Abstract
Non-destructive evaluation (NDE) methods are widely used to assess concrete quality, but their interpretation in reinforced concrete members remains challenging because measured responses may be influenced by reinforcement layout, casting and surface conditions, and testing configuration. This study investigates the effects of longitudinal reinforcement type, stirrup spacing, and stirrup material on Schmidt rebound hammer (SRH) and ultrasonic pulse velocity (UPV) responses of concrete beams. Nine beams were cast from the same concrete batch: one plain concrete reference beam, steel-reinforced beams, GFRP-reinforced beams, and hybrid steel–GFRP-reinforced beams. Two stirrup spacings, 100 and 200 mm, and two stirrup materials, steel and GFRP, were considered. In total, 1044 rebound readings and 162 UPV measurements were collected, with UPV testing performed using Right–Left direct, longitudinal direct, and Right–Left indirect configurations. Compared with the plain reference beam, the mean rebound number (RN) increased by up to 21.5% in steel-reinforced beams and 23.2% in hybrid beams, whereas the GFRP-reinforced beam with wider stirrup spacing showed a slight reduction of about 0.8%. UPV differences were more moderate, with a maximum increase of approximately 10% relative to the plain beam. Rebound results also showed a clear face effect, with the bottom face producing the highest values and the top face the lowest. The dense spatial mapping captured local variability within each beam; however, because one beam represented each configuration, the comparisons are interpreted as descriptive specimen-level trends rather than generalized reinforcement effects. Single-pair spacing comparisons indicated larger and more variable differences in RN than in UPV between the 100 and 200 mm specimens. These findings demonstrate the importance of documenting casting face, reinforcement proximity, measurement location, and transmission path when interpreting NDE results in hybrid-reinforced concrete members.
1. Introduction
Reliable assessment of concrete quality is essential in both newly constructed and existing reinforced concrete members, particularly when structural decisions must be made without extensive destructive sampling. For this reason, non-destructive evaluation (NDE) techniques such as the Schmidt rebound hammer (SRH) and ultrasonic pulse velocity (UPV) tests have been widely adopted in concrete practice. However, these methods do not directly measure in-situ compressive strength; rather, they provide indirect indicators related to near-surface hardness, stress-wave transmission, material uniformity, and damage state. Accordingly, their interpretation must account for method-specific limitations, testing conditions, and statistical uncertainty [1,2,3,4]. The SRH test provides a rebound number (RN) associated with the impact response of the near-surface concrete layer. Although the method is simple and rapid, ASTM C805 states that RN is affected by several parameters, including surface moisture, formwork or finishing condition, vertical position within the concrete placement, and carbonation depth. The same standard further specifies that the rebound hammer should not be used as the sole basis for acceptance or rejection of concrete and that reliable strength estimation requires a dedicated calibration for the concrete and testing conditions under consideration [5]. These limitations have also been emphasized in broader literature. Brencich et al. showed that rebound hammer results are significantly influenced by moisture content, concrete maturity, specimen size, boundary conditions, and stress state, concluding that no universal calibration curve can be applied to all concretes [6]. Similarly, Jedidi reported that the reliability of SRH-based in-situ assessment is strongly affected by surface texture, moisture condition, aggregate type, cement type, and carbonation, and therefore requires careful calibration and interpretation [7]. Kocáb et al. further demonstrated that even when strong correlations are achieved, rebound-based characteristic curves remain mix-specific and cannot be generalized to other concretes [8].
In contrast, UPV provides complementary information by evaluating stress-wave transmission through concrete and has been widely used to characterize the internal quality and mechanical response of cementitious materials [9,10,11]. According to ASTM C597, the method is applicable for assessing concrete uniformity and relative quality, indicating cracks and voids, and monitoring changes in condition over time [12]. Because the measured quantity is transit time, from which an apparent pulse velocity is calculated, the result is inherently influenced by path geometry, coupling quality, saturation state, and the orientation of internal discontinuities relative to wave travel. This sensitivity has been widely recognized in previous work. Jedidi reviewed the UPV method and concluded that it is highly useful for evaluating concrete quality and monitoring material changes, but its correlation with compressive strength is indirect and must be established for the specific concrete being tested [13]. Turgut and Kucuk also showed that direct, indirect, and semi-direct UPV measurements produce systematically different results, although indirect and semi-direct values may be related to equivalent direct UPV values through regression-based relationships [14]. More recently, Lencis et al. demonstrated that moisture condition significantly affects both UPV and rebound results, reinforcing the need for controlled testing conditions and cautious interpretation when comparing measurements obtained under different environmental states [15].
The interpretation of NDE data becomes more complex when these methods are applied to reinforced concrete members, because embedded reinforcement may influence both rebound and ultrasonic response. ASTM C597 explicitly states that pulse velocity in steel may be substantially higher than in concrete and warns that measurements taken close to reinforcing bars parallel to the pulse path may produce artificially elevated values [12]. This effect has also been confirmed experimentally. Gashti showed that embedded steel and fiber-reinforced polymer (FRP) bars significantly affect UPV measurements, with the magnitude of the effect depending on reinforcement material, bar orientation, and concrete moisture condition [16]. Likewise, Nanayakkara et al. reported that reinforcement diameter and cover depth measurably alter UPV response, confirming that reinforcement proximity must be considered when interpreting ultrasonic measurements in reinforced members. These findings demonstrate that NDE indicators in reinforced concrete are influenced not only by the concrete matrix itself, but also by the presence, position, and type of embedded reinforcement [17]. Although current standards and practice guidelines provide important guidance for NDE testing and reinforced concrete assessment, they also reveal limitations that motivate further investigation. ASTM C805 and ASTM C597 specify procedures for SRH and UPV testing, respectively, but they emphasize that the measured response is affected by test conditions, surface condition, moisture state, testing configuration, and reinforcement proximity rather than being a direct measure of concrete strength [5,12]. Similarly, ACI 228.1R provides guidance for estimating in-place concrete strength using NDE methods, including SRH and UPV testing, but emphasizes the inherent limitations of each method and the need for calibration and careful interpretation [1]. British/European guidance such as BS EN 12504-4 provides a standardized procedure for determining UPV in hardened concrete, while EN 13791 addresses the assessment of in-situ compressive strength; however, these documents are mainly concerned with testing procedures and strength assessment rather than quantifying the effect of reinforcement configuration on measured NDE response [18,19]. Design-oriented documents such as ACI 440.1R, fib Model Code, and Chinese concrete standards provide useful provisions for reinforced concrete members, but they primarily focus on structural design, material resistance, and strength evaluation rather than reinforcement-induced bias in SRH and UPV measurements [20,21,22,23,24]. Therefore, existing standards do not provide detailed procedures for quantifying how reinforcement type, local reinforcement proximity, stirrup spacing, and stirrup material influence SRH and UPV measurements in hybrid steel–GFRP-reinforced concrete members. This limitation highlights the need for reinforcement-aware NDE interpretation, which is the focus of the present study.
Recent experimental research has demonstrated that the configuration and arrangement of steel and glass FRP (GFRP) reinforcement in hybrid reinforced concrete beams significantly influence post-cracking stiffness, crack development, deformability, and ultimate load-carrying capacity [25]. Long-term durability investigations have nevertheless shown promising performance in severe exposure conditions. For example, Ramanathan et al. reported that after 18 years of marine exposure, deterioration in extracted GFRP bars was largely limited to the outer surface, whereas the internal core remained substantially intact [26]. From an NDE perspective, Elbawab et al. incorporated SRH testing into an experimental study of steel-, GFRP-, basalt FRP-, and hybrid-reinforced beams, although the measurements were used primarily to assess concrete strength rather than examine reinforcement-dependent spatial variations [27].
In recent years, hybrid steel–GFRP reinforcement has emerged as a promising strategy to combine the corrosion resistance of GFRP with the stiffness, ductility, and yielding behavior of steel. Nouri et al. reported that hybrid steel–GFRP-reinforced beams can achieve improved structural performance relative to conventional steel-reinforced beams while maintaining acceptable ductility when reinforcement proportions are properly selected [28]. At the same time, the broader NDE literature has increasingly shown that uncertainty, repeatability, and data interpretation play a decisive role in the reliability of concrete assessment. Kumavat and Chandak demonstrated, through a large rebound-hammer dataset, that within-test variability and uncertainty measures significantly affect the reliability of rebound-based interpretation [29]. In parallel, data-driven and combined NDE approaches have been explored to improve predictive performance. Alavi and Noel showed that machine-learning models based on combined RN and UPV data can outperform traditional empirical equations in estimating compressive strength, although their reliability still depends strongly on data quality and database representativeness [30]. Ivanchev similarly found that combined SonReb-type approaches can provide closer agreement with destructive compressive strength measurements than RN or UPV used individually [31]. While these studies confirm the value of advanced interpretation frameworks, they are primarily concerned with strength prediction rather than with the direct influence of reinforcement configuration on NDE response.
Despite the growing application of NDE in reinforced concrete structures, limited information is available on how longitudinal reinforcement type, stirrup configuration, casting face, and testing arrangement collectively influence measured SRH and UPV responses when the concrete mixture remains unchanged. This gap is particularly relevant for hybrid steel–GFRP-reinforced members, where differences in reinforcement material and geometry may complicate the interpretation of NDE measurements. A companion study [32] investigated the flexural behavior of the same nine beam specimens, including their load–deflection response, cracking characteristics, ultimate capacity, and failure modes. In contrast, the present study addresses a distinct research objective by examining previously unreported SRH and UPV measurements obtained before mechanical loading.
The novelty of this work lies in its spatially resolved, reinforcement-aware evaluation of NDE responses across plain, steel-reinforced, GFRP-reinforced, and hybrid steel–GFRP-reinforced beams produced from a single concrete batch. The experimental dataset comprises 1044 rebound measurements collected across four beam faces and 162 UPV measurements obtained using transverse direct, longitudinal direct, and indirect transmission arrangements. Rebound locations were classified according to casting face and nominal proximity to longitudinal reinforcement, while UPV measurements incorporated transverse, longitudinal, and surface transmission paths of 210, 1100, and 220 mm, respectively. This combined framework enables the observed responses to be examined in relation to measurement location, reinforcement layout, stirrup configuration, and pulse transmission path.
By integrating detailed spatial mapping with multiple ultrasonic configurations, the study provides insight into the different sensitivities of SRH and UPV in reinforced and hybrid-reinforced concrete members. Because each reinforcement configuration was represented by one beam, the results are interpreted as descriptive specimen-level trends, with repeated measurements used to characterize within-beam spatial variability. The findings establish a practical basis for documenting casting face, reinforcement proximity, stirrup arrangement, and transmission path when interpreting NDE measurements and support the development of more comprehensive investigations into reinforcement-aware concrete assessment.
2. Materials and Methods
This study used concrete beams reinforced with steel, GFRP, and hybrid bar arrangements to characterize differences in measured NDE response. The concrete, reinforcement, specimen preparation, and measurement procedures are described below.
2.1. Material Properties
2.1.1. Concrete
All nine beam specimens and their companion cylinders were produced from one concrete batch. The concrete mix proportions and material properties are summarized in Table 1. The 175 mm slump was measured once, immediately before casting, in accordance with ASTM C143 [33]. Three 150 mm × 300 mm companion cylinders were stored with the beams and tested in accordance with ASTM C39 [34]. The individual compressive strengths were 26.6, 24.4, and 25.5 MPa, giving a mean of 25.5 ± 1.1 MPa (sample SD; n = 3). Testing used a calibrated CONTROLS AUTOMAX Compact-Line automatic compression machine (CONTROLS, S.p.A., Liscate, Italy; model 50-C46P02; 2000 kN capacity). Load was applied under automatic closed-loop force control at 0.25 ± 0.05 MPa/s, and the integrated control and recording system captured peak force and calculated compressive strength.
Table 1.
Concrete mix proportions and material properties used for casting all beam specimens.
2.1.2. Reinforcement Bars
Two types of reinforcement bars were employed in this study: conventional deformed steel bars and GFRP bars. Deformed steel bars with a nominal diameter of 12.7 mm were used in accordance with ASTM A615 [35] and ASTM A370 [36]. These bars exhibit a well-known ductile stress–strain behavior characterized by a distinct yield plateau and significant post-yield deformation. Tensile steel bar testing was performed and demonstrated an average yield strength of approximately 470 MPa, with an ultimate tensile strength of around 580 MPa, and a strain at failure of approximately 11%, as shown in Figure 1. The estimated modulus of elasticity from the linear region was 205 GPa, consistent with design standards. GFRP bars, also 12.7 mm in diameter, were manufactured using a pultrusion process and consisted of continuous E-glass fibers embedded in a thermosetting polymer resin. The bars complied with ASTM D7957 [37] and ACI 440.1R [38] specifications. Tensile testing, conducted according to ASTM D7205 [39], involved anchoring the bars in steel tubes filled with high-strength grout. The GFRP bars exhibited an average tensile strength of approximately 850 MPa and an ultimate strain of 2%. The material displayed a linear elastic response until sudden rupture, with no yielding or strain hardening, as illustrated in Figure 1.
Figure 1.
Stress–strain curves for steel and GFRP reinforcement bars. Adapted from [32].
2.2. Specimen Preparation
A total of nine reinforced concrete (RC) beams were cast to investigate the influence of steel, GFRP, and hybrid reinforcement on concrete behavior, as well as to evaluate how reinforcement type and stirrup spacing affect the response of NDE techniques. All RC beams were fabricated with identical dimensions and cast using the same concrete batch to ensure experimental consistency. Each beam measured 210 mm × 210 mm × 1100 mm and was reinforced with a combination of longitudinal bars and transverse stirrups based on the designated configuration. The beams varied in the type of reinforcement (steel, GFRP, or hybrid), transverse reinforcement spacing (100 mm or 200 mm), and stirrup material (steel or GFRP), as illustrated in Table 2. One beam represented each configuration; thus, the specimen identifier and reinforcement configuration are not independently replicated. All longitudinal bars were #13 (12.7 mm nominal diameter), and the steel or GFRP stirrups were #10 (9.5 mm nominal diameter). A nominal clear concrete cover of 10 mm was provided to the outside of the stirrup, consistent with the companion specimen description [32]. Consequently, the nominal centerline of a corner longitudinal bar was approximately 25.9 mm from the adjacent concrete face. To clarify the reinforcement arrangement within each beam, the cross-sectional details of the tested specimens are shown in Figure 2. The figure illustrates the location of steel and GFRP longitudinal bars and the corresponding transverse reinforcement configuration. Figure 3 shows the fully assembled reinforcement cages for all beams prior to placement into the casting molds. Each cage reflects the intended combination of longitudinal and transverse reinforcement types and spacing.
Table 2.
Reinforcement configurations of the tested concrete beam specimens.
Figure 2.
Cross-sectional views of RC beams showing reinforcement details for each beam. Adapted from [32].
Figure 3.
Assembled reinforcement cages for the tested beam specimens before placement in the casting molds.
All beams were cast from the single concrete batch described in Section 2.1.1. Concrete was placed incrementally and consolidated with a CONTROLS portable internal poker vibrator (model 55-C0162/E) driven by a 2000 W motor. After 24 h, the specimens were demolded, covered with wet cloth sheets, and rewetted by daily spraying throughout a 28-day curing period. Companion concrete cylinders (150 mm in diameter and 300 mm in height) were also cast from the same batch and cured under the same conditions. These cylinders were later tested for compressive strength in accordance with ASTM C39 [34], providing baseline material properties to support the evaluation of NDE results. All specimens were air-dried, unloaded, and visually uncracked during NDE testing. The nominal laboratory condition was 25 °C and approximately 30% relative humidity.
The parameters in Table 2 define the intended reinforcement configurations: longitudinal reinforcement type, stirrup spacing, and stirrup material. Concrete mix, beam dimensions, nominal bar diameters, reinforcement grade, casting batch, and curing procedure were held constant. This control reduces known sources of variation, but it does not eliminate specimen-to-specimen variability because each configuration is represented by a single beam. Accordingly, configuration comparisons are treated as descriptive trends within this experimental set.
2.3. Non-Destructive Evaluation (NDE)
Non-destructive evaluation (NDE) techniques were employed to assess the surface hardness and internal quality of the concrete beams without causing damage to the specimens. In this study, two widely adopted NDE techniques were utilized: SRH and UPV tests. The SRH test evaluates surface hardness and stiffness, while the UPV test measures the propagation velocity of ultrasonic waves through concrete, which reflects the internal integrity and homogeneity of the material. To investigate possible spatial variations in concrete properties, measurements were performed at multiple predefined locations distributed over the beam surfaces. The beams include six faces: Top (T), Bottom (B), Left (L), Right (R), Front (F), and Back (Ba). The beams were unloaded, visually uncracked, and air-dried under a nominal laboratory condition of 25 °C and 30% relative humidity.
2.3.1. Rebound Hammer Test
The SRH test was conducted to evaluate the surface hardness of the concrete beams and to provide an indirect indication of concrete quality. The test was performed in accordance with ASTM C805 [5], using a spring-controlled impact mass that strikes the concrete surface through a plunger. A CONTROLS 58-C0181/DGT user-programmable digital Type N concrete test hammer (CONTROLS, Italy; nominal impact energy 2.207 N·m) served as the SRH instrument. Before testing, each beam surface was examined in its as-cast, air-dried condition and wiped with a clean cloth to remove dust and loose particles. No surface grinding was performed. One reported rebound number was retained for each predefined measurement location. The rebound distance of the internal mass was recorded as the RN, which reflects the relative hardness and stiffness of the concrete surface. To ensure a systematic and spatially representative assessment, SRH measurements were carried out on the four longitudinal beam surfaces, namely T, B, L, and R faces, as identified in Figure 4. This figure is provided to clarify the orientation of the hammer and the surfaces included in the SRH measurement. Each long surface was subdivided into three horizontal measurement zones, designated as Zone 1 (Z1), Zone 2 (Z2), and Zone 3 (Z3), as illustrated in Figure 5. This measurement grid was used consistently on the four long faces of each beam to allow comparison of RN response among faces, zones, and reinforcement conditions.
Figure 4.
Schmidt rebound hammer test setup showing the tested beam faces and hammer orientation.
Figure 5.
Layout and numbering of rebound hammer measurement points on each long beam surface.
A total of 29 mapped impact points were defined on each long face: 10 in Z1, 9 in Z2, and 10 in Z3, as listed in Table 3. The detailed x–y coordinates of the rebound hammer measurement points are listed in Table 4. Longitudinal coordinates were x = 55–1045 mm, giving a minimum end-edge distance of 55 mm, while transverse row coordinates were y = 53, 105, and 157 mm, giving a minimum side-edge distance of 53 mm. Adjacent impacts in a row were separated by 110 mm. Based on the nominal 25.9 mm corner-bar centerline, Z1 and Z3 were each approximately 27.1 mm in projected perpendicular distance from the nearest longitudinal-bar centerline; Z2 was approximately 79.1 mm from either row and was classified as between bars. Since each beam has four long surfaces, the same measurement grid was applied to each surface. Consequently, the total number of rebound hammer readings obtained for each beam was 29 readings per surface times 4 surfaces, which equals 116 readings per beam. Considering that nine beams were tested in this study, the overall dataset consisted of 1044 rebound hammer measurements. This extensive dataset allowed a detailed spatial evaluation of surface hardness across the tested beams. To eliminate the influence of hammer test orientation on RN, each beam was rotated during testing so that the hammer was always applied perpendicular to the tested surface and directed downward toward the ground for all four faces. Accordingly, the Top, Bottom, Left, and Right faces were tested under the same hammer orientation.
Table 3.
Summary of rebound hammer measurement scheme.
Table 4.
Coordinate layout of rebound hammer measurement points on each long surface.
2.3.2. Ultrasonic Pulse Velocity (UPV) Testing Procedure
The UPV testing was conducted to assess the transmission characteristics and relative quality of the tested concrete beam specimens. The method was applied in accordance with the general principles of ASTM C597 [12], in which the travel time of an ultrasonic pulse through concrete is measured and used to determine the pulse velocity. In concrete materials, the measured velocity is influenced by the continuity, density, elastic properties, and overall internal condition of the material; therefore, UPV provides a useful basis for comparing the quality and uniformity of different specimens without causing damage. A portable UPV device, CNS Farnell Limited Pundit Plus (Borehamwood, UK) with a matched pair of 54 kHz metallic transducers having 50 mm circular contact faces, was used for all measurements. One transducer functioned as the transmitter, generating the ultrasonic pulse, while the other served as the receiver, detecting the signal after propagation through or along the concrete. Beam surfaces were air-dried and were cleaned to remove dust and loose particles. Ultrasonic gel (Sterilsafe, Madrid, Spain) was applied in sufficient quantity to provide continuous coupling, and the transducers were held normal to the surface using approximately consistent manual pressure. For each designated path, the measured path length was entered into the instrument; the device measured transit time and displayed the corresponding velocity in m/s. Velocity was calculated from transit time and path length using Equation (1):
where is pulse velocity, is the entered distance between transducer contact points, and is the measured pulse travel time. The instrument displayed the corresponding velocity after the reading stabilized.
To obtain a more comprehensive evaluation of the beam specimens, UPV measurements were performed using three different transmission arrangements: Right–Left direct transmission, longitudinal direct transmission, and Right–Left indirect transmission, as illustrated schematically in Figure 6. One stabilized displayed velocity was recorded for each measurement path, and no UPV readings were excluded. The corresponding transducer positions, path lengths, and number of measurements are summarized in Table 5, and the selected UPV configurations were based on ASTM C597 [12] and are consistent with BS EN 12504-4 guidance [18]. The short direct path across the 210 mm beam width provides a transverse through-beam comparison. The longitudinal direct path interrogates a substantially longer 1100 mm path parallel to the beam axis. The indirect arrangement, with both transducers on the same long face, provides a surface-sensitive comparison. The use of multiple transmission arrangements was intentional, as each configuration captures a different aspect of the ultrasonic response.
Figure 6.
Schematic illustration of the UPV testing configurations.
Table 5.
Summary of UPV transmission configurations, transducer positions, path lengths, and number of measurements.
For Right–Left direct transmission, nine paths were positioned at beam mid-height (z = 105 mm) at x = 110, 220, 330, 440, 550, 660, 770, 880, and 990 mm; the through-beam path length was 210 mm. For longitudinal direct transmission, the transducers were positioned at the centroids of the Front and Back end faces (y = z = 105 mm), producing one 1100 mm path parallel to the beam axis. The centroidal longitudinal path is approximately 111.9 mm from the centerline of each corner longitudinal bar based on the nominal geometry. For indirect transmission, both transducers were placed at mid-height on the same Right or Left face. Four 220 mm segments were tested on each face using transmitter–receiver x-coordinate pairs of 110–330, 330–550, 550–770, and 770–990 mm. Each beam therefore contributed 18 UPV records (9 Right–Left direct, 1 longitudinal direct, and 8 indirect), and the nine beams contributed 162 records. These are spatial/path records nested within beams, not independent beam replicates. This relatively large number of readings was intended to improve the reliability of the comparison and to reduce the influence of isolated local variations on the final interpretation.
2.4. Experimental Unit and Descriptive Analysis
The beam was treated as the experimental unit for each reinforcement configuration. The 1044 RN readings and 162 UPV measurements represent repeated spatial observations within the nine beams rather than independent experimental units. Because only one beam represented each configuration, differences among configurations cannot be separated from normal specimen-to-specimen variability. Accordingly, no inferential statistical tests were used to estimate configuration effects. The results are therefore presented using descriptive statistics that retain the structure of the measurements. RN values are summarized for each beam according to the tested face and measurement zone. Error bars represent the sample spatial standard deviation among the mapped locations and should not be interpreted as measurement repeatability at a single point. Right–Left direct and indirect UPV results are summarized across the measured paths within each beam, with sample spatial standard deviations based on nine and eight paths, respectively. Face-specific indirect UPV summaries are based on four paths per face. Because only one longitudinal direct path was recorded for each beam, no within-beam standard deviation is reported for this arrangement. Comparisons between the specimens with 100 and 200 mm stirrup spacing are presented as arithmetic differences between individual beams and are interpreted descriptively rather than as causal effects of stirrup spacing. The complete point-level RN and UPV data used in the analysis are provided in Supplementary File S1.
3. Results and Discussion
3.1. Schmidt Rebound Number
Figure 7 presents mean RN by face for each tested beam. Each bar is the arithmetic mean of n = 29 mapped impact locations on one face, and each error bar is ±1 sample spatial standard deviation (SD) across those 29 locations. The error bars are not the standard error of the mean, a confidence interval, between-beam variability, or repeatability at a single impact point. Across the 36 beam-by-face summaries, the means ranged from 33.79 to 50.76 RN and the sample spatial SDs ranged from 0.99 to 3.12 RN. Although the beams used one concrete batch, differences among individual beams may reflect both the intended configuration and uncontrolled specimen-level variation. The discussion therefore separates the consistent within-beam face pattern from descriptive configuration-level trends and avoids treating the single-beam comparisons as independently replicated effects.
Figure 7.
Schmidt RN measured on the four longitudinal faces of all beam specimens.
3.1.1. Face Effect
Across the tested beams, a clear face-dependent pattern was observed: the bottom face generally produced the highest rebound numbers (RNs), the top face the lowest, and the two side faces intermediate values. The recurrence of this ordering across the reinforcement configurations indicates that casting orientation and near-surface condition were important influences on the measured response. Rebound testing is particularly sensitive to the properties of the outer concrete layer, including its hardness, moisture condition, texture, and casting position, as recognized in ASTM C805 [5] and previous studies [6,8,15,40]. The lower top-face values may be associated with bleeding, laitance formation, finishing effects, and less uniform near-surface consolidation. Conversely, gravitational settlement and compaction may have produced a denser and harder near-surface layer at the bottom face. These mechanisms provide plausible explanations for the observed pattern but should not be considered direct evidence of concrete stratification because density, porosity, moisture gradients, and microstructural changes were not measured through the beam depth. Differences between the right and left faces were generally smaller than the top-to-bottom variation, suggesting limited lateral asymmetry. Therefore, reporting RN results separately by casting face provides a more meaningful interpretation than relying solely on a beam-wide average. Replicated specimens and direct measurements of depth-dependent concrete properties would be required to confirm the underlying mechanism and establish whether this pattern can be generalized.
3.1.2. Influence of Reinforcement Configuration and Stirrup Spacing
Although all specimens were produced using the same concrete batch and maintained under comparable curing and storage conditions, the mean RN varied among the different reinforcement configurations. The plain beam exhibited an average RN of 38.70, whereas most reinforced specimens produced higher values. The highest responses were recorded for S200 and HG100, with mean RNs of 47.03 and 47.66, respectively, corresponding to increases of approximately 21.5% and 23.2% relative to the plain beam. Conversely, G200 recorded a slightly lower mean RN of 38.39, representing a difference of approximately −0.8%. These variations indicate that rebound measurements in reinforced members cannot be interpreted solely as indicators of concrete quality. As emphasized in ASTM C805 and previous investigations, the rebound response is influenced by local testing conditions and the mechanical characteristics of the material beneath the impact location [5,6].
The influence of reinforcement material differed according to specimen configuration. At a stirrup spacing of 100 mm, G100 exhibited a mean RN of 45.01, slightly higher than the value of 44.43 recorded for S100. At 200 mm spacing, however, S200 produced a considerably higher mean RN than G200, with values of 47.03 and 38.39, respectively. This change in relative ordering indicates that the distinction between steel and GFRP reinforcement cannot be represented by a single consistent increase or decrease in rebound response. Differences in elastic modulus, bond behavior, and reinforcement arrangement may contribute to changes in the local mechanical response beneath the impact point, as supported by previous studies on steel–GFRP-reinforced concrete members [25,28]. However, because the S and G series differ in both longitudinal and transverse reinforcement materials, the contribution of either component cannot be isolated directly from these comparisons.
Stirrup spacing also produced configuration-dependent differences. Reducing the nominal spacing from 200 to 100 mm increased the mean RN by approximately 17.2% in the GFRP-reinforced series and 21.6% in the hybrid series with GFRP stirrups. In contrast, the corresponding changes were approximately −5.5% in the steel-reinforced series and −0.8% in the hybrid series with steel stirrups. Accordingly, closer stirrup spacing did not consistently produce higher rebound values across all reinforcement systems. The larger changes observed in the G and HG series suggest that the measured response may be sensitive to the combined arrangement of longitudinal reinforcement, transverse reinforcement, and impact location rather than to stirrup spacing alone. A similar pattern was observed when comparing stirrup material within the hybrid configurations. At 100 mm spacing, HG100 recorded a higher mean RN than HS100, with values of 47.66 and 42.09, respectively. At 200 mm spacing, the ordering was reversed: HS200 recorded 42.42, compared with 39.19 for HG200. These differences further indicate that the influence of transverse reinforcement depends on its interaction with the overall reinforcement configuration and does not support a uniform ranking of steel and GFRP stirrups.
The companion flexural study on the same beams demonstrated that stirrup type, stirrup spacing, and hybrid reinforcement arrangement influence structural behavior under mechanical loading [32]. However, the present rebound measurements were obtained before loading, when the beams were uncracked. Therefore, the observed RN differences should not be attributed directly to mobilized confinement, which generally develops when concrete undergoes lateral expansion under applied stress [41]. A more appropriate interpretation is that reinforcement geometry and material properties may modify the local impact response and the effective support beneath the tested surface. Comparable research by Elbawab et al. [27] incorporated SRH testing into an experimental investigation of steel-, GFRP-, BFRP-, and hybrid-reinforced beams, primarily to characterize the concrete used in the specimens. The present results extend this perspective by examining how rebound readings vary among reinforcement configurations and spatial testing locations. Nevertheless, because each configuration was represented by a single beam, the reported differences should be interpreted as descriptive specimen-level trends rather than generalized reinforcement effects.
3.1.3. Combined Influence of Measurement Face and Reinforcement Proximity
Figure 8 presents the descriptive relationship between measurement face, nominal reinforcement proximity, and RN. The measurement locations were classified according to the nearest projected longitudinal reinforcement condition: no reinforcement, proximity to steel reinforcement, proximity to GFRP reinforcement, or the region between longitudinal bars. This classification allows the rebound response to be examined in relation to both casting face and the local reinforcement arrangement. For the reinforced beams, the outer measurement rows, Z1 and Z3, were located approximately 27.1 mm from the centerline of the nearest longitudinal bar, whereas the central row, Z2, was approximately 79.1 mm from either bar row. Consequently, the steel and GFRP categories identify the material of the nearest projected bar and do not represent impacts applied directly over the reinforcement.
Figure 8.
Descriptive variation in rebound number across the four beam faces according to the nearest projected longitudinal reinforcement conditions.
The face-related pattern remained evident across the different reinforcement-proximity categories, with bottom-face values generally exceeding those measured on the top face and intermediate responses observed on the side faces. This indicates that casting-face effects remained important even when the local reinforcement condition was considered. Regions associated with steel reinforcement generally produced higher pooled RN values than regions associated with GFRP reinforcement; however, the relative ordering was not consistent for every face or every hybrid specimen. Therefore, the observed differences should be interpreted as descriptive spatial trends rather than as a universal material-dependent correction. Local reinforcement may influence the rebound response by modifying the stiffness or boundary conditions of the concrete surrounding the impact location. Nevertheless, only one nominal concrete cover and a limited range of lateral offsets were investigated, preventing the determination of a minimum unaffected distance or a quantitative reinforcement-influence zone. From a practical perspective, rebound measurements should therefore be interpreted with reference to the casting face, measurement coordinates, concrete cover, and proximity to the nearest reinforcement.
3.2. Ultrasonic Pulse Velocity (UPV) Analysis
3.2.1. Comparison of Mean UPV Values
Figure 9 presents the mean UPV values for the three arrangements. Right–Left direct bars summarize nine spatial paths per beam, indirect bars summarize eight spatial paths per beam, and each longitudinal direct bar is one recorded path. The three configurations interrogate different geometries; differences among them are therefore path-dependent responses rather than estimates of a common property. Right–Left direct UPV ranged from 3820 m/s for G200 to 4069 m/s for HS100. Its sample spatial SD ranged from 38.3 to 100.3 m/s across beams. Indirect sample spatial SD ranged from 71.1 to 161.6 m/s. Error bars are therefore included only for the Right–Left direct and indirect series; no SD is assigned to the single longitudinal path.
Figure 9.
Mean UPV values for all tested specimens.
Longitudinal direct UPV ranged from 3560 to 3950 m/s across the individual beams. S200 produced the highest recorded value (3950 m/s), while G200 (3560 m/s) and P (3590 m/s) were lowest. All longitudinal values were below the corresponding 210 mm transverse direct values. The longer path, concrete heterogeneity, and reinforcement parallel to or near the path may influence apparent velocity, but one longitudinal record per beam cannot quantify repeatability or transmission stability and is not used to infer configuration performance. Indirect average UPV was lower than the direct arrangements for every specimen, ranging from 3413 m/s for G200 to 3599 m/s for S100. This ordering is consistent with differences in surface coupling and indirect-path geometry, but it does not independently validate concrete quality or demonstrate agreement between methods. The values are path averages within individual beams.
3.2.2. Surface-Wise Comparison of Indirect UPV Values
The surface-wise indirect UPV comparison is shown in Figure 10, where the mean values measured on the right and left surfaces are plotted separately for each specimen. This figure provides information that is not visible from the indirect average alone. Specifically, it reveals whether the two long faces of a given beam responded similarly under indirect testing or whether one side exhibited a noticeably higher or lower surface velocity. Several specimens exhibited almost symmetric indirect responses. The control beam P showed virtually identical values on the two sides, namely 3498 m/s on the right surface and 3500 m/s on the left surface. Similarly, G200 showed nearly identical values of 3410 m/s and 3415 m/s, while HS200 yielded exactly the same mean value on both sides (3548 m/s). These cases suggest good side-to-side consistency in the near-surface concrete response. Such symmetry is important because it indicates that the beam surfaces behaved similarly under indirect transmission and that no substantial local surface disparity was detected at the scale of the present measurements. In contrast, other specimens displayed more pronounced side-to-side differences. The largest surface difference was observed for G100, where the indirect mean increased from 3413 m/s on the right surface to 3600 m/s on the left surface. A similarly clear asymmetry was observed for HG100, but in the opposite direction, with a higher right-side value (3643 m/s) than left-side value (3490 m/s). S200 also showed a substantial difference between the right and left surfaces (3525 m/s and 3653 m/s, respectively). When expressed relative to the indirect average, the surface asymmetry was highest for G100 (about 5.3%), followed by HG100 (about 4.3%) and S200 (about 3.6%). By contrast, the asymmetry was negligible for P, G200, and HS200. These results indicate that some beams possessed a fairly uniform surface response, whereas others exhibited measurable non-uniformity between the two long faces.
Figure 10.
Comparison of mean indirect UPV values measured on the right and left faces of the tested beam specimens.
3.2.3. Reduction in UPV Relative to Direct Transmission
To quantify the effect of changing the transmission arrangement, the percentage reduction in UPV relative to the Right–Left direct measurement was calculated for both the longitudinal direct and indirect configurations, as shown in Figure 11. This normalized representation facilitates comparison of the different transmission arrangements within each specimen. The reduction from Right–Left direct to longitudinal direct ranged from about 1.47% for S200 to about 9.56% for HS100. Intermediate values were obtained for S100 (3.81%), HG200 (6.37%), HG100 (6.51%), G200 (6.81%), G100 (7.44%), HS200 (7.77%), and P (8.02%). The smallest reduction observed for S200 indicates that this specimen maintained its transmission efficiency well even when the pulse path increased from 210 mm to 1100 mm. On the other hand, the larger reductions observed for HS100, P, and HS200 indicate that these beams were more sensitive to the increased path length. A larger and more consistent reduction was observed when comparing the Right–Left direct values with the indirect averages. The direct-to-indirect reduction ranged from about 9.84% for S100 to about 12.74% for HS200. The remaining specimens showed reductions of approximately 10.36% (P), 10.48% (S200), 11.82% (G100), 11.80% (HG100), 11.93% (HG200), 10.66% (G200), and 12.17% (HS100). Two important observations emerge from this result. First, the indirect reduction was always larger than the longitudinal-direct reduction, showing that the change in transmission mode had a stronger influence on measured velocity than the increase in path length alone. Second, although the indirect method consistently produced lower values, the magnitude of the reduction varied among specimens, indicating that some beams were more sensitive to indirect transmission conditions than others. Because the longitudinal direct arrangement was represented by a single measurement per beam, variability could not be evaluated for this configuration.
Figure 11.
Percentage reduction in UPV for longitudinal direct and indirect configurations relative to the Right–Left direct transmission value.
3.2.4. General Interpretation of UPV Findings
Figure 9, Figure 10 and Figure 11 demonstrate that the three UPV arrangements provide complementary information about ultrasonic transmission within the tested beams. Right–Left direct transmission generally produced the highest velocities, followed by longitudinal direct transmission, whereas indirect measurements consistently yielded the lowest values. This ordering reflects differences in propagation direction, transmission distance, transducer positioning, and surface coupling, all of which can influence the measured ultrasonic response [12,14]. The comparison between the right and left indirect measurements further identifies differences in near-surface response, while the normalized reductions illustrate how individual specimens responded to changes in transmission arrangement. Among the tested specimens, G200 exhibited relatively low UPV values across the different configurations, whereas HS100, HS200, HG100, and HG200 generally produced higher Right–Left direct velocities. S200 showed the smallest reduction between the transverse and longitudinal direct measurements, indicating closer agreement between its short and long transmission paths. Conversely, HG100 exhibited noticeable differences between the indirect measurements obtained on its two side faces, despite producing relatively high direct UPV values. These examples demonstrate that similar direct velocities do not necessarily correspond to similar longitudinal or near-surface responses.
The observed differences should also be considered in relation to reinforcement geometry. Previous studies have shown that UPV measurements may be influenced by reinforcement proximity, bar orientation, and the position of the transmission path relative to embedded steel [16,17]. However, the present measurements do not distinguish the contribution of the concrete matrix from that of nearby reinforcement, and the longitudinal arrangement was represented by a single path per beam. Accordingly, the combined interpretation of direct velocities, side-to-side comparisons, and percentage reductions provides a more comprehensive description of specimen-specific transmission behavior than any individual measurement arrangement alone. The Right–Left direct configuration characterizes the short transverse response, the longitudinal direct configuration represents transmission along the beam length, and the indirect configuration provides additional information on near-surface variability.
3.3. Comparative Assessment of UPV and RN Results
Figure 12 presents a normalized comparison of the mean RN, Right–Left direct UPV, and indirect UPV for the nine beam specimens. Each value was divided by the maximum value obtained using the corresponding measurement method, allowing the specimen responses to be compared despite differences in units and measurement scales. The resulting profiles reveal areas of qualitative similarity as well as noticeable differences between the two techniques. For example, S200 and HG100 exhibited relatively high normalized responses across several indicators, whereas G200 generally remained among the lower-ranking specimens. Nevertheless, some beams with relatively high direct UPV did not exhibit correspondingly high RN values, indicating that favorable ultrasonic transmission does not necessarily coincide with increased near-surface rebound response.
Figure 12.
Normalized comparison of mean RN, Right–Left direct UPV, and indirect average UPV for all tested specimens.
The different degrees of variation observed in the normalized profiles further highlight the distinct sensitivities of the two methods. RN showed a wider specimen-to-specimen spread, reflecting its sensitivity to testing face, reinforcement proximity, and local surface conditions. UPV exhibited a comparatively narrower range, particularly for direct transmission, indicating a more consistent response along the measured pulse paths. Indirect UPV provided additional information concerning near-surface transmission and therefore complemented the direct measurements without replicating the rebound response. Previous studies have demonstrated that combined SonReb approaches can improve concrete strength estimation when supported by appropriate destructive calibration and independent validation [30,31]. Although companion cylinders provided a common compressive-strength reference for the concrete used in this study, they did not establish beam-specific calibration relationships or a validated strength-prediction model. Accordingly, the normalized comparison is intended to illustrate descriptive specimen-level trends and the complementary characteristics of SRH and UPV rather than demonstrate statistical agreement, establish a universal correlation, or predict concrete strength.
For transparent arithmetic comparison of each 100 mm–200 mm specimen pair, a pairwise percentage difference (PPD) was calculated using the 200 mm specimen as the reference:
where PPD is the percentage difference between the measured responses of the paired 100 mm and 200 mm specimens, M100 is the response of the 100 mm specimen, and M200 is the response of the corresponding 200 mm specimen. A positive value means that the individual 100 mm beam had a higher measured response; a negative value means that it had a lower response.
Table 6 lists the PPD for each individual specimen pair. RN changed more than UPV in several pairs, but the sign and magnitude were configuration-dependent. Each value combines any spacing-related difference with specimen identity, surface condition, and uncontrolled beam-to-beam variability.
Table 6.
Pairwise percentage differences (PPD) in measured SRH and UPV responses when stirrup spacing was reduced from 200 mm to 100 mm.
The normalized comparison and PPD presented in Figure 12 and Table 6 demonstrate that RN and UPV provide complementary, but not identical, descriptions of the tested specimens. S200 and HG100 exhibited relatively high responses across several indicators, whereas P and G200 generally showed lower normalized values. However, agreement between the two methods was not uniform. For example, HS100 produced a relatively high Right–Left direct UPV but only a moderate RN, while HG200 also exhibited a comparatively strong direct ultrasonic response without a correspondingly high RN value. The pairwise comparisons further illustrate this distinction: reducing stirrup spacing from 200 to 100 mm increased RN by 17.2% in the G series and 21.6% in the HG series, whereas the corresponding changes in Right–Left direct UPV were only 4.1% and −0.1%, respectively. These differences indicate that changes in local rebound response were not consistently accompanied by proportional changes in ultrasonic transmission.
The face-resolved measurements provide additional insight into the different spatial sensitivities of the two techniques. RN showed consistent ordering in which the bottom face produced the highest values, the top face produced the lowest values, and the side faces generally exhibited intermediate responses. This pattern is consistent with the influence of casting position and near-surface conditions on rebound measurements, although specific mechanisms such as bleeding, laitance formation, or changes in density were not independently verified. By comparison, indirect UPV measurements were restricted to the right and left longitudinal faces and therefore captured differences in near-surface ultrasonic transmission between the two sides. Specimens such as P, G200, and HS200 showed relatively similar responses on both faces, whereas G100, HG100, and S200 exhibited more noticeable side-to-side differences. Consequently, RN and indirect UPV identified different aspects of surface-related variability without necessarily reflecting the same physical mechanism.
The observed responses should also be interpreted in relation to reinforcement proximity and measurement geometry. RN is sensitive to the local mechanical conditions beneath the impact point, whereas UPV depends on the position and orientation of the transmission path relative to the surrounding concrete and embedded reinforcement. In the present configuration, no rebound impact was centered directly above a longitudinal bar: the Z1 and Z3 measurement rows were approximately 27.1 mm from the nearest projected bar centerline, while the Z2 row was approximately 79.1 mm from either bar row. These offsets allow comparisons between regions closer to and farther from longitudinal reinforcement but do not establish a definitive reinforcement-influence boundary. Accordingly, practical interpretation should consider the tested face, concrete cover, projected bar location, and ultrasonic transmission arrangement. Where feasible, reinforcement should be located before testing and measurements should be taken in clearly documented between-bar regions. Overall, the combined results describe specimen-specific NDE behavior rather than direct differences in concrete strength, structural performance, or reinforcement effectiveness.
3.4. Study Limitations and Future Research
The findings of this study should be interpreted within the scope of the experimental program. Each reinforcement configuration was represented by a single beam, limiting the ability to distinguish configuration-related trends from specimen-to-specimen variability. The investigation was also restricted to one concrete mixture, a limited number of reinforcement arrangements and stirrup spacings, and unloaded, uncracked specimens tested under controlled laboratory conditions. Consequently, the observed RN and UPV responses cannot be directly generalized to concrete members with different strength levels, reinforcement ratios, cover depths, loading histories, damage conditions, or environmental exposures. Furthermore, the study examined only two NDE techniques and did not establish calibrated relationships between measured responses and the mechanical properties of individual beams. Future investigations should incorporate replicated specimens, a broader range of concrete mixtures and reinforcement configurations, different cover thicknesses, and additional testing ages. Evaluating specimens under service loads, progressive cracking, environmental deterioration, and field conditions would further clarify the applicability of the observed trends to existing structures. Integrating SRH and UPV with complementary NDE methods and destructive reference measurements could also support the development of more reliable, reinforcement-aware assessment approaches for steel, GFRP, and hybrid-reinforced concrete members.
4. Conclusions
This study investigated the influence of steel, GFRP, and hybrid steel–GFRP reinforcement on SRH and UPV responses of concrete beams. A total of nine beams cast from the same concrete batch were evaluated through an extensive NDE program comprising 1044 rebound readings and 162 UPV measurements. Based on the results, the following conclusions are drawn:
- Rebound measurements showed a consistent casting-face effect. The bottom and top faces recorded average RNs of approximately 45.4 and 38.8, respectively, while the side faces exhibited intermediate values. This pattern demonstrates that casting position and near-surface condition should be considered when interpreting SRH measurements.
- RN varied considerably among the tested reinforcement configurations. Compared with the plain beam, HG100 exhibited an increase of approximately 23.2%, whereas G200 showed a slight decrease of approximately 0.8%. These results indicate that rebound response depends on the combined reinforcement arrangement rather than the presence of reinforcement alone.
- UPV measurements depended strongly on the transmission arrangement. Right–Left direct transmission produced beam-average velocities of up to 4069 m/s, whereas indirect transmission produced averages as low as 3413 m/s; longitudinal direct measurements generally fell between these responses. These differences reflect the influence of propagation direction, transmission mode, and path geometry.
- The pairwise percentage differences demonstrated that the influence of stirrup spacing was configuration-dependent. Reducing the spacing increased RN by 21.6% in the HG series but decreased it by 5.5% in the S series. Therefore, closer stirrup spacing did not consistently produce higher rebound values across all reinforcement systems.
- RN and UPV provided complementary information but did not respond equally to changes in reinforcement configuration. For the G series, the pairwise percentage difference associated with stirrup spacing was 17.2% for RN compared with 4.1% for Right–Left direct UPV. This difference confirms that localized rebound response and ultrasonic transmission capture distinct characteristics of the tested specimens.
- Because each reinforcement configuration was represented by a single beam tested under laboratory conditions, the reported differences should be interpreted as descriptive specimen-level observations rather than generalized reinforcement effects.
Supplementary Materials
The following supporting information can be downloaded at https://www.mdpi.com/article/10.3390/buildings16173550/s1. Supplementary File S1: Point-Level Beam NDE Database.
Author Contributions
Conceptualization, methodology, supervision, project administration, funding acquisition, data interpretation, and manuscript writing, E.A., H.A., A.A. and B.A.A. contributed to the experimental investigation and data organization and preparation. E.A. prepared the original draft of the manuscript. All authors have read and agreed to the published version of the manuscript.
Funding
The authors gratefully acknowledge Qassim University, represented by the Deanship of Graduate Studies and Scientific Research, for the financial support of this research under grant number (QU-J-UG-2-2025-56768) during the academic year 1446 AH/2024 AD.
Data Availability Statement
The data presented in this study are provided in Supplementary File S1.
Acknowledgments
The authors gratefully acknowledge Qassim University, represented by the Deanship of Graduate Studies and Scientific Research, for the financial support of this research under grant number (QU-J-UG-2-2025-56768) during the academic year 1446 AH/2024 AD. Also, during the preparation of this work, the authors used ChatGPT5.2 to refine language, improve readability, and enhance formatting consistency. After using this tool, the authors thoroughly reviewed and edited the content as needed and took full responsibility for the content of the publication.
Conflicts of Interest
The authors declare no conflicts of interest.
References
- ACI 228.1R-03; In-Place Methods to Estimate Concrete Strength. American Concrete Institute: Farmington Hills, MI, USA, 2003.
- Carino, N.J.; Malhotra, V.M. Handbook on Nondestructive Testing of Concrete; CRC Press: Boca Raton, FL, USA, 2004. [Google Scholar]
- International Atomic Energy Agency. Guidebook on Non-Destructive Testing of Concrete Structures; IAEA–TCS–17; International Atomic Energy Agency: Vienna, Austria, 2002. [Google Scholar]
- Alsuhaibani, E. Nondestructive Testing of Externally Bonded FRP Concrete Structures: A Comprehensive Review. Polymers 2025, 17, 1284. [Google Scholar] [CrossRef] [Scilit]
- ASTM C805/C805M-18; Standard Test Method for Rebound Number of Hardened Concrete. ASTM International: West Conshohocken, PA, USA, 2018. [CrossRef] [Scilit]
- Brencich, A.; Bovolenta, R.; Ghiggi, V.; Pera, D.; Redaelli, P. Rebound Hammer Test: An Investigation into Its Reliability in Applications on Concrete Structures. Adv. Mater. Sci. Eng. 2020, 2020, 6450183. [Google Scholar] [CrossRef] [Scilit]
- Jedidi, M. Evaluation of the Quality of Concrete Structures by the Rebound Hammer Method. Curr. Trends Civ. Struct. Eng. 2020, 5, 1–7. [Google Scholar] [CrossRef] [Scilit]
- Kocáb, D.; Misák, P.; Cikrle, P. Characteristic Curve and Its Use in Determining the Compressive Strength of Concrete by the Rebound Hammer Test. Materials 2019, 12, 2705. [Google Scholar] [CrossRef] [Scilit]
- Alsuhaibani, E. Mechanical and Ultrasonic Evaluation of Epoxy-Based Polymer Mortar Reinforced with Discrete Fibers. Polymers 2025, 17, 1250. [Google Scholar] [CrossRef] [Scilit]
- Estévez, E.; Martín, D.A.; Argiz, C.; Sanjuán, M.Á. Ultrasonic Pulse Velocity—Compressive Strength Relationship for Portland Cement Mortars Cured at Different Conditions. Crystals 2020, 10, 133. [Google Scholar] [CrossRef] [Scilit]
- Zhang, F.; Pang, K.; Li, J.; Liu, Q.; Du, J.; Xiao, H.; Guo, B.; Zhang, J. Ultrasonic pulse velocity as a non-destructive measure for the projectile impact resistance of cementitious composites across a wide range of mix compositions. J. Build. Eng. 2024, 94, 109875. [Google Scholar] [CrossRef] [Scilit]
- ASTM C597-22; Standard Test Method for Ultrasonic Pulse Velocity Through Concrete. ASTM International: West Conshohocken, PA, USA, 2022. [CrossRef] [Scilit]
- Jedidi, M. Evaluation of Concrete by Non-destructive Ultrasonic Pulse Velocity Method. Civ. Eng. Archit. 2022, 10, 1623–1630. [Google Scholar] [CrossRef] [Scilit]
- Turgut, P.; Kucuk, O.F. Comparative relationships of direct, indirect, and semi-direct ultrasonic pulse velocity measurements in concrete. Russ. J. Nondestruct. Test. 2006, 42, 745–751. [Google Scholar] [CrossRef] [Scilit]
- Lencis, U.; Klaucans, R.; Udris, A.; Korjakins, A.; Zhou, X.; Bumanis, G. The Moisture Effect on Ultrasonic, Rebound Hardness and Drilling Resistance Data in Non-Destructive Testing of Concrete. Appl. Sci. 2025, 15, 11973. [Google Scholar] [CrossRef] [Scilit]
- Gashti, M.F. The influence of FRP reinforcement on ultrasonic pulse velocity testing. Indian J. Fundam. Appl. Life Sci. 2015, 5, 1466–1476. [Google Scholar]
- Nanayakkara, O.; Najm, H.M.; Sabri, M.M.S. Effect of Using Steel Bar Reinforcement on Concrete Quality by Ultrasonic Pulse Velocity Measurements. Materials 2022, 15, 4565. [Google Scholar] [CrossRef] [Scilit]
- BS EN 12504-4:2021; Testing Concrete in Structures—Part 4: Determination of Ultrasonic Pulse Velocity. BSI: London, UK, 2021.
- BS EN 13791:2019; Assessment of In-Situ Compressive Strength in Structures and Precast Concrete Components. BSI: London, UK, 2019.
- ACI CODE-440.11-22; Building Code Requirements for Structural Concrete Reinforced with Glass Fiber-Reinforced Polymer (GFRP) Bars—Code and Commentary. American Concrete Institute: Farmington Hills, MI, USA, 2022.
- ACI 318-14; Building Code Requirements for Structural Concrete and Commentary. American Concrete Institute: Farmington Hills, MI, USA, 2014.
- fib. fib Model Code for Concrete Structures 2010; Ernst & Sohn: Berlin, Germany, 2013. [Google Scholar] [CrossRef] [Scilit]
- GB 50010-2010; Code for Design of Concrete Structures. China Architecture & Building Press: Beijing, China, 2010.
- GB/T 50152-2012; Standard for Test Methods of Concrete Structures. China Architecture & Building Press: Beijing, China, 2012.
- Şahin, A.; Er, Ş.B. Influence of Reinforcement Configuration on the Flexural Performance of Hybrid GFRP–Steel-Reinforced Beams. Buildings 2026, 16, 2757. [Google Scholar] [CrossRef] [Scilit]
- Ramanathan, S.; Benzecry, V.; Suraneni, P.; Nanni, A. Condition assessment of concrete and glass fiber reinforced polymer (GFRP) rebar after 18 years of service life. Case Stud. Constr. Mater. 2021, 14, e00494. [Google Scholar] [CrossRef] [Scilit]
- Elbawab, Y.; Elbawab, Y.; El Zoughby, Z.; ElKadi, O.; AbouZeid, M.; Sayed-Ahmed, E. Flexural Testing of Steel-, GFRP-, BFRP-, and Hybrid Reinforced Beams. Polymers 2025, 17, 2027. [Google Scholar] [CrossRef] [Scilit]
- Nouri, Y.; Ghanbari, M.A.; Fakharian, P. Flexural behavior of hybrid GFRP-steel reinforced concrete beam: Experimental and explainable artificial intelligence. Eng. Struct. 2025, 345, 121565. [Google Scholar] [CrossRef] [Scilit]
- Kumavat, H.R.; Chandak, N.R. Repeatability of concrete rebound hardness using comprehensive statistical analysis. J. King Saud Univ.-Eng. Sci. 2023, 35, 167–173. [Google Scholar] [CrossRef] [Scilit]
- Alavi, S.A.; Noel, M. Uncertainty and Prediction Intervals of New Machine Learning Approach for Non-Destructive Evaluation of Concrete Compressive Strength. Buildings 2025, 15, 544. [Google Scholar] [CrossRef] [Scilit]
- Ivanchev, I. Investigation with Non-Destructive and Destructive Methods for Assessment of Concrete Compressive Strength. Appl. Sci. 2022, 12, 12172. [Google Scholar] [CrossRef] [Scilit]
- Alsuhaibani, E.; Aldukail, A. Experimental Study on Hybrid Steel–GFRP Reinforced Concrete Beams with Different Stirrup Types and Spacings. Buildings 2025, 15, 4047. [Google Scholar] [CrossRef] [Scilit]
- ASTM C143/C143M-20; Standard Test Method for Slump of Hydraulic-Cement Concrete. ASTM International: West Conshohocken, PA, USA, 2020. [CrossRef] [Scilit]
- ASTM C39/C39M-21; Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens. ASTM International: West Conshohocken, PA, USA, 2021. [CrossRef] [Scilit]
- ASTM A615/A615M-12; Standard Specification for Deformed and Plain Carbon-Steel Bars for Concrete Reinforcement. ASTM International: West Conshohocken, PA, USA, 2012. [CrossRef] [Scilit]
- ASTM A370-24; Standard Test Methods and Definitions for Mechanical Testing of Steel Products. ASTM International: West Conshohocken, PA, USA, 2024. [CrossRef] [Scilit]
- ASTM D7957/D7957M-17; Standard Specification for Solid Round Glass Fiber Reinforced Polymer Bars for Concrete Reinforcement. ASTM International: West Conshohocken, PA, USA, 2017. [CrossRef] [Scilit]
- ACI 440.1R-15; Guide for the Design and Construction of Structural Concrete Reinforced with Fiber-Reinforced Polymer Bars. American Concrete Institute: Farmington Hills, MI, USA, 2015.
- ASTM D7205/D7205M-06(2016); Standard Test Method for Tensile Properties of Fiber Reinforced Polymer Matrix Composite Bars. ASTM International: West Conshohocken, PA, USA, 2016. [CrossRef] [Scilit]
- Kumavat, H.R.; Chandak, N.R.; Patil, I.T. Factors influencing the performance of rebound hammer used for non-destructive testing of concrete members: A review. Case Stud. Constr. Mater. 2021, 14, e00491. [Google Scholar] [CrossRef] [Scilit]
- CEB-FIP MODEL CODE 1990; Comite Euro-International Du Beton. Emerald Publishing Limited: Leeds, UK, 1993. [CrossRef] [Scilit]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2026 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.