Abstract
The utilization of geothermal energy is favorable for the improvement of energy efficiency. A hybrid system consisting of a seasonal heating and cooling cycle, an absorption refrigeration cycle and a liquid dehumidification cycle is proposed to meet dehumidification, space cooling and space heating demands. Geothermal energy is utilized effectively in a cascade approach. Six performance indicators, including humidity efficiency, enthalpy efficiency, moisture removal rate, coefficient of performance, cooling capacity, and heating capacity, are developed to analyze the proposed system. The effect of key design parameters in terms of desiccant concentration, air humidity, air temperature, refrigeration temperature and segment temperature on the performance indicators are investigated. The simulation results indicated that the increase of the desiccant concentration makes the enthalpy efficiency, the coefficient of performance, the moisture removal rate and the cooling capacity increase and makes the humidity efficiency decrease. With the increase of air humidity, the humidity efficiency and moisture removal rate for the segment temperatures from 100 to 130 °C are approximately invariant. The decreasing rates of the humidity efficiency and the moisture removal rate with the segment temperature of 140 °C increases respectively. Six indicators, except the cooling capacity and heating capacity, decrease with an increase of air temperature. The heating capacity decreases by 49.88% with the reinjection temperature increasing from 70 to 80 °C. This work proposed a potential system to utilize geothermal for the dehumidification, space cooling and space heating effectively.
1. Introduction
The growth of the population and the dependency of technology led to the rapid growth demand of energy [1]. In addition, the rapid growth demand of energy recognizes the challenges such as the overconsumption of fossil energy [2]. Those are disadvantageous for sustainable development. The utilization of the renewable energy and the improvement of energy utilization efficiency are two potential ways to solve the previous challenges [3]. Geothermal energy, being a renewable energy, can provide energy for the process system [4]. At the same time, the greenhouse effect intensified the requirement for air. In China, the hot summer and cold winter region is a typical climatic region. The high temperature and humidity climate makes the demands for refrigeration and dehumidification grow rapidly. The absorption refrigeration cycle (ARC) and the liquid dehumidification cycle (LDC) can be powered by the low-grade heat and are environmentally friendly [5]. Thus, the ARC and LDC are two effective technologies to meet the demands of refrigeration and dehumidification. A review of previous literatures was conducted to indicate the objective and necessity of this work.
Geothermal energy is a renewable energy. According to the heat source temperature, geothermal energy is divided into three categories: high-temperature geothermal energy (HTGE), mid-temperature geothermal energy (MTGE) and low-temperature geothermal energy (LTGE). The temperature of the HTGE is above 150 °C and is used for the electricity generation. The electricity generation technology with dry stream is suitable for the HTGE [6]. The MTGE is geothermal energy with the temperature from 90 to 150 °C. The MTGE is used to generate electricity by the binary cycle. The Organic Rankine Cycle (ORC) and Kalina cycle are normal technologies for MTGE [7]. The LTGE is geothermal energy with a temperature lower than 90 °C. This part of energy is best suitable for direct use such as space cooling and heating, industrial processing, and greenhouse heating [8]. From the viewpoint of energy and exergy, Yazici analyzed a geothermal district heating system and found that the efficiencies of energy and exergy were 46.17% and 60.63%, respectively [9]. Kanoglu et.al., applied geothermal with a temperature of 200 °C to a hybrid system consisting of an absorption refrigeration cycle and a Claude cycle. Energy and exergy results showed that the coefficient of performance (COP) and the exergy efficiency of the proposed system are 0.162 and 67.9%, respectively [10]. Ahmadi et al. optimized and analyzed a carbon dioxide (CO2) power cycle driven by geothermal energy. The simulation results showed that the exergy efficiency and the product cost rate of the cycle are 20.5% and USD 263,592.15/year respectively [11]. The previous research represented the reliability and sustainability of geothermal energy.
The absorption refrigeration cycle (ARC) is usually applied in low-grade waste heat recovery [12] or the recovery of other sustainable energy [13]. The advantages of environmental friendliness and low cost cause ARC to attract increased attention. Liu et al. proposed a hybrid system combining an ARC and a Kalina cycle. The simulation results indicated that the hybrid system could improve the net output power by 45% [14]. Subsequently, the author optimized the hybrid system based on the results of economic analysis, energy analysis and the life cycle assessment. According to the optimization results, the optimal energy efficiency and the relative minimum cost were 16.74% and USD 1.85 × 105 [15]. Geothermal energy is a common power for ARC. Khosravi et al. optimized a hybrid system combined with an ARC, a solar heating collection system and a geothermal energy system. The optimized results indicated that the payback time of the system was about 8 years [16]. Geothermal water out of the flash-binary geothermal power plant was used to drive the ARC and desalination by Gnaifaid et.al. The exergy efficiency and the cost rate with the optimization results were 58% and USD 242/h respectively [17]. El Haj Assad et al. applied geothermal energy to produce power by a single-flash geothermal power plant and then used the water to drive the ARC. The results showed that COP of the system could get 0.87 with the water temperature of 120 °C and the solution heat exchange effectiveness of 0.9 [18]. Al-Hamed et al. developed a hybrid system driven by geothermal energy to produce electric power, space heating and cooling, and domestic hot water. The energetic and exergetic efficiencies were 53.33% and 37.07%, respectively, and the energic efficiency with the optimization results could increase to 63.60% [19]. From the viewpoint of energy, exergy and exergoeconomy, Ghaebi et al. proposed and analyzed an integrated system driven by geothermal energy. The system consisted of an ARC and a liquefied natural gas cold energy recovery system and the thermal efficiency, exergy efficiency and sum unit cost of the product of the system were 85.92%, 18.52%, and USD 68.76/GJ respectively [20]. These previous literatures indicated that geothermal energy had excellent ability to drive the ARC.
The dehumidification process is significant for hot summer and cold winter regions in China. At present, the main dehumidification systems are based on condensation dehumidification technology [21]. The traditional condensation system reduces the air temperature into the dew point temperature to separate water vapor [22]. This process aggravated energy consumption [23]. In order to reduce energy consumption, the liquid dehumidification cycle (LDC) is regarded as the alternative technology to the traditional dehumidification technology [24]. Low et al. designed a LDC driven by solar energy and found that the efficiency of the system and the minimum area of solar heating collector were 78.8% and 59.83 m2, respectively [25]. Guan et al. determined the optimal mass flow rate of the desiccant and indicated that the optimal efficiency of the heat exchanger was 0.56 with the optimal ratio of desiccant-to-air being 1.5 [26]. The authors also modified the analytical solutions of the dehumidifier and the deviation between the modified results and the experimental results is less than 10% [27]. Zhang et al. optimized the LDC from the viewpoint of exergy destruction. The optimal exergy efficiency and COP of the LDC were 25% and 7.4, respectively [28]. Chen et al. developed a novel LDC driven by solar energy and optimized the area of solar heating collector [29]. Su et al. combined the ARC, vapor compression cycle with the LDC, and indicated that the efficiency of the proposed system was 34.97% higher than a traditional air conditioning system [30]. The advantageous dehumidification performance and the reliability of the LDC testified the feasibility of the LDC in hot summer and cold winter regions of China.
In this work, a hybrid system composed of an absorption refrigeration cycle, a liquid dehumidification cycle and seasonal heating and cooling cycles is developed. The power of the proposed system is geothermal energy. This hybrid system can meet the dehumidification demand, the space cooling demand, and the space heating demand, concurrently. Six indicators, including the moisture removal rate (MRR), the humidity efficiency (HE), the enthalpy efficiency (EE), COP, the cooling capacity and the heating capacity are proposed to evaluate the hybrid system. This work provides an effective solution to utilize geothermal energy.
2. System Description and Design Process
2.1. Description of System
The hybrid system is provided in Figure 1. The heat source of the proposed system is from a geothermal well. The proposed system consists of four cycles, including an absorption refrigeration cycle (ARC), a liquid dehumidification cycle (LDC) and two heat exchangers. The working pairs of ARC and LDC are lithium bromide solution (LiBr-H2O) and lithium chloride solution (LiCl-H2O), respectively. The mentioned cycles are combined to meet dehumidification, refrigeration, cooling, and heating demands.
Figure 1.
Schematic diagram for the coupling system.
2.1.1. The Geothermal Water
Geothermal water is the heat source of the proposed system. First, geothermal water is pumped from G1 with the mass flow rate of 5 kg/s and the temperature of 150 °C. The high-temperature fluid is introduced into the regenerator (G1) of LDC to provide the heat for the regeneration process of the desiccant. Then, the fluid enters the generator of the ARC to provide the heat for the separation of the vapor. Afterword, depending on the season, the mid-temperature fluid flows into the heat exchanger 3 (HX3) for heating purposes during winter. Finally, the low-temperature fluid returns to the reinjection well (G4).
2.1.2. The Absorption Refrigeration Cycle
The absorption refrigeration cycle (ARC) is used to produce the cooling energy for the proposed system. In this cycle, the LiBr-H2O is chosen as the working pair. The strong LiBr-H2O solution is heated by geothermal water. Due to the difference of boiling point, the vapor is produced in the generator. The vapor enters the condenser (A1). In the condenser, the cooling water of 33 °C is used to cool the vapor into saturated water. After flowing through the valve 1 (A3), the saturated water is introduced into the evaporator to produce the cooling energy. In the evaporator, the flash makes the saturated water become vapor. This process produces cooling energy. Then, depending on the season, the vapor from evaporator (A4) flows into the HX4 for the cooling purpose during summer or flows into the absorber to continue the cycle. In the absorber, the rich solution contacts with the vapor directly. The rich solution absorbs the vapor and becomes a weak solution. In the generator, the solution is divided as rich solution and vapor. The vapor is used for refrigeration and the rich solution is used to absorb the vapor from evaporator. The rich solution first flows into the HX1 (A5) to preheat the new solution and then enters the absorber (A7) after flowing through the valve 2 (A6). The weak solution from the absorber, pumped by pump 1 (A8), is introduced into the HX1 (A9) and then enters into the generator (A10) to continue the cycle. Generally, the ARC is used to produce cooling energy.
2.1.3. The Liquid Dehumidification Cycle
The liquid dehumidification cycle (LDC) is applied to remove moisture in the air. This cycle selected the LiCl-H2O as the working pair. There are five main units for the LDC, including a dehumidifier, a regenerator, a heat exchanger and two pumps. In the dehumidifier, the outside air (1) contacts with the liquid desiccant directly. The mass and heat transformation makes the wet air become dry air. Then, the dry air enters the room (2). The solution with low concentration from the dehumidifier flows into pump 2 (D1) and then enters into HX2 for preheating (D2). In the regenerator, the weak solution (D3) contacts with the air from room (4) directly. The heat for regeneration is provided by geothermal water. In this unit, the weak solution becomes the rich solution and then flows into the HX2 (D4) to preheat the weak solution. The rich solution from D5 is pumped by pump 3 (D5) and then enters the condenser (D6). The rich solution is cooled by the refrigerant of ARC then comes into the dehumidifier to continue the cycle consequently. The LDC meets the dehumidification demand by recovering geothermal effectively.
2.1.4. Seasonal Cooling and Heating Cycles
The seasonal cooling and heating cycles are composed of two heat exchangers. For the cooling purpose of summer, the HX4 keeps working during summer to provide cooling energy. In addition, the air from outside is dehumidified and cooled simultaneously. The HX3 is used for the heating purpose during winter. Geothermal water flows through the HX3 to release heat during winter and then flows into the reinjection well.
2.2. The Mathematical Equations for Two Subsystems
Based on the conservation of mass and energy, the LiBr-H2O ARC and the LiCl-H2O LDC are designed and analyzed. From the Figure 1, the main units of LiBr-H2O ARC and LiCl-H2O LDC can be classified as: pumps, valves, the heat exchangers, and packed towers. The mathematical equations can be calculated as follows and the detailed equations are introduced in Appendix A.
where represents the mass flow rate; and are the enthalpy and heat of streams respectively; is the power consumed by pumps.
2.3. The Performance Indicators for the Coupling System
- (1)
- Moisture removal rate (MRR): The MRR represents the moisture removal ability of the coupling systems. It can be defined as [31]:
- (2)
- Humidity efficiency (HE): The HE is an index to evaluate the performance of the dehumidifier. It can reveal the heat and mass transformation between air and desiccant in the dehumidifier. The HE is calculated as [32,33,34]:
- (3)
- COP: COP, as a usual performance index, can represent the utilization efficiency of a geothermal source. COP for the coupling system is defined as [35]:
- (4)
- Enthalpy efficiency (EE): The EE can evaluate the performance of the dehumidifier from the viewpoint of thermodynamics. It can be calculated as [36]:
2.4. Model Validations and the Design of the Coupling System
The LiBr-H2O ARC and the LiCl-H2O LDC are simulated in Aspen Plus. The ELECNRTL method is selected as the basic property method. In Table 1, the specification for the models is listed in detail. The generator is simulated by the Heater model and the Flash2 model. The Heater model and the ABSBR1 model are applied to simulate the regenerator. The condensation pressure, decided by the condensation temperature, is 7.38 kPa. According to the other references [14,15,37], the most optimal temperature of the generator for LiBr-H2O ARC is 90 °C. In this work, the generator temperature is set as 80 °C due to a temperature decrease of 10 °C. In our previous work [12,35], the reliabilities of LiBr-H2O ARC and LiCl-H2O LDC have been validated. The comparison results are listed in Table 2 and Table 3. The deviations of 0.4% and 0.2% represent the reliabilities of the LiBr-H2O ARC and LiCl-H2O LDC. The design procedure is introduced in Figure 2. The first step of the design process is to determine the refrigeration temperature. After the assumption of the segment temperature, the LiBr-H2O ARC and LiCl-H2O LDC are designed, respectively. In the coupling system, geothermal source is divided into two different parts. The high-temperature part is introduced to regenerate the desiccant and the low-temperature part is used to heat the LiBr-H2O solution. In addition, the cooling energy produced by the LiBr-H2O ARC is used for the refrigeration of desiccant and room respectively. Finally, the data is recorded to evaluate the coupling system. Before the simulation of the system, the design parameters are listed in Table 4. For the accuracy of the simulation, necessary assumptions are as follows [38,39,40]:
Table 1.
The detailed specification of the models.
Table 2.
The comparison results of absorption refrigeration cycle.
Table 3.
The comparison results of liquid dehumidification cycle.
Figure 2.
The design procedure for the coupling system.
Table 4.
The detailed parameters for the simulation of system.
- (1)
- The system is stable;
- (2)
- The heat loss and the drop loss of pipes are negligible;
- (3)
- The system is simulated with no kinetic energy and potential energy;
- (4)
- The units of the coupling system have no heat loss;
- (5)
- The stream and the liquid refrigeration are assumed as saturated.
3. Results and Discussions
Based on the simulation results, the influence of design parameters on the indicators are studied in this section. The relationship between the design parameters and the indicators are shown in vivid pictures.
3.1. The Effect of Desiccant Concentration on the Coupling System
The effect of desiccant concentration on performance indicators is provided in Figure 3, Figure 4, and Figure 5. With an increase of the desiccant concentration, COP, , and cooling capacity increase while the decreases, generally.
Figure 3.
The effect of desiccant concentration on the performance indicators with the refrigeration temperature of 2 °C. (a) COP and EE; (b) HE and MRR; (c) cooling capacity.
Figure 4.
The effect of desiccant concentration on the performance indicators with the refrigeration temperature of 5 °. (a) COP and EE; (b) HE and MRR; (c) cooling capacity.
Figure 5.
The effect of desiccant concentration on the performance indicators with the refrigeration temperature of 10 °C. (a) COP and EE; (b) HE and MRR; (c) cooling capacity.
Figure 3 is the performance indicators with the refrigeration temperature of 2 °C. For the , and COP, the increase of segment temperature has little effect on the indicators. But the Δω with the segment temperature of 140 °C is lower than that of 100 to 130 °C. As the desiccant concentration increases from 30% to 40%, the and COP rise with the increased rate of 5.78% and 5.79%, respectively. On the contrary, the decreases by 1.21% with the desiccant concentration increasing from 30% to 40%. However, the increases by 5.06%. The last index is the cooling capacity. Figure 3c indicates that the desiccant concentration and segment temperature have serious influence on the cooling capacity. With the increase of desiccant concentration, the cooling capacity for different segment temperature rises, respectively. As the segment temperature increases, the cooling capacity for the same desiccant concentration increases concurrently. In addition, the cooling capacity with the segment temperature of 100 °C is lower than that of 110 to 140 °C.
Figure 4a,c shows the performance indicators with the refrigeration temperature of 5 °C. As shown in Figure 3, the increase of desiccant concentration leads to an increase of COP, , and cooling capacity and a decrease of . Compared with the results with the refrigeration temperature of 2 °C, the values of COP, , and move increasingly closer. As the desiccant concentration rises from 30% to 40%, the and COP for different segment temperature increase by 7.29% and 7.28%, respectively. The Δω increases by 6.43% while the ηω decreases by 1.27%. For the index of cooling capacity, the effect of desiccant concentration and segment temperature is obvious. The tendency of the cooling capacity with the refrigeration temperature of 5 °C is similar to that of 2 °C. The cooling capacity with the segment temperature of 100 °C is lower than that of 110 to 140 °C. However, the cooling capacity with the segment temperature of 120 °C is close to that of 130 and 140 °C.
The performance indicators with the refrigeration temperature of 10 °C are introduced in Figure 5. Figure 5a is the and COP of the proposed system. Similar to the previous results, the values of COP and with different refrigeration temperature are almost equal. With the increase of desiccant concentration from 30% to 40%, the increase rate of and COP are 10.84% and 10.83%, respectively. The decreases by 9.69%. The with the refrigeration temperature of 140 °C is lower than that of 100 to 130 °C as the desiccant concentration increases from 30% to 35%. However, as the concentration increases to 40%, the with different segment temperatures are increasingly close. Figure 5c shows the cooling capacity with the refrigeration temperature of 10 °C. As the desiccant concentration increases, the cooling capacity of the proposed system increases sluggishly. With the same desiccant concentration, the increase of the segment temperatures from 110 to 140 °C leads to an almost homogeneous increase for the cooling capacity.
In general, a higher desiccant concentration represents a bigger COP, , and cooling capacity, while lowering . As the refrigeration temperature increases from 2 to 10 °C, the , , COP and cooling capacity decreases, while the increases. From the viewpoint of the change of desiccant concentration, higher concentration means better performance for the hybrid system. From the viewpoint of the refrigeration temperature, lower refrigeration temperature means better performance for the hybrid system.
3.2. The Effect of Air Humidity on the Coupling System
The performance indicators are introduced with different air humidity and refrigeration temperature from Figure 6, Figure 7 and Figure 8. Figure 6 shows the indicators with a refrigeration temperature of 2 °C. The results in Figure 6a indicate that the increase of segment temperature has a little influence on COP and . With the rising of the air humidity, the and COP increase by 24.66% and 187.37%, respectively. It means that the increase of air humidity has a great effect on COP. The increase of air humidity makes the and with the segment temperatures from 100 to 130 °C, respectively, change slightly. But the and , with a segment temperature of 140 °C, decrease by 3.54% and 3.55%, respectively. The decrease rate of Δω increases from 0.16% to 3.39%. The decrease rate of increases from 0.15% to 3.38%. The increase of air humidity makes the cooling capacity rise. The cooling capacity with the segment temperature of 100 °C is smaller than the cooling capacities with the segment temperatures from 110 to 140 °C.
Figure 6.
The effect of air humidity on the performance indicators with a refrigeration temperature of 2 °C. (a) COP and EE; (b) HE and MRR; (c) cooling capacity.
Figure 7.
The effect of air humidity on the performance indicators with the refrigeration temperature of 5 °C. (a) COP and EE; (b) HE and MRR; (c) cooling capacity.
Figure 8.
The effect of air humidity on the performance indicators with the refrigeration temperature of 10 °C. (a) COP and EE; (b) HE and MRR; (c) cooling capacity.
Figure 7 and Figure 8 show the performance indicators with the refrigeration temperature of 5 and 10 °C. Similar to the results in Figure 6, the and COP with different segment temperature are almost equal, and the segment temperature has a great effect on the and , with the segment temperature of 140 °C, and has little influence on the and with the segment temperatures from 100 to 130 °C. As the air humidity increases, the and COP with a refrigeration of 5 °C, increase by 20.43% and 195.07% respectively. The and COP with the refrigeration of 10 °C increase by 14.37% and 217.90%, respectively. The results of COP represent that the rise of refrigeration temperature has great effect on the increase rate of COP. The influence of refrigeration temperature on the increase rate of becomes smaller. For the refrigeration temperature of 5 °C, the decrease rate of the and with the segment temperature of 140 °C are 2.69% and 2.7%, respectively. For the refrigeration temperature of 5 °C, the decrease rate of the and with the segment temperature of 140 °C are 2.09% and 2.08%, respectively. The cooling capacities with the refrigeration temperature of 5 and 10 °C increase with the increase of air humidity, respectively.
As the refrigeration temperature increasing from 2 to 10 °C, the , and COP decrease, while the increases. The cooling capacities with the segment temperatures from 110 to 140 °C has little change.
3.3. The Effect of Air Temperature on the Coupling System
The results of the performance indicators for different air temperature are shown in Figure 9, Figure 10 and Figure 11. The increase of air temperature makes the , , and COP decrease, generally. The rise of air temperature has great effect on the indicators with different segment temperatures. The results in Figure 9 indicate that COP with the segment temperatures from 100 to 120 °C are almost equal. The has the same tendency. The decrease rates of for different segment temperatures increase from 12.18% to 25.62% and the decrease rates of COP for different segment temperatures rise from 23.41% to 35.14%. The with the segment temperature of 100 °C is equal to that of 110 °C. As the air temperature increases, the decrease rate of increases to 17.06%, and the increase rate of increases to 17.06%. The cooling capacities for different segment temperatures increase with the rise of air temperature. With the rise of segment temperature, the cooling capacity with the same air temperature increases.
Figure 9.
The effect of air temperature on the performance indicators with the refrigeration temperature of 2 °C. (a) COP and EE; (b) HE and MRR; (c) cooling capacity.
Figure 10.
The effect of air temperature on the performance indicators with the refrigeration temperature of 5 °C. (a) COP and EE; (b) HE and MRR; (c) cooling capacity.
Figure 11.
The effect of air temperature on the performance indicators with the refrigeration temperature of 10 °C. (a) COP and EE; (b) HE and MRR; (c) cooling capacity.
Figure 10 and Figure 11 are the indicators with the refrigeration temperatures of 5 and 10 °C, respectively. For the refrigeration temperature of 5 °C, the decrease rates of with different segment temperatures increase from 11.65% to 25.85%. The decrease rates of with different segment temperatures increase to 17.90%. For the refrigeration temperature of 10 °C, the decrease rates of with different segment temperatures increase from 10.64% to 23.87%. The decrease rates of with different segment temperatures increase to 16.47%.
As the refrigeration temperature increases, the and COP with same air temperature and segment temperature have little change. The and increase with a rise of refrigeration temperature. The cooling capacities with the segment temperatures from 110 to 140 °C for different refrigeration temperatures are within the range of 200 to 280 kW.
3.4. The Heating Capacity of the Proposed System
Figure 12 shows the results of the heating capacity of the proposed system. The heating capacity decreases by 49.88% with the increase of reinjection temperature. The space heating energy is collected from the reinjection water. The rise of reinjection temperature leads to the increase of constant-pressure specific heat. However, the increase rate of the constant-pressure specific heat is smaller than the increase rate of the difference for reinjection temperature. Thus, the heating capacity decreases with an increase of reinjection temperature.
Figure 12.
The space heating energy of the proposed system.
4. Conclusions
This work proposed a hybrid system combined dehumidification, space heating and space cooling. The humidity efficiency (), the enthalpy efficiency (), the moisture removal rate (), the coefficient of performance (COP), the cooling capacity and the heating capacity for the proposed system were analyzed. The effect of design parameters, including the desiccant concentration, air temperature and air humidity, and refrigeration temperature on the performance indicators were conducted. The conclusions are summarized as follows.
- (1)
- The increase of the desiccant concentration leads to the increase of COP, , and cooling capacity. The decreases with an increase of desiccant concentration. The increase of refrigeration temperature makes the , COP, and cooling capacity decrease and makes the increase.
- (2)
- The increase of the air humidity makes the COP, , and cooling capacity increase. For the same refrigeration temperature, the increase of segment temperature from 100 to 130 °C has a small effect on . The decrease rates of and for the segment temperature of 140 °C increase with the increase of air humidity.
- (3)
- The increase of air temperature leads to a decrease of COP, , and . As the refrigeration temperature rises, the with the same segment temperature and air temperature are almost equal. COP has the same tendency, but the and increase respectively with the cooling capacities for the segment temperature from 110 to 140 °C, which are within the range of 200 and 280 kW.
- (4)
- The heating capacity decreases by 49.88% with the reinjection temperature increasing from 70 to 80 °C.
Author Contributions
Conceptualization, investigation, writing—review and editing, and supervision, A.X.; methodology, investigation, writing—original draft, and writing—review and editing, M.X.; writing—review and editing and software, N.X.; investigation and validation, Y.X.; visualization, J.H.; investigation and software, Y.C.; supervision and writing—review and editing, Z.L.; conceptualization, project administration, S.Y. All authors have read and agreed to the published version of the manuscript.
Funding
This research was founded by the National Natural Science Foundation of China project (grant numbers: 22008265), the Research Foundation of Education Bureau of Hunan Province, China Project (grant numbers: 19B148) and College Students’ Innovative Entrepreneurial Training Plan Program (grant numbers: S202111535010).
Institutional Review Board Statement
Not applicable.
Informed Consent Statement
Not applicable.
Data Availability Statement
Not applicable.
Conflicts of Interest
The authors declare no conflict of interest.
Nomenclature
| m | mass flow rate, [kg∙s−1] |
| QL | heat duty for absorption refrigeration cycle, [kW] |
| h | enthalpy, [kJ∙kg−1] |
| x | concentration, [%] |
| QH | heat duty for liquid dehumidification cycle, [kW] |
| W | power of pump, [kW] |
| QT | heat duty consumed by the hybrid system, [kW] |
| QCW | heat duty absorbed by the cooling water, [kW] |
| A | absorption refrigeration cycle |
| D | liquid dehumidification cycle |
| a,in | inlet air |
| a,out | outlet air |
| Ts,equ | equilibrium humidity |
| C | cooling pair |
| T | total energy consumption |
| evap | evaporator |
| con | condenser |
| pump | pump |
| ARC | absorption refrigeration cycle |
| COP | coefficient of performance of the coupling system |
| LDC | liquid dehumidification cycle |
| HTGE | high-temperature geothermal energy |
| MTGE | mid-temperature geothermal energy |
| LTGE | low-temperature geothermal energy |
| ORC | organic Rankine Cycle |
| HE | humidity efficiency |
| MRR | moisture removal rate |
| EE | enthalpy efficiency |
| η | efficiency |
| ω | humidity |
Appendix A
For LiBr-H2O ARC, the main units can be classified as: four heat exchangers, four valves, two packed towers and a pump. The mathematical equations of the units can be calculated as following:
Generator:
Evaporator:
Condenser:
Absorber:
Heat exchanger:
Valves:
Pump 1:
For LiCl-H2O LDC, the main units can be classified as: a heat exchanger, two packed towers and two pumps. The mathematical equations of the units can be calculated as following:
Dehumidifier:
Regenerator:
LiCl condenser:
Pump 2:
Pump 3:
Heat exchanger:
References
- Laldjebaev, M.; Isaev, R.; Saukhimov, A. Renewable energy in Central Asia: An overview of potentials, deployment, outlook, and barriers. Energy Rep. 2021, 7, 3125–3136. [Google Scholar] [CrossRef] [Scilit]
- Askari, I.B.; Ameri, M.; Calise, F. Energy, exergy and exergo-economic analysis of different water desalination technologies powered by Linear Fresnel solar field. Desalination 2018, 425, 37–67. [Google Scholar] [CrossRef] [Scilit]
- Adedoyin, F.F.; Alola, A.A.; Bekun, F.V. The alternative energy utilization and common regional trade outlook in EU-27: Evidence from common correlated effects. Renew. Sustain. Energy Rev. 2021, 145, 111092. [Google Scholar] [CrossRef] [Scilit]
- Anderson, A.; Rezaie, B. Geothermal technology: Trends and potential role in a sustainable future. Appl. Energy 2019, 248, 18–34. [Google Scholar] [CrossRef] [Scilit]
- Dai, Y.; Liu, F.; Sui, J.; Wang, D.; Han, W.; Jin, H. Hybrid liquid desiccant air-conditioning system combined with marine aerosol removal driven by low-temperature heat source. Appl. Energy 2020, 275, 115365. [Google Scholar] [CrossRef] [Scilit]
- Ghiasirad, H.; Asgari, N.; Khoshbakhti Saray, R.; Mirmasoumi, S. Thermoeconomic assessment of a geothermal based combined cooling, heating, and power system, integrated with a humidification-dehumidification desalination unit and an absorption heat transformer. Energy Convers. Manag. 2021, 235, 113969. [Google Scholar] [CrossRef] [Scilit]
- Walraven, D.; Laenen, B.; D’Haeseleer, W. Comparison of thermodynamic cycles for power production from low-temperature geothermal heat sources. Energy Convers. Manag. 2013, 66, 220–333. [Google Scholar] [CrossRef] [Scilit]
- Shokati, N.; Ranjbar, F.; Yari, M. Exergoeconomic analysis and optimization of basic, dual-pressure and dual-fluid ORCs and Kalina geothermal power plants: A comparative study. Renew. Energy 2015, 83, 527–542. [Google Scholar] [CrossRef] [Scilit]
- Yazici, H. Energy and exergy based evaluation of the renovated Afyon geothermal district heating system. Energy Build. 2016, 127, 794–804. [Google Scholar] [CrossRef] [Scilit]
- Kanoglu, M.; Yilmaz, C.; Abusoglu, A. Geothermal energy use in absorption precooling for Claude hydrogen liquefaction cycle. Int. J. Hydrog. Energy 2016, 41, 11185–11200. [Google Scholar] [CrossRef] [Scilit]
- Ahmadi, M.H.; Mehrpooya, M.; Pourfayaz, F. Exergoeconomic analysis and multi objective optimization of performance of a Carbon dioxide power cycle driven by geothermal energy with liquefied natural gas as its heat sink. Energy Convers. Manag. 2016, 119, 422–434. [Google Scholar] [CrossRef] [Scilit]
- Xu, A.; Xu, M.; Xie, N.; Liang, J.; Zeng, K.; Kou, G. Performance analysis of a cascade lithium bromide absorption refrigeration/dehumidification process driven by low-grade waste heat for hot summer and cold winter climate area in China. Energy Convers. Manag. 2021, 228, 113664. [Google Scholar] [CrossRef] [Scilit]
- Bellos, E.; Tzivanidis, C.; Tsifis, G. Energetic, Exergetic, Economic and Environmental (4E) analysis of a solar assisted refrigeration system for various operating scenarios. Energy Convers. Manag. 2017, 148, 1055–1069. [Google Scholar] [CrossRef] [Scilit]
- Liu, Z.; Xie, N.; Yang, S. Thermodynamic and parametric analysis of a coupled LiBr/H2O absorption chiller/Kalina cycle for cascade utilization of low-grade waste heat. Energy Convers. Manag. 2020, 205, 112370. [Google Scholar] [CrossRef] [Scilit]
- Xie, N.; Liu, Z.; Luo, Z.; Ren, J.; Deng, C.; Yang, S. Multi-objective optimization and life cycle assessment of an integrated system combining LiBr/H2O absorption chiller and Kalina cycle. Energy Convers. Manag. 2020, 225, 113448. [Google Scholar] [CrossRef] [Scilit]
- Khosravi, A.; Syri, S. Modeling of Geothermal Power System Equipped with Absorption Refrigeration and Solar Energy Using Multilayer Perceptron Neural Network Optimized with Imperialist Competitive Algorithm. J. Clean. Prod. 2020, 276, 124216. [Google Scholar] [CrossRef] [Scilit]
- Gnaifaid, H.; Ozcan, H. Development and Multiobjective Optimization of an Integrated Flash-Binary Geothermal Power Plant with Reverse Osmosis Desalination and Absorption Refrigeration for Multi-Generation. Geothermics 2021, 89, 101949. [Google Scholar] [CrossRef] [Scilit]
- El Haj Assad, M.; Sadeghzadeh, M.; Ahmadi, M.H.; Al-Shabi, M.; Albawab, M.; Anvari-Moghaddam, A.; Bani Hani, E. Space Cooling Using Geothermal Single-Effect Water/Lithium Bromide Absorption Chiller. Energy Sci. Eng. 2021, 1–14. [Google Scholar] [CrossRef] [Scilit]
- Al-Hamed, K.H.M.; Dincer, I. Investigation of a Concentrated Solar-Geothermal Integrated System with a Combined Ejector-Absorption Refrigeration Cycle for a Small Community. Int. J. Refrig. 2019, 106, 407–426. [Google Scholar] [CrossRef] [Scilit]
- Ghaebi, H.; Parikhani, T.; Rostamzadeh, H. A Novel Trigeneration System Using Geothermal Heat Source and Liquefied Natural Gas Cold Energy Recovery: Energy, Exergy and Exergoeconomic Analysis. Renew. Energy 2018, 119, 513–527. [Google Scholar] [CrossRef] [Scilit]
- Qu, M.; Abdelaziz, O.; Gao, Z.; Yin, H. Isothermal membrane-based air dehumidification: A comprehensive review. Renew. Sustain. Energy Rev. 2018, 82, 4060–4069. [Google Scholar] [CrossRef] [Scilit]
- Liang, C.H.; Li, N.F.; Huang, S.M. Entropy and exergy analysis of an internally-cooled membrane liquid desiccant dehumidifier. Energy 2020, 192, 116681. [Google Scholar] [CrossRef] [Scilit]
- Su, W.; Li, H.; Sun, B.; Li, S.; Zhang, X. Performance investigation on a frost-free air source heat pump system employing liquid desiccant dehumidification and compressor-assisted regeneration based on exergy and exergoeconomic analysis. Energy Convers. Manag. 2019, 183, 167–181. [Google Scholar] [CrossRef] [Scilit]
- Zhang, L.; Song, X.; Zhang, X. Theoretical analysis of exergy destruction and exergy flow in direct contact process between humid air and water/liquid desiccant solution. Energy 2019, 187, 115976. [Google Scholar] [CrossRef] [Scilit]
- Low, E.; Huang, S.-M.; Yang, M.; Show, P.L.; Law, C.L. Design of Cascade Analysis for Renewable and Waste Heat Recovery in a Solar Thermal Regeneration Unit of a Liquid Desiccant Dehumidification System. Energy 2021, 235, 121284. [Google Scholar] [CrossRef] [Scilit]
- Guan, B.; Liu, X.; Zhang, T. Exergy analysis on optimal desiccant solution flow rate in heat exchanger for air dehumidification using liquid desiccant. Int. J. Refrig. 2021, 128, 129–138. [Google Scholar] [CrossRef] [Scilit]
- Guan, B.; Liu, X.; Zhang, T. Modification of analytical solutions of coupled heat and mass transfer processes in liquid desiccant dehumidifier for deep dehumidification. Int. J. Heat Mass Transf. 2021, 165, 120728. [Google Scholar] [CrossRef] [Scilit]
- Zhang, Q.; Liu, X.; Zhang, T.; Xie, Y. Performance optimization of a heat pump driven liquid desiccant dehumidification system using exergy analysis. Energy 2020, 204, 117891. [Google Scholar] [CrossRef] [Scilit]
- Chen, Y.; Liu, Y.; Wang, D.; Luo, X.; Liu, J.; Liu, J. Performance and optimization of a novel solar-driven liquid desiccant air conditioning system suitable for extremely hot and humid climates. Energy Convers. Manag. 2020, 215, 112899. [Google Scholar] [CrossRef] [Scilit]
- Su, W.; Zhang, X. Thermodynamic analysis of a compression-absorption refrigeration air-conditioning system coupled with liquid desiccant dehumidification. Appl. Therm. Eng. 2017, 115, 575–585. [Google Scholar] [CrossRef] [Scilit]
- Yin, Y.; Qian, J.; Zhang, X. Recent advancements in liquid desiccant dehumidification technology. Renew Sustain. Energy Rev. 2014, 31, 38–52. [Google Scholar] [CrossRef] [Scilit]
- Dai, Y.J.; Zhang, H.F. Numerical simulation and theoretical analysis of heat and mass transfer in a cross flow liquid desiccant air dehumidifier packed with honeycomb paper. Energy Convers. Manag. 2004, 45, 1343–1356. [Google Scholar] [CrossRef] [Scilit]
- Martin, V.; Goswami, D.Y. Effectiveness of heat and mass transfer processes in a packed bed liquid desiccant dehumidifier/regenerator. ASHRAE Trans. 2000, 106, 20–39. [Google Scholar] [CrossRef] [Scilit]
- Gandhidasan, P. A simplified model for air dehumidification with liquid desiccant. Sol. Energy 2004, 76, 409–416. [Google Scholar] [CrossRef] [Scilit]
- Xu, A.; Xu, M.; Wang, Z.; Li, Y.; Chen, H.; Zeng, K. Energy, Exergy, and Economic Analysis and Multiobjective Optimization of a Cascade Coupling System Driven by Low-Grade Waste Heat in Hot Summer and Cold Winter Areas of China. ACS Sustain. Chem. Eng. 2021. [Google Scholar] [CrossRef] [Scilit]
- Liu, J.; Liu, X.; Zhang, T. Analytical solution of heat and mass transfer process in internally cooled liquid desiccant dehumidifiers using refrigerant as cooling medium. Energy Build. 2019, 190, 1–14. [Google Scholar] [CrossRef] [Scilit]
- Cui, P.; Yu, M.; Liu, Z.; Zhu, Z.; Yang, S. Energy, exergy, and economic (3E) analyses and multi-objective optimization of a cascade absorption refrigeration system for low-grade waste heat recovery. Energy Convers. Manag. 2019, 184, 249–261. [Google Scholar] [CrossRef] [Scilit]
- Kabeel, A.E.; Abdelgaied, M.; Zakaria, Y. Performance evaluation of a solar energy assisted hybrid desiccant air conditioner integrated with HDH desalination system. Energy Convers. Manag. 2017, 150, 382–391. [Google Scholar] [CrossRef] [Scilit]
- Alirahmi, S.M.; Assareh, E. Energy, exergy, and exergoeconomics (3E) analysis and multi-objective optimization of a multi-generation energy system for day and night time power generation—Case study: Dezful city. Int. J. Hydrog. Energy 2020, 45, 31555–31573. [Google Scholar] [CrossRef] [Scilit]
- Ren, C.Q.; Tu, M.; Wang, H.H. An analytical model for heat and mass transfer processes in internally cooled or heated liquid desiccant-air contact units. Int. J. Heat Mass Transf. 2007, 50, 3545–3555. [Google Scholar] [CrossRef] [Scilit]
- Huang, X.; Liu, W.; Yu, X.; Ke, T.; Ling, X.; Li, Y. Thermodynamic analysis of a two-stage humidification–dehumidification system with reflux configuration. Energy Convers. Manag. 2019, 197, 111872. [Google Scholar] [CrossRef] [Scilit]
- He, W.; Yang, H.; Wen, T.; Han, D. Thermodynamic and economic investigation of a humidification dehumidification desalination system driven by low grade waste heat. Energy Conv. Manag 2019, 183, 848–858. [Google Scholar] [CrossRef] [Scilit]
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations. |
© 2021 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).