Simplification of ANN-Based Adaptive Load Prediction and Offline Controller for Photovoltaic Heating Systems

,
,
and
1
School of Rare Earth Industry, Inner Mongolia University of Science & Technology, Baotou 014010, China
2
Inner Mongolia Key Laboratory of Coal Chemical Engineering & Comprehensive Utilization, Baotou 014010, China
3
School of Mechanical Engineering, Inner Mongolia University of Science & Technology, Baotou 014010, China
*
Authors to whom correspondence should be addressed.

Abstract

This study examines how strongly demand-load prediction and adaptive load control in photovoltaic heating systems rely on computationally intensive artificial neural network (ANN) models. To streamline the computational workflow and reduce runtime resource requirements, we propose an ANN load-prediction-and-validation algorithm coupled with a corresponding offline control strategy. By optimizing the algorithmic structure and shifting heavy computations away from online execution, the proposed method substantially lowers the operational computational burden while preserving predictive accuracy, enabling efficient real-time load prediction and adaptive control. Based on a modelling study of a monocrystalline PV string comprising two 330 W modules connected in series, the proposed simplified prediction method produced annual cumulative energy outputs of 139.9, 391.2, 320.2, 251.4, and 154.1 kW·h across the five irradiance intervals [200, 400), [400, 600), [600, 800), [800, 1000), and [1000, ∞), respectively. Compared with a conventional artificial neural network (ANN)-based prediction approach, the corresponding deviations were 1.1%, −0.1%, 0.0%, 0.1%, and −0.4%, the total annual cumulative energy outputs across all intervals was 1256.7 kW·h with a mean deviation of −0.07%. Moreover, the simplified load-control strategy required only 3.57% of the computational resources consumed by the conventional ANN method. In addition, the method rapidly reallocates computational resources in response to changes in real-time input data, thereby minimizing redundant computation. Overall, the results demonstrate that the proposed framework markedly reduces computational complexity without sacrificing accuracy, providing an effective alternative to traditional ANN-based solutions and facilitating the practical deployment of photovoltaic heating systems.

1. Introduction

With the growing global emphasis on renewable energy, photovoltaic heating systems—integrating solar-to-electric conversion with thermal energy delivery—have emerged as a major research focus for improving building energy efficiency and enabling clean heating. By aligning photovoltaic power generation with thermal demand, these systems can reduce reliance on fossil fuels and improve overall energy-utilization efficiency [1]. However, optimizing system performance remains challenging because it requires accurate dynamic load prediction and coordinated real-time responses. These requirements jointly shape the trade-off between conversion efficiency and operating cost [2]. Numerous maximum power point tracking (MPPT) methods have been developed for photovoltaic (PV) systems [3].
A wide range of MPPT strategies has been developed to accommodate practical constraints, including hardware cost, measurement noise, transient response, and steady-state oscillations. The classical perturb-and-observe (P&O) method features a simple structure and low implementation cost, making it well suited for embedded deployment [4]; however, it tends to induce power oscillations around the steady-state operating point and may misjudge the direction of tracking under rapidly varying irradiance. Incremental conductance (IC) improves steady-state accuracy by exploiting the condition d P / d V = 0 at the maximum power point and can better distinguish environmental variations from control-induced perturbations than P&O [5]. Nevertheless, IC is more sensitive to voltage/current measurement accuracy and sampling rate, and inappropriate parameter settings or filtering designs can amplify noise. Ripple correlation control (RCC) leverages switching-ripple information to achieve tracking without explicit perturbation, offering promising transient performance; yet it strongly depends on ripple observability and circuit-level implementation details, and its effectiveness can be limited in low-ripple or heavily filtered systems [6]. To enhance robustness under nonlinearity and uncertainty, intelligent and nonlinear control-based MPPT approaches have also been extensively explored. Fuzzy logic control (FLC) translates heuristic rules into control laws and can tolerate modelling uncertainties, enabling acceptable performance under complex operating conditions; however, its rule base and membership functions often rely on empirical tuning, which may compromise generalizability and interpretability [7]. Artificial neural networks (ANNs) can approximate strongly nonlinear mappings and rapidly infer MPPT reference values under multi-regime conditions, but they typically require representative datasets; moreover, training and deployment can be challenged by data drift, overfitting, and the cost of online updates [8,9]. Lyapunov control schemes (LCS) construct energy-like functions grounded in stability theory, offering formal stability guarantees and improved dynamic robustness, yet they often require stronger assumptions on model structure or state measurability, leading to higher implementation complexity [10]. Under partial shading, where the power–voltage characteristic can exhibit multiple local maxima, global optimization algorithms become particularly advantageous. Particle swarm optimization (PSO) provides strong global search capability and can increase the likelihood of identifying the global maximum power point in multimodal landscapes; however, its convergence speed and stability depend on inertia weights, learning factors, and swarm size, and online iterations may incur computational overhead and introduce additional perturbations [11]. More recent data-driven discriminative learning approaches, such as Fisher discriminant dictionary learning (FDDL), distinguish operating regimes and power features by constructing discriminative sparse representations, thereby enabling a “regime recognition–strategy switching–rapid tracking” paradigm. While FDDL can couple classification with feature compression to improve recognition of complex patterns, it likewise faces challenges related to training-data representativeness, cross-scenario transferability, and the design of online adaptation mechanisms [12,13]. These approaches are typically evaluated under varying irradiance and shading conditions, often with additional environmental factors taken into account. Prior studies indicate that ANN-based MPPT can harvest more electrical energy from PV arrays than many alternative methods under diverse irradiance profiles [14,15]. Accordingly, load prediction and control in photovoltaic heating systems often rely on complex ANN-based models trained on large historical datasets to capture nonlinear load dynamics and achieve high predictive accuracy [16,17]. Nevertheless, multi-layer parameter optimization and iterative computations can impose substantial computational costs and increase response latency in practical implementations. In distributed deployments (e.g., remote areas or small communities), these requirements may exceed local hardware capabilities, thereby limiting adoption. Moreover, training and maintaining ANN models typically require long-term, high-quality datasets, which can be difficult to obtain and maintain due to data-collection costs and nonstationary environmental conditions. Although MPPT primarily maximizes electrical power extraction from a PV array, its benefit in photovoltaic heating systems is ultimately realized through downstream load matching and control. This is because the operating point imposed by the thermal load (or the power-electronic interface) couples the electrical maximum power point (MPP) to instantaneous heating demand and overall system efficiency.
Although ANN-based MPPT/prediction can capture nonlinear PV behavior, many implementations remain computationally and data intensive, which can limit real-time deployment in resource-constrained photovoltaic heating systems. Existing simplified strategies often trade accuracy for speed, and few studies quantify how far interval-based load matching can approximate an ANN benchmark over long-term operation. This work addresses this gap by deriving a low-complexity interval-based controller and validating its deviation against an ANN baseline [16,17].
This paper proposes a simplified load forecasting algorithm and an interval-based simplified controller that retain key advantages of ANN-based approaches while substantially reducing computational complexity and resource requirements. By optimizing model structure and parameter selection, the proposed method avoids the multi-layer iterations and complex optimization procedures typical of conventional ANN implementations, thereby reducing computational load while maintaining reliable predictive performance. The proposed method is evaluated by comparing annual cumulative output power with that of a conventional ANN-based adaptive load-prediction model.
In addition, we compare the data-call volume of the two control models to quantify the computational savings achieved by the simplified controller. This study makes two primary contributions. First, the simplified design alleviates the computational bottleneck of conventional methods and improves the feasibility of lightweight deployment in photovoltaic heating systems. Second, the method’s stability and accuracy under long-term operation are validated, providing empirical support for engineering applications. Beyond photovoltaic heating, the proposed low-complexity framework may be applicable to other distributed energy-management tasks, such as wind-power load matching and microgrid scheduling. From a societal perspective, reducing computational and operational costs can facilitate clean-energy deployment in resource-constrained settings and support progress toward dual-carbon targets and improved energy equity.

2. Construction of the Load Prediction Model for the Photovoltaic Heating System

2.1. Modeling and Simulation of Irradiance and PV Cell Temperature

Taking the region spanning longitudes 109°15′–110°26′ and latitudes 40°15′–42°43′ (N1) as an example, we used the Meteonorm 7 meteorological database software to generate a site-specific weather dataset. TRNSYS 18.02 then invoked this dataset and, with a time step of 0.125 h, simulated the annual plane-of-array (tilted-surface) solar irradiance incident on a surface tilted at 39° as well as the corresponding variations in ambient temperature [18]. After post-processing, we extracted the hourly data for periods when the irradiance exceeded 100 W/m2, as shown in Figure 1a,b. The plane-of-array irradiance ranges from 100.6 to 1287.3 W/m2, and the corresponding ambient temperature varies from −22.2 to 33.3 °C. For Simulink-based maximum power point tracking (MPPT) simulations, in addition to the tilted-surface irradiance, the PV module temperature is also required. However, the module temperature depends on multiple factors, including irradiance level, ambient temperature, wind speed, and mounting conditions. A widely used module-temperature model in PVsyst is based on the methodology detailed by Faiman [19,20], and is given by the following equation:
T c = T a + α E e ( 1 − η m ) U 0 + U 1 W S
where Ta denotes the ambient air temperature (°C), α is the module absorptance (typical value 0.9), ηm is the module efficiency (typically 0.08–0.20), and WS is the wind speed (m/s), the annual average wind speed in the local area is 1.5 m/s. U0 is the constant heat-transfer coefficient (W/(m2·°C)), and U1 is the convective heat-transfer coefficient (W/(m2·°C)). Typical values of U0 and U1 are 23.5–26.5 W/(m2·°C) and 6.25–7.68 W/(m2·°C), respectively. Ee denotes the effective irradiance, i.e., the portion of incident light that is directly available for conversion into electrical current by the PV material. In this study, Ee is taken as the plane-of-array (tilted-surface) irradiance. By substituting the irradiance and ambient-temperature data from Figure 1 into Equation (1), we computed the corresponding PV cell temperature. The resulting cell temperature ranges from −18.9 to 44.9 °C, as shown in Figure 1c.
Figure 1. (a) Monthly irradiance on a 39° tilted surface (>100 W/m2); (b) The ambient temperature variation corresponding to irradiance; (c) The PV cell temperature variation corresponding to irradiance.
Hourly samples with irradiance in the 100–200 W/m2 range were excluded from the binning analysis and subsequent model construction; they were retained only for completeness in the initial hourly irradiance dataset (Figure 1). For subsequent analysis, irradiance values exceeding 200 W/m2 were classified into five 200 W/m2 intervals. To avoid ambiguity at bin boundaries, the irradiance intervals were defined as half-open ranges: [200, 400), [400, 600), [600, 800), and [800, 1000), with the final interval defined as [1000, ∞) W/m2 (up to the observed maximum of 1287.3 W/m2). Accordingly, boundary values (e.g., 400 W/m2) were assigned to the upper interval [21,22]. The annual cumulative irradiance fractions within these intervals were 11.98%, 19.66%, 25.15%, 31.60%, and 11.61%, respectively (Figure 2). We also computed the annual mean irradiance and the corresponding mean PV cell temperature for each interval (Figure 3). The average irradiance values for the five intervals are 1053.2, 898.6, 699.8, 497.4, and 302.4 W/m2, with the corresponding average battery temperatures being 33.5, 28.2, 22.3, 20.3, and 17.5 °C, respectively. These results were used as inputs to the subsequent Simulink-based simulations.
Figure 2. Annual proportion of cumulative irradiance in each irradiance interval.
Figure 3. Annual average irradiance and average temperature in each irradiance interval.

2.2. Establishment of the Simplified Load Solution Model for the Photovoltaic Heating System

The Ulica Solar UL-330M-60 module was used as the PV module model, and its key parameters are summarized in Table 1. The module has a rated maximum power of Pmax = 330 W at the maximum power point, with Vmpp = 33.5 V and Impp = 9.85 A. The datasheet also reports the open-circuit voltage Voc, short-circuit current Isc, and the temperature coefficients for voltage and current. These ratings are specified under Standard Test Conditions (STC), i.e., an irradiance of 1000 W/m2 and a cell temperature of 25 °C. Multiple PV modules were electrically interconnected to form an array. A single PV string of two series-connected modules (Ns × Np = 2 × 1) was used in the simulations, where Ns and Ns denote the number of series and parallel modules, respectively. This configuration was used to evaluate the computational model and its design parameters.
Table 1. PV string parameters at STC (T = 25 °C and S = 1000 W/m2).

Maximum Output Power and Internal Resistance Calculation

Based on an array comprising two PV modules connected in series (Table 1), we implemented a no-load maximum power point (MPP) model in Simulink (Figure 4). The key component parameters were set as follows. For the Controlled Voltage Source: Source type = DC; Initial amplitude = 0 V; and a Ramp profile was applied with a slope of 100/0.05, starting at t = 0 s. In this model, irradiance S and cell temperature T were used as inputs. These inputs were set to the annual mean irradiance and the corresponding annual mean cell temperature for the five irradiance intervals defined above.
Figure 4. No-load Simulink maximum power point simulation model.
For each interval, the model outputs the maximum power and the corresponding MPP voltage under the specified S and cell T conditions. Using Ohm’s law, we calculated the equivalent internal resistance at each MPP as 6.3, 7.6, 10.1, 14.0, and 23.7 Ω (Figure 5).
Figure 5. Maximum output power and internal resistance at different irradiances and cell temperatures (no-load condition).
This paper investigates a photovoltaic heating system, which requires a load connection to form a closed-loop system. The study aims to compare the theoretical maximum output power differences between the loaded and no-load conditions. Based on the maximum power transfer theorem, we implemented a loaded MPP model in Simulink (Figure 6). The DC–DC boost converter shown in Figure 6 was used only in the simulation model to emulate a variable load for MPP testing. The final system does not include this converter, as load matching is achieved with discrete resistors selected via switches. The model employs a boost converter to enable the load to reach its maximum output power within a short period of time. The specific parameters of the model are as follows: RLC-C1 is the parallel snubber capacitor 1, with a capacitance of 10−5 F; RLC-L is the series snubber inductor, with an inductance of 10−3 H; RLC-C2 is the parallel snubber capacitor 2, with a capacitance of 10−3 F; RLC-R represents the load resistance, (Ω). PWM Generator (DC-DC): Switching frequency: 10−4 Hz; Sample time: 0 s; IGBT: Resistance Ron: 0.001 Ohms; Inductance Lon: 0 H; Forward voltage Vf: 1 V; Initial current Ic: 0 A:; Snubber resistance Rs: 10−5 Ohms; Diode; Resistance Ron: 0.001 Ohms; Inductance Lon: 0 H; Forward voltage Vf: 0.8 V; Snubber resistance Rs: 500 Ohms; Snubber capacitance Cs: 250 × 10−8 F; The resulting maximum output powers after load connection were 675.2, 519.6, 473.5, 339.0, and 206.9 W across the five irradiance intervals (Figure 7).
Figure 6. Loaded Simulink maximum power point simulation model.
Figure 7. Maximum output power and internal resistance at different irradiances and cell temperatures (loaded condition).
By comparing the loaded model (Figure 6) with the no-load model (Figure 4), we obtained relative power errors of 2.8%, 2.8%, 2.7%, 3.0%, and 2.8% across the five intervals (Figure 8). This error analysis supports the reliability of the proposed modeling approach and provides a basis for subsequent calculations of annual cumulative power output.
Figure 8. Comparison of Simulink maximum power output simulation models under no-load and loaded conditions.

2.3. Construction of the Adaptive Load Power Prediction Model for the Photovoltaic Heating System

Prior studies indicate that artificial neural networks (ANNs) are among the most effective approaches for modeling the power characteristics relevant to maximum power point tracking (MPPT) in photovoltaic systems. To evaluate the predictive performance of the simplified load model in Section 2.2, we developed an Interval-based adaptive load–power prediction model (Figure 9). The model comprises three modules: a data-input interface, a trained ANN model, and an output interface. The workflow is summarized as follows. The input interface provides irradiance and cell temperature to the trained ANN model. The trained ANN then estimates the maximum output power at the corresponding operating point via inference. During inference, the ANN performs a forward-propagation pass using stored network weights (i.e., weight retrieval followed by feedforward evaluation) to estimate the output; no online iterative optimization or parameter updating is performed. Finally, the output interface returns the predicted value.
Figure 9. Artificial neural network-based maximum output power prediction model.
Constructing the trained ANN model is a key step in the proposed predictive framework. The training dataset comprises maximum output power values corresponding to discrete irradiance levels and cell temperatures. Based on the meteorological data in Figure 1, Irradiance values above 200 W/m2 (200–1287.3 W/m2) were discretized into 10 bins with a step size of 100 W/m2. All values within each bin were represented by the bin midpoint, yielding representative irradiance levels from 250 to 1150 W/m2. For example, irradiance values in the 200–300 W/m2 range were assigned a representative value of 250 W/m2; the same midpoint-assignment rule was applied to all remaining bins. PV cell temperature was discretized into 14 bins with a step size of 5 °C over −16.8 to 44.9 °C. Each temperature bin was represented by its midpoint, resulting in representative values from −15 to 50 °C. For instance, temperatures in the −17.5 to −12.5 °C range were assigned a representative value of −15 °C; this midpoint-assignment rule was applied consistently across all bins. Using the above discretization scheme and the no-load Simulink MPP model (Figure 4), we systematically computed the maximum output power and equivalent internal resistance for each irradiance bin across all temperature bins. Figure 10 illustrates the maximum output power across the 14 cell-temperature bins (−15 to 50 °C) at an irradiance of 1150 W/m2.
Figure 10. Maximum power point at irradiance S = 1150 W/m2 under different temperature conditions.
Maximum power outputs under the remaining irradiance conditions were computed using the same procedure. Using the complete set of simulation results, we constructed the trained ANN model with 10 × 14 = 140 nodes (Figure 11). For each combination of the 10 irradiance bins and 14 temperature bins (140 operating points in total), the maximum output power and corresponding MPP internal resistance were computed.
Figure 11. Traditional artificial neural network database dataset.

3. Results and Discussion

3.1. Output Power Calculation of the Simplified Model

Following the approach described in Section 2, the simplified model partitions irradiance into five intervals, each associated with a corresponding cell temperature. Using Simulink, five equivalent internal resistances r1–r5 were calculated as 6.3, 7.6, 10.1, 14.0 and 23.7 Ω, respectively.
The equivalent internal resistance at the maximum power point (MPP) was computed as follows:
r e q = P m p p U m p p 2
where Pmpp and Umpp denote the output power and voltage at the maximum power point, respectively.
According to the maximum power transfer theorem, maximum power is delivered when the load resistance equals the corresponding internal resistance (i.e., RL1–RL5 = r1–r5).
We propose an adaptive-load photovoltaic direct-heating system; its operating principle is shown in Figure 12. The system dynamically selects among five load resistors (RL1–RL5) based on the real-time measured plane-of-array irradiance S. The online strategy used in the proposed simplified controller and the offline ANN baseline used for benchmarking. The proposed controller operates by classifying measured irradiance into five predefined half-open intervals and switching to the corresponding matched load resistance (RL1–RL5), with mutually exclusive contactor logic (KM1–KM5). Specifically, when S ∈ [200, 400) W/m2, contactor KM5 closes to connect RL5; otherwise, KM5 remains open. Similarly, for S ∈ [400, 600), [600, 800), [800, 1000), and [1000, 1200] W/m2, contactors KM4–KM1 close, respectively, to connect RL4, RL3, RL2 and RL1, thereby supplying power for water heating. To prevent parallel activation of multiple loads, contactors KM1–KM5 operate in a mutually exclusive (interlocked) mode such that only one contactor can be closed at any time, corresponding to the active irradiance interval. To avoid ambiguity at bin boundaries, the irradiance intervals are defined as half-open ranges: [200, 400), [400, 600), [600, 800), and [800, 1000), with the final interval defined as [1000, 1200] W/m2. Accordingly, a boundary value (e.g., 400 W/m2) is assigned to the upper interval, whereas 1200 W/m2 is included in the final interval. The contactor coils are powered by an external AC supply.
Figure 12. Operating principle of the simplified control model for the adaptive load photovoltaic heating system.
To prevent frequent interval switching caused by rapid changes in illumination conditions and transient deviations near interval boundaries, we incorporated a delay function into the simplified controller. This design reduces—or even avoids—potential adverse impacts on the heating system during periods of rapid fluctuations.
Using the hourly plane-of-array irradiance from Figure 1, together with the cumulative irradiance fractions, mean irradiance values, and interval power outputs from Figure 2, Figure 3 and Figure 7, the system computes the cumulative output power for each interval (Figure 13).
Figure 13. Annual cumulative output power comparison between the conventional and optimized artificial neural network prediction models.

3.2. Cumulative Output Power Calculation Using the Artificial Neural Network

Using the hourly plane-of-array irradiance from Figure 1, together with the cumulative irradiance fractions, mean irradiance values, and interval power outputs from Figure 2, Figure 3 and Figure 7, the system computes the cumulative output power for each interval (Figure 13). Using the same procedure, the hourly plane-of-array irradiance from Figure 1a was fed into the ANN-based output-power prediction model (Figure 9). The load was assumed to respond dynamically to the input conditions and to utilize all generated power (i.e., no curtailment). The simulation outputs were post-processed to obtain the ANN-predicted cumulative output power for each interval (Figure 13). No ANN inference or iterative optimization is executed in real time; instead, ANN is used only as a reference model to quantify prediction deviation in annual cumulative output power.
We conducted a comparative analysis of the annual cumulative energy output of the two models across five discretized irradiance intervals. The ANN model yielded annual cumulative energies of 141.4, 390.9, 320.1, 251.6, and 153.5 kW·h for the five intervals, respectively, whereas the simplified model produced 139.9, 391.2, 320.2, 251.4, and 154.1 kW·h. The corresponding relative deviations between the simplified and ANN models were 1.1%, −0.1%, 0.0%, 0.1%, and −0.4%. Overall, the total annual cumulative energy outputs were 1256.7 and 1257.5 kW·h for the simplified and ANN models, respectively, with an all-interval mean deviation of 0.07%. Given these small discrepancies, the simplified model achieved accuracy comparable to that of the ANN baseline and is therefore suitable for practical engineering applications.
The deviation was quantified as the relative error with respect to the ANN baseline. For each interval i, the relative error was defined as follows:
δ = P s i m p − P A N N P A N N × 100 %
where Psimp and PANN denote the cumulative output power predicted by the simplified model and the ANN model, respectively.
The overall (all-interval) mean deviation was computed as an irradiance-fraction–weighted mean of the interval-wise relative errors, defined as follows:
δ - o v e r a l l = ∑ i = 1 5 w i δ i ,   ∑ i = 1 5 w i = 1
where wi denotes the annual irradiance fraction (or time-share) associated with interval i, and δi is the corresponding relative error.

3.3. Comparison of Data Requirements for Control Output of Two Models

To reduce the computational burden of maximum output-power prediction, we simulated local meteorological conditions and extracted hourly irradiance and temperature data. The annual irradiance time series was grouped into five intervals with a 200 W/m2 step, and the annual mean irradiance and corresponding mean temperature were calculated for each interval. A no-load Simulink model was established to compute the maximum output power and the equivalent internal resistance at the maximum power point (MPP) for each of the five operating points. A loaded Simulink model was then built to compute the maximum output power and the equivalent internal resistance at the MPP after load connection for each of the five operating points. Based on these results, we implemented a simplified Interval-based control model (Figure 14) for adaptive load matching.
Figure 14. A simplified Interval-based control model.
The controller uses a single input—plane-of-array irradiance—and includes five ANN nodes. For a given irradiance input, the controller classifies the incoming irradiance into discrete intervals and uses predefined equivalent load resistances for each interval to achieve adaptive control, and switches in the matched load to initiate water heating, without performing any neural-network computation during operation. Owing to its low computational demand, the controller enables rapid response. The simplified controller does not perform any ANN computations during operation. Instead, it classifies the measured irradiance into one of five predetermined intervals and applies the corresponding equivalent load resistance (determined offline). The ANN model is used solely as an offline reference for performance validation, to quantify prediction deviation and validate the simplified strategy’s accuracy, rather than as part of the real-time control loop.
For the ANN-based maximum-power prediction model, we used the same meteorological simulations to obtain hourly irradiance and temperature data. The annual irradiance time series was discretized into 10 intervals with a 100 W/m2 step, and cell temperature was discretized into 14 intervals with a 5 °C step.
A no-load Simulink model was used to compute the maximum output power and the equivalent internal resistance at the MPP for all 140 operating points. A loaded Simulink model was further used to compute the maximum output power and the equivalent internal resistance at the MPP after load connection for the same 140 operating points. Based on these results, adaptive load matching was performed using the Interval-based controller (Figure 15). Figure 15 shows an idealized artificial neural network (ANN) control model for the photovoltaic heating system. The control logic is as follows: the measured irradiance and ambient temperature are first discretized into predefined intervals and assigned representative midpoint values; these assigned values are then mapped to the ANN inputs (S and T) to generate a load-resistance control signal, which switches in the corresponding load resistance. Moreover, a practical implementation of the 140-node ANN controller would require a DC–DC converter (or similar continuously variable load) to realize so many resistance levels. By contrast, the simplified five-interval design avoids this complexity by using only five discrete resistors (Figure 12).
Figure 15. Traditional artificial neural network ideal control model.

4. Conclusions

This study systematically compares conventional ANN-based prediction and control models with simplified counterparts using TRNSYS-generated meteorological data for training and validation. The main findings are summarized as follows:
(1)
For annual cumulative output power, the absolute deviation between the conventional and simplified prediction models ranges from −0.4% to 1.1%, and the overall (all-interval) mean deviation is 0.07%. This narrow deviation range indicates that the simplified prediction model achieves accuracy comparable to the conventional model.
(2)
Regarding data-call efficiency, the conventional controller uses 140 nodes, whereas the simplified controller uses five, corresponding to 3.57% of the conventional model’s node count. This reduction indicates that the simplified controller can substantially decrease computational demand and associated hardware cost. Consequently, the simplified controller provides a practical alternative to computationally intensive ANN-based approaches by offering a favorable trade-off between performance and cost.
(3)
Although results are reported for one module/array configuration, tilt angle, and climatic dataset, the proposed framework is transferable. For a new site or PV configuration, the same steps apply: generate site-specific irradiance/temperature series, compute the irradiance distribution, select representative operating points, and recompute matched load resistances from the PV model. The interval-based switching logic and error metrics remain unchanged.

Author Contributions

Conceptualization, S.X.; methodology, S.X.; software, S.X. and Q.S.; validation, Y.W. and S.A.; formal analysis, S.X.; investigation, Y.W.; resources, Y.W.; data curation, S.X. and Q.S.; writing—original draft preparation, S.X.; writing—review and editing, S.A.; visualization, S.X.; project administration, Y.W.; funding acquisition, Y.W. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by Inner Mongolia Applied Technology Research & Development Foundation, grant number 2023JBGS0012.

Data Availability Statement

The datasets generated during this study are fully available within the article.

Acknowledgments

The authors confirm that no AI-assisted language tools were used in the preparation or editing of this manuscript.

Conflicts of Interest

The authors declare no conflict of interest.

Abbreviations

The following abbreviations are used in this manuscript:
MPPMaximum power point
PVPhotovoltaic
MPPTMaximum power point tracking
ANNArtificial neural network
STCStandard Test Conditions
DC-DCDirect current to direct current
RLCRepeater Link Controller
PWMPulse Width Modulation
IGBTInsulated Gate Bipolar Transistor
P&OPerturb-and-observe
ICIncremental conductance
RCCRipple correlation control
FLCFuzzy logic control
LCSLyapunov control schemes
PSOParticle swarm optimization
FDDLFisher discriminant dictionary learning
VocThe open-circuit voltage of PV module, V
IscThe short-circuit current, A
VmppThe optimal voltage at maximum power point, V
ImppThe optimal current at maximum power point, A
TRNSYSTransient Systems Simulation Program

References

  1. Samykano, M. Hybrid photovoltaic thermal systems: Present and future feasibilities for industrial and building applications. Buildings 2023, 13, 1950. [Google Scholar] [CrossRef] [Scilit]
  2. Gaga, A.; Errahimi, F.; Es-Sbai, N. Design and Implementation of MPPT Solar System Based on the Enhanced P&O lgorithm Using Labview. In Proceedings of the International Renewable and Sustainable Energy Conference (IRSEC), Ouarzazate, Morocco, 17–19 October 2014; pp. 203–208. [Google Scholar] [CrossRef] [Scilit]
  3. Katche, M.L.; Makokha, A.B.; Zachary, S.O.; Adaramola, M.S. A comprehensive review of maximum power point tracking (mppt) techniques used in solar pv systems. Energies 2023, 16, 2206. [Google Scholar] [CrossRef] [Scilit]
  4. Ibrahim, A.A.; Caldognetto, T.; Biadene, D.; Mattavelli, P. Multidimensional ripple correlation technique for optimal operation of triple-active-bridge converters. IEEE Trans. Ind. Electron. 2022, 70, 8032–8041. [Google Scholar] [CrossRef] [Scilit]
  5. Sun, C.; Ling, J.; Wang, J. Research on a novel and improved incremental conductance method. Sci. Rep. 2022, 12, 15700. [Google Scholar] [CrossRef] [Scilit]
  6. Walczak, S. Advanced methodologies and technologies in artificial intelligence, computer simulation, and human-computer interaction. In Artificial Neural Networks; IGI Global Scientific Publishing: Hershey, PA, USA, 2019; pp. 40–53. [Google Scholar] [CrossRef] [Scilit]
  7. Hannan, M.A.; Ghani, Z.A.; Hoque, M.; Ker, P.J.; Hussain, A.; Mohamed, A. Fuzzy logic inverter controller in photovoltaic applications: Issues and recommendations. IEEE Access 2019, 7, 24934–24955. [Google Scholar] [CrossRef] [Scilit]
  8. Qamar, R.; Zardari, B.A. Artificial neural networks: An overview. Mesopotamian J. Comput. Sci. 2023, 2023, 124–133. [Google Scholar] [CrossRef] [Scilit] [PubMed]
  9. Wu, Y.; Feng, J. Development and Application of Artificial Neural Network. Wirel. Pers Commun. 2018, 102, 1645–1656. [Google Scholar] [CrossRef] [Scilit]
  10. Baghaee, H.R.; Mirsalim, M.; Gharehpetian, G.B.; Talebi, H.A. A decentralized power management and sliding mode control strategy for hybrid AC/DC microgrids including renewable energy resources. IEEE Trans. Ind. Inform. 2017, 1–10. [Google Scholar] [CrossRef] [Scilit]
  11. Shami, T.M.; El-Saleh, A.A.; Alswaitti, M.; Al-Tashi, Q.; Summakieh, M.A.; Mirjalili, S. Particle swarm optimization: A comprehensive survey. IEEE Access 2022, 10, 10031–10061. [Google Scholar] [CrossRef] [Scilit]
  12. Ahmad, M.E.; Numan, A.H.; Mahmood, D.Y. A comparative study of perturb and observe (P&O) and incremental conductance (INC) PV MPPT techniques at different radiation and temperature conditions. Eng. Technol. J. 2022, 40, 376–385. [Google Scholar] [CrossRef] [Scilit]
  13. Zhou, L.; Wang, S.; Zhao, Z.; Cai, G.; Yan, R.; Chen, X. Low-dimensional multi-scale Fisher discriminant dictionary learning for intelligent gear-fault diagnosis. Meas. Sci. Technol. 2021, 32, 084001. [Google Scholar] [CrossRef] [Scilit]
  14. Saxena, A.; Kumar, R.; Amir, M.; Muyeen, S. Maximum power extraction from solar PV systems using intelligent based soft computing strategies: A critical review and comprehensive performance analysis. Heliyon 2024, 10, e22417. [Google Scholar] [CrossRef] [Scilit] [PubMed]
  15. Hussain, T.; Sarwar, A.; Tariq, M.; Urooj, S.; BaQais, A.; Hossain, A. An evaluation of ANN algorithm performance for MPPT energy harvesting in solar PV systems. Sustainability 2023, 15, 11144. [Google Scholar] [CrossRef] [Scilit]
  16. Rao, S.N.V.B.; Yellapragada, V.P.K.; Padma, K.; Pradeep, D.J.; Reddy, C.P.; Amir, M.; Refaat, S.S. Day-ahead load demand forecasting in urban community cluster microgrids using machine learning methods. Energies 2022, 15, 6124. [Google Scholar] [CrossRef] [Scilit]
  17. Amir, M.; Prajapati, A.K.; Refaat, S.S. Dynamic performance evaluation of grid-connected hybrid renewable energy-based power generation for stability andpower quality enhancement in smart grid. Front. Energy Res. 2022, 10, 861282. [Google Scholar] [CrossRef] [Scilit]
  18. Redpath, D.; Paneri, A.; Singh, H.; Ghitas, A.; Sabry, M. Design of a building-scale space solar cooling system using TRNSYS. Sustainability 2022, 14, 11549. [Google Scholar] [CrossRef] [Scilit]
  19. Faiman, D. Assessing the outdoor operating temperature of photovoltaic modules. Prog. Photovolt. 2008, 16, 307–315. [Google Scholar] [CrossRef] [Scilit]
  20. Ya’ACob, M.E.; Hizam, H.; Khatib, T.; Radzi, M.A.M.; Gomes, C.; Bakri, A.M.; Marhaban, M.H.; Elmenreich, W. Modelling of photovoltaic array temperature in a tropical site using generalized extreme value distribution. J. Renew. Sustain. Energy 2014, 6, 033134. [Google Scholar] [CrossRef] [Scilit]
  21. Fragkos, K.; Charalampous, G.; Fountoulakis, I.; Papachristopoulou, K.; Hadjimitsis, D.; Kazadzis, S. Next-day solar irradiance forecasting: A preliminary study in Limassol. In Proceedings of the 2024 3rd International Conference on Energy Transition in the Mediterranean Area (SyNERGY MED), Limassol, Cyprus, 21–23 October; IEEE: Piscataway, NJ, USA, 2024; pp. 1–5. [Google Scholar] [CrossRef] [Scilit]
  22. Khalaf, H.H.; Hussain, A.N.; Mohammad, A.T.; Al-Sagar, Z.S. Study and performance analysis of photovoltaic module in winter conditions of Baghdad. AIP Conf. Proc. 2023, 2804, 050024. [Google Scholar] [CrossRef] [Scilit]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Article Metrics

Citations

Article Access Statistics

Multiple requests from the same IP address are counted as one view.