Instantaneous Overcurrent Protection for Active Distribution Networks Considering Photovoltaic Fault Current Contribution

,
,
,
,
,
,
and
1
State Grid Shandong Electric Power Company Liaocheng Power Supply Company, Liaocheng 252022, China
2
State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University, Beijing 102206, China
*
Author to whom correspondence should be addressed.
Electronics2026, 15(23), 5605;https://doi.org/10.3390/electronics15235605 
(registering DOI)

Abstract

Fault-current contributions from high-penetration distributed photovoltaic (PV) generation can extend the reach of instantaneous overcurrent protection. However, increasing the current pickup to maintain selectivity may conflict with relay setting limits, current transformer (CT) constraints, and near-end fault sensitivity requirements, leaving no feasible current-only setting. To address this problem, an instantaneous overcurrent protection setting method considering PV fault current contributions is proposed. Using the complementary variations in the protection reaches of the current and voltage elements with system operating conditions, a combined current–voltage protection reach model is established, and the settings of the two elements are coordinated to maximize the aggregate protection reach while satisfying selectivity and current capability constraints. A unified feasible setting region is further established to efficiently determine the optimal setting combination. The case study results show that, under operating conditions in which conventional instantaneous overcurrent protection cannot simultaneously satisfy selectivity and current capability constraints, the proposed method can still obtain implementable settings, ensure reliable blocking for external faults, and retain instantaneous protection for near-end faults.

Article Metrics

Citations

Article Access Statistics

Article metric data becomes available approximately 24 hours after publication online.