Input Current Harmonic Suppression in a 12-Pulse Delta/Wye-Connected System Using a Novel Passive Auxiliary Circuit

,
,
,
,
,
,
,
,
…
1
State Grid Heilongjiang Electric Power Research Institute, Harbin 150032, China
2
School of New Energy, Harbin Institute of Technology, Weihai 264200, China
*
Author to whom correspondence should be addressed.
This article belongs to the Section F3: Power Electronics

Abstract

The growing demand for high-power rectification has imposed increasingly strict power quality requirements on modern electrical grids. As prevalent nonlinear front-end devices, multi-pulse rectifiers (MPRs) inject substantial harmonic currents into the AC mains. Targeting the inherent shortcomings of conventional MPRs, this study develops a passive solution—termed the passive auxiliary circuit (PAC)—for harmonic mitigation at the source. The proposed system integrates a 12-pulse main rectifier, based on a delta/wye-connected transformer (DWCT), with the PAC. The PAC contains two interphase reactors (IPRs) and 10 diodes. A detailed operational analysis, grounded in Kirchhoff’s Current Law (KCL), is conducted to determine the circuit’s injection current characteristics across its distinct conduction modes. Furthermore, the IPR turns ratios are evaluated using an analytical input current THD model. The calculated combined apparent power rating of the IPRs is 2.53% of the DC output power, while the auxiliary diode conduction loss is estimated as 1.34ILUon under the constant forward-voltage drop assumption (IL: load current; Uon: diode voltage drop). Simulation and prototype testing support the PAC’s harmonic suppression capability. The measured input current THD is 3.62% at the reported operating point.

1. Introduction

The growing demand for high-power rectification in applications such as more-electric aircraft, hydrogen electrolysis, marine propulsion, and metallurgical processing has placed a premium on grid-side power quality. Within these systems, MPRs remain a prevalent choice due to their ruggedness, design simplicity, and favorable cost structure [1,2,3,4,5]. However, the inherent switching nonlinearity of diode bridges inevitably injects characteristic current harmonics into the AC supply, compromising the overall power factor and potentially violating grid codes. This issue is further exacerbated in modern grids where inverter-based resources are proliferating, necessitating more aggressive harmonic management at the equipment level; related work has also considered load adaptability and fault behavior [6,7].
To address this challenge, considerable research effort has been devoted to DC-side harmonic mitigation. Existing solutions are broadly classifiable into active, passive, and hybrid categories according to their reliance on controllable devices [8,9,10]. Among these, passive approaches have attracted sustained interest owing to their intrinsic reliability, absence of control circuitry, and ability to improve both input current quality and output voltage regulation. Within the passive domain, a further subdivision exists based on the number of sub-circuits employed in the modulation stage: single-passive (pulse-doubling) and dual-passive (pulse-tripling) configurations.
The single-passive family has been extensively explored. Early implementations, exemplified by [11,12,13], utilized a tapped IPR paired with two diodes to reshape the bridge output currents, effectively doubling the effective pulse number and thereby reducing the dominant harmonic magnitudes. Subsequent refinements sought to reduce component count and losses, including voltage-harmonic injection, current imposition, and multi-tap IPRs [14,15,16]. For instance, the topology in [17] replaced the tapped reactor with a single-phase diode bridge connected in parallel with the load, thereby limiting the auxiliary diode current to approximately 3% of the load current. Further simplifications were introduced in [18], where two IPRs and two diodes achieved comparable performance with fewer semiconductor devices. More recently, the schemes reported in [19,20] reduced the magnetic component count to a single IPR while maintaining loss and cost competitiveness.
To push harmonic suppression beyond the limits of single-passive designs, researchers have developed dual-passive circuits that effectively triple the pulse number. The configurations in this category are structurally more elaborate. For example, ref. [21] employed a tapped transformer with one auxiliary winding and six diodes, whereas [22,23] adopted two auxiliary windings with four diodes. Variations on this theme appear in [24,25], which differ primarily in the interconnection of the auxiliary windings. A more integrated design was proposed in [26], featuring a single IPR with three auxiliary windings and six diodes. Hybrid DC-side auxiliary structures have also been investigated [27]. While the dual-passive architectures in [21,22,23,24,25,26] reduce the theoretical input current THD to roughly one-third of the original value, residual harmonics persist, indicating that further improvement remains both possible and desirable.
The DWCT ranks among the most commonly used phase-shifting transformers in MPRs, owing to its simple winding arrangement and built-in electrical isolation [28]. Figure 1 depicts a canonical 12-pulse rectifier employing this transformer arrangement, in which the two three-phase diode bridges are interconnected in parallel via an IPR to supply the DC load. PF, DF, DPF, and phase-shifting magnetic component implementation are also relevant MPR design considerations [29,30]. Comparative studies of 12-, 18-, and 24-pulse rectifiers also illustrate the importance of considering harmonic performance, pulse count, and magnetic requirements together [31].
Figure 1. Configuration of a conventional 12-pulse rectifier employing a DWCT.
Building upon this baseline topology, the present work introduces a triple-passive harmonic reduction strategy that elevates the 12-pulse system of Figure 1 to a 48-pulse equivalent. The core of this upgrade is the proposed PAC, which integrates 10 diodes and two IPRs. Despite its modest component count, the PAC achieves a fourfold increase in effective pulse number, with its calculated combined apparent power rating amounting to 2.53% of the DC output power. Experimental validation confirms that the resulting 48-pulse rectifier attains an input current THD of 3.62%, a marked reduction from the 13.57% THD characteristic of the conventional DWCT-based 12-pulse counterpart.
The contribution of this work is a fully passive DC-side PAC for the isolated delta/wye-connected 12-pulse rectifier, in which a tapped-primary diode path and two secondary diode bridges redistribute the main-bridge currents through five natural conduction modes to obtain equivalent 48-pulse operation. These attributes motivate further investigation of the proposed 48-pulse rectifier for high-power applications requiring harmonic mitigation without auxiliary active switches or complex control strategies. Therefore, the proposed PAC has potential for use in front-end multi-pulse rectifiers for high-power AC–DC conversion systems, such as hydrogen electrolyzers, charging infrastructure, and data-center power supplies, where low input current distortion and high reliability are required.

2. Topology and Characteristic Analysis of the Proposed Delta/Wye-Connected 48-Pulse Rectifier

The proposed 48-pulse rectifier system, as illustrated in Figure 2, is mainly composed of three sections: the main rectifier stage built around the DWCT with two three-phase diode bridges, the PAC, and the DC load.
Figure 2. Circuit topology of the proposed 48-pulse rectifier based on a DWCT and the PAC.
In this configuration, uL and iL denote the output voltage and current supplied to the load, respectively. The main rectifier stage produces two sets of DC outputs, uL1 (iL1) and uL2 (iL2), which feed into the PAC. Additionally, is1 and is2 represent the currents drawn from the secondary-side full-bridge rectifiers embedded within PAC1 and PAC2, respectively.
Figure 3 illustrates the winding arrangement of the DWCT. To achieve the 30° phase shift required between the two three-phase voltage sets feeding the diode bridges, the turns ratio of the DWCT windings is configured as N 1 : N 2 : N 3 = 3 3 : 3 : 1 .
Figure 3. Winding configuration of the DWCT.
The three-phase AC input to the DWCT is defined in (1), where E denotes the RMS value of the phase voltage. Here, f is the supply frequency, ω = 2πf, and ωt is the electrical angle in radians.
u a = 2 E sin ( ω t ) u b = 2 E sin ( ω t − 2 3 π ) u c = 2 E sin ( ω t + 2 3 π )
Correspondingly, the DWCT generates two sets of three-phase output voltages with a 30° phase displacement, as expressed in (2).
u a 1 = 2 3 E sin ( ω t + π / 12 ) u b 1 = 2 3 E sin ( ω t − 7 π / 12 ) u c 1 = 2 3 E sin ( ω t + 3 π / 4 ) u a 2 = 2 3 E sin ( ω t − π / 12 ) u b 2 = 2 3 E sin ( ω t − 3 π / 4 ) u c 2 = 2 3 E sin ( ω t + 7 π / 12 ) .
By applying KCL and the ampere-turn balance principle to the DWCT windings of Figure 3, the relationship among the winding currents can be established as (3).
N 1 i 1 = N 2 i 11 − N 3 i a 2 N 1 i 2 = N 2 i 12 − N 3 i b 2 N 1 i 3 = N 2 i 13 − N 3 i c 2 i a 1 = i 11 − i 13 i b 1 = i 12 − i 11 i c 1 = i 13 − i 12 i a = i 1 − i 3 i b = i 2 − i 1 i c = i 3 − i 2
To facilitate the solution of (3), the switching functions Sa1, Sa2, Sb1, Sb2, Sc1, Sc2 are introduced to denote the conduction states of the corresponding diodes. The input current ia can then be expressed in the compact form of (4).
i a = N 2 N 1 i a 1 − N 3 N 1 ( i c 2 − i a 2 ) = 1 3 S a 1 i L 1 − 3 9 ( S c 2 − S a 2 ) i L 2 S a 1 = 0 ,   ω t ∈ [ 0 ,   π / 6 ) 1 ,   ω t ∈ [ π / 6 ,   5 π / 6 ) 0 ,   ω t ∈ [ 5 π / 6 ,   7 π / 6 ) − 1 ,     ω t ∈ [ 7 π / 6 ,   11 π / 6 ) 0 ,   ω t ∈ [ 11 π / 6 ,   2 π ] S b 1 = S a 1 ∠ − 2 π / 3 S c 1 = S a 1 ∠ + 2 π / 3 S a 2 = S a 1 ∠ − π / 6 S b 2 = S b 1 ∠ − π / 6 S c 2 = S c 1 ∠ − π / 6
Given the quarter-wave symmetry of the input current waveform, the analysis can be restricted to the interval [0, π/2]. Substitution of the switching function definitions into (4) yields the piecewise expression in (5).
i a = 3 9 i L 2 ,       ω t ∈ [ 0 ,   π / 6 ) 1 3 i L 1 + 3 9 i L 2 ,   ω t ∈ [ π / 6 ,   π / 3 ) 1 3 i L 1 + 2 3 9 i L 2 ,   ω t ∈ [ π / 3 ,   π / 2 ) .
The proposed PAC comprises two sub-modules, designated as PAC1 and PAC2, as illustrated in Figure 2. PAC1 is formed by IPR1—which incorporates a secondary winding—along with six diodes, whereas PAC2 employs IPR2 together with four diodes. The winding configurations of both IPRs are depicted in Figure 4.
Figure 4. Winding configurations of IPR1 and IPR2. (a) IPR1. (b) IPR2.
Figure 4 identifies the winding terminals used to define the IPR parameters. In IPR1, the primary winding between n1 and n2 contains Np1 turns and carries voltage up1. Its secondary, s1–s2, has Ns1 turns and voltage us1, while the tapped section t1–t2 contains 2Np11 turns. For IPR2, n3–n4 form the Np2-turn primary with voltage up2 and center tap t3; s3–s4 form the Ns2-turn secondary with voltage us2. The winding voltages therefore satisfy us1/up1 = Ns1/Np1 and us2/up2 = Ns2/Np2. The tap ratio am1 and the secondary-to-primary turns ratios m1 and m2 are defined in (6).
a m 1 = N p 11 N p 1 ,   m 1 = N s 1 N p 1 ,   m 2 = N s 2 N p 2 .
Under three-phase AC supply conditions, the main rectifier stage of the proposed system delivers two DC output voltages, uL1 and uL2, which are identical in waveshape, but displaced by 30° in phase. The instantaneous difference between these two voltages determines the conduction state of the PAC, giving rise to five distinct operating intervals, as illustrated in Figure 5.
Figure 5. Five operating modes of the PAC. (a) Mode 1. (b) Mode 2. (c) Mode 3. (d) Mode 4. I Mode 5.
(1)
Mode 1 occurs when up1 > 0, up2 < 0, us1 > uL, and |us2| > uL. Under these conditions, diodes D1, D4, D6, D7, and D9 are forward-biased and conduct, while all other auxiliary diodes remain reverse-biased. The corresponding equivalent circuit is depicted in Figure 5a. Application of KCL and the ampere-turn balance principle to this configuration yields the current relationships expressed in (7).
( 1 2 − a m 1 ) i L 1 = m 1 i s 1 1 2 i L 1 = m 2 i s 2 i L 2 = 0 i L = i L 1 + i s 1 + i s 2 .
(2)
Mode 2 is triggered when up1 decreases to the point where us1 < uL, while |us2| > uL still holds. In this interval, the single-phase full-bridge rectifier on the secondary side of PAC1 becomes reverse-biased and ceases conduction. Only D1, D7, and D9 remain conducting, with the remaining auxiliary diodes turned off. The PAC now operates according to Figure 5b, and the bridge currents iL1 and iL2 are governed by (8).
( 1 2 − a m 1 ) i L 1 = ( 1 2 + a m 1 ) i L 2 1 2 i L 1 = 1 2 i L 2 + m 2 i s 2 i s 1 = 0 i L = i L 1 + i L 2 + i s 2 .
(3)
Mode 3 begins as up1 falls to zero and remains there, while up2 rises from negative to positive. During this period, |us2| < uL causes the secondary-side rectifier of PAC2 to be reverse-biased and inactive. Only D1 and D2 are forward-biased and share the load current iL equally. The equivalent circuit of this mode is shown in Figure 5c, with the corresponding current expressions given in (9).
i L 1 = i L 2 i s 1 = i s 2 = 0 i L = i L 1 + i L 2 .
(4)
Mode 4: Similarly, when up1 < 0, up2 > 0, and |us1| < uL, us2 > uL, D2, D8 and D10 are conducting, and the circuit operates as per Figure 5d.
(5)
Mode 5: When up1 continues to decrease until |us1| > uL, and us2 > uL, D2, D3, D5, D8 and D10 turn on. The operating configuration for this final mode is illustrated in Figure 5e.
By combining the current relationships derived for Modes 1 through 3—as summarized in (7)–(9)—the complete piecewise expressions for iL1 and iL2 can be obtained, as given in (10).
i L 1 = i m 1   mode 1 i m 2   mode 2 i m 3   mode 3 i m 4   mode 4 i m 5   mode 5     i L 2 = i m 5   mode 1 i m 4   mode 2 i m 3   mode 3 i m 2   mode 4 i m 1   mode 5   i m 1 = 2 m 1 m 2 m 2 ( 2 m 1 − 2 a m 1 + 1 ) + m 1 i L i m 2 = m 2 ( 1 + 2 a m 1 ) 2 ( m 2 + a m 1 ) i L i m 3 = 1 2 i L i m 4 = m 2 ( 1 − 2 a m 1 ) 2 ( m 2 + a m 1 ) i L i m 5 = 0 .
Equation (10) gives five possible values for each bridge current, including zero. The operating-mode sequence produces an eight-step waveform for each bridge, with a 30° displacement between iL1 and iL2.
At the selected turns ratios of am1 = 0.246, m1 = 14.36, and m2 = 28.47, the normalized current pairs (iL1/iL, iL2/iL) for Modes 1–5 are (0.965950, 0), (0.739609, 0.251824), (0.500000, 0.500000), (0.251824, 0.739609), and (0, 0.965950), respectively. Substituting the corrected branch currents into (5), following the mode sequence in Figure 6, reproduces the 13 intervals of the first-quarter-cycle input current in (14). The total and fundamental RMS currents are 0.26289486iL and 0.26270721iL, respectively. Equation (15) therefore gives a theoretical input current THD of 3.7804%, consistent with the reported value of 3.78% after rounding.
Figure 6. Schematic waveforms of the 48-pulse rectifier: Branch currents, input current, and circuit voltages.
Exploiting the symmetry of the operating modes, the secondary-side output currents of the PAC1 and PAC2 full-bridge rectifiers—denoted as is1 and is2, respectively—can be derived from (7)–(9), yielding (11) and (12).
i s 1 = m 2 ( 1 − 2 a m 1 ) m 2 ( 2 m 1 − 2 a m 1 + 1 ) + m 1 i L   0 0 0 m 2 ( 1 − 2 a m 1 ) m 2 ( 2 m 1 − 2 a m 1 + 1 ) + m 1 i L   ,
i s 2 = m 1 m 2 ( 2 m 1 − 2 a m 1 + 1 ) + m 1 i L a m 1 a m 1 + m 2 i L 0 a m 1 a m 1 + m 2 i L m 1 m 2 ( 2 m 1 − 2 a m 1 + 1 ) + m 1 i L .
For a 50 Hz supply, the linearized voltage up follows a trapezoidal profile at 300 Hz. Applying Kirchhoff’s Voltage Law (KVL) to Figure 2 relates this voltage to the main-bridge output voltages and the IPR primary voltages, as expressed in (13).
u L 1 − u L 2 = u p 1 − u p 2 = u p .
Over one electrical cycle, 0 ≤ ωt ≤ 2π, the symmetric load voltage waveform contains 48 pulses. The analysis therefore approximates uL as a constant DC voltage.
Each complete step of the input current waveform occupies an electrical angle of π/24. Substituting (10) into (5) yields the quarter-period expression of ia for the 48-pulse rectifier, as presented in (14).
i a = 0             ω t ∈ [ 0 ,   π / 48 ) 3 9 i m 4         ω t ∈ [ π / 48 ,   π / 16 ) 3 9 i m 3         ω t ∈ [ π / 16 ,   5 π / 48 ) 3 9 i m 2         ω t ∈ [ 5 π / 48 ,   7 π / 48 ) 3 9 i m 1         ω t ∈ [ 7 π / 48 ,   3 π / 16 ) 1 3 i m 4 + 3 9 i m 2     ω t ∈ [ 3 π / 16 ,     11 π / 48 ) 3 + 3 9 i m 3     ω t ∈ [ 11 π / 48 ,   13 π / 4 8 ) 1 3 i m 2 + 3 9 i m 4   ω t ∈ [ 13 π / 4 8 ,   5 π / 16 ) 1 3 i m 1         ω t ∈ [ 5 π / 16 ,   17 π / 48 ) 1 3 i m 2 + 2 3 9 i m 4     ω t ∈ [ 17 π / 48 ,   19 π / 48 ) 3 + 2 3 9 i m 3     ω t ∈ [ 19 π / 48 ,   7 π / 16 ) 1 3 i m 4 + 2 3 9 i m 2   ω t ∈ [ 7 π / 16 ,   23 π / 48 ) 2 3 9 i m 1         ω t ∈ [ 23 π / 48 ,   π / 2 ] .
On the basis of (10)–(14) and the inherent symmetry of the circuit, Figure 6 presents the complete set of operating current and voltage waveforms for the proposed 48-pulse rectifier.
The analytical evaluation of input current THD uses the turns ratios am1, m1, and m2 as the design variables. The THD of ia is evaluated using (15), where Ia and Ia,fund represent the RMS value and the fundamental RMS value of ia, respectively.
THD i a = I a 2 − I a , fund 2 I a , fund I a = 1 2 π ∫ 0 2 π i a 2 ( ω t ) d ( ω t ) I a , fund = 1 2 π ∫ 0 2 π i a ( ω t ) sin ( ω t ) d ( ω t ) .
The numerical evaluation in MATLAB R2023b yielded the selected turns ratios am1 = 0.246, m1 = 14.36, and m2 = 28.47. At these values, (15) gives an analytical input current THD of 3.7804%, rounded to 3.78%. Figure 7 shows the single-parameter THD trends for this design.
Figure 7. Single-parameter THD curves for the IPR turns ratio design.
Each turns ratio was varied from 95% to 105% of its selected value in increments of 0.5%, giving 21 values per ratio and 9261 combinations. Equations (5), (10), (14), and (15) were evaluated with the transition angles in Equation (14) fixed at their selected design values. This mathematical perturbation isolates the effect of the ratios on the current levels at prescribed angles. A physical winding-tolerance analysis would also recalculate the transitions for each ratio combination. Within the fixed-angle model, the THD ranged from 3.7804% to 3.8105%, and the illustrative rounded ratio set (0.250, 14, 28) gave 3.7839%.

3. Analysis of Magnetic Component Capacity and Diode Conduction Loss of the PAC

3.1. Capacity Evaluation of the PAC

This subsection presents the theoretical capacity calculation for the magnetic components within the proposed PAC, based on the selected turns ratios determined in the preceding section.
For the steady-state capacity calculation, uL and iL are approximated by their DC average values UL and IL, respectively. Equation (16) gives UL from the transformer output voltage expressions in (2) and the voltage waveforms in Figure 6.
U L ≈ 2 3 × 3 × cos 15 ° × E ≈ 0.79 E .
Using (10)–(12), the RMS values of the relevant operating currents—iL1, iL2, is1, is2 and it1t2—are computed and summarized in (17).
I L 1 = I L 2 ≈ 0.576 I L I s 1 ≈ 0.00854 I L I s 2 ≈ 0.01042 I L I t 1 t 2 ≈ 0.178 I L .
From (16) and the voltage relationships depicted in Figure 6, the RMS voltages Up1 and Us1 are obtained as in (18).
U p 1 ≈ 0.045 U L U s 1 = 14.36 U p 1 ≈ 0.645 U L .
With reference to the winding configuration of IPR1 in Figure 4a, its apparent power rating SIPR1 is given by (19).
S IPR 1 = 1 2 × [ 2 × ( 1 2 − a m 1 ) U p 1 I L 1 + 2 a m 1 U p 1 I t 1 t 2 + U s 1 I s 1 . ] ≈ 0.0113 U L I L
Similarly, the RMS voltages Up2 and Us2 associated with IPR2 are expressed in (20).
U p 2 ≈ 0.032 U L U s 2 = 28.47 U p 2 ≈ 0.913 U L .
Based on the IPR2 winding arrangement shown in Figure 4b, the corresponding apparent power SIPR2 is formulated in (21).
S IPR 2 = 1 2 × ( U p 2 I L 1 + U s 2 I s 2 . ) ≈ 0.014 U L I L
Summing the individual contributions yields the total capacity of the PAC, as presented in (22).
S PAC = S IPR 1 + S IPR 2 ≈ 0.0253 U L I L .
The RMS quantities in (17)–(22) were evaluated using the mode durations and linearized waveforms in Figure 6. Modes 1 and 5 each occupy one-eighth of the repeating interval, while Modes 2–4 each occupy one-quarter. Using unrounded values gives calculated IPR1 and IPR2 winding apparent power ratings of 1.1302% and 1.3992% of the DC output power, respectively. Their sum is 2.5294%, rounded to 2.53%. These are theoretical ratings under the idealized model.

3.2. Diode Conduction Loss of the PAC

The diode conduction loss of the PAC1 can be calculated as
P loss _ PAC 1 = 2 I D 1 _ avg U on + 2 I s 1 _ avg U on ≈ 1.32 I L U on .
where ID1_avg, Is1_avg and Is2_avg represent the average value of iD1, is1 and is2, Uon represents the forward-voltage drop of the diode.
The diode conduction loss of the PAC2 can be calculated as
P loss _ PAC 2 = 2 I s 2 _ avg U on ≈ 0.02 I L U on .
The combined apparent power rating of the PAC magnetic components is approximately 2.53% of the output power. Using (23) and (24), the total auxiliary diode conduction loss relative to the output power is
P loss _ PAC 1 + P loss _ PAC 2 U L × I L ≈ 1.34 × U on U L .
This ratio quantifies the auxiliary diode conduction loss as a fraction of the output power under the constant forward-voltage drop assumption.
The auxiliary diode conduction loss estimate characterizes one contribution to converter losses under a constant forward-voltage drop assumption. In practice, the diode forward voltage depends on current and junction temperature. Relative to the conventional 12-pulse rectifier, the PAC adds 10 auxiliary diodes and replaces the original IPR with two IPRs. The net loss change therefore includes auxiliary diode conduction, the difference in IPR winding and core losses, and changes in the main-bridge and phase-shifting-transformer losses caused by the reshaped currents. The corresponding efficiency comparison requires AC input and DC output active power measurements for both configurations at matched output power.

4. Simulation and Experimental Results

4.1. Performance Evaluation of the Proposed Rectifier

To experimentally verify the harmonic suppression performance of the proposed 48-pulse rectifier equipped with the PAC, a 1 kW laboratory-scale prototype was built. The experimental configuration is depicted in Figure 8. A Chroma-61702 programmable AC source (Chroma ATE Inc., Taoyuan, Taiwan) delivers the three-phase input voltage, while a HIOKI-PW3198 power quality analyzer (Hioki E.E. Corporation, Ueda, Nagano, Japan) is employed to record the relevant voltage and current waveforms. SQL60A1600V diode modules (60 A/1600 V, commercially available), which provide a sufficient safety margin against voltage stresses during testing, are adopted as the rectifier bridge devices.
Figure 8. Experimental prototype of the proposed 48-pulse rectifier with PAC.
Table 1 lists the parameters used for the simulations and prototype tests. The analytical and simulation models adopt ideal operating conditions with a balanced three-phase supply; transformer leakage inductance and diode forward-voltage drops are omitted. The experimental comparison with and without the PAC was conducted at a single operating point using a nominally balanced 50 Hz three-phase supply, an input phase voltage of 160 V RMS, and a 15 Ω resistive load.
Table 1. Key simulation and experimental parameters.
The simulated harmonic magnitudes in Figure 9b and Figure 10b are expressed as percentages of the respective fundamental current. The simulation FFT window and THD cutoff order are unavailable in the retained records, so an exactly matched harmonic bandwidth for the simulation and experiment cannot be established. The measured harmonic magnitudes are referenced to the fundamental current of each test. Table A1 in Appendix A gives representative measured magnitudes and the THD-F readings from the PW3198.
Figure 9. Results for the baseline 12-pulse rectifier without the PAC: (a) simulated input currents; (b) simulated current spectrum; (c) measured input currents; (d) measured current spectrum; (e) bar plot of the measured harmonic magnitudes.
Figure 10. Input current and harmonic spectrum of the 48-pulse rectifier with PAC. (a) Simulated input currents. (b) Simulated input current spectrum. (c) Experimental input currents. (d) Experimental input current spectrum.
Without the PAC, the simulated current has a 12-step shape that approximates a sinusoid (Figure 9a). Spectral analysis (Figure 9b) gives an input current THD of 14.83%, with the largest components at the 11th, 13th, 23rd, and 25th harmonic orders, consistent with the characteristic 12k ± 1 pattern.
The measurements in Figure 9c,d show a 12-step current waveform with a THD of 13.57%. Figure 9e shows that the characteristic 12k ± 1 orders remain dominant, alongside residual 5th- and 7th-order components. Supply asymmetry and mismatches in windings or components may disturb current sharing and harmonic cancellation, providing possible explanations for these residuals.
With the PAC connected, the simulated and measured currents exhibit 48 steps and more closely follow a sinusoid than the baseline waveforms (Figure 10a,c). The simulated THD decreases from 14.83% to 3.69%, while the measured value falls from 13.57% to 3.62% (Figure 10b,d). The measured spectrum also shows substantial reductions in the 11th, 13th, 23rd, and 25th characteristic harmonics. From the measured THD values, the calculated distortion factor increases from 0.991 to 0.999. Under balanced sinusoidal supply conditions, the displacement factor is approximately unity. The distortion factors are derived from THD and do not represent measurements of total power factor or conversion efficiency.
The ideal waveform gives an analytical THD of 3.78%. The reported simulation and measurement give 3.69% and 3.62%, respectively. The harmonic processing information in Section 4.1 does not support a quantitative attribution of the differences.
The idealized simulation in Figure 10b contains pronounced 47th- and 49th-order harmonics, as expected from the analytical waveform. Their measured magnitudes in Figure 10d are substantially lower, at 0.50% and 0.39%, respectively. Practical nonidealities, including leakage inductance, inter-winding capacitance, frequency-dependent winding losses, and diode characteristics, may contribute to these spectral differences. These factors provide a qualitative interpretation of the observed behavior. Further modeling using measured prototype parameters would help quantify their respective contributions.
A comparison of Figure 9d and Figure 10d further shows that applying the PAC reduces the measured 5th- and 7th-order harmonic magnitudes, alongside the attenuation of the characteristic harmonics.
Despite differences in the detailed harmonic distributions, the simulation and experimental results both demonstrate attenuation of the targeted characteristic harmonics. First, the target characteristic harmonics—namely the 11th, 13th, 23rd, and 25th—are substantially suppressed, decreasing from initial levels of 9.09%, 6.47%, 3.79%, and 3.26% to 1.74%, 1.16%, 1.13%, and 1.00%, respectively. Second, the measured input current THD decreased from 13.57% to 3.62%, demonstrating the harmonic reduction achieved at the tested operating point.
Figure 11 compares the measured input current harmonics of orders 2–25 with and without the PAC, using the analyzer readings in Figure 9d and Figure 10d.
Figure 11. Measured low-order input current harmonics before and after applying the PAC.
Each series in Figure 11 is normalized to the fundamental current of its corresponding test. Assessment of IEEE 519-2022 [32] compliance at an installation requires the applicable PCC maximum demand load current and short-circuit ratio.
Figure 12a records the three-phase input waveforms ua, ub, and uc, with a measured phase voltage of 160 V RMS. For the two DC outputs, simulation (Figure 12b) and measurement (Figure 12c) show six-pulse voltage waveforms uL1 and uL2 displaced by 30°. Small notches near the voltage minima are consistent with the expected behavior of the DWCT-based main rectifier.
Figure 12. Experimental and simulated waveforms of the input three-phase voltages (ua, ub, and uc) and output voltages (uL1 and uL2) of the main circuit. (a) ua, ub, and uc (experimental results). (b) uL1 and uL2 (simulation results). (c) uL1 and uL2 (experimental results).
The simulation and experimental waveforms of the IPR terminal voltages—up1, up2, us1, and us2—are presented in Figure 13. It is observed that up1 and us1 share the same phase with an amplitude ratio of 1:m1, while up2 and us2 are trapezoidal in-phase waves with an amplitude ratio of 1:m2. Furthermore, up1 is the complement of up2. These findings are in good agreement with the theoretical analysis.
Figure 13. Waveforms of IPR terminal voltages up1, up2, us1, and us2. (a) Simulation results. (b) Experimental results.
Figure 14a,b present the simulated current waveforms of iL1, iL2, is1, and is2. The main-bridge currents iL1 and iL2 exhibit eight-step waveforms containing a zero level and displaced by 30°. The auxiliary current is1 has a pulsed waveform, while is2 exhibits three current levels, including zero. These simulated waveform features are consistent with the theoretical operating-mode analysis. The experimental iL1 trace in Figure 14c retains the stepped profile and exhibits smoother transitions than its simulated counterpart. The branch-current RMS values in (17) and the corresponding IPR apparent power ratings in Section 3.1 are analytical estimates based on the idealized operating model.
Figure 14. Simulated and experimental current waveforms of iL1, iL2, is1, and is2. (a) iL1 and iL2 (simulation results). (b) is1 and is2 (simulation results). (c) iL1 (experimental result).
Simulated and experimental load voltage waveforms are presented in Figure 15. A comparison of Figure 15a,b reveals that the PAC elevates the number of voltage pulses per AC cycle from 12 to 48, while significantly diminishing the voltage ripple. This confirms that the PAC successfully quadruples the effective pulse count of the rectifier. The experimental uL trace recorded after engaging the PAC is displayed in Figure 15c, exhibiting a small voltage ripple.
Figure 15. The load voltage uL. (a) Before using PAC (simulation result). (b) After using PAC (simulation result). (c) After using PAC (experimental result).
The 1 kW prototype demonstrates the proposed harmonic mitigation principle, while the calculated combined IPR apparent power rating of 2.53% of the DC output power provides a sizing reference for further development. At a fixed DC output voltage, higher power increases the winding and diode current stresses and temperature rise. Designs with higher voltage ratings require checks of magnetic volt-seconds and flux density, winding insulation, and diode reverse-voltage margins. Source and transformer leakage inductances affect commutation overlap, while IPR leakage inductance can affect auxiliary conduction timing and current sharing. Winding and core losses, cooling, installed volume, cost, and electromagnetic compatibility require application-specific assessment. Higher-power implementation therefore remains subject to further design and validation.
Figure 7 presents the single-parameter THD trends within the fixed-angle analytical model described in Section 2, with a calculated THD of 3.78% at the selected design. In a physical circuit, a deviation in the tap ratio changes the current division at the IPR1 taps, while deviations in the secondary-to-primary turns ratios change the secondary voltages that determine when the auxiliary rectifiers conduct. The resulting changes in the current steps can reduce cancellation of the characteristic input current harmonics.
Finite IPR magnetizing inductance introduces magnetizing current and can change the current division predicted by the ideal ampere-turn balance. Leakage inductance limits the rate at which auxiliary branch currents change during commutation. The total forward-voltage drop along each conducting diode path shifts the threshold for current injection, and unequal drops in paths used on opposite half-cycles can introduce asymmetry. The effects of inductance variation and diode mismatch on THD require quantitative verification with measured component parameters or dedicated tests.
The fault paths in Figure 2 and Figure 5 can be illustrated using D1 and D6 in PAC1. If D1 opens, the normal load current path through its tap is interrupted in Modes 1 and 2, and the equal current division through D1 and D2 in Mode 3 is lost. If D6 opens, the D6–D4 conduction path of the PAC1 auxiliary rectifier is interrupted in Mode 1. These open-circuit faults can distort the intended current steps and weaken cancellation of the characteristic input current harmonics.
A shorted D1 directly connects its tap to the positive DC terminal. If D2 becomes forward-biased, it can complete a low-impedance loop between the IPR1 taps. A shorted D6 clamps one end of the IPR1 secondary winding to the same terminal. On the opposite voltage polarity, forward conduction of D3 can then complete a low-impedance loop across the secondary winding. The resulting currents can overstress the affected windings and diodes, so fault detection and isolation are important. Fault-current peaks and post-fault THD remain to be quantified.

4.2. Comparison with the Baseline and Existing Rectifier Schemes

Table 2 compares the conventional 12-pulse baseline and the proposed PAC with the schemes in [8,11,13,22]. The analytical baseline and measured results for the present prototype are distinguished in the accompanying text. For the proposed PAC, the auxiliary diode conduction loss is estimated from a constant forward-voltage model, and the combined IPR apparent power rating is calculated from winding RMS quantities. The prototype comparison used a nominally balanced 50 Hz supply, a phase voltage of 160 V RMS, and a 15 Ω resistive load.
Table 2. Comparative evaluation of harmonic suppression performance and hardware requirements among the proposed 48-pulse rectifier and existing solutions.
Reference [8] reports 3.46% measured input current THD for its 3 kW prototype, compared with 3.62% for the present laboratory prototype at the operating point in Section 4.1. The reported values are specific to their respective test conditions. The auxiliary circuit in [8] comprises one IPR, seven diodes (three in the primary-tap paths and four in the auxiliary bridge), and two MOSFETs with their associated gate-drive circuitry. The present PAC uses two IPRs and 10 diodes.
Passive pulse-doubling schemes such as [11,13] use fewer auxiliary components but provide a lower pulse count. The present PAC employs two IPRs and 10 diodes to obtain 48-pulse operation without auxiliary active switches. This structural difference illustrates a trade-off between pulse multiplication and auxiliary hardware. The calculated magnetic ratings should be considered separately from installed volume, cost, and overall efficiency.
The approximately 15.2% THD is the ideal analytical value calculated from (5) with (iL1 = iL2 = IL/2); the corresponding simulated and measured values are 14.83% and 13.57%, respectively. The experimental comparison used a nominally balanced 50 Hz supply, a phase voltage of 160 V RMS, and a 15 Ω resistive load. Literature results should be considered together with their respective operating conditions and hardware requirements.
The conventional 12-pulse rectifier uses one IPR. The proposed configuration replaces that unit with two IPRs and adds 10 auxiliary diodes. The net change in installed volume and mass depends on the dimensions and mass of the original and replacement components, as well as diode mounting, cooling, electrical clearances, and wiring. The calculated combined IPR rating of 2.53% of the output power provides a starting point for magnetic sizing. Actual magnetic component dimensions depend on the core, winding, and mounting design. For applications with tight space or weight constraints, the harmonic reduction should be weighed against the installed volume and mass of the two complete assemblies. Measurements of both assemblies at the same rated output power are needed to quantify the difference in volumetric and gravimetric power density.
For clarity and balance, the main advantages and limitations of the proposed 48-pulse rectifier with the PAC are summarized in Table 3.
Table 3. Summary of the main advantages and limitations of the proposed 48-pulse rectifier with the PAC.
The experimental comparison covers one operating point of the 1 kW laboratory prototype. Load-sweep and nonideal-supply tests, separate measurements of iL2, is1, and is2, complete winding/core specifications, and paired input/output active power data are unavailable in the retained records. Validation at other loading points requires measurements of input current THD and individual harmonics across the load range and under supply-voltage unbalance or varying source impedance. The second main-bridge current and the two auxiliary branch currents should also be measured to verify conduction timing and current sharing. Higher-power validation requires documented winding and core specifications, checks of commutation and thermal performance, and measurements of input and output active power under matched conditions to compare conversion efficiency.

5. Conclusions

This paper has developed and experimentally validated a 48-pulse rectifier system that integrates a DWCT with a PAC. The key novelty lies in the PAC architecture—comprising two IPRs and 10 diodes—which enables pulse multiplication by a factor of four. The proposed PAC achieves pulse multiplication without auxiliary active switches or gate-drive circuitry, with a corresponding requirement for two IPRs and 10 diodes.
The selected IPR turns ratios were am1 = 0.246, m1 = 14.36, and m2 = 28.47. The calculated combined IPR apparent power rating is approximately 2.53% of the DC output power, and the auxiliary diode conduction loss is estimated as 1.34ILUon under the constant forward-voltage drop assumption. These results quantify the auxiliary magnetic rating and diode conduction loss of the proposed harmonic suppression strategy.
The harmonic mitigation performance at the reported operating point is supported by both simulation and experimental measurements. The key findings are summarized as follows:
(1)
The load voltage waveform is successfully converted from a 12-pulse to a 48-pulse profile;
(2)
At the reported operating point, substantial harmonic reduction is achieved: the measured input current THD declines from 13.57% to 3.62%, with the characteristic (12k ± 1)th harmonics effectively attenuated.
The simple, fully passive 48-pulse configuration has potential for industrial harmonic mitigation; verification at higher power levels remains necessary. For a specific installation, harmonic performance at the PCC requires a separate assessment.

Author Contributions

Conceptualization, B.G.; methodology, S.R. and F.M.; software, H.G. and W.G.; validation, M.Z. and Z.L. (Zhipeng Liu); formal analysis, C.Y. and X.L.; investigation, Y.H.; data curation, R.Z. and J.Z.; writing—original draft preparation, K.Y. and S.R.; writing—review and editing, H.C.; visualization, Z.L. (Zhiyang Liu) and Y.D.; supervision, B.G.; project administration, B.G.; funding acquisition, B.G. and F.M. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by the State Grid Corporation of China Technology Project (Project No. 522437260001).

Data Availability Statement

The original contributions presented in this study are included in the article. Further inquiries can be directed to the corresponding author.

Conflicts of Interest

Authors Bowen Gu, Shuang Rong, Huaiyu Guo, Wanlin Guan, Mingjiang Zhang, Zhipeng Liu, Chen Yang, Xueting Lei, Yuanting Hu, Rui Zhou, Jun Zheng, Hongyu Chen, Zhiyang Liu, and Yifan Dong were employed by State Grid Heilongjiang Electric Power Research Institute. The remaining authors, Fangang Meng and Kailai Ye, were affiliated with Harbin Institute of Technology, Weihai, and declare that, apart from the disclosed research funding, the research was conducted in the absence of any commercial or financial relationships that could be construed as potential conflicts of interest. The authors declare that this study received funding from the State Grid Corporation of China Technology Project (Project No. 522437260001). The funder had the following involvement with the study: providing financial support and participating in the research through its affiliated research institute, State Grid Heilongjiang Electric Power Research Institute. Researchers from this institute contributed to the study through research conceptualization, methodology development, software implementation, experimental validation, formal analysis, investigation, data curation, manuscript preparation and revision, supervision, and project administration. The specific contributions of individual authors are detailed in the Author Contributions section of the manuscript.

Abbreviations

The following abbreviations are used in this manuscript:
MPRMulti-pulse rectifier
DWCTDelta/wye-connected transformer
PACPassive auxiliary circuit
IPRInterphase reactor
THDTotal harmonic distortion
KCLKirchhoff’s Current Law
KVLKirchhoff’s Voltage Law

Appendix A. Representative Measured Harmonic Results

The retained PW3198 displays in Figure 9d and Figure 10d verify the channel 1 current selection, the percent-of-fundamental display, the interharmonic display status (off), and the reported THD-F readings. Table A1 lists representative measured harmonics and the two instrument readings.
Table A1. Representative measured input current harmonics before and after applying the PAC.
According to the HIOKI PW3198 specifications(Hioki E.E. Corporation, Ueda, Nagano, Japan), the analyzer uses a 10-cycle analysis window at 50 Hz, 4096 points per window, and a maximum harmonic order of 50 for its THD-F analysis. The retained displays do not independently verify the complete acquisition configuration, the analysis window settings used for the tests, or the total recording duration. Equation (A1) gives the fundamental-referenced THD-F definition for the specified harmonic range.
THD F = ∑ h = 2 50 I h 2 I 1 × 100 %
Here, Ih is the RMS current of the hth harmonic, and I1 is the fundamental RMS current.

References

  1. Singh, B.; Gairola, S.; Singh, B.N.; Chandra, A.; Al-Haddad, K. Multi-pulse AC-DC converters for improving power quality: A review. IEEE Trans. Power Electron. 2008, 23, 260–281. [Google Scholar] [CrossRef] [Scilit]
  2. Du, Q.; Gao, L.; Li, Q.; Li, T.; Meng, F.; Meng, G.F. Harmonic reduction methods at DC side of parallel-connected multipulse rectifiers: A review. IEEE Trans. Power Electron. 2021, 36, 2768–2782. [Google Scholar] [CrossRef] [Scilit]
  3. Chen, J.; Shen, Y.; Chen, J.; Bai, H.; Gong, C.; Wang, F. Evaluation on the autoconfigured multipulse AC/DC rectifiers and their application in more electric aircrafts. IEEE Trans. Transp. Electrif. 2020, 6, 1721–1739. [Google Scholar] [CrossRef] [Scilit]
  4. Tian, H.; Cui, H.; Han, W.; M, J.S.; Liang, G.; Chen, M.; Mekhilef, S. High-efficiency asymmetrically designed three-phase virtual 48-pulse power supply for electrolytic hydrogen. IEEE Trans. Power Electron. 2025, 40, 10335–10342. [Google Scholar] [CrossRef] [Scilit]
  5. Tian, H.; Han, W.; Sathik, M.J.; Chen, M.; Liang, G.; Mekhilef, S. High-efficiency, high-power asymmetrically designed three-phase power supply for electrolytic hydrogen production. IEEE Trans. Power Electron. 2025, 40, 92–97. [Google Scholar] [CrossRef] [Scilit]
  6. Li, Q.; Yan, X.; Wang, Z.; Ma, Y.; Liao, W.; Ma, K.; Jin, L.; Lei, E.; Wen, B. Study on hybrid harmonic mitigation technique and load adaptability of multi-pulse rectifiers. In Proceedings of the 2025 IEEE 8th International Electrical and Energy Conference (CIEEC), Changsha, China, 16–18 May 2025; pp. 1560–1565. [Google Scholar]
  7. Yang, C.; Zhang, F.; Cheng, L.; Zhang, Z. Open-circuit fault research on asymmetric delta-polygon 18-pulse autotransformer rectifier unit for more electric aircraft. IEEE Trans. Power Electron. 2022, 37, 14615–14630. [Google Scholar] [CrossRef] [Scilit]
  8. Lian, Y.; Yang, S.; Yang, W. Optimum design of 48-pulse rectifier using unconventional interphase reactor. IEEE Access 2019, 7, 61240–61250. [Google Scholar] [CrossRef] [Scilit]
  9. Abdollahi, R.; Gharehpetian, G.B.; Anvari-Moghaddam, A.; Blaabjerg, F. An improved 24-pulse rectifier for harmonic mitigation in more electric aircraft. IET Power Electron. 2021, 14, 2007–2020. [Google Scholar] [CrossRef] [Scilit]
  10. Sun, R.; Zeng, G.; Yang, B.; Wu, L.; Xu, W.; Jing, L.; Wu, X.; Lei, J.; Zhang, Y. A robust load adaptability method to suppress AC harmonic for series-connected 12-pulse rectifier with DC side active harmonic injection circuit. IEEE Trans. Power Electron. 2025, 40, 12794–12815. [Google Scholar] [CrossRef] [Scilit]
  11. Singh, B.; Bhuvaneswari, G.; Garg, V.; Gairola, S. Pulse multiplication in AC-DC converters for harmonic mitigation in vector-controlled induction motor drives. IEEE Trans. Energy Convers. 2006, 21, 342–352. [Google Scholar] [CrossRef] [Scilit]
  12. Singh, B.; Bhuvaneswari, G.; Garg, V. Power-quality improvements in vector-controlled induction motor drive employing pulse multiplication in AC-DC converters. IEEE Trans. Power Deliv. 2006, 21, 1578–1586. [Google Scholar] [CrossRef]
  13. Choi, S.; Lee, B.S.; Enjeti, P.N. New 24-pulse diode rectifier systems for utility interface of high-power AC motor drives. IEEE Trans. Ind. Appl. 1997, 33, 531–541. [Google Scholar] [CrossRef] [Scilit]
  14. Chen, X.; Bai, T.; Wang, Y.; Gong, J.; Mu, X.; Chang, Z. A novel series 24-pulse rectifier operating in low harmonic state based on auxiliary passive injection at DC side. Electronics 2024, 13, 1160. [Google Scholar] [CrossRef] [Scilit]
  15. Prakash, P.S.; Kalpana, R.; Mohankrishna, B.; Singh, B. Harmonic mitigation in 12-pulse bridge rectifier using DC current imposition technique. In Proceedings of the 2020 IEEE International Conference on Power Electronics, Smart Grid and Renewable Energy (PESGRE), Kerala, India, 2–4 January 2020; pp. 626–631. [Google Scholar]
  16. Lian, Y.; Yang, S.; Zeng, X.; Ben, H.; Yang, W. Comparative analysis of two different interphase reactors applied in 36-pulse diode rectifier. IET Electr. Power Appl. 2020, 14, 1011–1022. [Google Scholar] [CrossRef] [Scilit]
  17. Meng, F.; Xu, X.; Gao, L. A simple harmonic reduction method in multipulse rectifier using passive devices. IEEE Trans. Ind. Inform. 2017, 13, 2680–2692. [Google Scholar] [CrossRef] [Scilit]
  18. Wang, J.; Chen, A.; Yao, X.; Guan, Q.; Chen, Q. Input current step-doubling for autotransformer-based 12-Pulse rectifier using two auxiliary diodes. IEEE Trans. Ind. Electron. 2022, 69, 7607–7617. [Google Scholar] [CrossRef] [Scilit]
  19. Wang, J.; Chen, A.; Yao, X.; Li, L.; Lv, Y.; Chen, Q. A simple 24-pulse rectifier employing an auxiliary pulse-doubling circuit. IEEE Trans. Power Electron. 2022, 37, 8392–8403. [Google Scholar] [CrossRef] [Scilit]
  20. Yang, S.; Wang, J.; Yang, W. A novel 24-pulse diode rectifier with an auxiliary single-phase full-wave rectifier at DC side. IEEE Trans. Power Electron. 2017, 32, 1885–1893. [Google Scholar] [CrossRef] [Scilit]
  21. Gao, L.; Xu, X.; Man, Z.; Lee, J. A 36-pulse diode-bridge rectifier using dual passive harmonic reduction methods at DC link. IEEE Trans. Power Electron. 2019, 34, 1216–1226. [Google Scholar] [CrossRef] [Scilit]
  22. Abdollahi, R.; Gharehpetian, G.B.; Anvari-Moghaddam, A.; Blaabjerg, F. Pulse tripling circuit and twelve pulse rectifier combination for sinusoidal input current. IEEE Access 2021, 9, 103588–103599. [Google Scholar] [CrossRef] [Scilit]
  23. Prakash, P.S.; Kalpana, R.; Chethana, K.S.; Singh, B. A 36-pulse AC–DC converter with DC-side tapped interphase bridge rectifier for power quality improvement. IEEE Trans. Ind. Appl. 2021, 57, 549–558. [Google Scholar] [CrossRef] [Scilit]
  24. Malek, M.A.; Khan, M.A.G. A simple 18-pulse star rectifier using two passive auxiliary circuits at DC link. IEEE Trans. Power Electron. 2022, 37, 5583–5593. [Google Scholar] [CrossRef] [Scilit]
  25. Wang, J.; Lv, Y.; Yao, X.; Li, L.; Chen, Q. Input current step-tripling for 12-pulse rectifier using a passive four-tap changer. IEEE Trans. Ind. Electron. 2023, 70, 65–75. [Google Scholar] [CrossRef] [Scilit]
  26. Wang, J.; Yao, X.; Bai, J.; Gao, X.; Yang, S. A simple 36-pulse diode rectifier with hybrid pulse multiplication interphase reactor at DC side. IEEE J. Emerg. Sel. Top. Power Electron. 2021, 9, 3540–3555. [Google Scholar] [CrossRef] [Scilit]
  27. Li, Y.; Zhang, D.; Yang, Y.; Xu, W.; Wu, J.; Zhong, Y. A hybrid harmonic reduction multi-pulse rectifier with a DC-side auxiliary circuit. In Proceedings of the 2023 IEEE 2nd International Power Electronics and Application Symposium (PEAS), Guangzhou, China, 10–13 November 2023; pp. 1981–1986. [Google Scholar]
  28. Li, Q.; Gao, L.; Meng, F. An aeronautical multi-pulse rectification system for power density increasing and three-phase unbalance suppression. IEEE Trans. Transp. Electrif. 2024, 10, 9441–9455. [Google Scholar] [CrossRef] [Scilit]
  29. Arvindan, A.N.; Arshad Mohamed, M.A.; Aravind Kumar, R. Power quality analysis of six- and twelve-pulse rectifiers as series cascaded topologies of the three-pulse rectifier. In Proceedings of the 2019 2nd International Conference on Power and Embedded Drive Control (ICPEDC), Chennai, India, 21–23 August 2019; pp. 383–389. [Google Scholar]
  30. Islam, F.; Krishnamoorthy, H.S. Doubly-fed solid state auto-transformer (SSAT) concept for multi-pulse rectifiers. In Proceedings of the 2021 IEEE Energy Conversion Congress and Exposition (ECCE), Vancouver, Canada, 10–14 October 2021. [Google Scholar]
  31. Albalawi, H.; Wadood, A.; Khan, S.; Alatwi, A.M. Harmonic Mitigation in Multi-Pulse Rectification: A Comparative Study of 12-, 18-, and 24-Pulse Systems. Mathematics 2024, 12, 3257. [Google Scholar] [CrossRef] [Scilit]
  32. IEEE Std 519-2022; IEEE Standard for Harmonic Control in Electric Power Systems. IEEE: Piscataway, NJ, USA, 2022.
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.