Traveling-Wave-Based High-Speed Main Protection of Low-Frequency AC Submarine Cables with Analytical-Model-Based Offline Setting

,
,
,
and
1
CNOOC Research Institute Co., Ltd., Beijing 100028, China
2
School of Automation, Guangdong University of Technology, Guangzhou 510006, China
*
Author to whom correspondence should be addressed.

Abstract

Long-distance low-frequency alternating-current (LFAC) submarine cables exhibit pronounced high-frequency attenuation and dispersion, while background components generated by the modular multilevel matrix converter (M3C) complicate fault-wavefront extraction. This study proposes a single-ended traveling-wave primary protection scheme combining a Bergeron numerical model, variational mode decomposition (VMD), and the Teager energy operator (TEO). The Bergeron model is used offline to calculate theoretical wavefront counts for different fault locations and fault resistances. The most adverse offline result determines a unified fixed wavefront-count threshold for online protection. After the startup criterion is triggered, the 1-mode backward traveling wave within a 2 ms window is differentiated and normalized. VMD decomposes the signal into multiple modal components, and two informative modes are selected based on their energy contribution, wavefront characterization capability, and performance in the presence of noise to reconstruct the traveling-wave feature signal. TEO then maps the reconstructed signal into an energy sequence, where local peaks mark wavefront arrivals. An internal fault is identified when the measured wavefront count reaches the fixed threshold. Case studies conducted in PSCAD/EMTDC show that the starting criterion detects abrupt changes for single-phase grounding faults at different locations, and the proposed protection correctly distinguishes the tested internal and reverse external faults. The scheme operates correctly for all tested internal fault locations, including faults with fault resistances of up to 300 Ω, and remains secure for the tested reverse external faults.

1. Introduction

1.1. Background and Scope

Currently, long-distance offshore power transmission is increasingly required for deepwater oil and gas platforms, offshore wind farms, and remote island systems. Conventional power-frequency alternating-current (AC) transmission produces substantial cable charging current over long distances, reducing active-power transfer capability and increasing the risks of end-voltage limit violations and resonance [1]. Flexible direct current (DC) avoids cable charging current but requires costly offshore conversion equipment, while DC fault currents rise rapidly and lack natural zero crossings [2].
Low-frequency alternating-current (LFAC) transmission lowers the operating frequency through power-electronic conversion, thereby reducing cable charging reactive power and voltage drop and extending the feasible transmission distance. By locating the main alternating-current-to-alternating-current (AC-AC) conversion station onshore and using low-frequency transformers offshore, LFAC has been investigated for long-distance power supply to offshore oil and gas platforms [3], island clusters [4], offshore wind integration [5], and renewable-energy aggregation [6].
In engineering practice, LFAC has progressed beyond conceptual studies. The Taizhou Flexible LFAC Transmission Project in Zhejiang, China, reported as the world’s first offshore wind-power transmission project using flexible LFAC, was commissioned on 16 June 2022. It employs a 35 kV/20 Hz submarine-cable link, a 35 kV/12.5 MVA onshore modular multilevel matrix converter (M3C) station, and two 1.1 MW/20 Hz wind turbines on Dachen Island; field operation has verified stable low-frequency power transmission [6]. A separate 220 kV/20 Hz flexible LFAC onshore grid interconnection project has been reported in Hangzhou, while recent metrology research explicitly addresses the 20 Hz voltage-ratio traceability requirements of the 35 kV and 220 kV LFAC projects [7]. These practical developments indicate that LFAC is moving from feasibility studies toward engineering deployment, making dedicated protection for converter-dominated low-frequency cables increasingly important.

1.2. Related Works

Research on LFAC marine transmission has evolved from system-level feasibility studies toward frequency and techno-economic optimization, converter/control design, engineering demonstration, and dedicated protection. Ruddy et al. provided a foundational review of LFAC for offshore wind transmission [8], while Liu et al. developed a fractional-frequency transmission architecture for offshore wind integration [5]. Meere et al. quantified the influence of non-standard AC frequencies on offshore transmission range and cost [9]. Xiang et al. identified intermediate distance ranges in which LFAC can be cost-effective relative to HVAC and HVDC, whereas Dakic et al., using a different optimization framework and cost assumptions, found a more limited LFAC application range [10,11]. Tang et al. further proposed a DRU-based LFAC architecture with a hybrid onshore converter and corresponding control strategy [12]. These studies show that the technical and economic attractiveness of LFAC is sensitive to transmission distance, power and voltage ratings, cable configuration, converter topology, and cost assumptions rather than being characterized by a single universal break-even distance.
Compared with conventional synchronous-generator-dominated AC systems, an M3C-based LFAC system combines low-frequency AC behavior with converter-dominated fault characteristics. This combination complicates both steady-state measurement and early transient feature extraction.
At 16.67 or 20 Hz, the longer fundamental period increases the data window needed by full-cycle phasor estimation. Multifrequency M3C modulation can generate background harmonics that complicate early traveling-wave feature extraction [13]. During the early fault stage, converter control changes the terminal boundary and subsequent transient response. In long power cables, frequency-dependent distributed parameters attenuate and distort high-frequency traveling-wave components [14]. Reflections at line terminals and fault points further complicate close-in and remote-end faults, while high fault resistance weakens the observable fault component [15].
Existing LFAC protection methods can be broadly divided into power-frequency-based protection, communication-assisted unit protection, and transient-based single-ended protection. Single-ended power-frequency protection avoids communication dependence, but converter current limiting and fault ride-through control alter current phase and apparent impedance [16,17]. Also, the longer LFAC fundamental period increases the data window required for Fourier-based phasor estimation, limiting the speed of steady-state protection [18].
More recently, Dai et al. analyzed the adaptability of distance protection in flexible LFAC wind-power outgoing lines [18], further confirming that converter-limited fault-current magnitude and controllable phase can weaken conventional impedance-based criteria.
Communication-assisted LFAC protection has been investigated using backward-traveling-wave differences [19]. Its implementation depends on communication infrastructure [20]. Representative criteria also include directional protection [21] and statistical divergence features [22]. Schemes requiring time-aligned quantities additionally depend on synchronization, and external-fault transients can complicate security and observation-window selection.
Beyond these studies, Gao et al. proposed directional pilot protection specifically for LFAC submarine cables [21], and Gao et al. developed a Kullback–Leibler divergence-based pilot protection for offshore-wind low-frequency cable feeders [22]. These studies further demonstrate the active shift toward dedicated protection principles tailored to converter-interfaced LFAC cables.
Consequently, fast single-ended main protection remains valuable, particularly when communication is unavailable [23]. Transient protection uses the broadband wavefront generated at fault inception and can achieve millisecond-level decisions without dual-terminal data [24,25]. Wavelet-transform and mathematical-morphology techniques have been applied to transient-feature extraction [26]. For long LFAC submarine cables, however, high-frequency attenuation and converter-generated background components can obscure weak wavefronts. Moreover, protection settings often rely on repeated electromagnetic-transient simulations, leaving room for a more transparent analytical-model-based offline setting mechanism.
Recent single-ended/transient LFAC protection studies have also explored Canberra-distance criteria and transient high-frequency-energy features for offshore-wind flexible LFAC lines [24,25]. These results support the feasibility of sub-cycle protection, but they also reinforce the need for robust feature extraction under long-cable attenuation, dispersion, and converter-generated background components.

1.3. Research Gap and Motivation

Although existing studies have advanced LFAC line protection through phasor-based, pilot, and transient-based schemes, it remains difficult to simultaneously achieve fast operation, single-ended implementation, reliable extraction of weak transient features, and interpretable protection settings for long-distance submarine cables with power-electronic terminals.
First, for protection relying on fundamental-frequency components, the lower operating frequency of 16.67/20 Hz directly increases the absolute data-window duration when the same number of cycles is used. Meanwhile, the M3C and full-power wind converters at the two terminals produce fault currents with limited magnitudes and controllable phases, further weakening the applicability of conventional fundamental-frequency-based protection [18]. Existing studies, therefore, indicate that transient- or time-domain-based protection is better suited to shortening the fault-information acquisition time in such systems.
Second, pilot protection can provide clear internal/external fault discrimination by comparing measurements from both line terminals. Backward-traveling-wave-voltage-difference-based [19] and directional pilot protection [21] has been proposed for LFAC submarine cables and validated under converter control. However, such schemes require dual-terminal measurements and, therefore, depend on communication links. Criteria requiring temporal correspondence also involve synchronization, data alignment, and communication delay. Single-ended main protection is, therefore, still needed when communication is unavailable or limited.
In addition, the distributed and frequency-dependent parameters of submarine cables cause frequency-dependent attenuation and waveform distortion of fault traveling waves over long distances [14]. High-frequency transient components are further attenuated by line and terminal boundaries, making remote and high-resistance faults more difficult to detect [15]. Meanwhile, the M3C directly connects two AC systems with different fundamental frequencies, resulting in pronounced dual-frequency harmonic coupling and multifrequency components [27]. The superposition of these background components and fault-generated traveling waves further complicates weak-wavefront extraction and identification.
The setting mechanism is another key issue for transient-based protection. Many existing criteria still determine operating thresholds through numerical simulations or statistical analysis under specific system parameters. The dependence on numerical simulations and the lack of direct physical interpretation have been identified as important limitations, and analytical traveling-wave expressions have been used to relate protection criteria to their settings [28]. For LFAC submarine cables, an explicit relationship between protection settings and traveling-wave propagation, reflection, and refraction can improve setting interpretability and reduce reliance on repeated electromagnetic-transient simulations.
Accordingly, a single-ended main protection method is developed for LFAC submarine cables by separating offline settings from online transient-feature extraction. Offline, a Bergeron distributed-parameter equivalent model is used to analyze traveling-wave propagation, reflection, and refraction and to calculate the theoretical wavefront count within the prescribed observation window, which provides the basis for protection setting under the specified system topology and parameters. Online, only local voltage and current measurements are used; VMD extracts fault-informative modal components, and TEO enhances transient energy changes associated with wavefront arrivals for wavefront detection and counting. The proposed method, therefore, avoids waiting for full fundamental-frequency phasor formation and does not require dual-terminal communication, while replacing purely empirical simulation-based threshold selection with a physically interpretable offline setting process.

1.4. Contributions

To address these issues, this study separates offline analytical-model-based settings from online signal processing: the Bergeron model provides theoretical wavefront-count references, variational mode decomposition (VMD) reconstructs fault-informative transient modal components, and the Teager energy operator (TEO) highlights energy changes associated with wavefront arrivals.
(1) A Bergeron-model-based offline setting method is proposed. The wavefront-count threshold is determined from submarine-cable traveling-wave propagation characteristics and terminal boundary conditions, providing a clear physical basis for protection setting. When these conditions change, the setting calculation can be repeated. For the 45 scanned cases considered in this study, the offline computation time is reduced by approximately 91.38% compared with the estimated PSCAD/EMTDC scanning time.
(2) A VMD–TEO wavefront extraction procedure is developed for measured traveling waves. VMD modes are selected according to their energy contribution, wavefront characterization capability, and wavefront-counting performance under the tested noise condition, and the selected modes are linearly superimposed to reconstruct the traveling-wave feature signal. The reconstructed signal is then mapped into an energy sequence by the Teager energy operator (TEO) to highlight transient energy changes associated with wavefront arrivals. The theoretical wavefront counts obtained from the Bergeron model are evaluated offline to determine a unified fixed threshold for online comparison.
(3) A single-ended protection scheme using only local measurements is established. Internal/external fault discrimination is performed using a 2 ms post-startup observation window. Case study results demonstrate correct operation at all tested internal fault locations along the protected line, including faults with fault resistances up to 300 Ω, while the protection remains inoperative for the tested reverse external faults.

2. Theoretical Basis

2.1. Fixed-Parameter Bergeron Equivalent Circuit

The Bergeron method is a technique that analyzes the multiple reflections/refractions of waves using the concept of mixed waves, and its essence remains the solution to the wave equation [29]. In this study, a fixed-parameter Bergeron model is used to construct an approximate fault-component network for offline setting, thereby improving setting efficiency. Based on the characteristic impedance, propagation delay, history sources, and terminal boundary relations, the propagation, reflection, and refraction of fault traveling waves are represented recursively. The model-predicted wavefront arrival sequence and wavefront count within the prescribed observation window are then obtained for different fault locations and fault resistances. A physical mapping from cable parameters, propagation delay, and terminal boundary conditions to the wavefront count is, thus, established, providing the theoretical basis for offline determination of Nset. In this study, the 1-mode characteristic impedance and propagation delay used in the fixed-parameter Bergeron model are evaluated at 2 kHz, selected as a representative frequency in the lower kHz traveling-wave range relevant to remote high-resistance faults.
The protection setting threshold obtained from this model is then validated using a detailed PSCAD/EMTDC simulation model.
Transmission line: Let the wave impedance and length of Line-x in Figure 1 be ZMN and lx, respectively.
Figure 1. Transmission line model.
According to the traveling-wave relation, the voltage–current mixed quantities must include characteristic-impedance scaling. A wave launched from terminal M at t − tx reaches terminal N at t, where tx = lx/vx is the propagation time of Line-x and vx is the traveling-wave velocity. The terminal quantities are, therefore, related as follows:
U mn ( t − t x ) = u m ( t ) − Z mn i mn ( t ) U mn ( t − t x ) = u n ( t − t x ) + Z mn i nm ( t − t x )
where imn and inm are the terminal currents flowing into the line from terminals M and N, respectively, and Umn is the equivalent history voltage sources at terminals M [30]. Here, the equivalent history voltage source is formed by the delayed terminal voltage and the characteristic-impedance-scaled current. The equivalent calculation circuit viewed from terminal M is shown in Figure 2a. To maintain a consistent time scale for the history quantities, Equation (1) above is delayed by tx and rearranged as follows:
Z mn i mn ( t − t x ) = u m ( t − t x ) − U mn ( t − 2 t x )
Figure 2. Equivalent calculation circuit of transmission line. (a) M side equivalent. (b) N side equivalent.
By terminal duality, the corresponding expression at terminal N is obtained:
Z m n i n m ( t − t x ) = u n ( t − t x ) − U n m ( t − 2 t x )
Substituting Equation (3) into (1) eliminates the characteristic-impedance-scaled current term and yields the recursive relation for the history source at terminal M:
U mn ( t − t x ) = 2 u n ( t − t x ) − U nm ( t − 2 t x )
By terminal duality, the corresponding expression and equivalent circuit viewed from terminal N are obtained as shown in (5) and Figure 2b.
U nm ( t − t x ) = 2 u m ( t − t x ) − U mn ( t − 2 t x )
Equations (4) and (5) give the recursive relations for the equivalent history voltage sources at terminals M and N, respectively. The history sources are updated at each time step according to the line propagation delay and terminal boundary conditions, providing a discrete-time basis for the subsequent traveling-wave calculations.
Transformer: Based on the YNd transformer winding connection and magnetic circuit characteristics, for the 1-mode network, both the primary and secondary sides of the transformer have conductive paths, with tight magnetic coupling. In the reduced transient model, this is represented by the series combination of the primary leakage inductance and the referred secondary leakage inductance. For the 0-mode network, the grounded primary neutral provides a zero-sequence current path, while the delta-connected winding permits internal zero-sequence circulating current but blocks its direct transfer to the external secondary network. For the system and the prescribed 2 ms observation window considered in this study, the 1-mode component retains the dominant wavefront information used by the proposed protection. Therefore, the reduced transformer model and the subsequent protection criterion are formulated using the 1-mode quantities.
For the reduced 1-mode equivalent calculation, all secondary-side quantities are expressed on the same reference base as the primary-side quantities. The transformer is represented by the equivalent primary- and secondary-side leakage inductances Lpm and Lsm, whereas the magnetizing branch and winding losses are not explicitly included in the reduced offline-setting model [31]. The two leakage-inductance branches are connected through the internal calculation node u1(t), as shown in Figure 3. The voltage–current relations of the two equivalent leakage-inductance branches are written as:
u ( t ) = L T d i ( t ) d t L T = L pm 0 0 L sm  
Figure 3. Equivalent calculation circuit of the transformer.
In this reduced model, Lpm and Lsm are the equivalent primary- and secondary-side leakage inductances referred to as the common voltage base. Their sum corresponds to the total referred short-circuit leakage inductance. For the numerical implementation in this study, the total referred short-circuit leakage inductance Lσ is equally allocated to the two branches, i.e., Lpm = Lsm = Lσ/2.
Integrating Equation (6) from t − δt to t:
i ( t ) = i ( t − δ t ) + L T − 1 ∫ t − δ t t u ( τ ) d τ
u ( t ) = u p ( t ) − u 1 ( t ) u 1 ( t ) − u s ( t ) i ( t ) = i p ( t ) i s ( t )  
Applying trapezoidal integration to (7) gives ∫ t − δ t t u τ d τ ≈ δ t 2 u t + u t − δ t . Equation (7) can, therefore, be written in the following companion form [30].
i ( t ) = G T u ( t ) + I T ( t − δ t ) , I T ( t − δ t ) = i ( t − δ t ) + G T u ( t − δ t )
Here, u(t) is the voltage-drop vector of the two leakage-inductance branches, i(t) is the corresponding branch-current vector, and IT(t−δt) is the history-current vector. Under the current-reference directions shown in Figure 3, KCL at the internal node u1(t) gives ip(t) = is(t).
G T = δ t 2 L T − 1 = G p 0 0 G s G p = δ t 2 L pm ,   G s = δ t 2 L sm  
At the preceding time step, the first relation in (9) becomes:
i ( t − δ t ) = G T u ( t − δ t ) + I T ( t − 2 δ t )
I T ( t − δ t ) = I T ( t − 2 δ t ) + 2 G T u ( t − δ t )
Equation (11) represents the companion relation at the preceding time step. Substituting (11) into the second relation of (9) eliminates i(t − δt) and yields the history-current recursion in (12). Expanding (9) and (12) for the primary- and secondary-side leakage-inductance branches gives the following scalar relations:
i p ( t ) = G p u p ( t ) − u 1 ( t ) + I Tp ( t − δ t ) .
For the primary-side leakage-inductance branch, the corresponding history-current recursion is
I Tp ( t − δ t ) = I Tp ( t − 2 δ t ) + 2 G p u p ( t − δ t ) − u 1 ( t − δ t )
GT is the companion–conductance matrix obtained by trapezoidal discretization, and IT(t − δt) is the corresponding history-current vector. The numerical integration time step is δt = 10 μs.
Based on (9), (10) and (12), the corresponding discrete-time companion circuit is shown in Figure 3.
Similarly, the secondary-side leakage-inductance branch is expressed as:
i s ( t ) = G s u 1 ( t ) − u s ( t ) + I Ts ( t − δ t )
and its history-current recursion is:
I Ts ( t − δ t ) = I Ts ( t − 2 δ t ) + 2 G s u 1 ( t − δ t ) − u s ( t − δ t )
Equations (13)–(16) are the scalar expansions of the vector companion relations in (9) and (12).
Initial fault component: For a three-phase LFAC transmission system, electromagnetic coupling makes direct phase-domain solution of the initial transient process inconvenient. The Karrenbauer transform is, therefore, used for modal decoupling:
u m 0 ( t ) u m 1 ( t ) u m 2 ( t ) = 1 3 1 1 1 1 − 1 0 1 0 − 1 u ma ( t ) u mb ( t ) u mc ( t )
In the equation, uma, umb, umc, ima, imb, and imc represent the three-phase voltages/currents at node M; um0, um1, um2, im0, im1, and im2 represent the 0-mode, 1-mode, and 2-mode voltages/currents at node M.
Compared to the 1-mode and 2-mode components, the zero-mode component is only generated during ground faults. Additionally, the zero-mode component experiences greater attenuation in submarine cables due to the influence of the earth return path and the armor layer, which can affect the sensitivity of protection. Therefore, under the premise of improving protection sensitivity, this study selects the 1-mode component to construct the protection.
Taking the A-phase grounding fault in Figure 4 as an example, assume that at time t = t0, an A-phase grounding fault f occurs at a certain point on the transmission line. Correspondingly, the phase-domain boundary conditions at the fault point are:
u fa = − U nor + R g i fa i fb = 0 i fc = 0
where Unor is the A-phase rated voltage. ufa and ifa are the A-phase voltage and current at the fault point. Using Equation (17), the above equation is transformed into the modal domain:
u f 1 + u f 2 + u f 0 = − U nor + 3 i f 1 R g i f 1 = i f 2 = i f 0
Figure 4. A-phase ground fault.
According to Equation (19), the modal-domain equivalent circuit of the fault point can be drawn:
Based on Figure 5, the equivalent calculation circuit for the initial fault component of mode 1 can be constructed:
Figure 5. Modal-domain equivalent circuit of A-phase grounding fault.
In Figure 6, ZMN is the wave impedance of Line-MN, and Rlin represents the fault resistance together with the equivalent contribution of the 0-mode and 2-mode networks:
R lin = Z 0 + Z 2 2 + 3 R g
where Z0 and Z2 are the 0-mode and 2-mode wave impedances of Line-MN. In the adopted approximation, the 0-mode and 2-mode networks are omitted and R1in is simplified using (21).
R lin = 3 R g
Figure 6. Equivalent calculation circuit for A-phase grounding fault.

2.2. Equivalent Calculation Circuit of the LFAC System

An M3C-based flexible LFAC submarine-cable transmission system with a rated frequency of 16.67 Hz is established in PSCAD/EMTDC. The M3C has a rated capacity of 960 MVA, and the grid on the power-frequency side has a rated voltage of 525 kV. The submarine cable is 120 km long, and its 1-mode wave impedance is 41.53 Ω, as shown in Figure 7. When a single-phase grounding fault occurs at f2 with fault resistance Rg, the LFAC fault-component equivalent circuit can be constructed in Figure 7. The node-voltage equations are then formulated to solve u1(t)–u5(t).
u 1 ( t ) u 2 ( t ) u 3 ( t ) u 4 ( t ) u 5 ( t ) = Y - 1 ⋅ I T 1 1 ( t − Δ t ) − I T 1 11 ( t − Δ t ) U 2 f ( t − t l ) Z MN − I T 1 1 ( t − Δ t ) U f 2 ( t − t l ) Z MN − U nor ε ( t − t l ) 3 R g + U f 4 ( t − t l ) Z MN U 4 f ( t − t l ) Z MN − I T 2 1 ( t − Δ t ) I T 2 1 ( t − Δ t ) − I T 2 11 ( t − Δ t )
Y = δ t 2 L pm + δ t 2 L sm − δ t 2 L pm 0 0 0 − δ t 2 L pm δ t 2 L pm + 1 Z MN 0 0 0 0 0 2 Z MN + 1 3 Rg 0 0 0 0 0 1 Z MN + δ t 2 L pn − δ t 2 L pn 0 0 0 − δ t 2 L pn δ t 2 L pn + δ t 2 L sn
Figure 7. LFAC fault-component equivalent circuit.
The history current and voltage sources on the right-hand side of (22) are defined as follows:
I T pm ( t − δ t ) − I T sm ( t − δ t ) U 2 f ( t − t l ) Z MN − I T pm ( t − δ t ) U f 2 ( t − t l ) Z MN − U nor ε ( t − t l ) 3 R g + U f 4 ( t − t l ) Z MN U 4 f ( t − t l ) Z MN − I T pn ( t − δ t ) I T pn ( t − δ t ) − I T sn ( t − δ t )
The incremental history sources in the fault-component network are initialized to zero. Here, δt = 10 μs (fs = 100 kHz), and tl = l/v1. The solutions of (22)–(24) give the incremental voltage and current at each node, from which the quantities at protection point p are obtained:
u 1 T ( t ) = u 1 p nor + u 2 ( t ) , i 1 T ( t ) = i 1 p nor + u 2 ( t ) − U 2 f ( t − t l ) Z MN
In (25), the added terms are the pre-fault steady-state 1-mode voltage and current at protection point p.
For a lossless uniform transmission line, the traveling wave is represented by the superposition of forward and backward components. The 1-mode backward voltage traveling wave at p is extracted using (26).
u 1 T f = u 1 T ( t ) − Z MN i 1 T ( t ) 2

3. Methodology

3.1. Protection Starting Criterion

When a fault-generated traveling wave reaches the protection installation point, the 1-mode voltage changes abruptly. The absolute adjacent-sample voltage increment is, therefore, used as the starting criterion:
Δ U 1 m t = U 1 m t − U 1 m t − 1 f s ≥ k rel , start U 1 , set
where U1m is the measured 1-mode voltage, U1,set is the 1-mode voltage increment obtained for the weakest forward internal fault, and krel,start is the reliability coefficient. When (27) is satisfied, the corresponding time is recorded as the startup-criterion triggering time tf, which is used as the beginning of the subsequent data observation window, and the main protection is enabled.

3.2. Main Protection Criterion

3.2.1. Measured Waveform Preprocessing

After startup, the 1-mode voltage and current samples over the half-open interval [tf, tf + Tw) are extracted, where Tw = 2 ms. At the sampling frequency fs = 100 kHz, the observation window contains Nw = fs Tw = 200 samples. The 1-mode backward voltage traveling wave is calculated using (28).
U 1 mf = U 1 p ( t ) − Z MN I 1 p ( t ) 2 , t ∈ t f , t f + T w
In (28), U1p and I1p are the 1-mode voltage and current at protection point p, respectively, and ZMN is the wave impedance of the protected line.
To emphasize abrupt wavefront changes, the original traveling-wave signal is differentiated to obtain U1mf,diff(t):
U 1 m f _ diff ( t ) = ∇ U 1 m f ( t )
The differential signal is then standardized to place different cases on a common scale:
U 1 M f ( t ) = U 1 m f _ diff ( t ) − μ σ
where μ and σ are the mean and standard deviation of the differential signal over the Tw = 2 ms half-open observation window, respectively.

3.2.2. Wavefront Criterion Construction

For a reverse external fault, the transformer and adjacent bus attenuate the fault-related transient components of the backward voltage traveling wave reaching the protection point. Internal faults produce more detectable wavefronts within the selected window because of repeated reflections between the fault point and the measurement terminal. The number of detected wavefronts can, therefore, be used to distinguish the tested internal and reverse external faults.
The proposed criterion requires two operations: separating fault-informative transient features from the background components associated with M3C operation and counting the corresponding wavefront arrivals. VMD is used for modal decomposition and reconstruction, and TEO is used for energy mapping and wavefront marking. The essential formulations and their use in the proposed protection are summarized below.
VMD: VMD decomposes a non-stationary input x(t) into K band-limited intrinsic mode functions (IMFs), denoted by uk_IMF(t), with center frequencies ωk by minimizing their total estimated bandwidth [32]:
min { u k _ IMF } , { ω k } ∑ K ∂ t δ ( t ) + j π t ∗ u k _ IMF ( t ) e − j ω k t 2 2 s . t .   ∑ K u k _ IMF ( t ) = x ( t )
where uk_IMF denotes the k-th modal component, ωk is its center frequency, δ(t) is the Dirac delta function, and * denotes convolution. Introducing the quadratic penalty factor α and Lagrange multiplier λ(t), the constrained problem is solved by the alternating direction method of multipliers (ADMM). The modal component and center frequency are updated using (32) and (33), respectively.
u ^ k _ IMF n + 1 ( ω ) = x ^ ( ω ) − ∑ i ≠ k u ^ i _ IMF n ( ω ) + λ ^ n ( ω ) / 2 1 + 2 α ω − ω k n 2
ω k n + 1 = ∫ 0 ∞ ω u ^ k _ IMF n + 1 ( ω ) 2 dω ∫ 0 ∞ u ^ k _ IMF n + 1 ( ω ) 2 dω
The number of modes is set to K = 5, the penalty factor to α = 2000, and the maximum number of iterations to 500. The absolute and relative convergence tolerances are set to 5 × 10−6 and 5 × 10−3, respectively, while all other parameters use the default settings of the VMD function. Based on the energy contribution, wavefront characterization capability, and performance under the tested noise condition, u4_IMF and u5_IMF are selected and linearly superimposed to reconstruct the traveling-wave feature signal:
x ^ ( t ) = u 4 _ IMF ( t ) + u 5 _ IMF ( t )
The reconstructed signal suppresses part of the non-target high-frequency content while preserving the main abrupt features associated with fault-wavefront arrivals, thereby providing an effective input for subsequent wavefront detection and counting. The rationale for this mode selection and the effects of different mode combinations on protection performance are further analyzed in Section 5.1.
TEO: For a discrete signal x ^ n , the TEO is defined by (35) [33]. For a narrow-band amplitude-modulated/frequency-modulated (AM-FM) component, its output is related to the product of the squared instantaneous amplitude and squared instantaneous angular frequency, making it sensitive to abrupt changes in the energy of transient components.
ψ [ x ^ ( n ) ] = x ^ 2 ( n ) − x ^ ( n − 1 ) x ^ ( n + 1 ) E ( n ) = ψ [ x ^ ( n ) ] ,       n = 2 , … , N − 1
where E(n) is the absolute TEO magnitude. Its qualified local maxima are identified as wavefront arrivals. Applying TEO to the VMD-reconstructed signal produces local energy peaks when wavefronts arrive; the qualified local maxima are, therefore, counted as detected wavefronts.
The same wavefront extraction procedure is applied to the offline Bergeron waveform and the online measured 1-mode backward voltage traveling wave. The selected informative modal components are reconstructed according to (34), yielding U ^ H(t).
TEO is then applied to the reconstructed signal. The discrete energy sequence of the reconstructed 1-mode backward voltage traveling wave is given by (35), yielding E(n). Qualified local maxima satisfying the peak-height and peak-prominence conditions are counted as wavefronts, and the total count N over the Tw = 2 ms observation window is calculated using Equation (36).
N = ∑ n = n 0   n 0 + N W − 1 ⟦ [ E ( n ) > E ( n − 1 ) , E ( n ) > E ( n + 1 ) , E ( n ) > E set , P ( n ) > P set ] E set = 10 − 4 E ¯
Here, ⟦(·) denotes the indicator function, P(n) denotes the prominence of the candidate local maximum at sample n, and E ¯ denotes the mean TEO energy within the observation window. In the implemented peak-detection procedure, Pset is adaptively determined from the maximum and mean TEO energies within the observation window, following the locally adaptive Teager-energy thresholding principle in [34], using fixed empirical coefficients. For online measurements, the main protection operates according to Equation (37).
N M ≥ N set
where NM is the measured wavefront count and Nset is the fixed wavefront-count threshold. The fault is classified as internal when NM ≥ Nset, and a trip command is issued; otherwise, it is classified as external, and no trip command is issued.
The reliability coefficient krel provides a margin between the theoretical and measured wavefront counts. For each offline scan case, a candidate threshold is obtained, and the most adverse result is selected as the unified setting:
N set = min q k rel N T , q = 2
where NT,q is the theoretical wavefront count obtained from the Bergeron waveform for the offline case. Fault location and fault resistance are used only for offline scanning; the minimum candidate value gives the fixed online threshold Nset = 2. Figure 8 presents the offline wavefront-count and setting results.
Figure 8. Offline wavefront-count map.
The values in Figure 8 are theoretical wavefront counts NT obtained from the ideal Bergeron responses, whereas the measured counts NM are extracted from the PSCAD/EMTDC signals after VMD–TEO processing. The two counts may differ by one to three because wavefront overlap, partial cancellation among propagation paths, and finite sampling resolution can alter the detectability of closely spaced TEO peaks. The reliability coefficient krel accounts for this model-to-simulation discrepancy, and the resulting setting Nset = 2 is verified by the tested cases to maintain external-fault security and internal-fault dependability.
The overall procedure is shown in Figure 9.
Figure 9. Flowchart of the proposed protection.
In the offline part, the Bergeron model scans the specified fault locations and fault resistances, applies the same VMD–TEO counting procedure to the theoretical waveforms, and determines the unified threshold Nset = 2. Online, the local device continuously samples three-phase voltage and current, obtains the 1-mode quantities through the Karrenbauer transform, and evaluates the starting criterion. Once started, it extracts the 2 ms 1-mode backward voltage traveling-wave segment and performs differentiation, standardization, VMD reconstruction, and TEO energy mapping. The qualified TEO peaks give the measured count NM over the Tw = 2 ms observation window.
The fixed comparison NM ≥ Nset identifies an internal fault and issues a trip command; otherwise, the protection remains inoperative. Fault location and fault resistance are not online inputs.

4. Validation

An electromagnetic-transient model is established in PSCAD/EMTDC to validate the proposed method. The protection sampling frequency is 100 kHz, the simulation step is 0.01 ms, and protection point p is located at the sending end of the LFAC cable. After startup, the 2 ms 1-mode backward voltage traveling-wave segment is processed using the method in Section 3, and qualified TEO peaks are counted as wavefronts.

4.1. Protection Settings

4.1.1. Startup Criterion

The reference voltage increment is determined from the weakest tested forward internal fault: a single-phase-to-ground (1φ-G) fault with Rg = 300 Ω at dx = 0.9. The corresponding 1-mode voltage increment is ΔU1m = 10.52 kV, which is assigned to U1,set. With krel,start = 0.8, the resulting startup threshold is 8.416 kV. The waveform is shown in Figure 10.
Figure 10. Startup waveform (1φ-G, 300 Ω, dx = 0.9).
For clearer visualization of the waveform characteristics near the boundaries of the processing window, all waveforms are plotted over a slightly extended time interval. This extension is used solely for visualization, whereas all subsequent calculations are performed using the fixed Tw = 2 ms window defined in (28).

4.1.2. Main Protection Criterion

The Bergeron model is evaluated offline for the prescribed fault locations and fault resistances. For each case, the theoretical wavefront count is converted to a candidate setting using (38). The most adverse candidate is obtained for the metallic grounding fault at dx = 0.9; with krel = 0.7, ⌊0.7 × 3⌋ = 2. Therefore, the online protection uses the unified fixed threshold Nset = 2 for all cases, without fault-location or fault-resistance inputs.

4.2. Performance Validation

4.2.1. Security Under External Faults

At t = 2 s, a single-line-to-ground fault (1φ-G) occurs at f1 on the M3C/transformer side. This is a reverse external fault for protection p, which should remain inoperative. In the simulations, a fault resistance of 0.01 Ω is used to approximate metallic faults.
Using (28), the 1-mode backward traveling-wave segment within the 2 ms observation window after the initial wavefront arrival is extracted. The signal is preprocessed using (29) and (30), and the TEO results are shown in Figure 11.
Figure 11. TEO wavefronts (reverse 1φ-G).
Using (36), the measured wavefront count is NM = 0. Since NM < Nset = 2, the protection remains inoperative, consistent with the expected response for a reverse external fault.

4.2.2. Sensitivity Under Internal Faults

Metallic grounding fault. When a single-phase metallic grounding fault occurs at dx = 0.9 from the sending end, the measured 1-mode voltage detected by p is shown in Figure 12.
Figure 12. 1-mode voltage (1φ-G, 0.01 Ω, dx = 0.9).
The starting criterion operates at tf = 2.00072 s. The 1-mode voltage and current samples in the subsequent 2 ms window are extracted, and the 1-mode backward voltage traveling wave is calculated using (28), as shown in Figure 13.
Figure 13. Backward traveling wave (1φ-G, 0.01 Ω, dx = 0.9).
After preprocessing using (29) and (30), the signal in Figure 14 is processed by VMD and TEO, producing Figure 15 and Figure 16. The measured count is NM = 2. With the fixed threshold Nset = 2, NM ≥ Nset = 2, the case is identified as an internal fault, and a trip command is issued.
Figure 14. Preprocessed traveling wave (1φ-G, 0.01Ω, dx = 0.9).
Figure 15. VMD reconstruction (1φ-G, 0.01 Ω, dx = 0.9).
Figure 16. TEO wavefronts (1φ-G, 0.01 Ω, dx = 0.9).
When a single-phase metallic grounding fault occurs near the sending end (dx = 0.1), the measured 1-mode voltage is shown in Figure 17.
Figure 17. 1-mode voltage (1φ-G, 0.01 Ω, dx = 0.1).
The starting criterion operates at tf = 2.00008 s. The 1-mode voltage and current samples in the subsequent 2 ms window are extracted, and the 1-mode backward voltage traveling wave is calculated using (28), as shown in Figure 18.
Figure 18. Backward traveling wave (1φ-G, 0.01 Ω, dx = 0.1).
After preprocessing using (29) and (30), the signal in Figure 19 is processed by VMD and TEO, producing Figure 20 and Figure 21. The measured count is NM = 12. Since NM ≥ Nset = 2, the protection identifies an internal fault and trips.
Figure 19. Preprocessed traveling wave (1φ-G, 0.01 Ω, dx = 0.1).
Figure 20. VMD reconstruction (1φ-G, 0.01 Ω, dx = 0.1).
Figure 21. TEO wavefronts (1φ-G, 0.01 Ω, dx = 0.1).
High-resistance grounding fault. When a single-phase grounding fault with Rg = 300 Ω occurs at dx = 0.9, the starting criterion operates at tf = 2.00072 s. The 1-mode voltage and current samples in the subsequent 2 ms window are extracted, and the 1-mode backward voltage traveling wave is calculated using (28), as shown in Figure 22.
Figure 22. Backward traveling wave (1φ-G, 300 Ω, dx = 0.9).
After preprocessing using (29) and (30), the waveform in Figure 23 is used as the VMD input. The reconstructed signal and TEO result are shown in Figure 24 and Figure 25.
Figure 23. Preprocessed traveling wave (1φ-G, 300 Ω, dx = 0.9).
Figure 24. VMD reconstruction (1φ-G, 300 Ω, dx = 0.9).
Figure 25. TEO wavefronts (1φ-G, 300 Ω, dx = 0.9).
The measured count is NM = 6. Since NM ≥ Nset = 2, the protection identifies an internal fault and trips.
When a single-phase grounding fault with Rg = 300 Ω occurs near the sending end (dx = 0.1), the starting criterion operates at tf = 2.00008 s. The 1-mode voltage and current samples in the subsequent 2 ms window are extracted, and the 1-mode backward voltage traveling wave is calculated using (28), as shown in Figure 26.
Figure 26. Backward traveling wave (1φ-G, 300 Ω, dx = 0.1).
After preprocessing using (29) and (30), the waveform in Figure 27 is processed by VMD and TEO, producing Figure 28 and Figure 29. The measured count is NM = 7. Since NM ≥ Nset = 2, the protection identifies an internal fault and trips.
Figure 27. Preprocessed traveling wave (1φ-G, 300 Ω, dx = 0.1).
Figure 28. VMD reconstruction (1φ-G, 300 Ω, dx = 0.1).
Figure 29. TEO wavefronts (1φ-G, 300 Ω, dx = 0.1).

4.2.3. Practical Implementation and Timing

Three-phase voltages and currents are synchronously sampled by the local protection device, and the 1-mode voltage and current are obtained through the Karrenbauer transform. The startup time is taken as the starting point for online fault discrimination. After startup, an initial transient data window of Tw = 2 ms is extracted. Traveling-wave feature extraction and wavefront counting are then performed using the VMD–TEO procedure described above, and the measured wavefront count NM is compared with the setting threshold Nset to distinguish internal from external faults. Let talg denote the computation time of the online discrimination algorithm. The protection decision time is:
t dec = t f + T w + t alg
Taking the fault inception time t0 as the reference, the startup delay is defined as Tstart = tf − t0. When the input/output and trip-circuit delay TI/O of the protection device and the circuit-breaker opening time TCB are also considered, the total time from fault inception to fault clearance is expressed as
T clear = T start + T w + t alg + T I / O + T CB
The 2 ms interval used in this study is the criterion data window after startup and represents the time scale required to acquire the initial fault-transient information. Device-level protection operation and final fault clearance additionally depend on the online algorithm implementation, protection trip circuit, and switching equipment.
To evaluate the online computational burden of the proposed method, a single-phase metallic grounding fault at xf = 0.9l is selected. The sampled simulation data are fed into the complete VMD–TEO online discrimination program, which is executed 100 times on a computer equipped with an AMD Ryzen 7 8700G processor, 31.22 GB of physical memory, Windows 10 64-bit, and MATLAB R2021b. The mean, 95th-percentile, and maximum execution times are 29.565 ms, 30.986 ms, and 34.074 ms, respectively, with most of the computational burden arising from VMD. Excluding the startup delay and protection-device input/output delay, the current MATLAB prototype requires an average of approximately 31.565 ms from startup to protection decision.
Under low-frequency operation, fundamental-frequency phasor-based protection is directly affected by the longer fundamental period. One cycle lasts 50 ms at 20 Hz and approximately 60 ms at 16.67 Hz. A half-cycle or shorter data window can reduce the phasor estimation time but requires a tradeoff among operating speed, transient measurement error, and the suppression of harmonics and decaying DC components. In contrast, the proposed criterion uses broadband transient traveling-wave information during the initial fault stage and requires only 2 ms of post-startup transient data to construct the internal/external fault criterion, without waiting for complete fundamental-frequency phasor formation. This window corresponds to approximately 4.0% and 3.3% of one fundamental cycle at 20 Hz and 16.67 Hz, respectively, demonstrating the suitability of transient-based protection for rapid fault identification in LFAC transmission lines from the perspective of fault-information acquisition time.
From the perspective of protection–control coordination, protection discrimination, converter fault ride-through control, and fault isolation after an LFAC system fault are interrelated processes operating on different time scales. Existing studies on fault ride-through control for M3C-based LFAC transmission show that, after a low-frequency-side fault occurs, arm overcurrents can be rapidly suppressed by dynamically adjusting the low-frequency-side modulation-voltage reference, followed by voltage and power recovery over a time scale of several hundred milliseconds [35].

4.2.4. Performance Assessment

Additional PSCAD/EMTDC cases are evaluated at f1 and f2 for the fault locations and fault resistances listed in Table 1. The condition at f1 is a reverse external single-phase-to-ground (1φ-G) fault, whereas the conditions at f2 are internal 1φ-G faults. Table 1 summarizes the measured wavefront counts and trip decisions; √ denotes operation and × denotes non-operation. Protection p operates for all tested internal single-phase grounding faults, including cases with Rg = 300 Ω, and remains inoperative for the tested reverse external fault.
Table 1. Protection performance assessment.

5. Discussion

5.1. VMD Reconstruction Mode Selection

The selection of reconstruction modes after VMD directly affects the subsequent enhancement of fault wavefronts by TEO. Previous studies show that the key issues in VMD applications include not only decomposition-parameter settings but also the selection of effective modes matched to the target features. For partial-discharge signal denoising, Dhandapani et al. distinguished noise-dominated modes from signal-dominated modes using the mutual information between the phase spectra of adjacent modes and further performed mode classification and signal reconstruction using dispersion entropy [36]. For traveling-wave protection, mode selection is also constrained by the frequency characteristics of the propagation channel. Traveling-wave energy attenuates with propagation distance in cables, and the attenuation varies among frequency components [37]. Therefore, the retention of internal-fault wavefronts and the suppression of non-target transients from reverse external faults are used as the direct criteria for reconstruction mode selection, while the modal energy distribution and wavefront-counting results under the tested noise condition are also considered.
For the three representative cases, the sums of the individual energy shares of u 4 IMF and u 5 IMF are 33.85%, 53.25%, and 99.90%, respectively, as listed in Table 2. For the remote 300 Ω internal fault, the sum of the individual energy shares of the two selected modes is 33.85%, while a higher sum of the individual energy shares of the two selected modes is obtained for the close-in metallic internal fault.
Table 2. Individual modal energy shares, their sums, and wavefront counts for different reconstruction mode combinations.
From the perspective of propagation characteristics, higher-frequency traveling-wave components experience more severe attenuation in cables, and their amplitudes and edge features become more susceptible to distortion as the propagation distance increases [37]. VMD–TEO studies on overhead-cable hybrid lines also show that traveling-wave frequency components and their propagation characteristics directly affect wavefront-arrival-time extraction, requiring effective transient components to be selected according to frequency-dependent propagation characteristics [38]. For the submarine cable considered in this study, the higher-frequency modes enhance local abrupt changes but are more sensitive to propagation attenuation, terminal frequency response, and measurement noise. In contrast, the frequency bands of the selected modes retain the major transient changes associated with internal faults while suppressing high-frequency oscillations caused by external faults.
To further determine the reconstruction mode combination used for subsequent TEO-based wavefront extraction, 76 dB additive white Gaussian noise is independently added to the instantaneous three-phase voltage and current samples acquired at the protection point. Under the same noisy inputs, the two reconstruction schemes are compared in terms of their ability to retain effective internal-fault wavefronts and suppress non-target peaks caused by reverse external faults. The signal-to-noise ratio is defined as 10 log 10 P s P n , where Ps and Pn denote the average powers of the input signal and the added noise, respectively. The reconstructed waveforms under noise for the remote high-resistance internal fault, close-in metallic internal fault, and reverse external fault are shown in Figure 30, Figure 31 and Figure 32.
Figure 30. Reconstructed waveforms for different mode combinations at 76 dB SNR (1φ-G, 300 Ω, dx = 0.9).
Figure 31. Reconstructed waveforms for different mode combinations at 76 dB SNR (1φ-G, 0.01 Ω, dx = 0.1).
Figure 32. Reconstructed waveforms for different mode combinations at 76 dB SNR (reverse 1φ-G).
As shown in Figure 33, Figure 34 and Figure 35, the u 1 IMF and u 2 IMF combination produces wavefront counts of 5, 12, and 7 for the remote high-resistance internal fault, close-in metallic internal fault, and reverse external fault, respectively. The selected reconstruction combination yields corresponding counts of 6, 12, and 0. With the fixed threshold Nset = 2, the former produces seven non-target wavefronts during the reverse external fault, leading to an incorrect internal-fault decision. In contrast, the latter retains 6 and 12 effective wavefronts for the two internal faults, respectively, while suppressing the wavefront count of the reverse external fault to 0.
Figure 33. TEO wavefront detection results for different mode combinations at 76 dB SNR (1φ-G, 300 Ω, dx = 0.9).
Figure 34. TEO wavefront detection results for different mode combinations at 76 dB SNR (1φ-G, 0.01 Ω, dx = 0.1).
Figure 35. TEO wavefront detection results for different mode combinations at 76 dB SNR (reverse 1φ-G).
Based on the above results, u4_IMF and u5_IMF are selected to construct the TEO input signal. This combination retains sufficient fault-related transient components and effective wavefronts for remote high-resistance faults, preserves the major wavefronts for close-in internal faults, and effectively suppresses non-target peaks caused by reverse external faults under the same noisy conditions. It, therefore, provides better discrimination between useful internal-fault information and external-fault disturbances.

5.2. Performance Validation for Different Fault Types

To evaluate the applicability of the proposed protection to different fault types, four additional metallic fault types—phase-to-phase (LL), two-phase-to-ground (LLG), three-phase (LLL), and three-phase-to-ground (LLLG)—are considered in addition to the original single-phase-to-ground faults.
When a phase-to-phase (2φ) fault occurs near the sending end (dx = 0.1), the signal is processed using the same preprocessing method and subsequently processed by VMD and TEO. The resulting TEO waveform is shown in Figure 36. The measured count is NM = 13. Since NM ≥ Nset = 2, the protection identifies an internal fault and trips.
Figure 36. TEO wavefronts (2φ, 0.01 Ω, dx = 0.1).
LLG fault. When a two-phase-to-ground (2φ-G) fault occurs near the sending end (dx = 0.1), the signal is processed using the same preprocessing method and subsequently processed by VMD and TEO. The resulting TEO waveform is shown in Figure 37. The measured count is NM = 13. With the fixed threshold NM ≥ Nset = 2, the case is identified as an internal fault, and a trip command is issued.
Figure 37. TEO wavefronts (2φ-G, 0.01 Ω, dx = 0.1).
LLL fault. When a three-phase (3φ) fault occurs near the sending end (dx = 0.1), using the same preprocessing method, the signal in Figure 38 is processed by VMD and TEO, producing Figure 39 and Figure 40. The measured count is NM = 13. With the fixed threshold NM ≥ Nset = 2, the case is identified as an internal fault and a trip command is issued.
Figure 38. Preprocessed traveling wave (3φ, 0.01 Ω, dx = 0.1).
Figure 39. VMD reconstruction (3φ, 0.01 Ω, dx = 0.1).
Figure 40. TEO wavefronts (3φ, 0.01 Ω, dx = 0.1).
LLLG fault. When a three-phase-to-ground (3φ-G) fault occurs near the sending end (dx = 0.1), after preprocessing, the signal in Figure 41 is processed by VMD and TEO, producing the reconstructed waveform and TEO result shown in Figure 42 and Figure 43. The measured count is NM = 13. With the fixed threshold NM ≥ Nset = 2, the case is identified as an internal fault, and a trip command is issued.
Figure 41. Preprocessed traveling wave (3φ-G, 0.01 Ω, dx = 0.1).
Figure 42. VMD reconstruction for 3φ and 3φ-G faults (0.01 Ω, dx = 0.1).
Figure 43. TEO wavefronts (3φ-G, 0.01 Ω, dx = 0.1).
As shown in Figure 42, the VMD-reconstructed waveforms for the 3φ and 3φ-G faults are nearly identical. The correlation coefficients of the phase-A currents and the derivatives of the backward voltage traveling waves for the two fault cases reach 0.999991 and 0.999998, respectively, while the corresponding peak-to-peak amplitudes of the backward traveling waves are 146.137 and 145.877. Under the balanced three-phase conditions considered, the zero-sequence components of both faults are negligible, and the common-point potential of the 3φ fault is naturally close to ground potential. Consequently, the additional grounding connection produces no appreciable zero-sequence current, making the 3φ and 3φ-G faults approximately electrically equivalent, as observed from the measurement terminal. Normalization preserves this inherent similarity. Since the proposed criterion relies on wavefront timing and counting, this equivalence does not affect the protection decision.
Therefore, under the system conditions considered in this study, the proposed wavefront-counting criterion with Nset = 2 is applicable to all tested multiphase fault types.

5.3. Validation for Different Submarine-Cable Lengths

To investigate the effects of line length on the wavefront count and protection setting, the baseline submarine-cable length is changed from 120 km to 100 km, while the system topology, terminal boundary conditions, per-unit-length cable parameters, and other simulation parameters remain unchanged. The same fixed 2 ms observation window is used for the 100 km cable model, and the offline scan is repeated for 45 combinations of fault location and fault resistance to determine the corresponding wavefront-count threshold.
According to Equation (38), NT,q is the theoretical wavefront count obtained from the Bergeron waveform for the offline case. Fault location and fault resistance are used only for offline scanning; the minimum candidate value gives the fixed online threshold Nset = 2. Figure 44 presents the offline wavefront-count and setting results.
Figure 44. Offline wavefront-count map for the 100 km submarine cable.
High-resistance grounding fault. When a single-phase grounding fault with 300 Ω occurs at xf = 90%l from the sending end, the signal measured at the protection point is preprocessed using Equations (28)–(30). The signal in Figure 45 is processed by VMD and TEO, producing Figure 46 and Figure 47. The measured count is NM = 4. With the fixed threshold Nset = 2, NM ≥ Nset = 2, the case is identified as an internal fault, and a trip command is issued.
Figure 45. Preprocessed traveling wave (1φ-G, 300 Ω, dx = 0.9).
Figure 46. VMD reconstruction (1φ-G, 300 Ω, dx = 0.9).
Figure 47. TEO wavefronts (1φ-G, 300 Ω, dx = 0.9).
Reverse external fault. With the remaining simulation parameters unchanged, a single-phase grounding fault is applied at f1 on the left side of the protected line. This is a reverse external fault for protection p, which should remain inoperative. The signal in Figure 48 is processed by VMD and TEO, producing Figure 49 and Figure 50.
Figure 48. Preprocessed traveling wave (reverse 1φ-G).
Figure 49. VMD reconstruction (reverse 1φ-G).
Figure 50. TEO wavefronts (reverse 1φ-G).
NM = 1 < Nset = 2; therefore, the protection remains inoperative.
Overall, the wavefront-counting criterion with Nset = 2 is validated for the tested fault types and cable lengths. The proposed fixed-parameter Bergeron model provides a physically interpretable offline setting method for LFAC submarine-cable protection. Once the line parameters, system topology, and terminal boundary conditions are specified, a fixed online threshold is obtained through offline scanning; the setting is recalculated when these conditions change significantly. For the 45 cases in Figure 8, the proposed method requires 938.99 s, whereas the PSCAD/EMTDC scanning time is estimated at approximately 10,890 s. Thus, the proposed offline setting requires only 8.62% of the estimated PSCAD/EMTDC time, corresponding to a 91.38% reduction, while retaining the physical interpretability of the setting process.

6. Conclusions

A single-ended traveling-wave main protection method is proposed for flexible LFAC submarine cables. A fixed-parameter Bergeron fault-component network establishes the physical relationship among cable parameters, propagation delay, terminal boundary conditions, and predicted wavefront counts, while the same VMD–TEO procedure as that used online determines the fixed threshold offline. Scanning 45 fault-location–resistance combinations gives a unified threshold of Nset = 2, with an estimated 91.38% reduction in setting computation time compared with PSCAD/EMTDC scanning. The online criterion requires no prior knowledge of fault location or fault resistance.
Considering the modal energy contribution, internal-fault wavefront retention, external-fault transient suppression, and performance under the tested noise condition, u4_IMF and u5_IMF are selected to construct the TEO input. At 76 dB SNR, the qualified wavefront counts for the remote high-resistance internal fault, close-in metallic internal fault, and reverse external fault are 6, 12, and 0, respectively.
At a 100 kHz sampling rate, all tested internal single-phase, multiphase, and 300 Ω high-resistance faults reach the fixed threshold, whereas the tested reverse external faults remain inoperative. Only local measurements and a 2 ms post-startup observation window are required, without waiting for fundamental-frequency phasor formation. The fixed-parameter Bergeron model used in this study is intended primarily for offline estimation of the wavefront-arrival sequence and the protection-setting threshold, rather than for reproducing the full frequency-dependent propagation characteristics of the submarine cable. Systematic validation of the offline setting procedure using frequency-dependent cable models, together with real-time digital simulation, hardware-in-the-loop testing, and practical measurement chains, will be pursued in future work.

Author Contributions

Conceptualization, C.L.; methodology, J.G., Y.X.; software, N.Y.; validation, N.Y.; formal analysis, N.Y.; investigation, N.Y.; resources, C.L.; data curation, Y.X.; writing—original draft preparation, Y.X.; writing—review and editing, N.T. (Ning Tong); visualization, N.T.; supervision, C.L.; project administration, C.L.; funding acquisition, C.L. All authors have read and agreed to the published version of the manuscript.

Funding

This work was supported by the Director’s Fund (2025) of the National Energy Deepwater Oil and Gas Engineering Technology R&D Center under Contract No. 202523858745.

Data Availability Statement

The datasets generated and/or analyzed during the current study are not publicly available due to privacy and confidentiality concerns but are available from the corresponding author on reasonable request.

Conflicts of Interest

Author Cong Liu and Jiangyan Guo were employed by CNOOC Research Institute Co., Ltd. The remaining authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.

References

  1. Lu, Y.; Chen, A.W.; Zhao, G.L.; Wang, X.L.; Xiang, N.W.; Bi, J.G. Low Frequency AC Transmission for Offshore Wind Power. In Proceedings of the 2024 27th International Conference on Electrical Machines and Systems (ICEMS), Fukuoka, Japan, 26–29 November 2024; pp. 3750–3756. [Google Scholar] [CrossRef] [Scilit]
  2. Taherzadeh, E.; Radmanesh, H.; Javadi, S.; Gharehpetian, G.B. Circuit breakers in HVDC systems: State-of-the-art review and future trends. Prot. Control Mod. Power Syst. 2023, 8, 38. [Google Scholar] [CrossRef] [Scilit]
  3. Ray, A.; Rajashekara, K. Electrification of Offshore Oil and Gas Production: Architectures and Power Conversion. Energies 2023, 16, 5812. [Google Scholar] [CrossRef] [Scilit]
  4. Ma, Z.; Ning, L.; Han, J. Research on the control strategy of multi-terminal low frequency transmission system for island power supply scenes. In Proceedings of the 2020 4th International Conference on HVDC (HVDC), Xi’an, China, 6–9 November 2020; pp. 616–621. [Google Scholar] [CrossRef] [Scilit]
  5. Liu, S.; Wang, X.; Ning, L.; Wang, B.; Lu, M.; Shao, C. Integrating Offshore Wind Power Via Fractional Frequency Transmission System. IEEE Trans. Power Deliv. 2017, 32, 1253–1261. [Google Scholar] [CrossRef] [Scilit]
  6. Dong, Y.; Zhan, C.; Hu, J.; Qiu, P.; Lin, Y.; Qiu, D.; Xu, H.; Pan, L.; Tian, J. A Flexible Low-Frequency AC Transmission System: Principles and Applications. IEEE Power Energy Mag. 2025, 23, 81–91. [Google Scholar] [CrossRef] [Scilit]
  7. Li, X.; Guo, J.; Bi, J.; Li, H. Development of 3 kV low-frequency induction voltage divider using two-stage excitation. High Volt. 2025, 10, 998–1009. [Google Scholar] [CrossRef] [Scilit]
  8. Ruddy, J.; Meere, R.; O’Donnell, T. Low Frequency AC transmission for offshore wind power: A review. Renew. Sustain. Energy Rev. 2016, 56, 75–86. [Google Scholar] [CrossRef] [Scilit]
  9. Meere, R.; Ruddy, J.; McNamara, P.; O’Donnell, T. Variable AC transmission frequencies for offshore wind farm interconnection. Renew. Energy 2017, 103, 321–332. [Google Scholar] [CrossRef] [Scilit]
  10. Xiang, X.; Fan, S.; Gu, Y.; Ming, W.; Wu, J.; Li, W.; He, X.; Green, T.C. Comparison of Cost-effective Distances for LFAC with HVAC and HVDC in Their Connections for Offshore and Remote Onshore Wind Energy. CSEE J. Power Energy Syst. 2021, 7, 954–975. [Google Scholar] [CrossRef] [Scilit]
  11. Dakic, J.; Cheah-Mane, M.; Gomis-Bellmunt, O.; Prieto-Araujo, E. Low frequency AC transmission systems for offshore wind power plants: Design, optimization and comparison to high voltage AC and high voltage DC. Int. J. Electr. Power Energy Syst. 2021, 133, 107273. [Google Scholar] [CrossRef] [Scilit]
  12. Tang, Y.; Zhang, Z.; Xu, Z. DRU Based Low Frequency AC Transmission Scheme for Offshore Wind Farm Integration. IEEE Trans. Sustain. Energy 2021, 12, 1512–1524. [Google Scholar] [CrossRef] [Scilit]
  13. Luo, J.; Zhang, X.-P.; Xue, Y.; Gu, K.; Wu, F. Harmonic Analysis of Modular Multilevel Matrix Converter for Fractional Frequency Transmission System. IEEE Trans. Power Deliv. 2020, 35, 1209–1219. [Google Scholar] [CrossRef] [Scilit]
  14. Lu, D.; Liu, Y.; Xie, J.; Wang, B.; Liao, Q. Multi-Layer Model Enabled Fault Location for Underground Cables in MMC-HVDC Grids Considering Distributed and Frequency Dependent Line Parameters. IEEE Trans. Power Deliv. 2022, 37, 3082–3096. [Google Scholar] [CrossRef] [Scilit]
  15. He, J.; Du, X.; Li, M.; Zhang, Y.; Zhang, J.; Wang, H. Non-Unit Protection Based on Transient Voltage Time-Frequency Characteristics for Offshore Flexible Low-Frequency Transmission Lines. IEEE Trans. Power Deliv. 2026, 41, 1325–1336. [Google Scholar] [CrossRef] [Scilit]
  16. Zhang, H.; Xiang, W.; Hong, Q.; Wen, J. Active phase control to enhance distance relay in converter-interfaced renewable energy systems. Int. J. Electr. Power Energy Syst. 2022, 143, 108433. [Google Scholar] [CrossRef] [Scilit]
  17. Yang, Z.; Liao, W.; Zhang, Q.; Bak, C.L.; Chen, Z. Fault Coordination Control for Converter-Interfaced Sources Compatible With Distance Protection During Asymmetrical Faults. IEEE Trans. Ind. Electron. 2023, 70, 6941–6952. [Google Scholar] [CrossRef] [Scilit]
  18. Dai, Y.; Shu, H.; Tang, Y.; Liu, H. Adaptability analysis of distance protection in flexible low frequency ac outgoing transmission line of wind power system. Results Eng. 2025, 28, 107118. [Google Scholar] [CrossRef] [Scilit]
  19. Gao, X.; Song, G.; Kang, X.; Cui, C.; Yan, J. Pilot Protection Based on Backward Traveling-wave Voltage Difference for Submarine Cables of Low-frequency Transmission System with Integrated Offshore Wind Power. J. Mod. Power Syst. Clean Energy 2025, 13, 1176–1187. [Google Scholar] [CrossRef] [Scilit]
  20. An, W.; Ma, J.J.; Zhou, H.Y.; Chen, H.S.; Jun, X.; Jian, X. Application of an Integrated Protection and Control System for Smart Distribution Grid Based on PTN and 4G LTE Communication. In Proceedings of the 2019 3rd International Conference on Smart Grid and Smart Cities (ICSGSC), Berkeley, CA, USA, 25–28 June 2019; pp. 70–75. [Google Scholar] [CrossRef] [Scilit]
  21. Gao, X.; Song, G.; Zhang, C.; Kang, X.; Yan, J. A Novel Directional Pilot Protection of Submarine Cables for Low Frequency Transmission System With Offshore Wind Power. IEEE Trans. Power Deliv. 2025, 40, 273–286. [Google Scholar] [CrossRef] [Scilit]
  22. Gao, S.; Zhou, Y.; Wang, C.; Zhou, J.; Zhao, Z.; Song, G. Pilot protection method based on K-L divergence for offshore wind power low-frequency cable feeder line. Int. J. Electr. Power Energy Syst. 2025, 169, 110814. [Google Scholar] [CrossRef] [Scilit]
  23. Wilches-Bernal, F.; Bidram, A.; Reno, M.J.; Hernandez-Alvidrez, J.; Barba, P.; Reimer, B.; Montoya, R.; Carr, C.; Lavrova, O. A Survey of Traveling Wave Protection Schemes in Electric Power Systems. IEEE Access 2021, 9, 72949–72969. [Google Scholar] [CrossRef] [Scilit]
  24. Zhang, D.; Li, M.; Wei, Y.; Du, X.; Zuo, Z.; Li, J. Protection of Offshore Wind Power Flexible Low-Frequency Transmission Lines Based on Canberra Distance. In Proceedings of the 2024 IEEE International Conference on Energy Internet (ICEI), Zhuhai, China, 1–3 November 2024; pp. 766–771. [Google Scholar] [CrossRef] [Scilit]
  25. Gao, X.; Sun, T.; Wu, T.; Yao, G.; He, Y.; Tai, N. A Protection Scheme for Flexible Low Frequency AC System Power Collecting Line of Offshore Wind Farm Based on Transient High Frequency Energy. In Proceedings of the 2023 8th International Conference on Power and Renewable Energy (ICPRE), Shanghai, China, 22–25 September 2023; pp. 79–85. [Google Scholar] [CrossRef] [Scilit]
  26. Guillén-García, E.; Morales-Velazquez, L.; Zorita-Lamadrid, A.L.; Duque-Perez, O.; Osornio-Rios, R.A.; Romero-Troncoso, R.d.J. Accurate identification and characterisation of transient phenomena using wavelet transform and mathematical morphology. IET Gener. Transm. Distrib. 2019, 13, 4021–4028. [Google Scholar] [CrossRef] [Scilit]
  27. Li, J.; Zhao, B.; Liu, S.; Li, J.; Wang, X.; Wang, X. A Novel Harmonic State-space Modelling Method on the Modular Multilevel Matrix Converter and Coupling Analysis. CSEE J. Power Energy Syst. 2025, 11, 78–90. [Google Scholar] [CrossRef] [Scilit]
  28. Wang, T.; Yu, Z.; Xie, F.; Hao, Z.; Monti, A.; Ponci, F. Protection of Line Faults in HVDC Grids Through Convexity Detection in Backward Traveling Wave Voltages. IEEE Trans. Power Deliv. 2023, 38, 3660–3676. [Google Scholar] [CrossRef] [Scilit]
  29. Dong, X. The Theory of Fault Travel Waves and Its Application, 1st ed.; Springer: Singapore, 2022. [Google Scholar] [CrossRef] [Scilit]
  30. Dommel, H.W. Digital Computer Solution of Electromagnetic Transients in Single- and Multiphase Networks. IEEE Trans. Power App. Syst. 1969, PAS-88, 388–399. [Google Scholar] [CrossRef] [Scilit]
  31. Manitoba Hydro International Ltd. The Classical Approach. PSCAD/EMTDC Web Help. Available online: https://pscad.com/webhelp-v502-ol/EMTDC/Transformers/The_Classical_Approach/the_classical_approach.htm (accessed on 24 September 2026).
  32. Dragomiretskiy, K.; Zosso, D. Variational Mode Decomposition. IEEE Trans. Signal Process. 2014, 62, 531–544. [Google Scholar] [CrossRef] [Scilit]
  33. Hasheminejad, S.; Seifossadat, S.G.; Razaz, M.; Joorabian, M. Ultra-high-speed protection of transmission lines using traveling wave theory. Electr. Power Syst. Res. 2016, 132, 94–103. [Google Scholar] [CrossRef] [Scilit]
  34. Hamila, R.; Renfors, M.; Haverinen, T.; Gunnarsson, G. Teager-Kaiser Operator Based Filtering. In Proceedings of the 10th European Signal Processing Conference (EUSIPCO 2000), Tampere, Finland, 4–8 September 2000. [Google Scholar]
  35. Liu, X.; Zhou, G.; Li, W.; Liu, Y.; Ning, L.; Liu, C.; Wang, J.; Wang, Q.; Zhang, J. Research on Low-Frequency Fault Ride-Through Control for Offshore Wind Delivery System Based on M3C. Electronics 2026, 15, 2871. [Google Scholar] [CrossRef] [Scilit]
  36. Dhandapani, R.; Mitiche, I.; McMeekin, S.; Mallela, V.S.; Morison, G. Enhanced Partial Discharge Signal Denoising Using Dispersion Entropy Optimized Variational Mode Decomposition. Entropy 2021, 23, 1567. [Google Scholar] [CrossRef] [Scilit] [PubMed]
  37. Huo, W.; Qu, Z.; Ao, Z.; Zhang, Y.; Zhao, E.; Zhang, C.; Jiang, H. Fault location of cable hybrid transmission lines based on energy attenuation characteristics of traveling waves. Sci. Rep. 2022, 12, 22448. [Google Scholar] [CrossRef] [Scilit] [PubMed]
  38. Yu, D.; Zhou, N.; Liao, J.; Wang, Q.; Lyu, Y. Modified VMD Algorithm-Based Fault Location Method for Overhead-Cable Hybrid Transmission Line in MTDC System. IEEE Trans. Instrum. Meas. 2024, 73, 3517711. [Google Scholar] [CrossRef] [Scilit]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.