Four-Coil Wireless Power Transfer for High-Voltage Transmission Line Sensors with Numerical Assessment of Environmental Electric Fields

,
,
and
1
School of Electrical and Electronic Engineering, North China Electric Power University, Beijing 102206, China
2
School of Electrical Engineering, Southeast University, Nanjing 210096, China
*
Author to whom correspondence should be addressed.
This article belongs to the Section Electronic Sensors

Abstract

The coil separation imposed by high-voltage insulation requirements limits magnetic coupling and complicates efficient wireless power delivery to transmission line sensors. To address this problem, this study proposes a four-coil resonant wireless power transfer system arranged along a composite insulator. Two intermediate relay coils provide successive coupling stages, while spiral coils wound with Litz wire are selected to limit high-frequency winding losses. A series–series compensated equivalent circuit and field–circuit simulations evaluate power transfer within the prescribed mounting geometry. At 460 kHz, the implemented spiral-coil model yielded a simulated efficiency of 88.71%. Electric field analyses under wind deflection, icing, and meltwater conditions, together with an angular-misalignment analysis, identify local field intensification and coupling degradation as design considerations. A low-voltage prototype built on a 1.5 m composite insulator delivers 100.28–158.20 W at three laboratory operating points, demonstrating power transfer in the selected mounting arrangement.

1. Introduction

Transmission line sensors provide weather, icing, and structural information needed to monitor high-voltage infrastructure [1]. Their usefulness depends on a power supply that can operate at distributed outdoor locations. Battery maintenance and the weather dependence of solar generation complicate this task [2]. Conductor-side current-transformer (CT) harvesters provide another energy source, but supplying tower-side monitoring equipment requires power delivery across the insulation distance. Wireless power transfer (WPT) offers a contactless route for this purpose [3,4,5,6] and could complement conductor-side harvesting where the source and load are separated by the insulator. Solar supplies remain an alternative, depending on the installation conditions. For the insulator-mounted WPT link considered here, the design problem is therefore to obtain useful power transfer within the available mounting geometry while evaluating how the added coils affect the surrounding electric field.
Resonant relay coils can divide an extended transfer path into successive coupling stages [7,8,9]. For an insulator-mounted system, however, coil number and position are constrained by the available space. Once the arrangement is specified, its performance depends on the electrical parameters of the coils, their coupling, and the compensation network. Previous studies have investigated mutual-inductance modeling and WPT operating conditions [3,10,11,12,13,14], impedance matching [15], coil geometry optimization [16,17], and compensation parameter selection [18]. Research on charging systems further illustrates the importance of topology and circuit design [19,20,21,22]. These studies provide tools for evaluating an installation-specific configuration; they do not remove the need to establish the physical and electrical conditions of that configuration.
The choice of winding is one part of this design problem. High-frequency conductor losses and winding geometry affect the coil parameters used in circuit analysis. Finite-element evaluation of WPT coils, printed circuit board coil design, and inductive-coil optimization have been investigated [23,24,25]. Coil resistance and load resistance also influence power and efficiency [26,27]. A comparison between winding configurations must therefore establish how geometry, material representation, compensation, and losses differ. A change in predicted efficiency alone does not identify which of these factors produced the difference.
The high-voltage installation introduces a second set of questions concerning the electric field around the insulator. WPT has been investigated for 110 kV transmission line monitoring equipment [28], and displacement and rotation tolerance have been studied in other coil configurations [29,30]. For misalignment sensing, Chen et al. combined orientation-sensitive detection coils with an improved ResNet to recognize longitudinal, lateral, and yaw misalignments in wireless electric vehicle charging systems [31]. In the present installation, wind-induced deflection, ice accretion, and meltwater films motivate evaluation of both field distributions and coupling sensitivity. Electrical characteristics of resonant coils provide the basis for the latter assessment [32]. Power-transfer performance and insulation-related field response are distinct outputs: a favorable nominal efficiency does not by itself establish performance under changing environmental conditions.
This study examines whether a four-coil resonant link can deliver power in the mounting geometry of a 110 kV composite insulator and how the selected arrangement responds in the investigated environmental models. The work connects installation constraints to an equivalent circuit, compares the implemented simplified and spiral-coil configurations, and evaluates the spiral arrangement through electric field analyses and laboratory measurements. Its contribution is the assessment of a specific insulator-mounted WPT design across these complementary forms of evidence. The circuit model explains the quantities relevant to design, simulations characterize the selected configurations, and the prototype tests power-delivery feasibility. This scope distinguishes laboratory power transfer from experimental validation of high-voltage or adverse-weather operation.
Building on existing WPT systems for transmission line monitoring [7,8,28], this study evaluates a four-coil arrangement mounted along a composite insulator. Its focus is the assessment of the selected configuration through circuit modeling, low-voltage bench tests, and numerical analyses of wind deflection, icing, and meltwater conditions. The contribution concerns this installation-specific assessment. Figure 1 summarizes the study workflow, from installation constraints and circuit design to coil-model comparison, environmental assessment, and prototype measurements. Laboratory measurements evaluate power delivery, while environmental calculations characterize electric field response and coupling sensitivity.
Figure 1. Overall workflow of the four-coil WPT study.

2. Design Requirements and System Modeling

2.1. Installation Geometry and Evaluation Requirements

The proposed link follows the axis of a composite insulator used for 110 kV transmission line equipment. The conductor is located at the high-voltage end, whereas the monitoring load is placed toward the tower-side, low-voltage end. The insulator geometry limits where the coils can be mounted and imposes a substantial separation between the ends of the link. The design is evaluated using output power and transfer efficiency, together with the electric field distributions produced by the installed coils. These quantities address power delivery and field response without assuming that either one alone establishes service suitability.
An FXBW-110 composite insulator with an overall length of 1.5 m was selected. A transmitting coil and receiving coil are located near the first and last large sheds, respectively, with two relay coils distributed between them. The specified adjacent-coil spacing is approximately 0.327 m. The arrangement follows the available installation geometry, as illustrated in Figure 2. The overall insulator length and the transmitter–receiver separation are distinct dimensions. The insulator sheds provide the surface creepage path and influence wetting and water drainage. Practical integration of the WPT coils requires mounting arrangements that preserve the required creepage distance and air clearances without bridging sheds or damaging the insulating housing. The insulation and mechanical performance of the complete assembly require further validation before field deployment.
Figure 2. Composite insulator and installation of the simplified coils.
The four-coil layout is the installation configuration evaluated in this work. The coil count and mounting locations remain fixed in the configuration comparison. Because an alternative coil-count study is not presented, the four-coil arrangement is treated as a design choice rather than an established optimum. Its power-transfer response is evaluated through the circuit model, and its effect on the electric field is assessed using separate models of the surrounding insulator.
The four-coil arrangement was selected to divide the available transfer span into three coupling stages using two intermediate relays. This reduces the adjacent-coil spacing compared with equally spaced two- and three-coil arrangements over the same span. However, additional relays introduce winding losses and compensation requirements. Since a controlled coil-count comparison has not been performed, four coils are treated as an implementation choice rather than an established optimum.

2.2. Resonant Circuit and Power Transfer Model

With the mounting arrangement specified, an equivalent circuit is required to connect coil parameters to power delivery. The transmitting coil, two relay coils, and receiving coil form a resonant link along the insulator. The general multi-coil formulation below describes the electrical response of this arrangement and provides the basis for the four-coil calculations.
Series–series (SS) compensation was adopted so that each coil loop could be compensated at the selected operating frequency. It provides a common circuit topology for the two coil configurations considered here. Alternative series–parallel (SP), parallel–series (PS), and parallel–parallel (PP) arrangements are not compared in this study. Under the assumed resonant conditions, compensation reduces the reactive component of the loop impedances. Figure 3 shows the high-frequency source, coil loops, compensation capacitors, and equivalent load. The two relay coils occupy the intermediate positions defined by the installation geometry.
Figure 3. Equivalent circuit of the multi-coil WPT system.
Here, L i ( i = 1, 2, …, n), C i ( i = 1, 2, …, n), and R i ( i = 1, 2, …, n) denote the self-inductance, series compensation capacitance, and loss resistance of each coil, respectively. The inverter equivalent resistance R s is included in the transmitting-loop impedance together with R 1 . The equivalent load resistance R L is referred to the rectifier input, M i j ( i , j = 1, 2, …, n) denotes the mutual inductance between two coils, and U s is the fundamental component of the inverter output voltage.
Applying Kirchhoff’s voltage law gives the system impedance equation:
Z 1 j ω M 12 … j ω M 1 n j ω M 21 Z 2 … j ω M 2 n ⋮ ⋮ ⋱ ⋮ j ω M n 1 j ω M n 2 … Z n + R L I ˙ 1 I ˙ 2 ⋮ I ˙ n = U ˙ s 0 ⋮ 0
The off-diagonal entry is j ω M i j for every i ≠ j, including non-adjacent coil pairs. For the four-coil system, the formulation therefore includes M13, M14, and M24, in addition to the adjacent-coil mutual inductances.
Z 1 = R 1 + R S + j ω L 1 + 1 j ω C 1
Z i = R i + j ω L i + 1 j ω C i ( i = 2 , 3 , … , n )
The angular frequency of the source is ω = 2 π f . The coil currents can be obtained using Cramer’s rule:
D i = Z 1 j ω M 12 … U ˙ s … j ω M 1 n j ω M 21 Z 2 … 0 … j ω M 2 n ⋮ ⋮ ⋮ ⋮ ⋮ ⋮ j ω M n 1 j ω M n 2 … 0 … Z n + R L
D = Z 1 j ω M 12 … j ω M 1 n j ω M 21 Z 2 … j ω M 2 n ⋮ ⋮ ⋱ ⋮ j ω M n 1 j ω M n 2 … Z n + R L
I i = D i D
In these expressions, D i denotes the determinant of the corresponding matrix. Considering the active power delivered to the load and the resistive losses, the input power P i n , output power P o , and transfer efficiency η are expressed as follows:
P o = I n 2 R L
P i n = I 1 2 ( R S + R 1 ) + I 2 2 R 2 + … + I n 2 ( R n + R L )
η = P o P i n × 100 %
The circuit model relates the design choices to measurable performance. Coil geometry and conductor properties enter through self-inductance L i and loss resistance R i , while the compensation capacitance C i is selected for the operating angular frequency ω . Mutual inductance M i j links the geometry and relative positions of the coils to energy transfer between loops. The coil count n sets the number of coupled stages. For the selected four-coil arrangement, these relationships motivate evaluation of the winding configuration while retaining the specified mounting positions. The circuit expressions quantify power transfer; the electric field around the insulator is evaluated separately in Section 4.

3. Coil Configurations and Power Transfer Performance

The comparison in this section examines how the implemented coil configurations behave within the installation described in Section 2. A simplified polygonal configuration and a spiral configuration wound with Litz wire are evaluated with the four-coil topology and a nominal operating frequency of 460 kHz. The sequence establishes each configuration and its circuit parameters, compares the calculated power-transfer outputs, and then examines the associated electric field distribution. Interpretation of the difference depends on both the physical winding and its representation in the model.

3.1. Simplified Coil Configuration

The simplified configuration provides an initial representation of the four-coil link. Its polygonal geometry reduces the detail required in the field model and defines the first configuration used for the performance comparison. Figure 4 shows its geometry and spacing.
Figure 4. Geometry and spacing of the simplified coils.
Circular coils were approximated by polygonal structures, with strand twisting and detailed turn geometry omitted. The field–circuit model represented the coils through their equivalent self-inductance, resistance, and mutual inductance. Dimensions and spacing were specified according to the selected installation. The operating frequency was 460 kHz, and series capacitors were assigned to compensate for the coil reactances. Table 1 lists the reported geometric and electrical parameters.
Table 1. Parameters of the simplified coil model.
For the uniformly spaced four-coil arrangement, the separation is defined by
d 12 = d 23 = d 34 = d − 4 h 3
where d denotes the total axial separation between the transmitting coil L1 and the receiving coil L4, h is the axial thickness of each individual coil, and d12, d23, and d23 represent the axial spacings between adjacent coils, as illustrated in Figure 4. In this study, the total coil separation is set to d = 1 m and the coil thickness is h = 4.75 mm, yielding a uniform adjacent-coil spacing of d12 = d23 = d23 ≈ 327 mm.
The self-inductances were calculated using the AC magnetic (eddy-current) solver in ANSYS (Ansys Electronics Desktop 2025 R1) Maxwell 3D at 460 kHz. Each coil was excited individually with a current of 1 A, while the currents in the other coils were set to zero. The diagonal entries of the resulting inductance matrix were taken as the self-inductances L1–L4. The calculated values and the corresponding geometric and electrical parameters are summarized in Table 1.
For reference, Table 3 in Section 3.2 summarizes independent mutual-inductance estimates obtained using Neumann’s integral for idealized five-turn circular coils. These estimates describe the specified idealized geometry and are not verified coupling parameters of the simplified field–circuit model. A coupled coil–circuit simulation model was constructed to calculate input power, output power, and transfer efficiency. The simulation circuit is shown in Figure 5.
Figure 5. Field–circuit simulation configuration for the simplified-coil WPT system.
The simplified configuration yielded an output power of 18.18 W and a transfer efficiency of 26.36% under the simulated conditions. These values establish its calculated operating point for comparison with the spiral configuration. Figure 6 shows the instantaneous input power at the inverter DC terminals and the output power delivered to the load. Negative input-power intervals indicate temporary energy return to the input side. Transfer efficiency is evaluated using steady-state average input and output powers.
Figure 6. Simulated input and output power waveforms for the simplified-coil system.
Electric field calculations were performed in ElecNet to characterize the insulator with this coil configuration. Figure 7 shows the field and potential distributions. The reported peak electric field strength was approximately 2.245 × 106 V/m. This result provides the configuration-specific reference for the later field comparison; it is distinct from the power-transfer calculation. The field contours use a global linear color scale. The lowest blue band represents a range of field magnitudes rather than a uniquely zero value.
Figure 7. Electric field strength and potential distributions for the simplified-coil arrangement.
The limited power-transfer efficiency predicted for this configuration motivates examination of the spiral winding. The comparison considers the implemented configurations as a whole, since changing the winding geometry and its representation can also change the equivalent parameters supplied to the circuit model.

3.2. Spiral Coil Configuration

A circular spiral winding made from Litz wire was selected for the second configuration. The conductor consists of multiple fine strands and was chosen with the aim of reducing high-frequency conductor losses. The distributed turns also alter the winding geometry represented in the electromagnetic model. These are the design motivations; their separate contributions to the calculated efficiency require resistance and coupling data beyond the aggregate power comparison.
The spiral coils have an outer diameter of 30 cm, five turns, a specified turn spacing of 9 mm, and an equivalent conductor diameter of 5 mm. Adjacent-coil spacing remains 0.327 m. Self-inductances were extracted from finite-element calculations, and series compensation was selected for operation at 460 kHz. Figure 8 shows the coil positions, and Table 2 lists the parameters used for this configuration.
Figure 8. Positions of the circular spiral Litz wire coils.
Table 2. Parameters of the circular spiral coil model.
Figure 8 and Figure 9 illustrate the geometric positions and installation of the Litz wire spiral coils on the composite insulator. Consistent with the notation defined in Figure 4 and Equation (10), d denotes the fixed axial separation between the transmitting coil L1 and receiving coil L4, h is the axial coil thickness, and d12, d23, and d34 are the spacings between adjacent coils (L1–L2, L2–L3, and L3–L4, respectively).
Figure 9. Composite insulator and installation of the Litz wire coils.
An independent coupling estimate was obtained using Neumann’s integral under an air-core filament approximation. Each winding was represented by five coincident circular turns of radius 150 mm. The adjacent center-to-center spacing was 331.75 mm, corresponding to a face clearance of 327 mm and a winding thickness of 4.75 mm. Finite winding dimensions, leads, nearby metal components, and capacitive effects were excluded. The estimated mutual inductances for all six coil pairs in the idealized four-coil arrangement are summarized in Table 3, including the non-adjacent couplings M13, M14, and M24. These values are theoretical estimates for the specified geometry, rather than measured prototype parameters.
Table 3. Idealized mutual-inductance estimates for the four-coil arrangement.

3.3. Comparison of the Implemented Configurations

The two configurations use the four-coil topology, the same specified mounting positions, and the reported load resistance of 6 Ω. Each field–circuit model supplies the electrical response of its corresponding coil representation. Figure 10 shows the spiral-coil simulation circuit. The comparison evaluates these implemented models; equivalence of their conductor-loss representations is not established by matching topology and load alone. The simulated efficiency is evaluated using the steady-state average input power at WM1, upstream of the inverter, and the output power at WM2, delivered to the load after rectification and filtering. This boundary includes the modeled inverter, compensated coil link, and rectifier. A separate voltage-regulation stage is not included in Figure 10.
Figure 10. Field–circuit simulation configuration for the Litz wire coil system.
The implemented spiral-coil model yielded an output power of 64.14 W and an efficiency of 88.71% (Figure 11). The outputs of both implemented models are summarized in Table 4. These are model-specific results and do not establish a performance improvement attributable to coil geometry or Litz wire, because consistent conductor-loss representations and corresponding AC resistance and mutual-inductance values have not been established.
Figure 11. Simulated input and output power waveforms for the Litz wire coil system.
Table 4. Calculated outputs of the two implemented coil configurations.
The spiral configuration was also evaluated using the electric field model to determine whether its favorable calculated power-transfer result was accompanied by a higher peak field around the insulator. Figure 12 shows the resulting distributions.
Figure 12. Electric field strength and potential distributions for the Litz wire coil arrangement.
The reported peak field for the spiral configuration was approximately 1.192 × 106 V/m, compared with 2.245 × 106 V/m for the simplified configuration. Thus, the higher simulated efficiency was accompanied by a lower calculated peak field in this comparison. Table 4 summarizes the configuration-level results. The comparison supports examining the spiral arrangement further, while the role of physical winding changes and modeling assumptions remains to be resolved.
Values characterize the implemented models; the contribution of physical winding changes has not been isolated.
The spiral configuration was carried forward to the environmental assessment and prototype evaluation. These analyses ask whether the nominal-condition result is sufficient to describe the intended application. Section 4 examines field distributions and coupling sensitivity under the specified environmental models, and Section 5 tests power delivery in a laboratory implementation.

4. Electric Field and Environmental Response

The spiral arrangement introduces conductive coils into the electric field environment of the insulator. Its evaluation therefore extends beyond the nominal power-transfer result. Applied-voltage analyses first examine the field distribution with and without coils. Wind-related analyses then consider changes in insulator orientation and, separately, relative coil angle. Ice and water-film models examine changes near the shed edges. These models describe specific field and coupling responses; their outputs are interpreted according to the quantity calculated in each case. ElecNet was used for the electric field calculations of the nominal coil configurations in Section 3. ANSYS Maxwell was selected for the environmental assessment in this section to organize the models with different coil orientations, ice geometries, and water-film thicknesses within a common modeling and post-processing workflow.

4.1. Electric Field Under Nominal and Elevated Voltages

Electric field models were evaluated for nominal system voltage levels of 110, 220, and 500 kV. For the 110 kV case, the phase-to-ground voltage is 63.5 kV RMS, corresponding to a peak value of 89.8 kV. The appropriate potential difference was applied between the high- and low-voltage fittings to compare configurations with and without WPT coils.
With and without coils, the strongest fields occurred near the insulator end fittings and grading rings, while the central region exhibited more gradual variation (Figure 13). The maximum field with coils was approximately 1.21 × 106 V/m. The principal observation is that the added coils did not change the locations of the dominant end-region fields in this modeled case. The reference-field comparison is used as a numerical screening measure.
Figure 13. Electric field distributions at nominal voltage: (a) with coils; (b) without coils.
The applied voltage was then increased to 1.15 per unit to examine how the modeled field changed at an elevated voltage. The maximum field with coils increased to approximately 1.39 × 106 V/m (Figure 14).
Figure 14. Electric field distributions at 1.15 per unit voltage: (a) with coils; (b) without coils.
Models of 110, 220, and 500 kV installations were additionally evaluated in ANSYS (Figure 15). Their calculated maximum fields remained below the adopted reference in the investigated configurations. These results extend the field assessment to the represented geometries and applied voltages. They do not extend the power-transfer or prototype results to all three voltage classes.
Figure 15. Electric field distributions in the modeled 110, 220, and 500 kV configurations.
The field calculations represent the applied transmission line voltage; the 460 kHz operating voltages of the WPT coils were not imposed. The results therefore describe the field distribution under the specified external-voltage conditions and do not represent the complete insulation stress during energized WPT operation.

4.2. Wind-Induced Deflection

Wind-induced deflection changes the orientation and surrounding clearances of the insulator assembly. Electric field models were therefore evaluated at wind speeds of 10, 20, and 30 m/s. The corresponding deflection angles from the mechanical model are listed in Table 5. Relative rotation between individual coils is considered separately because an assembly deflection angle does not, by itself, specify their angular misalignment.
Table 5. Wind speeds and corresponding insulator deflection angles.
The wind-deflection analysis used the four-coil arrangement on the 1.5 m composite insulator for the 110 kV system. The receiver was located at the low-voltage end near the tower, the transmitter at the high-voltage conductor end, and the relays between them. In the ANSYS Maxwell models, the insulator moved with the conductor and the coils followed the local insulator orientation. Figure 16 shows the geometries at the three wind speeds.
Figure 16. Insulator configurations under different wind speeds.
The geometric change under wind loading can alter air gaps on the inward-bending side of the assembly. The first wind-related assessment therefore extracts the electric field along the insulator surface path to examine where field concentrations change.
A second assessment considers the mutual inductance of two coils at different relative angles. This calculation quantifies sensitivity to angular misalignment. Relating it to a particular wind speed requires the local coil orientations from an appropriate mechanical model.

4.2.1. Electric Field Under Wind-Induced Deflection

Voltage boundary conditions were applied to the fittings at both ends of the insulator. The measurement path followed the shed edges on the inward-bending side. Electric field strength along this path was extracted for wind speeds of 0, 10, 20, and 30 m/s, as shown in Figure 17.
Figure 17. Electric field strength along the shed-edge measurement path under different wind speeds. The vertical quantity is electric field strength in V/m; the horizontal quantity is distance in m.
The extracted field remained concentrated near the insulator ends. Deflection changed the sampled path and the end-region peaks, whereas the middle region retained lower values. The comparison therefore identifies the end regions as important locations for examining the effect of the modeled deflection.
At 30 m/s, the reported maximum along the measurement path was 5.53 × 105 V/m, approximately 13.5% above the no-wind value. The sampled field remained below the adopted reference, Eair = 3 × 106 V/m. This is a result for the specified extraction path, which should be distinguished from a maximum over the entire computational domain.

4.2.2. Magnetic Coupling Under Angular Misalignment

To examine the sensitivity of magnetic coupling to relative coil rotation, a simplified model of two adjacent coils was considered (Figure 18). This pairwise analysis isolates angular misalignment from the overall motion of the insulator assembly.
Figure 18. Geometric model of angular misalignment between two coils.
In Figure 18, the z and z′ axes are normal to the transmitting and receiving coils, respectively, and α is the relative angle between them. The distance between the coil centers O1 and O2 is d. The turn counts are n1 and n2, and the radii are r1 and r2. The differential conductor elements dl1 and dl2 lie on the respective coil circumferences l1 and l2 and are separated by Rl. The angular coordinates are θ and φ. For coils with an axial center-to-center displacement and nonparallel planes, the geometric relations are written as
d l 1 = r 1 ( cos θ − sin θ ) d θ d l 2 = ( sin φ sin α + r 2 cos φ − r 2 sin φ cos α ) d φ
R l = r 1 2 + r 2 2 + d 2 − 2 d r 2 cos φ sin α − 2 r 1 r 2 ( cos θ cos φ cos α + sin θ sin φ )
The mutual inductance is then expressed as
M = μ 0 n 1 n 2 4 π ∮ ∮ d l 1 d l 2 R l = μ 0 n 1 n 2 4 π ∫ 0 2 π ∫ 0 2 π r 1 r 2 ( cos θ cos φ + sin θ sin φ cos α ) d θ d φ R l
As the receiving coil rotates, its effective projected area relative to the incident magnetic flux decreases, tending to reduce flux linkage. The angular dependence was evaluated using the design parameters d = 32.7 cm, n1 = n2 = 5, and r1 = r2 = 15 cm. Figure 19 shows the finite-element model and the calculated mutual-inductance curve.
Figure 19. Mutual inductance under angular misalignment: (a) coil model; (b) mutual inductance M in μH versus misalignment angle α in degrees.
The angular-misalignment estimate used five-turn circular windings with radii of 150 mm and a center-to-center separation of 331.75 mm. The coil centers remained fixed while one winding was tilted. Under this idealized geometry, the calculated mutual inductance was approximately 0.426 μH at 0° and approached zero at 90°.
Mutual inductance decreased as the relative angle increased and fell below 1 u H above approximately 80°. This establishes coupling sensitivity within the two-coil calculation. Figure 20 shows the associated magnetic flux-density distributions at 0°, 20°, 40°, and 60°. Applying this trend to the full four-coil system would require the relative orientations of all coils and the corresponding mutual-inductance matrix. The curve alone therefore does not determine the transfer efficiency at a specified wind speed.
Figure 20. Magnetic flux-density distributions under angular misalignment of (a) 0°, (b) 20°, (c) 40°, and (d) 60°.
The angular analysis characterizes the mutual-inductance sensitivity of an idealized two-coil configuration. It does not determine the efficiency of the complete four-coil system. Furthermore, the overall insulator deflection angle does not directly specify the relative angles between individual coils.

4.3. Ice Accretion and Meltwater Films

Ice and meltwater modify the geometry and electrical properties around the insulator sheds. The analyses distinguish icicle length from water-film thickness so that the resulting electric field changes can be associated with the specified model parameter. The comparison between configurations with and without coils evaluates the contribution of coil installation to each modeled field distribution.

4.3.1. Effect of Icicle Length

Ice can accumulate on the sheds, while runoff may refreeze into pendant icicles and alter the surface-potential distribution. The model used a spacing of 96.4 mm between adjacent large sheds. Ice thickness on the upper shed surfaces was set to 10 mm, and ice on the lower surfaces was neglected. Icicle length T was varied to represent increasing ice severity. The icing classification used here associates short icicles of approximately 10–30 mm with light icing and lengths of approximately 30–70 mm with moderate icing; severe icing approaches the shed spacing. Representative lengths of 30, 70, and 80 mm were selected. For comparison, uniform ice was applied on only one side of the large sheds. Electric field strength E and potential U were extracted along the measurement path. The first eight iced large sheds near the high-voltage end were selected because this region exhibits the strongest fields and the most pronounced potential changes. Figure 21 shows the geometry and the calculated distributions.
Figure 21. Effect of icicle length: (a) model and measurement path, with an upper-surface ice thickness of 10 mm and icicle length T; (b) electric field strength; (c) potential along the shed-edge path.
Increasing icicle length narrowed the gaps between neighboring icicles and produced stronger field concentrations along the measurement path. The steeper local potential changes and higher field peaks identify the remaining air gaps as the locations most affected in these calculations.
For T = 30 mm, the configurations with and without coils differed little. At T = 70 mm, the field in an air gap near the high-voltage end decreased from 3.43 × 105 V/m without coils to 3.08 × 105 V/m with coils, a reduction of 10.2%. At T = 80 mm, the minimum gap was 6.5 mm, and the corresponding field decreased from 7.31 × 105 to 6.68 × 105 V/m, a reduction of 8.6%. Thus, the coils reduced the selected local field values in these dry-ice models, even as longer icicles increased field concentration. Figure 22 compares the field contours for T = 30 and 70 mm. These results concern local field redistribution under the specified ice geometry.
Figure 22. Electric field distributions for icicle lengths of (a) 30 mm and (b) 70 mm.

4.3.2. Effect of Meltwater Film Thickness

During melting, increasing ambient temperature and surface leakage current can produce a conductive water film over the ice. Such a film can alter the surface field and increase flashover susceptibility. An iced-insulator model with a 10 mm upper-surface ice layer and an icicle length of T = 80 mm was used. The ice-layer thickness and icicle length were held constant while water-film thicknesses of t = 0, 1, and 2 mm were considered. Figure 23 shows the model and the dependence of the measurement-path electric field E w f on film thickness t .
Figure 23. Effect of water-film thickness: insulator model and electric field distribution along the measurement path. The model labels identify the measurement path and water-film thickness t.
At the fixed icicle length of T = 80 mm, the electric field strength in the air gaps increased with water-film thickness. With t = 0 mm, the two coil-installation cases differed little. At t = 1 mm, the field in the first air gap near the high-voltage end decreased from 1.05 × 106 V/m without coils to 9.19 × 105 V/m with coils, a reduction of 12.48%. At t = 2 mm, it decreased from 2.15 × 106 to 1.99 × 106 V/m, a reduction of approximately 7.4%. The comparison reveals two simultaneous effects: coil installation reduced the selected local field relative to the case without coils, whereas increasing film thickness raised the field within each case. The lower value with coils therefore does not eliminate the sensitivity to meltwater films.

5. Prototype Evaluation

A laboratory prototype was constructed to determine whether the spiral-coil arrangement could deliver power in the selected installation geometry. The prototype used an FXBW-110 composite-insulator support and the four-coil layout developed above. Figure 24 shows the platform. This test addresses physical implementation and power delivery, complementing the configuration and environmental calculations.
Figure 24. Laboratory prototype of the four-coil WPT system.
The prototype comprises a high-frequency inverter, a transmitting coil, two relay coils, a receiving coil, resonant compensation capacitors, a rectification and voltage-regulation module, and a load. SS compensation was used, and the coils were wound with Litz wire according to the spiral geometry described above.
The transmitter was placed on the side representing the conductor end, with the relays along the insulator and the receiver at the load end. The assembly reproduces the mounting arrangement considered for the 110 kV application. The measurements presented here characterize the laboratory power-transfer link; energized high-voltage insulation testing is outside this experimental dataset.
Input and output voltages and currents were recorded using a power analyzer and an oscilloscope. The reported procedure repeated measurements under each operating condition and used averages to calculate performance. Load resistance and operating frequency were adjusted during evaluation. Table 6 gives the available input power, output power, and efficiency values for three operating points. These records characterize the demonstrated operating points rather than a continuous efficiency–load response.
Table 6. Reported experimental measurements of the WPT prototype.
The experimental input power was measured at the DC supply terminals upstream of the inverter. The output power was measured at the load after the voltage-regulation module. The reported experimental efficiency therefore includes the inverter, compensated coil link, rectifier, and voltage-regulation stage.
The prototype delivered output powers of 100.28, 106.95, and 158.20 W, with reported efficiencies of 61.15%, 60.59%, and 60.00%, respectively. The measurements demonstrate power transfer through the implemented four-coil link. All three reported efficiencies were below the spiral-configuration simulation result of 88.71%.
The reported efficiency values differ from the simulation by 27.56–28.71 percentage points. Since the measured output powers also differ from the simulated 64.14 W, these records do not establish agreement at a common operating point. Their immediate contribution is evidence of laboratory power delivery. The model interpretation and the measurements needed for quantitative validation are discussed in Section 6.

6. Discussion

6.1. Interpretation of the Coil Configuration Comparison

The main design result is the implementation of a four-coil power-transfer link within the selected insulator mounting arrangement. The spiral configuration combines a favorable simulated operating point with demonstrated laboratory power delivery. The accompanying field calculations place that nominal result in its intended installation context. Together, these assessments provide a basis for further development of this configuration, although they do not yet identify an optimal winding or establish service performance.
The 62.35-percentage-point efficiency difference between the two coil models must be interpreted at the level of the implemented configurations. The simplified model omits winding detail, whereas the spiral model specifies turns and a Litz wire conductor. The present comparison does not separate a physical winding improvement from differences in geometric or conductor-loss representation. The use of the same nominal frequency, load, and relay positions is necessary for comparison, but it does not establish equivalence of all model assumptions. A controlled comparison should identify the actual baseline winding and use consistent loss representations before assigning the full efficiency difference to a design change.
The circuit formulation indicates where such an explanation should be sought; coil resistance determines dissipation, mutual inductance describes magnetic coupling, and compensation affects the operating point. The aggregate power results do not quantify their individual contributions. Measurements or consistently modeled values of AC resistance and mutual inductance would distinguish conductor-loss effects from geometry and tuning effects. This distinction is especially important when the claimed benefit is attributed to the use of Litz wire.

6.2. Experimental Validation and Sensor Power Requirements

The prototype delivered 100.28–158.20 W through the fabricated four-coil link, demonstrating laboratory power delivery in the selected mounting arrangement. These bench tests complement the numerical study by evaluating the physical windings together with the power conversion circuitry. The simulation and experiment were conducted at different operating points, and the experimental efficiency also includes an additional voltage-regulation stage. These differences should be considered when comparing the efficiencies and interpreting the total losses.
Based on the input and output powers in Table 5, the total losses at Tests 1 and 3 were 63.72 W and 105.92 W, respectively. Potential contributors include inverter conduction and switching losses, AC winding losses, compensation-capacitor losses, rectification and regulation losses, and interconnection losses. These contributions were not measured separately, so their individual values and relative importance cannot be determined from the available data. A quantitative explanation of the efficiency difference requires component-level loss measurements and simulations at matched operating points.
For the intended sensor application, output power alone is insufficient to establish load suitability. The prototype was evaluated using a load rather than an identified sensor installation with documented power demand. Relating the demonstrated output to a particular monitoring device requires its voltage and power requirements, operating duty, and regulation needs. The present result therefore concerns power-transfer capability in the investigated arrangement.

6.3. Meaning and Limits of the Environmental Assessment

The environmental models show why nominal power-transfer efficiency and installation response require separate evaluation. Increasing relative coil angle reduced mutual inductance in the pairwise model, whereas increasing meltwater-film thickness raised local electric fields in the ice model. These results identify different quantities relevant to subsequent design: coupling depends on relative coil geometry, while the electric field assessment depends on the modeled insulator geometry, applied voltage, and surface conditions.
The wind-deflection and angular-misalignment calculations do not provide an efficiency–angle or efficiency–wind-speed relationship. The overall insulator deflection angle does not directly specify the relative orientations of individual coils. Quantifying power-transfer performance requires the position and orientation of each coil under wind loading. The corresponding mutual-inductance matrix must then be calculated and incorporated into the compensated circuit model. Similarly, the modeled ice and water-film field changes do not quantify power-transfer efficiency or demonstrate flashover withstand.
The electric field assessment does not establish insulation withstand under wet or iced conditions. The calculations also exclude the 460 kHz operating voltages of the coils, and mesh convergence and parameter uncertainty have not been quantified. Accordingly, the local field differences between configurations are not interpreted as evidence of improved insulation performance. Further assessment requires the operating coil potentials, numerical convergence and sensitivity studies, and insulation testing under representative environmental conditions.

7. Conclusions

This study addressed the difficulty of wireless power delivery across the coil separation imposed by high-voltage insulation requirements by developing a four-coil resonant link along a composite insulator. Two relay coils provide successive coupling stages, while SS compensation and spiral coils wound with Litz wire form the selected implementation. At 460 kHz, the spiral configuration yielded a simulated efficiency of 88.71% and an output power of 64.14 W. Its efficiency was 62.35 percentage points above the 26.36% calculated for the simplified configuration. This difference characterizes the implemented models; its attribution to a physical winding improvement requires a consistent comparison of their geometry and loss representations.
The environmental analyses identified conditions that nominal power-transfer performance alone does not describe. Relative angular misalignment reduced mutual inductance, and increasing meltwater-film thickness intensified local electric fields. The environmental calculations illustrate field redistribution under the specified geometries and surface conditions. These model results identify design considerations rather than establish adverse-weather reliability or insulation compliance.
A prototype constructed on a 1.5 m composite insulator delivered 100.28–158.20 W with reported efficiencies of 60.00–61.15%, demonstrating power transfer in the selected mounting arrangement. Taken together, the configuration comparison, environmental assessment, and prototype measurements support the feasibility of this relay-based approach and provide a basis for evaluating the design beyond its nominal simulated efficiency. Further validation should align simulated and measured operating conditions and assess power delivery and insulation under representative energized and environmental conditions.

Author Contributions

Conceptualization, Y.X.; methodology, Y.X.; software, Y.X. and L.T.; validation, Y.X., L.T., Y.Z., and F.L.; formal analysis, Y.X.; investigation, L.T.; resources, Y.X. and L.T.; data curation, L.T.; writing—original draft preparation, Y.X. and L.T.; writing—review and editing, Y.X., L.T., Y.Z., and F.L.; visualization, Y.X.; supervision, L.T.; project administration, Y.X.; funding acquisition, L.T. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Data Availability Statement

Data will be made available on request.

Conflicts of Interest

The authors declare no conflicts of interest.

Abbreviations

Abbreviation Definition
WPTWireless power transfer
SSSeries–series
SPSeries–parallel
PSParallel–series
PPParallel–parallel
RMSRoot mean square

References

  1. Gouda, O.; Khalifa, D. On-Line Monitoring of High Voltage Transmission Line; Lambert Academic Publishing: Saarbrucken, Germany, 2012. [Google Scholar]
  2. Singh, A.K.; Kumar, S.; Singh, B. Solar PV energy generation system interfaced to three phase grid with improved power quality. IEEE Trans. Ind. Electron. 2020, 67, 3798–3808. [Google Scholar] [CrossRef] [Scilit]
  3. Ojukwu, H.; Seet, B.C.; Rehman, S.U. Metasurface-aided wireless power transfer and energy harvesting for future wireless networks. IEEE Access 2022, 10, 52431–52450. [Google Scholar] [CrossRef] [Scilit]
  4. Boys, J.T.; Covic, G.A. The inductive power transfer story at the University of Auckland. IEEE Circuits Syst. Mag. 2015, 15, 6–27. [Google Scholar] [CrossRef] [Scilit]
  5. Mou, X.; Gladwin, D.; Jiang, J.; Li, K.; Yang, Z. Near-field wireless power transfer technology for unmanned aerial vehicles: A systematical review. IEEE J. Emerg. Sel. Top. Ind. Electron. 2022, 4, 147–158. [Google Scholar] [CrossRef] [Scilit]
  6. Peng, C.; Chen, Z.; Liu, Z.; Wang, J.-F.; Liang, J.; Li, C.; Tao, S.; Li, J. On the load-independence of a multi-receiver wireless power transfer system. IEEE Microw. Wirel. Compon. Lett. 2019, 29, 563–565. [Google Scholar] [CrossRef] [Scilit]
  7. Wu, Z.; Tan, L.; Xu, H.; Shen, S.; Huang, X. Design of the long-distance wireless power transfer system with multiple relay coils based on loss optimization. Electr. Eng. 2024, 106, 3337–3348. [Google Scholar] [CrossRef] [Scilit]
  8. Cui, Y.; Lin, Z.; Dai, Z.; Cai, W.; Zheng, J. The design of a long-distance high-efficiency WPT for online monitoring equipment based on a new relay structure. Electr. Eng. 2022, 104, 3007–3014. [Google Scholar] [CrossRef] [Scilit]
  9. de Miranda, C.M.; Pichorim, S.F. A three-coil wireless power transfer system using self-resonant open-bifilar coils. AEU Int. J. Electron. Commun. 2022, 154, 154300. [Google Scholar] [CrossRef] [Scilit]
  10. Qian, L.; Chen, M.; Cui, K.; Shi, G.; Wang, J.; Xia, Y. Modeling of mutual inductance between two misalignment planar coils in wireless power transfer. IEEE Microw. Wirel. Compon. Lett. 2020, 30, 814–817. [Google Scholar] [CrossRef] [Scilit]
  11. Pham, T.S.; Nguyen, T.D.; Tung, B.S.; Khuyen, B.X.; Hoang, T.T.; Ngo, Q.M.; Hiep, L.T.H.; Lam, V.D. Optimal frequency for magnetic resonant wireless power transfer in conducting medium. Sci. Rep. 2021, 11, 18690. [Google Scholar] [CrossRef] [Scilit] [PubMed]
  12. Ming, C.; Yanting, L.; Yongmin, Y.; Yingchun, Z.; Yingxiao, X. Performance optimization method of wireless power transfer system based on magnetic field editing. In Proceedings of the 2021 4th International Conference on Advanced Electronic Materials, Computers and Software Engineering (AEMCSE), Changsha, China, 26–28 March 2021; IEEE: Piscataway, NJ, USA, 2021; pp. 10–17. [Google Scholar]
  13. Zhang, J.; Zhao, J.; Zhang, Y.; Deng, F. A wireless power transfer system with dual switch-controlled capacitors for efficiency optimization. IEEE Trans. Power Electron. 2019, 35, 6091–6101. [Google Scholar] [CrossRef] [Scilit]
  14. Sha, L.; Liu, J.; Chen, Z. Research on evaluation method of electric vehicle wireless charging interoperability based on two parameter representation. Processes 2022, 10, 1591. [Google Scholar] [CrossRef] [Scilit]
  15. Wang, Z.; Sun, X.; Zhang, Q.; Chen, Z. Matching network design for input impedance optimization of four-coil magnetic resonance coupling wireless power transfer systems. J. Power Electron. 2022, 22, 1627–1637. [Google Scholar] [CrossRef] [Scilit]
  16. Prosen, N.; Domajnko, J. Optimization of a circular planar spiral wireless power transfer coil using a genetic algorithm. Electronics 2024, 13, 978. [Google Scholar] [CrossRef] [Scilit]
  17. Zhang, H.; Sui, X.; Sui, P.; Wei, L.; Huang, Y.; Yang, Z.; Yang, H. Coil parameter optimization method for wireless power transfer system based on crowding distance division and adaptive genetic operators. Energies 2024, 17, 3289. [Google Scholar] [CrossRef] [Scilit]
  18. Xu, F.; Wei, S.; Li, J.; Yuan, D.; Chen, K. Investigation on compensation topology and its parameter matching method for dynamic wireless power transfer system. IEEE Trans. Ind. Appl. 2024, 60, 5692–5701. [Google Scholar] [CrossRef] [Scilit]
  19. Rayan, B.A.; Subramaniam, U.; Balamurugan, S. Wireless power transfer in electric vehicles: A review on compensation topologies, coil structures, and safety aspects. Energies 2023, 16, 3084. [Google Scholar] [CrossRef] [Scilit]
  20. Van Mulders, J.; Delabie, D.; Lecluyse, C.; Buyle, C.; Callebaut, G.; Van der Perre, L.; De Strycker, L. Wireless power transfer: Systems, circuits, standards, and use cases. Sensors 2022, 22, 5573. [Google Scholar] [CrossRef] [Scilit] [PubMed]
  21. Okasili, I.; Elkhateb, A.; Littler, T. A review of wireless power transfer systems for electric vehicle battery charging with a focus on inductive coupling. Electronics 2022, 11, 1355. [Google Scholar] [CrossRef] [Scilit]
  22. Vinod, M.; Kishan, D.; Reddy, B.D.; Harischandrappa, N. Efficient and cost-effective wireless CC/CV charging for electric vehicles: A bipolar duty cycle approach. Comput. Electr. Eng. 2024, 118, 109470. [Google Scholar] [CrossRef] [Scilit]
  23. Pugi, L.; Grasso, F.; Paolucci, L.; Luchetti, L.; Zini, G. Finite element analysis of copper wire for wireless power transfer applications. In Proceedings of the 2022 IEEE 21st Mediterranean Electrotechnical Conference (MELECON), Palermo, Italy, 14–16 June 2022; IEEE: Piscataway, NJ, USA, 2022; pp. 801–806. [Google Scholar] [CrossRef] [Scilit]
  24. Fu, Y.; Zhu, Y.; Jiang, D.; Ji, B.; Peng, Z. Improved design of PCB coil for magnetically coupled wireless power transfer. Electronics 2024, 13, 426. [Google Scholar] [CrossRef] [Scilit]
  25. Solouma, N.H.; Kassahun, H.B.; Alsharafi, A.S.; Syed, A.; Gardner, M.R.; Alsharafi, S.S. An efficient design of inductive transmitter and receiver coils for wireless power transmission. Electronics 2023, 12, 564. [Google Scholar] [CrossRef] [Scilit]
  26. Stankiewicz, J.M. Evaluation of the influence of the load resistance on power and efficiency in the square and circular periodic WPT systems. Energies 2023, 16, 2950. [Google Scholar] [CrossRef] [Scilit]
  27. Stankiewicz, J.M. Estimation of the influence of the coil resistance on the power and efficiency of the WPT system. Energies 2023, 16, 6210. [Google Scholar] [CrossRef] [Scilit]
  28. Cai, C.; Wang, J.; Liu, R.; Fang, Z.; Zhang, P.; Long, M.; Hu, M.; Lin, Z. Resonant wireless charging system design for 110-kV high-voltage transmission line monitoring equipment. IEEE Trans. Ind. Electron. 2018, 66, 4118–4129. [Google Scholar] [CrossRef] [Scilit]
  29. Domajnko, J.; Prosen, N. A z-axis-tolerant inductive power transfer system using a bipolar double D receiver coil structure. Electronics 2023, 12, 4303. [Google Scholar] [CrossRef] [Scilit]
  30. Domajnko, J.; Prosen, N. A control of a z-axis rotation-tolerant wireless power transfer system using a double DD coil. Electronics 2023, 12, 606. [Google Scholar] [CrossRef] [Scilit]
  31. Chen, H.; Niu, S.; Shao, Z.; Jian, L. Recognizing multitype misalignments in wireless EV chargers with orientation-sensitive coils: A data-driven strategy using improved ResNet. IEEE Trans. Ind. Inform. 2023, 20, 280–290. [Google Scholar] [CrossRef] [Scilit]
  32. Wang, Z.; Liu, Y.; Wei, Y.; Song, Y. Study on electromagnetic characteristics of the magnetic coupling resonant coil for the wireless power transmission system. J. Appl. Biomater. Funct. Mater. 2018, 16, 140–149. [Google Scholar] [CrossRef] [Scilit] [PubMed]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.