Abstract
In this study, infrared thermography (IRT) was used to quantitatively evaluate the thermal bridge characteristics and in situ thermal performance of exterior wall-to-floor junctions in occupied precast concrete (PC) and reinforced concrete (RC) apartment buildings with different exterior wall systems. Three representative PC apartment buildings with different exterior wall systems were investigated under winter nighttime conditions. IRT was used to qualitatively assess thermal bridge characteristics in all three buildings, while the in situ thermal performance of one representative case was quantitatively evaluated by estimating the effective thermal transmittance (U-value) from infrared surface temperature measurements based on heat transfer theory. The estimated U-value was validated using three-dimensional heat transfer simulations. The results showed that exterior wall-to-floor junctions were major heat-loss pathways in all cases, while the thermal bridge patterns varied depending on the exterior wall system and continuity of insulation. In Case 3, the PC curtain wall system with improved insulation continuity exhibited less pronounced thermal bridging than the corresponding RC system. The IRT-estimated was 0.379 W/m2·K for the PC building and 0.661 W/m2·K for the RC building, representing a 42.7% lower value for the PC building. The corresponding simulated values were 0.407 and 0.514 W/m2·K, with differences between the IRT-estimated and simulated values of 7.4% and 22.2%, respectively. These findings are expected to provide useful baseline data for post-occupancy performance assessment and improvement in envelope design for off-site construction (OSC)-based PC residential buildings.
1. Introduction
The building sector accounts for a substantial share of global energy consumption and greenhouse gas emissions, making improvements in building energy efficiency a key strategy for reducing energy demand and achieving carbon neutrality targets (UNEP, 2023) [1]. In South Korea, apartment buildings constitute the predominant residential building type, and heat loss through exterior walls, which account for the largest portion of the building envelope, directly affects heating energy consumption and indoor thermal comfort. Accordingly, thermal insulation requirements for apartment building envelopes have been progressively strengthened, and high-performance insulation materials, along with various thermal bridge mitigation technologies, have been widely adopted.
However, the in situ thermal performance of buildings may differ from that predicted during the design stage. In Korean apartment buildings, particularly during the winter heating season, heat loss at the exterior wall-to-floor junction is exacerbated by hydronic floor heating pipes embedded in the floor slab, as illustrated in Figure 1a. Consequently, the exterior wall-to-floor junction is recognized as one of the primary locations of thermal bridge occurrence in apartment building envelopes. The heat transfer characteristics of this junction can directly affect both heating energy consumption and indoor thermal comfort. Assessment based solely on design specifications or one-dimensional thermal transmittance cannot fully characterize the multidimensional heat transfer occurring at these junctions. Therefore, direct evaluation under actual operating conditions is required to determine whether the intended thermal performance is achieved after construction.
Figure 1.
Thermal bridge at the exterior wall-to-floor junction. Reproduced with permission from Joo, N.Y.; Song, S.Y., “Thermal insulation performance of wall-to-floor joints in precast concrete sandwich panel systems for off-site construction of apartment buildings,” Energy and Buildings, Vol. 367, 117743, Copyright Elsevier (2026) [2].
Meanwhile, precast concrete (PC) apartment buildings, in which structural components are prefabricated in factories and assembled on-site, offer significant advantages in terms of construction quality, productivity, and efficiency. Although cast-in-place reinforced concrete (RC) construction remains the dominant method for apartment buildings in South Korea, the application of PC construction has steadily expanded with the increasing adoption of off-site construction (OSC) and carbon neutrality policies. In particular, the exterior wall systems of Korean PC apartment buildings have evolved from early sandwich panel systems with intermediate insulation (Figure 1b) to interior-insulated curtain wall systems incorporating thermal bridge mitigation details. Because these systems differ substantially in insulation continuity and wall-to-floor junction configurations, their actual thermal bridge characteristics cannot be adequately explained by the structural system alone. Evaluating PC and RC buildings under comparable in-service conditions is therefore necessary to distinguish the effects of structural type from those of exterior wall configuration and junction details.
The heat flow meter (HFM) method is one of the most widely used techniques for evaluating the in situ thermal performance of building envelopes. Specified in ISO 9869-1 [3], this method determines the thermal transmittance (U-value) of a building envelope by measuring the heat flux through the building component together with the temperature difference between the indoor and outdoor environments. According to ISO 9869-1, the HFM method is applicable to plane building components consisting of opaque layers perpendicular to the direction of heat flow and exhibiting no significant lateral heat flow. However, these assumptions are not satisfied in building components with material or geometric inhomogeneities, such as thermal bridges, where lateral heat flow and multidimensional heat transfer occur. Its applicability is therefore limited for quantitatively assessing complex exterior wall-to-floor junctions in actual buildings.
Infrared thermography (IRT) has been widely recognized as an effective noncontact and nondestructive technique for detecting thermal bridges, insulation defects, and air leakage in building envelopes. Furthermore, because it provides a visual representation of surface temperature distributions under operating conditions, IRT is particularly useful for identifying thermal bridge locations and assessing relative heat loss characteristics. Previous studies have also demonstrated the potential of combining IRT with heat-transfer models to quantitatively assess thermal bridges and estimate thermal transmittance. Nevertheless, an important knowledge gap remains. Previous investigations have largely focused on general envelope components, controlled or laboratory conditions, or individual thermal bridge configurations, while quantitative field evaluations of exterior wall-to-floor junctions in occupied apartment buildings remain limited. In particular, little information is available on how different PC exterior wall systems and junction details affect both thermal bridge patterns and effective thermal transmittance under actual occupancy conditions.
Therefore, this study aims to evaluate the thermal bridge characteristics and in situ thermal performance of exterior wall-to-floor junctions in occupied apartment buildings using IRT. To achieve this objective, PC apartment buildings with different exterior wall systems were selected and compared with RC apartment buildings within the same residential complexes to investigate the influence of exterior wall system configurations on in situ thermal performance. The distinctive contribution of this study lies in integrating qualitative IRT-based thermal bridge assessment with quantitative estimation of effective thermal transmittance () and applying this approach to exterior wall-to-floor junctions in occupied PC and RC apartment buildings. Through these analyses, the study provides field-based evidence of how exterior wall configurations and junction details affect the actual thermal performance of PC apartment buildings and demonstrates the viability of combining IRT and quantitative estimation as a practical, nondestructive approach for post-occupancy thermal performance assessment.
2. Literature Review
The thermal performance of building envelopes is one of the key factors influencing building energy consumption. Shi et al. (2019) [4] reviewed the magnitude and causes of the building performance gap and showed that discrepancies between predicted and measured building performance can arise from multiple factors, including modeling assumptions, construction quality, building systems, and operational conditions. These findings underscore the importance of evaluating the actual thermal performance of building envelopes under operating conditions rather than relying solely on design-stage predictions.
Thermal bridges are widely recognized as an important building-envelope factor affecting heat transfer and building energy performance. They occur at discontinuities in the building envelope, including structural connections, slab edges, openings, and junctions, where multidimensional heat transfer increases local heat loss. François et al. (2021) [5] noted the limitations of conventional theoretical and numerical approaches and proposed an in situ method combining infrared thermography and inverse analysis for quantifying thermal transmittance in non-homogeneous walls and thermal bridges. More recently, Nguyen et al. (2023) [6] evaluated the structural performance of a thermal-bridge insulation system for multi-residential buildings, demonstrating the feasibility of thermal bridge mitigation technologies.
Meanwhile, with the increasing adoption of off-site construction (OSC), increasing attention has been given to improving the environmental and thermal performance of prefabricated building systems. Li et al. (2016) [7] systematically reviewed recent advances in OSC technologies and identified future directions for improving construction quality and productivity in prefabricated buildings. Aghasizadeh et al. (2022) [8] reviewed the environmental and economic performance of prefabricated construction, including the thermal and energy performance of prefabricated buildings. In the context of PC building envelopes, Joo and Song (2023) [9] proposed improved insulation details for PC curtain wall junctions to mitigate thermal bridges and verified their effectiveness through three-dimensional heat transfer simulations. These studies indicate that maintaining insulation continuity and improving junction details are important considerations for enhancing the thermal performance of prefabricated and PC building envelopes.
IRT is one of the most widely used nondestructive techniques for evaluating thermal bridges in existing buildings. By measuring infrared radiation emitted from building surfaces in a noncontact manner, IRT visualizes surface temperature distributions and enables the detection of thermal bridges, insulation defects, air leakage, and moisture-related anomalies. Kirimtat and Krejcar (2018) [10] comprehensively reviewed IRT methodologies for investigating building-envelope defects and demonstrated its broad applicability to building-envelope diagnostics. Tardy (2023) [11] reviewed recent IRT-based methods for in situ characterization of building-envelope thermal properties and highlighted the potential of IRT as a rapid and non-invasive alternative or complementary approach to conventional heat-flux-meter methods, while emphasizing the importance of environmental conditions and thermal-capacitance effects.
In recent years, increasing efforts have been made to extend IRT from qualitative thermal anomaly detection toward quantitative evaluation of the in situ thermal performance of building envelopes. O’Grady et al. (2017) [12] developed an outdoor IRT method for quantifying heat loss through thermal bridges and investigated the influence of wind velocity on the estimated linear thermal transmittance (Ψ-value). Tejedor et al. (2018) [13] investigated the influence of operating conditions and thermophysical properties on U-values obtained using quantitative internal IRT. Tejedor et al. (2020) [14] subsequently developed a two-dimensional U-value mapping method to quantify the effects of thermal bridges over wall surfaces. François et al. (2021) [5] further proposed an active IRT-based method for the in situ quantification of thermal transmittance in non-homogeneous walls and thermal bridges. More recently, Mahmoodzadeh et al. (2021, 2022) [15,16] investigated exterior quantitative IRT methods for determining wall U-values and effective U-values considering thermal bridging effects and compared the results with numerical simulations and other established approaches.
Despite these advances, field-based quantitative evaluations of exterior wall-to-floor junctions in occupied apartment buildings remain limited. In particular, relatively few studies have simultaneously examined thermal bridge characteristics and effective thermal transmittance at wall-to-floor junctions while comparing different structural and exterior wall systems under post-occupancy conditions. Therefore, in this study, the thermal bridge characteristics of exterior wall-to-floor junctions in PC apartment buildings with different exterior wall systems are investigated using IRT. Furthermore, the effective thermal transmittance estimated from field measurements is compared with that obtained from three-dimensional steady-state heat transfer simulations to evaluate the in situ thermal performance of building envelopes under post-occupancy conditions.
3. Methodology
3.1. Case Buildings
To investigate the thermal bridge characteristics and in situ thermal performance of exterior wall-to-floor junctions in Korean apartment buildings, three representative apartment complexes located in Bundang, Gimpo, and Pyeongtaek, Gyeonggi Province, South Korea, were selected as case studies. The three case studies represent different PC structural systems, exterior wall configurations, and insulation details, ranging from an early load-bearing sandwich panel system to more recent load-bearing and rahmen-type PC systems.
Within each complex, both precast concrete (PC) and reinforced concrete (RC) apartment buildings were constructed, allowing corresponding RC buildings within the same apartment complex to serve as reference buildings for direct comparison under similar building and environmental conditions. All selected complexes are located in Central Region 2, as defined by the Korean Building Energy Conservation Design Standard, corresponding to ASHRAE Climate Zone 4A (Mixed-Humid).
All RC buildings employed interior insulation systems (Figure 2a–c), whereas the PC buildings adopted different exterior wall systems and insulation details depending on the case. The characteristics of the PC exterior wall systems are described below. This case selection therefore enabled an examination of how differences in PC exterior wall systems and junction details influence the thermal bridge characteristics and in situ thermal performance of exterior wall-to-floor junctions.
Figure 2.
Cross-sectional details of the wall-to-floor junctions in Cases 1–3. Reproduced with permission from Joo, N.Y.; Song, S.Y., “Thermal insulation performance of wall-to-floor joints in precast concrete sandwich panel systems for off-site construction of apartment buildings,” Energy and Buildings, Vol. 367, 117743, Copyright Elsevier (2026) [2]. In Figure 2f, the red dashed lines indicate the additional insulation at the junctions, while the blue dashed line indicates the concrete corbel supporting the PC curtain wall.
3.1.1. Case 1—Load-Bearing PC Apartment with Sandwich Panels
Case 1 is an apartment complex completed in 1994, representing an early application of a precast concrete (PC) load-bearing wall system. The complex comprises nine residential buildings, including seven PC buildings and two reinforced concrete (RC) buildings. The PC buildings employ a sandwich panel system with mid-layer insulation, in which the insulation layer is installed between the interior and exterior concrete wythes (Figure 2d). This configuration provides continuous insulation across the exterior wall-to-floor junction, thereby reducing thermal bridging at the junction. However, given the age of the buildings, long-term deterioration of silicone joint sealants, construction tolerances, and maintenance conditions may have affected the in situ thermal performance.
3.1.2. Case 2—Load-Bearing PC Apartment with Interior Insulation
Case 2 is an apartment complex completed in 2020, representing a recent application of a precast concrete (PC) load-bearing wall system. Among the residential buildings in the complex, only Building 108 was constructed using the PC system, while all remaining buildings were constructed using reinforced concrete (RC). To minimize the panel thickness and ensure structural integrity, the PC exterior wall incorporates embedded steel connectors and cast-in-place concrete, forming an integrated wall system (Figure 2e). Consequently, unlike the sandwich panel system used in Case 1, the insulation is installed on the interior side of the exterior wall, adopting the same interior insulation system as the RC buildings. However, because the continuity of the insulation layer is interrupted at the exterior wall-to-floor junction, this configuration may promote the formation of a linear thermal bridge at the junction.
3.1.3. Case 3—Rahmen-Type PC Apartment with Interior Insulation
Case 3 is an apartment complex completed in 2025, representing the latest application of a precast concrete (PC) rahmen-type system that incorporates enhanced insulation requirements and thermal bridge mitigation technologies for PC curtain wall systems. Within the complex, only Building 107 was constructed using the PC system, while all remaining buildings were constructed using reinforced concrete (RC). The PC building adopts a rahmen-type system with PC curtain wall exterior panels. To improve the continuity of the insulation layer, additional insulation was provided at the exterior wall-to-girder and exterior wall-to-floor junctions, as indicated by the red dashed lines in Figure 2f. In addition, the concrete corbel supporting the PC curtain wall, highlighted by the blue dashed line, was designed to bear on top of the girder, thereby minimizing thermal bridge formation.
The main characteristics of the three case studies are summarized in Table 1.
Table 1.
Characteristics of the selected case study buildings.
3.2. Infrared Thermography Measurement
The measurement equipment used in this study is summarized in Table 2. Infrared thermographic measurements were performed using a FLIR T620 infrared camera (FLIR Systems, Wilsonville, OR, USA), which provides a thermal image resolution of 640 × 480 pixels and a thermal sensitivity of less than 0.05 °C. During the measurements, ambient environmental conditions, including outdoor air temperature, relative humidity, and wind speed, were simultaneously monitored using an HD32.3TC environmental meter (Delta Ohm, Padova, Italy). In addition, indoor air temperature was continuously recorded using a TR-74Ui temperature data logger (T&D Corporation, Matsumoto, Japan) for the quantitative evaluation of the in situ thermal performance.
Table 2.
Infrared thermography measurement equipment.
A passive thermography approach was adopted in this study without the use of any artificial heat source. The naturally occurring temperature difference between the heated indoor environment and the outdoor air was utilized to evaluate heat loss through the exterior wall surface. Infrared thermographic measurements focused on the exterior wall-to-floor junction, where thermal bridges are most likely to occur. To ensure measurement consistency, the camera height and viewing direction were maintained constant throughout all measurements.
The infrared camera detected longwave infrared radiation emitted from the building surface and converted it into surface temperature distributions. On the basis of these temperature distributions, the thermal characteristics of the exterior wall-to-floor junctions were evaluated. Considering the surface properties of concrete and silicone joint sealants, an emissivity of 0.90, as recommended in the ASHRAE Handbook—Fundamentals [17], was adopted for all thermographic measurements.
Although the thermographic images included different surface materials and finishes, including exterior wall finishes and joint sealants, a uniform emissivity of 0.90 was applied throughout the analysis to maintain consistent measurement conditions. The quantitative analysis was primarily based on an ROI representing the exterior wall surface rather than individual joint sealant regions. Because the actual emissivity and reflected apparent temperature of each surface material were not independently measured during the field investigation, material-specific emissivity corrections were not applied retrospectively, as this would require additional assumptions not supported by the field measurements.
The acquired thermographic images were analyzed to evaluate the surface temperature distributions and thermal bridge characteristics of the exterior wall-to-floor junctions. A qualitative analysis was performed for all three case studies to compare the thermal patterns and the relative heat loss characteristics. In addition, Case 3 was subjected to a quantitative analysis, in which the effective thermal performance of the exterior wall-to-floor junction was evaluated using the measured average exterior surface temperature and the indoor–outdoor temperature difference. The results were subsequently compared with those obtained from three-dimensional steady-state heat transfer simulations. The measurement conditions adopted for the IRT are summarized in Table 3.
Table 3.
Summary of infrared thermography measurement conditions.
3.3. Effective Thermal Transmittance Calculation
The thermal transmittance (U-value) specified in the Korean Building Energy Conservation Design Standard (MOLIT, 2024 [19]) and the Construction Standard for Energy-Efficient and Environmentally Friendly Housing (MOLIT, 2020 [20]) is determined under the assumption of one-dimensional heat transfer and, therefore, does not account for the multidimensional heat transfer occurring at thermal bridges. To evaluate the in situ thermal performance of the building envelope, the effective thermal transmittance () was adopted, as expressed in Equation (1). A lower indicates superior thermal insulation performance.
where
| : Effective thermal transmittance (W/m2·K) | |
| : Measured heat flux (W/m2) | |
| : Average indoor air temperature (°C) | |
| : Average outdoor air temperature (°C) |
The surface heat flux () at the exterior wall surface was estimated from the average exterior surface temperature obtained by IRT together with the outdoor air temperature. On the basis of Newton’s law of cooling, the convective heat flux from the exterior wall surface to the ambient air is expressed as follows:
where
| : Exterior surface heat flux (W/m2) | |
| : Exterior surface heat transfer coefficient (W/m2·K) | |
| : Exterior surface average temperature (°C) |
The Korean Building Energy Efficiency Rating Certification Standard [21] specifies an exterior surface heat transfer coefficient () of 23 W/m2·K (MOLIT, 2024), whereas the ASHRAE Handbook—Fundamentals [17] recommends values ranging from approximately 7 to 30 W/m2·K depending on the wind speed. However, under outdoor conditions, the wind speed, outdoor air temperature, and surrounding radiative environment vary continuously. Therefore, the use of a constant surface heat transfer coefficient may not adequately represent the heat transfer characteristics of the building envelope.
In the present field measurements, the effective radiative temperature of the sky and surrounding surfaces was not measured separately. Therefore, the outdoor air temperature () was used as an approximation of the effective radiative surroundings temperature in calculating the exterior surface heat flux. Accordingly, in Equation (2) represents a combined exterior surface heat-transfer coefficient accounting for both convective and longwave radiative heat transfer. This approximation was adopted to enable the quantitative evaluation using the available field-measured parameters. However, the actual longwave radiative exchange occurs between the exterior wall surface and the sky and surrounding surfaces, whose effective radiative temperature may differ from the outdoor air temperature. Therefore, the use of as the radiative reference temperature introduces uncertainty into the estimated heat flux and effective thermal transmittance. This limitation should be considered when interpreting the quantitative results.
According to the EnergyPlus Engineering Reference (DOE, 2021) [22], the exterior surface heat transfer coefficient () can be expressed as the sum of the convective heat transfer coefficient () and the radiative heat transfer coefficient (). Accordingly, in this study, and were calculated using the empirical correlations provided in the ASHRAE Handbook—Fundamentals [17], while the calculation procedure was based on the algorithm described in the EnergyPlus Engineering Reference [22].
where
| : Exterior surface heat transfer coefficient (W/m2·K) | |
| : Convective heat transfer coefficient (W/m2·K) | |
| : Radiative heat transfer coefficient (W/m2·K) | |
| : Empirical coefficient for natural convection (5.8 W/m2·K) | |
| : Empirical wind-speed coefficient (3.94 W·s/m3·K) | |
| : Average wind speed (m/s) | |
| : Emissivity | |
| : Stefan–Boltzmann constant ( W/m2·) | |
| : Mean temperature of the exterior surface and outdoor air (K) |
The average exterior surface temperature () was defined as the arithmetic mean of the surface temperatures of all pixels within the selected region of interest (ROI) and was calculated using Equation (6).
where
| : Number of pixels within the selected area | |
| : Surface temperature of the i-th pixel (°C) |
3.4. 3D Heat Transfer Simulation
Three-dimensional steady-state heat transfer simulations calculate heat transfer through a building envelope under steady-state conditions and are widely used for the detailed evaluation of thermal insulation performance. Commercial software packages such as Physibel, THERM, and ANSYS are typically employed for this purpose. This approach enables detailed analysis of heat flow through junctions and complex thermal bridge regions that are difficult to evaluate experimentally in buildings, thereby facilitating the comparison of alternative design solutions. In particular, Physibel TRISCO is suitable for evaluating linear thermal bridges at building junctions in accordance with the methodology specified in ISO 10211 [23]. TRISCO is a specialized software package capable of solving steady-state heat transfer in three-dimensional orthogonal domains comprising different materials and boundary conditions. It therefore enables the thermal behavior of complex building components to be calculated with a high degree of accuracy. Accordingly, the three-dimensional steady-state heat transfer analysis adopted in this study is appropriate for evaluating thermal bridge effects at junctions where multidimensional heat transfer is dominant.
In this study, three-dimensional steady-state heat transfer simulations were conducted using Physibel TRISCO 15.0w under the same numerical conditions specified in Table 4. The analysis procedure involved assigning the thermal properties of the constituent materials and boundary conditions, formulating a system of linear equations based on the energy balance method, and solving the system using a fast iterative algorithm. For nonlinear problems, a modified linear system was repeatedly solved until convergence was achieved.
Table 4.
Boundary conditions and thermal properties used in the three-dimensional heat transfer simulations.
As shown in Table 4, the indoor and outdoor air temperatures for the Case 3 heat-transfer analysis were set to 25 °C and −15 °C, respectively, and the interior and exterior surface thermal resistances were set to 0.110 and 0.043 m2·K/W, respectively, in accordance with the Building Energy Conservation Design Standards [19]. The thermal conductivities of the principal materials are also presented in Table 4. The exterior wall consisted of 150 mm thick concrete and 145 mm thick phenolic foam (PF) board, with a thermal conductivity of 0.025 W/m·K. The analysis domain was defined to correspond to the ROI used for the quantitative IRT analysis.
The numerical accuracy was primarily assessed using the object divergence criterion. Object divergence is defined as the algebraic sum of all elemental heat flows, with incoming heat flows taken as positive and outgoing heat flows as negative, divided by one-half of the sum of their absolute values, as expressed in Equation (7). According to ISO 10211 [23], object divergence should not exceed 0.01% to ensure reliable numerical results.
where
| : Object divergence (%) | |
| : Total incoming heat flow for the object (W) | |
| : Total outgoing heat flow for the object (W) |
In the simulations, heat transfer within air cavities was calculated using the equivalent thermal conductivity, as expressed in Equation (8). The equivalent thermal conductivity was determined by the software according to the geometry of the air cavity and the direction of heat flow, on the basis of the calculation procedures specified in EN ISO 10077-2 [24] and EN ISO 6946 [25].
where
| : Equivalent thermal conductivity (W/m·K) | |
| : Convective heat transfer coefficient (W/m2·K) | |
| : Radiative heat transfer coefficient (W/m2·K) | |
| : Depth of air cavity (m) |
The heat flux () was calculated by dividing the total heat loss through the interior surface obtained from the three-dimensional heat transfer analysis, including all thermal bridge regions, by the exterior wall area. The effective thermal transmittance () was then determined using Equation (1).
The location of the cut-off plane for modeling the analysis domain was defined in accordance with ISO 10211 [23]. When no adjacent plane of symmetry exists, ISO 10211 [23] recommends that the cut-off plane be located at a distance greater than either 1 m from the central element or three times the thickness of the flanking element adjacent to the central element, whichever is larger. In addition, nonmetallic material layers with a thickness of 1 mm or less may be omitted from the numerical model because their influence on heat transfer is negligible.
4. Results
The exterior surface temperature distributions of the walls, including the thermal bridge regions, were analyzed to qualitatively evaluate the locations, spatial patterns, and relative heat loss tendencies of the exterior wall-to-floor junctions for each envelope system. A qualitative assessment was conducted for all three case studies (Cases 1–3) to compare the thermal bridge characteristics on the basis of the surface temperature patterns observed in the thermographic images.
In contrast, a quantitative assessment was performed to estimate the effective thermal transmittance using the measured surface temperatures and the indoor–outdoor temperature difference, thereby enabling a quantitative comparison of the in situ thermal performance of the junctions. This assessment was limited to Case 3, in which thermal bridge mitigation details were incorporated into the PC structure; therefore, improved insulation performance was expected.
All investigated dwelling units were occupied during the thermographic measurements and were continuously heated under similar thermostat settings. However, owing to the nature of the occupied conditions, the indoor temperatures of the individual units could not be artificially maintained at identical levels. Accordingly, the qualitative analysis was based on thermographic images acquired when the outdoor air temperature was closest to its mean value during the measurement period. For the quantitative analysis of Case 3, the mean indoor temperature continuously measured in each dwelling unit was applied as the indoor boundary condition.
4.1. Qualitative Assessment of Thermal Bridge Characteristics
To compare the thermal bridge characteristics of exterior wall-to-floor junctions among different exterior wall systems, IRT was conducted in three apartment complexes, followed by a qualitative analysis. The characteristics of the investigated buildings and the corresponding measurement locations are summarized in Table 5.
Table 5.
Characteristics of the apartment buildings and measurement areas used for qualitative infrared thermography.
4.1.1. Case 1—Load-Bearing Wall-Type PC Apartment with Sandwich Panels
Building 609, incorporating the PC system, and Building 604, constructed with the RC system, were selected for comparison to investigate the thermal bridge characteristics of the exterior wall-to-floor junctions. IRT was conducted between 4:00 and 5:00 a.m. on 23 January 2025, when the outdoor air temperature was −4.1 °C, and the thermographic results are presented in Table 6.
Table 6.
Infrared thermal images of Case 1.
In both Building 609 with the PC sandwich panel system and Building 604 with the RC system, horizontal high-surface-temperature regions were repeatedly observed along the exterior wall-to-floor junctions, indicating concentrated thermal bridge formation at these locations. Under the winter conditions of January, when the indoor–outdoor temperature difference was large, relatively brighter regions on the exterior wall surface represented areas of elevated surface temperature caused by heat transfer from the interior to the exterior. These observations indicate that the exterior wall-to-floor junctions acted as major heat-loss pathways in both buildings.
Although horizontal thermal bridge patterns were observed along the exterior wall-to-floor junctions in both the RC and PC buildings, the surface temperature distributions exhibited distinct patterns. In Building 604 with the RC system, a relatively continuous horizontal thermal bridge pattern was observed along the exterior wall-to-floor junctions. In addition, a localized region with an elevated surface temperature compared with the surrounding areas was identified at the central portion of the exterior wall (red dashed circle). This location corresponds to the bathroom area, suggesting that the observed temperature increase may be associated with thermal insulation discontinuities at the bathroom exterior wall, indoor heating conditions, or both. In contrast, Building 609 with the PC sandwich panel system exhibited repeated localized high-surface-temperature regions around the panel connections, indicating point thermal bridges.
As illustrated in Figure 3a, the PC sandwich panel system incorporates insulation between the interior and exterior concrete wythes, providing structural continuity of the insulation layer across the exterior wall-to-floor junctions. From a design perspective, this configuration is expected to be advantageous for mitigating thermal bridges at the junctions. However, the thermographic images still revealed high-surface-temperature regions at the PC exterior wall-to-floor junctions. Localized point-shaped thermal anomalies were repeatedly observed around the panel connectors. These observations suggest that the structural advantages of the sandwich panel system were not clearly reflected in the qualitative thermographic assessment and that the panel joints and steel connectors may still act as significant heat-loss paths. Furthermore, heat loss at these locations may be exacerbated by poor construction quality, insufficient airtightness at the joints, and long-term deterioration of the sealant, as shown in Figure 3b.
Figure 3.
(a) Cross-section of the exterior wall-floor junction; (b) cracking and peeling of sealant at exterior wall joints in Case 1.
4.1.2. Case 2—Load-Bearing Wall-Type PC Apartment with Interior Insulation
Building 108 with the PC system and Building 104 with the RC system were selected for comparison to investigate the thermal bridge characteristics of the exterior wall-to-floor junctions. IRT was conducted between 5:00 and 6:00 a.m. on 22 January 2025, when the outdoor air temperature was −0.6 °C, and the thermographic results are presented in Table 7.
Table 7.
Infrared thermal images of Case 2.
Horizontal high-surface-temperature regions were observed along the exterior wall-to-floor junctions in both Building 108 and Building 104, indicating the presence of thermal bridges concentrated at these locations. This observation is likely attributable to the fact that both the PC and RC buildings in the Case 2 apartment complex employ an interior insulation system, in which the continuity of the insulation layer is interrupted at the exterior wall-to-floor junctions. Consequently, thermal bridges were more pronounced at these junctions, and distinct linear heat-loss patterns were clearly identified along the junctions in the thermographic images. These findings suggest that in load-bearing wall-type systems with interior insulation, discontinuities in the insulation layer at the exterior wall-to-floor junctions may result in concentrated thermal bridge formation.
Unlike those in conventional PC rahmen-type buildings, where curtain wall panels serve as non-load-bearing exterior walls, the exterior wall panels in the load-bearing wall-type PC apartment building (Case 2) are configured as load-bearing wall panels connected by steel connectors, as illustrated in Figure 2e. Accordingly, an interior insulation system is adopted, and the exterior wall-to-floor junction is expected to exhibit thermal behavior similar to that of the RC load-bearing wall system.
4.1.3. Case 3—Rahmen-Type PC Apartment with PC Curtain Walls
Building 1547, which incorporates a PC curtain wall system, and Building 1548, which is constructed with an RC system, were selected for comparison to investigate the thermal bridge characteristics of the exterior wall-to-floor junctions. IRT was conducted between 4:00 and 5:00 a.m. on 30 January 2026, when the outdoor air temperature was −11.8 °C, and the thermographic results are presented in Table 8. In both the RC and PC buildings, regions of relatively high surface temperature were observed along the exterior wall-to-floor junctions, indicating that these junctions acted as major heat-loss pathways.
Table 8.
Infrared thermal images of Case 3.
However, the surface temperature distributions differed between the two buildings. In the RC building, a relatively continuous linear thermal bridge pattern was observed along the exterior wall-to-floor junctions. In contrast, the high-surface-temperature regions associated with the linear thermal bridge pattern were less pronounced in the building with the PC curtain wall system. This result is likely attributable to the greater continuity of the insulation layer provided by the PC curtain wall system at the exterior wall-to-floor junction, thereby reducing thermal bridge effects.
4.1.4. Comparative Analysis of Qualitative Thermographic Results
The infrared thermographic analyses of the three case studies revealed that despite differences in structural systems and exterior wall configurations, relatively high surface temperature regions were consistently observed along the exterior wall-to-floor junctions in all apartment buildings. These observations indicate that the exterior wall-to-floor junction is a major heat-loss pathway regardless of the structural system.
However, the surface temperature distributions varied depending on the exterior wall system. In Case 1, which employed a PC sandwich panel system with insulation between the concrete wythes, repeated localized high-surface-temperature regions were observed around the panel joints and steel connectors, indicating point thermal bridges. In Case 2, which employed an interior insulation system, both the RC and PC buildings exhibited continuous high-surface-temperature regions along the exterior wall-to-floor junctions, indicating similar thermal distribution characteristics. In Case 3, which incorporated a PC curtain wall system, the high-surface-temperature regions along the exterior wall-to-floor junctions were less pronounced than those observed in the corresponding RC building.
These results demonstrate that although the exterior wall-to-floor junction was identified as a common location of thermal bridge formation in all three cases, the spatial distribution of thermal bridges differed according to the exterior wall system. Notably, the infrared thermographic analysis presented in this section provides a qualitative assessment intended to identify the locations of thermal bridges and their relative heat-loss tendencies under operating conditions. The measured surface temperatures may be influenced by measurement conditions, including the imaging distance and spatial resolution of the infrared camera. Therefore, the present results are useful for qualitatively comparing the thermal bridge characteristics and relative heat-loss tendencies associated with different exterior wall systems. A quantitative comparison of thermal bridge performance was subsequently performed only for Case 3, where identical measurement conditions were established. The effective thermal transmittance was estimated and validated through three-dimensional steady-state heat transfer analysis.
4.2. Quantitative Assessment of the Thermal Performance of Case 3
Section 4.1 qualitatively compared the thermal bridge characteristics of exterior wall-to-floor junctions among different exterior wall systems. In this section, a quantitative evaluation was performed for Case 3, in which thermal bridge mitigation details were incorporated into the PC structure, and improved thermal performance was therefore expected. The effective thermal transmittance was estimated from the average exterior surface temperature measured by IRT using the indoor–outdoor temperature difference. The estimated values were then compared with the results of three-dimensional steady-state heat transfer analysis to quantitatively evaluate the thermal bridge characteristics of the exterior wall-to-floor junctions.
4.2.1. Measurement Conditions and ROI Definition
The indoor and outdoor temperatures were continuously monitored using temperature sensors installed inside and outside the dwelling units where the IRT measurements were conducted. In particular, the indoor temperature sensors were positioned near the center of each dwelling unit, at sufficient distances from the exterior walls, windows, and heating equipment to minimize the effects of occupant activities and localized thermal conditions. Figure 4 shows the indoor and outdoor temperature variations from 3:00 to 5:00 a.m., including the one-hour period preceding the quantitative IRT measurement. The indoor and outdoor temperatures remained relatively stable without abrupt changes before and during the measurement period, indicating relatively stable thermal conditions. During the quantitative IRT measurement conducted between 4:00 and 5:00 a.m., the mean indoor temperatures were 23.7 °C for the RC dwelling unit and 22.6 °C for the PC dwelling unit, while the mean outdoor air temperature was −11.8 °C. Because the measurements were conducted in occupied apartment buildings, identical indoor temperatures could not be maintained between the dwelling units. Therefore, the measured mean indoor temperature of each dwelling unit during the IRT measurement period was used as the corresponding indoor boundary condition for estimating the effective thermal transmittance.
Figure 4.
Indoor and outdoor temperature trends and average temperatures during infrared thermography measurements.
Table 9 summarizes the measurement conditions and input parameters used to estimate the effective thermal transmittance. The infrared thermographic analysis revealed that the mean exterior surface temperatures of the exterior walls were −10.0 °C for the RC building and −10.8 °C for the PC building. The measured mean exterior surface temperatures were then used to calculate the exterior surface heat flux according to Equation (2). The calculated exterior surface heat fluxes were 23.44 W/m2 for the RC building and 13.02 W/m2 for the PC building. The wind speed was measured at approximately 1.0 m above ground level and 6.0 m away from the exterior wall surface. To minimize the influence of wind speed on the estimation of exterior surface heat transfer, the field measurements were intentionally conducted on a day with low and relatively stable wind conditions, with an average wind speed of approximately 0.9 m/s during the measurement period.
Table 9.
Measurement conditions and calculated surface heat flux.
To ensure sufficient spatial resolution and a field of view encompassing the exterior wall-to-floor junction for the quantitative analysis, the measurement distance and camera installation height were determined based on the instantaneous field of view (IFOV) and field of view (FOV) specifications of the FLIR T620 infrared camera. Accordingly, the measurement distance was set to approximately 6 m, and the camera was positioned at a height of approximately 1.1 m (Figure 5, right). In IRT, the spatial resolution at the target surface is determined by the measurement distance and the IFOV. The surface area represented by a single pixel () can therefore be calculated as follows:
where
| : Pixel size (m/pixel) | |
| : Camera-to-object distance (m) | |
| : Instantaneous field of view (rad) |
Figure 5.
Determination of pixel size and inspection area based on IFOV and FOV parameters.
The IFOV of the camera was 0.68 mrad. At a measurement distance of 6 m, the corresponding pixel size was calculated as 6 × 0.00068 ≈ 0.0041 m. Accordingly, each pixel in the thermographic image represented an area of approximately 4.1 mm × 4.1 mm on the exterior wall surface (Figure 5, left).
The area captured in the thermographic image was determined by the field of view (FOV) of the camera. The FLIR T620 equipped with the standard lens has a horizontal FOV of 25° and a vertical FOV of 19°. At a measurement distance of 6 m (Figure 5, right), the corresponding imaging area was approximately 2.66 m in the horizontal direction and 2.01 m in the vertical direction.
For the quantitative analysis, a region of interest (ROI) was defined around the exterior wall-to-floor junction. The ROI was selected to include the slab-to-exterior wall junction so that the heat transfer characteristics and thermal bridge effects could be evaluated. To minimize image distortion near the edges of the thermographic image, the ROI was positioned at the center of the image. Accordingly, a 2.0 m × 2.0 m region was selected from the total imaging area of 2.66 m × 2.01 m, corresponding to approximately 487 × 487 pixels. The mean surface temperature of the ROI was calculated as the arithmetic average of the temperatures of all pixels within the selected region (Equation (6)). The ROI used for quantitative analysis is shown in Figure 6.
Figure 6.
Thermal images of the selected ROI at the wall-to-floor junctions.
4.2.2. Effective Thermal Transmittance of Wall-to-Floor Junctions
Table 10 compares the effective thermal transmittance estimated from IRT with that obtained from the three-dimensional steady-state heat transfer analysis, while Table 11 presents the simulated surface temperature distributions at the exterior wall-to-floor junctions. The effective thermal transmittance estimated from IRT was 0.661 W/m2·K for the RC building and 0.379 W/m2·K for the PC building, indicating that the value for the PC building was approximately 42.7% lower than that for the RC building.
Table 10.
Determination of effective thermal transmittance.
Table 11.
Simulated surface temperature distributions of wall-to-floor junctions.
Because this comparison was based on case-specific field measurements rather than a sufficiently large statistical sample, the observed difference should not be interpreted as evidence of statistical significance. Nevertheless, the magnitude of the reduction is practically meaningful from a building-envelope perspective, as a lower effective thermal transmittance indicates reduced heat transfer through the exterior wall-to-floor junction under the measured conditions. This result suggests that maintaining insulation continuity and incorporating thermal bridge mitigation details at the PC curtain wall junction can reduce localized transmission heat loss. Such reductions may contribute to improved overall envelope thermal performance and reduced heating energy demand; however, the present study did not directly measure whole-building energy consumption. Therefore, the 42.7% reduction should be interpreted as an improvement in the in situ thermal performance of the investigated junction rather than as an equivalent reduction in whole-building energy use.
The improved thermal performance of the PC building is primarily attributed to the thermal bridge mitigation details incorporated into the PC curtain wall junction rather than to the PC structural system itself. As illustrated in Figure 2f, additional insulation was installed at the exterior wall-to-girder and exterior wall-to-floor junctions to improve the continuity of the insulation layer. In addition, the concrete corbel supporting the PC curtain wall was designed to bear on top of the girder, thereby reducing the extent of the highly conductive concrete path across the insulation layer. In contrast, the interior insulation system of the corresponding RC building is interrupted by the floor slab at the exterior wall-to-floor junction, creating a more continuous heat-transfer path through the concrete. Consequently, the improved insulation continuity and thermally optimized junction geometry of the PC curtain wall system reduced the thermal bridge effect at the junction, resulting in the lower effective thermal transmittance observed in the PC building.
A similar trend was observed in the three-dimensional steady-state heat transfer analysis. As shown in Table 11, the simulated exterior surface temperatures of the PC building were generally lower than those of the RC building. These results suggest that the PC curtain wall system can reduce heat loss at the exterior wall-to-floor junction.
The effective thermal transmittance obtained from the three-dimensional steady-state heat transfer analysis was 0.514 W/m2·K for the RC building and 0.407 W/m2·K for the PC building. Compared with the values estimated by IRT, the percentage differences were 22.2% for the RC building and 7.4% for the PC building. Notably, the discrepancy between the effective thermal transmittance estimated from IRT and that obtained from the three-dimensional steady-state heat transfer analysis was smaller for the PC building than for the RC building.
5. Discussion
The results of this study demonstrate that exterior wall-to-floor junctions are critical thermal bridge locations in occupied apartment buildings, regardless of whether PC or RC structural systems are used. However, the observed thermal bridge patterns differed according to the exterior wall system and junction configuration, indicating that insulation continuity and junction details have a greater influence on thermal bridge behavior than the structural system itself. This finding highlights the importance of evaluating the thermal performance of PC apartment buildings in relation to their specific envelope configurations rather than solely on the basis of structural type.
The comparison among the case studies further illustrates the influence of exterior wall and junction details on in situ thermal performance. In Case 1, the intended benefit of continuous insulation in the PC sandwich panel system was not clearly reflected in the qualitative thermographic results, suggesting that in-service thermal performance may be affected by local features such as panel joints and steel connectors, as well as construction quality and aging. In contrast, the PC curtain wall system in Case 3, which incorporated additional junction insulation and an improved support detail, exhibited reduced heat loss compared with the corresponding RC building. The quantitative evaluation further supported this observation, with the IRT-estimated effective thermal transmittance of the PC building being 42.7% lower than that of the RC building. These findings suggest that maintaining insulation continuity and improving junction details are important for reducing heat loss at exterior wall-to-floor junctions.
The comparison between the IRT-estimated effective thermal transmittance and the three-dimensional steady-state heat transfer analysis also showed differences between in-service and numerically predicted thermal performance. Such differences may result from factors that are not fully represented in steady-state numerical models, including actual environmental conditions, construction quality, material aging, and occupant heating operation. Accordingly, the IRT-based approach should be considered complementary to numerical analysis rather than a direct method for verifying design-stage thermal performance. By combining spatial visualization of thermal bridge patterns with quantitative estimation of effective thermal transmittance, IRT provides a practical and nondestructive approach for assessing the thermal behavior of complex junctions under actual operating conditions and for identifying potential discrepancies between predicted and in-service performance.
6. Conclusions
In this study, the thermal bridge characteristics and in situ thermal performance of exterior wall-to-floor junctions in occupied apartment buildings were evaluated using IRT. Three PC apartment buildings with different exterior wall systems were compared with corresponding RC buildings within the same apartment complexes to investigate their thermal bridge characteristics. In addition, the effective thermal transmittance of Case 3 was quantitatively evaluated by comparing the values estimated from IRT with those obtained from three-dimensional steady-state heat transfer analysis. The main findings are summarized as follows.
- (1)
- In all cases, the exterior wall-to-floor junction was identified as a common location of thermal bridge formation in apartment building envelopes. Relatively high surface temperatures were consistently observed along the junctions, indicating that these locations acted as major heat-loss pathways.
- (2)
- The thermal bridge characteristics were influenced more strongly by the exterior wall system and junction details than by the structural system itself. Although the PC sandwich panel system with insulation between the concrete wythes was designed to provide continuous thermal insulation, the qualitative infrared thermographic assessment alone could not clearly verify whether this structural advantage resulted in improved thermal performance under operating conditions.
- (3)
- The quantitative evaluation of Case 3 revealed that the effective thermal transmittance was 0.379 W/m2·K for the PC building and 0.661 W/m2·K for the corresponding RC building, indicating that the effective thermal transmittance of the PC building was approximately 42.7% lower than that of the RC building. These results suggest that recently developed junction insulation details and the PC curtain wall system can effectively reduce heat loss at exterior wall-to-floor junctions.
- (4)
- Comparison with the three-dimensional steady-state heat transfer analysis revealed differences between the IRT-estimated in situ thermal performance and the numerically predicted performance. These results indicate that IRT-based quantitative assessment can complement numerical analysis by providing information on the actual thermal behavior of building envelopes under operating conditions.
From a practical perspective, these findings have implications for the design, construction, and post-occupancy assessment of OSC buildings. At the design stage, maintaining insulation continuity and minimizing thermal bridges at panel joints and exterior wall-to-floor junctions should be considered key requirements for envelope and junction detailing. During construction, these locations should receive particular attention in quality control because discontinuities in insulation, panel joints, and connection details can affect the intended thermal performance. After occupancy, IRT can be used as a rapid and nondestructive tool to identify thermal anomalies and evaluate whether critical junctions exhibit unexpected heat-loss patterns. Accordingly, integrating design-stage thermal analysis with post-occupancy IRT assessment can provide a practical framework for identifying potential performance gaps and supporting improvements in OSC envelope design and construction quality.
Several limitations of this study should be acknowledged. The field investigation was limited to three PC apartment building cases, and quantitative evaluation of effective thermal transmittance was performed only for Case 3. In addition, the IRT measurements were conducted under specific winter nighttime conditions, and the measured surface temperatures may be affected by environmental and operating conditions. Therefore, the quantitative results obtained in this study should not be generalized to all PC or OSC building configurations without further validation.
Future research should extend the proposed approach to a broader range of PC structural systems, exterior wall configurations, insulation details, and climatic conditions. Long-term and repeated field measurements are also required to examine seasonal and temporal variations in thermal performance. In addition, systematic uncertainty analyses should be conducted to quantify the effects of environmental conditions, material properties, measurement parameters, and occupant heating operation on IRT-based Ueff estimation. Further validation against other in situ measurement methods and numerical analyses would improve the reliability and applicability of the proposed approach. Ultimately, establishing a systematic feedback process that connects post-occupancy thermal performance assessment with envelope design and construction quality control could contribute to improving the actual energy performance and long-term reliability of OSC building envelopes.
Author Contributions
Conceptualization, S.-Y.S. and N.-Y.J.; methodology, S.-Y.S. and N.-Y.J.; software, N.-Y.J.; validation, S.-Y.S.; formal analysis, S.-Y.S. and N.-Y.J.; investigation, N.-Y.J.; resources, S.-Y.S.; data curation, N.-Y.J.; writing—original draft preparation, N.-Y.J.; writing—review and editing, S.-Y.S.; visualization, N.-Y.J.; supervision, S.-Y.S.; project administration, S.-Y.S.; funding acquisition, S.-Y.S. All authors have read and agreed to the published version of the manuscript.
Funding
This work was supported by the National Research Foundation of Korea (NRF) grant funded by the Korean government (MSIT) (Grant No. RS-2024-00344190).
Data Availability Statement
Data will be made available on request.
Conflicts of Interest
The authors declare no conflicts of interest.
References
- United Nations Environment Programme (UNEP). 2023 Global Status Report for Buildings and Construction; UNEP: Nairobi, Kenya, 2023. [Google Scholar]
- Joo, N.Y.; Song, S.Y. Thermal insulation performance of wall-to-floor joints in precast concrete sandwich panel systems for off-site construction of apartment buildings. Energy Build. 2026, 367, 117743. [Google Scholar] [CrossRef] [Scilit]
- ISO 9869-1:2014; Thermal Insulation—Building Elements—In-Situ Measurement of Thermal Resistance and Thermal Transmittance—Part 1: Heat Flow Meter Method. International Organization for Standardization: Geneva, Switzerland, 2014.
- Shi, X.; Si, B.; Zhao, J.; Tian, Z.; Wang, C.; Jin, X.; Zhou, X. Magnitude, Causes, and Solutions of the Performance Gap of Buildings: A Review. Sustainability 2019, 11, 937. [Google Scholar] [CrossRef] [Scilit]
- François, A.; Ibos, L.; Feuillet, V.; Meulemans, J. In situ measurement method for the quantification of the thermal transmittance of a non-homogeneous wall or a thermal bridge using an inverse technique and active infrared thermography. Energy Build. 2021, 233, 110633. [Google Scholar] [CrossRef] [Scilit]
- Nguyen, H.C.; Gayoon, L.; An, H.; An, S.; Han, S.W.; Lee, K. Experimental evaluation of a vertical heat bridge insulation system for the structural performance of multi-residential buildings. Structures 2023, 58, 105686. [Google Scholar] [CrossRef] [Scilit]
- Li, L.; Luan, H.; Yin, X.; Dou, Y.; Yuan, M.; Li, Z. Understanding sustainability in off-site construction management: State of the art and future directions. J. Constr. Eng. Manag. 2022, 148, 03122008. [Google Scholar] [CrossRef] [Scilit]
- Aghasizadeh, S.; Tabadkani, A.; Hajirasouli, A.; Banihashemi, S. Environmental and economic performance of prefabricated construction: A review. Environ. Impact Assess. Rev. 2022, 97, 106897. [Google Scholar] [CrossRef] [Scilit]
- Joo, N.Y.; Song, S.Y. Improvement of thermal insulation performance of precast concrete curtain walls for apartment buildings. Energy Build. 2023, 296, 113350. [Google Scholar] [CrossRef] [Scilit]
- Kirimtat, A.; Krejcar, O. A review of infrared thermography for the investigation of building envelopes: Advances and prospects. Energy Build. 2018, 176, 390–406. [Google Scholar] [CrossRef] [Scilit]
- Tardy, F. A review of the use of infrared thermography in building envelope thermal property characterization studies. J. Build. Eng. 2023, 75, 106918. [Google Scholar] [CrossRef] [Scilit]
- O’Grady, M.; Lechowska, A.A.; Harte, A.M. Quantification of heat losses through building envelope thermal bridges influenced by wind velocity using the outdoor infrared thermography technique. Appl. Energy 2017, 208, 1038–1052. [Google Scholar] [CrossRef] [Scilit]
- Tejedor, B.; Casals, M.; Gangolells, M. Assessing the influence of operating conditions and thermophysical properties on the accuracy of in-situ measured U-values using quantitative internal infrared thermography. Energy Build. 2018, 171, 64–75. [Google Scholar] [CrossRef] [Scilit]
- Tejedor, B.; Barreira, E.; Almeida, R.M.S.F.; Casals, M. Thermographic 2D U-value map for quantifying thermal bridges in building façades. Energy Build. 2020, 224, 110176. [Google Scholar] [CrossRef] [Scilit]
- Mahmoodzadeh, M.; Gretka, V.; Hay, K.; Steele, C.; Mukhopadhyaya, P. Determining overall heat transfer coefficient (U-value) of wood-framed wall assemblies in Canada using external infrared thermography. Build. Environ. 2021, 199, 107897. [Google Scholar] [CrossRef] [Scilit]
- Mahmoodzadeh, M.; Gretka, V.; Lee, I.; Mukhopadhyaya, P. Infrared thermography for quantitative thermal performance assessment of wood-framed building envelopes in Canada. Energy Build. 2022, 258, 111807. [Google Scholar] [CrossRef] [Scilit]
- ASHRAE. ASHRAE Handbook—Fundamentals; American Society of Heating, Refrigerating and Air-Conditioning Engineers: Atlanta, GA, USA, 2021. [Google Scholar]
- ISO 6781-1:2023; Performance of Buildings—Detection of Heat, Air and Moisture Irregularities in Buildings by Infrared Methods—Part 1: General Procedures. International Organization for Standardization: Geneva, Switzerland, 2023.
- Ministry of Land, Infrastructure and Transport (MOLIT). Building Energy Conservation Design Standards; MOLIT: Sejong, Republic of Korea, 2024.
- Ministry of Land, Infrastructure and Transport (MOLIT). Construction Standards for Energy-Saving Environment-Friendly Housing; MOLIT: Sejong, Republic of Korea, 2020.
- Ministry of Land, Infrastructure and Transport (MOLIT); Ministry of Trade, Industry and Energy (MOTIE). Standards for Building Energy Efficiency Rating Certification and Zero Energy Building Certification; Notification No. 2023-911 (MOLIT) and No. 2023-242 (MOTIE); MOLIT/MOTIE: Sejong, Republic of Korea, 2023.
- U.S. Department of Energy (DOE). EnergyPlus Engineering Reference; U.S. Department of Energy: Washington, DC, USA, 2021.
- ISO 10211:2017; Thermal Bridges in Building Construction—Heat Flows and Surface Temperatures—Detailed Calculations. International Organization for Standardization: Geneva, Switzerland, 2017.
- ISO 10077-2:2017; Thermal Performance of Windows, Doors and Shutters—Calculation of Thermal Transmittance—Part 2: Numerical Method for Frames. International Organization for Standardization: Geneva, Switzerland, 2017.
- ISO 6946:2017; Building Components and Building Elements—Thermal Resistance and Thermal Transmittance—Calculation Methods. International Organization for Standardization: Geneva, Switzerland, 2017.
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2026 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.