Skip to Content
EnergiesEnergies
  • Article
  • Open Access

24 November 2026

16 Pages

Design and Validation of a 10 kV SiC MOSFET-Based Medium-Voltage Power Cell

,
,
,
,
,
,
,
,
…
1
CSG EHV Electric Power, Research Institute, China Southern Power Grid Company Limited, Guangzhou 510663, China
2
State Key Laboratory of Power Transmission Equipment Technology, Chongqing University, Chongqing 400044, China
*
Author to whom correspondence should be addressed.
Energies2026, 19(23), 5686;https://doi.org/10.3390/en19235686 
(registering DOI)

Abstract

Driven by the demand for higher switching frequency and power density in modular medium-voltage converters, 10 kV SiC MOSFETs provide a promising solution for reducing the number of power cells and improving system integration. However, there are few 10 kV SiC prototypes for design reference, and practical implementation remains challenging due to stringent requirements on insulation coordination, parasitic control, and high-speed gate driving. This paper presents a compact medium-voltage half-bridge power cell based on 10 kV SiC MOSFETs, focusing on system-level integration, insulation coordination, and reliable high-current operation. An adapter board and short coaxial interconnections reduce gate-loop parasitics, while the PCB busbar achieves a tradeoff among low inductance, current capability, and insulation performance. External insulation among the power module, DC-link capacitors, and heatsink is also optimized. Experimental results demonstrate low commutation-loop parasitics, satisfactory partial-discharge performance, and stable operation at a reduced DC-link voltage of 1.5 kV, a switching frequency of 1 kHz, and an RMS circulating current of approximately 60 A. The proposed design provides a practical reference for compact medium-voltage SiC power-cell design.

1. Introduction

With increasing demands for higher voltage, efficiency, and power density, medium-voltage (MV) converters have attracted extensive attention in grid interfaces, solid-state transformers, MV drives, and medium-voltage DC(MVDC) systems [1,2,3,4]. Modular multilevel converters (MMCs) are widely adopted due to their scalability and high-voltage capability [1,5,6]. Compared with conventional Si IGBT-based MMCs, 10 kV SiC MOSFETs can reduce the number of series-connected power cells while enabling higher switching frequency and improved power density [5,6,7].
10 kV SiC MOSFETs also introduce significant challenges for practical power-cell implementation. The high dv/dt and di/dt during fast switching impose strict requirements on gate-drive performance, parasitic control, power interconnection, and insulation coordination [8,9,10]. Therefore, developing compact and reliable 10 kV SiC MOSFET power cells requires coordinated optimization of electrical, thermal, and insulation designs.
Significant efforts have been devoted to the development of 10 kV SiC MOSFET-based medium-voltage conversion systems, including device modules, converter submodules, power stacks, and integrated power cells. At the device level, Das et al. developed a 10 kV/120 A SiC half-bridge MOSFET module, demonstrating the feasibility of high-voltage SiC device packaging for medium-voltage applications [2]. Grider et al. and Passmore et al. from Cree Inc. (Wolfspeed, Durham, NC, USA) further developed 10 kV/120 A SiC half-bridge modules for 1 MVA solid-state power substations and next-generation high-current 10 kV SiC power modules, respectively [11,12]. Madhusoodhanan et al. at North Carolina State University demonstrated solid-state transformer and MV grid-tie applications using 10 kV SiC MOSFET-based multilevel converters [1]; Palmer et al. further validated a 10 kV SiC MOSFET-based MMC phase-leg for medium-voltage grid applications, while Pan et al. demonstrated a 7-kV, 1-MVA SiC-based MMC prototype for medium-voltage electric machine drives [5,6]. Wang et al. from The Ohio State University presented the hardware design of a 10 kV SiC MOSFET-based MMC for grid-tied applications [13]. These studies verified the potential of 10 kV SiC devices for medium-voltage converters from the module and system perspectives. Previous studies have investigated high-current gate drivers, low-coupling-capacitance isolated auxiliary power supplies, fast protection circuits, and compact integration methods to improve the reliability of 10 kV SiC MOSFET operation under high dv/dt conditions [8,9,10,14]. In addition, multilayer PCB busbars have been increasingly adopted in MV SiC power conversion systems because of their compact structure and low parasitic characteristics [15,16,17,18,19]. At the system level, Mocevic et al. developed a medium-voltage half-bridge power cell based on a 10 kV SiC MOSFET module and investigated several key technologies, including enhanced gate drivers, planar PCB DC busbars, high-voltage insulation, auxiliary power supplies, and high-speed communication. The developed power cell was experimentally demonstrated under 6 kV voltage, 84 A current, and high switching frequency conditions [7,8]. In addition, several studies have explored medium-voltage SiC power stacks and converter integration methods [20,21].
However, existing studies have mainly demonstrated the high-voltage switching capability of SiC devices or investigated individual enabling technologies, such as gate-drive circuits, insulation structures, or packaging solutions. The integrated design and experimental validation of a complete 10-kV SiC MOSFET power cell, including electrical interconnection, insulation coordination, thermal management, and control interfaces, remain insufficiently explored.
Therefore, this paper presents a compact medium-voltage half-bridge power cell based on 10 kV SiC MOSFETs. Unlike existing demonstrations that focus on either converter-level validation [2,5,21] or partial subsystem integration [7,8], this work emphasizes comprehensive power-cell-level integration, with particular attention to component- and system-level insulation coordination. A comparison with existing 10 kV SiC MOSFET-based power-cell implementations is summarized in Table 1.
Table 1. Comparison of representative 10 kV SiC MOSFET-based power-cell and converter platforms.

2. 10 kV SiC MOSFET Power-Cell Architecture

The proposed medium-voltage power cell employs a 10 kV SiC MOSFET half-bridge module as its core power device. The basic structure of the module is shown in Figure 1. The module consists of upper and lower switching positions, with each switch comprising four 10 kV/15 A SiC MOSFET dies connected in parallel to meet the requirements of medium-voltage and high-current operation [22]. The overall architecture of the power cell is shown in Figure 2. The module was developed based on the structure reported in [22] and is housed in an XHP™3 package with overall dimensions of 144 mm × 100 mm × 40 mm.
Figure 1. The 10 kV/60 A SiC MOSFET power module and its internal circuit [22].
Figure 2. Overall architecture of the 10 kV SiC MOSFET power cell.
The power cell mainly consists of a 10 kV SiC MOSFET half-bridge module, DC-link capacitors, a PCB power busbar, gate-drive and communication units, sensing and monitoring units, and a heatsink assembly. As shown in Figure 2, the DC side employs four 2 kV/125 μF film capacitors connected in series, providing a total voltage rating of 8 kV and an equivalent capacitance of approximately 31.3 μF. The intermediate nodes between the series-connected capacitors are denoted as M+, N, and M−. The upper and lower switches of the half-bridge are connected across the DC link, while the midpoint of the bridge leg serves as the AC output terminal, denoted as AC. The gate-drive unit and sensing unit introduced in Figure 2 are detailed in Section 3 (Figure 3 and Figure 4).
Figure 3. Overall Architecture of the High-Voltage SiC MOSFET Gate-Drive Circuit.
Figure 4. BJT Current Booster Circuit.
The measured voltage and current quantities indicated in Figure 2 are defined as follows: uC12 and uC34 denote the voltages across the upper (C1, C2) and lower (C3, C4) capacitor banks, respectively; iAC denotes the AC output current; and uL denotes the voltage across the external inductor connected to the AC terminal.
To enable medium-voltage, high-frequency operation, the power cell adopts a modular integrated structure in which the power module, DC-link capacitors, PCB busbar, gate-drive and communication units, and sensing and monitoring units are compactly arranged. The functional subsystems are interconnected through the PCB busbar and isolated communication links to realize power transfer, gate-drive control, and operating-state monitoring.

3. Gate-Drive and Communication System

The switching performance of 10 kV SiC MOSFETs strongly depends on the gate-drive capability. Compared with lower-voltage devices, high-voltage SiC MOSFETs exhibit larger gate charge and input capacitance, requiring higher drive current and improved transient immunity. Therefore, the gate-drive system must provide sufficient driving capability while maintaining electrical isolation and reliable high-speed signal transmission [23]. The gate charge can be calculated according to Equation (1).
Q g = ∫ i g ⋅ d t
Figure 3 illustrates the overall architecture of the SiC MOSFET gate-drive circuit. The proposed gate-drive circuit is designed for high-voltage, high-current, and high-frequency power conversion applications and adopts a modular architecture consisting of an auxiliary isolated power supply, a fiber-optic PWM receiver, gate-drive current amplification, voltage and current sensing circuits, and an adapter board. This architecture provides electrical isolation, logic-level interfacing, and power transfer between the low-voltage control circuitry and the high-power switching stage, thereby supporting high-speed and reliable switching of the SiC MOSFETs.
The system is supplied by an external 24 V DC source. A self-developed 24 V/24 V isolated power supply is first employed to establish a floating auxiliary-power domain. This power supply has a designed isolation level of 10 kV and an experimentally measured input-to-output parasitic coupling capacitance of approximately 2.65 pF [24]. Within the floating secondary-side domain, a QA243C-2005R3 (K-CUT, Shenzhen, China) isolated DC/DC converter generates VDD = +20 V and VEE = −5 V for the output side of the gate-driver IC, providing the positive and negative gate-to-source voltages required for turning the SiC MOSFETs on and off. Meanwhile, a non-isolated K7805-500R (MORNSUN, Guangzhou, China) 3 regulator generates VCC = 5 V referenced to SGND for the PWM receiver, the input-side logic circuitry of the gate-driver IC, and the signal-conditioning circuitry. By employing isolated power supplies with low input-to-output parasitic coupling capacitance and maintaining separation between the control-side and power-side grounds, this power-supply architecture effectively reduces common-mode interference coupling between the control ground and the power ground, thereby improving the noise immunity of the gate-drive circuit under high-dv/dt switching conditions.
Signal transmission between the controller and the gate-drive unit is implemented through fiber-optic transceivers. The PWM signal generated by the controller first enters the PWM receiving and conditioning stage, where it undergoes logic-level matching, pulse conditioning, and isolated transmission before being delivered to the isolated gate-driver IC. This stage mainly performs the interface conversion from low-voltage control signals to power-stage drive signals, while ensuring sufficient edge integrity and noise immunity of the gate-drive input. For high-frequency SiC MOSFET switching operation, particular attention must be paid to propagation delay, channel-to-channel delay mismatch, and common-mode transient interference in the PWM signal path to prevent bridge-leg shoot-through, false turn-on, or other faults caused by signal distortion or spurious triggering [9,10,25].
On the power-drive side, the isolated gate-driver IC converts the input-side PWM control signal into the gate-drive voltage required by the power stage. To enable fast switching of the SiC MOSFETs, an external gate-current booster stage is incorporated at the driver output to increase the peak gate current, as shown in Figure 4. The amplified gate-drive signal is then delivered to the gate terminal of the SiC MOSFET through an adapter board. The adapter board serves as an interface between the gate-drive circuit and the SiC MOSFET module, enabling flexible routing of the gate and auxiliary-source connections while maintaining a compact integrated structure. Experimental measurements show that this booster stage delivers a peak turn-on gate current of 10.83 A and a peak turn-off gate current of −13.75 A.

4. Design of High-Capacity, High-Insulation PCB Busbars

The PCB busbar serves as both the mechanical and electrical interface between converter components [26]. For medium-voltage SiC converters, parasitic inductance cannot be treated as the sole optimization objective. Reducing the spacing between overlapping forward and return current paths enhances magnetic-field cancelation, while widening the copper conductors improves current-carrying capability. However, both measures reduce insulation clearances and aggravate electric-field concentration at conductor edges and copper–FR-4–air triple junctions. Therefore, the proposed design jointly optimizes three coupled objectives: minimizing commutation-loop inductance, ensuring sufficient current-carrying capability, and limiting electric-field stress [15,18,27].

4.1. Minimize Loop Inductance

To suppress parasitic inductance, magnetic-flux cancelation within the commutation loop should be maximized. The conductive paths should either maximize their overlap on adjacent layers or be routed on the same layer with the enclosed loop area minimized. Because the module geometry and terminal positions are fixed, a laminated layout is impractical. Figure 5 compares two commutation-loop layouts. Although Layout 2 reduces conductor length, it increases loop area and limits layout flexibility. Therefore, Layout 1 is preferred because of its smaller commutation-loop area and better integration compatibility. In addition, the central region is intentionally kept free of copper to reduce the magnetic field above the busbar and thereby mitigate electromagnetic interference with the gate-driver board.
Figure 5. Capacitor Layout and Its Commutation Loop. Numbers 1–4 denote the four DC-link capacitors (C1–C4).
Figure 6a shows the initial six-layer conductor layout used to define the current paths. Subsequent insulation optimization introduces additional electric-field-control layers while retaining these low-inductance paths. The decoupling capacitor PCB busbar, indicated by the yellow arrows in Figure 6a, provides the electrical connection between the decoupling capacitors and the PCB power busbar, forming a compact high-frequency current commutation loop. The exploded view of the copper conductors is presented in Figure 6b, where the conductor nodes and their corresponding layers are identified. To further reduce the commutation-loop stray inductance, additional terminals are introduced on the DC conductors, and a decoupling capacitor array is accommodated in the vertical space above the busbar and placed close to the module DC terminals. This arrangement reduces the commutation-path length to approximately 25% of its original value.
Figure 6. Preliminary PCB Design. (a) Conductor layout; (b) Exploded view.
At 10 MHz, the parasitic inductance of the main PCB commutation loop extracted using Ansys Q3D (Ansys, Inc., Canonsburg, PA, USA) was 119.7 nH, whereas the measured value was 128.6 nH, corresponding to a discrepancy of 7.4%. This discrepancy is mainly attributed to additional elements in the measurement setup, including the test fixture and soldered interconnections. After a local decoupling capacitor array was installed near the power-module terminals, the measured commutation-loop inductance decreased to 43.4 nH. This result indicates that the high-frequency commutation loop is primarily determined by the geometry between the power module and the local decoupling capacitors, rather than by the complete path through the DC-link capacitors. The parasitic inductance results are summarized in Table 2.
Table 2. Simulated and measured parasitic inductance values.

4.2. Current-Carrying Capacity Design

Considering the SiC module rating and experimental requirements, the DC and AC conductors were designed for 60 A current capability, while the N and M conductors were designed for 30 A. To maintain the required insulation clearances between pads and vias at different potentials, the conductor paths must avoid these regions. Consequently, the conductors exhibit irregular geometries, with nonuniform widths along different sections of the same conductor. In the initial layout, the minimum widths of the DC conductors and the N/M conductors were 25 mm and 18 mm, respectively, while the AC conductor width was 75 mm.
The required copper thickness was evaluated according to the current-carrying guidelines of IPC-2221 [28] and IPC-2152 [29]. The conductor thickness was selected considering both the allowable temperature rise and practical multilayer PCB fabrication constraints. Based on these criteria, the final copper thickness and layer arrangement were determined, as summarized in Table 3.
Table 3. Copper thickness value selection.
Based on IPC-2152 guidelines, the initial copper thickness was estimated for different conductor widths according to Equation (2). Considering the high-frequency characteristics of SiC switching currents, multiple thinner copper layers were adopted instead of a single thick copper layer to improve current distribution and reduce high-frequency current crowding [26].
I ∝ t
Reference [26] further indicates that, for capacitor-loop oscillation currents in the megahertz range and higher-frequency switching oscillation currents, the skin depth may be smaller than the thickness of a single thick copper layer. Therefore, multiple thin copper planes are more favorable for high-frequency current distribution. Table 3 presents the copper thicknesses calculated according to the two design criteria, together with the final selections of copper thickness and layer count, for a temperature rise of 40 °C.
In addition, plated-through-hole arrays are arranged around the pads and along the current paths to promote current sharing among the layers and improve heat dissipation from the internal layers. These vias also spread the heat generated near the module and capacitor terminals to the other copper layers. The finished via diameter is 0.61 mm, with a nominal barrel copper thickness of 2.5 μm. The via pitches along the DC/N paths and within the AC current-injection region are 2.0 mm and 2.5 mm, respectively.

4.3. Insulation Design

Mature PCB fabrication technologies enable the electric-field strength both inside and outside the board to be accurately controlled around terminals, cutouts, and board edges by adjusting the interlayer dielectric thicknesses and conductor offsets, thereby minimizing the peak electric-field stress. To provide sufficient design margins for local defects, temperature rise, and long-term aging, the maximum electric-field strengths are generally limited to 20 kV/mm within the PCB and 2 kV/mm in the surrounding air [8,29,30,31]. Accordingly, high-performance FR-4 is selected as the insulation material because it combines a glass-transition temperature of approximately 170–185 °C with high dielectric strength.
Figure 7a presents an overall view of the PCB busbar and identifies the locations of the four enlarged regions shown in Figure 7b–e. Four complementary electric-field mitigation measures are adopted in these regions. First, as illustrated in Figure 7b,c, a 2.5 mm-wide slot is introduced between the DC pads to increase the creepage distance, and the spacing between the DC and N conductors is optimized to 11 mm. Second, as shown in Figure 7c, field-shaping shield pads with slightly larger lateral dimensions are placed beneath the exposed high-voltage pads. These shielding structures do not eliminate the electric field; instead, they reshape the equipotential contours and redistribute the peak electric-field stress from the air into the FR-4, which has a higher dielectric strength. Third, as shown in Figure 7d, unnecessary pad extensions are shortened without compromising the current-carrying capability, and horizontal offsets are introduced between the N and M conductors and between the inner- and outer-layer DC conductors. The N-to-M offset is set to 0.5 mm, while the offset between the inner- and outer-layer DC conductors is set to 1.0 mm. These measures reduce the simulated peak electric-field strength inside the PCB from 23.2 kV/mm to 18.9 kV/mm without noticeably reducing the effective current-carrying width. Finally, as shown in Figure 7e, shielding layers with slightly larger lateral dimensions are added beneath the via arrays to prevent the large-area exposed metal arrays from causing excessive electric-field stress in the surrounding air.
Figure 7. Electric field optimization regions; (a) overall layout, with labeled regions corresponding to the enlarged views in (b–e); (b) region between the DC pads; (c) region between a DC pad and the N conductor; (d) capacitor-terminal region; (e) via-array region.
The final busbar incorporates ten copper layers within an overall thickness of 3.5 mm. The outermost copper layers carry only the AC conductors, while the adjacent inner layers are used for electric-field shielding. Layers L3 and L8 accommodate the N conductors, whereas layers L4–L7 are partitioned to accommodate the DC and M conductors. The central core is 0.53 mm thick to ensure sufficient mechanical strength. The dielectric thickness between the DC and N layers is 0.40 mm, while the outer dielectric thickness is 0.42 mm. Therefore, the additional layers are primarily introduced to control the electric-field distribution rather than merely increase the overall insulation thickness. This approach maintains a low-profile structure while avoiding the parasitic-inductance penalty associated with the increased interlayer spacing of conventional thick laminated busbars.

5. External Insulation and Converter Integration

5.1. External Insulation Design

The actual arrangement of the heat sink and DC-link capacitors is shown in Figure 8. The capacitor enclosures are maintained at approximately 0 V, while the heatsink potential floats due to the parasitic capacitance between the module and heatsink under high-frequency switching transients. Without a defined grounding scheme for the heat sink, a time-varying potential difference exists between the capacitor enclosures and the heat sink. Under a conservative theoretical worst-case capacitive-voltage-division assumption for a 6 kV DC-link, the floating heatsink potential may theoretically reach approximately 3 kV, with the maximum electric-field strength occurring at its sharp corners, as shown in the right panel of Figure 8. This value represents a theoretical upper-bound estimation under full capacitive coupling, which may not appear in practical operation if minor leakage paths to ground exist. Inadequate insulation may therefore cause discharge during operation and compromise submodule performance. However, simply increasing the insulation clearances between components would reduce the power density of the submodule [18,19,20].
Figure 8. Physical structure and field strength distribution of the capacitor and heat sink.
A parametric sweep of the insulation distance between the capacitors and the heat sink was performed. Considering the tradeoff between power density and insulation performance, a distance of 6 mm was selected, as shown in Figure 9.
Figure 9. Electric field strength varies with the distance between the heat sink and the capacitor.

5.2. Converter Integration

With the PCB busbar and external-insulation designs established, the remaining components are further integrated into a compact power-cell structure. Due to the high dv/dt and di/dt characteristics of 10 kV SiC MOSFETs, minimizing gate-loop parasitics and reducing coupling between power and gate-drive loops are essential for stable switching performance [8,27,32]. However, direct connection between the gate-driver board and the module gate terminals is constrained by the mechanical dimensions of the driver board, the terminal arrangement of the power module, and the spatial layout of the PCB busbar. Such a connection would not only increase the difficulty of mechanical design and assembly, but also make it difficult to simultaneously satisfy the requirements for a short gate-drive loop, sufficient insulation clearance, and modular integration. Therefore, an adapter board is introduced between the power module and the upper gate-drive unit, forming a compact vertically integrated structure consisting of the power module–adapter board–PCB busbar–gate-driver board, as shown in Figure 10b.
Figure 10. Integrated structure of the proposed 10 kV SiC MOSFET power cell: (a) 3D structural view; (b) exploded view.
The adapter board primarily serves as an electrical interface converter, signal breakout interface, and mechanical transition structure. According to the locations of the gate and auxiliary-source terminals of the 10 kV SiC MOSFET module, the adapter board rearranges the gate-drive interfaces and converts the distributed module-side drive terminals into a standardized interface that facilitates connection to the gate-driver board mounted above the module, thereby reducing the complexity of gate-driver design and assembly. During switching transients, the PCB busbar is subjected to a high common-mode voltage slew rate. If the gate-drive signals are transmitted through long conventional PCB traces, they are susceptible to electromagnetic coupling from the power loop. To further shorten the gate-signal transmission path, slots are introduced in the non-current-carrying regions of the PCB busbar, and short flexible coaxial cables are used to connect the gate-driver board to the adapter board. This arrangement allows the gate-drive signals to pass directly through the busbar, thereby minimizing the interconnection length between the gate-driver board and the power module.
The proposed vertical integration scheme forms a compact modular assembly consisting of the gate-driver board, adapter board, PCB busbar, and 10 kV SiC MOSFET module. Compared with a spatially separated arrangement of the gate-driver board and power module, this structure effectively shortens the gate-drive loop and reduces both the gate-loop parasitic inductance and the parasitic coupling between the power loop and the gate-drive loop. As a result, gate-voltage oscillations, false turn-on, and switching transient overvoltage caused by parasitic effects can be mitigated, thereby improving the stability of the gate-drive system under conditions with high dv/dt. Consequently, the integrated structure enables low-parasitic and high-power-density integration of the gate-drive and power circuits while preserving the high-speed switching capability of the 10 kV SiC MOSFET.
MMKP334J3F2701 capacitors, each rated at 2 kV and 330 nF, are employed for local decoupling. Four capacitors are connected in series, providing an equivalent voltage rating of 8 kV and an equivalent capacitance of 82.5 nF. The final structure satisfies the insulation, electromagnetic performance, and current-carrying requirements established in the preceding sections while achieving compact integration of the gate-drive system, power interconnection, local decoupling, and thermal-management structure [21]. The resulting integrated power cell provides the complete hardware platform for the subsequent pump-back power-cycling experiments.

6. Pump-Back Operation and Experimental Validation

6.1. Experimental Setup and Control Strategy

To validate the practical operating performance of the proposed 10 kV SiC MOSFET power cell, a pump-back power-cycling test platform was constructed, as shown in Figure 11. The platform comprises the 10 kV SiC MOSFET half-bridge under test (HB-1), a 4.5 kV/450 A IGBT auxiliary half-bridge (HB-2, Infineon FF450R45T3E4_B5 XHP™3, Infineon Technologies AG, Neubiberg, Germany), and a 0.8 mH circulating inductor rated at 10 kV and 80 A. The two half-bridges share a common DC-link and exchange circulating power through the ac-side inductor.
Figure 11. Pump-Back Power-Cycling Experimental Platform.
A master–slave control scheme is employed in the experiment. HB-1 serves as the device under test (DUT) and operates with a fixed PWM duty ratio of 0.5, while HB-2 acts as the auxiliary power unit and regulates the circulating-inductor current via a single-edge adjustment strategy. During operation, the inductor charging interval is kept constant, and only the rising-edge position of S4 is adjusted according to the error between the measured circulating current and its reference value, thereby regulating the circulating current by varying the discharging interval. The topology and switch configuration of the platform are shown in Figure 12. For clarity, the four series-connected DC-link capacitors of the auxiliary HB-2 are represented by the equivalent capacitor CHB2,eq in Figure 12a. Meanwhile, a dead-time constraint is imposed to ensure safe commutation of HB-2. The DC-link voltage and switching frequency are set to 1500 V and 1 kHz, respectively.
Figure 12. Pump-back topology and control timing. (a) Circuit topology and switch configuration; (b) switching timing diagram and current regulation.

6.2. Experimental Results

The insulation performance of the proposed power cell was first evaluated through partial-discharge (PD) tests. The experimental setup is shown in Figure 13. The test was conducted according to IEC 60270 [33] and IEC 60060-1 [34] under 50 Hz AC excitation. Since the background noise of the measurement system was approximately 20 pC, an apparent charge of 20 pC was selected as the PD inception criterion. This partial-discharge measurement was performed on the standalone PCB busbar; all DC-link and decoupling capacitors were disassembled from the test sample.
Figure 13. Experimental setup for partial discharge measurements.
The PD inception voltage (PDIV) was measured for different terminal combinations of the PCB busbar. As shown in Figure 14, the final busbar structure achieved the required insulation margin for all tested ports. For the DC+–DC− terminal combination, the maximum PDIV of an individual sample reached 10.4 kV rms, while the average PDIV of five samples was 9.62 kV rms.
Figure 14. Partial discharge inception voltages of five PCB-busbar samples for different terminal pairs.
Figure 15 presents the phase-resolved partial-discharge (PRPD) patterns measured between the DC+ and DC− terminals before and after PD inception. No obvious discharge activity was observed at an applied voltage of 10 kV rms. When the voltage was increased to 10.4 kV rms, distinct discharge signals appeared, confirming the PDIV of the tested sample.
Figure 15. PRPD pattern between DC+ and DC−.
The practical operating performance of the proposed 10 kV SiC MOSFET power cell was further verified through a pump-back power-cycling experiment. The test platform and operating waveforms are shown in Figure 11 and Figure 16, respectively. During the experiment, all switching devices operated according to the predefined timing sequence, and the circulating current remained stable under this single-edge current-regulation strategy. No evident sustained voltage imbalance was observed between the upper and lower DC-link capacitor banks.
Figure 16. Waveforms of the pump-back power-cycling experiment: (a) gate-drive signals of S1–S4; (b) circulating-inductor current, inductor voltage, and DC-link capacitor voltages.
The circulating current reached a peak value of approximately 91.4 A and an RMS value of approximately 60.98 A, demonstrating stable continuous operation of the proposed power cell under the test conditions. The current-carrying capability of the PCB busbar was also evaluated. The RMS current flowing through the AC conductor reached approximately 60.98 A, satisfying the design requirement of 60 A.
As shown in Figure 17, the infrared thermal images after continuous operation indicate that the maximum temperature of the N conductor was approximately 58.1 °C. The higher-temperature regions were mainly concentrated around the power-module terminals and interconnection areas due to local current crowding and heat transfer from the power module. The maximum temperatures of the DC and AC conductors were approximately 62.2 °C and 61.9 °C, respectively. Most regions of the PCB busbar remained below 60 °C, and the maximum PCB temperature was approximately 62.2 °C without evident abnormal hotspots.
Figure 17. Infrared thermal images of the PCB busbar after power-cycling operation.
The above insulation and power-cycling tests demonstrate that the proposed power cell achieves both sufficient high-voltage insulation capability and reliable high-current operation, validating the feasibility of the integrated gate-drive, power-interconnection, and insulation design.

7. Conclusions

This paper presents the design and validation of a compact medium-voltage power cell based on 10 kV SiC MOSFETs. The proposed design integrates the gate-drive system, power interconnection, and insulation structure to simultaneously achieve low parasitic effects, high current capability, and sufficient insulation margin. A compact gate-drive integration scheme and a multilayer PCB busbar with electric-field management were developed to improve the overall performance of the power cell.
A pump-back power-cycling platform was established to verify the practical operation of the proposed power cell. Experimental results demonstrated stable circulating-current regulation at a DC-link voltage of 1.5 kV and a switching frequency of 1 kHz, with an RMS circulating current of approximately 60 A. The insulation, current-carrying performance, and thermal performance were verified through partial-discharge and continuous-operation tests. These results confirm the feasibility of the proposed integrated gate-drive, power-interconnection, and insulation design, providing a hardware foundation for the application of 10 kV SiC MOSFET power cells in modular medium-voltage converters.

Author Contributions

Conceptualization, K.X. and Z.Z.; Methodology, S.T., X.Y., and Z.Z.; Formal Analysis, L.D.; Resources, X.Y.; Investigation, Y.H. and X.Y.; Data Curation, J.Z.; Writing—Original Draft, Y.X.; Validation, Q.Z. and X.Y.; Visualization, J.P.; Supervision, Z.Z.; Writing—Review and Editing and Project Administration, H.F. All authors have read and agreed to the published version of the manuscript.

Funding

This research and the APC were funded by the Science and Technology Program of EHV Power Transmission Company of China Southern Power Grid Co., Ltd., grant number CGYKJXM20240103.

Data Availability Statement

Data are contained within the article.

Conflicts of Interest

Authors Kai Xiao, Shuming Tan, Longlong Deng, Xilin Yan, and Yilong Huang were employed by the company CSG EHV Electric Power, Research Institute, China Southern Power Grid Company Limited, Guangzhou, China. The remaining authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest. The authors declare that this study received funding from Science and Technology Program of EHV Power Transmission Company of China Southern Power Grid Co., Ltd. The funder was not involved in the study design, collection, analysis, interpretation of data, the writing of this article or the decision to submit it for publication.

References

  1. Madhusoodhanan, S.; Tripathi, A.; Patel, D.; Mainali, K.; Kadavelugu, A.; Hazra, S.; Bhattacharya, S.; Hatua, K. Solid-state transformer and MV grid tie applications enabled by 15 kV SiC IGBTs and 10 kV SiC MOSFETs based multilevel converters. IEEE Trans. Ind. Appl. 2015, 51, 3343–3360. [Google Scholar] [CrossRef] [Scilit]
  2. Das, M.K.; Capell, C.; Grider, D.E.; Leslie, S.; Ostop, J.; Raju, R.; Schutten, M.; Nasadoski, J.; Hefner, A. 10 kV, 120 A SiC half H-bridge power MOSFET modules suitable for high-frequency, medium-voltage applications. In Proceedings of the 2011 IEEE Energy Conversion Congress and Exposition (ECCE), Phoenix, AZ, USA, 17–22 September 2011. [Google Scholar] [CrossRef] [Scilit]
  3. Marzoughi, A.; Burgos, R.; Boroyevich, D. Investigating impact of emerging medium-voltage SiC MOSFETs on medium-voltage high-power industrial motor drives. IEEE J. Emerg. Sel. Top. Power Electron. 2019, 7, 1371–1387. [Google Scholar] [CrossRef] [Scilit]
  4. Millán, J.; Godignon, P.; Perpiñà, X.; Pérez-Tomás, A.; Rebollo, J. A survey of wide bandgap power semiconductor devices. IEEE Trans. Power Electron. 2014, 29, 2155–2163. [Google Scholar] [CrossRef] [Scilit]
  5. Palmer, J.; Ji, S.Q.; Huang, X.X.; Zhang, L.; Giewont, W.; Wang, F.F.; Tolbert, L.M. Testing and validation of 10 kV SiC MOSFET based 35 kVA MMC phase-leg for medium voltage (13.8 kV) grid. In Proceedings of the 2019 IEEE Energy Conversion Congress and Exposition (ECCE), Baltimore, MD, USA, 29 September–3 October 2019; pp. 2001–2006. [Google Scholar] [CrossRef] [Scilit]
  6. Pan, J.Y.; Ke, Z.W.; Al Sabbagh, M.; Li, H.; Potty, K.A.; Perdikakis, W.; Na, R.S.; Zhang, J.L.; Wang, J.; Xu, L.Y. 7-kV, 1-MVA SiC-based modular multilevel converter prototype for medium-voltage electric machine drives. IEEE Trans. Power Electron. 2020, 35, 10137–10149. [Google Scholar] [CrossRef] [Scilit]
  7. Mocevic, S.; Yu, J.; Fan, B.; Sun, K.; Xu, Y.; Stewart, J.; Rong, Y.; Song, H.; Mitrovic, V.; Yan, N.; et al. Design of a 10 kV SiC MOSFET-based high-density, high-efficiency, modular medium-voltage power converter. iEnergy 2022, 1, 100–113. [Google Scholar] [CrossRef] [Scilit]
  8. Mocevic, S.; Yu, J.H.; Xu, Y.; Stewart, J.; Wang, J.; Cvetkovic, I.; Dong, D.; Burgos, R.; Boroyevich, D. Power cell design and assessment methodology based on a high-current 10-kV SiC MOSFET half-bridge module. IEEE J. Emerg. Sel. Top. Power Electron. 2021, 9, 3916–3935. [Google Scholar] [CrossRef] [Scilit]
  9. Wang, J.; Mocevic, S.; Burgos, R.; Boroyevich, D. High-scalability enhanced gate drivers for SiC MOSFET modules with transient immunity beyond 100 V/ns. IEEE Trans. Power Electron. 2020, 35, 10180–10199. [Google Scholar] [CrossRef] [Scilit]
  10. Zhang, L.; Ji, S.Q.; Gu, S.D.; Huang, X.X.; Palmer, J.E.; Giewont, W.; Wang, F.F.; Tolbert, L.M. Design considerations for high-voltage insulated gate drive power supply for 10-kV SiC MOSFET applied in medium-voltage converter. IEEE Trans. Ind. Electron. 2021, 68, 5712–5724. [Google Scholar] [CrossRef] [Scilit]
  11. Grider, D.; Das, M.; Agarwal, A.; Palmour, J.; Leslie, S.; Ostop, J.; Raju, R.; Schutten, M.; Hefner, A. 10 kV/120 A SiC DMOSFET half H-bridge power modules for 1 MVA solid state power substation. In Proceedings of the 2011 IEEE Electric Ship Technologies Symposium (ESTS), Alexandria, VA, USA, 10–13 April 2011; pp. 131–134. [Google Scholar] [CrossRef] [Scilit]
  12. Passmore, B.; Cole, Z.; McGee, B.; Wells, M.; Stabach, J.; Bradshaw, J.; Shaw, R.; Martin, D.; McNutt, T.; VanBrunt, E.; et al. The next generation of high voltage (10 kV) silicon carbide power modules. In Proceedings of the 2016 IEEE 4th Workshop on Wide Bandgap Power Devices and Applications (WiPDA), Fayetteville, AR, USA, 7–9 November 2016; pp. 1–4. [Google Scholar] [CrossRef] [Scilit]
  13. Wang, K.; Ma, D.; Hu, B.; Wang, J.; Singh, A.; Mather, B. Hardware design of medium voltage SiC-based modular multilevel converters for grid-tied applications. In Proceedings of the 2021 IEEE 8th Workshop on Wide Bandgap Power Devices and Applications (WiPDA), Redondo Beach, CA, USA, 7–10 November 2021; pp. 339–344. [Google Scholar] [CrossRef] [Scilit]
  14. Dalal, D.N.; Christensen, N.; Jørgensen, A.B.; Jørgensen, J.K.; Bęczkowski, S.; Munk-Nielsen, S.; Uhrenfeldt, C. Impact of Power Module Parasitic Capacitances on Medium-Voltage SiC MOSFETs Switching Transients. IEEE J. Emerg. Sel. Top. Power Electron. 2020, 8, 298–310. [Google Scholar] [CrossRef] [Scilit]
  15. Xu, Y.; Feng, X.Y.; Wang, J.; Gao, C.F.; Burgos, R.; Boroyevich, D.; Hebner, R.E. Medium-voltage SiC-based converter laminated bus insulation design and assessment. IEEE J. Emerg. Sel. Top. Power Electron. 2019, 7, 1715–1726. [Google Scholar] [CrossRef] [Scilit]
  16. Stewart, J.; Xu, Y.; Burgos, R.; Ghassemi, M. Design of a multilayer PCB bus for medium voltage DC converters. In Proceedings of the 2019 IEEE Electric Ship Technologies Symposium (ESTS), Arlington, VA, USA, 14–16 August 2019; pp. 329–336. [Google Scholar] [CrossRef] [Scilit]
  17. Ravi, L.; Lin, X.; Dong, D.; Burgos, R. A 16 kV PCB-based DC-bus distributed capacitor array with integrated power-AC-terminal for 10 kV SiC MOSFET modules in medium-voltage inverter applications. In Proceedings of the 2020 IEEE Energy Conversion Congress and Exposition (ECCE), Detroit, MI, USA, 11–15 October 2020; pp. 3998–4005. [Google Scholar] [CrossRef] [Scilit]
  18. Xu, Y.; Stewart, J.; Song, H.; Cheng, L.; Cvetkovic, I.; Burgos, R.; Boroyevich, D. High power density medium-voltage converter integration via electric field management. IEEE J. Emerg. Sel. Top. Power Electron. 2022, 10, 895–905. [Google Scholar] [CrossRef] [Scilit]
  19. Zhang, C.X.; Xu, Y.; Dong, M.; Burgos, R.; Ren, M.; Boroyevich, D. Design and assessment of external insulation for critical components in a medium voltage SiC-based converter via optical method. IEEE Trans. Power Electron. 2020, 35, 12887–12897. [Google Scholar] [CrossRef] [Scilit]
  20. Stewart, J.; Motwani, J.K.; Yu, J.; Cvetkovic, I.; Burgos, R. Improved Power Density of a 6 kV, 1 MW Power Electronics Building Block Through Insulation Coordination. In Proceedings of the 2022 IEEE 23rd Workshop on Control and Modeling for Power Electronics (COMPEL), Tel Aviv, Israel, 20–23 June 2022; pp. 1–7. [Google Scholar] [CrossRef] [Scilit]
  21. Dalal, D.N.; Zhao, H.; Jørgensen, J.K.; Christensen, N.; Jørgensen, A.B.; Bęczkowski, S.M.; Uhrenfeldt, C.; Munk-Nielsen, S. Demonstration of a 10 kV SiC MOSFET Based Medium Voltage Power Stack. In Proceedings of the 2020 IEEE Applied Power Electronics Conference and Exposition (APEC), New Orleans, LA, USA, 15–19 March 2020; pp. 2751–2757. [Google Scholar] [CrossRef] [Scilit]
  22. Xiao, K.; Zhang, Y.; Tan, S.; Pan, J.; Feng, H.; Liang, Y.; Zeng, Z. Design and Demonstration of a 10 kV, 60 A SiC MOSFET-Based Medium-Voltage Power Module. Energies 2025, 18, 4407. [Google Scholar] [CrossRef] [Scilit]
  23. Zhang, Y.; Wang, Y.; Wang, D.; Feng, H.; Ran, L. Design of high isolation and compact gate driver for 6.5 kV IGBT module in medium voltage converters. In Proceedings of the 2023 IEEE Applied Power Electronics Conference and Exposition (APEC), Orlando, FL, USA, 19–23 March 2023; pp. 306–311. [Google Scholar] [CrossRef] [Scilit]
  24. Zhang, F. Research on High-Isolation and High-Immunity Gate Driver for Medium-Voltage SiC MOSFET under High Switching Speed. Master’s Thesis, Chongqing University, Chongqing, China, 2025. (In Chinese) [Google Scholar]
  25. Guo, Z.; Li, H. A Fiber-Optic-Less 50-MHz Single Transformer Isolated Gate Driver With Fault Feedback for 10-kV SiC MOSFETs. IEEE Trans. Ind. Electron. 2024, 71, 10854–10863. [Google Scholar] [CrossRef] [Scilit]
  26. Chen, Z.; Huang, A.Q. Busbar design for high-power SiC converters. Electronics 2024, 13, 4758. [Google Scholar] [CrossRef] [Scilit]
  27. Diendorfer, C.; Yang, Q.; Song, S.; Barnola, I.; Ramin, R. Electrical Design and Evaluation for a 10 kV SiC Power Module-Based Submodule of a Modular Multilevel Converter. In Proceedings of the IECON 2024—50th Annual Conference of the IEEE Industrial Electronics Society, Chicago, IL, USA, 3–6 November 2024; pp. 1–7. [Google Scholar] [CrossRef] [Scilit]
  28. IPC-2221; Generic Standard on Printed Board Design. Association Connecting Electronics Industries: Bannockburn, IL, USA, 1998.
  29. IPC-2152; Standard for Determining Current-Carrying Capacity in Printed Board Design. Association Connecting Electronics Industries: Bannockburn, IL, USA, 2009.
  30. Wu, H.; Wang, J.; Liu, P.; Peng, Z.; Deng, Z.; Wei, X. Research on corona inception electric-field strength and critical electric-field values for valve hall fittings. In Proceedings of the 2014 IEEE Conference on Electrical Insulation and Dielectric Phenomena (CEIDP), Des Moines, IA, USA, 19–22 October 2014; pp. 308–311. [Google Scholar] [CrossRef] [Scilit]
  31. Wang, J.; Wu, H.; Deng, Z.; Peng, Z.; Liao, J. E-field distribution analysis on three types of converter double valve in 800 kV valve hall. In Proceedings of the 2015 IEEE 11th International Conference on the Properties and Applications of Dielectric Materials (ICPADM), Sydney, NSW, Australia, 2015; pp. 692–695. [Google Scholar] [CrossRef] [Scilit]
  32. Li, X.; Chen, Y.; Chen, H.; Paul, R.; Song, X.; Mantooth, H.A. A 10 kV SiC MOSFET Power Module With Optimized System Interface and Electric Field Distribution. IEEE Trans. Power Electron. 2024, 39, 9540–9553. [Google Scholar] [CrossRef] [Scilit]
  33. IEC 60270; High-Voltage Test Techniques—Partial Discharge Measurements. IEC: Geneva, Switzerland, 2015.
  34. IEC 60060-1:2010; High-Voltage Test Techniques—Part 1: General Definitions and Test Requirements. IEC: Geneva, Switzerland, 2010.
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Article Metrics

Citations

Article Access Statistics

Article metric data becomes available approximately 24 hours after publication online.