Abstract
Proton exchange membrane fuel cells (PEMFCs) have considerable potential for frequency support in grid-forming applications. However, their transient dispatchable power is nonlinearly influenced by operating conditions, such as the oxygen excess ratio and stack temperature, thereby weakening frequency support performance by delaying power compensation during disturbances. To address this issue, a coordinated control strategy for inertia support and active power compensation is proposed that explicitly accounts for operating-state effects. Based on a dynamic PEMFC model, the effects of the oxygen excess ratio and stack temperature on transient output capability are analyzed, and a jointly corrected inertia coefficient is introduced into the virtual synchronous generator (VSG) rotor motion equation to achieve adaptive adjustment of virtual inertia under varying operating conditions. In addition, model predictive control (MPC) is incorporated into the VSG control framework, and a performance index is formulated using weighted quadratic terms of frequency variation and input power, thereby enabling the compensation power to be determined online and the PEMFC power reference to be updated accordingly. Simulation results show that the proposed strategy can effectively suppress frequency fluctuations under disturbance conditions. Compared with Conventional PI-VSG, the maximum frequency deviation and the peak rate of change of frequency (ROCOF) are reduced by 49.1% and 62.1%, respectively.
1. Introduction
After being connected to the grid, grid-forming power sources can provide equivalent inertia and frequency regulation, thereby alleviating inertia deficiency in modern power systems and improving frequency stability. However, when the source response exhibits a significant delay, inertia support cannot be promptly translated into system frequency dynamics [1,2,3]. Proton exchange membrane fuel cells (PEMFCs) are characterized by high efficiency, environmental friendliness, and rapid start-up and shut-down, and their application scope has continued to expand in recent years [4]. However, their output power is jointly affected by multiple physical processes, including gas supply, electrochemical reactions, and thermal management, leading to a pronounced delay in dynamic response [5]. Consequently, it is difficult for PEMFCs to rapidly increase their output power during sudden load changes or frequency drops, thereby weakening their frequency support capability and increasing the risk of operational limit violations.
Existing studies on the limited response capability of PEMFCs have mainly focused on two aspects, namely, mechanistic modeling and operating-condition regulation. Reference [6] compared the applicability of PEMFC models with different levels of complexity for power system dynamic analysis and discussed the trade-off between model accuracy and computational complexity. Reference [7] also established a mechanistic model that includes an air compressor, gas pipelines, a humidifier, an intercooler, and a fuel cell stack, and employed intelligent algorithms for parameter identification to improve air-supply capability and operational stability across different operating conditions. Other studies based on PEMFC system models examined the influence of operational parameters, including cathode pressure, relative humidity, temperature, and oxygen excess ratio, on stack voltage and air-supply dynamics under rapid load variations. They reported that these factors often constrain rapid power ramp-up [8,9]. At the control level, Reference [10] adopted an active disturbance rejection control approach to regulate oxygen supply and humidity in real time, thereby improving dynamic air-supply performance under different load conditions. In addition, several studies combined online parameter estimates with adaptive model predictive control (MPC) to improve power tracking performance in DC microgrids [11]. Although existing work has extensively investigated the mechanistic characteristics of PEMFCs and the regulation of their operating conditions, a dedicated discussion is still lacking on how power-response delays caused by physical factors, such as temperature and oxygen excess ratio, propagate into frequency dynamics under grid-forming operation.
To assess the feasibility of PEMFC participation in frequency regulation, existing studies have incorporated PEMFCs into primary frequency-control frameworks. Reference [12] employed fuzzy logic to achieve primary frequency regulation of PEMFCs in an islanded microgrid, whereas Reference [13] examined the dynamic frequency response of fuel cells using a conventional droop mechanism. Reference [14] further adopted an improved sliding-mode control method to design maximum-power-point-tracking and primary-frequency-regulation strategies. It enhanced frequency regulation performance by introducing a temperature- and pressure-dependent regulation coefficient. In general, such methods rely primarily on active-power regulation for primary frequency control, and their effects are primarily reflected in reduced steady-state frequency deviations. From the perspective of the inertia support required for grid-forming operation, however, these studies have not yet established a corresponding inertia-response mechanism during the initial stage of disturbances. Therefore, their adaptability to dynamic frequency support remains limited.
With the high penetration of renewable energy, grid-forming control has attracted increasing attention in modern power systems and has been introduced into frequency-support studies [15]. Among these methods, the virtual synchronous generator (VSG) enhances dynamic frequency response by establishing an equivalent inertia loop based on the synchronous generator’s rotor motion [16]. However, for power sources such as PEMFCs, the inherent slow dynamics of gas supply and thermal processes limit rapid increases in output power. As a result, during sudden load changes, the inertia support expected from the VSG cannot be promptly translated into actual active-power output. To address this issue, References [17,18] adaptively adjust parameters, such as the VSG’s virtual rotational inertia, to improve frequency response. However, these adjustments remain prone to delay, making it difficult to achieve both effective disturbance suppression and rapid response during severe frequency fluctuations.
To enhance the dynamic performance of grid-forming control during fast disturbances, current research has begun to integrate MPC with VSGs [19]. Some studies have incorporated the rate of change of frequency (ROCOF) into the prediction model and formulated the optimization objective using weighted terms of frequency deviation and VSG output, thereby enabling online computation and feedback regulation of power increments [20,21]. Other studies have integrated the coupling effect of active-power regulation on voltage into the predictive model while simultaneously optimizing both active and reactive power to coordinate frequency and voltage dynamics [22]. In addition, MPC has been extended to flexible hybrid microgrids with plug-and-play capability by combining logic control with classical MPC to address optimal control and energy management under multiple operating modes [23]. Methods such as adaptive inertia parameter tuning, coordinated adaptive parameter adjustment, and variable-weight MPC have also been employed to enhance the frequency-regulation performance of VSGs [24,25,26]. However, these methods are mainly developed for fast-response sources such as battery energy storage systems, where inertia regulation is typically updated online according to frequency deviation, power mismatch, or VSG state variables, and the source side is assumed to be capable of providing the required support power within a short time. For PEMFCs, by contrast, the transient realizable power is jointly affected by multiple dynamic processes, including gas supply, gas transport, electrochemical reaction, and thermal-state evolution, and it also varies with operating conditions such as stack temperature and oxygen excess ratio. Under such conditions, if an existing adaptive-inertia or MPC-VSG design is directly adopted, the active-power support demand associated with the inertia increase during the initial disturbance stage may not fully match the actual transient supply capability of the PEMFC source, thereby limiting the effectiveness of inertia support. Therefore, in PEMFC-based grid-forming frequency support, in addition to introducing adaptive inertia and MPC mechanisms, it is also necessary to consider the coordination between inertia regulation, power compensation, and the dynamic capability of the source side. Based on this, this paper focuses on the inertia-support problem of PEMFCs under grid-forming operation, corrects the equivalent inertia using temperature and oxygen excess ratio, and combines it with MPC compensation to construct a coordinated control strategy, so as to enhance the frequency-support effect during the initial stage of disturbances and improve the source-side response capability to frequency-support demand.
To address the coordination issue between frequency-support demand and source-side response capability of PEMFCs under varying stack temperature and oxygen excess ratio, this paper proposes a grid-forming frequency-support strategy. A grid-forming PEMFC power-generation system model is established in MATLAB/Simulink, and the effectiveness of the proposed strategy is validated under typical load disturbances.
The main contributions of this paper are summarized as follows:
- (1)
- A dynamic PEMFC model that accounts for stack temperature, oxygen excess ratio, and electrochemical characteristics is established to characterize the transient power response and the variation pattern of dispatchable power under different operating conditions, thereby providing a source-side dynamic basis for the design of frequency-support strategies.
- (2)
- To address discrepancies in transient capacity caused by fluctuations in stack temperature and oxygen excess ratio, a jointly corrected equivalent inertia coefficient is introduced into the VSG rotor motion equation, enabling the virtual inertia to be adjusted online with the operating state and thereby improving frequency support during the initial stage of disturbances.
- (3)
- An MPC-based compensation channel is introduced into the VSG active-power loop. By coordinating compensation-power regulation with the equivalent inertia corrected by operating state variables, the proposed strategy improves frequency recovery and source-side power response under PEMFC dynamic constraints. Comparisons with Conventional PI-VSG, Fixed-Inertia MPC-VSG, and Uncorrected Adaptive-Inertia MPC-VSG are conducted under the same operating conditions and disturbance scenarios.
2. PEMFC System and Modeling
The proposed configuration of the PEMFC-VSG system is depicted in Figure 1. It consists of a PEMFC power generation system, a Boost DC-DC converter, and a VSG-regulated DC/AC inverter. The PEMFC’s output voltage as a direct current power source fluctuates with changes in load. To meet the downstream converter’s voltage requirements, a BOOST converter is placed at the front stage to boost and stabilize the fuel cell output, and constant-power control maintains the output power consistent with the VSG reference power. The downstream DC/AC converter employs VSG control, providing inertia support and frequency regulation by emulating the rotor dynamics and electromagnetic equations of a synchronous generator, thereby rendering the fuel cell output steadier and enhancing the system’s dynamic support potential.
Figure 1.
PEMFC-VSG system structure diagram.
2.1. PEMFC Stack Voltage Model
To capture the main dynamic characteristics of the PEMFC while meeting the needs of system-level frequency-support analysis and control design, this study adopts the following assumptions in the modeling process:
- (1)
- The gas species in each region of the stack obey the ideal gas law, and their variations are described by the average state of each region, without considering spatial nonuniformity in the flow channels and catalyst layers.
- (2)
- Water production, transport, and hydration state in the membrane are treated in an averaged manner, while spatial variations of water content and local humidity inside the membrane are neglected.
- (3)
- The thermal state of the stack is represented by an average temperature, which can vary with operating conditions, while temperature gradients and local overheating inside the stack are not considered.
On this basis, the stack voltage model is further established. The PEMFC stack voltage varies nonlinearly with load current. It is affected by cathode pressure, oxygen excess ratio, partial pressures of gas species, temperature, and membrane hydration state. Therefore, the voltage of a single fuel cell can be expressed as
where ENernst is the reversible potential, and Vact is the activation polarization loss voltage, Vohmic is the ohmic polarization loss voltage, and Vcon is the concentration polarization loss voltage.
By considering only the effects of ambient temperature and reactant gas pressure, and assuming that the Gibbs free energy of hydrogen is completely converted into electrical energy, the Nernst equation can be obtained as
where R signifies the universal gas constant, quantified at 8.3144 J/(mol·K). T indicates the operational temperature of the fuel cell stack, PH2, PO2 are the partial pressures of hydrogen and oxygen, respectively, and F is Faraday’s constant, valued at 96,485 C/mol.
The activation overpotential can be expressed as
where I is the fuel cell current, and ξ1, ξ2, ξ3, ξ4 are parameters obtained by experimental fitting. Based on the experimental data analysis, the values of these parameters can be determined to accurately calculate the activation polarization overpotential as follows:
where A is the active area of the proton PEMFC, and CO2 and CH2 denote the dissolved concentrations of H2 and O2 at the gas–liquid interface, respectively. Their values can be obtained from Henry’s law [27].
According to Ohm’s law, the ohmic overpotential can be expressed as
where i is the current density, RC is the equivalent resistance of the electronic conduction path, and RM is the equivalent resistance of the proton conduction pathway, computed as follows:
where t is the ionic conductivity and the thickness of the PEMFC. The value of t is contingent upon the membrane type. θm is the water content of the proton exchange membrane.
During fuel cell operation, fluctuations in reactant availability lead to concentration polarization loss, which can be expressed as
where n is an empirical constant with a value of 8, and m is calculated as follows:
2.2. Anode Flow Channel Model
The gas in the anode flow channel predominantly consists of hydrogen and water vapour. To determine the exact hydrogen partial pressure during fuel cell operation, it is crucial to develop a dynamic model of the anode flow channel. A mass conservation equation for the anode flow channel is derived, assuming that water vapour does not participate in the reaction and that only its convective inflow and outflow are accounted for, while the current density defines the hydrogen consumption term.
where mH2,react is the hydrogen consumption rate, MH2 denotes the molar mass of hydrogen, and F represents Faraday’s constant.
The fluctuation in hydrogen mass within the anode flow channel is governed by the mass conservation equation as follows:
where mH2,in is the inlet hydrogen mass flow rate of the anode, and mH2,out is the outlet hydrogen mass flow rate.
The partial pressure of gas can be articulated in accordance with the ideal gas equation of state as follows:
where Rg,H2 is the gas constant of hydrogen, and Van is the anode volume.
The fluctuation of water vapour mass in the anode flow channel can be articulated by the component mass conservation equation:
where mv,an,in is the inlet water vapor mass flow rate of the anode, and mv,an,out is the outlet water vapor mass flow rate.
By further applying the ideal gas law, the anode-side water vapor partial pressure can be obtained in the same manner, and the theoretical maximum water vapor content can be determined from the saturated vapor pressure relation at the given stack temperature. Therefore, the anode relative humidity is expressed as follows:
where xv,an is the mole fraction of water vapor. Pv,an is the partial pressure of water vapor inside the anode.
2.3. Cathode Flow Channel Model
The oxygen dynamics on the cathode side are governed by the conservation of component mass, the intake supply, the outlet discharge, and the electrochemical consumption term. At the same time, nitrogen does not participate in the reaction, and only its convective inflow and outflow are considered. Water vapor includes both the inlet convective term and the reaction-generation term, and is discharged through the outlet.
The oxygen consumption rate and the water vapor generation rate are related to the current density:
where mO2,react is the oxygen consumption rate attributed to the cathodic reaction, mv,gen is the water generation rate, MO2 and Mv are the molar masses of oxygen and water, respectively.
This is how the mass of oxygen in the cathode flow path is described:
where mO2,in is the oxygen inlet mass flow rate, and mO2,out is the oxygen outlet mass flow rate.
The partial pressure of oxygen can be expressed as follows:
where Rg,O2 is the gas constant of oxygen, and Vca is the cathode volume.
The changing mass of water vapor in the cathode flow channel is represented as
where mv,ca,in refers to the mass flow rate of water vapor at the cathode inlet, while mv,ca,out corresponds to that at the cathode outlet.
From the cathode-side water vapor partial pressure and the saturated vapor pressure relation, the cathode relative humidity can be obtained as
2.4. Transmembrane Water Transport Model
To enhance the model’s fidelity under practical operating conditions, a transmembrane water transport model is further established in this paper, and the dynamic membrane water content is determined using real-time relative humidity from the anode and cathode flow channel models. The average water activity of the PEMFC can be derived from the anode and cathode water activities, given that water activity is synonymous with relative humidity:
where aan is the anode water activity, aca is the cathode water activity, and am is the water activity.
The water contents of the anode, cathode, and proton exchange membrane are determined using the Springer empirical correlation as follows:
where i = an, ca, m.
3. Improved MPC-VSG Control Strategy Based on PEMFC
The system consists of a PEMFC power generation unit, a Boost DC-DC converter, a VSG inverter, and loads, as illustrated in Figure 2. The PEMFC functions as the DC-side power supply and runs under continuous power management through the dual-loop-controlled Boost converter, with the power reference jointly established by the droop characteristic and the MPC compensation. The reference power is then utilised in the VSG rotor dynamic equation to replicate the inertia and damping properties of a synchronous generator, facilitating dynamic frequency regulation and stabilisation. Meanwhile, the PEMFC operating states, including temperature and oxygen excess ratio, are incorporated into the equivalent inertia model to enable adaptive regulation of the VSG inertia, thereby capturing the fuel cell’s actual output capability under diverse operating conditions.
Figure 2.
Structure and control strategy of the grid-forming PEMFC power generation unit.
3.1. Conventional Virtual Synchronous Generator Control Method
Under grid-forming operating conditions, the inverter must establish the grid frequency and provide inertia support, whereas conventional control methods struggle to produce an effective inertial response. Given the limited dynamic power response of PEMFC, this paper adopts VSG control on the inverter side to achieve frequency support.
The VSG features a governor loop that enables primary frequency regulation in grid-forming proton exchange membrane fuel cell systems. The fuel cell’s output power is automatically adjusted to compensate for the discrepancy between the system frequency and its nominal value, thereby achieving primary frequency regulation. A PI integral loop is implemented to eliminate steady-state frequency variation and achieve coordination between primary and secondary frequency regulation. Simultaneously, by implementing a corresponding dampening signal, the active power loop of the VSG can demonstrate inertial properties with dynamic behaviour akin to that of a synchronous generator.
The frequency adjustment of a standard VSG is attained by integrating the rotor motion equation with droop control, articulated as follows:
where Pm is the mechanical power supplied by the prime mover, Pe is the electromagnetic output power of the synchronous generator, Pset is the rated power of the synchronous generator, J is the rotor moment of inertia, D is the damping coefficient associated with the synchronous generator, ω is the mechanical angular frequency, and ω0 is the rated angular frequency, Kp is the frequency droop coefficient.
The VSG voltage regulation is implemented using droop control, which may be expressed as follows:
where Um is the reference RMS voltage, Uref is the rated RMS voltage, Qset is the reactive power setpoint, Qe is the actual reactive power of the synchronous generator, and Kq is the voltage-reactive power droop coefficient.
Figure 3 illustrates the traditional PI-controlled secondary frequency regulation of the VSG.
Figure 3.
Block diagram of the traditional PI-controlled secondary frequency regulation VSG.
3.2. Physics Informed Adaptive Inertia Design
To elucidate the correlation between active power and frequency fluctuations in the VSG. Equation (21) is rearranged as follows:
As seen in Equation (23), when the system reaches a constant state, both sides of the equation are zero. When an active power disturbance occurs, the angular frequency remains continuous at the instant of disturbance. In contrast, the power imbalance is reflected through the inertia loop as a positive or negative accelerating effect. For example, if the input-side power decreases suddenly, the inertia loop produces a positive accelerating effect, causing the frequency to rise. Thereafter, under the combined regulation of the virtual damping and active power droop loops, the accelerating effect is gradually weakened, and the power balance is re-established, so that the system converges to a new operating point, with the frequency deviation determined by the droop characteristic, exhibiting a static law similar to that of primary frequency regulation.
Furthermore, the traditional VSG does not impose a specific limit on the rate of frequency shift during the initial phase of a disturbance, and the ROCOF in this stage is mainly determined by the power mismatch through the inertia channel. Hence, the value of virtual rotational inertia significantly affects the rate of change. Therefore, an adaptive rotational inertia regulation mechanism can be introduced into the VSG framework to enhance the comprehensive suppression capability for both frequency deviation and ROCOF.
When the frequency variation is small, with the damping term neglected, Equation (23) can be simplified as follows:
When the active power deficit is given, Equation (24) is further simplified, and the relationship between the ROCOF and the moment of inertia can be obtained as follows:
It can be obtained from Equation (25) that df/dt is inversely proportional to J, that is, a larger moment of inertia results in a smaller ROCOF. A larger inertia is more effective in suppressing system frequency fluctuations, but it also prolongs the frequency recovery time. Consequently, it is essential to execute adaptive regulation of the moment of inertia, with the corresponding control algorithm delineated as follows:
where k0 is the adaptive coefficient of the moment of inertia.
To further account for the influence of PEMFC source-side operating conditions on transient support capability, a weighted correction factor K based on stack temperature and oxygen excess ratio is introduced. Equation (26) gives the basic form of inertia-adaptive regulation driven by power mismatch. It can reflect the effect of disturbance severity on inertia demand, but it does not yet capture differences in source-side realizable capability across operating conditions. For a PEMFC, stack temperature and oxygen excess ratio affect not only the output capability but also the transient power margin available from the source during a disturbance. If the same inertia-enhancement rule is applied across different operating conditions, the resulting support demand may become inconsistent with the source’s actual realizable capability. For this reason, temperature and oxygen excess ratio are normalized separately, and a combined correction factor K is constructed.
where , , , are the lower and upper safe operating limits of the fuel cell temperature and the oxygen excess ratio, respectively. is the reference oxygen excess ratio.
The influence coefficients , are defined to reflect the effects of temperature and oxygen excess ratio on the regulation of system inertia, respectively. The comprehensive correction coefficient K is expressed as follows:
The adaptive coefficient of the moment of inertia Keq is expressed as follows:
Therefore, Equation (26) can be rewritten as follows:
Equation (30) shows that the correction factor K acts on the adaptive coefficient and regulates the variation range of Jeq during the disturbance process. When the operating point lies in the middle of the safe operating region, the adjustment margins for stack temperature and oxygen excess ratio are sufficient. In this case, K takes a smaller value, and Jeq can return more quickly after the disturbance, maintaining the response speed during the recovery stage.
As the operating point approaches the constraint boundary, the source-side short-term power regulation capability weakens. Under this condition, K increases, and the rise in Jeq becomes more pronounced. This strengthens the inertial buffering effect in the initial stage of the disturbance, suppresses the ROCOF peak, and reduces the dependence on rapid source-side power ramping. Figure 4 illustrates the block structure of the adaptive inertia VSG control method.
Figure 4.
Block diagram of the adaptive-inertia VSG control.
3.3. Establishment of the Adaptive-Inertia MPC-VSG Model
After introducing adaptive inertia, the VSG can suppress ROCOF to some extent during disturbances, but the response speed of online inertia adjustment still limits its regulation process. When the disturbance magnitude is large or changes rapidly, inertia correction alone may still be insufficient to reduce the instantaneous power mismatch over time, leading to a large ROCOF peak at the initial stage.
To further enhance frequency support during the early disturbance period, this paper incorporates an MPC-based rolling optimization mechanism into the adaptive-inertia VSG framework. It calculates the active-power compensation term Pmpc online based on the measured load power Pe. In the control structure, Pmpc acts on the VSG active-power channel and, together with the original mechanical power command Pm, forms the updated reference power Pref = Pm + Pmpc. The PEMFC output power Pfc is regulated by the outer power loop to track Pref, thereby further improving active-power support during the initial disturbance stage, in addition to inertia regulation. The corresponding control structure is shown in Figure 5.
Figure 5.
Block diagram of the adaptive-inertia MPC-VSG control.
Owing to the integration of the active power compensation Pmpc, Equation (23) can be rewritten as follows:
At the instant of a load disturbance, Pmpc can compensate the load power Pe, thereby effectively reducing the ROCOF; with proper compensation, the system frequency may even remain unchanged. MPC first calls for the establishment of a mathematical model. By integrating Equations (21) and (30), the rotor motion equation of the VSG with adaptive inertia can be articulated in state space representation as follows:
where Pe is the measurable external disturbance variable, Pm is the controllable input variable, and yc(t) denotes the output equation.
By applying forward Euler approximation to discretize Equation (32), the discrete-time model with a sampling period of Ts can be derived as follows:
where , ,
This study establishes both the prediction horizon and the control horizon at 3 to reconcile computational accuracy with online solution efficiency, thereafter defining the three-step anticipated output vector and the three-step control input vector as follows:
Accordingly, the predicted outputs of the system over the next three steps can be calculated by the following prediction equation:
where
The objective function reflects the trade-off requirements considered in this paper for control performance. In addition to driving the output to be close to zero, large variations in the control input are also undesirable; therefore, the following objective function is adopted:
where and are the weighting matrices.
R(k + 1) is the designated reference sequence of the control output, articulated as follows:
where is the weighting factor for frequency variation, is that for input power variation.
The frequency-increment term in the cost function strengthens the suppression of frequency fluctuations during the disturbance period, while the input-power term constrains the magnitude and rate of change of the compensation-power command, preventing the rolling optimization from generating overly aggressive control actions. This study focuses on frequency-support performance in the initial stage of a disturbance, and therefore, a relatively large weight is assigned to the frequency-increment term. In the PEMFC system, the rapid establishment of source-side power is jointly constrained by dynamic processes, including gas supply, gas transport, and electrochemical reactions. Excessively fast compensation-power requests may therefore exceed the source’s actual response capability on a fast time scale. Accordingly, the input-power term is also retained with a certain weight, so that the generated compensation power can enhance frequency-support performance while remaining compatible with the dynamic characteristics of the PEMFC source. The weighting factors are finally selected as α = 10 and β = 1. The compensation power used to suppress frequency fluctuations is then obtained through rolling optimization.
3.4. Solution of the Adaptive-Inertia MPC-VSG Model
The objective function Equation (41) is reformulated as a quadratic programming problem as follows:
To facilitate the solution of Equation (43), an auxiliary variable is defined as follows:
Then Equation (43) can be reformulated as follows:
Substituting the prediction Equation (37) into Equation (44) yields:
where
Therefore, Equation (45) becomes
where , and the extremum condition of is given by
The optimal solution is obtained as follows:
Furthermore, since , Equation (43) yields a minimum solution. Substituting Equation (40) into Equation (45) gives the solution to the optimization problem Equation (43), hereby yielding the optimal control sequence at time k:
To assess the online implementability of the proposed adaptive-inertia and MPC-coordinated control strategy, the computational burden and real-time execution conditions are analyzed. The adaptive inertia loop primarily involves parameter updates and algebraic operations, thereby imposing a relatively low computational load. In contrast, the MPC compensation loop requires a rolling optimization problem to be solved at each control interval. Since both the prediction and control horizons are set to 3, and only a three-dimensional control increment sequence is solved at each interval, with only the first element applied, the overall online optimization scale remains small.
Given that the thermal and gas-supply dynamics of the PEMFC are much slower than the inner-loop dynamics of power electronic converters, the discrete sampling period of the upper-layer MPC controller is set to 5 ms to balance the need for fast frequency support during the initial disturbance stage with online implementability. Program-level execution time statistics were obtained on a Lenovo Legion R9000P 2023 laptop (Lenovo, Beijing, China). The device was equipped with an AMD Ryzen 9 7945HX processor at 2.50 GHz and 16.0 GB RAM. MATLAB R2023b was used together with the profile tool and the quadprog solver. The results show that the average single-step computation time of the control algorithm is 1.47 ms, which is below the 5 ms control period, indicating that the proposed method has a certain potential for online implementation at the program level.
The flowchart of the adaptive inertia MPC-VSG is shown in Figure 6.
Figure 6.
Block diagram of the adaptive-inertia MPC-VSG control flow.
As illustrated in Figure 6, the first element of ∆Pm∗(k) is taken as the active power compensation Pmpc and fed into the system for rolling optimization. The VSG reference power is Pref = Pm + Pmpc, then set to Pfc is controlled to follow the VSG reference power Pref.
4. Simulation Verification
4.1. Effects of System Variables on the PEMFC System
Based on the above modeling framework, a comprehensive PEMFC system model is developed, from which polarisation and power density characteristics are derived to examine the dynamic response to fluctuations in temperature, oxygen excess ratio, and gas pressure. The major parameters utilised in the model are encapsulated in Table 1.
Table 1.
Parameters of the PEMFC system.
4.1.1. Effect of Load Current on PEMFC Performance
Figure 7 illustrates the standard polarity and power density curves of the PEMFC. Changes in polarisation properties and power density directly evidence the impact of load current on fuel cell performance.
Figure 7.
Combined current density–voltage and power curves.
The operational parameters are established as follows: temperature at 70 °C, cathode pressure at 0.2 MPa, anode pressure at 0.2 MPa, and relative humidity of both anode and cathode gases at 100%. Conclusions may be drawn from the attributes of change in the polarization curve and the power density curve:
The PEMFC system demonstrates significant nonlinear properties. As the load current density increases, the output voltage decreases consistently, while the power density initially increases and then decreases. At low current density, voltage loss is primarily influenced by activation polarisation; in the medium range, activation loss stabilises while ohmic loss increases linearly; at elevated current density, ohmic loss continues to escalate, and concentration polarisation becomes more pronounced.
To analyze the dynamic response under a sudden load change, the simulation time is set to 50 s, and a step disturbance is applied to the load current at t = 25 s, increasing it from 160 A to 250 A to simulate a sudden load increase, and the following validation is conducted:
4.1.2. Effect of Anode and Cathode Gas Supply on PEMFC Performance
The working temperature of the PEMFC is established at 70 °C, the cathode pressure at 0.2 MPa, and the gas humidity at the anode and cathode at 100%. The output power curves for anode hydrogen pressures of 0.1–0.3 MPa and cathode oxygen pressures of 0.1–0.3 MPa are presented in Figure 8.
Figure 8.
Effect of anode and cathode gas supply on PEMFC output power: (a) anode hydrogen pressure; (b) cathode oxygen pressure.
As shown in Figure 8, increasing the reactant gas pressure is generally beneficial to PEMFC performance. This effect can be explained by three aspects. First, the reversible potential increases with pressure. Second, the exchange current density becomes larger, which reduces activation polarization loss. Third, the reactant concentration inside the cell, including that in the catalyst layer, increases, which facilitates the electrochemical reaction.
Therefore, a moderate increase in gas pressure can be used to improve cell performance. However, higher pressure also places stricter requirements on system sealing and the pressure resistance of the proton exchange membrane. In PEMFC systems using air as the oxidant, pressurization also increases compressor power consumption, which leads to additional system power loss.
Meanwhile, the influence of anode hydrogen pressure on output power is weaker than that of cathode air pressure, and the difference between the two becomes more pronounced as current density increases. Therefore, in the design of the gas supply system, priority should be given to the regulation strategy of the air-side pressure.
4.1.3. Effect of Stack Temperature on PEMFC Performance
The cathode and anode pressures of the PEMFC are both set to 0.2 MPa, and the relative humidity of the gases is 100%. The PEMFC output power curves under different temperatures from 40 °C to 80 °C are plotted, as shown in Figure 9.
Figure 9.
Effect of temperature on PEMFC output power.
Figure 9 illustrates that elevating the operating temperature markedly improves the output performance of the PEMFC. This enhancement is primarily due to increased catalytic activity in the electrochemical reactions and expedited hydrogen-ion transport, which reduces membrane resistance and associated ohmic losses while simultaneously facilitating water transport within the proton exchange membrane. Excessive operating temperatures elevate the partial pressure of water vapor and diminish the effective concentration of reactant gases, leading to a gradual decline in performance enhancement and potentially hastening membrane breakdown, thereby reducing its operational lifespan. Therefore, increasing the operating temperature can improve fuel cell performance, but only within a certain range, and an optimal operating temperature exists for each PEMFC. Empirical experience indicates that the optimal operating temperature generally lies between 60 °C and 80 °C.
4.1.4. Effect of Gas System Dynamics on PEMFC Performance
The PEMFC gas supply system comprises an anode hydrogen subsystem and a cathode air subsystem. Hydrogen is delivered from a high-pressure tank and can be swiftly adjusted via a proportional valve in relation to the cathode pressure; thus, its dynamic effect can be neglected. In contrast, oxygen is supplied by an air compressor, which introduces a significant time delay and parasitic power consumption. Therefore, the transient performance of the PEMFC is primarily determined by the cathode air-supply subsystem. Insufficient airflow rate to meet the increased oxygen demand from a rapid load change may cause a rapid decline in output voltage and power, potentially leading to oxygen deprivation and permanent damage to the fuel cell stack. Conversely, further increasing the airflow rate after the oxygen demand has been satisfied results in oxygen saturation, where the power improvement becomes marginal while the net system power decreases due to additional compressor consumption.
The cathode and anode pressures of the PEMFC are both set to 0.2 MPa, and the relative humidity of the gases is 100%. The PEMFC output power curves under different oxygen excess ratios from 1.5 to 3.5 are plotted, as shown in Figure 10.
Figure 10.
Effect of oxygen excess ratio on PEMFC output power.
As illustrated in Figure 10, an increased oxygen excess ratio improves cathode oxygen supply and stack power output by alleviating oxygen transport limitations. Nevertheless, the power gain gradually saturates at higher ratios. For a given PEMFC system, an optimal oxygen excess ratio exists for each load current, and a value of 2 is commonly adopted in practice.
4.2. Verification of Frequency Support Performance Under Active Power Disturbance
4.2.1. Effect of Stack Temperature on Frequency Support
The active load is set to 150 kW, and a 50 kW load step increase is applied at 1.5 s. The PEMFC follows the VSG power command to achieve secondary frequency regulation. The temperatures are set to 50 °C, 60 °C, and 70 °C, respectively, and the oxygen excess ratio is set to 2. The system frequency and output power are shown in Figure 11. The VSG control parameters are given in Table 2.
Figure 11.
Comparison of System frequency and output power under different temperatures: (a) system frequency; (b) PEMFC output power.
Table 2.
Parameters of the VSG control.
Figure 11 shows that under load-step conditions, the dynamic frequency and output power characteristics of the PEMFC exhibit considerable variation across distinct operating temperatures. As temperature rises, the pace of the electrochemical reaction increases, while the activation and ohmic overvoltages decrease due to enhanced membrane conductivity, resulting in reduced equivalent internal resistance and increased transient power responsiveness of the stack. At higher temperatures, the PEMFC exhibits faster power escalation after a load step and maintains a higher steady-state output level.
From the standpoint of frequency response, the frequency deviation is reduced, the recovery time is diminished, and a more pronounced recovery slope is observed.
In the 50–60 °C range, the frequency drop is significantly reduced, and recovery is faster, while both the power ramping rate and the steady-state output are markedly improved.
In the 60–70 °C range, performance still increases, but with a clearly diminished improvement margin, indicating a bottleneck effect. As membrane conductivity saturates, the reaction rate enhancement becomes marginal, and water evaporation from the membrane intensifies, potentially increasing membrane resistance.
These results indicate that higher temperatures are not always better, and a moderate temperature rise can achieve an optimal balance among performance, lifetime, and safety.
4.2.2. Effect of Oxygen Excess Ratio on Frequency Support
The active load is set to 150 kW, and a 50 kW load step increase is applied at 1.5 s. The PEMFC follows the VSG power command to achieve secondary frequency regulation. The temperature is set to 70 °C, and the oxygen excess ratios are set to 1.5, 2, 2.5, and 3, respectively. Figure 12 illustrates the system frequency.
Figure 12.
System frequency under different oxygen excess ratios.
As shown in Figure 12, a higher oxygen excess ratio indicates a higher oxygen concentration and flow rate on the cathode side. Following the load step, at an oxygen excess ratio of 1.5, the frequency decline is most pronounced, and recovery is the most gradual. As the oxygen excess ratio increases to 2 and 2.5, the frequency nadir rises gradually, and the recovery curve becomes steeper, indicating an enhanced frequency regulation capability of the system.
When the oxygen excess ratio rises to 3, compressor power consumption increases further, and the frequency dip is additionally mitigated; however, the improvement is marginal compared with that at 2.5. A moderate increase in the oxygen excess ratio can enhance dynamic support performance while avoiding reductions in system efficiency and accelerated component aging caused by excessively high oxygen excess ratios.
4.2.3. Performance Comparison of Primary and Secondary Frequency Regulation
Under rated operating conditions, the active load is set to 150 kW, and a 50 kW load step increase is applied at 1.5 s. The temperature is set to 70 °C, and the oxygen excess ratio is set to 2. The system frequency responses during primary and secondary frequency regulation are shown in Figure 13.
Figure 13.
System frequency variation: (a) primary frequency regulation; (b) System frequency during secondary frequency regulation.
Figure 13 shows the frequency response under primary frequency regulation with only VSG control. It can be observed that although the VSG adjusts its output according to the droop characteristic, the PEMFC does not promptly increase its power. As a result, after the frequency drop, the system frequency remains below 50 Hz and cannot recover to the rated value. After introducing the secondary frequency regulation, as shown in Figure 13b, the PEMFC gradually increases its output power in response to the frequency deviation, enabling the frequency to rise back to 50 Hz after a brief drop and thus achieving full recovery from the disturbance.
4.3. Comparison of Frequency Support Performance Under Different Control Strategies
To further illustrate the frequency-support performance of the proposed strategy and to clarify its distinction from existing adaptive-inertia MPC-VSG methods, a unified comparative study is conducted under the same disturbance scenario as in Section 4.2.3. Under the same PEMFC operating conditions, the system is evaluated using four control schemes: Conventional PI-VSG, Fixed-Inertia MPC-VSG, Uncorrected Adaptive-Inertia MPC-VSG, and State-Corrected Inertia MPC-VSG. The first two correspond to the conventional VSG baseline and the MPC-VSG baseline with fixed inertia, respectively. The third scheme retains the adaptive-inertia and MPC compensation framework but does not incorporate operating-state correction. The fourth scheme further introduces operating-state correction into the equivalent inertia regulation and coordinates it with MPC compensation. The simulation outcomes are illustrated in Figure 14 and Figure 15.
Figure 14.
Equivalent inertia coefficient Jeq.
Figure 15.
Frequency-support responses of different control strategies in the PEMFC system: (a) system frequency; (b) ROCOF; (c) PEMFC output power; (d) MPC compensation power.
As shown in Figure 14, the conventional strategy employs a fixed virtual inertia. When a sudden load increase occurs, the proposed improved strategy raises Jeq to a peak value to suppress ROCOF, and then gradually reduces it as the power mismatch decreases, finally stabilizing around 1.3.
As shown in Figure 15a, the minimum system frequencies under Conventional PI-VSG, Fixed-Inertia MPC-VSG, State-Corrected Inertia MPC-VSG, and Uncorrected Adaptive-Inertia MPC-VSG control are 49.839 Hz, 49.867 Hz, 49.892 Hz, and 49.887 Hz, respectively. The corresponding maximum frequency deviations are 0.161 Hz, 0.133 Hz, 0.108 Hz, and 0.113 Hz. Compared with Conventional PI-VSG, Fixed-Inertia MPC-VSG, and Uncorrected Adaptive-Inertia MPC-VSG, the proposed strategy reduces the maximum frequency deviation by 49.1%, 23.1%, and 4.6%, respectively. These results indicate that MPC-based active-power compensation improves the post-disturbance frequency response, while the introduction of adaptive inertia further enhances the inertial buffering effect during the initial disturbance stage. Moreover, by incorporating stack temperature and oxygen excess ratio into the inertia correction process, the proposed strategy achieves the highest frequency nadir among the four schemes, indicating a better match between inertia-support demand and the transient realizable power of the PEMFC under the current operating condition.
As shown in Figure 15b, the peak ROCOF magnitudes under Conventional PI-VSG, Fixed-Inertia MPC-VSG, State-Corrected Inertia MPC-VSG, and Uncorrected Adaptive-Inertia MPC-VSG control are 0.47 Hz/s, 0.35 Hz/s, 0.29 Hz/s, and 0.32 Hz/s, respectively. Compared with the other three control schemes, the proposed strategy achieves lower maximum ROCOF values, with reductions of 62.1%, 20.7%, and 10.3%, respectively. These results indicate that the proposed strategy more effectively suppresses the rapid frequency excursion immediately after the disturbance. The comparison also shows that adaptive inertia helps strengthen the inertial buffering capability during the initial disturbance stage. At the same time, operating-state correction further improves the matching between inertia regulation and the PEMFC transient response.
As shown in Figure 15c, the PEMFC output power under all four control schemes eventually reaches a new steady-state value after the disturbance, but the transient response processes are different. Conventional PI-VSG exhibits the slowest power rise, while the introduction of MPC improves the source-side power response. The proposed control strategy approaches the new steady-state value earlier, indicating that it can improve the tracking speed of the PEMFC to the support power command.
As shown in Figure 15d, all three MPC-VSG schemes generate compensation power rapidly during the initial disturbance stage, but their dynamic responses are different. Compared with the other two MPC-VSG schemes, the proposed control strategy provides a stronger compensation-power response during the initial frequency-drop stage, indicating a stronger active-power support capability at the beginning of the disturbance. After being superimposed on the PEMFC power reference, this compensation term helps improve the source-side response to the frequency-support demand.
In summary, Conventional PI-VSG exhibits the deepest frequency dip and the largest ROCOF peak, indicating a relatively weak frequency-support capability during the initial disturbance stage. Fixed-Inertia MPC-VSG improves the active-power response through MPC compensation and reduces the initial frequency deviation, but its equivalent inertia remains unchanged during the disturbance and cannot simultaneously balance initial frequency suppression and subsequent recovery speed. Uncorrected Adaptive-Inertia MPC-VSG further enhances the inertial buffering effect during the initial disturbance stage, but its inertia regulation is mainly updated according to disturbance-related signals and does not account for the influence of stack temperature and oxygen excess ratio on the transient realizable power of the PEMFC. As a result, a certain mismatch remains between the support demand generated by the controller and the transient power response of the source side. By coordinating MPC compensation with operating-state-corrected inertia, the proposed control strategy improves the matching between frequency-support demand and the dynamic response capability of the PEMFC source, thereby achieving a higher frequency nadir, a lower ROCOF peak, and a faster power recovery process under the same operating conditions.
5. Conclusions
This study addresses the frequency support challenge of grid-forming PEMFC power generation systems, develops a dynamic model that incorporates the effects of stack temperature and oxygen excess ratio, and subsequently finalises the design and simulation-based validation of the control strategy. Consequently, the ensuing conclusions can be derived:
- (1)
- Variations in stack temperature and oxygen excess ratio directly affect the PEMFC’s transient output capability and further alter its frequency support performance during grid-forming operation. Simulation outcomes indicate that under varying operational conditions, the stack exhibits significant differences in both power ramp-up capability and recovery process. It is difficult for grid-forming control with fixed parameters alone to capture such differences, whereas incorporating stack temperature and oxygen excess ratio into the frequency support design improves consistency between the control parameters and the source-side dynamic capability.
- (2)
- Under the same load-disturbance condition, the proposed method yields a minimum system frequency of 49.892 Hz, a maximum frequency deviation of 0.108 Hz, and a maximum ROCOF of 0.29 Hz/s. Compared with Conventional PI-VSG, Fixed-Inertia MPC-VSG, and Uncorrected Adaptive-Inertia MPC-VSG, the maximum frequency deviation is reduced by 49.1%, 23.1%, and 4.6%, respectively, while the maximum ROCOF is reduced by 62.1%, 20.7%, and 10.3%, respectively. These results show that the proposed method can simultaneously reduce the frequency dip and the ROCOF peak during the initial disturbance stage, thereby improving the transient frequency-support performance of the system.
- (3)
- The proposed method enhances the inertial buffering effect during the initial disturbance stage through operating-state-corrected inertia regulation and improves the subsequent active-power response through MPC-based compensation. As a result, the PEMFC output power approaches the new steady state earlier, and the frequency recovery process is improved. The comparative results show that operating-state correction helps improve the consistency between inertia regulation and the transient realizable power of the PEMFC source, thereby improving the frequency-support performance under grid-forming operation.
Future work will further focus on the multiphysics coupled dynamics and engineering implementation issues in PEMFC-based grid-forming control. Based on the present model, greater attention will be given to stack temperature gradients, local oxygen-transport differences, and more complex thermo-fluid-electrochemical coupling processes, so as to improve the model’s ability to represent actual operating characteristics. Meanwhile, the dynamic influences of the air-supply system and power-conversion stage will be incorporated to analyze the system response under parameter variations and more complex disturbance conditions. On this basis, the engineering applicability and implementation performance of the proposed strategy will be further validated through hardware platforms, real-time simulation, and practical operating scenarios.
Author Contributions
Conceptualization, X.L., L.K. and Y.H.; Methodology, X.L. and Y.H.; Software, X.L.; Validation, X.L. and Y.R.; Investigation, X.L.; Resources, L.K.; Writing—original draft preparation, X.L.; Writing—review and editing, L.K., X.L. and Y.H.; Supervision, L.K. and Y.H. All authors have read and agreed to the published version of the manuscript.
Funding
This research was funded by the 2024 Provincial Budget Basic Construction Fund (Innovation Capacity Building) Project of the Jilin Provincial Development and Reform Commission, “Research on Coupled Operation Control Technology for Large-Scale Renewable Energy and Alkaline Water Electrolysis Hydrogen Production” (Project No. 2024C020-5).
Data Availability Statement
The original contributions presented in the study are included in the article, further inquiries can be directed at the corresponding author.
Acknowledgments
The authors of this article thank the editorial department of the publisher and the School of Northeast Electric Power University of Technology for their strong support.
Conflicts of Interest
The authors declare no conflicts of interest.
References
- He, C.; Geng, H.; Rajashekara, K.; Chandra, A. Analysis and control of frequency stability in low-inertia power systems: A review. IEEE J. Autom. Sin. 2024, 11, 2363–2383. [Google Scholar] [CrossRef] [Scilit]
- Yuan, T.J.; Zhang, J.F.; Teng, Y. Coordinated control strategy of renewable energy hydrogen production system based on virtual synchronous generator. Proc. CSEE 2025, 45, 163–175. [Google Scholar] [CrossRef]
- Ahmadimonfared, Z.; Eichner, S. Stability assessment of fully inverter-based power systems using grid-forming controls. Electronics 2025, 14, 4202–4230. [Google Scholar] [CrossRef] [Scilit]
- Wang, S.B.; Kong, L.G.; Cai, G.W.; Yan, G.H.; Han, Z.J.; Liu, C.; Wan, Y.M.; Yang, S.H.; Wang, X.C. Key application technologies of hydrogen energy storage in power systems: Status, challenges and prospects. Proc. CSEE 2023, 43, 6660–6681. [Google Scholar] [CrossRef]
- Pan, M.; Li, C.; Liao, J.; Lei, H. Design and modeling of PEM fuel cell based on different flow fields. Energy 2020, 207, 118331. [Google Scholar] [CrossRef] [Scilit]
- Barać, B.; Krpan, M.; Capuder, T. Modelling of PEM fuel cell for power system dynamic studies. IEEE Trans. Power Syst. 2023, 39, 3286–3298. [Google Scholar] [CrossRef] [Scilit]
- Sankar, K.; Saravanakumar, G.; Jana, A.K. Nonlinear multivariable control of an integrated PEM fuel cell system with a DC-DC boost converter. Chem. Eng. Res. Des. 2021, 167, 141–156. [Google Scholar] [CrossRef] [Scilit]
- Chen, H.; Liu, Y.; Deng, C.; Chen, J. Research on improving dynamic response ability of 30 kW real fuel cell system based on operating parameter optimization. Int. J. Hydrogen Energy 2023, 48, 1075–1089. [Google Scholar] [CrossRef] [Scilit]
- Trinh, D.H.; Nguyen, N.D.; Choi, Y.; Yu, S. A comprehensive dynamic system model of proton exchange membrane fuel cell for analysis of high current power generation. Renew. Energy 2025, 256, 124396. [Google Scholar] [CrossRef] [Scilit]
- Xiao, Y.G.; Wu, X.L.; Li, X. Control of cathode relative humidity and oxygen excess ratio of PEMFC system based on ADRC. Acta Energiae Solaris Sinica 2023, 44, 14027–14054. [Google Scholar] [CrossRef]
- Liu, Y.; Hu, Y.; Wang, Y.; Chau, T.K. A novel adaptive model predictive control for proton exchange membrane fuel cell in DC microgrids. IEEE Trans. Smart Grid 2022, 13, 1801–1812. [Google Scholar] [CrossRef] [Scilit]
- Shafiee Roudbari, E.; Beheshti, M.T.H.; Rakhtala, S.M. Voltage and frequency regulation in an islanded microgrid with PEM fuel cell based on a fuzzy logic voltage control and adaptive droop control. IET Power Electron. 2020, 13, 78–85. [Google Scholar] [CrossRef] [Scilit]
- Li, X.; Song, J.; Yang, S.; Li, Z. Primary frequency regulation technology of power grid and frequency regulation potential analysis of hydrogen fuel cell. In Proceedings of the IEEE 16th Conference on Industrial Electronics and Applications (ICIEA), Chengdu, China, 24–27 April 2021; pp. 357–362. [Google Scholar] [CrossRef] [Scilit]
- Wu, L.; Ren, Z.; Dong, Z.Y.; Li, C.; Wang, K. A primary frequency regulation control strategy for PEM fuel cell considering physical factors. CSEE J. Power Energy Syst. 2025, 1–12. [Google Scholar] [CrossRef]
- Cao, W.; Qin, H.C.; Lu, J.Z.; He, B.L.; Zhuang, K.Q. The positioning and application prospects of virtual synchronous machines in new power systems. Autom. Electr. Power Syst. 2023, 47, 190–207. [Google Scholar] [CrossRef]
- Chi, Y.N.; Jiang, B.W.; Hu, J.B.; Lin, W. grid-forming converters: Physical mechanism and characteristics. High Volt. Eng. 2024, 50, 590–604. [Google Scholar] [CrossRef]
- Shi, Q.; Du, C.; Sun, Y.; Cai, W. An improved adaptive inertia and damping combination control of virtual synchronous generator. IET Gener. Transm. Distrib. 2021, 15, 2540–2552. [Google Scholar] [CrossRef] [Scilit]
- Zheng, Y.; Xu, Y.; Yang, Y.; Hua, L. Application of adaptive virtual synchronous generator based on improved active power loop in photovoltaic storage systems. Front. Energy Res. 2025, 12, 1468629. [Google Scholar] [CrossRef] [Scilit]
- Zhao, S.Q.; Wang, H.; Tian, N.; Meng, J.H. Optimal virtual inertia optimization method for DC microgrids based on model predictive control. Trans. China Electrotech. Soc. 2023, 38, 3264–3276. [Google Scholar] [CrossRef]
- Long, B.; Liao, Y.; Chong, K.T.; Rodríguez, J. MPC-controlled virtual synchronous generator to enhance frequency and voltage dynamic performance in islanded microgrids. IEEE Trans. Smart Grid 2020, 12, 953–964. [Google Scholar] [CrossRef] [Scilit]
- Ni, Z.L.; Lin, Y.J.; Wang, Z.T.; Xu, Z.Y. Frequency regulation control of energy storage based on model predictive virtual synchronous generator. Power Syst. Prot. Control 2022, 50, 85–93. [Google Scholar] [CrossRef]
- Sun, J.H.; Wang, X.H.; Huang, J.G.; Cao, H. Dynamic stability control strategy of frequency and voltage for islanded microgrids based on MPC-VSG. Electric Power 2023, 56, 51–60. [Google Scholar] [CrossRef]
- Cavus, M.; Allahham, A.; Adhikari, K.; Giaouris, D. A hybrid method based on logic predictive controller for flexible hybrid microgrid with plug-and-play capabilities. Appl. Energy 2024, 359, 122752. [Google Scholar] [CrossRef] [Scilit]
- Zheng, Y.C.; Zhao, J.B.; Pan, C. Model predictive VSG frequency regulation control strategy for solid oxide fuel cells. High Voltage 2024, 50, 3715–3724. [Google Scholar] [CrossRef]
- Wang, R.; Wang, M.; Wang, K.; Wang, X. Optimization of frequency dynamic characteristics in microgrids: An improved MPC-VSG control. Int. J. Electr. Power Energy Syst. 2024, 156, 109783. [Google Scholar] [CrossRef] [Scilit]
- Guo, X.M.; Li, Y.G.; Zhou, Y.C. Frequency regulation strategy for virtual synchronous generator based on variable-weight adaptive model predictive control. Trans. China Electrotech. Soc. 2025, 40, 6956–6969. [Google Scholar] [CrossRef]
- Hu, D.; Wang, Y.; Li, J.; Yang, Q.; Wang, J. Investigation of optimal operating temperature for the PEMFC and its tracking control for energy saving in vehicle applications. Energy Convers Manag. 2021, 249, 114842. [Google Scholar] [CrossRef] [Scilit]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2026 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.