Abstract
The single-stage three-phase isolated Y-rectifier (iYR) merges power-factor correction and galvanic isolation into two conventional B6 bridges. Its power is conventionally regulated by the phase-shift angle alone at a fixed switching frequency. At light load, the transformer current then forms high-peak pulses whose rms value is large relative to the transferred power, and the efficiency falls. This paper proposes a hybrid phase-shift and variable-frequency control that raises the switching frequency as the load falls, without altering the internal space-vector timings. At the lightest tested load, about 300 , the measured rms current falls by roughly 50 when the frequency is raised from 25 to 80 . The loss-optimal frequency is identified from hardware measurements rather than from simulation, and is stored as a two-dimensional look-up table indexed on the power reference and the dc output voltage. The strategy is validated on a 3 prototype over a 350 –450 dc-bus range and a 25 –80 frequency range. At 400 and 300 , the measured loss falls by , raising the efficiency from to . Two transformer designs differing only in the magnetizing inductance are compared, which sets the frequency range over which the strategy reduces the loss.