Abstract
Absorption cooling systems can operate using thermal energy supplied by renewable sources or recovered from low-grade waste heat, providing an alternative to vapor-compression cooling technologies. Intermittent operation is particularly suitable for applications with variable heat availability because it decouples the desorption and absorption processes, requiring desorption devices capable of stable operation. In this work, a membrane-based desorber operating with a LiBr + LiCl/H2O mixture (mass ratio 2:1, LiBr:LiCl) was experimentally evaluated for intermittent absorption cooling system applications. Two polytetrafluoroethylene (PTFE) membranes with pore sizes of 0.22 and 0.45 μm and two initial salt concentrations of 50.01 ± 0.06% and 44.96 ± 0.01% w/w were tested at solution and cooling-water temperatures of 90.2 ± 0.1 °C and 30.0 ± 0.1 °C, respectively. After 3 h of operation, cumulative distilled water production ranged from 5.36 ± 0.17 to 11.03 ± 0.10 kg/m2, with the highest production corresponding to the 0.45 μm membrane and an initial salt concentration of 44.96% w/w. Under the comparable operating conditions evaluated, LiBr/H2O produced 69.9% more cumulative distilled water than LiBr + LiCl/H2O, while LiBr + LiCl/H2O produced 22.4% more than LiCl/H2O. However, at an initial salt concentration of 44.96% w/w and using a 0.22 μm membrane, LiBr + LiCl/H2O produced only 1.8% less cumulative distilled water than LiBr/H2O at 49.59% w/w using a 0.45 μm membrane. When a 0.45 μm membrane was used for both solutions, LiBr + LiCl/H2O produced 15.4% more cumulative distilled water than LiBr/H2O. These results indicate the potential of LiBr + LiCl/H2O as a competitive alternative to conventional mixtures used in intermittent absorption cooling systems.