and modeled lighting demand describe whole-room context for RQ2; they are supporting outcomes, not proof of conserved light quantity. High UDI records an excessive-illuminance trade-off and contributes to the RQ3 comparison screen. Rear-zone DA averages the analyzed-hour fraction at or above 300 lx across sensors deeper than 6 m. Uniformity assigns zero when hourly mean illuminance is zero. Percentile-based ratios and a daylit-hour subset test dependence on extreme sensors.
Table 3. Metrics and prespecified comparative screening criteria.
sDA300/50 is the sensor-area fraction whose DA300 is at least 50%, following the threshold notation of LM-83 [78]. No operated-blind algorithm is modeled, and the analysis is not an LM-83 compliance assessment. UDI100–2000 follows the original useful-illuminance band [79,80]. The high-UDI fraction is the sensor-averaged percentage of hours above 2000 lx, not ASE and not a glare probability. UDI is used in the compact factor heatmap because it decreases for both underlit and overlit conditions; primary spatial conclusions are assessed separately with rear-zone DA and uniformity. EN 17037 provides broader daylight criteria [81]. The 300 lx setpoint is a controlled comparison target, not a claim that every university teaching task meets EN 12464-1 [82].
A comparison screen pairs sDA ≥ 75% with high UDI ≤ 10%. The 75% level is motivated by the preferred-sufficiency convention associated with sDA [78], subject to the procedural differences above. The 10% cap is an analyst-selected tolerance for excessive illuminance; it is not borrowed as an equivalent of ASE ≤ 10%. No evidence establishes it as a classroom comfort threshold. A 3 × 3 sensitivity grid combines sDA cutoffs of 55%, 75%, and 90% with high-UDI caps of 5%, 10%, and 15%. Eligible-case counts and orientation-specific highest-UDI cases are reported rather than declaring a universal optimum.
The sensor-level dimming fraction is max(0.10, 1 − min(E/300, 1)); its annual area-weighted mean is multiplied by 9 W m−2 and analysis hours. The fully on baseline is 32.85 kWh m−2 y−1. This idealized model excludes occupancy switching, standby losses, luminaire photometry, actual sensor placement, and commissioning. Supplementary comparisons group sensors into three depth bands or one room-wide zone; each zone shares a dimming fraction driven conservatively by its minimum daylight sensor. Identical installed power density is retained. These are control-resolution scenarios, not validated luminaire designs.
Workplane illuminance cannot determine view-dependent glare. Luminance-based DGP requires observer position and view direction [83,84,85,86]; CIE 171:2006 provides test cases for assessing the accuracy of lighting simulation programs [87]; these tests were not performed in the present study. Neither comfort improvement nor total building energy reduction is inferred from these grid metrics.

2.5. Supplementary Analyses and Statistical Interpretation

The original 3650 h baseline is retained to avoid changing the underlying comparison without disclosure. A nine-hour window of 08:30–17:30 is additionally approximated using weights 0.5 on the 08:30 and 17:30 bins and 1 on the intervening bins, totaling 3285 h. Hourly illuminance is assumed constant within each bin; this is a time-weight sensitivity test, not a subhourly simulation. DA, UDI, sDA eligibility, and lighting demand use the corresponding weighted denominators. The split-day scenario retains 08:00–12:00 and 14:00–18:00 (2920 h). The term-weekday scenario retains those bins Monday–Friday in March–June and September–December (1392 h), using calendar 2023 to match the EPW header’s Sunday start. It is illustrative, not an official timetable; holidays, examinations, and evening classes are not modeled.
Geometry checks vary depth to 6 and 12 m, holding width, height, WWR 45%, and overhang 0.60 m fixed. In each room, rear wall reflectance remains 0.80, and side reflectance is recalculated as 0.55−0.25W/(2D): 0.40 at 6 m and 0.475 at 12 m, preserving the equal-mean contrast. The rearmost third is used for cross-depth comparison. Shading checks remove the overhang or increase its projection to 1.20 m in the 9 m room. Each alternative compares uniform and high-reflectance rear walls in all four orientations: 32 additional annual cases. Width, height, glazing transmittance, furniture, and combined depth–shading interactions remain untested.
Matched effects are reported as absolute percentage-point changes for daylight fractions, absolute ratio changes for uniformity, and kWh m−2 y−1 for lighting demand. Marginal means describe WWR and orientation context. Orthogonal sums of squares partition variation across the complete balanced 96-case set. These shares depend on the selected factor ranges; they are not population effect sizes or universal rankings. No inferential p-values are assigned to this deterministic design set.
New controls compare minimum power fractions 0, 0.10, and 0.20 at all three zoning resolutions (Data S9); zero is an ideal mathematical bound, not a claim that an installed system switches off. Data S10 repeats the main-factor sum-of-squares calculation for the 5th- and 10th-percentile/mean definitions. Rear-surface coverage tests at 45% WWR place a flush diffuse 0.20 strip across the full rear wall width, rising from the floor to 0.825 or 1.650 m, covering 25% or 50% of its area. Both uniform and high-reflectance rear schemes receive identical coverage in all four orientations (16 additional annual cases). Side walls are not rebalanced: the purpose is to test loss of exposed finish area, not maintain the original equal-mean intervention after adding objects. Thickness, shelves, occupants, and arbitrary furniture layouts remain absent. Data S12 reports each result. Data S13 reruns north-facing rearward-gradient and east-facing frontward-gradient cases at 45% WWR with 8192 ambient divisions and 2048 super-samples; remaining parameters are fixed. Selection targets proximity to the screen, not a demonstrated global worst case.

3. Results

3.1. Reflectance Redistribution and the Rear Seating Area

Table 4 and Figure 3 address RQ1 through 16 matched aperture–orientation pairs per scheme. The high-reflectance rear scheme changed rear-zone DA by +3.97 percentage points on average (range +1.42 to +7.01) and median minimum/mean uniformity by +0.020. Its average UDI change was +0.51 points. These are redistribution effects at un-changed mean reflectance, not the effect of making all walls lighter.
Table 4. Mean matched differences from uniform walls at the same WWR and orientation.
Figure 3. Matched reflectance-redistribution effects. Dots show the mean of 16 WWR–orientation pairs and lines the observed range, not confidence intervals. Rear-zone DA and uniformity are the primary outcomes.
Across the 16 baseline pairs, mean rear-zone DA is 39.96% for uniform walls and 43.94% for the high-reflectance rear scheme; the corresponding mean of case-level median uniformities is 0.245 and 0.265 (Data S11). These give approximately 9.94% and 8.07% changes relative to the respective aggregate baselines, not observed changes in perceived brightness. Mean whole-room DA changes by only +0.82 percentage points. It remains available in the case-level dataset; Table 4 and Table 6 omit that additional column to keep the primary spatial comparison and candidate summary legible, while Table 5 retains it.
Table 5. Marginal means across the remaining design factors.
The rearward gradient changed rear-zone DA by +1.58 points and uniformity by +0.015. The frontward gradient changed the same outcomes by −1.43 and −0.020, respectively. Scheme effects therefore depend on where the reflecting area is placed, not simply on its existence. Small whole-room changes do not by themselves justify a construction intervention.

3.2. Aperture and Orientation as Design Context

Table 5 reports the WWR and orientation context for RQ2. Larger apertures expand daylight availability but can also raise excessive-illuminance frequency. These effects confirm established façade-design principles; they are the boundary conditions for the reflectance comparison rather than the principal novelty.
Figure 4 visualizes UDI for all 96 cases because it retains the tradeoff between in-adequate and excessive illuminance. It is supplementary to the distribution-focused matched effects in Figure 3, not a substitute for rear-zone DA or uniformity.
Figure 4. Annual UDI100–2000 across orientation, WWR, and reflectance zoning. Each cell is the sensor-averaged analyzed-hour fraction. S, E, W, and N identify the façade orientation.
The east and west cases are not assumed to be daylight symmetric. Geometric symmetry alone does not make a weather-based annual sky symmetric: morning and afternoon direct/diffuse radiation, cloud cover, solar time, and the selected clock-hour window can differ. Supplementary Data S6 reports the input weather split by clock period. This is a plausible input-based explanation, not a demonstrated causal allocation of the east–west difference. A mirrored-sky counterfactual and a second climate are outside the present checks.

3.3. Relative Contributions Within the Tested Factor Ranges

Figure 5 partitions variation in the regenerated full factorial. It distinguishes the dominant aperture/orientation context from the stronger role of reflectance zoning in spatial uniformity. These are descriptive shares within the tested ranges; changing the ranges or adding geometric factors would change the shares. The figure should not be read as a universal hierarchy of architectural design variables.
Figure 5. Share of total sum of squares in the complete balanced factorial. Each percentage describes variation within this design set and is not a population effect size.
The factor ranking is metric-dependent. Reflectance scheme accounts for 53.04% of total variation in minimum/mean uniformity, 50.35% in 5th-percentile/mean, and 45.15% in 10th-percentile/mean. Orientation accounts for 29.81%, 43.13%, and 51.36%, respectively (Data S10). It therefore overtakes scheme for the 10th-percentile definition. These percentages also depend on the four aperture levels, cardinal orientations, and six selected schemes. A factorial variance share is not an intrinsic measure of an architectural variable’s importance.

3.4. Spatial Illustration and Threshold-Dependent Candidate Cases

Figure 6 illustrates the north-facing 45% WWR pair. This mid-range aperture avoids the near-ceiling sDA values of the largest aperture, while north exposure reduces the confounding of the spatial pattern by direct sun. The pair was chosen to make the distribution mechanism legible, not because it represents the average effect. Its exact outputs are listed in Supplementary Data S1; the 16-pair ranges in Table 4/Figure 3 establish how far the observation extends across the design set.
Figure 6. Sensor-level DA300 in the regenerated north-facing 45% WWR pair and its percentage-point difference. This is an illustrative pair, not a representative sample. Dashed lines show the near, middle, and rear sensor bands.
Table 6 lists five highest-UDI candidates meeting the prespecified comparison screen, with uniformity used to break a UDI tie. There are 12 eligible cases, belonging to orientations E, N. Selection changes when the screen changes (Supplementary Data S5). No candidate is described as an overall building-energy optimum: thermal loads, glare, views, costs, and actual lighting operation were not jointly optimized.
Table 6. Highest-UDI cases meeting sDA ≥ 75% and high UDI ≤ 10% in the regenerated baseline.

3.5. Schedule, Control Resolution, and Transferability Checks

Table 7 summarizes matched rear wall effects under alternative schedules, control resolution, and uniformity definitions. All scenarios use the same regenerated arrays within a comparison, so their contrasts do not mix original-submission and regenerated runs. Detailed case-level results are provided in Supplementary Datas S1–S7.
Table 7. Mean matched high-reflectance rear wall changes in supplementary scenarios.
The illustrative term schedule contains 1392 analysis hours rather than 3650. Its rear-zone and energy contrasts differ from the all-year baseline, so the full-year lighting-demand values must not be read as measured classroom bills. Grouped-zone results also show why the sensor-independent estimate is conditional on control resolution. The conservative minimum-sensor model changes both baseline demand and the finish benefit; it does not reproduce a particular installed luminaire layout.
The 32 geometry/shading cases yield rear-third DA contrasts from +0.68 to +8.39 percentage points. Equal-mean reflectance is preserved at each depth, but effect magnitudes are configuration dependent. These one-factor checks expand the evidence beyond the 9 m baseline without validating all room dimensions or shading arrangements. The 5th/10th-percentile uniformity checks reduce dependence on the single darkest sensor; differences across these definitions caution against interpreting the minimum/mean result alone.
The paired ambient-division checks show absolute 4096-to-8192 uniformity changes up to 0.004 for the four checked configurations. Supplementary Data S7 reports each metric and each paired effect, rather than treating the original single-case convergence test as proof that every small difference is resolved. No field-accuracy claim follows from this numerical exercise.
The north-facing rearward-gradient boundary case changes from sDA 74.03% at 4096 divisions to 75.32% at 8192, while high UDI changes from 6.12% to 6.07%. It crosses into the baseline screen at the higher setting. The east-facing frontward-gradient case changes from sDA 77.92% to 76.62%, with high UDI 10.09% to 10.10%, and remains outside the 10% cap (Data S13). Thus, the exact candidate set is not numerically invariant. Table 6 is a descriptive 4096-division list, not a convergence-certified recommendation; the checks do not establish the stability of every candidate or the highest-UDI ranking after rerunning all 96 cases.
At 45% WWR, increasing ambient divisions from 4096 to 8192 retained positive rear-zone DA contrasts in both checked orientations: +3.14 to +2.45 points for south and +7.00 to +6.63 points for north. The corresponding uniformity contrasts changed from +0.022 to +0.014 and from +0.021 to +0.027. The direction survives these checks, but the exact magnitude should not be treated as numerically invariant. Across the original submission summaries and regenerated baseline, the largest single-case discrepancy was 3.25 sDA points, 1.30 rear-zone DA points, 0.021 uniformity, and 0.099 kWh m−2 y−1 lighting demand. These discrepancies are disclosed rather than interpreted as independent physical uncertainty bounds.
The nine-hour weighted window yields a mean rear-zone DA contrast of +4.20 percentage points and a lighting-demand contrast of −0.120 kWh m−2 over 3285 weighted hours (Data S8). At sensor-level control, changing the minimum power fraction from 0 to 0.10 to 0.20 changes the mean demand contrast from −0.157 to −0.130 to −0.103 kWh m−2 over the baseline year. The three-depth-zone values are −0.102, −0.091, and −0.077; whole-room values are −0.751, −0.624, and −0.504 (Data S9). Their different magnitudes reflect the shared minimum-sensor signal and dimming floor, not measured system savings. In the coverage checks, the mean rear-zone DA contrast is +4.13 points with 25% coverage and +1.31 with 50% coverage (Data S12). Coverage position and interreflection make a linear reduction inappropriate; these limited cases do not prescribe a minimum exposed wall area.

4. Discussion

4.1. Contribution Relative to Reflectance and Classroom Studies

The controlled contribution concerns the location of reflectance rather than a general claim that lighter surfaces improve daylight. A useful physical interpretation follows the diffuse interreflection balance: each surface receives transmitted/incident light and reflected light from other surfaces; its outgoing reflected component depends on both its reflectance and that incident field [67,68]. Equal area-weighted reflectance does not equalize incident flux, surface view factors, or their coupling. Changing the rear wall and compensating side walls therefore changes transfer paths and sensor illuminance unequally. Rear-zone DA records threshold crossings in the deep zone; uniformity records the spatial low-to-mean relation. These outputs support a redistribution interpretation, but no path-resolved flux decomposition was computed. The frontward gradient is a counterexample to treating equal mean reflectance as spatial equivalence.
The 2025 study by Cheshmeh Noor and colleagues jointly varies WWR and wall reflection coefficient across plan geometries while evaluating photopic, melanopic, and glare outcomes at critical times [50]. Their 2026 analysis addresses depth-to-width ratio and orientation-dependent non-visual responses [51]. The present study adds an annual, spatial-allocation contrast with constant mean wall reflectance. It does not supersede their spectral or glare evaluations. The supplementary depth checks agree with their broader conclusion that geometry conditions the effect of reflectance but use a different outcome and should not be compared as equivalent effect sizes.
Angelaki and Besenecker’s classroom pilot treats distribution and directionality as design variables, primarily for electric lighting [52]. Its architectural perspective supports linking finishes and spatial use, but its scenarios cannot validate the present daylight model. Vidiyanti and colleagues assess actual visual fatigue under daylight configurations and learning-media conditions [53]. Their work reinforces the need for direct occupant evidence before attributing comfort or fatigue benefits to the present changes. The original contribution here remains a bounded physical-design comparison.
The WWR and orientation results confirm established window/shading relationships [24,25,26,27,28,29,39,40,41,42]. The supplementary overhang comparison makes clear that a single fixed shading baseline is not an orientation-neutral optimum. Published fixed/dynamic shading research [54,55,56,57] is therefore used to contextualize subsequent design evaluation, not to claim that fins, alternative glazing, or automated shades were validated by the baseline factorial.

4.2. Magnitude, Numerical Sensitivity, and Lighting Demand

The mean rear-zone change of 3.97 percentage points equals approximately 145 additional 300 lx-qualified hours per rear sensor over the 3650 h comparison window; those hours need not occur simultaneously across sensors. It is not a percentage increase in room brightness or a demonstrated perceptual improvement. The practical question is whether this change matters to a planned finish specification, not whether it warrants a major façade intervention.
The sensor-level lighting-demand reduction of 0.130 kWh m−2 y−1 is approximately 1.5% of the matched uniform wall baseline and about 8.4 kWh per modeled classroom over that comparison year. This is a small, modeled benefit. No payback, net-carbon, maintenance cost, or whole-building saving can be inferred without embodied impacts, actual operating hours, tariffs, and heating/cooling calculations. Reflectance zoning may be worth evaluating when painting is already planned; this study does not establish a cost-effective stand-alone retrofit.
The paired convergence tests and percentile-based uniformity checks qualify the effect sizes. Stable engine behavior and a favorable average contrast do not make every near-zero difference meaningful. Threshold-based sDA can change when a few sensors cross 50%; minimum-based uniformity can change when the darkest sensor changes. Numerical sensitivity is therefore reported alongside matched ranges, and small scheme differences should be treated as design hypotheses until they survive project-specific numerical and empirical checks.
Lighting-control resolution is an additional mechanism, not a minor implementation detail. Studies of daylight-responsive lighting and integrated design [58,59,60,66] emphasize operation and commissioning. The supplementary grouped-zone calculations bound a more conservative common-signal scenario. They still omit actual luminaire photometry and feedback-sensor calibration, so they cannot predict the installed system’s energy use.

4.3. Architectural Implications and Their Evidence Boundaries

The tested variables map directly to architectural project decisions: orientation to site/massing, aperture to elevation, overhang to section, and reflectance zones to interior elevations and finish schedules. Climate-based dashboards and design sequences support comparing such decisions iteratively rather than treating one illuminance metric as a complete brief [17,18,19,64]. Within this model, finish placement refines rear-zone distribution, while envelope variables set the larger daylight context. The study does not establish a universally optimal sequence or a standard classroom specification.
For new construction, alternative aperture positions, head heights, and solar-control sections should be evaluated before fixing a finish specification. For an existing classroom with a fixed envelope, a finish study can be limited to practicable exposed areas and checked with actual lighting zones. Integrated design research supports attention to envelope coordination and operation [37,38,66]. The flush-strip sensitivity illustrates why boards, storage, and acoustic treatments can change the finish benefit, but does not model a furnished room. Durability, gloss, cleaning, projector contrast, and soiling remain additional specification requirements rather than demonstrated benefits.
Task and seated-view evaluation must accompany grid metrics when a project decision concerns comfort. Metric comparisons and classroom subjective studies show why workplane thresholds cannot replace direct evidence of occupant response [20,21]. Luminance-based glare evaluation needs specified views [83,84,85,86], and daylight/view guidance addresses requirements not optimized here [63]. Consequently, a high-UDI cap can identify a comparison trade-off without demonstrating acceptable glare, thermal conditions, or user experience.

4.4. Limitations and Further Validation

Limitations affecting confidence in the present numerical conclusions include the lack of measured calibration, coarse solar allocation within the 145-patch sky, threshold crossings near the screen, and sensitivity of minimum-based uniformity to a single sensor. Ambient-division checks do not test sky angular resolution, and published engine validation does not establish this model’s accuracy. Original/regenerated discrepancies and the new candidate-set change require cautious interpretation. Measurement-versus-simulation research reinforces this distinction [88]. No comfort, glare, or whole-building energy benefit is established.
Transferability is separately limited by one Nanjing weather file; fixed width, height, glazing, and centered-window form; limited depth and horizontal-overhang alternatives; and the absence of site obstructions or a full furnished configuration. Rebalancing side reflectance is necessary when W/D changes. The rear-coverage cases and academic-time scenario are controlled sensitivity models, not field observations. Grouped control re-mains idealized and lacks installed luminaire photometry, actual photosensor calibration, occupancy switching, and commissioning. Equal RGB wall inputs do not resolve hue, chroma, gloss, spectral appearance, or perceived lightness.
The first priority is measured workplane and seated-view luminance validation with documented geometry, reflectance, skies, and exposed surfaces, together with an explicit direct-sun/high-angular-resolution check. Next, screening candidates require targeted numerical checks and actual lighting-control layouts and schedules. Broader application then requires multiple climates and room proportions, alternative opening heights and distributions, glazing and shading combinations, and coupled thermal/lighting evaluation. This order separates confidence in the present numerical mechanism from subsequent design-space generalization.

5. Conclusions

At constant opaque-wall mean reflectance, wall-finish placement changes the modeled depth distribution of daylight. Across 16 matched aperture–orientation pairs, the high-reflectance rear scheme raises rear-zone DA from 39.96% to 43.94% on average and case-level median minimum/mean uniformity from 0.245 to 0.265. The contribution is this controlled spatial comparison within a building-design model, rather than the established effects of aperture and orientation.
The associated mean lighting-demand reduction is 0.130 kWh m−2 over the standardized 3650 h year under ideal sensor-level dimming. Schedule, dimming-floor, control-grouping, coverage, metric-definition, and convergence checks make its conditional nature explicit. A boundary case crosses the sDA screen at higher ambient divisions, and the dominant uniformity factor changes with the percentile definition. Candidate lists and variance shares should therefore remain descriptive of the tested calculation.
These findings support project-specific evaluation of exposed wall finishes together with classroom geometry, window design, solar control, and lighting operation. They do not establish perceptible comfort improvements, a broadly optimal WWR/orientation, or lower total building energy demand. Measured validation and higher-resolution solar treatment remain necessary before stronger recommendations.

Supplementary Materials

The following supporting information can be downloaded at: https://www.mdpi.com/article/10.3390/buildings16234660/s1, Method S1 and Datas S1–S13 accompany the revision. Datas S8–S13 document the nine-hour weighting, dimming floors, uniformity-factor shares, absolute baselines, rear-surface coverage, and boundary convergence. The versioned code archive FiveReviewer_Code_and_Data_20261110 contains executable scripts, model inputs, numerical outputs, version metadata, and SHA-256 checksums. Original submission and preceding-revision metrics remain separately identified. No public repository DOI has been registered for this archive.

Author Contributions

Conceptualization, B.H., P.L. and Y.S.; methodology, Y.S.; formal analysis, B.H.; investigation, P.L.; resources, B.H. and Y.S.; data curation, Y.S.; writing—original draft preparation, B.H. and P.L.; writing—review and editing, Y.S.; funding acquisition, B.H. and Y.S. All authors have read and agreed to the published version of the manuscript.

Funding

This research was supported by The College Students’ Innovation Training Projects of Nanjing Forestry University, grant number 2026NFUSPITP0121.

Data Availability Statement

The accompanying research archive contains simulation and postprocessing scripts, regenerated case metrics, supplementary results, and source weather inputs. No field measurement or participant dataset was collected. The regenerated annual sensor arrays are retained with the research files.

Acknowledgments

The authors used OpenAI ChatGPT Work (the model version is 6.1.) to assist with language translated and reference format checking. All analyses were rerun, and all outputs, citations, and interpretations were reviewed by the authors, who take full responsibility for the content.

Conflicts of Interest

The authors declare no conflicts of interest.

Abbreviations

The following abbreviations are used in this manuscript:
DADaylight Autonomy
DGPDaylight Glare Probability
EPWEnergyPlus Weather Format
sDASpatial Daylight Autonomy
UDIUseful Daylight Illuminance
VTVisible Transmittance
WWRWindow-to-Wall Ratio

Appendix A. Submission-Stage Ambient-Division Check

Table A1 preserves the submission-stage numerical check for historical transparency. It is not substituted for the newly regenerated results. Updated paired checks for both reflectance configurations in north and south orientations are provided in Supplementary Data S7 and discussed in Section 3.5.
Table A1. Original submission-stage ambient-division check for the south-facing 45% WWR uniform case.

References

  1. Wong, I.L. A review of daylighting design and implementation in buildings. Renew. Sustain. Energy Rev. 2017, 74, 959–968. [Google Scholar] [CrossRef] [Scilit]
  2. Tregenza, P.; Mardaljevic, J. Daylighting buildings: Standards and the needs of the designer. Light. Res. Technol. 2018, 50, 63–79. [Google Scholar] [CrossRef] [Scilit]
  3. Galasiu, A.D.; Reinhart, C.F. Current daylighting design practice: A survey. Build. Res. Inf. 2008, 36, 159–174. [Google Scholar] [CrossRef] [Scilit]
  4. Costanzo, V.; Evola, G.; Marletta, L. A review of daylighting strategies in schools: State of the art and expected future trends. Buildings 2017, 7, 41. [Google Scholar] [CrossRef] [Scilit]
  5. Barrett, P.; Davies, F.; Zhang, Y.; Barrett, L. The impact of classroom design on pupils’ learning: Final results of a holistic, multi-level analysis. Build. Environ. 2015, 89, 118–133. [Google Scholar] [CrossRef] [Scilit]
  6. Bluyssen, P.M.; Zhang, D.; Kurvers, S.; Overtoom, M.; Ortiz-Sanchez, M. Self-reported health and comfort of school children in 54 classrooms of 21 Dutch school buildings. Build. Environ. 2018, 138, 106–123. [Google Scholar] [CrossRef] [Scilit]
  7. Heschong, L.; Wright, R.L.; Okura, S. Daylighting impacts on human performance in school. J. Illum. Eng. Soc. 2002, 31, 101–114. [Google Scholar] [CrossRef] [Scilit]
  8. Xu, J.; Gao, Y.; Wu, Y. The visual and non-visual effects of annual daylighting performance on middle school students: A longitudinal field survey of classrooms in Eastern China. Energy Build. 2025, 331, 115364. [Google Scholar] [CrossRef] [Scilit]
  9. Vasquez, N.G.; Rupp, R.F.; Andersen, R.K.; Toftum, J. Occupants’ responses to window views, daylighting and lighting in buildings: A critical review. Build. Environ. 2022, 219, 109172. [Google Scholar] [CrossRef] [Scilit]
  10. Van de Perre, L.; Smet, K.; Hanselaer, P.; Dujardin, M.; Ryckaert, W. The effect of correlated colour temperature and wall luminance on spatial brightness and scene preference in a windowless office setup. Light. Res. Technol. 2024, 56, 316–336. [Google Scholar] [CrossRef] [Scilit]
  11. von Castell, C.; Hecht, H.; Oberfeld, D. Bright paint makes interior-space surfaces appear farther away. PLoS ONE 2018, 13, e0201976. [Google Scholar] [CrossRef] [Scilit]
  12. Cai, W.; Yue, J.; Dai, Q.; Hao, L.; Lin, Y.; Shi, W.; Huang, Y.; Wei, M. The impact of room surface reflectance on corneal illuminance and rule-of-thumb equations for circadian lighting design. Build. Environ. 2018, 141, 288–297. [Google Scholar] [CrossRef] [Scilit]
  13. Yao, Q.; Cai, W.; Li, M.; Hu, Z.; Xue, P.; Dai, Q. Efficient circadian daylighting: A proposed equation, experimental validation, and the consequent importance of room surface reflectance. Energy Build. 2020, 210, 109784. [Google Scholar] [CrossRef] [Scilit]
  14. Brembilla, E.; Hopfe, C.; Mardaljevic, J. Influence of input reflectance values on climate-based daylight metrics using sensitivity analysis. J. Build. Perform. Simul. 2018, 11, 333–349. [Google Scholar] [CrossRef] [Scilit]
  15. Hosseini, S.M.; Mohammadi, M.; Rosemann, A.; Schröder, T. Quantitative investigation through climate-based daylight metrics of visual comfort due to colorful glass and orosi windows in Iranian architecture. J. Daylight. 2018, 5, 21–33. [Google Scholar] [CrossRef] [Scilit]
  16. Dangol, R.; Kruisselbrink, T.; Rosemann, A. Effect of window glazing on colour quality of transmitted daylight. J. Daylight. 2017, 4, 37–47. [Google Scholar] [CrossRef] [Scilit]
  17. Reinhart, C.F.; Mardaljevic, J.; Rogers, Z. Dynamic daylight performance metrics for sustainable building design. LEUKOS 2006, 3, 7–31. [Google Scholar] [CrossRef] [Scilit]
  18. Kleindienst, S.; Bodart, M.; Andersen, M. Graphical representation of climate-based daylight performance to support architectural design. LEUKOS 2008, 5, 39–61. [Google Scholar] [CrossRef] [Scilit]
  19. Reinhart, C.F.; Wienold, J. The daylighting dashboard—A simulation-based design analysis for daylit spaces. Build. Environ. 2011, 46, 386–396. [Google Scholar] [CrossRef] [Scilit]
  20. Van Den Wymelenberg, K.; Inanici, M. A Critical investigation of common lighting design metrics for predicting human visual comfort in offices with daylight. LEUKOS 2014, 10, 145–164. [Google Scholar] [CrossRef] [Scilit]
  21. Liu, B.; Liu, Y.; Deng, Q.; Hu, K. A study on daylighting metrics related to the subjective evaluation of daylight and visual comfort of students in China. Energy Build. 2023, 287, 113001. [Google Scholar] [CrossRef] [Scilit]
  22. Wang, M.; Peng, X.; Cai, Y. A multi-metric evaluation of classroom daylighting: Integrating myopia prevention and visual comfort. J. Build. Eng. 2025, 99, 111616. [Google Scholar] [CrossRef] [Scilit]
  23. Korsavi, S.S.; Zomorodian, Z.S.; Tahsildoost, M. Visual comfort assessment of daylit and sunlit areas: A longitudinal field survey in classrooms in Kashan, Iran. Energy Build. 2016, 128, 305–318. [Google Scholar] [CrossRef] [Scilit]
  24. Alwetaishi, M.; Benjeddou, O. Impact of window to wall ratio on energy loads in hot regions: A study of building energy performance. Energies 2021, 14, 1080. [Google Scholar] [CrossRef] [Scilit]
  25. Lim, Y.W.; Kandar, M.Z.; Ahmad, M.H.; Ossen, D.R.; Abdullah, A.M. Building façade design for daylighting quality in typical government office building. Build. Environ. 2012, 57, 194–204. [Google Scholar] [CrossRef] [Scilit]
  26. Kazanasmaz, T.; Grobe, L.O.; Bauer, C.; Krehel, M.; Wittkopf, S. Three approaches to optimize optical properties and size of a south-facing window for spatial daylight autonomy. Build. Environ. 2016, 102, 243–256. [Google Scholar] [CrossRef] [Scilit]
  27. Xue, P.; Li, Q.; Xie, J.; Zhao, M.; Liu, J. Optimization of window-to-wall ratio with sunshades in China low latitude region considering daylighting and energy saving requirements. Appl. Energy 2019, 233–234, 62–70. [Google Scholar] [CrossRef] [Scilit]
  28. Mahdavinejad, M.; Bazazzadeh, H.; Mehrvarz, F.; Berardi, U.; Nasr, T.; Pourbagher, S.; Hoseinzadeh, S. The impact of facade geometry on visual comfort and energy consumption in an office building in different climates. Energy Rep. 2024, 11, 1–17. [Google Scholar] [CrossRef] [Scilit]
  29. Lee, K.; Han, K.; Lee, J. The impact of shading type and azimuth orientation on the daylighting in a classroom–focusing on effectiveness of façade shading, comparing the results of DA and UDI. Energies 2017, 10, 635. [Google Scholar] [CrossRef] [Scilit]
  30. Sedaghatnia, M.; Faizi, M.; Khakzand, M.; Sanaieian, H. Energy and daylight optimization of shading devices, window size, and orientation for educational spaces in Tehran, Iran. J. Archit. Eng. 2021, 27, 04021011. [Google Scholar] [CrossRef] [Scilit]
  31. Moazzeni, M.; Ghiabaklou, Z. Investigating the influence of light shelf geometry parameters on daylight performance and visual comfort, a case study of educational space in Tehran, Iran. Buildings 2016, 6, 26. [Google Scholar] [CrossRef] [Scilit]
  32. Freewan, A.A.; Al Dalala, J.A. Assessment of daylight performance of advanced daylighting strategies in large university classrooms; case study classrooms at JUST. Alex. Eng. J. 2020, 59, 791–802. [Google Scholar] [CrossRef] [Scilit]
  33. Kwon, C.W.; Lee, K.J. Integrated daylighting design by combining passive method with daysim in a classroom. Energies 2018, 11, 3168. [Google Scholar] [CrossRef] [Scilit]
  34. Al-Sallal, K.A. Daylighting and visual performance: Evaluation of classroom design issues in the UAE. Int. J. Low.-Carbon Technol. 2010, 5, 201–209. [Google Scholar] [CrossRef] [Scilit]
  35. Nocera, F.; Lo Faro, A.; Costanzo, V.; Raciti, C. Daylight performance of classrooms in a mediterranean school heritage building. Sustainability 2018, 10, 3705. [Google Scholar] [CrossRef] [Scilit]
  36. Luo, J.; Yan, G.; Zhao, L.; Zhong, X.; Su, X. Evaluation of design parameters for daylighting performance in secondary school classrooms based on field measurements and physical simulations: A case study of secondary school classrooms in Guangzhou. Buildings 2024, 14, 637. [Google Scholar] [CrossRef] [Scilit]
  37. Abdollahi Rizi, R.; Sangin, H.; Haghighatnejad Chobari, K.; Eltaweel, A.; Phipps, R. Optimising daylight and ventilation performance: A building envelope design methodology. Buildings 2023, 13, 2840. [Google Scholar] [CrossRef] [Scilit]
  38. Sawyer, A.O.; Navvab, M.; Weissman, D.; Ji, G. Facade photometry: Linking annual daylight performance to facade design. Buildings 2022, 12, 1556. [Google Scholar] [CrossRef] [Scilit]
  39. Liu, J.; Li, Z.; Zhong, Q.; Wu, J.; Xie, L. Multi-objective optimization of daylighting performance and energy consumption of educational buildings in different climatic zones of China. J. Build. Eng. 2024, 95, 110322. [Google Scholar] [CrossRef] [Scilit]
  40. Lakhdari, K.; Sriti, L.; Painter, B. Parametric optimization of daylight, thermal and energy performance of middle school classrooms, case of hot and dry regions. Build. Environ. 2021, 204, 108173. [Google Scholar] [CrossRef] [Scilit]
  41. Ziaee, N.; Vakilinezhad, R. Multi-objective optimization of daylight performance and thermal comfort in classrooms with light-shelves: Case studies in Tehran and Sari, Iran. Energy Build. 2022, 254, 111590. [Google Scholar] [CrossRef] [Scilit]
  42. Zhang, A.; Bokel, R.; van den Dobbelsteen, A.; Sun, Y.; Huang, Q.; Zhang, Q. Optimization of thermal and daylight performance of school buildings based on a multi-objective genetic algorithm in the cold climate of China. Energy Build. 2017, 139, 371–384. [Google Scholar] [CrossRef] [Scilit]
  43. Gagne, J.; Andersen, M. A generative facade design method based on daylighting performance goals. J. Build. Perform. Simul. 2012, 5, 141–154. [Google Scholar] [CrossRef] [Scilit]
  44. Hosseini, S.M.; Mohammadi, M.; Guerra-Santin, O. Interactive kinetic façade: Improving visual comfort based on dynamic daylight and occupant’s positions by 2D and 3D shape changes. Build. Environ. 2019, 165, 106396. [Google Scholar] [CrossRef] [Scilit]
  45. Chi, D.A.; Moreno, D.; Esquivias, P.M.; Navarro, J. Optimization method for perforated solar screen design to improve daylighting using orthogonal arrays and climate-based daylight modelling. J. Build. Perform. Simul. 2017, 10, 144–160. [Google Scholar] [CrossRef] [Scilit]
  46. You, W.; Qin, M.; Ding, W. Improving building facade design using integrated simulation of daylighting, thermal performance and natural ventilation. Build. Simul. 2013, 6, 269–282. [Google Scholar] [CrossRef] [Scilit]
  47. Pilechiha, P.; Mahdavinejad, M.; Pour Rahimian, F.; Carnemolla, P.; Seyedzadeh, S. Multi-objective optimisation framework for designing office windows: Quality of view, daylight and energy efficiency. Appl. Energy 2020, 261, 114356. [Google Scholar] [CrossRef] [Scilit]
  48. Xie, J.C.; Xue, P.; Mak, C.M.; Liu, J.P. Balancing energy and daylighting performances for envelope design: A new index and proposition of a case study in Hong Kong. Appl. Energy 2017, 205, 13–22. [Google Scholar] [CrossRef] [Scilit]
  49. Freewan, A.A. Impact of external shading devices on thermal and daylighting performance of offices in hot climate regions. Sol. Energy 2014, 102, 14–30. [Google Scholar] [CrossRef] [Scilit]
  50. Noor, M.C.; Saradj, F.M.; Yazdanfar, S.A. Optimal daylighting design for standard photopic and melanopic equivalent daylight illuminance, and glare minimization in Tehran classrooms. J. Build. Eng. 2025, 105, 112104. [Google Scholar] [CrossRef] [Scilit]
  51. Cheshmeh Noor, M.; Yazdanfar, S.A.; Mehdizadeh Saradj, F. Quantitative analysis of daylighting design impacts on light’s non-visual effects in classrooms: Case study in a cold semi-arid climate (Tehran). Build. Environ. 2026, 288, 113973. [Google Scholar] [CrossRef] [Scilit]
  52. Angelaki, S.; Besenecker, U. Lighting distribution in school classrooms: A pilot study. Archit. Sci. Rev. 2026, 1–14. [Google Scholar] [CrossRef] [Scilit]
  53. Vidiyanti, C.; Wonorahardjo, S.; Koerniawan, M.D. Classroom visual fatigue indication and its determinants: Daylighting, learning media, and spatial factors. Build. Environ. 2026, 290, 114135. [Google Scholar] [CrossRef] [Scilit]
  54. Esquivias, P.; Munoz, C.; Acosta, I.; Moreno, D.; Navarro, J. Climate-based daylight analysis of fixed shading devices in an open-plan office. Light. Res. Technol. 2016, 48, 205–220. [Google Scholar] [CrossRef] [Scilit]
  55. Konstantoglou, M.; Tsangrassoulis, A. Dynamic operation of daylighting and shading systems: A literature review. Renew. Sustain. Energy Rev. 2016, 60, 268–283. [Google Scholar] [CrossRef] [Scilit]
  56. Shen, H.; Tzempelikos, A. Sensitivity analysis on daylighting and energy performance of perimeter offices with automated shading. Build. Environ. 2013, 59, 303–314. [Google Scholar] [CrossRef] [Scilit]
  57. Tzempelikos, A.; Chan, Y.C. Estimating detailed optical properties of window shades from basic available data and modeling implications on daylighting and visual comfort. Energy Build. 2016, 126, 396–407. [Google Scholar] [CrossRef] [Scilit]
  58. Papinutto, M.; Boghetti, R.; Colombo, M.; Basurto, C.; Reutter, K.; Lalanne, D.; Kämpf, J.H.; Nembrini, J. Saving energy by maximising daylight and minimising the impact on occupants: An automatic lighting system approach. Energy Build. 2022, 268, 112176. [Google Scholar] [CrossRef] [Scilit]
  59. Odiyur Vathanam, G.S.; Kalyanasundaram, K.; Elavarasan, R.M.; Hussain Khahro, S.; Subramaniam, U.; Pugazhendhi, R.; Ramesh, M.; Gopalakrishnan, R.M. A review on effective use of daylight harvesting using intelligent lighting control systems for sustainable office buildings in India. Sustainability 2021, 13, 4973. [Google Scholar] [CrossRef] [Scilit]
  60. Yu, X.; Su, Y.; Chen, X. Application of RELUX simulation to investigate energy saving potential from daylighting in a new educational building in UK. Energy Build. 2014, 74, 191–202. [Google Scholar] [CrossRef] [Scilit]
  61. Pellegrino, A.; Cammarano, S.; Lo Verso, V.R.; Corrado, V. Impact of daylighting on total energy use in offices of varying architectural features in Italy: Results from a parametric study. Build. Environ. 2017, 113, 151–162. [Google Scholar] [CrossRef] [Scilit]
  62. Acosta, I.; Campano, M.Á.; Leslie, R.; Radetsky, L. Daylighting design for healthy environments: Analysis of educational spaces for optimal circadian stimulus. Sol. Energy 2019, 193, 584–596. [Google Scholar] [CrossRef] [Scilit]
  63. Lee, E.S.; Matusiak, B.S.; Geisler-Moroder, D.; Selkowitz, S.E.; Heschong, L. Advocating for view and daylight in buildings: Next steps. Energy Build. 2022, 265, 112079. [Google Scholar] [CrossRef] [Scilit]
  64. Reinhart, C.; LoVerso, V. A rules of thumb-based design sequence for diffuse daylight. Light. Res. Technol. 2010, 42, 7–31. [Google Scholar] [CrossRef] [Scilit]
  65. Xiao, W.; Zhong, W.; Wu, H.; Zhang, T. Multiobjective optimization of daylighting, energy, and thermal performance for form variables in atrium buildings in China’s hot summer and cold winter climate. Energy Build. 2023, 297, 113476. [Google Scholar] [CrossRef] [Scilit]
  66. Gentile, N.; Lee, E.S.; Osterhaus, W.; Altomonte, S.; Naves David Amorim, C.; Ciampi, G.; Garcia-Hansen, V.; Maskarenj, M.; Scorpio, M.; Sibilio, S. Evaluation of integrated daylighting and electric lighting design projects: Lessons learned from international case studies. Energy Build. 2022, 268, 112191. [Google Scholar] [CrossRef] [Scilit]
  67. Ward, G.J. The RADIANCE lighting simulation and rendering system. In 21st Annual Conference on Computer Graphics and Interactive Techniques—SIGGRAPH’94; ACM: New York, NY, USA, 1994; pp. 459–472. [Google Scholar] [CrossRef] [Scilit]
  68. Bourgeois, D.; Reinhart, C.F.; Ward, G. Standard daylight coefficient model for dynamic daylighting simulations. Build. Res. Inf. 2008, 36, 68–82. [Google Scholar] [CrossRef] [Scilit]
  69. Reinhart, C.F.; Walkenhorst, O. Validation of dynamic RADIANCE-based daylight simulations for a test office with external blinds. Energy Build. 2001, 33, 683–697. [Google Scholar] [CrossRef] [Scilit]
  70. McNeil, A.; Lee, E. A validation of the radiance three-phase simulation method for modelling annual daylight performance of optically complex fenestration systems. J. Build. Perform. Simul. 2013, 6, 24–37. [Google Scholar] [CrossRef] [Scilit]
  71. Brembilla, E.; Chi, D.; Hopfe, C.; Mardaljevic, J. Evaluation of climate-based daylighting techniques for complex fenestration and shading systems. Energy Build. 2019, 203, 109454. [Google Scholar] [CrossRef] [Scilit]
  72. Brembilla, E.; Mardaljevic, J. Climate-Based Daylight Modelling for compliance verification: Benchmarking multiple state-of-the-art methods. Build. Environ. 2019, 158, 151–164. [Google Scholar] [CrossRef] [Scilit]
  73. Climate.OneBuilding.Org. Repository of Free Climate Data for Building Performance Simulation. Available online: https://climate.onebuilding.org/ (accessed on 23 August 2026).
  74. Ward, G. Official Radiance 6.0 Release. Available online: https://discourse.radiance-online.org/t/official-radiance-6-0-release/6873 (accessed on 10 November 2026).
  75. Radiance. Gendaymtx Manual. Available online: https://floyd.lbl.gov/radiance/man_html/gendaymtx.1.html (accessed on 10 November 2026).
  76. Kharvari, F. An empirical validation of daylighting tools: Assessing radiance parameters and simulation settings in Ladybug and Honeybee against field measurements. Sol. Energy 2020, 207, 1021–1036. [Google Scholar] [CrossRef] [Scilit]
  77. Mousavi, S.M.; Khan, T.H.; Lim, Y.W. Empirical validation of radiance-IES daylight simulation for furnished and unfurnished rooms under a tropical sky. Int. J. Sustain. Build. Technol. Urban Dev. 2016, 7, 61–69. [Google Scholar] [CrossRef] [Scilit]
  78. IES LM-83-12; Approved Method: IES Spatial Daylight Autonomy (sDA) and Annual Sunlight Exposure (ASE). Illuminating Engineering Society (IES): New York, NY, USA, 2012.
  79. Nabil, A.; Mardaljevic, J. Useful daylight illuminance: A new paradigm for assessing daylight in buildings. Light. Res. Technol. 2005, 37, 41–57. [Google Scholar] [CrossRef] [Scilit]
  80. Nabil, A.; Mardaljevic, J. Useful daylight illuminances: A replacement for daylight factors. Energy Build. 2006, 38, 905–913. [Google Scholar] [CrossRef] [Scilit]
  81. EN 17037:2018+A1:2021; Daylight in Buildings. European Committee for Standardization (CEN): Brussels, Belgium, 2021.
  82. EN 12464-1:2021; Light and Lighting—Lighting of Work Places—Part 1: Indoor Work Places. European Committee for Standardization (CEN): Brussels, Belgium, 2021.
  83. Wienold, J.; Christoffersen, J. Evaluation methods and development of a new glare prediction model for daylight environments with the use of CCD cameras. Energy Build. 2006, 38, 743–757. [Google Scholar] [CrossRef] [Scilit]
  84. Karlsen, L.; Heiselberg, P.; Bryn, I.; Johra, H. Verification of simple illuminance based measures for indication of discomfort glare from windows. Build. Environ. 2015, 92, 615–626. [Google Scholar] [CrossRef] [Scilit]
  85. Jakubiec, J.; Reinhart, C. The ‘adaptive zone’—A concept for assessing discomfort glare throughout daylit spaces. Light. Res. Technol. 2012, 44, 149–170. [Google Scholar] [CrossRef] [Scilit]
  86. Chaloeytoy, K.; Ichinose, M.; Chien, S.C. Determination of the simplified daylight glare probability (DGPs) criteria for daylit office spaces in Thailand. Buildings 2020, 10, 180. [Google Scholar] [CrossRef] [Scilit]
  87. CIE 171:2006; Test Cases to Assess the Accuracy of Lighting Computer Programs. International Commission on Illumination (CIE): Vienna, Austria, 2006.
  88. Brembilla, E.; Drosou, N.; Mardaljevic, J. Assessing daylight performance in use: A comparison between long-term daylight measurements and simulations. Energy Build. 2022, 262, 111989. [Google Scholar] [CrossRef] [Scilit]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Article Metrics

Citations

Article Access Statistics

Multiple requests from the same IP address are counted as one view.