Waste Heat Recovery Limits for Energy-Efficient Climate Control in Mobile Working Machines

,
,
,
,
and
1
Department of Biosystems Engineering, Faculty of Environmental and Mechanical Engineering, Poznań University of Life Sciences, Wojska Polskiego 50, 60-627 Poznań, Poland
2
Department of Mathematical and Statistical Methods, Faculty of Agriculture, Horticulture and Biotechnology, Poznań University of Life Sciences, Wojska Polskiego 28, 60-637 Poznań, Poland
3
Department of Vehicles and Machines, Faculty of Technical Sciences, University of Warmia and Mazury in Olsztyn, 10-719 Olsztyn, Poland
4
Department of Mechanics, Escuela Politécnica Superior, University of Córdoba, Campus de Rabanales, 14071 Córdoba, Spain
This article belongs to the Section J1: Heat and Mass Transfer

Abstract

Low-grade waste heat may potentially support desiccant regeneration in the climate-control systems of mobile working machines, if both sufficient source temperature and usable thermal power are available. This study re-analyses 64 previously published operating points of a renewable air-cooling unit comprising a desiccant wheel and a dew-point indirect evaporative cooler. Measured or published air states and volumetric flows were reconciled to calculate conditional heating-coil requirements for a nominal 60 °C outlet temperature. Supplementary outlet-temperature ranges from separate experiments were transferred only to 30 cases with exactly matching published inlet settings. Nominal demand ranged from 6.30 to 23.81 kW (median 13.29 kW); the remaining 34 cases had no supplementary temperature ranges. A consistency audit found that system-level process/regeneration moisture-indicator ratios were within ±10% of unity in only 8 of 64 cases and that the reconstructed 5–7 enthalpy change exceeded conditional 5–6 heating demand in 15 cases. These comparisons identify unresolved boundary/state limitations, not proven violations of conservation. Illustrative input-perturbation calculations were reported separately from experimental uncertainty. The resulting heating demands and source-screening inequalities are necessary conditional references, not measured recovered heat, demonstrated engine integration, COP improvement or fuel savings.

1. Introduction

Agricultural tractors, combine harvesters and other mobile working machines operate under environmental conditions that place considerable demands on operator-cabin climate control. The cabin must provide acceptable thermal conditions, visibility, operational safety and compatibility with the machine’s principal functions. Solar radiation, ambient temperature, humidity, ventilation and internal heat sources contribute to sensible and latent cooling loads.
Experimental and numerical investigations of agricultural tractor cabins have addressed cabin temperatures and airflow organisation. Riaz et al. [1] combined experimental measurements and computational fluid dynamics to investigate an air-conditioned tractor cabin, while Riaz et al. [2] considered related operating conditions during agricultural tillage. These studies demonstrate the importance of effective climate control under varying operating conditions. Conventional mechanical cooling systems, however, impose additional energy demands on machines whose operating speeds and available mechanical power change during fieldwork and transport.
Internal combustion engines reject thermal energy through exhaust gases, cooling circuits and other pathways. Such energy may represent a secondary resource if it is available at the temperature, heat rate and operating duration required by the receiving process. Saidur et al. [3] reviewed methods of engine exhaust-heat recovery, while Sprouse and Depcik [4] examined organic Rankine cycle systems for exhaust-energy recovery. The existence of rejected heat nevertheless does not automatically establish its suitability for regeneration of a desiccant cooling system. Practical suitability depends on usable thermal power, source temperature, heat-exchanger characteristics, losses, auxiliary loads and the working-machine duty cycle.
A solid-desiccant wheel reduces the humidity ratio of process air by adsorption. Moisture retained by the sorbent must then be removed using a separate, typically heated, regeneration air stream. Regeneration temperature influences both the sensible heating requirement and achievable moisture desorption. Angrisani et al. [5] investigated desiccant-wheel dehumidification and thermal performance, Comino et al. [6] studied low-temperature wheel activation, and Su et al. [7] examined regeneration conditions and energy performance. Reducing the temperature of the regeneration supply decreases conditional sensible heating requirements, but does not guarantee effective desorption or favourable whole-system performance.
Combining desiccant dehumidification with dew-point indirect evaporative cooling enables latent- and sensible-load treatment to be considered separately. Romero-Lara et al. [8] experimentally assessed a renewable air-cooling unit (RACU) integrating a solid-desiccant wheel and dew-point indirect evaporative cooler (DIEC). Their experimental campaign comprised 64 operating points and reported process and regeneration conditions, airflow rates and auxiliary electrical consumption. During the tests, regeneration heat was supplied through an external hot-water circuit. No engine waste-heat recovery system was installed or validated in the original campaign.
A central issue in interpreting these experiments is the separation of heating-coil duty from the full regeneration-path enthalpy change. The regeneration stream passes first through a coil and then through the regeneration sector of the wheel. The thermal requirement between the coil inlet and outlet differs from the change between regeneration inlet and wheel exhaust, where heat and moisture transfers occur. Similarly, a RACU electrical COP excluding regeneration heat is not a complete system-energy indicator. Giampieri et al. [9] discussed system-level sorption-based thermal and humidity management, illustrating the importance of matching regeneration requirements to usable heat sources.
The original research team subsequently confirmed that reported volumetric airflows were actual steady-state measurements rather than normalised flows, identified 60 °C as the nominal regeneration temperature and supplied additional temperature intervals from separate RACU tests. These observations constrain the present analysis but do not constitute measured heating-coil outlet temperatures for each of the original 64 tests.
This study introduces TRACE (Thermal Regeneration and Air-Conditioning Energy Assessment) to address a question not resolved by the original RACU performance tests: what heating-coil demands follow conditionally from the reported air states, and what necessary heat-rate and inlet-temperature conditions would an external waste-heat source have to satisfy? The original contribution lies in (i) separating experimentally reported air states, source-paper settings and conditional assumptions; (ii) reproducing 64 nominal regeneration-heating calculations while restricting supplementary T6 intervals to 30 exact set-point matches; and (iii) exposing consistency and sensitivity limitations before evaluating source compatibility. TRACE neither measures regeneration-coil duty in the original tests nor demonstrates machine-integrated waste-heat recovery, COP improvement or fuel savings.

2. Materials and Methods

2.1. Research Design and Experimental Evidence

TRACE follows four successive stages: (i) reconciliation of experimental records, (ii) psychrometric reconstruction, (iii) conditional regeneration-temperature scenarios and (iv) screening against necessary thermal-source requirements. Figure 1 illustrates these stages. Their evidence levels must not be conflated: measured values and published operating settings are used to calculate model quantities, while engine-source compatibility is evaluated only as a conditional requirement.
Figure 1. TRACE research design and evidence hierarchy. Experimental RACU data are followed by psychrometric reconstruction, conditional regeneration heating scenarios, and preliminary thermal-power and temperature screening requirements.

2.2. RACU Configuration and Control Volumes

The experimental RACU included a solid-desiccant wheel and a downstream DIEC [8]. Process air was dehumidified in the wheel’s adsorption sector and subsequently cooled indirectly. Regeneration air was heated by a hot-water coil upstream of the regeneration sector. The process-air path also included a flow split within the evaporative cooler; the process inlet flow was therefore not taken as identical to the useful conditioned supply-air flow.
Figure 2 identifies CV1 as process-air treatment between states 1 and 4, CV2 as the heating coil between states 5 and 6, and CV3 as desiccant regeneration between states 6 and 7. These boundaries avoid assigning the combined regeneration-path enthalpy change from states 5 to 7 to the heating coil itself.
Figure 2. Thermodynamic control volumes of the RACU. CV1 covers the process-air treatment path (states 1, 2, 4); CV2 covers regeneration heating (states 5–6); and CV3 covers the desiccant-wheel regeneration sector (states 6–7).

2.3. Input Data and Evidence Classification

The 64 tests N1–N64 were reconciled with published regeneration inlet conditions in the external Table 5 of Romero-Lara et al. [8]. The source RACU workbook, now available for direct audit, provides process inlet/outlet temperatures and humidity ratios, regeneration exhaust air conditions, volumetric airflows and power drawn by the three fans. Although columns for regeneration inlet temperature and humidity ratio exist, their values are blank in the workbook; published set points therefore serve as separate source-paper inputs. State 6 heating-coil outlet temperatures were not measured individually for the 64 original tests. These provenance classes are recorded in Table 1 and Table S1.
Table 1. Experimental and reconstructed variables used in TRACE.
The original research team confirmed that the recorded volumetric flows were actual steady-state measurements, not standard-condition flows. The workbook confirms the flow values but does not document their exact measurement-section thermodynamic state or pressure for each test. Converting them to dry-air mass flow therefore requires a stated state convention and an assumed reference pressure of 101.325 kPa. This conversion remains a reconstructed quantity, not an independently verified mass-flow measurement.

2.4. Humid-Air Properties and Mass-Flow Reconstruction

Specific humid-air enthalpy per unit mass of dry air was calculated from Equation (1), using cp,da = 1.006 kJ kg−1 K−1, cp,v = 1.86 kJ kg−1 K−1 and reference vaporisation enthalpy hfg,0 = 2501 kJ kg−1.
h T , w = c p , da T + w h fg , 0 + c p , v T
The density of humid air was reconstructed by Equation (2), with Rda = 287.05 J kg−1 K−1 and absolute pressure p in Pa. The dry-air mass flow was then obtained from Equation (3), using airflow in m3 s−1 and density and volumetric flow referred to the same thermodynamic state.
ρ = p R da T + 273.15 1 + 1.6078 w
m ˙ da = ρ V ˙ 1 + w

2.5. Process-Air Indicators

Process temperature decrease, humidity-ratio decrease and specific enthalpy difference were defined by Equations (4)–(6).
Δ T P = T Pi − T Po
Δ w P = w Pi − w Po
Δ h P = h Pi − h Po
An inlet-flow-weighted diagnostic enthalpy rate and water-vapour mass-flow difference were defined by Equations (7) and (8). The superscript asterisk indicates the use of process inlet dry-air mass flow rather than necessarily useful conditioned-air flow.
H ˙ P ∗ = m ˙ da , Pi Δ h P
m ˙ w , P ∗ = m ˙ da , Pi Δ w P
Conditional sensible and latent air-treatment quantities may be calculated from Equations (9) and (10), provided that the conditioned outlet dry-air flow and the selected reference-state convention are explicitly specified. These relationships are not used to claim measured cabin-cooling loads.
Q ˙ S = m ˙ da , Po c p , da + w Po c p , v T Pi − T Po
Q ˙ L = m ˙ da , Po w Pi − w Po h fg , 0 + c p , v T Pi

2.6. Regeneration-Path Indicators

The regeneration humidity-ratio increase and associated reconstructed water-vapour flow are given by Equations (11) and (12).
Δ w R = w 7 − w 5
m ˙ w , R = m ˙ da , R Δ w R
Equations (13) and (14) describe the specific enthalpy and enthalpy-flow changes over states 5–7. Because this includes both the heating coil and the wheel regeneration sector, the resulting energy change is not the heating-coil duty.
Δ h R = h 7 − h 5
Δ H ˙ R = m ˙ da , R Δ h R

2.7. Conditional Heating-Coil Demand

Heating-coil duty was defined only across states 5–6, as in Equation (15). Assuming no moisture addition or removal in the coil, the temperature-based expression is Equation (16).
Q ˙ HC , req = m ˙ da , R h 6 − h 5
Q ˙ HC , req = m ˙ da , R c p , da + w 5 c p , v T 6 − T 5
For non-negative required heating, Equation (17) was used. The zero-valued result obtained where prescribed T6 equals T5 means no required sensible air-temperature increase; it does not demonstrate effective regeneration of the desiccant wheel.
Q ˙ HC , req + = m ˙ da , R c p , da + w 5 c p , v max 0 , T 6 , req − T 5

Nominal and Externally Informed Temperature Scenarios

A nominal regeneration temperature T6 = 60 °C was used for all 64 original operating points based on supplementary clarification from the source research team. Four additional temperature intervals were obtained from separate RACU experiments. They were associated with original tests only when both regeneration inlet temperature and inlet humidity ratio matched. Table 2 reports the resulting four groups: 30 test records were matched and 34 were left in the nominal scenario alone.
Table 2. Supplementary state 6 temperature intervals and original tests with matching inlet conditions.
The supplementary observations originated from experimental campaigns distinct from the original 64-test dataset. They were not re-labelled as original state 6 measurements or treated as confidence intervals. No interval interpolation or extrapolation was performed for unmatched conditions.

2.8. Auxiliary Electrical Power Accounting

The subtotal of the three measured RACU fan powers is defined in Equation (18). Equation (19) additionally identifies the desiccant-wheel motor and DIEC hydraulic-pump components needed for complete electrical accounting.
P fans = P PF + P RF + P DF
P el , tot = P fans + P motor , DW + P HP , DIEC
Complete test-level values for the additional auxiliaries were unavailable in the supplied workbook. Thus, the fan subtotal was not used as total RACU electricity in a newly calculated COP. The electrical COP reported in the original study [8] excludes regeneration thermal input.

2.9. Necessary Waste-Heat Compatibility Conditions

For a prospective external waste-heat source, usable thermal power must at least satisfy the conditional coil demand (Equation (20)). The source inlet temperature must also satisfy the necessary temperature approach criterion in Equation (21). Both conditions are screening requirements; neither constitutes a physically validated exchanger design.
Q ˙ WH , usable ≥ Q ˙ HC , req +
T WH , in ≥ T 6 , req + Δ T min
The conditional heat-rate availability ratio is defined by Equation (22) for a strictly positive demand. No numeric value was assigned to an actual engine because no engine-side thermal measurements were available.
Φ Q = Q ˙ WH , usable Q ˙ HC , req +

2.10. Thermal Substitution and Energy-System Boundaries

Equation (23) expresses potential time-integrated substitution of external regeneration heat using the lower of the usable heat rate and the required coil rate. Additional source-temperature and heat-exchanger constraints apply throughout the operating interval. The result is not an equation for vehicle fuel savings.
E heat , disp = ∫ t 0 t 1 min Q ˙ WH , usable t , Q ˙ HC , req + t dt

2.11. Uncertainty and Calculation Assumptions

Uncertainty sources include measured temperature, humidity ratio, volumetric flow, reference pressure and the choice of T6. For uncorrelated standard uncertainties, the first-order propagation relation is Equation (24). Correlations require covariance terms, while manufacturer accuracy limits must not be identified automatically with standard deviations [10].
u y 2 ≈ ∑ i = 1 n ∂ f ∂ x i 2 u x i 2
For the humid-air enthalpy function, Equation (25) gives the sensitivities to the air temperature and humidity ratio. Because calibrated standard uncertainties, input covariances and original 64-test outlet temperatures T6 are unavailable, Equation (24) cannot support numerical 95% coverage intervals. Instead, the model was re-evaluated using explicit hypothetical input perturbations: pressure ±1 kPa, regeneration-inlet temperature T5 ±1 °C, inlet humidity ratio w5 ±0.001 kg kg−1, volumetric airflow ±5%, and prescribed T6 ±2 °C around 60 °C. A paired lower/upper corner scenario perturbs all these inputs simultaneously and recalculates mass flow and heat demand. Those numerical envelopes quantify assumed input sensitivity, not measurement uncertainty, a transfer-mismatch probability distribution, or observed T6 variability; they must not be attached to the 30 separate-experiment temperature intervals as confidence bounds. The complete case-level scenarios are reproduced in Table S9.
∂ h ∂ T = c p , da + w c p , v ,     ∂ h ∂ w = h fg , 0 + c p , v T

2.12. Numerical and Statistical Analysis

Each operating point was processed using the documented experimental inputs and consistent thermodynamic equations. Nominal coil requirements were calculated at 60 °C for all 64 records; lower and upper conditional values were calculated only for the 30 exact matches with separate-experiment temperature ranges. The published script was executed to verify the 64 nominal computations and 30 matched bounds. We additionally compared the two system-level moisture indicators and the magnitude of the reconstructed 5–7 enthalpy change with nominal 5–6 heating demand as diagnostics of model/data consistency; neither comparison was imposed as a closed wheel balance. Descriptive summaries used minima, medians and maxima; no inferential test or claim of integrated engine validation was made. Numerical sensitivity perturbations included simultaneous illustrative scenarios rather than empirically validated uncertainty intervals. The supporting derived files and calculation scripts are provided in Supplementary Materials (Tables S1–S9 and Codes S1 and S2). The reproducibility scripts use Python 3 (https://www.python.org/) and pandas (https://pandas.pydata.org/) (accessed on 22 November 2026).
Reproducibility and provenance audit. The source RACU workbook supplied by the original research team was available for this revision and was cross-checked numerically against all 64 test records in the merged TRACE dataset (eight measured state/flow columns; maximum absolute discrepancy below 10−7 in the reported units). The workbook does not contain individual regeneration-inlet T5 and w5 values or measured heating-coil outlet T6 values; the former were taken from published experimental settings and the latter remain conditional assumptions. Experimental sensor calibration certificates, original time histories, paired wheel-sector states and actual engine-source measurements remain unavailable. Tables S8 and S9 document the numerical consistency checks and explicitly hypothetical perturbation scenarios.

3. Results

3.1. Reconciliation of the 64 Experimental Records

All 64 test identifiers were linked to the publication-derived regeneration-inlet settings and cross-checked against the newly available RACU workbook. The workbook contains measured process-inlet/outlet and regeneration-exhaust states, actual process/regeneration volumetric flows and fan powers, but does not contain original test-level values for T5, w5 or T6. The values for T5 and w5 were assigned using published set points; T6 was treated only as a conditional temperature. Table 3 summarises these distinct evidence categories.
Table 3. Completeness and evidential status of the analysed RACU records.

3.2. Process-Air Temperature and Enthalpy Changes

Across the 64 original operating points, process-air temperature decreased by 2.10–23.55 °C (median 13.79 °C). The inlet-flow-weighted enthalpy difference ranged from 8.66 to 41.11 kW (median 24.54 kW). Figure 3 displays available and publication-derived psychrometric states, whereas Figure 4 presents the distributions of temperature and enthalpy changes; Table 4 summarises diagnostic stream indicators. These quantities should not be interpreted as a directly measured cabin-cooling capacity.
Figure 3. Temperature–humidity-ratio states for all 64 RACU tests. Filled points denote measured states; open diamonds denote published regeneration-inlet settings. Relative-humidity curves are illustrative at 101.325 kPa; state 6 is not plotted.
Figure 4. Distribution of process-air temperature reduction (a) and inlet-flow-weighted process-air enthalpy difference (b) for the 64 experiments. Dashed lines indicate medians. The enthalpy-flow difference is a diagnostic quantity, not independently validated useful cooling capacity.
Table 4. Process-air state changes and inlet-flow-weighted diagnostic quantities for 64 experiments.
The values combine measured states from the source workbook with calculated inlet dry-air flow. Figure 3 displays the available temperature–humidity-ratio states for all 64 tests and the distinct publication-derived regeneration-inlet settings, without inventing unmeasured heating-coil outlet states. The underlying relative-humidity curves are calculated at 101.325 kPa and serve only as psychrometric guides. Because the RACU process stream is split, inlet-weighted enthalpy differences are not independently validated conditioned-cabin supply cooling capacities.

3.3. Regeneration-Path Psychrometric Reconstruction

Regeneration inlet settings were combined with the experimental regeneration exhaust temperatures and humidity ratios. Reconstructed regeneration-stream moisture-flow increase ranged from 2.55 to 15.08 kg h−1; the combined 5–7 enthalpy-flow change ranged from 4.70 to 23.46 kW (Table 5). These values describe the complete regeneration path, not heating-coil power.
Table 5. Reconstructed regeneration-path quantities across 64 experiments.

3.4. Limits of Wheel-Level Moisture Accounting

The ratio of calculated regeneration-side moisture gain to inlet-flow-weighted process-side moisture removal ranged from 0.22 to 1.61 (median 0.80); only 8 of the 64 ratios were within ±10% of unity. These are diagnostic quantities across different system boundaries, not a closed four-port desiccant-wheel moisture balance. The incomplete process-side flow split, use of published regeneration-inlet settings rather than simultaneous measurements, and absent paired wheel-sector states prevent assigning this departure to one physical cause. The discrepancies are retained, rather than forcing water balance closure, in Table S8.
In 15 of the 64 records, the computed air-stream enthalpy change from states 5 to 7 exceeds the nominal conditional heating-coil load for states 5 to 6. For N50, these quantities are 15.97 and 13.33 kW, respectively. This apparent ordering is a useful consistency warning, but it does not establish a violated first-law inequality because the regeneration-sector wheel exchanges heat and moisture with the process sector and the complete wheel control volume was not instrumented. In particular, h7 ≤ h6 is not universally implied by an adiabatic whole-wheel boundary. A source-setpoint mismatch, missing wheel-side flow data or other incomplete boundary terms may contribute, but none can be identified uniquely. The diagnostic flags for all 64 tests are provided in Table S8.

3.5. Representative Test N14

Test N14 showed a process inlet temperature of 40.61 °C and outlet temperature of 17.30 °C, giving a 23.31 °C reduction. Its process humidity ratios were 0.01125 and 0.007348 kg kg−1 dry air. The published regeneration inlet condition was 32 °C and 8 g kg−1 dry air, and the measured regeneration airflow was 1090 m3 h−1. Table 6 separates measured inputs, reconstructed quantities and conditional heating demand.
Table 6. Experimental, reconstructed and conditional quantities for test N14.
The N14 regeneration inlet condition of 32 °C and 8 g kg−1 was absent from the four supplementary categories. Therefore, N14 was evaluated at nominal 60 °C only and not assigned an externally informed state 6 temperature interval.

3.6. Electrical Auxiliary Consumption

Measured electrical consumption of the three RACU fans ranged from 1.08 to 3.72 kW, with a median of 2.07 kW (Table 7). This is a measured subtotal, not complete electrical consumption of the entire RACU, and was not used to estimate a new complete-system COP.
Table 7. Measured electrical consumption of the three RACU fans.

3.7. Nominal Regeneration Heating Requirements

For all 64 records, Equation (17) was evaluated at the nominal T6 = 60 °C. The calculated demands are plotted by original experiment identifier in Figure 5. The range was 6.30–23.81 kW, with a median of 13.29 kW (Table 8). The large variation reflects differences in inlet temperature, humidity ratio and measured volumetric airflow, and demonstrates that one fixed regeneration heating rate does not describe every investigated operating point.
Figure 5. Conditional regeneration heating-coil requirements across all 64 RACU experimental operating points for nominal T6 = 60 °C. The dashed horizontal line shows the 13.29 kW median. The values are conditional calculations rather than measured heating-coil powers.
Table 8. Conditional heating requirements at nominal T6 = 60 °C.

3.8. Externally Informed Regeneration Heating Intervals

The four supplementary state 6 temperature ranges could be assigned to 30 experiments using exact regeneration-inlet condition matching. Table 9 reports combined group extremes, each determined across the matching original measured flow rates and the permitted conditional T6 interval. These group ranges are not direct heating-coil measurements or confidence intervals.
Table 9. Conditional heating-demand ranges based on supplementary regeneration temperatures.
The corrected Figure 6 was recreated from the 30 matched original experiment identifiers. Its black symbols are nominal 60 °C heating requirements calculated using the original experiment airflow; grey vertical bands represent the lower-to-upper heating-demand range calculated from temperature intervals obtained in separate RACU experiments. The A–D group labels distinguish four inlet-condition categories; the intervals are not original state 6 measurements.
Figure 6. Conditional heating requirements in 30 inlet-matched tests. Vertical grey segments show separate-experiment temperature scenarios, not statistical confidence intervals.
In group C, 24 tests were matched to T5 = 32 °C, w5 = 11 g kg−1 and an external T6 interval of 58–60 °C. The two tests in group D had T5 = 40 °C and an additional lower bound T6 = 40 °C, yielding zero required sensible heating at that boundary. Such a zero-heating value does not demonstrate effective desiccant regeneration. The other 34 original records have no matched supplemental temperature range.

3.9. Comparison of Nominal and Matched-Interval Requirements

The distribution summaries across all nominal tests and the matched group lower and upper scenarios are provided in Table 10. The median lower-bound requirement among 30 matched tests was 9.84 kW; the corresponding upper-bound median was 12.34 kW. This difference represents prescribed scenario variation rather than experimental repeatability or statistical uncertainty.
Table 10. Heating-demand statistics for nominal and supplementary scenarios.

3.10. Necessary Source Compatibility Requirements

The maximum nominal conditional heating requirement of 23.81 kW provides a receiving-system thermal-load reference for external source screening. It does not show that any real engine coolant or exhaust circuit can provide that rate. The corrected Figure 7 presents necessary conditions in a consistent axis orientation: usable waste-heat power increases horizontally and waste-heat source inlet temperature increases vertically. The two dashed thresholds partition the conceptual design space into power-limited, temperature-limited, jointly limited, and simultaneous-criterion regions.
Figure 7. Necessary external-source heat-rate and inlet-temperature screening conditions. Satisfying both thresholds does not establish actual integrated recovery feasibility.
The upper-right region satisfies both necessary inequalities but is not a validated feasibility domain for a designed recovery installation. Actual exchanger performance, source mass flow, source-side heat capacity, approach profiles, losses, duty-cycle variability and auxiliary loads remain unknown. Table 11 states the evidential extent of the thermodynamic conclusions.
Table 11. Evidence classification and limitations of TRACE conclusions.

4. Discussion

4.1. Meaning of Conditional Regeneration Heating Power

The main thermodynamic distinction in TRACE is between conditional heating-coil demand from states 5 to 6 and the observed/reconstructed overall regeneration-path enthalpy change from states 5 to 7. The nominal 6.30–23.81 kW range is calculated for prescribed 60 °C outlet temperature, not measured heater duty. In 15 of 64 records, the reconstructed positive 5–7 enthalpy-flow difference is numerically larger than this nominal 5–6 demand. For example, test N50 gives 15.97 kW (5–7) versus 13.33 kW (5–6). This flags unresolved consistency of the selected boundaries and source state/flow assignments; it is not a direct demonstration that the nominal heater duty is impossible. In particular, treating h7 ≤ h6 as an unconditional wheel-side inequality would omit exchange with the process stream and any other relevant wheel control-volume energy terms. Without paired wheel-sector inlet and outlet observations, heat transfer, losses and transient storage cannot be separated. The inconsistent comparisons are therefore reported openly as diagnostic limitations and not adjusted by inventing test-specific temperatures.

4.2. Contribution of the Supplementary Experimental Clarifications

The actual steady-state volumetric flows were checked against the source workbook, whereas the regeneration-inlet T5 and w5 data originate from published set points rather than filled workbook columns. The separate experiments provide four T6 intervals for 30 exact set-point matches, but matching inlet conditions does not establish equivalence of wheel moisture loading, rotational speed, airflow or transient stability. The magnitude of potential transfer mismatch is not identifiable from the available paired data. These additional intervals are scenario bounds, not pointwise measurements or statistical confidence intervals for the original tests.

4.3. Thermal Demand Versus Sorbent Regeneration Effectiveness

Reducing prescribed regeneration temperature decreases the sensible coil demand. However, sorption performance also depends on adequate desorption, airflow, adsorbent behaviour and operating conditions [5,6,7]. A zero conditional coil load at T6 = T5 does not imply successful moisture regeneration. An optimisation of total-system energy use would require paired evidence for regeneration performance and useful conditioned supply-air capacity, which cannot be validated independently from these records.

4.4. Screening Prospective Waste-Heat Sources

The conditional 6–24 kW range at nominal regeneration temperature gives a receiving-system benchmark for prospective low-grade sources. Nonetheless, a thermally powerful source can be too cold, and a hot source can deliver insufficient usable heat. Figure 7 separates these failure modes. Satisfying both screening inequalities is necessary but not sufficient for practical exchanger performance: realistic hot- and cold-side temperature profiles, heat-transfer area, available flow, time variability, heat losses and parasitic loads remain to be established experimentally for a host working machine.

4.5. Position Relative to Previous Research

Studies by Angrisani et al. [5], Comino et al. [6] and Su et al. [7] addressed desiccant-wheel regeneration performance. Romero-Lara et al. [8] evaluated the combined RACU experimentally, and Giampieri et al. [9] illustrated sorption-based humidity management in a broader energy-integration context. TRACE does not introduce a new desiccant device or an experimentally demonstrated engine recovery architecture. Its contribution is the explicit separation of observed air states, derived heating requirements, externally informed temperature assumptions and source-side conditions that remain unmeasured.

4.6. Thermal and Electrical Energy Boundaries

The source RACU electrical COP excludes supplied regeneration heat. The currently available fan-power measurements are a subset of the unit’s electrical input. Consequently, fan subtotal and nominal heating requirement cannot be combined into a validated whole-energy COP. Potential substitution of external regeneration heat likewise cannot be equated with a proportional fuel saving without reference-system efficiency, parasitic losses and integrated machine operating data.

4.7. Uncertainty and Experimental Limitations

The original 64-record RACU workbook was inspected and used to verify the reconstructed measured states and volumetric flow values. However, it provides steady-state test-level outputs rather than sensor time histories or calibration-based uncertainty models; its regeneration-inlet temperature and humidity columns are unpopulated. Source-paper regeneration-inlet settings and the conditional T6 treatment therefore remain distinct from measured test states. A defensible GUM-style combined standard uncertainty and coverage interval would require documented standard uncertainties, correlations, measurement-section definitions and an experimentally observed or separately validated T6. The additional scenario exercise does not close these gaps.
Under simultaneous illustrative perturbations of p (±1 kPa), airflow (±5%), T5 (±1 °C), w5 (±1 g kg−1) and prescribed T6 (±2 °C), the resulting case-level heating-demand scenario envelopes span 5.02–27.46 kW across the full set of 64 cases. The median lower- and upper-corner values were 11.13 and 15.66 kW, respectively. These ranges are entirely assumption dependent and must not be interpreted as validated experimental uncertainty intervals. The actual unknown test-specific T6, transfer mismatch between separate experiments, systematic model bias and transient operating conditions cannot be quantified by this scenario exercise; Table S9 provides per-record values and scenario inputs.

4.8. Future Source-Side Validation

Future validation should measure usable source heat rate, inlet temperature, source flow and duty-cycle variability in a representative mobile working machine. It should then quantify exchanger effectiveness, pressure losses, ancillary power and wheel regeneration effectiveness under the integrated heat supply. Only such a paired study could demonstrate real recovered energy, modified cooling performance and fuel consumption. TRACE currently defines the required receiving-system conditions against which those measurements could be evaluated.

5. Conclusions

  • All 64 test identifiers were reconciled with published regeneration inlet conditions. Available inputs support psychrometric reconstruction but not original test-level measured heating-coil outlet temperatures.
  • The process-air temperature decrease ranged from 2.10 to 23.55 °C (median 13.79 °C), while inlet-weighted enthalpy differences are diagnostic stream descriptors rather than independently validated cabin-cooling powers. Reconstructed moisture indicators did not close a wheel-level balance: only 8 of 64 system-level ratios fell within ±10% of unity.
  • At prescribed T6 = 60 °C, nominal conditional heating demand ranged from 6.30 to 23.81 kW (median 13.29 kW). Joint hypothetical perturbations of p, T5, w5, air flow and prescribed T6 produce assumption-dependent response envelopes only; experimental confidence or coverage intervals are not supported by the available accuracy and covariance information.
  • Separate experimentally informed T6 intervals could be associated by exact inlet-condition matching with 30 tests; the other 34 were retained in the nominal scenario without interpolation.
  • The data-grounded Figure 6 preserves the actual 30 matched test identifiers and distinguishes original measured flows from supplementary temperature intervals. Neither intervals nor calculated heating loads are direct original state 6 measurements.
  • Heating-coil requirements were defined across states 5 and 6 and distinguished from the combined regeneration-path enthalpy change between states 5 and 7. The latter exceeded nominal calculated coil demand in 15 of 64 cases, indicating unresolved model/state consistency that prevents treating either comparison as a verified complete wheel balance.
  • The corrected Figure 7 identifies the necessary thermal-power and source-temperature screening conditions. No engine-side heat rates, recovered energies, complete-system COP gains or fuel savings were experimentally established.
TRACE provides a reproducible, conditional receiving-side heating-demand benchmark and necessary external-source screening criteria. Its scope remains limited by unavailable measured T6 values, incomplete four-port wheel balances and lack of source-side integration evidence. Neither the scenario envelopes nor the source-condition diagram constitute validation of practical heat recovery.

Supplementary Materials

The following supporting information can be downloaded at: https://www.mdpi.com/article/10.3390/en19235759/s1. Table S1, provenance and published regeneration-inlet conditions; Table S2, reconstructed psychrometric descriptors; Table S3, nominal and externally informed conditional heating requirements; Table S4, supplementary regeneration-temperature (T6) scenarios; Table S5, descriptive statistics and numerical verification; Table S6, original test identifiers and conditional heating-demand data supporting Figure 6; Table S7, necessary thermal-power and temperature criteria supporting Figure 7; Table S8, moisture- and enthalpy-balance consistency diagnostics for all 64 tests; Table S9, illustrative coupled input-perturbation sensitivity envelopes; Code S1, reproduction of the nominal and matched-temperature calculations; and Code S2, reproduction of the coupled input-perturbation sensitivity analysis. The original RACU experimental workbook is held by the source research team and is not redistributed as part of these Supplementary Materials without permission from the data provider.

Author Contributions

Conceptualization, K.D.; methodology, K.D., J.B. and M.J.R.-L.; validation, K.D.; formal analysis, K.D. and J.B.; investigation, K.D., J.B. and M.J.R.-L.; resources, M.J.R.-L.; data curation, K.D. and M.J.R.-L.; visualization, K.D.; writing—original draft preparation, K.D.; writing—review and editing, K.D., M.L., Z.K. and P.M.; supervision, K.D.; project administration, K.D.; funding acquisition, M.L., Z.K. and P.M. All authors have read and agreed to the published version of the manuscript.

Funding

The publication was co-financed by the Polish Minister of Science and Higher Education as part of the Strategy of the Poznan University of Life Sciences for 2024–2026 in the field of improving scientific research and development work in priority research areas. Additional financial support was provided through the University of Warmia and Mazury in Olsztyn, Poland, with funding from the Ministry of Science and Higher Education of the Republic of Poland.

Data Availability Statement

The source RACU workbook supplied by the original research team was used to cross-check the 64 experimental rows; sharing of the source measurements requires the data provider’s permission. Reconstructed outputs, diagnostic comparisons, scenario inputs and reproducibility code are supplied as Supplementary Materials Tables S1–S9 and Codes S1 and S2. Regeneration inlet settings are taken from the source publication, while the external T6 ranges originate from separate experiments and were not measured for the original 64 tests.

Acknowledgments

The authors used ChatGPT (OpenAI) for assistance with language editing, scientific drafting, code development and numerical/graphical checking during manuscript preparation. All scientific interpretations, calculation choices, verification procedures and the final text were assessed and approved by the authors, who retain full responsibility for the content. ChatGPT is available at https://chatgpt.com/ (accessed on 22 November 2026).

Conflicts of Interest

The authors declare no conflicts of interest.

Nomenclature

SymbolDefinitionUnit
RACURenewable air-cooling unit—
DIECDew-point indirect evaporative cooler—
TRACEThermal Regeneration and Air-Conditioning Energy Assessment—
TAir temperature°C
wHumidity ratiokg kg−1 dry air
hHumid-air specific enthalpykJ kg−1 dry air
ρHumid-air densitykg m−3
m ˙ daDry-air mass flowkg s−1
Q ˙ HC,reqConditional heating-coil requirementkW
Q ˙ WH,usableUsable waste-heat powerkW
ΔTminMinimum heat-exchanger temperature approachK

References

  1. Riaz, M.; Mahmood, M.H.; Ashraf, M.N.; Sultan, M.; Sajjad, U.; Hamid, K.; Farooq, M.; Wang, F. Experiments and CFD simulation of an air-conditioned tractor cabin for thermal comfort of tractor operators in Pakistan. Heliyon 2023, 9, e23038. [Google Scholar] [CrossRef] [Scilit] [PubMed]
  2. Riaz, M.; Mahmood, M.H.; Ashraf, M.N.; Sultan, M.; Sajjad, U.; Riaz, F.; Farooq, M.; Zhang, Z. Experimental study of an air-conditioned tractor cabin using CFD analysis for primary and secondary tillage operations in Pakistan. Results Eng. 2025, 26, 104540. [Google Scholar] [CrossRef] [Scilit]
  3. Saidur, R.; Rezaei, M.; Muzammil, W.K.; Hassan, M.H.; Paria, S.; Hasanuzzaman, M. Technologies to recover exhaust heat from internal combustion engines. Renew. Sustain. Energy Rev. 2012, 16, 5649–5659. [Google Scholar] [CrossRef] [Scilit]
  4. Sprouse, C., III; Depcik, C. Review of organic Rankine cycles for internal combustion engine exhaust waste heat recovery. Appl. Therm. Eng. 2013, 51, 711–722. [Google Scholar] [CrossRef] [Scilit]
  5. Angrisani, G.; Minichiello, F.; Roselli, C.; Sasso, M. Experimental analysis on the dehumidification and thermal performance of a desiccant wheel. Appl. Energy 2012, 92, 563–572. [Google Scholar] [CrossRef] [Scilit]
  6. Comino, F.; Táboas, F.; Peci, F.; Ruiz de Adana, M. Detailed experimental analysis of the energy performance of a desiccant wheel activated at low temperature. Appl. Therm. Eng. 2020, 178, 115580. [Google Scholar] [CrossRef] [Scilit]
  7. Su, X.; Tian, S.; Shao, X.; Zhang, X. Experimental and numerical study on low temperature regeneration desiccant wheel: Parameter analysis with a comprehensive energy index. Int. J. Refrig. 2020, 120, 237–247. [Google Scholar] [CrossRef] [Scilit]
  8. Romero-Lara, M.J.; Comino, F.; Ruiz de Adana, M. Experimental assessment of the energy performance of a renewable air-cooling unit based on a dew-point indirect evaporative cooler and a desiccant wheel. Energy Convers. Manag. 2024, 310, 118486. [Google Scholar] [CrossRef] [Scilit]
  9. Giampieri, A.; Ling-Chin, J.; Beeson, C.; Roskilly, A.P. Sustainable Humidity and Thermal Management in UK Indoor Swimming Pools with Liquid Desiccant Technology. Energies 2026, 19, 1823. [Google Scholar] [CrossRef] [Scilit]
  10. Joint Committee for Guides in Metrology. JCGM 100:2008; Evaluation of Measurement Data—Guide to the Expression of Uncertainty in Measurement. BIPM: Sèvres, France, 2008. [Google Scholar] [CrossRef] [Scilit]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.