Abstract
With the high-proportion integration of renewable energy, integrated energy systems face greater demands regarding renewable energy utilisation, power balancing, and operational efficiency. By aggregating distributed generation, energy storage and load resources, integrated energy systems can provide effective support for multi-energy coordinated scheduling. This paper proposes a 24 h day-ahead multi-objective optimal scheduling framework for an integrated hydro–wind–photovoltaic–storage energy system based on multi-objective particle swarm optimisation (MOPSO). Firstly, this paper establishes mathematical models for wind power, photovoltaic (PV), hydropower, and energy storage units. Subsequently, it incorporates the outputs of hydropower, wind power, PV, and storage, along with the charging and discharging of energy storage and the process of purchasing electricity from and selling electricity to the main grid, into a unified optimisation model. The objectives are to maximise economic benefit and variable renewable energy utilisation while minimising the peak-to-valley difference in residual load. To address the conflicts between these multiple objectives, a MOPSO algorithm combined with a normalised weighted scoring method is employed to select a compromise optimal solution. Results from case studies based on typical days of the four seasons and various operational strategies demonstrate that the proposed method can rationally allocate the outputs of different energy sources, reduce the system’s dependence on the main grid, and improve variable renewable energy utilisation, thereby providing a reference for the optimal scheduling of integrated energy systems.
1. Introduction
As the global energy structure undergoes an accelerated transition towards low-carbon, clean, and intelligent energy, the development of a new power system centred on renewable energy has become a key priority in the energy sector [1]. However, the outputs of wind power and PV systems are significantly affected by meteorological conditions and exhibit pronounced intermittency, variability, and uncertainty. Their large-scale grid integration imposes higher demands on power balance and the safe, stable operation of the power system [2]. To enhance renewable energy utilisation and mitigate operational risks, aggregating and coordinating diverse resources, including hydropower, wind power, photovoltaics, and energy storage, into an integrated energy system has become a key development direction in the energy sector [1,2,3,4]. Within such systems, the output characteristics of different energy sources exhibit inherent temporal complementarity: hydropower offers flexible regulation and rapid response, enabling it to compensate to some extent for fluctuations in wind and PV output, while energy storage enables the transfer of energy across time periods, further mitigating fluctuations in residual load [3,4]. Recent work has further addressed PV hosting-capacity planning in hydro-dominant distribution grids through a bi-level framework that explicitly considers hydraulic safety constraints [5], highlighting the importance of coordinating renewable energy integration with hydropower operating limitations. Consequently, how to scientifically formulate day-ahead scheduling plans within the framework of combined hydro–wind–PV–storage operation so as to balance economic efficiency, environmental sustainability and operational stability is a core issue that urgently needs to be addressed in the optimisation and control of integrated energy systems.
Recent multi-objective scheduling studies have addressed hydro–wind–PV–storage systems from different perspectives. Scenario-based optimisation has been used to account for renewable uncertainty and extreme-weather conditions [6], while multi-objective deep reinforcement learning has been applied to coordinate complementary generation and residual-load regulation [7]. Multi-timescale dispatch frameworks have coupled medium- and long-term scheduling with short-term power balance [8], and flexibility-oriented approaches have further linked day-ahead scheduling with real-time operation under renewable uncertainty [9]. Although these studies have advanced coordinated renewable energy scheduling, their emphasis is mainly on uncertainty, operational risk, multi-timescale coordination, or adaptive control. Relatively limited attention has been paid to a compact day-ahead framework that explicitly evaluates the trade-offs between economic benefit, wind/PV utilisation, and residual-load smoothing while retaining an interpretable basis for compromise decision-making.
Accordingly, the methodological contribution of this study does not lie in proposing a new MOPSO search operator. Rather, it lies in integrating an operator-oriented three-objective scheduling formulation with problem-specific feasibility handling and a post-Pareto preference-based decision procedure within a unified hydro–wind–PV–storage day-ahead scheduling framework. In recent years, swarm intelligence optimisation algorithms have been widely applied in the field of energy system optimisation and scheduling due to their strong adaptability to complex non-linear problems. Among these, the particle swarm optimisation algorithm offers advantages such as a simple model, few parameters, and rapid convergence [10]. The multi-objective particle swarm optimisation algorithm developed on this basis is capable of searching for a set of Pareto-optimal solutions through an external archive and a non-dominance sorting mechanism, providing an effective solution approach for multi-objective scheduling problems [11]. However, multi-objective optimisation typically cannot directly yield a single optimal solution but rather generates a set of candidate solutions that represent trade-offs between different objectives. Without further comprehensive evaluation that incorporates system operational preferences, the selection of a scheduling scheme still lacks a clear basis. Therefore, it is necessary to introduce a trade-off solution selection method based on multi-objective optimisation so that the final scheme can better meet the diverse requirements of integrated energy system operators regarding economic efficiency, variable renewable energy utilisation, and operational stability.
To address the above research gap within the scope of day-ahead scheduling, this paper proposes a multi-objective optimisation framework for integrated hydro–wind–PV–storage energy systems based on MOPSO. The main contributions of this paper are as follows:
- A 24 h day-ahead scheduling model is formulated for the coordinated operation of hydropower, wind power, PV, energy storage, and grid exchange. The model jointly optimises economic benefit, wind and PV utilisation, and residual-load peak-to-valley difference, thereby capturing the trade-offs between economic performance, variable renewable energy utilisation, and operational stability.
- To handle the heterogeneous operational constraints of the hydro–wind–PV–storage scheduling problem, an aggregated infeasibility index is used to quantify violations of variable bounds, power balance, terminal energy, SOC limits, and mutually exclusive operating states. A feasibility-priority rule is then embedded in particle comparison, personal-best updating, and external-archive maintenance, providing a consistent feasibility-handling procedure within the Pareto search.
- Pareto search and operator-preference decision-making are separated into two stages. The three objectives are first optimised without scalarisation to obtain a feasible non-dominated solution set, after which a normalised weighted scoring procedure is applied to select a compromise solution according to operator preferences. This preserves the trade-off information contained in the Pareto front while providing an interpretable transition from multiple non-dominated alternatives to an implementable scheduling scheme.
- The framework is evaluated using typical-day data for all four seasons and different operational preference settings. The Pareto front and objective trade-offs are analysed, while repeated independent runs are conducted to assess the statistical robustness and computational performance of the optimisation results. In addition, comparisons with single-objective PSO baselines are performed to demonstrate the value of multi-objective coordination.
The remainder of this paper is structured as follows: Section 2 introduces mathematical models for hydro, wind, photovoltaic and energy storage systems and analyses the power output characteristics of each energy unit; Section 3 constructs a multi-objective optimal scheduling model, describing the multi-objective particle swarm algorithm and the method for selecting compromise solutions; Section 4 presents the case-study results, including the seasonal scheduling analysis, convergence and Pareto-front analysis, comparison with single-objective PSO baselines, evaluation under different operational strategies, and computational-efficiency analysis; finally, Section 5 summarises the research. The main symbols used throughout the paper are summarised in Table 1.
Table 1.
Definitions of the main symbols used in this study.
2. Theoretical Foundations of Distributed Energy Generation
An integrated energy system involves the comprehensive utilisation of distributed clean energy sources within a region, including wind power, photovoltaics, hydropower, and energy storage. To facilitate coordinated and optimal control of power generation units and energy storage devices, it is first necessary to investigate their respective power generation mechanisms and output characteristics. On this basis, mathematical models that reflect their operating principles are established, and corresponding simulation models are developed in MATLAB. Subsequently, using typical meteorological and hydrological data from south-western China, the validity and accuracy of the models are verified. The output characteristics of each generation unit under different scenarios are analysed, thereby providing power boundaries and an operational basis for subsequent research on scheduling and control strategies.
2.1. Wind Power
The actual output of a wind turbine is directly affected by fluctuations in wind speed and typically exhibits a distinct piecewise characteristic [12]. When the wind speed has not yet reached the conditions required for the turbine to commence power generation or has exceeded the maximum permissible wind speed for the turbine, the generator will cease operation to prevent damage to the equipment. When the wind speed is within the operational range but has not yet reached the rated wind speed, the generator’s output power will increase continuously as the wind speed rises, and the rate of power increase will also gradually accelerate. If the wind speed rises further above the rated wind speed, while still remaining within the generator’s safe operating range, the generator will maintain a constant power output. Given that, in the actual energy conversion process, wind energy must pass through both the mechanical transmission stage and the power generation stage; the effects of mechanical transmission efficiency, , and power generation efficiency, , must also be taken into account when calculating the output power of a wind power generation system [13]. Consequently, the mathematical expression for the output power of a wind power generation system can be written as
where represents the wind speed at any given time; , and represent the cut-in, cut-out and rated wind speeds respectively; represents the transmission efficiency of the mechanical drive train; represents the power generation efficiency of the wind turbine; represents the rated power; and represents the output power.
2.2. Photovoltaic Power Generation
Photovoltaic power generation primarily uses the photovoltaic effect at semiconductor interfaces to convert the light energy from sunlight directly into electrical energy. When sunlight strikes a semiconductor PN junction, a photo-generated current is produced within the material. By connecting multiple PN junctions in series, a significant output power can be supplied to an external circuit [14].
A photovoltaic power generation system primarily consists of a photovoltaic array, a controller, a DC-DC converter and a DC-AC inverter. Since the output voltage and power of a single photovoltaic cell are relatively low, they cannot directly meet the power supply requirements of practical applications. Therefore, in engineering practice, multiple photovoltaic cells are often connected in series and parallel in a specific configuration to form a photovoltaic array.
Building on this, to further describe the power generation capacity of a photovoltaic system, its output power can be expressed as follows [15]:
where is the output power of the photovoltaic system (W); is the conversion efficiency of the photovoltaic array; is the overall system efficiency, accounting for losses due to dust, temperature rise, module mismatch, inverter losses, and line transmission; is the irradiance received by the inclined surface of the photovoltaic array (W/m2); and is the total area of the photovoltaic array (m2).
2.3. Hydropower
Hydropower is also a relatively mature clean energy technology that harnesses the potential energy difference between natural water bodies to generate electricity. The process can be described as follows: a head (water-level difference) is created, typically by constructing a dam, to convey water with higher potential energy from upstream to downstream. As the water flows at high speed, it strikes the turbine blades, causing them to rotate and thereby converting hydropower (the sum of potential and kinetic energy of the water) into mechanical energy, which is then converted into electrical energy by a generator [16].
Hydroelectric generating units are typical non-linear dynamic systems characterised by the coupling of hydraulic, mechanical, and electrical components. The development of an accurate mathematical model forms the basis for dynamic simulation and the study of control strategies. However, while the simultaneous equations method provides a relatively accurate representation of the operational characteristics of a hydro-generator unit over its entire operating range, it is computationally complex. Therefore, while ensuring that the required engineering accuracy is met, this paper employs a simplified model of the hydro-generator unit to simulate and analyse its power output characteristics.
The volume of water passing through a turbine per unit time is defined as the flow rate, denoted by , and is calculated as follows [17]:
where is the average flow velocity across the cross-section (m/s) and is the cross-sectional area (m2).
Head refers to the difference in water level between the upstream and downstream sides of a hydropower station, measured in metres. It can be further divided into gross head and net head. Gross head is the water-level difference specified in the power station’s design; net head, on the other hand, is the difference between the turbine inlet and the downstream tailwater level. Net head can be calculated using the following formula:
where is the head occupied by the generating unit structure and the tailrace arrangement (m) and is the head loss caused by the flow through the pressure water conveyance system (m).
The power of a hydraulic turbine is divided into input power and output power. Input power, , is the power transferred from the water to the turbine, expressed as
The output power, , is the power delivered at the turbine shaft and can be obtained by multiplying the input power by the efficiency:
where is the energy conversion efficiency of the turbine, i.e., the ratio of output power to input power. Its value is usually determined by the head conditions and generally ranges from 0.8 to 0.95.
Taking all the above factors into account, the power output of a hydroelectric generator set can ultimately be expressed as
where is the efficiency of the generator set, generally taken to be between 0.90 and 0.98.
2.4. Energy Storage System
In integrated energy systems, energy storage systems differ from conventional distributed energy resources in that they shift electrical energy across time through charging and discharging. When the output of hydropower, wind power, and PV is high and surplus electricity is available, energy storage devices can absorb and store part of the excess energy; when renewable energy output decreases or load demand reaches its peak, the stored energy is released to compensate for the supply–demand imbalance. This approach not only mitigates the impact of renewable energy fluctuations and reduces wind and PV curtailment, but it also enables more flexible complementary regulation in coordination with hydropower. Furthermore, energy storage systems offer rapid response, which helps to smooth the power injected into the grid, improve power quality, and enhance the controllability and operational stability of the integrated energy system while satisfying the relevant operational constraints. Recent field-based analysis of a grid-connected PV-battery system further shows that daily operating regimes are closely associated with meteorological conditions, load demand, battery charging/discharging behaviour, and grid exchange, highlighting the importance of coordinated energy management under varying operating conditions [18].
In integrated energy systems, batteries are currently one of the most widely used types of energy storage devices, and their energy storage level is generally expressed by the state of charge (SOC). SOC reflects the proportion of the battery’s remaining charge relative to its rated capacity at a given moment, ranging from 0 to 100%. When SOC = 0, the battery is fully discharged, while when SOC = 100%, the battery is fully charged. During actual operation, to minimise the impact of overcharging and over-discharging on battery life and operational safety, it is usually necessary to set reasonable upper and lower limits for SOC, ensuring that the energy storage system always operates within the permissible range. Effective SOC management is also important for coordinating battery charging and discharging and maintaining stable operation of battery energy storage systems [19]. Furthermore, the charging and discharging power of the battery must not exceed its specified limits; otherwise, this will accelerate performance degradation and consequently shorten its service life [17].
Let denote the remaining capacity of the battery at time and denote the rated capacity of the battery. The state of charge can then be expressed as follows [12]:
where is the battery discharge current (A); both and are in kilowatt-hours (kWh). This equation shows that as the battery continues to discharge, its remaining capacity steadily decreases and the SOC consequently declines.
To better describe the battery’s dynamic characteristics, it is also necessary to establish separate SOC recursive models for charging and discharging.
During discharge ( > 0), the SOC is updated as follows:
During charging ( < 0), the SOC is updated as follows:
where is the self-discharge rate, is the charge/discharge efficiency, and is the charge/discharge power of the energy storage system at time .
3. Multi-Objective Optimal Scheduling Model and Algorithm Design for Integrated Energy Systems
Integrated energy systems integrate multiple energy resources, including hydropower, wind power, PV, and energy storage. However, in actual scheduling operations, the output characteristics of different power sources are not the same. The primary challenge in multi-energy coordinated scheduling is how to satisfy the system’s energy demand while simultaneously balancing operational economic benefits, renewable energy utilisation, and the stability of the residual load. Therefore, this section establishes a multi-objective optimal scheduling model for hydro–wind–PV–storage systems, with objectives of maximising economic benefits, maximising the variable renewable energy utilisation rate, and minimising the peak-to-valley difference in the residual load. The model is solved using a multi-objective particle swarm optimisation (MOPSO) algorithm, providing a modelling foundation and algorithmic support for subsequent case studies.
3.1. Multi-Objective Particle Swarm Optimisation Algorithm
The particle swarm optimisation (PSO) algorithm is a typical swarm intelligence-based global optimisation method [10]. The core principle of PSO is to combine the personal best position of each particle with the global best position of the swarm. Specifically, the velocity of particle at the next time step is determined not by a single factor, but jointly by its current velocity, ; its personal best position, ; and the global best position, , currently found by the entire population. Subsequently, the particle moves from its current position, , to a new position, xi+1, based on the updated velocity. Guided by the global leader, the swarm is iteratively updated and gradually converges towards promising regions of the search space, ultimately approaching the global optimum in the decision space. Owing to its simple structure, small number of adjustable parameters, ease of implementation, and fast convergence, PSO has been widely applied in fields such as continuous function optimisation, neural network training, and engineering parameter identification.
At each iteration, the particle updates its velocity and position by tracking its local optimum, , and the global optimum, [20]:
where denotes the iteration number, denotes the velocity of particle at the kth iteration, and are learning factors, is the inertial weight, and and are random numbers in the interval [0, 1].
However, optimisation problems in practical engineering often involve multiple conflicting objective functions, and single-objective PSO algorithms struggle to handle such complex scenarios directly. To address this shortcoming, Coello et al. proposed the multi-objective particle swarm optimisation (MOPSO) algorithm [11]. While retaining the swarm update mechanism of PSO, MOPSO introduces three main improvements: firstly, it employs non-dominance sorting to evaluate particles hierarchically, storing non-dominated solutions in an external archive; secondly, it updates the individual optima of particles based on the Pareto dominance criterion, while prioritising the selection of global leaders from the sparse grid of the external archive; thirdly, it maintains the archive size using an adaptive grid or crowding distance, thereby ensuring solution set diversity. Upon termination, the solution set stored in the archive constitutes a set of non-dominated solutions approximating the Pareto front, from which decision-makers can make their final selection based on their actual preferences.
Several established algorithms have been widely used for multi-objective optimisation, including NSGA-II, MOEA/D, and MOPSO. These methods differ in their search mechanisms, diversity-preservation strategies, and implementation characteristics, as summarised in Table 2.
Table 2.
Comparison of representative multi-objective optimisation algorithms.
MOPSO is selected as the optimisation algorithm in this study because, compared with NSGA-II and MOEA/D, it offers a simpler search structure and better handles continuous variables. For the scheduling problem considered in this study, it can also be conveniently integrated with the proposed constraint-handling mechanism and external Pareto archive.
This paper employs the MOPSO algorithm based on an external archive and a grid selection mechanism to solve a 24-period optimal scheduling model for the integrated energy system. Given that the multiple optimisation objectives involve trade-offs rather than a simple preferential relationship, the model incorporates economic benefits, variable renewable energy utilisation, and the residual-load peak-to-valley difference into a Pareto optimisation framework for joint treatment. Simultaneously, the portions of certain constraints that exceed their limits are aggregated into an infeasibility index, . This paper calculates both the objective vector and the infeasibility index, , when evaluating particles. This approach retains the MOPSO algorithm’s ability to search the Pareto front, while also enhancing its stability under complex constraints and improving the interpretability of the results.
The infeasibility index, , is introduced only for constraint handling and is not included as an additional optimisation objective. It is defined as
where and denote the violation degrees of the variable bounds, power-balance constraint, terminal energy constraint, SOC limits, and mutual-exclusivity constraints, respectively. For each constraint, only the residual exceeding the corresponding feasibility tolerance is counted as a violation, and these residual violations are aggregated to obtain . Thus, represents a feasible solution, whereas represents an infeasible solution, with a smaller c indicating a smaller overall degree of constraint violation.
A feasibility-priority rule is adopted for particle comparison: feasible solutions dominate infeasible solutions; two feasible solutions are compared according to Pareto dominance, whereas two infeasible solutions are compared according to their infeasibility indices. The same rule is applied to personal-best updating and external-archive maintenance.
The implementation procedure of the proposed MOPSO-based day-ahead optimal scheduling method is illustrated in Figure 1. The overall procedure includes scenario and parameter initialisation, particle swarm and external archive initialisation, fitness evaluation, leader selection, particle updating, archive updating, and compromise solution selection.
Figure 1.
Flowchart of the proposed MOPSO-based day-ahead optimal scheduling method.
3.2. Objective Functions
- (1)
- Maximisation of economic benefit
The net benefit of the integrated energy system is calculated as revenue minus costs. Revenue primarily comprises income from selling electricity to end-users and income from selling electricity to the main grid, while costs consist of the system’s internal operation and management costs, the cost of purchasing electricity from the main grid, and penalties for wind and PV curtailment, as shown in the following formula:
where is the objective function for economic benefits, is the revenue from selling electricity to users during period , is the revenue from selling electricity to the main grid during period , is the internal operation and management cost during period , is the cost of purchasing electricity from the main grid during period , is the penalty cost for wind and PV curtailment during period , and is the total number of time periods.
(1) The revenue from electricity sales to internal users, , is calculated as
where is the electricity selling price to users during period and is the load demand during period .
(2) The revenue from selling electricity to the main grid, , is calculated as
where is the electricity price for selling to the main grid during period and is the amount of electricity sold to the main grid during period .
(3) Operation and management costs.
Including the management costs of hydro, wind, and PV units, as well as energy storage batteries, during time period , the expression is as follows [21]:
where , and are the outputs of hydro, wind, and PV units during period , respectively; and are the charging and discharging rates of the energy storage battery during period , respectively; and , , and are the operation and management coefficients for hydro, wind, PV, and storage, respectively.
It should be noted that the present study considers a 24 h day-ahead scheduling horizon, and the long-term capacity degradation of the energy storage system is therefore not explicitly modelled. The operation and management cost of the energy storage system in Equation (17) is associated with its charging and discharging power, meaning that energy storage cycling is not treated as completely cost-free.
(4) The cost of purchasing electricity from the main grid is
where is the electricity purchase price from the main grid during period and is the amount of electricity purchased from the main grid during period .
(5) Penalty cost for wind and PV curtailment.
During the operation of the integrated energy system, it is sometimes necessary to curtail wind and PV output to maintain system power balance [22]. To reflect the economic losses resulting from such curtailment, this paper introduces a curtailment penalty cost. The penalty cost for period can be expressed as
where is the unit penalty cost for curtailed wind and PV power and is the amount of wind and PV curtailment during period .
- (2)
- Maximisation of the variable renewable energy utilisation rate
When large-scale renewable energy is connected to the grid, it imposes significant stress on the grid, leading to wind and PV curtailment. To maximise local utilisation of wind and PV power, this paper takes the maximum variable renewable energy utilisation rate as an objective, which helps reduce curtailment. The calculation formula is as follows:
where is the objective function for variable renewable energy utilisation, is the maximum permissible output of wind farm at time , is the maximum permissible output of PV station at time , and is the time interval.
It should be noted that the utilisation-rate objective defined above specifically refers to wind and PV generation rather than all renewable energy resources in the system. Hydropower is treated as a dispatchable and flexible regulating resource in the proposed scheduling framework. Its output is coordinated with wind and PV generation to compensate for their fluctuations and maintain system power balance; therefore, hydropower is not included in the wind and PV utilisation-rate calculation.
- (3)
- Minimisation of the peak-to-valley difference in residual load
An objective function is defined to minimise the peak-to-valley difference in the residual load, thereby mitigating the impact of large load fluctuations on the safe and stable operation of the integrated energy system and the grid. The calculation formula is as follows:
where is the objective function for the peak-to-valley difference in the residual load and is the residual load at time .
3.3. Constraints
- (1)
- System power balance constraintwhere is the output of hydroelectric station at time ; is the output of wind farm at time ; is the output of PV station at time ; and are the charging and discharging power of the energy storage system at time , respectively; is the number of hydroelectric stations; is the number of wind farms; and is the number of PV stations.
- (2)
- Upper and lower output limits of power units
(1) Hydroelectric power output limits:
where and are the minimum and maximum outputs of hydroelectric station at time , respectively.
(2) Wind power output limits:
where and are the minimum and maximum outputs of wind farm at time , respectively.
(3) PV power output limits:
where and are the minimum and maximum outputs of PV station at time , respectively.
- (3)
- Energy storage constraints:
Energy storage devices cannot charge and discharge simultaneously within the same time period. Therefore, this paper introduces a Boolean variable, ∊{0, 1}, to represent the operating state of the energy storage system at time : = 1 indicates charging, and = 0 indicates discharging. Based on this state variable, the charging and discharging power constraints are formulated as follows [23]:
Similarly, the dynamic constraint on the energy (state of charge) of the energy storage system can be expressed as
where and are the maximum charging and discharging power of the energy storage system, respectively; is the energy (state of charge) of the energy storage system at time and is the maximum capacity; and are the charging and discharging coefficients, respectively; and and are the energy of the energy storage system at the beginning and end of the scheduling period, respectively.
- (4)
- Power exchange constraints between the integrated energy system and the main grid:
To prevent the integrated energy system from purchasing and selling electricity to the main grid simultaneously within the same time period, a Boolean variable, ∊{0, 1}, is introduced to represent the power exchange state: = 1 indicates purchasing electricity from the main grid, and = 0 indicates selling electricity to the main grid. Based on this state variable, the power exchange constraints are formulated as follows:
where and are the upper limits of the power purchased from and sold to the main grid, respectively.
3.4. Multi-Objective Compromise Solution Selection Method
After establishing the objective functions and constraints, this paper solves the model using the multi-objective particle swarm optimisation algorithm described in Section 3.1, ultimately obtaining a set of Pareto-non-dominated solutions that satisfy the constraints. It should be noted that the result of multi-objective optimisation is typically not a single fixed solution but a set of multiple alternative solutions; consequently, it is difficult to directly determine a unique optimal scheduling scheme. At the same time, during actual operation, operators often place varying degrees of importance on the three objectives (economic benefit, variable renewable energy utilisation rate, and residual-load peak-to-valley difference), and these preference differences further influence the selection of the final scheduling scheme.
Furthermore, the three objective values (economic benefit, variable renewable energy utilisation rate, and residual-load peak-to-valley difference) for each candidate solution on the Pareto front have different units and orders of magnitude. If a weighted evaluation is performed directly on the original objective values of the Pareto feasible solutions, a particular objective may dominate unreasonably due to its larger numerical magnitude, thereby compromising the objectivity of the results. Therefore, it remains difficult to determine a unique and reasonable final scheduling scheme based solely on the Pareto solution set. To address this, this paper employs a normalised weighted scoring method to comprehensively evaluate each candidate solution in the Pareto non-dominated solution set and thereby selects the optimal compromise scheduling solution.
To facilitate a unified solution of the model using a multi-objective algorithm, the three objectives defined in Section 3.2 are first converted into minimisation forms. Specifically, the economic benefit objective is taken as its negative, the variable renewable energy utilisation rate objective is converted to (1 − ), and the residual-load peak-to-valley difference objective is kept in its original form. Following the above treatment, the objective vector corresponding to the -th feasible solution in the Pareto feasible solution set, , can be expressed as
At this stage, the three objective values , and can be uniformly evaluated according to the principle that ‘the smaller the value, the better the solution’. This avoids the problem of inconsistent evaluation criteria among different objectives and provides a uniform basis for the subsequent normalisation of the Pareto set and the selection of a compromise solution.
Subsequently, the objectives in are normalised to ensure that different objectives are comparable in the comprehensive evaluation [24]. For the -th objective, the normalisation is defined as
where is the set of Pareto feasible solutions and and are the maximum and minimum values of the -th objective in , respectively. After normalisation, ∊ [0, 1], and a larger value indicates better performance of the solution on that objective.
To reflect different scheduling preferences, we define the original weight vector, , and normalise it to obtain standardised weights that satisfy :
On this basis, we construct the comprehensive evaluation function for the -th feasible solution:
Finally, the Pareto feasible solution with the highest overall score is selected as the optimal compromise solution:
where is the final selected scheduling scheme.
This method, while preserving the multi-objective trade-off relationships of the Pareto front, integrates economic benefit, variable renewable energy utilisation rate, and residual-load peak-to-valley difference into a unified evaluation framework. At the same time, it uses weighting to reflect different operational preferences, thereby providing a clear basis for decision-making on day-ahead scheduling schemes for the integrated energy system.
4. Case Validation and Analysis
4.1. Parameter Settings
All simulations were performed using MATLAB R2022a on a laptop computer equipped with a 12th Gen Intel® Core™ i7-12700H processor and 16 GB RAM under the Windows 11 operating system. The main parameters of the MOPSO algorithm used in the case studies, including the population size, maximum number of iterations, learning factors, inertia weight, and dimension of the decision-variable vector, are summarised in Table 3.
Table 3.
Parameter settings of the MOPSO algorithm.
The MOPSO parameters listed in Table 3 were selected by considering the computational scale of the 96-dimensional day-ahead scheduling problem and the balance between Pareto-search diversity and computational burden. This study focuses on the proposed scheduling framework rather than exhaustive MOPSO hyperparameter tuning. The population size of 150 was used to maintain solution diversity, while the maximum iteration number of 200 was adopted because the convergence curves indicate that the objective values gradually stabilise within the prescribed iteration range. The inertia weight of 0.5 and the learning coefficients = 1.5 and = 2.0 were used to balance exploration, individual learning, and archive-leader guidance. The same settings were applied to all seasonal cases and comparative tests.
When optimising the scheduling of integrated energy systems, it is necessary first to define the cost parameters of each component unit, as well as the electricity purchase and sale prices, so that subsequent cost and revenue calculations have a consistent basis. Based on relevant engineering cases and existing research, this paper sets the operation and management costs for the main units as shown in Table 4 [21,25]. For PV and wind power systems, in addition to operation and management costs, curtailment penalty costs for PV and wind power are also specified [25,26].
Table 4.
Economic parameters of the main units.
On the demand side, to reflect the cost-effectiveness of different types of electricity consumption in the optimal scheduling, this paper sets corresponding settlement prices based on the standard tariff schedules for general industrial, commercial, and residential consumers. The residential electricity tariff is set at 0.5464 CNY/kWh, while general industrial and commercial loads (covering lighting, HVAC, etc.) are subject to the peak, flat, and valley time-of-use tariffs shown in Table 5.
Table 5.
Peak–flat–valley time-of-use electricity tariffs of the integrated energy system.
The power exchange between the integrated energy system and the main grid is likewise subject to a time-of-use tariff. The peak, flat, and valley periods for the exchange tariff are aligned with those defined in the TOU pricing mechanism for internal loads, with the corresponding parameters presented in Table 6.
Table 6.
Time-of-use electricity prices for power exchange between the integrated energy system and the main grid.
4.2. Seasonal Scheduling Results Under Equal Objective Weights
To analyse the scheduling performance of the integrated energy system under different seasonal conditions, this section first compares the optimisation results for typical days in spring, summer, autumn, and winter under equal weights (i.e., a ratio of 1:1:1) for the three objectives: economic benefit, variable renewable energy utilisation rate, and peak-to-valley difference in residual load.
Figure 2 illustrates the power output distribution of the combined system for typical days in spring, summer, autumn, and winter over a 24 h scheduling horizon. Overall, the system meets load demands at different times of the day through the coordination of hydropower, wind power, PV, energy storage, and electricity purchased from and sold to the main grid. As can be seen from the changes in the load curve, electricity consumption rises significantly during the day, generally remaining at a high level from the afternoon into the evening, before falling back somewhat at night.
Figure 2.
Combined system output for a typical day in each season.
Looking further at the output characteristics of different energy sources, hydropower output is significantly affected by seasonal variations, with hydropower bearing the primary responsibility for power supply, especially in summer and autumn. The high hydropower output levels in summer and autumn indicate abundant inflow during the wet season, enabling hydropower to provide relatively stable base-load support. Moreover, after meeting its own load demand, the system still has surplus electricity that can be sold to the main grid for revenue, reflecting its ability to export excess power during the wet season. In contrast, during the spring and winter dry seasons, hydropower output drops significantly. The system essentially ceases selling electricity to the main grid, and its reliance on purchasing electricity from the main grid increases substantially to meet load demand at all times.
In terms of output patterns, PV output is mainly concentrated during the day, typically peaking around midday, while there is virtually no output at night. Wind power output, by contrast, is more dispersed and can provide some supplementary power during certain evening and night periods. However, due to its high variability, wind power alone cannot ensure a stable power supply.
The energy storage system plays a role in peak shaving, valley filling, and smoothing power fluctuations across all four seasons. When renewable energy output is high or demand is low, it absorbs surplus electricity; when demand increases or renewable energy output is insufficient, it releases electricity to compensate for the power shortage.
A comprehensive comparison across the four seasons shows that in summer and autumn the integrated energy system has a strong renewable energy supply capacity, requiring minimal electricity purchase from the main grid and having a significant surplus for sale. In contrast, in spring and winter, due to reduced hydropower and photovoltaic output, the system’s reliance on purchasing electricity from the main grid increases markedly. Thus, optimal scheduling of the integrated energy system helps leverage the complementary advantages of multiple energy sources, meet load demand across seasons, and improve variable renewable energy utilisation while reducing dependence on the main grid, thereby providing a solid foundation for economic and stable operation. These scheduling characteristics are similar to field observations of a grid-connected PV-battery system, where surplus daytime PV generation was stored and shifted to evening demand periods, thereby supporting greater on-site PV utilisation and reducing reliance on grid imports, while also providing measurable economic benefits under actual operating conditions [27].
Figure 3 illustrates the typical daily output patterns of hydropower, wind power, and PV across the four seasons. Overall, these three types of generation exhibit a certain degree of complementarity across different seasons and time periods.
Figure 3.
Typical daily power output curves of hydropower, wind power, and PV across the four seasons.
As shown in Figure 3, the outputs of hydropower, wind power, and PV exhibit pronounced complementary regulation characteristics in spring and winter. In spring, when PV output is high at midday, hydropower output decreases relatively; conversely, when PV output decreases in the evening and wind output increases, hydropower output also decreases. In winter, when PV output is high at midday, hydropower output decreases slightly, whereas when both wind and PV outputs are low in the evening, hydropower output increases. This indicates that hydropower compensates for fluctuations in wind and PV output to some extent. The optimisation model in this section adopts equal weights for the three objectives: maximising economic benefit, maximising variable renewable energy utilisation, and minimising the peak-to-valley difference in residual load. Therefore, the scheduling results seek to improve the utilisation of wind and PV resources while mitigating residual-load fluctuations. Consequently, the complementary relationship between hydropower, wind power, and PV outputs becomes more pronounced in spring and winter, when the available power from wind and PV is relatively limited.
By contrast, during the wet seasons (summer and autumn), hydropower output is generally high, the system’s renewable energy supply capacity is strong, and reliance on electricity purchased from the main grid is low. When hydropower and PV output are sufficient, the system can absorb surplus electricity by charging energy storage or selling it to the grid; thus, hydropower does not need to adjust its output directly in response to wind and PV output fluctuations. As a result, the complementarity between hydropower, wind power, and PV is less evident in the figure.
Overall, Figure 3 shows that the performance of the hydro–wind–PV complementary system varies across seasons. In spring and winter, hydropower primarily compensates for wind and PV output fluctuations; in summer and autumn, due to the relative abundance of hydropower resources, system regulation is characterised more by the coordinated operation of hydropower, wind power, PV, and energy storage, together with power exchange with the main grid.
Considering the stochastic characteristics of MOPSO, the optimisation process for each seasonal case under equal objective weights was independently repeated 30 times. The means and 95% confidence intervals of the three objective indicators were calculated to evaluate the robustness of the optimisation results across independent runs, and the results are reported in Table 7. The results show that although stochastic variations exist among independent runs, the main seasonal conclusions remain consistent. Specifically, the economic benefits in summer and autumn are considerably higher than those in spring and winter, which is consistent with the stronger hydropower supply capacity during the wet seasons. The variable renewable energy utilisation rate remains within a relatively concentrated range across the four seasons, while the residual-load peak-to-valley difference is highest in summer. These results indicate that the seasonal analysis is not dependent on a single optimisation run.
Table 7.
Statistical results of the equal-weight MOPSO-based scheduling results for four typical seasonal days.
4.3. Convergence and Pareto-Front Analysis
Since the optimisation processes for typical days across the four seasons are similar, to avoid repetition, this paper uses one independent spring optimisation run to illustrate the iterative convergence process and the corresponding Pareto front.
Figure 4 shows the convergence process. The fitness values on the vertical axis have been uniformly converted according to Equation (34); after this conversion, all three objective values follow the criterion that smaller values indicate better solutions. In the figure, solid lines represent the optimal value of each objective in each generation, while dashed lines represent the contemporary compromise optimal solution selected with equal weights. As can be seen from Figure 4, each objective value decreases rapidly in the early iterations, indicating that the algorithm quickly locates the optimal solution region. As iterations proceed, the curves gradually stabilise, demonstrating good convergence. However, among the three objectives, when one reaches its optimum, the others may not be simultaneously optimal; therefore, the compromise solution (dashed line) differs from the single-objective optimum. Under equal weights, the MOPSO algorithm does not pursue any single objective in isolation but achieves a coordinated balance between economic benefit, variable renewable energy utilisation rate, and residual-load peak-to-valley difference. As iterations continue, both the single-objective optimal values and the compromise solution gradually stabilise, showing that the algorithm can obtain a scheduling scheme with good overall performance while ensuring convergence.
Figure 4.
MOPSO convergence results for a typical spring day. (Solid line: current optimal value for this objective; dashed line: current compromise solution selected based on weights.)
Figure 5 shows the Pareto front obtained by MOPSO and the pairwise relationships between the three objectives. The non-dominated solutions are distributed over a relatively broad region of the objective space, providing multiple feasible scheduling alternatives with different trade-offs between economic benefit, variable renewable energy utilisation, and residual-load smoothing.
Figure 5.
Three-objective Pareto front and pairwise objective trade-offs.
As shown in Figure 5b–d, different degrees of synergy and trade-off can be observed between the three objectives. Figure 5b shows an overall positive relationship between economic benefit and variable renewable energy utilisation rate, indicating that these two objectives exhibit a certain degree of synergy within the obtained Pareto solution set. In other words, improving variable renewable energy utilisation does not necessarily require a reduction in economic benefit over the entire solution space. By contrast, Figure 5c shows that a higher economic benefit is generally accompanied by a larger residual-load peak-to-valley difference. Therefore, achieving higher economic benefits generally comes at the expense of residual-load smoothing, indicating a trade-off between these two objectives. A similar, and more pronounced, trade-off can be observed in Figure 5d: as the variable renewable energy utilisation rate increases, the residual-load peak-to-valley difference generally increases. This is mainly because accommodating a larger proportion of variable wind and PV generation introduces greater fluctuations into the residual load, while the regulating capability of hydropower and energy storage is constrained by their operating limits.
According to the normalised weighted scoring method, the solution highlighted by the orange marker is selected as the final compromise solution. It yields an economic benefit of 8862.03 CNY, a variable renewable energy utilisation rate of approximately 66.30%, and a residual-load peak-to-valley difference of 957.61 kW. Compared with other Pareto-optimal candidates, this solution does not pursue the extreme value of any single objective; instead, it provides a balanced compromise between economic performance, variable renewable energy utilisation, and residual-load smoothing under the adopted preference setting.
4.4. Comparison with Single-Objective PSO Baselines
To further evaluate the multi-objective coordination capability of the proposed framework, three single-objective PSO baselines were constructed for comparison. For each seasonal case and each optimisation method, 30 independent runs were conducted under the same decision variables, constraints, seasonal input data, population size, maximum number of iterations, and feasibility-priority constraint-handling rule. The three single-objective baselines optimise economic benefit, variable renewable energy utilisation, and the residual-load peak-to-valley difference separately. The MOPSO result in this comparison corresponds to the compromise solution selected from the Pareto set under equal weights for the three objectives. The results are reported in Table 8.
Table 8.
Comparison between the equal-weight MOPSO solution and single-objective PSO baselines for typical seasonal days.
As shown in Table 8, each single-objective PSO baseline achieves the best value for its corresponding optimisation target, but this is accompanied by degradation in the other indicators. The economic-oriented PSO obtains the highest total benefit of the integrated energy system, but it leads to relatively low variable renewable energy utilisation and a large residual-load peak-to-valley difference. The renewable-oriented PSO substantially improves wind and PV utilisation, but it also causes the largest residual-load fluctuation in all four seasons. The peak–valley-oriented PSO achieves the lowest residual-load peak-to-valley difference, but this comes at the expense of economic benefit and variable renewable energy utilisation. By contrast, the MOPSO solution avoids these extreme scheduling tendencies and provides a more balanced compromise between economic performance, variable renewable energy utilisation, and residual-load fluctuation mitigation.
4.5. Scheduling Results Under Different Operational Strategies
The above comparison demonstrates the need to balance the three conflicting objectives rather than optimising any single objective in isolation. On this basis, the effects of different operational preferences on the compromise scheduling solution are further investigated.
To analyse the impact of different objective preferences on the optimisation results of the integrated energy system, three operational strategies are established for comparative analysis. The objective weights for the three strategies are shown in Table 9. Strategy 1 prioritises economic benefit, aiming to maximise the total economic benefit of the integrated energy system; Strategy 2 prioritises variable renewable energy utilisation, aiming to maximise the variable renewable energy utilisation rate; Strategy 3 prioritises operational stability, aiming to minimise the peak-to-valley difference in residual load.
Table 9.
Weight settings for the three operational strategies.
Using the MOPSO algorithm and the normalised weighted scoring method, optimal scheduling schemes for different seasons and operational strategies are obtained. Figure 6 presents a comparison of the optimisation results for the three strategies across the four typical days (spring, summer, autumn, and winter).
Figure 6.
Comparison of scheduling results for the three operational strategies on a typical day across different seasons.
As can be seen from Figure 6, all three strategies yield optimisation results consistent with their weight preferences: Strategy 1 achieves the highest total economic benefit in every season, indicating that when the weight for economic benefit is increased, the model prioritises scheduling schemes that are more favourable for improving the total economic benefit; Strategy 2 achieves the highest variable renewable energy utilisation rate across all seasons, indicating that increasing the weight for variable renewable energy utilisation effectively guides the system to improve wind and PV utilisation; Strategy 3 achieves the smallest residual-load peak-to-valley difference in every season, suggesting that this strategy is more effective at mitigating residual-load fluctuations and improving system operational stability. Meanwhile, Strategy 2 results in the largest peak-to-valley difference in residual load across all seasons, and its difference from Strategy 3 is particularly significant. These results reveal a pronounced conflict between the objectives of maximising variable renewable energy utilisation and minimising the residual-load peak-to-valley difference.
Overall, different weight configurations can steer the scheduling results consistently towards the corresponding target preferences, indicating that the model and solution method perform well in multi-objective coordination. Furthermore, the variation patterns induced by different scheduling strategies remain largely consistent across the four seasons, further demonstrating that this method is well-suited to various scenarios. In practical applications, operators of integrated energy systems can flexibly adjust the objective weights according to specific requirements regarding economic benefit, variable renewable energy utilisation, and operational stability, thereby obtaining a scheduling plan that better aligns with their operational needs.
4.6. Computational Efficiency and Scalability Analysis
To evaluate the computational efficiency of the proposed scheduling framework, the MOPSO optimisation was independently executed 30 times for each of the four typical-day cases under identical algorithm settings and equal objective weights, resulting in a total of 120 independent runs. The computation time was measured for each optimisation run. The overall mean computation time was 46.30 s, with a standard deviation of 1.85 s. In addition, the mean computation times of the four seasonal cases ranged from 44.61 to 47.49 s, indicating that variations in seasonal input data have only a limited influence on the computational burden when the system configuration, problem dimension, and algorithm settings remain unchanged.
With a 96-dimensional decision-variable vector, a population size of 150, and a maximum of 200 iterations, the average computation time of 46.30 s on a laptop indicates that the proposed method demonstrates adequate computational efficiency for day-ahead scheduling applications without relying on dedicated high-performance computing resources. Furthermore, updating renewable energy forecasts, load profiles, and other day-ahead input data is not expected to substantially increase the computational burden as long as the system configuration and problem dimension remain unchanged.
For larger-scale integrated energy systems, the computational burden is expected to increase with the number of generation units, storage devices, scheduling periods, and associated decision variables. In such cases, computational efficiency could be further improved through parallel particle evaluation, adaptive stopping criteria, or decomposition strategies. These extensions will be investigated in future work to support larger-scale and rolling scheduling applications.
5. Conclusions
This study proposes a day-ahead optimal scheduling method based on a multi-objective particle swarm optimisation algorithm for energy systems comprising hydropower, wind power, photovoltaic power, and energy storage. By constructing a multi-objective scheduling model centred on maximising economic benefit, maximising the variable renewable energy utilisation rate, and minimising the peak-to-valley difference in residual load, the proposed method achieves coordinated optimisation of different energy units while satisfying constraints including power balance, unit output limits, state of charge of energy storage, and power exchange with the main grid. Simulation analyses demonstrate that the model can rationally allocate output schedules among energy sources according to the target weights set by the operator, thereby enabling coordinated utilisation of renewable energy resources while reducing dependence on electricity purchased from the main grid.
In the investigated typical-day cases, the convergence results show that the MOPSO algorithm reaches a stable solution within the prescribed iteration limit. Repeated independent runs further show that the main seasonal conclusions remain consistent despite the stochastic nature of MOPSO. The Pareto-based multi-objective framework provides a set of non-dominated candidate solutions representing different trade-offs between economic benefit, variable renewable energy utilisation, and residual-load smoothing. Combined with the normalised weighted scoring method, a compromise solution can be selected according to specific operational preferences. Comparison with the single-objective PSO baselines further shows that optimising an individual objective in isolation leads to deterioration in the other performance indicators, whereas the MOPSO-based framework provides a more balanced compromise between the three objectives. The seasonal case studies indicate that during the summer and autumn wet seasons, the system has greater renewable energy supply capacity and surplus electricity export potential, whereas greater electricity purchases from the main grid are required during the spring and winter dry seasons. The comparison of three preference strategies further shows that the optimisation results respond consistently to changes in objective weights across the four seasonal cases. The repeated computational tests yielded an average runtime of 46.30 s for the 96-dimensional day-ahead scheduling problem, indicating adequate computational efficiency for the investigated day-ahead cases.
This study has several limitations. The current scheduling model is based on deterministic day-ahead data and does not yet account for forecasting errors and uncertainties regarding wind speed, irradiance, inflow conditions, and load demand. The case validation is primarily based on historical data from typical days; the model’s robustness under real-time rolling optimisation or in stochastic scenarios requires further testing. Furthermore, factors such as the response time of hydroelectric units, energy storage lifespan degradation, and power ramping constraints have been simplified in the current analysis, and a more detailed dynamic model has not yet been established. In addition, the MOPSO-based solution method has inherent computational limitations. As a stochastic population-based metaheuristic, its computational cost is affected by the population size, number of iterations, and algorithm parameter settings. As the system scale, scheduling period, and decision-variable dimension increase, repeated objective-function and constraint evaluations, together with external-archive and grid-management operations, increase the computational burden. Although adequate computational efficiency has been demonstrated for the current day-ahead scheduling cases, the computational scalability of the proposed method for substantially larger systems and real-time rolling scheduling remains to be further validated.
Future work will extend the proposed framework to multi-timescale optimisation and scheduling covering day-ahead, intraday, and real-time periods, incorporating stochastic or robust optimisation methods to enhance the model’s ability to adapt to uncertainties in wind and PV output, inflow conditions, and load demand. Further research will refine the unit dynamic models, taking into account energy storage ageing and ramping constraints, and validate the algorithm’s generalisation capabilities on larger-scale energy systems, thereby facilitating the translation of the model into practical engineering applications. In addition, parallel particle evaluation, adaptive stopping criteria, and decomposition strategies will be investigated to improve the computational efficiency and scalability of the MOPSO framework for larger-scale and rolling scheduling applications.
Author Contributions
Conceptualisation, R.G. and X.Y.; methodology and software, X.Y.; validation, W.S., Y.B., H.L. (Hui Li), H.L. (Hongyin Liu), and B.L.; resources and data curation, R.G. and W.S.; writing—original draft preparation, X.Y.; writing—review and editing, R.G., W.S., Y.B., H.L. (Hui Li), H.L. (Hongyin Liu), B.L., Y.C. (Yansong Cui), J.Z., Y.C. (Yuan Cao), and X.Y.; supervision, Y.C. (Yuan Cao); project administration and funding acquisition, R.G. and W.S. All authors have read and agreed to the published version of the manuscript.
Funding
This work was supported by the Science and Technology Project of China Southern Power Grid Company Ltd., titled “Research on Refined Evaluation and Enhancement Technology of Distributed Photovoltaic Accommodation Capacity Under Dual Constraints of Main and Distribution Power Grids” under Grant YNKJXM20240558. The funder provided project support and access to desensitised field data. The funder was not involved in the independent analysis or interpretation of the data, the writing of this article, or the decision to submit it for publication.
Institutional Review Board Statement
Not applicable.
Informed Consent Statement
Not applicable.
Data Availability Statement
The datasets generated and analysed during the current study are available from the corresponding author upon reasonable request. The data are not publicly available due to project-related restrictions.
Conflicts of Interest
Authors Ruizhu Guo, Wei Song, Yiting Bai, and Hui Li were employed by Lincang Power Supply Bureau, Yunnan Power Grid Co., Ltd. Authors Hongyin Liu and Baolin Liu were employed by the Power Planning and Construction Research Center, Yunnan Power Grid Co., Ltd. Authors Yansong Cui and Jing Zi were employed by China Southern Power Grid Internet Service Co., LTD. The remaining authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest. This work was supported by the Science and Technology Project of China Southern Power Grid Company Ltd, titled "Research on Refined Evaluation and Enhancement Technology of Distributed Photovoltaic Accommodation Capacity Under Dual Constraints of Main and Distribution Power Grids" under Grant YNKJXM20240558. The funder was not involved in the study design, collection, analysis, interpretation of data, the writing of this article or the decision to submit it for publication.
References
- Zhao, J.; Chen, L.; Wang, Y.; Liu, Q. A Review of System Modeling, Assessment and Operational Optimization for Integrated Energy Systems. Sci. China Inf. Sci. 2021, 64, 191201. [Google Scholar] [CrossRef] [Scilit]
- Jurasz, J.; Canales, F.A.; Kies, A.; Guezgouz, M.; Beluco, A. A Review on the Complementarity of Renewable Energy Sources: Concept, Metrics, Application and Future Research Directions. Sol. Energy 2020, 195, 703–724. [Google Scholar] [CrossRef] [Scilit]
- Zhang, X.; Ma, G.; Huang, W.; Chen, S.; Zhang, S. Short-Term Optimal Operation of a Wind-PV-Hydro Complementary Installation: Yalong River, Sichuan Province, China. Energies 2018, 11, 868. [Google Scholar] [CrossRef] [Scilit]
- Luo, X.; Wang, J.; Dooner, M.; Clarke, J. Overview of Current Development in Electrical Energy Storage Technologies and the Application Potential in Power System Operation. Appl. Energy 2015, 137, 511–536. [Google Scholar] [CrossRef] [Scilit]
- Guo, R.; Peng, R.; Zhu, Z.; Wang, W.; Liu, H.; Du, C.; Zhang, X.; Cui, Y.; Zi, J.; He, L.; et al. Adaptive Bi-Level Planning of Photovoltaic Hosting Capacity for Hydro-Dominant Distribution Grids Considering Hydraulic Safety Constraints. Symmetry 2026, 18, 1079. [Google Scholar] [CrossRef] [Scilit]
- Zhou, S.; Han, Y.; Zalhaf, A.S.; Chen, S.; Zhou, T.; Yang, P.; Elboshy, B. A Novel Multi-Objective Scheduling Model for Grid-Connected Hydro-Wind-PV-Battery Complementary System under Extreme Weather: A Case Study of Sichuan, China. Renew. Energy 2023, 212, 818–833. [Google Scholar] [CrossRef] [Scilit]
- Ge, Y.; Xie, J.; Chang, J.; Feng, S. A Multi-Objective Deep Reinforcement Learning Method for Intelligent Scheduling of Wind-Solar-Hydro-Battery Complementary Generation Systems. Int. J. Electr. Power Energy Syst. 2025, 167, 110635. [Google Scholar] [CrossRef] [Scilit]
- Xu, Y.; Jiang, Z.; Peng, W.; Lu, P.; Wang, J.; Xu, Y.; Lu, J. Multi-Objective Optimization and Mechanism Analysis of Integrated Hydro-Wind-Solar-Storage System: Based on Medium-Long-Term Complementary Dispatching Model Coupled with Short-Term Power Balance. Energy 2025, 332, 137246. [Google Scholar] [CrossRef] [Scilit]
- Qiao, L.; Tan, Q.; Wen, X.; Wang, Z. Complementary Scheduling of Hydro-Wind-PV-Storage Systems: Addressing Flexibility Demand for High-Penetration Variable Renewable Energy Integration. Renew. Energy 2026, 257, 124718. [Google Scholar] [CrossRef] [Scilit]
- Kennedy, J.; Eberhart, R. Particle Swarm Optimization. In Proceedings of the ICNN’95—International Conference on Neural Networks; IEEE: Perth, WA, Australia, 1995; Volume 4, pp. 1942–1948. [Google Scholar] [CrossRef] [Scilit]
- Coello, C.A.C.; Pulido, G.T.; Lechuga, M.S. Handling Multiple Objectives with Particle Swarm Optimization. IEEE Trans. Evol. Comput. 2004, 8, 256–279. [Google Scholar] [CrossRef] [Scilit]
- Zhang, C. Stability Analysis of Wind Power Grid-Connection and Operation Optimization of Virtual Power Plant. Master’s Thesis, Yanshan University, Qinhuangdao, China, 2019. (In Chinese) [Google Scholar] [CrossRef]
- Li, C.; Zheng, Y.; Zhu, D.; Liu, Y.; Li, G. Study on Output Power Models of Wind Turbines. Water Power 2014, 40, 123–125, 128. (In Chinese) [Google Scholar]
- Parida, B.; Iniyan, S.; Goic, R. A Review of Solar Photovoltaic Technologies. Renew. Sustain. Energy Rev. 2011, 15, 1625–1636. [Google Scholar] [CrossRef] [Scilit]
- Mayer, D.; Wald, L.; Poissant, Y.; Pelland, S. Performance Prediction of Grid-Connected Photovoltaic Systems Using Remote Sensing; Report IEA-PVPS T2-07:2008; International Energy Agency: Paris, France, 2008. [Google Scholar]
- Okedu, K.E.; Al Siyabi, M.S. Harnessing Hydropower Potential in Desert Regions: The Case of Wadi Dayqah Dam, Quriyat, Oman. Front. Water 2021, 3, 686856. [Google Scholar] [CrossRef] [Scilit]
- Xu, J. Control Strategy and System Research on Hydro-Wind-Solar Complementary Power Generation. Master’s Thesis, Nanchang Institute of Technology, Nanchang, China, 2019. (In Chinese) [Google Scholar] [CrossRef]
- Štěpanec, L.; Aye, H.Y.; Lin, O.Z.; Koutroulis, E.; Juchelkova, D. Unsupervised Learning-Based Operational Regime Discovery and Weather Sensitivity Analysis of a Residential Photovoltaic Battery System for Energy Management. Eng. Appl. Artif. Intell. 2026, 181, 115336. [Google Scholar] [CrossRef] [Scilit]
- Zhang, D.; Wang, X.; Wang, Y.; Cai, B.; Gao, S.; Tian, M.; Cai, S.; Deng, Y.; Cao, Y.; Li, F. State-of-Charge Balancing Control for Dual-Bus Battery System with Low-Voltage Output Regulation. World Electr. Veh. J. 2024, 15, 10. [Google Scholar] [CrossRef] [Scilit]
- Gad, A.G. Particle Swarm Optimization Algorithm and Its Applications: A Systematic Review. Arch. Comput. Methods Eng. 2022, 29, 2531–2561. [Google Scholar] [CrossRef] [Scilit]
- Zhang, H.; Zhou, J.; Zhang, Y. Research on Economic Optimization Operation of Virtual Power Plant with Source-Load-Storage. Electr. Drive 2021, 51, 55–60. (In Chinese) [Google Scholar] [CrossRef]
- Zhang, S.; Li, J.; Qu, D.; Kong, D. Scheduling Model of Carbon Capture Virtual Power Plant Considering Joint Operation. Model. Simul. 2024, 13, 649–660. (In Chinese) [Google Scholar] [CrossRef]
- Li, S.; Chen, X.; Hu, Y.; Gan, L.; Zhou, Z. An Energy Storage System Configuration Strategy of Public Buildings for PV Local Consumption and Three-Phase Unbalance Management. Front. Energy Res. 2024, 12, 1374122. [Google Scholar] [CrossRef] [Scilit]
- Liu, Y.; Yao, L.; Li, T.; Qian, T. Optimization Scheduling of Multi-Energy Complementary Systems Considering Wind and Solar Uncertainty and Peak Shaving Initiative. Model. Simul. 2024, 13, 4753–4766. (In Chinese) [Google Scholar] [CrossRef]
- Liu, C.; Jiang, T.; Cao, Y.; Liu, W.; Liu, W. Source-Storage Coordination Optimal Scheduling Method with Concentrating Solar Power. Smart Grid 2023, 13, 1–14. (In Chinese) [Google Scholar] [CrossRef]
- Niu, H.; Yang, L.; Zhao, J.; Wang, Y.; Wang, W.; Liu, F. Flexible-Regulation Resources Planning for Distribution Networks with a High Penetration of Renewable Energy. IET Gener. Transm. Distrib. 2018, 12, 4099–4107. [Google Scholar] [CrossRef] [Scilit]
- Lin, O.Z.; Koutroulis, E.; Štěpanec, L.; Aye, H.Y.; Juchelkova, D. Decentralized Solar PV Systems for Energy Resilience: Lessons from Myanmar’s Post-2021 Political Turmoil Using Field Test Data. Renew. Energy 2026, 267, 125793. [Google Scholar] [CrossRef] [Scilit]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2026 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.