Abstract
Estimating line resistance and reactance from advanced metering infrastructure (AMI) measurements is difficult when branch voltage drops are comparable to measurement noise. This study evaluates an unsupervised physics-informed neural network (uPINN) for impedance identification from voltage magnitudes and active and reactive power injections. The network uses power and voltage residuals and encourages consistent impedance estimates across operating snapshots. We compare the estimator with bounded linear least squares and an inverse power-flow baseline that uses nonlinear least squares on three radial feeder benchmarks under simulated measurement noise. The two baselines receive simulated voltage magnitudes at all retained buses, and the uPINN uses voltage measurements at metered buses. On the 118-bus feeder at a voltage noise standard deviation of 0.5%, uPINN yielded resistance and reactance mean absolute percentage errors (MAPEs) of 7.31% and 15.39%, compared with 15.02% and 31.40% for the inverse power-flow baseline. On the same feeder, the inverse power-flow baseline gave a lower reactance MAPE at the highest tested power measurement noise levels (2% for active power and 4% for reactive power). On the 69-bus equivalent, power flow calculations with impedances estimated at a voltage noise standard deviation of 0.2% gave a relative root-mean-square error in voltage magnitude of 0.0420%. The evaluation assumed known feeder topology and used impedance bounds derived from simulation references.
1. Introduction
Distribution feeder models rely on branch resistance and reactance for power-flow analysis, voltage control, and operational planning [1,2]. Utility records typically provide nominal impedances, but incomplete records and changes to feeder assets can introduce discrepancies [3]. Advanced metering infrastructure (AMI) provides time-stamped voltage magnitude and active and reactive power measurements. For a radial feeder with known topology, the resulting inverse problem is to recover branch impedances from these measurements when voltage drops can be small relative to meter noise.
Phasor-based methods estimate line parameters using synchronized voltage and current measurements [4,5,6]. Extensions account for transformer taps and systematic measurement errors [7,8]. Distribution-network studies have used synchrophasors or combined phasor measurement unit (PMU) and supervisory control and data acquisition (SCADA) data [9,10]. A second group reduces the need for synchronized measurements by using unsynchronized terminal measurements, measurement-tolerance models, or SCADA data [11,12,13].
Smart-meter-based methods also estimate topology and line parameters jointly [14,15,16,17]. For example, Wang et al. [16] derive a topology descriptor from historical measurements and use clustering and regression to recover topology and parameters. Wang and Yu [18] estimate three-phase resistance and reactance matrices by fitting a physics-based graphical model to smart-meter data. Their method assumes known feeder topology and phase connections, uses source-bus SCADA voltage measurements, and can incorporate impedance information from the geographic information system (GIS). Guo et al. [19] estimate feeder topology from smart-meter data and then recover line impedances by solving a nonlinear inverse power flow problem for each branch. Identification of asymmetric line-to-ground parameters is a related problem with a different estimation target [20].
Physics-informed neural networks use residuals derived from governing equations to train estimators [21,22]. Jiang et al. [23] use active and reactive power mismatches to compute AC power-flow states for a given network model. In this study, the unknowns of interest are the branch resistances and reactances. Table 1 compares these formulations in terms of inputs, topology, supervision, physical formulations, and estimation targets. The topology descriptor in [16] is used to estimate topology and line parameters jointly, whereas the topology is fixed here. The three-phase estimator in [18] uses a three-phase feeder model, known load phase connections, and source-bus voltage measurements. This study evaluates an estimator that combines power and voltage residuals with a penalty on variation in branch impedance estimates across operating snapshots. We compare this formulation with fitting a single impedance per branch across all snapshots.
Table 1.
Comparison of representative approaches to power-flow calculation and distribution line parameter estimation.
The study asks how measurement noise and small branch voltage drops affect impedance estimation, and how snapshot-specific estimates with a consistency penalty compare with shared impedance estimates.
- (1)
- We formulate a multi-snapshot impedance identification problem for a known radial feeder. The uPINN jointly estimates branch powers, unmeasured bus voltage magnitudes, and candidate line impedances. The physical residuals couple these quantities, while the consistency terms reflect the assumption that branch impedances are stable across the observed operating conditions.
- (2)
- Under a common simulation protocol, we compare a scheme that estimates impedance for each snapshot and penalizes variation across snapshots with a scheme that fits one resistance and one reactance per branch to all snapshots.
- (3)
- We compare the estimator with numerical and neural benchmarks across voltage and power noise levels, examine errors on branches with small voltage drops, and quantify the effects of impedance estimation errors on steady-state power flow calculations.
The evaluation uses the 33-bus feeder, an equivalent of the 69-bus feeder, and the 118-bus feeder. The benchmark assumes known topology and uses bounds derived from the simulation reference impedances.
2. uPINN-Based Line Parameter Identification Method
2.1. Problem Formulation
This study considers a distribution network consisting of N buses and L distribution lines. Under AMI measurement conditions, voltage magnitudes and nodal active/reactive power injections can be obtained at multiple time snapshots, whereas voltage phase angles and branch current phasors are generally unavailable. Therefore, the objective of this study is to identify the line resistance and reactance parameters from incomplete steady-state measurements.
For the k-th measurement snapshot, the available measurement vector is defined as
where Vk, Pk, and Qk denote the measured bus voltage magnitudes, active power injections, and reactive power injections, respectively. All voltage and power variables in this study refer to fundamental-frequency steady-state quantities.
The unknown line parameter vector is expressed as
where Rl and Xl are the resistance and reactance of the l-th line. Since the true values of these parameters are generally unavailable in practical distribution networks, they are not used as supervised labels during model training. Instead, the proposed method estimates θ by enforcing consistency among AMI measurements, neural-network outputs, and distribution power flow equations.
2.2. Input–Output Mapping
The proposed uPINN maps AMI-based nodal measurements to branch operating variables and line parameters. For each time snapshot, the network input consists of voltage magnitude and nodal active/reactive power measurements. When voltage measurements are available only at a subset of buses, the measured voltage vector is combined with nodal power injections to form the input feature vector:
where m is the number of buses with voltage measurements.
The network output is defined as
where and are the active and reactive powers at the sending ends of branches, Rk and Xk are the line resistance and reactance vectors, and denotes the voltage magnitudes at buses without voltage measurements.
Branch powers and unmeasured bus voltage magnitudes vary across snapshots, while each branch impedance is assumed constant over the observation period. The network predicts a candidate impedance for each snapshot, and the consistency loss penalizes variation among these estimates.
With active and reactive injection inputs for all N buses and voltage magnitudes at m buses, the input has 2N + m components. The joint output has 4L + N − m components, comprising two sending-end powers and two impedance components per branch and one voltage magnitude per bus without a voltage measurement. With voltage measurements at every bus, the joint output has 4L components.
2.3. Residual Block and Network Architecture
The uPINN adopts a residual fully connected neural network as the trainable function approximator. Since the input data are structured numerical measurements rather than images or sequential signals, fully connected layers are used to learn the nonlinear mapping from nodal measurements to branch variables and line parameters. However, stacking multiple hidden layers may cause gradient attenuation or unstable updates, especially when measurement-consistency and physics-based losses are optimized together. To improve trainability, residual connections are introduced into the hidden layers, and the structure of a residual block is shown in Figure 1.
Figure 1.
Structure of the residual block.
For a residual block with input z, the output is expressed as
where F(·) represents the nonlinear transformation inside the residual block, and σ(·) is the activation function. The shortcut connection allows the input features to be directly propagated to deeper layers, which helps preserve useful measurement information and improves gradient transmission during backpropagation.
Figure 2 shows the network architecture for the joint formulation in Section 2.2. It consists of an input mapping layer, several residual blocks, and an output mapping layer. The input layer receives AMI-based voltage magnitude and active/reactive power measurements, while the output layer generates branch sending-end active/reactive powers, line resistance/reactance parameters, and unmeasured bus voltages. Gaussian error linear unit (GELU) is used in the hidden layers. A linear mapping allows the branch power outputs to take either sign. A scaled sigmoid maps each resistance and reactance output to its prescribed interval.
Figure 2.
Residual fully connected uPINN architecture for the joint formulation in Section 2.2.
Based on this architecture, the network outputs are not directly regarded as final identification results. Instead, they are treated as intermediate physical variables and further substituted into the distribution-network equations. The physical consistency of these outputs is evaluated through measurement consistency, branch voltage relationships, and the impedance variance-consistency constraint.
2.4. Physics-Informed Loss Function
Since true line parameter labels are not available, the proposed uPINN is trained in an unsupervised manner. The total loss function consists of three parts: nodal power-consistency loss, branch voltage-equation loss, and impedance variance-consistency loss. Figure 3 illustrates the physical interpretation of these three loss terms. These terms penalize mismatches in nodal power and branch voltage, as well as variation in impedance estimates across snapshots.
First, the nodal power-consistency loss is introduced to ensure that the branch powers generated by the network can reproduce the measured nodal active and reactive power injections. Since the network predicts the sending-end branch powers, the receiving-end branch powers are first calculated by considering line losses. As illustrated in Figure 4, the squared current magnitude of branch l, flowing from bus i to bus j at snapshot k, is calculated from the predicted sending-end active and reactive powers, and the sending-end voltage magnitude as
where and are the sending-end active and reactive powers of line l at snapshot k, Vk,i is the sending-end voltage magnitude. The active and reactive line losses are then expressed as
In this study, branch terminal powers are defined as positive when flowing from the connected bus into the branch. Under this sign convention, the receiving-end terminal powers are derived as
Accordingly, the reconstructed nodal active and reactive power injections are obtained by summing the terminal powers of all incident branches according to the network topology:
where and denote the sets of branches whose sending ends and receiving ends are connected to bus i, respectively. and are the reconstructed active and reactive power injections at bus i in snapshot k, obtained by summing the terminal powers of all incident branches according to the network topology. The superscript (*) denotes quantities reconstructed from the network-predicted branch powers, rather than directly measured values. The nodal power-consistency loss is then defined as
where Pk,i and Qk,i are the measured nodal active and reactive power injections. This term penalizes discrepancies between nodal injections reconstructed from the predicted branch powers and the corresponding AMI measurements.
Second, the branch voltage-equation loss is introduced to enforce the physical coupling among branch powers, line parameters, branch current, and bus voltages [24]. For line l from bus i to bus j, the downstream voltage magnitude calculated from the branch voltage-drop equation is expressed as
where denotes the voltage magnitude calculated from the upstream voltage, branch power, branch current, and line impedance. The voltage residual at bus j is then defined as
The corresponding voltage-equation loss is calculated over all non-slack buses as
In a radial distribution network, each non-slack bus has one upstream branch; therefore, the voltage residual of bus j is obtained from the branch ending at this bus. This term penalizes deviations of predicted or measured voltage magnitudes from those calculated using the branch voltage-drop equation.
Third, an impedance variance-consistency loss is introduced to reflect the assumed constancy of line parameters over the observation period. In a distribution network, line resistance and reactance are physical parameters of the feeder and should remain unchanged across different measurement snapshots. Therefore, the impedance values inferred from different snapshots are expected to be consistent.
For line l, the mean resistance and reactance over K snapshots are calculated as
where Rk,l and Xk,l are the resistance and reactance of line l inferred from snapshot k, while and are their mean values over all snapshots. The impedance variance-consistency loss is then defined as
This loss penalizes the dispersion of impedance estimates across different operating conditions and encourages the network to identify stable line parameters rather than snapshot-dependent fitting results. The total loss function is then formulated as
where λpq, λv, and λvar are weighting coefficients. These coefficients balance the contributions of measurement consistency, branch voltage constraints, and impedance variance-consistency during training.
Figure 3.
Physical interpretation of the loss functions.
Figure 4.
Simplified two-bus line model for branch current calculation.
2.5. Training and Identification Procedure
First, the distribution-network topology and multi-snapshot AMI measurements are collected. The voltage magnitude and active/reactive power data are preprocessed through time alignment, filtering of anomalous measurements, and normalization. Then, the processed measurements are fed into the residual fully connected network to generate branch powers, unmeasured bus voltage magnitudes, and candidate line parameters.
Next, the network outputs are combined with the network topology to calculate nodal power reconstruction errors, branch voltage-equation residuals, and impedance variance-consistency loss. The training loss combines these components using the weights in Equation (17), with the mini-batch impedance consistency penalties described below. The network weights are updated by backpropagation using the Adam optimizer. During training, the network gradually adjusts its outputs so that the inferred line parameters can explain the measured operating states while satisfying distribution-network physical constraints.
Equation (16) defines the impedance consistency objective over all snapshots. During mini-batch training, the variance term is evaluated using the current batch mean. To further maintain consistency across different batches, an exponential moving average of historical batch means is maintained, and deviations of the current batch mean from this moving average are additionally penalized. Both terms use the same consistency weight.
Training stops when the total loss no longer decreases appreciably over consecutive epochs. Finally, the identified resistance and reactance values are used in power flow calculations for verification. The voltage and power reconstruction errors are then analyzed to evaluate the physical consistency and identification performance of the proposed method.
3. Case Study and Results
3.1. Test Feeders and Experimental Protocol
The benchmark uses three radial distribution feeders with 32, 50, and 117 energized branches. The 50-branch case is the 51-bus equivalent of the original 69-bus feeder. Each case uses 2000 simulated operating snapshots for identification. The uPINN uses available nodal voltage magnitudes as inputs and predicts the voltage magnitudes of retained buses without measurements. Figure 5 illustrates the series-branch aggregation rule used to obtain the 69-bus feeder equivalent.
Figure 5.
Series-branch aggregation in the 69-bus feeder. (a) Two series sections joined at an unmetered zero-injection node (red) are replaced by a single branch whose impedance is the sum of the original impedances. (b) A branching junction (blue) is retained.
To isolate the effect of voltage measurement noise, its relative standard deviation was varied across 0.1%, 0.2%, 0.3%, and 0.5%. Active and reactive power noise standard deviations were fixed at 1% and 2%, respectively, and the same noisy power samples were used at every voltage noise level. Measurement errors were simulated as multiplicative Gaussian noise, with the percentages denoting relative standard deviations. No meter accuracy class was assigned.
The simulations use known topology and common line-specific bounds of 0.5 to 2.0 times the reference resistance and reactance for all estimators. Accuracy is evaluated against the simulation references. The training objective uses no impedance labels.
Each input feature was centered by its mean across the identification snapshots and divided by its population standard deviation, with a minimum divisor of 10−6. The benchmark residual network (ResNet) uses stages of width 256 and 128, with two residual blocks per stage. The input projection applies a linear layer, layer normalization, and the GELU, in that order. The projection between stages also uses GELU. Each residual branch applies layer normalization, a width-preserving linear layer, GELU, dropout with probability 0.01, and a second width-preserving linear layer. Each block adds the residual branch output to its input and applies an activation to the sum, as in Equation (5). Final layer normalization follows the second stage. GELU uses the exact formulation without a trainable activation parameter. The benchmark used a training budget of 61 epochs, by which point the total loss had largely plateaued. Training used a batch size of eight, an initial Adam learning rate of 0.0002, and gradient-norm clipping at 1.0. The weights for nodal power consistency, branch-voltage consistency, and impedance consistency are 1, 10 and 10, respectively. The consistency weight applies to both within-batch and between-batch terms.
The benchmark uses the all-bus nodal power consistency loss in Equation (11). It sums the squared active and reactive power residuals at each retained bus and averages this sum over all retained buses and snapshots. The voltage loss is the mean squared branch voltage residual. Section 3.4 describes the within-batch variance and between-batch consistency terms.
For N retained buses and L branches, the input and output dimensions are 2N + m and 4L + N − m, respectively, where m is the number of retained buses with voltage measurements. The outputs include branch sending-end active and reactive powers, candidate line resistances and reactances, and voltage magnitudes at unmeasured retained buses. The 33-bus, 69-bus equivalent, and 118-bus cases use 31, 49, and 118 voltage measurements per snapshot, respectively. The unmeasured voltage magnitudes correspond to buses 2 and 3 in the 33-bus feeder and to original buses 3 and 4 in the 69-bus feeder. These are zero-injection buses that remain in the network because they cannot be eliminated by series-branch aggregation. Their input/output dimensions are 97/130, 151/202, and 354/468. Counting the linear weights and biases and the trainable scales and offsets of layer normalization gives 406,274, 429,386, and 515,668 trainable parameters for the three ResNet-uPINN models, respectively. A fully connected mapping lets each branch estimate depend on measurements across the feeder. Residual connections provide an identity path through each same-width block. Section 3.3 compares the resulting estimator with the multilayer perceptron (MLP) and graph convolutional network (GCN) architectures under the same physics-based objective.
3.2. Numerical Baselines and Noise Sensitivity
The comparison uses bounded linear least squares and an inverse power-flow baseline. Bounded linear least squares fits differences between squared terminal voltage magnitudes using downstream powers with line losses omitted. The inverse power-flow baseline propagates estimated line losses upstream and fits branch voltage residuals by nonlinear least squares. It scans 65 logarithmically spaced resistance-to-reactance ratios between 0.2 and 5.0 and solves within the common impedance bounds. The branch voltage residual and bottom-up sweep follow Guo et al. [19]. Both conventional baselines require voltage magnitudes at both ends of each branch to form their voltage residuals. The conventional baselines therefore receive simulated voltage magnitudes at all retained buses under the specified test conditions. The uPINN uses only the voltage measurements at metered buses and predicts the missing voltage magnitudes. The feeder topology is given in the benchmark.
Figure 6 shows that the ranking depends on the feeder, noise level, and impedance component. At 0.1% voltage noise, inverse nonlinear least squares gave the lowest reactance mean absolute percentage error (MAPE) for the 33- and 118-bus feeders. At 0.5% voltage noise on the 118-bus feeder, the resistance and reactance MAPEs were 7.31% and 15.39% for ResNet-uPINN and 15.02% and 31.40% for inverse nonlinear least squares. For each feeder and impedance component, MAPE is the mean of the absolute percentage errors across the identified branches. The voltage and power noise comparisons use a single random seed.
Figure 6.
Mean absolute percentage error (MAPE) of the three estimators under voltage measurement noise. Panels (a–c) show resistance MAPE, and (d–f) show reactance MAPE. Within each group, the panels show the 33-bus feeder, the 69-bus equivalent, and the 118-bus feeder, in that order. Active and reactive power noise standard deviations were 1% and 2%, respectively.
Figure 7 compares the three estimators under three levels of active and reactive power measurement noise on each feeder. The voltage measurements were fixed at a relative noise standard deviation of 0.2%. Scaling the same power noise samples by 0.5, 1, and 2 gave active/reactive power noise standard deviations of 0.5%/1%, 1%/2%, and 2%/4%. At each level, the methods used the same simulated operating snapshots and branch-wise impedance bounds, with voltage coverage as described above.
Figure 7.
Resistance MAPE (a–c) and reactance MAPE (d–f) under active and reactive power measurement noise. Each group shows the 33-bus feeder, 69-bus equivalent, and 118-bus feeder, in that order. The voltage noise standard deviation was 0.2%.
ResNet-uPINN gave the lowest resistance MAPE in all nine feeder and power-noise combinations. Its reactance MAPE increased on all three feeders, with the largest increase on the 118-bus feeder, from 14.48% to 18.41%. At the highest noise level on this feeder, inverse nonlinear least squares gave the lower reactance MAPE of 16.48%. ResNet-uPINN retained the lowest reactance MAPE at all three noise levels on the 33-bus and 69-bus equivalent feeders. The relative performance varied with the feeder and impedance component for this noise realization.
To examine errors on individual branches, we ranked the 118-bus feeder branches by the mean of the resistance and reactance absolute percentage errors (APEs) from ResNet-uPINN at a voltage noise standard deviation of 0.2%. Figure 8 and Figure 9 compare all three methods on the 10 branches with the lowest mean APEs and the 10 with the highest. Within each group, branches are ordered by increasing mean APE. The reference voltage drops and sending-end powers are root-mean-square (RMS) values across the 2000 operating points. They were calculated using reference impedances, non-slack power injections, and slack-bus voltages. Panel (d) plots active power in kW and reactive power in kvar on the same numerical scale.
Figure 8.
Ten branches with the lowest mean ResNet-uPINN error on the 118-bus feeder. (a) Resistance absolute percentage error (APE), (b) RMS reference voltage drop, (c) reactance APE, and (d) RMS sending-end active and reactive power.
Figure 9.
Ten branches with the highest mean ResNet-uPINN error on the 118-bus feeder. (a) Resistance APE, (b) RMS reference voltage drop, (c) reactance APE, and (d) RMS sending-end active and reactive power.
For the lowest- and highest-error groups, the median RMS branch voltage drops were 103.3 and 5.6 V, respectively. The corresponding median sending-end active power RMS values were 4.82 and 0.38 MW, and the reactive power values were 3.06 and 0.22 Mvar. The selected high-error branches therefore tended to have smaller voltage drops and carry less power. In that group, inverse nonlinear least squares had a lower median resistance APE than ResNet-uPINN (10.12% versus 17.89%), while ResNet-uPINN had a lower median reactance APE (39.28% versus 48.80%). Both groups were selected using the ResNet-uPINN error ranking. Figure 6 provides the comparison over all branches.
3.3. Network Architecture and Width
Figure 10 compares the impedance estimation errors of the three architectures using the same measurements and loss terms. The MLP uses the same sequence of layers as the ResNet with the skip connections removed. The GCN uses two graph convolutional layers with 64 hidden features. At 0.2% voltage noise on the 118-bus feeder, reactance MAPEs were 15.71%, 16.80%, and 16.89% for ResNet, MLP, and GCN, respectively.
Figure 10.
Comparison of ResNet-uPINN, multilayer perceptron uPINN (MLP-uPINN), and graph convolutional network uPINN (GCN-uPINN) under voltage noise. Panels (a–c) show resistance MAPE, and (d–f) show reactance MAPE. Each group shows the 33-bus feeder, 69-bus equivalent, and 118-bus feeder, in that order.
Figure 11 shows the unweighted total power loss and branch voltage loss over 61 epochs on the 118-bus feeder. The total power loss in Figure 11a is the nodal power consistency loss in Equation (11), averaged over all retained buses and snapshots. ResNet and MLP end training with lower power loss than GCN. The corresponding voltage losses were 0.000812, 0.000991, and 0.000954. Branch-level impedance accuracy is assessed separately in Figure 10. The relative noise standard deviations for voltage magnitude, active power, and reactive power were 0.2%, 1%, and 2%, respectively.
Figure 11.
Unweighted training loss components on the 118-bus feeder. (a) Total power loss across all retained buses, defined in Equation (11). (b) Branch voltage loss.
After comparing the architectures and their training losses, we varied the ResNet stage widths to assess whether a larger network improved identification under the same training schedule. Figure 12 shows the 128/64, 256/128, and 512/512 configurations at 0.2% voltage noise. On the 118-bus feeder, their resistance/reactance MAPEs were 6.64%/16.35%, 6.35%/15.71%, and 6.45%/15.73%, respectively. Increasing the stage widths from 256/128 to 512/512 produced little change in either MAPE on this feeder.
Figure 12.
Effect of ResNet hidden-layer width on (a) resistance MAPE and (b) reactance MAPE at 0.2% voltage noise. Dark blue denotes the reference 256/128 configuration.
Table 2 compares the effects of batch size, stage width, and residual depth on estimation accuracy and training cost. Each run changes one setting from the common baseline of batch size 8, stage widths 256/128, and four residual blocks. The width cases complement Figure 12 by reporting the training time on the 118-bus feeder.
Table 2.
ResNet-uPINN ablation on the 118-bus feeder.
Across two, four, and six residual blocks, the reactance MAPE varied by 0.26 percentage points. The six-block model gave the lowest reactance MAPE (15.45%). At the same epoch count, increasing the batch size from 8 to 16 halved the number of optimizer updates and reduced training time from 145.4 to 74.2 s, while reactance MAPE increased from 15.71% to 16.63%.
Table 3 compares identification time and accuracy on the 118-bus feeder using the same 2000 simulated snapshots for all five methods. Voltage inputs follow Section 3.2. Each method was run once on a single thread of an Intel Core i5-1340P CPU, with the runs performed in sequence. Wall-clock time includes method-specific initialization and preprocessing, solving or training, and the computation of the final impedance estimates. Common data loading and preparation, calculation of error metrics, and file output were excluded.
Table 3.
Identification time and estimation errors on the 118-bus feeder.
The two numerical methods returned estimates in less than 0.31 s, compared with 148.32–232.42 s for the neural methods. ResNet-uPINN gave the lowest resistance and reactance MAPEs in this comparison, at 6.35% and 15.71%, respectively.
3.4. Shared and Snapshot-Specific Impedance
A direct shared-impedance estimator optimizes one bounded resistance and one bounded reactance per branch across all snapshots. The snapshot-specific estimator instead uses snapshot-specific candidate impedances with within-batch variance and a between-batch penalty relative to an exponential moving average. The exponential moving average retains 90% of its previous value and incorporates 10% of the current batch mean. The final estimate averages the candidates over the identification snapshots. The comparison evaluates the two complete parameterization and training schemes. The comparison changes the impedance parameterization and consistency penalties together, so it does not isolate the contribution of the exponential moving average (EMA) term.
After the same number of training epochs, ResNet-EMA had lower resistance and reactance MAPEs on all three feeders (Table 4). On the 33-bus feeder, the shared-impedance estimator had more branches with reactance error within 10% (11 versus 7).
Table 4.
Resistance and reactance estimation errors for the two impedance parameterizations.
3.5. Loss Weight Sensitivity
The sensitivity analysis examines how the weights assigned to the branch voltage loss and the impedance consistency terms affect the estimated parameters. Figure 13 varies both weights over 0.1, 0.5, 1, and 10 on the 118-bus feeder at 0.2% voltage noise, with the nodal power consistency weight fixed at one. At a branch voltage loss weight of 10, reducing the common consistency weight from 10 to 1 changed resistance MAPE from 6.35% to 6.24% and reactance MAPE from 15.71% to 12.38%. The main comparisons use 1, 10, and 10 as a common benchmark configuration. Figure 13 shows how sensitive the results are to changes in that configuration. The analysis covers one feeder, one noise level, and one training seed. The weight assigned to impedance consistency was shared by its within-batch and between-batch terms.
Figure 13.
Sensitivity of (a) resistance MAPE and (b) reactance MAPE to the voltage and impedance consistency weights on the 118-bus feeder. Outlined cells mark the benchmark weights. Each panel has its own color scale.
3.6. Effects of Missing Measurements and Time Misalignment
We tested whether sporadic missing readings and differences in meter sampling times affect impedance identification. We generated 2000 snapshots at 15 min intervals for each feeder. We constructed synthetic load trajectories by applying shape-preserving cubic interpolation to simulated nodal power injections at hourly anchor points and solved power flow at the nominal and offset sampling times. The relative Gaussian noise standard deviations for voltage magnitude, active power, and reactive power were 0.2%, 1%, and 2%, respectively. Both tests use the complete, time-aligned records for these trajectories as their reference. The reference row in Table 5 comes from these separately generated trajectories. Table 3 and Table 4 use the main benchmark operating snapshots.
Table 5.
Resistance and reactance MAPE (%) of ResNet-uPINN under random missing measurements and sampling time offsets.
For the missing-measurement test, we randomly masked 0.1%, 0.5%, or 2.0% of the individual available readings in each of the voltage magnitude, active power, and reactive power matrices. The first snapshot retained its available readings. Each missing reading was replaced with the last available noisy reading of the same quantity at the same bus before training ResNet-uPINN. We retained all 2000 snapshots in each test.
For the time-misalignment test, we selected approximately 25% of the non-slack buses. At each selected bus, the same fixed offset from the nominal time was applied to all available measurement channels. The offset applied to active and reactive power and also to voltage magnitude wherever a voltage measurement was available. The offset magnitude was 1, 3, or 5 min, with positive and negative offsets distributed as evenly as possible across the selected buses. The slack bus and the other buses remained aligned. The selected buses, offset directions, and Gaussian noise draws were held fixed across offset magnitudes. At each offset, ResNet-uPINN and the two conventional baselines used the same simulated load trajectories and impedance bounds, with the voltage inputs specified in Section 3.2.
Based on the values displayed in Table 5, across the missing-rate tests, the largest absolute changes relative to the complete measurements were 0.09 percentage points for resistance MAPE and 0.18 percentage points for reactance MAPE. At 2.0% missing measurements, the numbers of complete snapshots before filling were 272, 95, and 1 for the 33-bus, 69-bus equivalent, and 118-bus cases, respectively. The small changes in MAPE describe the combined effect of the sparse missing readings and the filling procedure.
Based on the displayed values in Table 5, at an offset of ±5 min, ResNet-uPINN reactance MAPE increased by 0.33, 0.02, and 0.07 percentage points across the three feeders in the same order. The changes for bounded linear least squares were +1.78, −0.05, and +0.69 percentage points. The increases for inverse nonlinear least squares were 1.72, 0.57, and 0.73 percentage points. ResNet-uPINN had lower resistance and reactance MAPEs than both numerical baselines at all tested offsets, including zero offset. These differences apply to the simulated load trajectories, voltage coverage, and tested noise levels. The missing-measurement test used one random mask sequence, and the time-misalignment test used one meter selection per feeder.
3.7. Equivalent Branches and Voltage-Drop Observability
The 69-bus equivalent represents 68 original line sections by 50 branches. In the series-only line model, two series sections joined at an unmetered zero-injection node carry the same current. The terminal voltage relation depends on the sum of their impedances. The equivalent impedance is the sum of the section impedances on a common voltage base. The reduction replaces consecutive sections joined by eligible unmetered zero-injection buses with a single branch. The slack bus, branching nodes, and buses with nonzero injection are retained. In the reduced-network benchmark, the two retained buses without voltage measurements are buses 3 and 4 in the original 69-bus numbering. Both are zero-injection buses that cannot be eliminated by series-branch aggregation. The uPINN predicts their voltage magnitudes. The identification errors are evaluated against the impedances of the 50 branches in the reduced network. Table A3 lists the original bus path of each equivalent branch. Of the 50 branches, 36 retain a single original segment and 14 combine segments in series.
To test whether the pattern in Figure 8 and Figure 9 also occurs on another feeder, Figure 14 relates branch APE to a voltage-drop signal-to-noise ratio (SNR) calculated after the simulation for all 50 branches of the 69-bus equivalent. For each branch, the numerator is the RMS reference terminal voltage difference across snapshots. The denominator is the RMS difference between the noise-perturbed and reference terminal voltage differences over the same snapshots. The calculation uses simulated voltages at both branch terminals, including terminals at buses without voltage measurements in the uPINN inputs. This diagnostic therefore requires simulation reference voltages as well as the noise-perturbed voltages. At 0.2% voltage noise, the 21 branches with ratios below two had resistance and reactance MAPEs of 18.92% and 23.27%. The other 29 branches had MAPEs of 4.51% and 13.43%.
Figure 14.
(a) Resistance APE and (b) reactance APE versus voltage-drop signal-to-noise ratio on the 69-bus equivalent. Each point represents one equivalent branch. The SNR is a post hoc simulation diagnostic computed from reference and noise-perturbed terminal voltages. The dashed line marks a ratio of 2.
3.8. Power Flow Calculations with Estimated Impedances
The power flow calculations assess how impedance errors affect voltage magnitudes and slack-bus power injections. A backward–forward sweep uses the identified impedances, reference slack-bus voltage, and reference non-slack active and reactive power injections. The resulting non-slack voltage magnitudes and slack-bus injections are compared with the simulation reference outputs for the same 2000 operating points used for identification.
All power flow calculations converged using impedances estimated at a voltage noise standard deviation of 0.2%. Figure 15a shows relative RMS errors in voltage magnitude of 0.0236%, 0.0420%, and 0.1185% on the 33-bus, 69-bus equivalent, and 118-bus feeders, respectively. On the 69-bus equivalent, all voltage errors fell within 0.2%, even though the branch resistance and reactance MAPEs were 10.56% and 17.56%. On the 118-bus feeder, 85.69% of the bus–snapshot pairs fell within 0.2%, and every snapshot contained at least one bus above that level. The 0.2% line marks the simulated voltage measurement noise standard deviation. Using the identified impedances, the relative RMS errors in slack-bus active and reactive power were 0.011% to 0.031% and 0.071% to 0.092%, respectively, across the three feeders. The corresponding standard deviations for active and reactive power measurement noise during identification were 1% and 2%.
Figure 15.
Power flow errors with estimated and perturbed impedances. (a) RMS, 95th-percentile, and maximum relative voltage magnitude errors using the estimated impedances. (b) Relative RMS errors in slack-bus active and reactive power after scaling all reference impedances by 0.90 or 1.10. Dashed lines mark the corresponding measurement noise standard deviations.
To examine the effect of a systematic impedance bias, we repeated the power-flow calculations after scaling all reference resistances and reactances by 0.90 or 1.10. Figure 15b reports the resulting relative RMS errors in slack-bus active and reactive power. Across the three feeders, the uniform perturbations yielded active power RMS errors of 1.17% to 1.38% and reactive power RMS errors of 1.37% to 1.82%. The corresponding voltage RMS errors were 1.34% to 1.64%. The uniform ±10% bias produced larger voltage and slack-bus power errors than those obtained with the estimated impedances on all three feeders.
4. Discussion
The method rankings depend on measurement noise, the impedance component, and the voltage coverage used in the comparison. Inverse nonlinear least squares gives the lowest reactance MAPE for the 33- and 118-bus feeders at 0.1% voltage noise. The residual estimator gives lower resistance and reactance errors than this baseline on the 118-bus feeder at 0.5% voltage noise. In the 118-bus timing comparison in Table 3, ResNet-uPINN took 148.32 s and the two numerical baselines each took less than 0.31 s.
The comparison with direct shared impedance compares the complete snapshot-specific estimation scheme, including its consistency terms, with the shared-impedance scheme. The sensitivity analysis with one training seed shows how resistance and reactance MAPE respond to changes in the voltage and impedance-consistency weights.
Under the series-only model shown in Figure 5, adjoining line sections carry the same current when their junction has zero injection. If the junction voltage is unmeasured, the endpoint measurements constrain only the sum of the section impedances. The reduction therefore depends on the topology and meter placement of this feeder. An unmodeled injection at a removed bus would invalidate the common-current assumption, and uncertainty in an equivalent impedance cannot be assigned to specific sections from these measurements alone. Among the retained branches, small voltage drops are associated with higher impedance errors. The power flow calculations quantify the effect of these errors at the simulated operating points, including the node-level and upper-tail voltage deviations in the 118-bus case.
The main comparisons assume known topology, partial coverage of retained-bus voltage magnitudes, and impedance bounds derived from simulation references. In practice, conductor type and section length can provide nominal impedances if asset records are available. Their uncertainty should be reflected in the bounds and tested independently of the reference values used to assess accuracy. Field AMI measurements and independently verified field impedances were unavailable. The simulated noise levels characterize the test conditions, and the power flow calculations quantify errors in voltage magnitude and slack-bus power injections for the simulated operating points. Field deployment also depends on identifying the metered buses, aligning voltage and power records in time, and verifying feeder connectivity. The tested voltage-noise standard deviations extend to 0.5%. The separate power-noise experiments characterize sensitivity to active and reactive power measurement errors.
5. Conclusions
This study examined how measurement noise and the magnitude of branch voltage drops affect the identification of resistance and reactance on radial feeders. The relative performance of uPINN and the numerical baselines depended on the noise source and impedance component. On the 118-bus feeder, uPINN reduced both component errors relative to inverse nonlinear least squares at 0.5% voltage noise. At the highest tested power noise levels, reactance MAPE on that feeder was 18.41% for uPINN and 16.48% for inverse nonlinear least squares. The snapshot-specific formulation also gave lower resistance and reactance MAPEs than direct shared impedance on all three feeders at the baseline noise levels.
On the 69-bus equivalent, branches with a simulation-derived voltage-drop SNR below two had resistance and reactance MAPEs of 18.92% and 23.27%, compared with 4.51% and 13.43% for the other branches. For the 69-bus equivalent, power flow calculations with impedances estimated at a voltage noise standard deviation of 0.2% gave a relative RMS error in voltage magnitude of 0.0420%, and every evaluated voltage error fell within 0.2%. On the 118-bus feeder, 85.69% of the bus–snapshot voltage errors fell within that same threshold.
The missing-measurement and time-misalignment tests used synthetic load trajectories. Using the values displayed in Table 5, after filling each missing measurement with the last available reading, random missing measurements changed resistance and reactance MAPE by at most 0.09 and 0.18 percentage points, respectively. At ±5 min offsets, the increase in ResNet-uPINN reactance MAPE ranged from 0.02 to 0.33 percentage points across the three feeders. The experiments assumed known feeder topology and used bounds derived from the simulation reference impedances. The power flow calculations used the same operating points as impedance identification, with reference power injections and slack-bus voltages held fixed. Field evaluation requires independently sourced impedance priors and measurements from actual feeders.
Author Contributions
Conceptualization, L.S.; methodology, L.S. and X.Z.; software, L.S.; validation, L.S., X.Z. and M.W.; formal analysis, L.S. and R.G.; investigation, L.S. and Z.C.; resources, X.Z. and M.W.; data curation, L.S. and Z.C.; writing—original draft preparation, L.S.; writing—review and editing, L.S., X.Z., M.W., R.G., Z.C. and W.F.; visualization, L.S.; supervision, W.F.; project administration, W.F.; funding acquisition, W.F. All authors have read and agreed to the published version of the manuscript.
Funding
This research was funded by the Science and Technology Project of State Grid Hubei Electric Power Co., Ltd., grant number 521500250012.
Data Availability Statement
Appendix A provides the modified 33-bus feeder data. Section 3.7 describes the 51-bus equivalent of the MATPOWER 69-bus case, and Appendix B lists the branch mapping in Table A3. The 118-bus feeder is based on the MATPOWER case file case118zh.m. The input measurements are simulated under the conditions described in Section 3.1.
Conflicts of Interest
Authors Lei Su, Xiaoqian Zhu, Mingjiang Wei, Ruoshi Gu, Ziya Chen, and Wanli Feng were employed by State Grid Hubei Electric Power Research Institute, State Grid Hubei Electric Power Co., Ltd. The authors declare that this study received funding from State Grid Hubei Electric Power Co., Ltd. The funder was not involved in the study design, collection, analysis, interpretation of data, the writing of this article or the decision to submit it for publication.
Appendix A
Table A1 and Table A2 list the bus loads and branch impedances for the modified 33-bus feeder. The loads at buses 2, 3, and 6 are zero in this feeder. In the 33-bus benchmark, voltage measurements are available at 31 buses. Buses 2 and 3 are the two unmeasured zero-injection buses retained in the network, and the uPINN predicts their voltage magnitudes. The branch impedances in Table A2 are in per unit on a base of 12.66 kV and 100 MVA.
Table A1.
Modified bus data of the IEEE 33-bus distribution system.
Table A2.
Branch data of the IEEE 33-bus distribution system.
Appendix B
Table A3 maps all 68 active branches in the original MATPOWER 69-bus case to the 50 branches used in the reduced feeder. The ordered bus path identifies the original segments by consecutive bus pairs. The first and last buses are the endpoints of the equivalent branch. The 18 eliminated buses have zero load and degree two in the original feeder.
Table A3.
Equivalent branch IDs and original bus paths for the 69-bus feeder.
References
- Bahrami, S.; Chen, Y.C.; Wong, V.W.S. Dynamic Distribution Network Reconfiguration with Generation and Load Uncertainty. IEEE Trans. Smart Grid 2024, 15, 5472–5484. [Google Scholar] [CrossRef] [Scilit]
- Zheng, Y.; Zhang, H.; Long, Z.; Gao, S.; Yang, Q.; Ji, H. Data-Driven Multi-Mode Adaptive Control for Distribution Networks with Multi-Region Coordination. Processes 2025, 13, 3046. [Google Scholar] [CrossRef] [Scilit]
- Yao, L.; Huang, J.; Zhang, W. Line–Household Relationship Identification Method for a Low-Voltage Distribution Network Based on Voltage Clustering and Electricity Consumption Characteristics. Processes 2024, 12, 288. [Google Scholar] [CrossRef] [Scilit]
- Li, C.; Zhang, Y.; Zhang, H.; Wu, Q.; Terzija, V. Measurement-Based Transmission Line Parameter Estimation with Adaptive Data Selection Scheme. IEEE Trans. Smart Grid 2018, 9, 5764–5773. [Google Scholar] [CrossRef] [Scilit]
- Mousavi-Seyedi, S.S.; Aminifar, F.; Afsharnia, S. Parameter Estimation of Multiterminal Transmission Lines Using Joint PMU and SCADA Data. IEEE Trans. Power Deliv. 2015, 30, 1077–1085. [Google Scholar] [CrossRef] [Scilit]
- Zhao, X.; Zhou, H.; Shi, D.; Zhao, H.; Jing, C.; Jones, C. On-Line PMU-Based Transmission Line Parameter Identification. CSEE J. Power Energy Syst. 2015, 1, 68–74. [Google Scholar] [CrossRef] [Scilit]
- Pegoraro, P.A.; Sitzia, C.; Solinas, A.V.; Sulis, S. Estimation of Line Parameters, Tap Changer Ratios, and Systematic Measurement Errors Based on Synchronized Measurements and a General Model of Tap-Changing Transformers. IEEE Open J. Instrum. Meas. 2022, 1, 9000411. [Google Scholar] [CrossRef] [Scilit]
- Laurano, C.; Pegoraro, P.A.; Sitzia, C.; Solinas, A.V.; Sulis, S.; Toscani, S. Refined Modeling and Compensation of Current Transformers Behavior for Line Parameters Estimation Based on Synchronized Measurements. IEEE Open J. Instrum. Meas. 2023, 2, 9000211. [Google Scholar] [CrossRef] [Scilit]
- Pegoraro, P.A.; Brady, K.; Castello, P.; Muscas, C.; von Meier, A. Line Impedance Estimation Based on Synchrophasor Measurements for Power Distribution Systems. IEEE Trans. Instrum. Meas. 2019, 68, 1002–1013. [Google Scholar] [CrossRef] [Scilit]
- Sun, J.; Chen, Q.; Xia, M. Data-Driven Detection and Identification of Line Parameters with PMU and Unsynchronized SCADA Measurements in Distribution Grids. CSEE J. Power Energy Syst. 2024, 10, 261–271. [Google Scholar]
- Nassaj, A.; Dobakhshari, A.S.; Terzija, V.; Azizi, S. A Hybrid Γ-Model for Distribution Feeders: Linear Parameter Estimation Using Unsynchronized Terminal Measurements. IEEE Trans. Power Syst. 2025, 40, 4395–4398. [Google Scholar] [CrossRef] [Scilit]
- Prostejovsky, A.M.; Gehrke, O.; Kosek, A.M.; Azizi, S.; Strasser, T.; Bindner, H.W. Distribution Line Parameter Estimation under Consideration of Measurement Tolerances. IEEE Trans. Ind. Inform. 2016, 12, 726–735. [Google Scholar] [CrossRef] [Scilit]
- Dutta, R.; Patel, V.S.; Chakrabarti, S.; Sharma, A.; Das, R.K.; Mondal, S. Parameter Estimation of Distribution Lines Using SCADA Measurements. IEEE Trans. Instrum. Meas. 2021, 70, 9000411. [Google Scholar] [CrossRef] [Scilit]
- Yu, J.; Weng, Y.; Rajagopal, R. PaToPa: A Data-Driven Parameter and Topology Joint Estimation Framework in Distribution Grids. IEEE Trans. Power Syst. 2018, 33, 4335–4347. [Google Scholar] [CrossRef] [Scilit]
- Jongh, S.D.; Mueller, F.; Osterberg, F.; Cañizares, C.A.; Leibfried, T.; Bhattacharya, K. Data-Driven Topology and Parameter Identification in Distribution Systems with Limited Measurements. IEEE Trans. Power Deliv. 2025, 40, 249–260. [Google Scholar] [CrossRef] [Scilit]
- Wang, X.; Zhao, Y.; Zhou, Y. A Data-Driven Topology and Parameter Joint Estimation Method in Non-PMU Distribution Networks. IEEE Trans. Power Syst. 2024, 39, 1681–1692. [Google Scholar] [CrossRef] [Scilit]
- Guo, L.; Yang, G.; Liu, Y.; Zhang, Y.; Wang, Z.; Yu, H.; Wang, Y.; Wang, C. Topology and Parameter Identification of Three-Phase Low-Voltage Distribution Network and Voltage Control Strategy Based on User Smart Meter Measurements: A Data-Driven Approach. IEEE Trans. Instrum. Meas. 2025, 74, 9006413. [Google Scholar] [CrossRef] [Scilit]
- Wang, W.; Yu, N. Estimate Three-Phase Distribution Line Parameters with Physics-Informed Graphical Learning Method. IEEE Trans. Power Syst. 2022, 37, 3577–3591. [Google Scholar] [CrossRef] [Scilit]
- Guo, Y.; Yuan, Y.; Wang, Z. Distribution Grid Modeling Using Smart Meter Data. IEEE Trans. Power Syst. 2022, 37, 1995–2004. [Google Scholar] [CrossRef] [Scilit]
- Guo, M.; Jiao, Y.; Zheng, Z.; Zhang, B.; Lin, J.; Hong, Q. Online Split-Phase Identification of Asymmetric Parameters between Distribution Lines and Ground for Unbalanced Voltage Compensation Based on Power Electronics. IEEE Trans. Power Electron. 2024, 39, 10067–10078. [Google Scholar] [CrossRef] [Scilit]
- Huang, B.; Wang, J. Applications of Physics-Informed Neural Networks in Power Systems—A Review. IEEE Trans. Power Syst. 2023, 38, 572–588. [Google Scholar] [CrossRef] [Scilit]
- Liu, S.; An, Q.; Yuan, Z.; Lei, P. Physics-Informed Neural Networks for Parameter Identification of Equivalent Thermal Parameters in Residential Buildings During Winter Electric Heating. Processes 2025, 13, 2860. [Google Scholar] [CrossRef] [Scilit]
- Jiang, B.; Qin, C.; Wang, Q. An Unsupervised Physics-Informed Neural Network Method for AC Power Flow Calculations. IEEE Trans. Power Syst. 2025, 40, 4407–4410. [Google Scholar] [CrossRef] [Scilit]
- Chen, L.; Gong, J.; Liu, L.; Lao, K.-W.; Wang, L. Enhancing Operational Efficiency in Active Distribution Networks: A Two-Stage Stochastic Coordination Strategy with Joint Dispatch of Soft Open Points and Electric Springs. Processes 2025, 13, 2825. [Google Scholar] [CrossRef] [Scilit]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2026 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.