Temporal Feature Clustering-Based Two-Level Equivalent Modeling and Coordinated Regulation of Distributed Resources Under Extreme Events

,
,
,
,
,
,
and
1
Duyun Power Supply Bureau, Guizhou Power Grid Co., Ltd., Duyun 558000, China
2
School of Electric Power Engineering, South China University of Technology, Guangzhou 510641, China
*
Author to whom correspondence should be addressed.

Abstract

High penetration of distributed energy resources and frequent extreme events challenge the operation of distribution networks. Numerous heterogeneous devices must be coordinated while accounting for their time-varying operating patterns and network constraints. This paper proposes an identification-modeling-regulation framework for distributed resource clusters. First, 768-dimensional temporal features extracted from eight seasonal day-type scenarios are reduced by principal component analysis and grouped into six clusters using K-means++. The held-out silhouette coefficient is 0.656 in a common standardized temporal feature space, compared with 0.591 for grouping by device type. Second, a two-level equivalent model uses clusters as control objects and 22 feeder blocks as injection units, yielding a maximum voltage deviation of 0.0151 p.u. and a loss underestimation of 4.09% at nominal load. Third, an event-driven regulation strategy formulates a linear program for each energized component and verifies the disaggregated device commands by detailed AC power flow. Case studies on a real 10 kV network with 214 modeled devices use synthetic annual operating profiles and planned wind and storage units. Under the modeled conditions, 71.57%, 83.31%, and 78.44% of total demand are served in the typhoon, heatwave, and thunderstorm scenarios, respectively.

1. Introduction

Driven by the carbon-peaking and carbon-neutrality goals, distribution networks are transforming from passive networks into active networks with deeply integrated distributed energy resources (DERs). Grid-connected photovoltaic (PV) systems and wind generation introduce technical challenges such as voltage rise, bidirectional power flow and protection coordination [1,2]. Meanwhile, extreme events, including typhoons, ice storms, lightning and prolonged heatwaves, occur more frequently and threaten the secure operation of distribution networks, motivating extensive research on resilience quantification and enhancement [3,4]. Against this background, the coordinated regulation of massive heterogeneous DERs faces three fundamental contradictions: (i) the number of controllable devices is large, whereas the computational capability of the control center is limited; (ii) the device types are heterogeneous, whereas a unified regulation interface is required; and (iii) the operation patterns vary with time, whereas the regulation model needs to remain relatively stable. Cluster equivalent modeling, which groups scattered devices into a small number of aggregated units, is a mainstream approach to resolve these contradictions, but existing methods still suffer from unsystematic feature extraction, unreasonable cluster partitioning, equivalent models lacking physical support, and regulation strategies that are difficult to implement in practice.
A substantial body of work has addressed cluster partitioning of distribution networks. Classical clustering algorithms, such as K-means [5], K-means++ [6] and silhouette-based validation [7], have been widely applied to electrical load pattern grouping [8]. In power systems, network partitioning is frequently performed by hierarchical spectral clustering of power grids [9], by electrical distance derived from the node impedance matrix [10,11], and by network-partition-based voltage coordination control for high-PV distribution networks [12]. Electrical and geographical partitions capture network structure, whereas temporal features capture similarities in device operation across seasonal and day-type conditions. The two criteria can therefore lead to different groupings on the same network.
On the equivalent modeling side, the classical Ward equivalent [13] and electromechanical equivalents constructed by modal analysis [14] laid the foundations for network reduction. Recent studies develop dynamic equivalents of active distribution networks with synthesized load units [15] and analyze the aggregated behavior of multiple distributed generations [16]. However, most existing equivalent models focus on static parameters and aggregate an entire cluster into a single equivalent node. When a cluster spans several feeders, moving its injections to a single node can change branch power flows and affect voltage and loss estimates.
For the regulation of DERs, virtual power plants (VPPs) aggregate distributed resources for scheduling and market participation under various uncertainties [17], demand response (DR) provides flexible adjustment capability on the load side [18], peer-to-peer energy sharing further decentralizes the coordination [19], and distribution-level market-based aggregation further optimizes the VPP portfolio [20]. Under extreme events, resilience-oriented operation typically evaluates system performance curves and restores critical loads with microgrids [3,4]. The resulting dispatch problem requires both an aggregation rule and a check of whether the disaggregated commands can be delivered within the source, device, and network limits of each post-event component. Table 1 summarizes the representative studies discussed above and their key limitations.
Table 1. Comparison between the proposed method and representative studies on cluster partitioning, equivalent modeling, and regulation of distributed resources.
To fill this gap, this paper proposes an integrated identification–modeling–regulation framework for distributed resource clusters, comprising multi-scenario temporal feature clustering, a two-level cluster equivalent model, and event-driven cluster-level coordinated regulation. The framework is evaluated on a practical 10 kV distribution network using network and load/PV records, synthetic operating profiles, and planned wind and storage configurations. The main contributions are summarized as follows.
  • A temporal-feature-based cluster partitioning method is proposed for heterogeneous DERs. The method is compared with electrical-distance clustering and direct grouping by reference device type. Operating-pattern separation is assessed in a common temporal feature space using both full-year and held-out profiles, and the sensitivity of the partition is examined across data-generation seeds and profile perturbations.
  • A two-level cluster equivalent model is constructed from the regulation perspective. Feature-based clusters act as control objects, while feeder-level blocks within each cluster act as equivalent injection units. The effects of injection-node selection and feeder subdivision on voltage deviation and active power loss are quantified against a detailed AC model.
  • An event-driven cluster-level coordinated regulation strategy is developed for extreme events. Device capability limits and nodal voltage sensitivities are incorporated into a linear program for each energized component. The resulting cluster-level targets are decomposed into device commands and checked by detailed AC power flow subject to the assumed voltage reference and source limits.
Figure 1 illustrates the overall framework, which consists of three stages: temporal feature extraction and cluster partitioning (Stage I), two-level equivalent modeling (Stage II), and event-driven coordinated regulation (Stage III).
Figure 1. Overview of temporal grouping, feeder-level injection equivalencing, and event dispatch with device-level AC verification.
The rest of this paper is organized as follows. Section 2 presents the temporal feature extraction and cluster partitioning method. Section 3 develops the two-level equivalent model and the event-driven coordinated regulation strategy. Section 4 describes the test system, the data and the extreme event scenarios. Section 5 reports and discusses the case study results. Section 6 concludes the paper.

2. Temporal Feature Extraction and Cluster Partitioning

2.1. Problem Description and Data Preprocessing

The distributed resources considered in this paper comprise six source/load types: residential loads, commercial loads, industrial loads, PV generation, wind generation and energy storage systems (ESSs). The input data consist of synthetic device-level daily power curves with a 15 min resolution (96 points per day) covering one full year (365 days). The curves are generated using type-specific templates and scaled by device rated active power. To guarantee the quality of the extracted features, a daily curve is discarded if more than 20% of its samples are missing. A PV curve is also discarded if its maximum output in the daytime screening window is below 0.01 MW, and a load curve is discarded if its daily maximum is below 0.01 MW. A moving-average filter is applied with window lengths of five points for PV, three for loads and wind, and two for ESSs.

2.2. Multi-Scenario Typical Curves and Temporal Feature Vectors

The operation pattern of a DER differs on two orthogonal time scales: the seasonal scale (irradiation, temperature and load composition) and the day-type scale (production versus household electricity-use patterns). Accordingly, the one-year dataset is partitioned into four seasons (spring, summer, autumn and winter) and two day types (workday and weekend), forming eight operation scenarios, which jointly cover the dominant operation conditions of the network. For each device and each scenario, the typical daily curve is extracted as the element-wise median of all qualified daily curves in that scenario:
p ¯ i , s , t = m e d i a n p i , d , t ∣ d ∈ D i , s
where p ¯ i , s , t denotes the power of device i at time step t of day d, and D i , s is the set of qualified days of device i in scenario s. The median operator is preferred over the mean because it is robust against outlier days that pass the quality filters.
Because devices of the same type may have different capacities, each typical curve is normalized by its peak magnitude to retain its shape for clustering. The normalized curve is defined as follows.
p ^ i s t = p i s t a i s ,     a i s > 10 − 6 MW p i s t ,     a i s ≤ 10 − 6 MW
where p i s t and p ^ i s t denote the original and normalized values of the typical power curve, respectively, for device i in scenario s at time step t. For load, photovoltaic and wind devices, a i s is the maximum value of p i s t over the 96 time steps. For energy storage devices, a i s is the maximum absolute value over the same time steps, accounting for both charging and discharging. When a i s does not exceed 10 − 6 MW, the original curve is retained without rescaling.
The eight normalized typical curves of each device are concatenated in a fixed scenario order, forming a 768-dimensional (8 × 96) temporal feature vector, which serves as the “operation fingerprint” of the device:
f i = p ^ i , 1,1 , … , p ^ i , 8,96 T ∈ R 768
where f i is the feature vector of device i. Through this construction, all six heterogeneous source/load types are mapped into one unified feature space, in which “similar operation patterns” can be measured directly. Figure 2 visualizes the typical curves of the six types under the eight scenarios for the test system described in Section 4.
Figure 2. Median normalized typical profiles for six device types across eight seasonal and day-type scenarios.

2.3. PCA-Based Dimensionality Reduction

Before applying PCA, each coordinate of the 768-dimensional feature vector is standardized using its mean and standard deviation across the devices in the fitting data. The standardized feature vector is projected onto the retained principal directions using PCA [21], as follows.
z i = W T x i
where x i denotes the standardized feature vector for device i, W is the matrix whose columns are the retained principal directions, and z i is the projected feature vector. The smallest retained dimension is selected using the 90% cumulative explained-variance criterion in Equation (5).
d = m i n d ′ ∣ ∑ j = 1 d ′ λ j ∑ j = 1 768 λ j ≥ 0.90
where λ j is the j-th eigenvalue of the covariance matrix. For the full-year features of the 214-device case, four principal components retain 90.50% of the variance, as shown in Figure 3.
Figure 3. Cumulative explained variance of the principal components; the first four components retain 90.5% of the total variance.

2.4. K-Means++ Clustering and Evaluation Metrics

The reduced feature vectors are partitioned with the K-means++ algorithm, whose careful seeding improves both the quality and the stability of the clustering result compared with the classical random seeding [6]. The algorithm minimizes the within-cluster sum of squared distances:
m i n C 1 , … , C K ∑ k = 1 K ∑ i ∈ C k z i − μ k 2
where C k is the k-th cluster, μ k is its centroid, and K is the number of clusters. In this work, K is set to six, corresponding to the six reference device types. A scan from K = 4 to K = 10 is used to evaluate inertia and the silhouette coefficient in the PCA space.
Two metrics are used to evaluate the clustering quality. The silhouette coefficient measures how compact and well separated the clusters are:
s i = b i − a i m a x a i , b i
where a i is the mean distance from device i to the other members of its own cluster and b i is the mean distance to the members of the nearest neighboring cluster. Because the device types are known from the registry, the physical interpretability of the clusters is additionally quantified by the cluster purity against the type labels:
P = 1 N ∑ k = 1 K m a x c C k ∩ T c
where N is the total number of devices, T c is the set of devices whose registered type is c , and · denotes the cardinality of a set. The reference labels include residential, commercial, and industrial categories inferred from distribution transformer capacity, together with photovoltaic, wind, and storage categories. Purity therefore measures agreement with the reference labels. The silhouette coefficient and the within-group sum of squared distances per device are also calculated in the same standardized temporal feature space for all groupings. This common-space comparison measures operating-pattern separation independently of the feature space used to construct each grouping.

2.5. Comparison Groupings and Held-Out Evaluation

To demonstrate the value of the temporal features, an electrical-distance clustering method is implemented as the baseline. The node admittance matrix Y is first built from the network parameters, with a large grounding admittance added at the slack buses to keep Y invertible, and the node impedance matrix is obtained as:
Z = Y − 1
where Y is the nodal admittance matrix of the network. The electrical distance between two nodes is then defined by the classical impedance-difference measure:
D i j = Z i i + Z j j − 2 Z i j
where D i j is the electrical distance between nodes i and j, and Z i j is the corresponding element of the node impedance matrix Z. The absolute-value operator denotes the magnitude of the complex impedance difference.
For electrical-distance clustering, the distance vector of each device node is used directly as the input to K-means++, with six clusters, ten initializations, and the same random seed as the temporal-clustering comparison. The type-grouping baseline assigns each device to its reference type directly. It therefore has 100% purity by construction.
To evaluate operating-pattern separation on held-out days, every fourth day within each season and day-type stratum is reserved for evaluation. Standardization, PCA, and temporal clustering are fitted on the remaining dates. The held-out profiles of the same devices are then standardized using the fitted parameters and evaluated with the fixed grouping assignments. This procedure assesses the temporal consistency of the grouping within the test system.

3. Two-Level Equivalent Modeling and Event-Driven Coordinated Regulation

3.1. Two-Level Architecture: Feature Clustering for Control and Feeder Blocking for Modeling

At Level 1, the temporal clusters obtained in Stage I serve as control objects. At Level 2, the devices within each cluster are subdivided by feeder to form equivalent injection blocks. This construction retains the same device membership at both levels and represents network injections at a finer spatial resolution than the control decisions.
Aggregation is performed separately within each source-connected component. For the test system, six temporal clusters yield 22 feeder blocks. Two single-node baselines are included in the voltage and loss comparisons. Each cluster is represented within each component by either its largest device location or its capacity-weighted electrical center. The single-center and feeder-center cases use the same placement rule, allowing the effect of feeder subdivision to be assessed.

3.2. Equivalent Injections and AC Power Flow

For a feeder block b, the equivalent active and reactive injections are the sums of the device injections at the evaluated operating point. Generation has a positive injection and load consumption has a negative injection. Reactive load consumption is calculated from the corresponding power factor. Distributed generators and ESS units that do not serve as voltage references are represented at the unity power factor in the case study.
P b = ∑ i ∈ b P i
Q b = ∑ i ∈ b Q i
where b denotes a feeder block, i indexes the devices within that block, and P i and Q i are the active and reactive injections of device i at the evaluated operating point. The quantities P b and Q b are the corresponding block-level injections.
Each equivalent injection node is selected from the device nodes within the corresponding block by minimizing the capacity-weighted electrical distance to its member devices as follows.
n b = a r g m i n n ∈ N b ∑ i ∈ b P r , i D n , n i
where n b is the selected injection node of block b, N b is the set of device nodes within the block, P r , i is the rated active power of device i, n i is its node, and D n , n i is the electrical distance from candidate node n to node n i .
The single-center baseline uses the same placement rule, and the largest-device baseline uses the location of the device with the highest rated active power. Both the detailed and equivalent AC models retain the full branch network. The equivalent model represents the same total injections at fewer nodes.
Balanced Newton–Raphson AC power flow is used to calculate the nodal voltages, active power losses, and active and reactive outputs of the reference source. For the detailed-network load scan, the calculated nodal voltage magnitudes are cross-checked against an independent backward–forward sweep.

3.3. Equivalent Accuracy Metrics

Three metrics quantify the accuracy of the equivalent model against the detailed AC solution. The maximum absolute voltage deviation and the voltage mean absolute percentage error measure voltage accuracy, and the signed active power loss bias measures loss overestimation or underestimation. The loss difference is also reported in megawatts, and the voltage-limit classifications of the two models are compared at each energized node.
ε v = m a x n V n , e q − V n , A C
M A P E v = 100 % N ∑ n V n , e q − V n , A C V n , A C
ε l = 100 % × P l , e q − P l , A C P l , A C
where V n , e q and V n , A C are the voltage magnitudes at energized node n in the equivalent and detailed AC models, respectively, and N is the number of energized nodes included in the comparison. P l , e q and P l , A C are the total active power losses from the equivalent and detailed AC models, respectively.

3.4. Event-Driven Cluster-Level Coordinated Regulation

3.4.1. Post-Event Components and Supply Limits

After removal of the tripped branches, the regulation problem is formulated separately for each connected component. A component connected to a substation retains its upstream voltage reference. For each island with an eligible planned storage unit, that unit is assumed to provide the voltage reference subject to the modeled active and reactive power limits. An island without an available voltage reference is classified as de-energized, and its demand is counted as unserved.
For the grid-connected heatwave scenario, the pre-event AC import of each component defines its base import cap. An alternative case allows additional upstream headroom. The imposed cap defines the required local response to the load surge. The AC reference-source output includes the power required to cover network losses.

3.4.2. Cluster Capability Assessment Under the Event

The adjustable demand of each load is limited to its event-time consumption multiplied by the device-specific demand-response fraction. PV and wind generation are set to their synthetic available outputs, with zero upward reserve. In an energized island, their downward adjustment is limited by the current output and the power change achievable within the required response time.
Storage starts at zero active power. For each unit, the maximum discharge is the minimum of rated power, the ramp-limited power change, and the energy-limited discharge over the event duration. The energy limit uses the initial state of charge, the minimum state of charge, the energy capacity, and the discharge efficiency. The same active-power limit applies to storage acting as the voltage reference.
P i , m a x = m i n P i , r a t e d , r i T r , η i E i m a x S O C i , 0 − S O C i , m i n , 0 T h
where P i , m a x is the maximum available discharge power of storage device i and P i , r a t e d is its rated active power. The ramp rate r i is expressed in MW/min and the response time T r in minutes. The rated energy E i is expressed in MWh, the event duration T h in hours, and η i is the discharge efficiency. The quantities S O C i , 0 and S O C i , m i n are the initial and minimum states of charge, expressed as fractions.

3.4.3. Cluster-Level Linear Programming Model

Within each energized component, each eligible cluster action has a utilization variable between zero and one. The action may combine controllable demand reduction and non-reference storage discharge in proportion to their available capacities. Eligible renewable curtailment is represented by a separate downward action. An additional utilization variable represents involuntary load shedding, distributed in proportion to the remaining demand after reserving the maximum controllable demand reduction. Demand response and involuntary shedding change reactive demand according to the load power factor.
The coordinated regulation problem is formulated as a linear program (LP) that penalizes the total absolute change in scheduled active power, with a weight of 1000 on involuntary shedding and a unit weight on other actions. The sensitivities of nodal voltage magnitudes and reference-source active and reactive outputs are calculated by finite differences using a backward–forward sweep at the current operating point. The corresponding linear constraints impose nodal voltage and source-output limits. The number of decision variables depends on the available control groups and actions in each component.
Δ P i = ∑ j B i j P u j Δ Q i = ∑ j B i j Q u j 0 ≤ u j ≤ 1
m i n u ∑ j w j c j u j
y ^ u = y u 0 + J u − u 0 ; y = V 1 , … , V n , P r e f , Q r e f T
y m i n ≤ y ^ u ≤ y m a x
where i indexes devices and j indexes control actions. The variable u j denotes the utilization of action j . The coefficients B i j P and B i j Q denote, respectively, the active and reactive injection changes for device i at full utilization. The coefficient c j is the sum of the absolute active-power changes associated with action j , and w j is its objective weight. The vector y contains nodal voltage magnitudes and reference-source active and reactive outputs. The vector u 0 denotes the current linearization point, J is the sensitivity matrix at that point, and y ^ u is the resulting prediction. The vectors y m i n and y m a x specify the applicable lower and upper limits, respectively.
The same formulation is applied to direct grouping by device type, electrical-distance clustering, and the device-level benchmark. In the device-level benchmark, each eligible device forms an individual control group. All formulations are evaluated under the same modeled constraints.

3.4.4. Device-Level Disaggregation and AC Verification

The cluster-level utilization variables are decomposed into individual device commands using the capacity-proportional mapping adopted for sensitivity calculation. The device adjustment bounds are checked, and the resulting commands are applied to the detailed AC network. A solution is accepted when the AC power flow converges and the modeled voltage and reference-source limits are satisfied. If a bound is violated, the linearization is updated, the corresponding margin is tightened, and the LP is solved again. Cases without an accepted solution are reported separately.
The served-load ratio is the total demand remaining after both demand response and involuntary shedding, divided by total event demand. All demand in de-energized components is counted as unserved. This ratio includes load supplied by upstream or local resources.
R s e r v e d = 100 % × ∑ n P n , s e r v e d ∑ n P n , e v e n t
where R s e r v e d is the system-wide served-load ratio, P n , e v e n t is the event demand at node n , and P n , s e r v e d is the demand served at that node after demand response and involuntary load shedding. For each de-energized node, P n , s e r v e d is set to zero. The summations cover all demand nodes in the event case.

4. Case Studies and Simulation Setup

4.1. Test System

The test system is a practical 10 kV distribution network in China, as shown in Figure 4. The network contains 385 nodes, two substations and five feeders. Standard distribution test feeders provide a reference for the scale of this network [22,23,24]. The topology and load and PV capacity data are taken from network records. The three wind turbines and six ESS units are planned configurations. Residential, commercial, and industrial load categories are inferred from distribution transformer capacity tiers. Each planned ESS has a rated energy capacity of 1 MWh. Table 2 summarizes the main parameters of the test distribution network.
Table 2. Main parameters of the test distribution network.
Figure 4. Topology of the test system: a practical 10 kV distribution network in China, with 385 nodes, five feeders and two substations. Node coordinates are schematic only.
The device registry contains 214 devices. The 196 loads are mapped from the distribution transformer capacity tiers of the registry: transformers no larger than 200 kVA are classified as residential loads (134 devices, 6.978 MW), those between 200 and 1000 kVA as commercial loads (45 devices, 14.592 MW) and those above 1000 kVA as industrial loads (17 devices, 20.733 MW), totaling 42.303 MW. The nine PV plants (6.932 MW) come from the actual registry and are co-located with loads. The three wind turbines (6 MW) and six ESS units (3 MW) are planned configurations, since the real network does not yet contain wind or storage assets; this is stated explicitly for transparency.

4.2. Operation Data

One-year device-level time series with a 15 min resolution (365 × 96 points) are generated using type-specific templates and scaled by the rated active power of each device. The templates incorporate seasonal and day-type variation, device-specific variation, and artificial disturbances. A fixed seed of 42 is used for the main case. Measured profiles are unavailable for calibration of the noise and spatiotemporal dependence.
Sensitivity to data construction is evaluated over ten data-generation seeds (42–51). The disturbance tests include additive noise with standard deviations of 2.5%, 5%, and 10% of rated power and a within-day autoregressive coefficient of 0.8. For the correlated case, a shared feeder component accounts for 60% of the added noise variance. Missing data are introduced in six-hour intervals at two levels, approximately 5% and 15% of samples. In a separate test, the day-level perturbations in peak timing and peak width are doubled. The sensitivity to K-means++ initialization is evaluated using ten seeds for the main input realization.

4.3. Loading Conditions and Event Scenarios

The static equivalence tests use nominal, light, and peak load multipliers of 1.0, 0.5, and 1.3. The corresponding generation multipliers are 1.0, 0.6, and 1.0, with storage idle. A separate load scan uses multipliers from 0.5 to 1.5 with generation held at its nominal setting. For the linearization test, the detailed AC results are compared with linear predictions for a common demand-response direction at 0%, 25%, 50%, 75%, and 100% of the available demand-response capability.
The event study uses the same synthetic day for the three main cases. The typhoon case opens two feeder-head branches at 14:00. The heatwave case increases load by 20% at 20:00 under the modeled import cap. The thunderstorm case opens three branches at 22:00. The response times are 180, 600, and 120 s, respectively. The base event duration is 30 min, and the initial storage state of charge is 80%. The case-study voltage window is 0.93–1.07 p.u. The sensitivity cases vary event time, storage state of charge and duration, grid-forming availability, the presence of planned assets, and the heatwave surge and upstream headroom.
An additional stress test uses the 20:00 pre-event operating point of the heatwave case. Active and reactive demands are scaled by the same factor, with the network topology, available generation, and storage settings held fixed. At each loading level, the first temporal-grouping LP schedule is evaluated using detailed AC power flow before any relinearization. The scan is conducted with the heatwave import cap in place and with the cap removed to isolate the voltage constraint. The first transition from AC feasibility to an AC constraint violation is refined by bisection to a load-multiplier interval narrower than 0.00001. The AC feasibility check uses tolerances of 10−5 p.u. for voltage and 10−5 MW for active power.

4.4. Computational Scaling Test

The effect of aggregation on LP runtime is quantified in a separate synthetic scaling test. The number of participating devices N is increased from 200 to 50,000, and the devices are assigned to six groups. Devices within each group share the same cost and voltage coefficients. Both formulations use 12 synthetic voltage constraint rows and one aggregate dispatch constraint, in addition to the variable bounds. The device-level formulation has N decision variables, and the aggregated formulation has six. For each size, the median runtime of five HiGHS LP calls is recorded. The timing covers the LP call, with data aggregation, matrix construction, command disaggregation, and AC verification outside the timed interval.
At 50,000 devices, the median runtime is 266.66 ms for the device-level LP and 1.02 ms for the aggregated LP. Both formulations return the same objective value to numerical precision for this synthetic benchmark. Figure 5 reports the solver-call times as the number of devices increases.
Figure 5. Median HiGHS LP runtime over five calls for the device-level and six-group formulations in the synthetic benchmark.

5. Results and Discussion

5.1. Cluster Partitioning Validity

Figure 2 and Figure 3 show the typical profiles and the variance retained by PCA. Among the values of K from four to ten, K = 6 yields the highest silhouette coefficient in the PCA space for the main realization. The full-year temporal grouping has a purity of 98.60% against the reference types. Its common-space silhouette is 0.679, compared with 0.607 for direct type grouping and −0.158 for electrical-distance clustering.
On held-out days, the common-space silhouettes are 0.656, 0.591, and −0.146, respectively. The temporal grouping therefore gives stronger separation of operating patterns than direct type grouping on these synthetic days. The agreement with reference types is partly shaped by the type-specific generators and the capacity-based load labels. Table 3 summarizes the comparison among the three grouping methods.
Table 3. Clustering comparison in the common standardized temporal feature space.
Figure A1 shows the full-year and held-out silhouette coefficients alongside the K scan. The temporal grouping is identical across the ten tested K-means++ seeds for the main input realization.
Figure A2 shows the sensitivity to profile generation and perturbation. Across the eight scenario settings, the temporal grouping has mean purity between 96.36% and 97.34%. The lowest purity in the runs is 95.79%, and the lowest adjusted Rand index relative to the main realization is 0.576. The change in adjusted Rand index indicates that agreement with device types can remain high even when individual device assignments change.

5.2. Accuracy of the Two-Level Equivalent Model

Figure 6 compares the detailed and two-level AC voltage profiles for the nominal, light, and peak load conditions. The two-level model has maximum voltage errors of 0.0151, 0.0103, and 0.0126 p.u., respectively. It underestimates active power loss by 0.01237, 0.00437, and 0.01874 MW, corresponding to signed biases of −4.09%, −5.47%, and −3.74%. Table 4 shows the effects of injection-node selection and feeder subdivision.
Figure 6. Detailed and two-level AC voltage profiles under (a) nominal, (b) light, and (c) peak load.
Table 4. Voltage and active power loss accuracy against the detailed AC model.
Figure A3 shows that the benefit of feeder subdivision depends on the operating condition and the injection-node rule. At nominal load, the change from the largest-device node to the single electrical center reduces the maximum voltage deviation from 0.01692 to 0.01538 p.u. Feeder subdivision gives a further reduction to 0.01513 p.u. At light load, the largest-device placement gives a lower maximum voltage error than feeder subdivision. These results show that voltage error and loss bias should be assessed together when selecting an equivalent model. Loss underestimation can reduce the predicted upstream power requirement, and voltage error can affect the assessment of nodes close to a limit. The dispatch verification therefore uses the detailed AC network and accounts for losses in the reference-source output.
Figure A4 compares linearized voltage changes with detailed AC power flow over the tested demand-response directions and load multipliers of 0.5–1.5. The largest voltage-magnitude error is 5.55 × 10−5 p.u., and the linear predictions and detailed AC results give the same voltage feasibility classifications within the 0.93–1.07 p.u. case-study window.
With the heatwave import cap in place, the first LP schedule violates the cap in the detailed AC check at a load multiplier of approximately 1.0053. All nodal voltages remain within the case-study limits at this transition. At the 1.20 multiplier used in the main heatwave case, the LP predicts an import of 13.52589 MW in the limiting component, equal to its cap, while detailed AC power flow gives 13.52832 MW for the same schedule. The import decreases to 13.52296 MW after relinearization and passes the AC check.
With the import cap removed, the first LP schedule violates the lower voltage limit in the detailed AC check at a load multiplier of approximately 3.5780. At a multiplier of 4.00, the LP predicts a minimum voltage of 0.93000 p.u., while detailed AC power flow gives 0.92982 p.u. for the same schedule. After relinearization, the detailed AC minimum voltage is 0.93022 p.u. These thresholds apply to the tested heatwave loading direction and the specified feasibility tolerances.

5.3. Coordinated Regulation Under Extreme Events

Table 5 and Figure A5 compare the served-load ratios under the three extreme events. The proposed temporal grouping serves 71.57%, 83.31%, and 78.44% of total demand in the typhoon, heatwave, and thunderstorm cases, respectively. Direct grouping by device type gives the same ratios to the reported precision, and the device-level benchmark yields similar values. Thus, the improvement in operating-pattern separation shown in Section 5.1 is accompanied by comparable served-load performance for the two groupings in the tested events.
Table 5. AC-verified served-load ratios under the three main event scenarios.
The temporal-grouping schedules pass the modeled device, voltage, and reference-source checks in the energized components. Across the three main events, the detailed AC power flow gives nodal voltages of 0.9822–1.0045 p.u. in the energized components under the temporal-grouping schedules, within the case-study limits of 0.93–1.07 p.u. One component in the typhoon case and two in the thunderstorm case have no available voltage reference and are counted as de-energized. For the electrical-distance baseline, the dispatch LP reports infeasibility in one component of each of those two events. Its heatwave result serves 88.80% of demand under the modeled limits. The modeled island response draws on the use of microgrids for service restoration [25] and storage for flexibility [26]. The nodal voltage checks address the voltage impact of device adjustments, a consideration also central to reactive-power-based voltage control [27].
Figure A6 shows the effect of changing the event assumptions. Removing the grid-forming option reduces served demand from 71.57% to 70.61% in the typhoon case and from 78.44% to 76.76% in the thunderstorm case. In the heatwave case, permitting 20% additional upstream import relative to the pre-event level increases the served-load ratio from 83.31% to 98.11%. Raising the heatwave load multiplier from 1.20 to 1.35 under the base import cap reduces the ratio to 77.03%. The comparison shows how the upstream supply boundary and the availability of an island voltage reference affect the reported outcomes.

5.4. Discussion

Temporal clustering and feeder-level aggregation serve different purposes in the framework. The former groups devices with similar synthetic operating profiles, and the latter controls the spatial resolution of injections. The type-grouping comparison shows that the incremental value of temporal clustering depends on the evaluation metric. The observed gains are clearer in operating-pattern separation than in the served-load ratio of the three main events. Zonal voltage control for high-PV distribution networks [28] provides a related application of network partitioning. In the proposed framework, the temporal clusters define control groups and feeder blocks define equivalent injections. The component-wise event assessment addresses the post-event service restoration problem discussed in distribution resilience studies [29]. Distributed partition-based volt/VAR control [30] provides a related approach to voltage coordination, whereas the present regulation study evaluates disaggregated commands and served load after extreme events.
The annual profiles are synthetic, and the wind and storage assets and the island voltage-reference capability are planning assumptions. The type-specific generators influence the separation between device categories. The perturbation tests assess sensitivity to assumed noise and correlation structures, but measured data are needed to establish whether the reported purity and membership stability persist under actual measurement noise and spatiotemporal dependence. The analysis uses balanced steady-state snapshots with assumed import and device limits. Its feasibility results are specific to the modeled network, profiles, and operating constraints. Field deployment would require measured operating data and confirmation of the available source capabilities and network ratings. The present analysis evaluates steady-state voltages and power balance. Time-domain frequency and voltage behavior during fault clearing and island transition remains outside its scope.

6. Conclusions

This paper proposes an integrated identification–modeling–regulation framework for distributed resources in distribution networks. The framework is evaluated on a practical 10 kV network with 214 modeled devices, synthetic annual operating profiles, and planned wind and storage units. The main conclusions are summarized as follows.
  • Multi-scenario temporal feature clustering yields a held-out silhouette coefficient of 0.656 in the common standardized temporal feature space, compared with 0.591 for direct grouping by device type. Both groupings give the same served-load ratios to the reported precision in the three main events.
  • The two-level equivalent model represents the six temporal clusters by 22 feeder-level injection blocks. At nominal load, the maximum voltage deviation is 0.0151 p.u. and the active power loss is underestimated by 4.09% relative to the detailed AC model. In the demand-response scan over load multipliers of 0.5–1.5, the maximum voltage linearization error is 5.55 × 10−5 p.u.
  • For the event-driven coordinated regulation strategy, device commands are verified by detailed AC power flow. The temporal-grouping schedules serve 71.57%, 83.31%, and 78.44% of total demand in the typhoon, heatwave, and thunderstorm cases, respectively. The outcomes depend on the assumed source limits and availability of an island voltage reference. Measured operating data and verified asset capabilities are needed to assess performance under field conditions.

Author Contributions

Conceptualization, Z.Z., Q.Y. and T.Y.; methodology, Z.Z., Y.L. and T.Y.; investigation, Z.Z., Q.Y., Z.L., M.C., Z.M. and Y.L.; resources, Z.Z., Q.Y. and Z.L.; data curation, L.Y.; writing—original draft preparation, Z.M. and Y.L.; writing—review and editing, Z.Z., T.Y. and Z.M.; visualization, Z.M. and Y.L.; supervision, T.Y. and Z.Z.; project administration, Z.Z. and T.Y.; funding acquisition, Z.Z. and T.Y. All authors have read and agreed to the published version of the manuscript.

Funding

This research was supported by the China Southern Power Grid Corporation Technology Project (GZKJXM20240546).

Data Availability Statement

The original contributions presented in the study are included in the article, further inquiries can be directed to the corresponding author.

Conflicts of Interest

Authors Zhi Zhou, Quanhai Yang, Zikun Liu, Manchao Chen, and Lifei Yu were employed by the company Duyun Power Supply Bureau, Guizhou Power Grid Co., Ltd., a subsidiary of China Southern Power Grid Corporation. The remaining authors (Zixi Mo, Tao Yu, and Yubin Liu) declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as potential conflicts of interest. The funder had the following involvement with the study through the employment of authors Zhi Zhou, Quanhai Yang, Zikun Liu, Manchao Chen, and Lifei Yu, whose contributions included conceptualization, methodology, resources, investigation, data curation, writing—review and editing, supervision, project administration, and funding acquisition, as detailed in the Author Contributions section.

Abbreviations

The following abbreviations are used in this manuscript:
BFSBreadth-first search
DERDistributed energy resources
ESSEnergy storage system
LPLinear programming
MAPEMean absolute percentage error
PCAPrincipal component analysis
PVPhotovoltaic
RMSERoot mean square error
SOCState of charge
VVC Voltage and reactive power control
WTWind turbine

Appendix A

The following figures report clustering comparisons, sensitivity to profile perturbations, equivalent-model errors, linearization errors, and the results of the event dispatch and sensitivity cases.
Figure A1. Full-year and held-out silhouette coefficients in the common temporal feature space, and the PCA-space silhouette scan over the number of clusters.
Figure A2. Sensitivity of common-space silhouette, temporal-cluster purity, and adjusted Rand index to profile perturbations. Markers and error bars show the mean and standard deviation across ten data-generation seeds.
Figure A3. Maximum voltage error and signed active power loss bias across load multipliers for three equivalent-injection placements.
Figure A4. Maximum voltage-magnitude error of the linear approximation against detailed AC power flow across load multipliers and demand-response utilization levels.
Figure A5. AC-verified served-load ratios under three extreme events. Crosses denote groupings for which at least one component has no accepted dispatch solution.
Figure A6. Served-load ratios under variations in event time, grid-forming availability, storage state of charge, event duration, upstream headroom, and planned resource availability.

References

  1. Karimi, M.; Mokhlis, H.; Naidu, K.; Uddin, S.; Bakar, A.H.A. Photovoltaic penetration issues and impacts in distribution network—A review. Renew. Sustain. Energy Rev. 2016, 53, 594–605. [Google Scholar] [CrossRef] [Scilit]
  2. Ahmed, S.D.; Al-Ismail, F.S.M.; Shafiullah, M.; Al-Sulaiman, F.A.; El-Amin, I.M. Grid integration challenges of wind energy: A review. IEEE Access 2020, 8, 10857–10878. [Google Scholar] [CrossRef] [Scilit]
  3. Panteli, M.; Mancarella, P.; Trakas, D.N.; Kyriakides, E.; Hatziargyriou, N.D. Metrics and quantification of operational and infrastructure resilience in power systems. IEEE Trans. Power Syst. 2017, 32, 4732–4742. [Google Scholar] [CrossRef] [Scilit]
  4. Bie, Z.; Lin, Y.; Li, G.; Li, F. Battling the extreme: A study on the power system resilience. Proc. IEEE 2017, 105, 1253–1266. [Google Scholar] [CrossRef] [Scilit]
  5. MacQueen, J. Some methods for classification and analysis of multivariate observations. In Proceedings of the Fifth Berkeley Symposium on Mathematical Statistics and Probability, Volume 1: Statistics; University of California Press: Berkeley, CA, USA, 1967; Volume 1, pp. 281–297. [Google Scholar]
  6. Arthur, D.; Vassilvitskii, S. K-means++: The advantages of careful seeding. In Proceedings of the 18th Annual ACM-SIAM Symposium on Discrete Algorithms, New Orleans, LA, USA, 7–9 January 2007; pp. 1027–1035. [Google Scholar]
  7. Rousseeuw, P.J. Silhouettes: A graphical aid to the interpretation and validation of cluster analysis. J. Comput. Appl. Math. 1987, 20, 53–65. [Google Scholar] [CrossRef] [Scilit]
  8. Rajabi, A.; Eskandari, M.; Ghadi, M.J.; Li, L.; Zhang, J.; Siano, P. A comparative study of clustering techniques for electrical load pattern segmentation. Renew. Sustain. Energy Rev. 2020, 120, 109628. [Google Scholar] [CrossRef] [Scilit]
  9. Sánchez-García, R.J.; Fennelly, M.; Norris, S.; Wright, N.; Niblo, G.; Brodzki, J.; Bialek, J.W. Hierarchical spectral clustering of power grids. IEEE Trans. Power Syst. 2014, 29, 2229–2237. [Google Scholar] [CrossRef] [Scilit]
  10. Lagonotte, P.; Sabonnadière, J.-C.; Léost, J.-Y.; Paul, J.-P. Structural analysis of the electrical system: Application to secondary voltage control in France. IEEE Trans. Power Syst. 1989, 4, 479–486. [Google Scholar] [CrossRef] [Scilit]
  11. Cotilla-Sanchez, E.; Hines, P.D.H.; Barrows, C.; Blumsack, S.; Patel, M. Multi-attribute partitioning of power networks based on electrical distance. IEEE Trans. Power Syst. 2013, 28, 4979–4987. [Google Scholar] [CrossRef] [Scilit]
  12. Chai, Y.; Guo, L.; Wang, C.; Zhao, Z.; Du, X.; Pan, J. Network partition and voltage coordination control for distribution networks with high penetration of distributed PV units. IEEE Trans. Power Syst. 2018, 33, 3396–3407. [Google Scholar] [CrossRef] [Scilit]
  13. Ward, J.B. Equivalent circuits for power-flow studies. Trans. Am. Inst. Electr. Eng. 1949, 68, 373–382. [Google Scholar] [CrossRef] [Scilit]
  14. Undrill, J.M.; Turner, A.E. Construction of power system electromechanical equivalents by modal analysis. IEEE Trans. Power Appar. Syst. 1971, PAS-90, 2049–2059. [Google Scholar] [CrossRef] [Scilit]
  15. Hu, S.; Li, Y.; Zhang, X.; Mu, Q.; Tian, P. Dynamic equivalents of active distribution networks based on active synthesis load units. IEEE Trans. Power Deliv. 2024, 39, 2041–2052. [Google Scholar] [CrossRef] [Scilit]
  16. Wang, S.; Liu, X.; Wang, K.; Wu, L.; Zhang, Y. Tracing harmonic contributions of multiple distributed generations in distribution systems with uncertainty. Int. J. Electr. Power Energy Syst. 2018, 95, 585–591. [Google Scholar] [CrossRef] [Scilit]
  17. Yu, S.; Fang, F.; Liu, Y.; Liu, J. Uncertainties of virtual power plant: Problems and countermeasures. Appl. Energy 2019, 239, 454–470. [Google Scholar] [CrossRef] [Scilit]
  18. Jordehi, A.R. Optimisation of demand response in electric power systems, a review. Renew. Sustain. Energy Rev. 2019, 103, 308–319. [Google Scholar] [CrossRef] [Scilit]
  19. Chen, L.; Liu, N.; Li, C.; Zhang, S.; Yan, X. Peer-to-peer energy sharing with dynamic network structures. Appl. Energy 2021, 291, 116831. [Google Scholar] [CrossRef] [Scilit]
  20. Liu, X.; Huang, T.; Qiu, H.; Li, Y.; Lin, X.; Shi, J. Optimal aggregation of a virtual power plant based on a distribution-level market with the participation of bounded rational agents. Appl. Energy 2024, 364, 123196. [Google Scholar] [CrossRef] [Scilit]
  21. Jolliffe, I.T. Principal Component Analysis, 2nd ed.; Springer: New York, NY, USA, 2002; ISBN 978-0-387-95442-4. [Google Scholar]
  22. Baran, M.E.; Wu, F.F. Network reconfiguration in distribution systems for loss reduction and load balancing. IEEE Trans. Power Deliv. 1989, 4, 1401–1407. [Google Scholar] [CrossRef] [Scilit]
  23. Kersting, W.H. Radial distribution test feeders. IEEE Trans. Power Syst. 1991, 6, 975–985. [Google Scholar] [CrossRef] [Scilit]
  24. Schneider, K.P.; Mather, B.A.; Pal, B.C.; Ten, C.-W.; Shirek, G.J.; Zhu, H.; Fuller, J.C.; Pereira, J.L.R.; Ochoa, L.F.; de Araujo, L.R.; et al. Analytic considerations and design basis for the IEEE distribution test feeders. IEEE Trans. Power Syst. 2018, 33, 3181–3188. [Google Scholar] [CrossRef] [Scilit]
  25. Xu, Y.; Liu, C.-C.; Schneider, K.P.; Tuffner, F.K.; Ton, D.T. Microgrids for service restoration to critical load in a resilient distribution system. IEEE Trans. Smart Grid 2018, 9, 426–437. [Google Scholar] [CrossRef] [Scilit]
  26. Zhang, Z.; Ding, T.; Zhou, Q.; Sun, Y.; Qu, M.; Zeng, Z.; Ju, Y.; Li, L.; Wang, K.; Chi, F. A review of technologies and applications on versatile energy storage systems. Renew. Sustain. Energy Rev. 2021, 148, 111263. [Google Scholar] [CrossRef] [Scilit]
  27. Zeraati, M.; Golshan, M.E.H.; Guerrero, J.M. Voltage quality improvement in low voltage distribution networks using reactive power capability of single-phase PV inverters. IEEE Trans. Smart Grid 2019, 10, 5057–5065. [Google Scholar] [CrossRef] [Scilit]
  28. Xiao, C.; Sun, L.; Ding, M. Multiple spatiotemporal characteristics-based zonal voltage control for high penetrated PVs in active distribution networks. Energies 2020, 13, 249. [Google Scholar] [CrossRef] [Scilit]
  29. Wang, Y.; Chen, C.; Wang, J.; Baldick, R. Research on resilience of power systems under natural disasters—A review. IEEE Trans. Power Syst. 2016, 31, 1604–1613. [Google Scholar] [CrossRef] [Scilit]
  30. Li, P.; Zhang, C.; Wu, Z.; Xu, Y.; Hu, M.; Dong, Z. Distributed adaptive robust voltage/VAR control with network partition in active distribution networks. IEEE Trans. Smart Grid 2020, 11, 2245–2256. [Google Scholar] [CrossRef] [Scilit]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Article Metrics

Citations

Article Access Statistics

Article metric data becomes available approximately 24 hours after publication online.