1. Introduction
The distribution network is the electrical link closest to end users and is therefore directly related to power supply reliability, service restoration speed, and operating safety [
1,
2,
3]. With the development of new power systems, distribution networks are being connected to distributed generation, flexible loads, switching devices, and measurement terminals on a larger scale. Their topology, operating mode, neutral-point grounding state, and load distribution are more complex than those of traditional radial feeders. Under these conditions, fault features are more easily affected by line parameters, grounding mode, and operating fluctuation, which increases the difficulty of fault location and fault isolation.
Single-phase-to-ground faults are frequent in medium-voltage distribution networks. In a small-current grounding system, the neutral point is generally ungrounded or grounded through an arc-suppression coil. After a single-phase-to-ground fault occurs, the three-phase line voltages may remain approximately symmetrical for a short period, and the fault current amplitude is much lower than that of a phase-to-phase short-circuit fault. The system can continue to operate temporarily under the fault state. However, if the fault is not located and isolated in time, it may develop into an interphase short circuit, enlarge the outage range, damage key equipment, and create safety risks. Rapid and accurate fault location is therefore important for distribution network maintenance and intelligent operation [
4,
5,
6].
Accurate fault location requires not only fault line or fault section identification but also determination of the specific fault point along the faulted section. In practical distribution networks, manual inspection is inefficient and may require a large searching range. A location algorithm that can identify the fault position with acceptable accuracy can reduce the inspection workload and support faster service restoration. The location problem becomes more challenging in small-current grounding systems because the steady-state fault current is weak, transient features decay rapidly, and line branches produce multiple reflected and refracted waves.
Traveling-wave methods use the high-frequency transient waves generated at the instant of fault occurrence. These waves contain abundant fault position information and are less affected by steady-state compensation and fault current amplitude. In principle, the fault distance can be calculated from the arrival times of the initial traveling waves at one or more measurement terminals. Compared with impedance and steady-state methods, traveling-wave methods offer faster response and higher theoretical location accuracy. They are therefore suitable for distribution-network accurate fault location, especially when the steady-state fault feature is weak [
7,
8,
9].
Other accurate fault location methods mainly include impedance-based methods, time-domain fault analysis methods, signal injection methods, threshold-free detection methods, Hough-transform methods, and intelligent fault location methods. Impedance-based methods estimate the fault position according to the relationship between measured voltage, current, and line impedance, but the results are easily influenced by transition resistance, line asymmetry, parameter uncertainty, and multi-branch topology. Time-domain and signal injection methods can improve identification capability, but their performance depends on model accuracy, measurement quality, synchronization precision, or additional field devices, which may increase engineering implementation cost [
10,
11,
12].
For a fair comparison with previous studies, fault location performance should be described not only by whether the correct fault line or section is identified but also by quantitative metrics such as maximum absolute error, mean absolute error, error range under different fault resistances or inception angles, sampling rate, tested topology, terminal configuration, response speed, and whether noise or synchronization perturbation is considered. The cited traveling-wave and Hough-transform studies are mainly evaluated by distance-error-related metrics under specified topologies and terminal configurations, whereas threshold-free, signal injection, and intelligent fault location studies are commonly evaluated by line or section identification accuracy, adaptability to transition resistance, response speed, and test system conditions. Therefore, the present work reports the available fault point, fault distance, tested terminal pair, transition resistance, inception angle, maximum and average absolute errors, and comparison method errors while explicitly stating the deterministic validation scope so that the results are not compared beyond equivalent test conditions.
Nevertheless, traveling-wave fault location in distribution networks still faces two technical difficulties. The first difficulty is initial wavefront calibration. The initial wavefront duration is extremely short, and it can be superimposed with high-frequency oscillation, reflected waves, refracted waves, and measurement noise [
13,
14]. If the arrival time of the first wavefront is not calibrated accurately, the error will be directly reflected in the final distance calculation. The second difficulty is the dependence of conventional double-ended traveling-wave location formulas on fixed empirical wave velocity. In practical overhead and distribution lines, the actual propagation path is affected by conductor arrangement, terrain, sag, frequency-dependent parameters, and line branches. The practical line length may deviate from the horizontal length used in the model, and a fixed empirical velocity may introduce additional error [
15,
16,
17]. Therefore, the applicable propagation conditions and boundary assumptions of the improved propagation-time-ratio formula need to be stated explicitly when interpreting traveling-wave location results in branched distribution networks.
To address these problems, this study proposes a double-ended traveling-wave accurate fault location method based on VMD-GST-SDEO. The method uses voltage line-mode traveling waves as the basic input. VMD is adopted to separate the high-frequency transient mutation component from low-frequency background variation. GST is then used to enhance local time–frequency features near the initial wavefront. The SDEO is further used to extract the first significant energy mutation point, which is taken as the wavefront arrival time. In the distance calculation stage, an improved double-ended location formula based on the absolute propagation time ratio is introduced. The formula no longer explicitly substitutes a fixed empirical wave velocity and instead calculates the fault position using the horizontal length of the fault section and the propagation time ratio at both ends.
The main contributions of this study are summarized as follows: First, a wavefront calibration framework that combines VMD, GST, and the SDEO is constructed for nonstationary voltage traveling-wave signals. The framework separates transient high-frequency components, enhances local time–frequency mutation features, and identifies the first significant energy mutation point. Second, an improved double-ended traveling-wave location model is derived. The model calculates the fault-point horizontal distance according to the section length and the absolute propagation time ratio, reducing the influence of fixed velocity selection. Third, the tested PSCAD/EMTDC-MATLAB simulation cases are reorganized with clearer terminal pair definitions, sampling resolution interpretation, branch boundary conditions, and quantitative comparison data. The validation scope is limited to the studied single topology, arc-suppression-coil grounding mode, and deterministic simulation cases, and the conclusions are stated within this range.
It should be emphasized that the novelty is not the independent invention of VMD, GST, or the SDEO, which are established signal-processing tools, but their coordinated use for the first-arrival wavefront calibration problem in small-current grounding distribution networks and their integration with a double-ended distance formula that avoids direct use of a fixed empirical wave velocity. This distinction separates the methodological contribution of this study from the established signal-processing foundations.
4. Discussion
4.1. Mechanism-Level Advantages of VMD-GST-SDEO
The advantage of the proposed method comes from the cooperation of the three signal-processing stages. VMD first decomposes the original voltage line-mode traveling wave into several finite-bandwidth IMF components. This decomposition separates the high-frequency mutation component from low-frequency background variation and reduces the probability of direct misidentification from the original waveform. GST then enhances local time–frequency features of the selected high-frequency mode. Because the initial wavefront is a short-duration mutation, a time–frequency representation with high time resolution is useful for wavefront calibration. Finally, the SDEO uses a central difference structure to extract the energy mutation point. This operation is more stable than direct amplitude thresholding under weak mutation conditions.
The method therefore uses physical characteristics and signal-processing characteristics simultaneously. The input signal is a voltage line-mode traveling wave, which is relatively stable compared with the zero-mode component. The wavefront is calibrated using local mutation information rather than steady-state amplitude variation. This feature makes the method suitable for small-current grounding systems, in which steady-state current features may be weak or affected by arc-suppression-coil compensation.
4.2. Interpretation of the Improved Double-Ended Location Formula
In a conventional double-ended traveling-wave formula, the wave velocity is an explicit input. Once the selected velocity deviates from the actual propagation velocity, the calculated fault position is affected. The improved formula in this study uses the absolute propagation time ratio. When the propagation velocity on both sides of the fault point is approximately the same within the same fault section, the ratio of horizontal distance can be represented by the ratio of propagation time. Therefore, the final formula depends on the section horizontal length and the two absolute propagation times instead of depending directly on an empirical velocity.
The improved formula also has clear sensitivity to wavefront timing errors. As shown by Equation (11), independent timing errors at the two terminals, including synchronization error, ADC sampling quantization, and channel noise, can perturb both the numerator and the denominator of the propagation time ratio. The 10 MHz sampling rate gives a 0.1 μs sampling interval, corresponding to an ideal propagation distance interval of about 30 m. This explains why several deterministic cases show repeated or close error values: the identified arrival time can fall into the same sampling bin under different operating conditions.
This improvement is meaningful for reducing the explicit dependence on a selected empirical wave velocity, but it does not eliminate the requirement for accurate time synchronization. If a common time offset affects both terminal records equally, its influence can be partly canceled in the ratio. However, the relative clock error between the two terminals changes Tm and Tn differently and may directly affect the calculated distance. Therefore, the proposed formula should be used together with high-precision synchronized acquisition devices. Quantitative tests with controlled synchronization error, jitter, and measurement noise will be necessary in future work to fully evaluate engineering robustness.
The propagation-time-ratio formula is most appropriate when the selected fault section can be treated as a section with approximately uniform propagation characteristics. In mixed overhead cable sections, sections containing conductor-type transitions, or feeders with an internal branch between the two measurement terminals, the propagation velocity and wave attenuation on the two sides of the fault point may differ. Under these conditions, the simple ratio model may introduce systematic error, and a segmented propagation model or calibrated section-specific velocity ratio should be used. Because the available validation data do not include mixed overhead cable or nonuniform parameter cases, this limitation is now stated explicitly rather than treated as already verified.
4.3. Interpretation of the Existing Simulation Results
The deterministic simulation results show that the proposed method maintains errors below 100 m under the studied changes in fault distance, transition resistance, and fault inception angle. The fault distance results indicate that the method can calculate the fault position correctly for the selected tested sections. The transition-resistance results indicate that the wavefront can still be calibrated under high transition resistance after VMD-GST-SDEO processing. The inception angle results show that weak mutation conditions can also be handled within the adopted sampling resolution. However, because the validation set does not include repeated trials, noise realizations, synchronization jitter tests, or confidence intervals, these results should be understood as deterministic simulation evidence rather than full statistical robustness verification.
The comparison with EMD-TEO, VMD-TEO, and VMD-GST further explains the role of each processing stage. EMD-TEO suffers from mode mixing during decomposition. VMD-TEO improves decomposition but still relies on a single energy operator. VMD-GST enhances the time–frequency representation but does not include the SDEO mutation detection step. The proposed method integrates the advantages of these stages and therefore obtains lower and more stable location errors under the deterministic test conditions listed in
Table 5.
The comparison is limited to EMD-TEO, VMD-TEO, and VMD-GST because the available data set contains only the deterministic waveforms and error values used for these algorithms. Recent wavelet-based, Hough-transform, threshold-free, and intelligent fault location methods are important reference methods, but a fair numerical comparison would require implementing each method under the same topology, sampling frequency, noise condition, and terminal configuration. Since such additional simulations are not available in the present data set, this manuscript does not create unsupported comparison values and instead lists broader comparative evaluation as future work.
The result groups are interpreted according to the revised tables and figures. The fault distance, transition resistance, fault inception angle, and algorithm comparison results jointly show the role of the proposed signal-processing chain under the deterministic simulation settings. They do not replace repeated-trial statistics, confidence intervals, or field data validation. This interpretation keeps the claims consistent with the available validation data while making the relationship among the existing validation cases clearer.
4.4. Engineering Applicability and Limitations
The proposed method has potential engineering applicability in distribution networks equipped with synchronized traveling-wave measurement devices at both ends of the fault section. The method does not require an injected signal source, and the main signal-processing steps can be implemented in MATLAB or embedded algorithms after signal acquisition. The method is also compatible with a fault section identification scheme: after the fault section is determined, the two terminals of the fault section can be used for accurate fault point calculation.
In practical distribution networks, the required measurement infrastructure includes high-speed voltage traveling-wave acquisition units, synchronized clocks at both terminals, communication or data retrieval channels for the two terminal records, and a triggering strategy for detecting the fault inception reference. These requirements may increase installation cost compared with methods using only steady-state measurements. The 10 MHz sampling rate used in the simulation also implies that the achievable location accuracy is linked to the recorder bandwidth, ADC resolution, triggering stability, and GPS/BeiDou timing uncertainty. Therefore, the proposed method is more suitable for feeders or critical sections where synchronized traveling-wave recording devices are already installed or can be justified by the required fault location accuracy.
The verification is based on the PSCAD/EMTDC-MATLAB simulation model and the deterministic result set. Additional simulation conditions beyond the studied topology and grounding mode are not included in the present validation. Before formal engineering application, further work should be carried out using measured waveform data, semi-physical simulation data, different noise levels, different sampling frequencies, controlled synchronization errors, mixed overhead cable structures, and line parameter variation. These additional studies are outside the scope of the present manuscript and are listed as future work to avoid overextending the conclusions.
Possible failure cases include a wavefront that is completely masked by noise, a weak mutation below the SDEO selection level, severe terminal synchronization mismatch, internal reflections arriving before the selected first mutation window, and line sections whose propagation characteristics differ strongly on the two sides of the fault point. In such cases, the detected mutation point may shift to a secondary reflection or to a noise-induced peak, which will directly affect Tm, Tn, and the final distance result. These conditions should be tested before the method is used as an engineering decision tool.
4.5. Practical Use in a Fault-Handling Workflow
In an engineering fault-handling workflow, the proposed accurate location method can be used after the fault line and fault section have been identified. The measurement terminals at the two ends of the suspected fault section provide the three-phase voltage traveling-wave signals. The algorithm then calculates the fault distance from the upstream terminal. This result can be used to guide patrol inspection, switching operation, and restoration planning. The method therefore complements section location methods rather than replacing them.
The method also has a clear data requirement. It requires high-frequency voltage traveling-wave data at both ends of the fault section and reliable synchronization between the two measurement terminals. The simulation uses a 10 MHz sampling frequency, which provides a 0.1 μs time interval for identifying the initial wavefront. In practical implementation, the sampling capability and synchronization precision of the measurement device should be selected according to the target location accuracy, and the possible quantization floor should be considered.
Because the improved formula uses a propagation time ratio, it can reduce but not completely eliminate the influence of nonuniform line parameters. If the fault section contains a uniform overhead line, the assumption of approximately equal propagation velocity on both sides of the fault point is reasonable. If the section contains mixed overhead lines and cables, conductor-type changes, internal branch nodes, or obvious parameter discontinuities, a segmented model may be required. This boundary condition should be considered during engineering application.
5. Conclusions
(1) A VMD-GST-SDEO-based double-ended traveling-wave accurate fault location method is proposed for single-phase-to-ground faults in small-current grounding distribution networks. The method extracts the voltage line-mode component using Clarke transformation, applies VMD to separate high-frequency transient features, uses GST to enhance local time–frequency mutation characteristics, and adopts the SDEO to identify the initial wavefront arrival time. An improved double-ended location formula based on the absolute propagation time ratio is used to calculate the fault distance.
(2) Theoretical analysis shows that the voltage line-mode component is more suitable for fault traveling-wave processing than the zero-mode component because it is less affected by earth-return parameters and frequency-dependent attenuation. VMD can reduce mode mixing and provide a clearer high-frequency component. GST improves time–frequency feature representation near the wavefront. The SDEO provides a stable instantaneous energy spectrum and helps identify the first significant mutation point.
(3) The PSCAD/EMTDC-MATLAB deterministic simulation results show that the proposed method maintains an absolute location error below 100 m under the studied fault distances, transition resistances, and fault inception angles. The representative errors include 15 m at the 2.5 km fault point, 45 m under a 500 Ohm transition resistance, and 11 m under a 90-degree inception angle at the 6.15 km fault point. Compared with EMD-TEO, VMD-TEO, and VMD-GST, the proposed method achieves lower average error under the tested deterministic conditions. These results verify feasibility within the current simulation scope, but they do not represent repeated-trial statistics.
(4) The method reduces the explicit dependence of conventional double-ended traveling-wave location on fixed empirical velocity by using the propagation time ratio. This improvement can weaken the influence of velocity selection error and actual line length deviation, but it still requires accurate wavefront calibration and reliable terminal synchronization. Future work will further verify the method using additional noise conditions, synchronization error tests, repeated trials, mixed-line structures, sampling frequency variation, and field-recorded transient data. The practical implication is that the method can provide a candidate accurate-location module after fault section identification when synchronized traveling-wave measurements are available, but it should not be regarded as a complete standalone field fault location system until additional validation under measured, noisy, nonuniform, and synchronized-acquisition conditions is completed.