Experimental Study on Flameless Venting of Methane Explosions Under the Coupled Effects of Dual Vents and Porous Materials

,
,
,
,
,
,
,
,
and
1
Northeast Sichuan Gas Mining District of Southwest Oil and Gas Field, Dazhou 635000, China
2
College of Safety Engineering, Chongqing University of Science and Technology, Chongqing 401331, China
3
Chongqing Key Laboratory for Oil and Gas Production Safety and Risk Control Technology, Chongqing 401331, China
*
Author to whom correspondence should be addressed.

Abstract

Explosion venting is an important measure for mitigating gas explosion hazards in confined spaces; however, conventional venting processes often generate high speed, high temperature jet flames, leading to severe secondary hazards. To achieve flameless venting, an experimental study on methane explosions under the coupled effects of dual explosion vents and porous materials was conducted in a confined pipe. Porous silicon carbide foam ceramics with different pore densities (10, 20, and 25 PPI) were installed at the vent openings under various vent layout conditions. Combined with high-speed imaging and dynamic pressure measurements, the flame evolution, jet flame suppression, and explosion overpressure characteristics were systematically analyzed. The results indicate that porous materials effectively attenuate jet flame intensity without compromising venting efficiency and increasing pore density significantly enhances flame-quenching performance. In addition, explosion vents located closer to the ignition source facilitate earlier energy release, thereby improving the reliability of flameless venting.

1. Introduction

In densely populated urban areas, facilities such as fueling stations, natural gas gathering and transmission stations, and compressor rooms are typical confined spaces. These structures are predominantly rectangular workshops or square buildings characterized by high spatial confinement and a tendency for combustible media concentrations to accumulate. When natural gas is released, it readily mixes with the surrounding air, resulting in a combustible mixture. When exposed to an ignition source, this mixture can readily trigger violent explosions. In severe cases, detonation phenomena may occur, posing a significant threat to urban safety operations [1,2,3].
In the field of workplace safety, monitoring, early warning, and operational maintenance management serve as fundamental measures for preventing gas explosions. However, accident statistics in recent years indicate that such measures alone cannot comprehensively contain risks. In confined spaces such as public buildings and chemical plants, factors like aging equipment pipelines, human operational errors, and improper emergency responses frequently cause natural gas leaks. Coupled with natural gas’s low ignition point, these leaks can readily trigger fires or explosions upon encountering open flames, posing severe threats to surrounding environments and the safety of personnel and property [4,5,6]. Therefore, relying solely on preemptive monitoring is insufficient to achieve comprehensive prevention and control across all scenarios. Exploring active control technologies for the early stages of explosions has become a critical breakthrough for reducing accident losses.
In confined environments, natural gas explosions generate high-temperature and high-pressure gases that can severely damage nearby equipment and structures, leading to substantial economic losses. Explosion venting is widely recognized as a practical and economical approach for mitigating explosion hazards [7,8]. Current mainstream venting technologies focus on rapid internal energy release, utilizing explosion vent walls, windows, and similar facilities to channel explosive energy and mitigate impact damage within space [9]. Nevertheless, this method is accompanied by notable limitations. During pressure relief, the explosion flame may be expelled through the vent openings, giving rise to an external jet flame, as illustrated in Figure 1. This jet can reach heights of several meters, potentially exceeding the safe distance between buildings. Moreover, jet flame possesses both high temperature and high velocity characteristics, making it highly likely to ignite surrounding combustibles and cause burns to personnel, leading to secondary disasters.
Figure 1. Schematic diagram of explosion jet flame and test.
Currently, research on explosion flame suppression technology is advancing in multiple directions. Porous material suppression is a commonly employed suppression method, primarily leveraging the numerous microscopic channels within porous materials. Its unique three-dimensional structure and effectiveness in resisting and dissipating shock wave energy enable the creation of resistance friction within these channels when an explosion flame and shock wave enter the porous material. consuming active groups within the flame and effectively dispersing the flow of combustion gases. As a result, flame propagation is markedly slowed, and complete flame quenching may occur when the flame is unable to pass through the narrow microchannels [10,11,12].
In 1955, Evans et al. [13] reported one of the earliest investigations into the suppression performance of an energy-absorbing material (sintered bronze, 50% porosity) in hydrogen explosions. Drawing on experimental investigations of various flame arresting units, Phillips and Pritchard [14] proposed correlations for estimating the maximum flame propagation velocity, while Piotrowski [15] developed expressions for the quenching diameter and quenching length. Recent studies have demonstrated the effectiveness of porous media in suppressing combustible gas explosion flames [16,17,18,19]. Using LS-DYNA simulations, Liu et al. [20] investigated the mitigation behavior of aluminum foam based materials, including sandwich configurations, as well as other explosion-resistant structures under tunnel gas explosion conditions. The findings demonstrated a noticeable reduction in structural damage when these materials were applied, and the aluminum foam sandwich configuration exhibited the most favorable performance. Cao and Wu et al. [21,22,23] examined the use of porous materials in utility tunnels, with particular attention to the key factors affecting their performance. Duan et al. [24] experimentally examined the roles of pore diameter and material thickness in flame suppression by porous media, with particular emphasis on the associated variations in pressure wave propagation and flame dynamics.
Diao et al. [25] investigated methane–air explosion flames interacting with foamed alumina porous media and reported that increasing both pore density and material thickness leads to improved flame suppression performance.
Similar observations were also reported in other studies [26,27], indicating that smaller pore sizes and greater material thickness contribute to more effective flame quenching and stronger attenuation of explosion overpressure. Zhuang et al. [28] performed explosion venting experiments in a spherical vessel with a neck to examine how porous materials affect overpressure and flame behavior during methane/air premixed gas explosions. The burst pressure of the Al2O3 50PPI porous material was the highest. The pressure reduction (Pred) of SiC 20PPI porous material is the highest. Abdul et al. [29] loaded Ag NPs onto the ceramic porous matrix as an explosion suppressant. The silver-coated ceramic foam exhibited an approximately 60% increase in compressive strength relative to the uncoated ceramic foam, rising from 0.58 MPa to 0.93 MPa. The flame suppression and explosion relief processes studied in this paper are consistent with the basic physical concepts embodied in the current international explosion protection standards. The flame arrestors specified in ISO 16852:2016 [30] usually adopt rigid porous structures such as metals or ceramics, achieving flame suppression through flame segmentation and heat absorption in the restricted channels; EN 14994:2007 [31] emphasizes controlling internal overpressure and reducing the risk of flame escape through an engineered explosion relief system; EN 16009:2011 [32] proposes design requirements for flameless explosion relief to release explosion pressure while suppressing the external flame emission, and EN 14797:2006 [33] covers explosion relief devices with regular geometric dimensions and filtering structures to regulate the explosion relief process and weaken the flame intensity. Although these standards are targeted at different types of explosion protection devices, their core all reflect the basic idea of jointly controlling the explosion consequences through flow obstruction, heat transfer enhancement, and flame segmentation.
Although research on porous materials in explosion suppression and venting has achieved phased progress, existing results still exhibit limitations and research gaps. Existing studies have largely concentrated on the “forward flame blocking” behavior associated with conventional venting ports. while studies on the adaptability to “lateral venting” scenarios—commonly employed in restricted-space engineering through venting doors and windows—remain severely inadequate. Due to factors such as opening mechanisms, frame structures, and lateral pressure release pathways, the flame propagation patterns and pressure release characteristics of venting doors and windows significantly differ from those of conventional venting ports. Research on the operational mechanisms of porous materials in dual-vent configurations within confined spaces remains largely unexplored, particularly lacking quantitative assessments of porous materials’ effectiveness for such dual-vent systems. Therefore, this paper delves into the optimized design of porous materials for venting ports, exploring the mechanism by which this venting measure influences the explosion characteristics of air premixed gas. A series of experiments were performed in a dual-vent configuration, where porous materials with different porosity levels were applied, as illustrated in Figure 1. This provides critical support for developing control strategies to manage the characteristics of flameless venting during natural gas explosions in confined spaces. This research holds critical significance for effectively mitigating natural gas explosion risks and refining flameless venting technology systems, while also providing robust scientific support for related engineering applications.

2. Experimental Systems

Figure 2 shows a schematic of the experimental setup, which includes an explosion pipeline, pressure and high-speed imaging subsystems, an ignition unit, a gas supply system, and the porous medium. Extensive research indicates that larger explosion vents prove more effective for exhausting gases, and dual venting ports deliver superior explosion vent performance compared to single vents [34]. As shown in Figure 2, the explosion vents are installed at different distances from the ignition point: 200 mm/400 mm, 200 mm/600 mm, and 400 mm/600 mm. Each vent measures 80 mm × 80 mm. The gas supply system includes a methane cylinder and an air cylinder, with the flow rates controlled by two Alicat MCS mass flow controllers set to 5 L/min. The inlet valve is located on the left steel plate. Combustion is triggered using a high-frequency pulse ignition system composed of an ignition coil and a control switch, operating at 6 V. The high-speed imaging system includes a high-speed camera (Phantom 710 L) and a data acquisition computer. For subsequent flame image analysis, the camera was operated at 2000 fps, with a spatial resolution of 1280 × 300 pixels and an exposure time of 490 μs. The pressure capture system comprises one high-frequency pressure sensor, a Blast-Pro shock tester, and one cable. The pressure sensor operates over a range of 0–690 kPa, with a sensitivity of 0.1% and a sampling rate of 50 kHz. The impact tester is used to trigger and synchronously record the initial time signals of the ignition and data acquisition systems. CH 1 is the synchronous trigger channel in the data acquisition system and is equipped with a pressure sensor, which is used to ensure the temporal consistency between the pressure signal and the high-speed imaging data.
Figure 2. Schematic illustration of the experimental apparatus.
Silicon carbide foam ceramic porous materials (hereinafter referred to as “porous materials”) exhibit high porosity, high-temperature resistance, impact resistance, and wave absorption properties due to their interconnected internal network structure. The distinctive porous architecture of these materials, together with their fire suppression and flame inhibition capabilities, plays an essential role in enabling flameless deflagration [35]. Taking both suppression performance and cost considerations into account, silicon carbide foam ceramics were selected as the explosion suppression material, as illustrated in Figure 3. To achieve flameless vent and prevent escaping flames from affecting the external environment, this experiment employs three porous materials with different porosities. Specifically, the maximum pore size for 10PPI is 4.85 mm, for 20PPI it is 2.95 mm, and for 25PPI it is 1.98 mm, ensuring that pore size progressively decreases with increasing porosity. The selection of this material enables in-depth investigation and evaluation of its suppression effectiveness in real or simulated explosive environments while ensuring cost-effectiveness and avoiding significant increases to the project budget. This provides reliable data support for its future practical application.
Figure 3. Schematic diagram of porous ceramic materials.
Connect all equipment as shown in Figure 2, inspect the airtightness of each device, and ensure proper operation. Set parameters according to different operating conditions as shown in Table 1. Two mass flow controllers are used to independently regulate the methane and air flow rates, with the methane concentration fixed at 9.5% by volume.
Table 1. Experimental setup and conditions. An equivalence ratio of Φ = 1 was adopted throughout the experiments, corresponding to a methane volume fraction of 9.5%.
The porous material is installed at the vent opening, which is subsequently sealed with a PVC membrane to ensure the enclosure is fully filled with a combustible gas mixture. Prior to ignition, the vent opening was sealed with a polyvinyl chloride (PVC) film to ensure airtightness. The PVC film had a thickness of 0.1 mm and a static failure pressure of 1.98 kPa. During each installation, care was taken to keep the film as flat as possible in order to minimize the influence of film flatness on the experimental results. Ventilation is performed using the 4-fold volume method 0 for 8 min. During this period, gas detectors are used to check leaks at all connections, ensuring the safety of the entire experimental process and the gas coverage within the explosion space. After 8 min of gas introduction, simultaneously shut off the methane cylinder, air compressor, and inlet/outlet valves. Allow 15 s of static time to ensure uniform gas mixing within the space. Calibrate the data acquisition system and high-speed camera system. Then, press the ignition switch to simultaneously capture explosion flame images and explosion pressure images.
After each experiment, valid data from the imaging and pressure monitoring systems were promptly stored. Turn on the air compressor to replace residual exhaust gases with fresh air, preventing interference with the next experiment. Prepare to restore all experimental equipment to its pre-experiment state for the next run. To ensure data reliability, each operating condition must be repeated at least three times.

3. Results and Analysis

3.1. Flame Characteristics of Methane Explosion Without Porous Material

This study focuses on the evolution characteristics of flames at explosion vents, providing only a brief overview of the initial flame evolution process. Figure 4 illustrates the dynamic changes in flame structure during a methane explosion at dual explosion vents under varying explosion source distances: Following ignition, the flame initially exhibits spherical diffusion. With the advancement of the explosion reaction, the initially spherical flame evolves into a finger-like structure. During this phase, the flame front area continuously expands, significantly enhancing the combustion-driven effect [36].
Figure 4. Flame image of double vents without porous materials.
Driven by the pressure differential across the pipeline after vent opening, the flame front develops a convex profile before being expelled through the vent, forming an irregular external jet flame. By comparing the flame images and the arrival time of the flame front at each explosion vent and at the pipe end, it can be determined that: The flame evolution pattern in a pipe with a length-to-diameter ratio of 8 under a dual-vent layout remains consistent with that of a pipe with a length-to-diameter ratio of 10 [37]. The closer the explosion vent is to the explosion source, the better the flame suppression effect.
To further quantify the influence of explosion vent layout on flame behavior, Figure 5 illustrates the temporal variation in height and velocity of the jet flame outside the explosion vent. The figure indicates that the maximum heights of the jet flame under different operating conditions are: 0.2525 m (Case s1), 0.1984 m (Case s2), and 0.2710 m (Case s3). The fastest flame velocities are: 48.25 m/s (Case s1), 40.84 m/s (Case s2), and 78.26 m/s (Case s3). The disparity in accumulated explosion energy within the pipeline is the primary cause of significant differences in jet flame height and velocity. Notably, the maximum jet flame height occurs under the operating condition where the explosion vent is farthest from the explosion source (Case s3). In practical engineering applications, although explosion vents effectively relieve internal overpressure, their structural characteristics allow high-temperature flames to be discharged externally during the venting process. These escaping explosion flames may cause secondary damage to surrounding structures, equipment, and personnel.
Figure 5. Flame height and speed as well as their measurement methods.
Therefore, to address secondary hazards caused by flame leakage during venting, flame arresting components such as porous materials should be added to the explosion vent. This achieves flame-free venting, enhancing the comprehensiveness and reliability of gas explosion prevention and control systems.

3.2. The Influence of Vent Installation of Porous Materials on Jet Flames

Building on the results presented in Section 3.1, the effects of porous materials with different porosities at the explosion vent on the external jet flame are investigated in this section. Figure 6 illustrates the evolution of flame structures when porous materials with different PPI values are installed at the explosion vent. Overall, the introduction of porous materials does not significantly alter the fundamental evolution patterns of the internal pipeline flame. The pressure differential across the pipeline continues to promote the formation of an upward-convex flame at the explosion vent, while gas can pass smoothly through the internal pores of the porous material. In contrast, the intensity of the resulting external jet flame is markedly attenuated.
Figure 6. Images of methane explosion flames installed with different PPI porous materials.
Firstly, analyze the operating conditions of porous materials with a pore density of 10 PPI (Cases a1, a2, a3). Regarding flame quenching effectiveness, weak jet flames appear outside the two explosion vents at 97 ms (Case a1), 85.5 ms (Case a2), and 87.5 ms (Case a3), respectively. This indicates that the porous material with this porosity fails to completely block flame leakage, resulting in partial quenching failure.
It is noteworthy that the timing of quenching failure exhibits significant positional dependence: For explosion vents closer to the explosion source, quenching failure does not occur when the flame front first passes through the porous material component. Instead, flame leakage only occurs after the flame front has completely traversed the explosion vent. Conversely, for explosion vents farther from the explosion source, quenching failure occurs as soon as the flame front contacts and penetrates the porous material. This behavior highlights the effect of explosion source distance on the quenching efficiency of porous materials. Owing to the insufficient quenching performance observed at 10 PPI, the porosity level of the porous material was increased to 20 PPI. As shown in Figure 6d–f, the external jet flame characteristics exhibit significant changes. No flame signals are observed outside the explosion vent closer to the explosion source, indicating effective quenching. However, flame leakage persists at the explosion vent farther from the explosion source, where quenching failure still occurs. These results indicate that increasing pore density significantly improves the extinguishing performance of porous materials, with this improvement being more pronounced for explosion vents near the explosion source.
After further increasing the pore density to 25 PPI, flame image monitoring results show that under the explosion vent combination configurations of 200 mm/400 mm and 200 mm/600 mm, no flame leakage occurs from either explosion vent throughout the entire explosion process, achieving complete extinguishment. However, in the 400 mm/600 mm explosion vent combination configuration, flame leakage persists at the rear explosion vent. Table 2 summarizes the quantitative comparison of quenching performance and jet flame height for porous materials with varying porosity levels. The quenching capability of the 25 PPI porous material is significantly higher than that of the 10 PPI and 20 PPI materials. The explosion vent near the explosion source can release explosive energy earlier, reducing subsequent flame intensity and creating favorable conditions for porous material quenching. In the dual-explosion vent combination, failure to extinguish at the rear explosion vent indicates that the flame retains high energy when propagating to the distant explosion vent, exceeding the quenching limit of the 25 PPI material.
Table 2. The height of the flame escaping from the explosion vent.
The results demonstrate that a higher pore density in porous materials leads to a markedly improved quenching performance under dual explosion vent conditions. Furthermore, the combination of explosion vent locations critically influences quenching success rates, with layouts incorporating explosion vents near the explosion source more readily achieving complete flame containment throughout the process. However, the core function of a blast relief system extends beyond preventing flame escape. It must also ensure rapid and effective release of explosive pressure to prevent structural damage in pipelines or enclosed spaces caused by pressure buildup.
Porous materials serve as supplementary flame arresting components at explosion vents. Their pore structures may significantly influence gas discharge resistance and pressure release rates, thereby altering venting efficiency. While studies on the flame-quenching properties of porous materials are well-established, it remains unclear whether they compromise the pressure-release capability of venting systems while blocking flames. Additionally, the evolution of explosion pressure within pipelines under different combinations of porosity and explosion vent location remains unexplored. Therefore, to comprehensively evaluate the overall impact of porous materials on venting systems and ensure the synergistic achievement of flameless venting and efficient pressure relief, the following study will investigate flame velocity and explosion overpressure during the venting process. This study examines how porous materials placed at explosion vents influence venting efficiency.

3.3. Effects of Porous Materials Installed at Exhaust Ports on Explosion Venting Performance

Flame visualization images can only intuitively present the macroscopic phenomena of successful or failed quenching, failing to reveal their underlying mechanisms. A binarization-based image processing approach is applied to extract the flame boundary from high-speed images, enabling quantitative evaluation of flame evolution and determination of the flame front propagation velocity [38]. The processing workflow is shown in Figure 7.
Figure 7. Extraction method of flame edge.
Figure 8 presents the temporal evolution of flame velocity under different operating conditions. During the initial combustion phase (before 10 ms), flame propagation speeds show minimal differences across conditions. At this stage, flame propagation is primarily driven by ignition energy and remains largely unaffected by the explosion vent and porous material. Around 15 ms, influenced by the excitation effect from membrane rupture, flame velocities across all conditions exhibit a rapid surge. When the flame front nears the explosion vent, a portion of the unburned gases is released in advance, generating a weak thrust that leads to a slight increase in flame propagation velocity. At approximately 20 ms, the flame front velocity reaches a maximum and then declines rapidly as the flame exits through the vent. Subsequently, influenced by flame oscillations triggered by fluctuations in combustion efficiency and propagation uncertainties, the velocity curve exhibits minor fluctuations. Owing to the development of Rayleigh–Taylor instability [39], the flame propagation velocity remains nearly constant during the final stage of combustion.
Figure 8. Image of the speed and acceleration of the flame striker.
Based on peak velocity data, as shown in Figure 9, under the same explosion vent position combination, the maximum flame front velocity exhibits a monotonically decreasing trend with increasing porosity material PPI. However, the rate of decrease varies significantly across different position combinations. For explosion vent locations at 200 mm and 400 mm, the peak flame front velocities corresponding to increasing PPI values are 11.47, 11.16, 11.00, and 10.98 m/s, respectively. For vent locations at 200 mm and 600 mm, the corresponding maximum velocities decrease to 11.01, 10.87, 10.26, and 9.80 m/s. When the explosion vent position is 400 mm/600 mm, the values are: 21.43 m/s, 20.86 m/s, 20.86 m/s, 18.69 m/s.
Figure 9. The maximum value graphs of flame velocity and acceleration.
Although the porous material lowers the peak flame velocity, the flame reaches the pipeline outlet in a shorter time. This phenomenon occurs because, after installing porous material at the explosion vent, the material both suppresses flame propagation through a quenching effect and, due to its structural resistance to gas flow, forces partially unquenched flames back into the pipeline. This phenomenon is observed under all operating conditions, creating a secondary combustion drive that accelerates flame propagation toward the end.
Case c3’s flame front velocity variation further reveals the coupled effects of position and material. At approximately 75 ms, a secondary surge in flame velocity is observed, reaching a peak of 4.67 m/s, which directly leads to the failure of flame quenching at the rear explosion vent. Under the dual-rear explosion vent configuration, the flame is decelerated by the porous material at the front explosion vent. It then undergoes secondary acceleration due to the strong suction effect from the pressure differential across the rear explosion vent. When the high-velocity flame flows rapidly and penetrates the porous material, it exceeds the material’s quenching capacity threshold, ultimately causing the flame to escape.
To more accurately characterize the acceleration and deceleration dynamics of the flame, the velocity curve alone is insufficient to capture transient features. Therefore, the curve is differentiated once to obtain the flame acceleration evolution curve. Figure 8 reveals that, like the velocity curves discussed earlier, the differences in maximum acceleration values across various operating conditions are relatively small. This explains why the differences in maximum velocity values are also small for different PPI porous materials under the same explosion vent location. Observations reveal that the most significant factor influencing the time difference for flames to reach the end of the pipe is the minimum acceleration value. This minimum acceleration increases with PPI. Under the non-porous condition, the minimum flame acceleration is the lowest, which leads to reduced overall propulsion of kinetic energy within the pipe and, consequently, a longer flame travel time to the outlet.
Porous materials reduce peak flame velocity while quenching the flame, but the variation patterns in acceleration and terminal arrival time suggest that the material’s obstruction of gas flow may alter combustion dynamics within the pipe. However, flame velocity and acceleration only reflect flame motion states and cannot directly characterize the pressure release efficiency of the explosion venting system. To further assess the influence of porous materials on venting performance, explosion pressure within the duct is analyzed in the following section, with particular attention to the role of porous materials at the explosion vent.
Figure 10 and Figure 11 illustrate the temporal evolution of overpressure within the pipeline, along with the corresponding peak values and overpressure rise rates (dp/dt). The pressure rise rate (dp/dt) is a key indicator of combustion velocity and explosion intensity [40]. Overall, the overpressure evolution trends exhibit consistency across all operating conditions, with the overpressure rise rate generally aligning with the dynamic overpressure variation patterns. This indicates that the introduction of porous materials has not altered the fundamental characteristics of explosion overpressure.
Figure 10. Explosion overpressure and its maximum value.
Figure 11. The variation graph of the rate of overpressure rise.
During explosion venting, the internal overpressure is governed by the balance between the net volumetric expansion produced by combustion and the gas flow discharged through the vent [41,42]. Following ignition, rapid fuel combustion within the pipeline causes a significant pressure rise. When the pressure reaches the bursting threshold of the explosion vent’s sealing membrane, the membrane ruptures. The rapid gas discharge triggers a pressure drop, forming the first overpressure peak PB1. However, since the rupture of the membrane is not instantaneous, the pressure exhibits noticeable fluctuations. As combustion proceeds, low-density products are generated, while unburned gases move downstream and are discharged through the vent, leading to a rapid decrease in pipeline pressure. As the explosive energy continues to accumulate, the overpressure release rate gradually balances with the generation rate, causing the pressure inside the pipeline to enter a brief stable phase. The pressure differential between the interior and exterior draws external air and expels unburned gases back into the combustion zone, triggering secondary combustion. This propels the pressure to rise rapidly once more, forming a second overpressure peak PB2. The gas leakage effect at the explosion vent further intensifies, causing the gas release rate to exceed the volumetric generation rate of the combustion reaction. This results in the pressure dropping to negative values. Ultimately, driven by the pressure differential between the inside and outside of the pipeline, the pressure rebounds and gradually stabilizes. The initial overpressure peak (PB1) is mainly governed by rapid pressure buildup and membrane rupture during early combustion. The porous material does not alter the generation mechanism of PB1; instead, it attenuates pressure wave transmission and reduces the pressure rise rate by introducing additional flow resistance and shock dissipation, leading to a reduced peak magnitude. The secondary overpressure peak (PB2) is associated with post-venting flow reconstruction and secondary combustion induced by pressure-driven backflow and re-entrainment of unburned gases. The porous material plays a dominant role at this stage by increasing backflow resistance, reducing the amount of unburned mixture participating in secondary combustion, and enhancing heat absorption. Accordingly, the internal logic of pressure evolution has been reorganized as a sequential process in which the porous material mainly influences overpressure attenuation and secondary peak suppression, rather than the initial pressure generation.
After installing porous materials, the maximum overpressure within the pipeline exhibits varying degrees of reduction. Compared to conditions without porous materials, case b1 shows the largest decrease at 16.33%. Other locations demonstrate no significant reduction, with decreases maintaining around 5%, indicating an insignificant drop. Analysis of the overpressure curve and peak values indicates that porous materials do not significantly alter the original venting pattern of the explosion vent. They may even reduce the explosive overpressure within the pipeline. Tural damage, delivering dual protective effects: extinguishing flames and alleviating shock impacts. Due to the energy-absorbing properties of porous materials, when the explosive shockwave passes through their pore structure, multiple reflections and scatterings occur. Part of the shockwave energy is absorbed by the material and converted into thermal or vibrational energy, ultimately achieving energy dissipation. Furthermore, data indicates that in scenarios where porous materials achieve effective flame quenching, the rate of overpressure increase is significantly reduced. This implies that porous materials not only prevent fire propagation through venting but also mitigate explosion shock intensity by suppressing pressure rise rates. Consequently, they lower the risk of pipeline structural damage, delivering dual protective effects: extinguishing flames and alleviating shock impacts.

3.4. Mechanism Analysis

To facilitate the interpretation of the experimental observations, a simplified porous structure model is introduced to qualitatively illustrate the interaction between the flame, pressure wave, and porous skeleton. It should be emphasized that this model is intended solely as a conceptual and illustrative tool, rather than as a predictive or validated numerical model. The model is used to provide a possible physical explanation for the observed attenuation of overpressure peaks and flame fragmentation when porous inserts are applied. The adopted geometric and thermal parameters are selected to reflect the typical characteristics of rigid porous ceramics reported in the literature, instead of quantitatively reproducing the experimental conditions. Consequently, no direct comparison between numerical results and experimental measurements is performed in this study.
Figure 12 reveals the synergistic mechanism of explosion vent and flame extinction after installing porous materials. It should be noted that due to experimental limitations, direct observation of the pore structure within the porous material and flame propagation details is not feasible. Therefore, this study employs modeling software to construct a simplified porous material model. The figure displays the three-dimensional model and its cross-sectional structure. Although this model does not fully replicate the actual pore distribution of the material, it accurately reflects the core function of porous materials, providing intuitive support for the explanation of the mechanism.
Figure 12. Schematic diagram of mechanism analysis.
When the rupture membrane of the explosion vent ruptures and initiates venting, the flame within the pipe migrates toward the vent driven by the external pressure difference, exhibiting an upward-inclined morphology. When interacting with the porous structure, the continuous flame front is broken into multiple discrete micro flames by the solid skeleton, which then propagate through the internal microchannels of the material. This process significantly increases the contact area between the flame and the solid wall surface, forming the basis for subsequent heat exchange and radical dissipation. The explosive pressure wave propagating synchronously with the flame encounters resistance from the skeletal structure as it traverses the porous material, undergoing multiple reflections and scatterings within the pores. Energy is progressively dissipated across successive layers, leading to a marked attenuation of pressure, while intense heat transfer occurs between the micro flames and the porous material walls. The material rapidly absorbs flame heat through thermal conduction, causing the flame temperature to continuously decrease. When the temperature falls below the critical threshold for methane combustion, the flame loses its propagation momentum and gradually extinguishes. During the initial stage when the flame first meets the porous material, flame fragmentation and enhanced heat transfer play a dominant role. The continuous flame front is divided into multiple micro-scale flame units by the porous material framework, significantly increasing the contact area between the flame and the solid wall, thereby enhancing the heat conduction and heat dissipation capacity. The shock wave dissipation mainly functions during the explosion relief and pressure release stage. When the explosion shock wave passes through the porous structure, it undergoes multiple reflections and scattering within the pores, and some of the energy is absorbed by the material and converted into thermal energy or vibrational energy. This mechanism is quantitatively characterized by the maximum overpressure value and the rate of overpressure increase. Free radical quenching, as an auxiliary mechanism at the microscopic scale, works in conjunction with thermal quenching. Although the free radical concentration cannot be directly measured in the experiment, by comparing the critical states of successful and failed quenching of different PPI porous materials under the same explosion relief layout, it is possible to indirectly reflect the significant enhancement of the probability of free radical recombination on the wall under high PPI conditions, thereby promoting the termination of the chain reaction.
Simultaneously, this enhances the material’s absorption of reaction heat. This dual effect interrupts the chain reaction, achieving flame quenching [43]. Conversely, large pore structures fail to provide sufficient wall contact opportunities and thermal absorption efficiency. And the radical generation rate exceeds the dissipation rate, allowing chain reactions to persist and making flame extinction difficult. Although porous materials can significantly reduce shock wave energy, a small amount of high-pressure gas can still slowly escape through the pores. This characteristic prevents structural damage caused by excessive pressure buildup within the pipeline. Moreover, since escaping gas no longer carries flames, it effectively blocks the path for high-pressure gas to carry flames outward, thus preventing the direct propagation of flames and residual overpressure to the external environment and averting secondary disasters.

4. Conclusions

(1)
Dual vent configuration significantly affects flame evolution and flameless venting performance. Explosion vents located closer to the ignition source release explosion energy at an earlier stage, effectively reducing downstream flame intensity and suppressing jet flame development at subsequent vents, thereby improving the overall reliability of flameless venting.
(2)
Porous materials can achieve effective jet flame suppression without degrading venting efficiency. Silicon carbide foam ceramic porous materials installed at the vent openings significantly attenuate external jet flames while maintaining rapid pressure relief. Increasing pore density enhances flame-quenching capability, with higher PPI materials exhibiting superior suppression performance.
(3)
The coupled application of dual vents and porous materials provides a reliable flameless venting strategy. Through combined effects of flame fragmentation, enhanced heat transfer, shock wave energy dissipation, and radical quenching within the porous structure, the dual-vent porous system reduces explosion overpressure and mitigates secondary hazards, offering practical guidance for explosion prevention design in confined-space applications.
(4)
Overall, this study demonstrates that coupling dual explosion vents with optimized porous materials provides a reliable and efficient strategy for achieving flameless venting of methane–air explosions in confined spaces. The results offer valuable insights for the design and optimization of explosion mitigation systems in urban energy infrastructure and industrial confined environments.

Author Contributions

Data curation, Y.R. and J.G.; Methodology, Y.R., J.G. and Q.H.; Investigation, X.H. and D.D.; Formal analysis, X.H. and D.D.; Software, W.X.; Supervision, W.X.; Funding acquisition, L.W.; Project administration, L.W.; Visualization, Y.D. and H.M.; Writing—original draft preparation, Y.D. and H.M.; Validation, X.L. and L.W.; Writing—review and editing, X.L. and Q.H. All authors have read and agreed to the published version of the manuscript.

Funding

This work was supported by the National Natural Science Foundation of China (Grant No. 52274177); Science and Technology Research Program of Chongqing Municipal Education Commission (Grant No. KJZD-K202401501).

Data Availability Statement

The data that has been used is confidential.

Acknowledgments

During the preparation of this manuscript, the authors employed ChatGPT4.5 as a tool for grammatical review. All content was subsequently examined, revised, and approved by the authors.

Conflicts of Interest

Authors Yanhui Ren, Jianhua Gong, Xuesong Huang, Defei Du, Wei Xia, Linling Wang was employed by the company Northeast Sichuan Gas Mining District of Southwest Oil and Gas Field. The remaining authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.

References

  1. Wang, S.; Xiao, G.; Feng, Y.; Mi, H. Investigation of premixed hydrogen/methane flame propagation and kinetic characteristics for continuous obstacles with gradient barrier ratio. Energy 2023, 267, 126620. [Google Scholar] [CrossRef] [Scilit]
  2. Huang, L.; Wang, Y.; Pei, S.; Cui, G.; Zhang, L.; Ren, S.; Zhang, Z.; Wang, N. Effect of elevated pressure on the explosion and flammability limits of methane-air mixtures. Energy 2019, 186, 115840. [Google Scholar] [CrossRef] [Scilit]
  3. Liu, C.; Liao, Y.; Yang, W.; Yin, Y.; Wang, Y.; Cui, G.; Li, Y. Estimation of explosion overpressure associated with background leakage in natural gas pipelines. J. Nat. Gas Sci. Eng. 2021, 89, 103883. [Google Scholar] [CrossRef] [Scilit]
  4. Li, H.; Li, Y.; Zhang, L.; Zhou, Y. On the evaluation of the “coal-to-gas” project in China: A life cycle cost analysis. Energy Sustain. Dev. 2023, 73, 116–125. [Google Scholar] [CrossRef] [Scilit]
  5. Huang, W.; Duan, J.; Chang, H.; Luo, Q.; Zhou, L.; Sun, Q. Construction of natural gas energy-measuring system in China: A discussion. Nat. Gas Ind. B 2022, 9, 33–40. [Google Scholar] [CrossRef] [Scilit]
  6. Vera, M.S.; Manrique, L.G.; Peña, I.R.; De La Vega Navarro, A. Drivers of electricity GHG emissions and the role of natural gas in mexican energy transition. Energy Policy 2023, 173, 113316. [Google Scholar] [CrossRef] [Scilit]
  7. Nie, Z.; Gao, W.; Jiang, H.; Zhao, F.; Zheng, G.; Zhang, Z. Flameless venting characteristics of hydrogen explosion under the coupling of carbon dioxide and metal foam. Process Saf. Environ. Prot. 2023, 180, 375–385. [Google Scholar] [CrossRef] [Scilit]
  8. Qi, B.; Li, H.; Zhai, F.; Yu, M.; Wei, C. Experimental and numerical study on the explosion characteristics of syngas under different venting conditions. Energy 2024, 290, 130069. [Google Scholar] [CrossRef] [Scilit]
  9. Yu, M.; Yang, X.; Zheng, K.; Luan, P. Progress and development of coal mine gas explosion suppression and disaster reduction technology in China. J. China Coal Society. 2020, 45, 168–188. [Google Scholar]
  10. Bivol, G.; Golovastov, S. Effects of polyurethane foam on the detonation propagation in stoichiometric hydrogen-air mixture. Process Saf. Environ. Prot. 2019, 130, 14–21. [Google Scholar] [CrossRef] [Scilit]
  11. Bivol, G.Y.; Golovastov, S.V. The effect of porous coating on the flame acceleration in hydrogen–air mixture. Process Saf. Environ. Prot. 2020, 137, 128–139. [Google Scholar] [CrossRef] [Scilit]
  12. Bivol, G.Y.; Golovastov, S.V.; Golub, V.V. Effect of channel geometry and porous coverage on flame acceleration in hydrogen–air mixture. Process Saf. Environ. Prot. 2021, 151, 128–140. [Google Scholar] [CrossRef] [Scilit]
  13. Evans, M.W.; Given, F.I.; Richeson, W.E. Effects of Attenuating Materials on Detonation Induction Distances in Gases. J. Appl. Phys. 1955, 26, 1111–1113. [Google Scholar] [CrossRef] [Scilit]
  14. Phillips, H.; Pritchard, D. Performance requirements of flame arresters in practical applications. Proc. I Chem. E Symp. Ser. 1986, 97, 47–61. [Google Scholar]
  15. Piotrowski, T.C. Specification of flame arresting devices for manifolded low pressure storage tanks. Plant/Oper. Prog. 1991, 10, 102–106. [Google Scholar] [CrossRef] [Scilit]
  16. Chen, Q.; Li, B.; Wang, Y.; Zhang, D.; Xie, L.; Song, X. Effect of polyurethane foam and carbon dioxide on the suppression of hydrogen/air explosion. Int. J. Hydrogen Energy 2024, 63, 538–546. [Google Scholar] [CrossRef] [Scilit]
  17. He, Y.; Fang, Q.; Yuan, B.; Cao, C.; Zhan, Y.; Chen, X.; Huang, C.; Zhang, Y.; Ding, Q. Explosion evolution behavior of methane/air premixed gas in a closed pipe filled with a bio-based porous material. Fuel 2022, 318, 123716. [Google Scholar] [CrossRef] [Scilit]
  18. Song, X.; Zuo, X.; Yang, Z.; Chen, J.; Xie, L.; Li, B. The explosion-suppression performance of mesh aluminum alloys and spherical nonmetallic materials on hydrogen-air mixtures. Int. J. Hydrogen Energy 2020, 45, 32686–32701. [Google Scholar] [CrossRef] [Scilit]
  19. Yuan, B.; He, Y.; Chen, X.; Ding, Q.; Tang, Y.; Zhang, Y.; Li, Y.; Zhao, Q.; Huang, C.; Fang, Q.; et al. Flame and shock wave evolution characteristics of methane explosion in a closed horizontal pipeline filled with a three-dimensional mesh porous material. Energy 2022, 260, 125137. [Google Scholar] [CrossRef] [Scilit]
  20. Liu, X.; Li, Y.; Wang, X.; Filip, G. Anti-Explosion Performance of Different Anti-Explosion Structures under Gas Explosion in Pipe Gallery. Chin. J. High Press. Physics. 2019, 33, 197–206. [Google Scholar]
  21. Cao, J.; Wu, J.; Zhao, Y.; Cai, J.; Bai, Y.; Pang, L. Suppression effects of energy-absorbing materials on natural gas explosion in utility tunnels. Energy 2023, 281, 128262. [Google Scholar] [CrossRef] [Scilit]
  22. Wu, J.; Li, Z.; Cai, J.; Zhao, Y.; Zhou, R.; Pang, L. Experimental analysis of suppression effects of crosswise arranged porous iron-nickel materials on the natural gas explosion in utility tunnels. J. Loss Prev. Process Ind. 2022, 77, 104775. [Google Scholar] [CrossRef] [Scilit]
  23. Wu, J.; Zhao, Y.; Zhou, R.; Cai, J.; Bai, Y.; Pang, L. Suppression effect of porous media on natural gas explosion in utility tunnels. Fire Saf. J. 2022, 128, 103522. [Google Scholar] [CrossRef] [Scilit]
  24. Duan, Y.; Wang, S.; Yang, Y.; Li, Y.; Zheng, K. Experimental study on methane explosion characteristics with different types of porous media. J. Loss Prev. Process Ind. 2021, 69, 104370. [Google Scholar] [CrossRef] [Scilit]
  25. Diao, S.; Li, H.; Jiang, X.; Qin, C.; Yu, M.; Shu, C.-M. Effects of foam alumina porous media on methane/air explosion flames: A combined study of X-ray CT scanning-based image reconstruction and three-dimensional pore-level simulations. Fuel 2025, 396, 135203. [Google Scholar] [CrossRef] [Scilit]
  26. Wen, X.; Guo, Z.; Wang, F.; Pan, R.; Liu, Z.; Zhang, X. Experimental study on the quenching process of methane/air deflagration flame with porous media. J. Loss Prev. Process Ind. 2020, 65, 104121. [Google Scholar] [CrossRef] [Scilit]
  27. Shao, J.; Zhuang, C.; Wang, Z.; Huang, Y.; Lu, W. Explosion Suppression Effect of Combined Porous Materials on Methane/Air Mixtures in Container Pipeline System. Explos. Shock. Waves 2018, 38, 905–912. [Google Scholar]
  28. Zhuang, C.; Wang, Z.; Zhang, Y.; Lu, Y.; Zhang, K.; Jiang, Q.; Huang, H.; Dou, Z. Effect of Porous Materials on Explosion Venting Overpressure and Flame of CH4/air Premixed Gas. Combust. Sci. Technol. 2021, 195, 508–529. [Google Scholar] [CrossRef] [Scilit]
  29. Jalil, A.A.; Hamzah, N.F.; Kasmani, R.M.; Chandren, S.; Jusoh, N.W.C.; Hassan, N.S.; Bahari, M. Effect of silver inhibition on the ceramic foam as flame suppression. E3S Web Conf. 2024, 516, 06001. [Google Scholar] [CrossRef] [Scilit]
  30. ISO 16852:2016; Flame Arresters—Performance Requirements, Test Methods and Limits for Use. International Organization for Standardization: Geneva, Switzerland, 2016.
  31. EN 14994:2007; Gas Explosion Venting Protective Systems. European Committee for Standardization (CEN): Brussels, Belgium, 2007.
  32. EN 16009:2011; Flameless Explosion Venting Devices. European Committee for Standardization (CEN): Brussels, Belgium, 2011.
  33. EN 14797:2006; Explosion Venting Devices. European Committee for Standardization (CEN): Brussels, Belgium, 2006.
  34. Duan, Y.; Qiao, Y.; Du, K.; Deng, L.; Cao, F.; Liu, H.; Si, R. Experimental and numerical study on the explosion characteristics of hydrogen-doped natural gas under dual-vent conditions. Int. J. Hydrogen Energy 2025, 168, 150997. [Google Scholar] [CrossRef] [Scilit]
  35. Nie, B.; He, X.; Zhang, R.; Chen, W.; Zhang, J. The roles of foam ceramics in suppression of gas explosion overpressure and quenching of flame propagation. J. Hazard. Mater. 2011, 192, 741–747. [Google Scholar] [CrossRef] [Scilit]
  36. Duan, Y.; Yang, J.; Long, J.; Liu, L.; He, G.; Lei, S.; Duan, X. Inhibiting effects of internal explosion-venting on natural gas explosion in urban underground utility tunnels. Tunn. Undergr. Space Technol. 2026, 167, 107082. [Google Scholar] [CrossRef] [Scilit]
  37. Duan, Y.; Yang, Y.; Deng, L.; Duan, X.; Qiao, Y.; Si, R. Influence of double explosion vent on methane-hydrogen explosion characteristics in confined space. Fuel 2026, 407, 137398. [Google Scholar] [CrossRef] [Scilit]
  38. Li, R.; Xiu, Z.; Liu, Z.; Xiao, F.; Li, M.; Liu, Q. Experimental study on the effect of concentration gradient on explosion dynamics and flame propagation in a methane-filled pipeline. Int. Commun. Heat Mass Transf. 2025, 165, 109110. [Google Scholar] [CrossRef] [Scilit]
  39. Hu, Q.; Shen, X.; Huang, Z.; Qian, X.; Jiang, J.; Yuan, M.; Pang, L. Shock wave dynamics and venting overpressure hazards induced by indoor premixed hydrogen/air explosion. Int. J. Hydrogen Energy 2024, 51, 830–847. [Google Scholar] [CrossRef] [Scilit]
  40. Pan, C.; Wang, X.; Li, G.; Zhao, J.; Liu, M.; Liu, Y.; Zhu, X. Influences of multi vents’ numbers and distributions on vented ethanol-gasoline vapor deflagrations. Process Saf. Environ. Prot. 2021, 152, 164–177. [Google Scholar] [CrossRef] [Scilit]
  41. Wang, Q.; Luo, X.; Li, Q.; Rui, S.; Wang, C.; Zhang, A. Explosion venting of hydrogen-air mixture in an obstructed rectangular tube. Fuel 2022, 310, 122473. [Google Scholar] [CrossRef] [Scilit]
  42. Wang, S.; Zhao, Y.; Li, G.; Xie, Y.; Wu, D. Effect of different vent covers on the overpressure and flame propagation characteristics of hydrocarbon fuel-air mixture venting explosion. Fuel 2022, 324, 124620. [Google Scholar] [CrossRef] [Scilit]
  43. Wang, Y.; Jiang, S.; Wu, Z.; Shao, H.; Wang, K.; Wang, L. Study on the inhibition influence on gas explosions by metal foam based on its density and coal dust. J. Loss Prev. Process Ind. 2018, 56, 451–457. [Google Scholar] [CrossRef] [Scilit]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Article Metrics

Citations

Article Access Statistics

Multiple requests from the same IP address are counted as one view.